Monogram ZV750SPSS Installation Manual

INSTALLATION INSTRUCTIONS
36” Vent Hood
ZV750, ZV755
Hotte Aspirante 36 po Instructions d’installation
La section française commence à la page 19
Campana de ventilación de 36” Instrucciones de instalación
La sección en español empieza en la página 37
monogram.com
Safety Information
READ AND SAVE THESE INSTRUCTIONS
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT Save these instructions
for local inspector’s use.
IMPORTANT Observe all governing
codes and ordinances.
Note to Installer — Be sure to leave these
instructions with the Consumer.
Note to Consumer — Keep these instructions with
your Owner’s Manual for future reference.
Skill Level — Installation of this appliance requires
basic mechanical and electrical skills.
Completion Time — 1 to 3 hours.
Proper installation is the responsibility of the
installer. Product failure due to improper installation is not covered under the warranty. See Owner’s Manual for warranty information.
For Monogram local service in your area, call
1.800.444.1845. For Monogram service in Canada, call
1.800.561.3344. For Monogram Parts and Accessories, call
1.800.626.2002.
CAUTION
vent hoods and to reduce the risk of personal injury or damage to the product, TWO PEOPLE ARE
REQUIRED FOR PROPER INSTALLATION.
WARNING
shock, do not use this range hood with any external solid-state speed control device. Any such alteration from original factory wiring could result in damage to the unit and/or create an electrical safety hazard.
TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK.
Due to the weight and size of these
To reduce the risk of fire or electrical
B. Before servicing or cleaning the unit, switch the
power off at the service panel and lock the service disconnecting means to prevent the power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device,such as a tag, to the service panel.
CAUTION
ONLY. DO NOT USE TO EXHAUST HAZARDOUS MATERIALS, EXPLOSIVE MATERIALS OR VAPORS.
WARNING
ELECTRICAL SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire­rated construction.
Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back-drafting. Follow the heating equipment manufacturer’s guidelines and safety standards, such as those published by the National Fire Protection Association (NFPA), the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) and the local code authorities. When applicable, install any makeup (replacement) air system in accordance with local building code requirements. Visit GEAppliances.com for available makeup air solutions.
When cutting or drilling into walls or ceilings, do not damage electrical wiring and other hidden utilities.
Ducted systems must always be vented to the outdoors.
Local codes vary. Installation of electrical
connections and grounding must comply with applicable codes. In the absence of local codes, the vent should be installed in accordance with National Electrical Code ANSI/NFPA 70-1990 or latest edition.
FOR GENERAL VENTILATING USE
TO REDUCE THE RISK OF FIRE,
WARNING
ELECTRICAL SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Use this unit only in the manner intended by the
manufacturer. If you have any questions, contact the manufacturer.
TO REDUCE THE RISK OF FIRE,
CAUTION
exhaust air, be sure to duct air outside—do not vent exhaust air into spaces within walls or ceilings or into attics, crawl spaces or garages.
To reduce risk of fire and to properly
2 31-10724-7
Design Information
to Ceiling
CONTENTS
Design Information
Models Available ........................................................... 3
Product Dimensions ...................................................... 3
Advance Planning
Ductwork Planning ....................................................... 4
Wall Framing for Adequate Support ............................. 4
Advance Planning ........................................................ 4
Installation Preparation
Duct Fittings .................................................................. 5
Power Supply ................................................................ 6
Tools and Materials Required ....................................... 6
Remove the Packaging ................................................ 7
Check Installation Hardware ........................................ 7
Determine Installation Height ........................................ 8
Installation Instructions
Installation – Vented to the Outside ........................ 9–13
Step 1, Install Framing for Hood Support...................... 9
Step 2, Install Mounting Brackets................................ 10
Step 3, Install the Hood ............................................... 10
Step 4, Install Duct Bracket ......................................... 11
Step 5, Connect Ductwork .......................................... 12
Step 6, Connect Electrical ........................................... 12
Step 7, Install Duct Cover and Utensil Rods ............... 13
Step 8, Install Filters .................................................... 13
Step 9, Finalize Installation ......................................... 13
Installation – Recirculating .................................... 14–18
Step 1, Install Framing for Hood Support.................... 14
Step 2, Install Mounting Brackets................................ 15
Step 3, Install the Hood ............................................... 15
Step 4, Assemble Deflector and Connector ................ 16
Step 5, Size Duct Piece .............................................. 16
Step 6, Install Air Deflector Assembly ......................... 16
Step 7, Connect Electrical ........................................... 17
Step 8, Install Duct Cover and Utensil Rods ............... 17
Step 9, Install Filters .................................................... 18
Step 10, Finalize Installation ....................................... 18
MODELS AVAILABLE
Model ZV750 Model ZV755
These hoods may be installed to vent to the outdoors, or they may be installed for recirculating operation. All necessary parts for recirculating operation are supplied with the hood. No kits required.
• These vent hoods can be installed over any 30″ or 36″ Monogram electric or gas cooktop except Monogram
Professional cooktops or ranges larger than 30″.
PRODUCT DIMENSIONS AND CLEARANCES
The vent hood must be
installed 24″ minimum, and 30″ maximum above
the cooking surface. NOTE: Installation
height should be measured from the cooking surface to the lowest part of the hood.
24″ Minimum
30″ Maximum
36″ Minimum
• Reversible duct covers accommodate recirculating operation.
• The telescopic duct covers conceal the ductwork running from the top of the hood to the ceiling.
• The supplied duct cover is sized to reach ceiling heights up to 9’ or more, depending on the installation. See the table on page 8.
*Height
8-1/4"
35-3/8 (excluding utensil rods) 36-1/2 (including utensil rods)
27-1/2”
ZX7510SPSS Duct Cover Accessory
This accessory is available for installations with ceiling heights above 9’ to 10’ and higher. See the table on page 8.
The duct cover accessory must be on-site with the hood at the time of installation.
31-10724-7 3
Advance Planning
DUCTWORK PLANNING
This hood is designed to be vented vertically through the ceiling. Use locally supplied elbows to vent horizontally through the rear wall.
Determine the exact location of the vent hood.
Plan the route for venting exhaust to the outdoors.
Use the shortest and straightest duct route possible.
For satisfactory performance, duct run should
not exceed 10′ equivalent length for any duct
configurations.
Refer to “Duct Fittings” chart to compute the maximum permissible length for duct runs to the outdoors.
Use rigid metal ductwork only.
This vent hood must use a 6” round duct. The 6” round
duct can transition to 3-1/4” x 10” or 3-1/4” x 12”.
Install the house duct to run horizontally between ceiling joists or straight up through the roof.
Install a wall or roof cap with damper at the exterior opening. Order the wall or roof cap and any transition and length of duct needed in advance.
When applicable, install any makeup (replacement) air system in accordance with local building code requirements. Visit GEAppliances.com for available makeup air solutions.
WALL FRAMING FOR ADEQUATE SUPPORT
This vent hood is heavy. Adequate structural support must be provided. The hood must be secured to vertical studs in the wall. See page 9 or 14.
We strongly recommend that the vent hood with duct cover be on site before final framing and wall finishing. This will also help to accurately locate the ductwork and electrical service.
Installation will be easier if the vent hood is installed before the cooktop and countertop are installed.
ADVANCE PLANNING
A duct cover accessory may be required for your hood installation depending on ceiling height.
WARNING
USE ONLY RIGID METAL DUCTWORK.
TO REDUCE THE RISK OF FIRE,
4 31-10724-7
Installation Preparation
DUCT FITTINGS
This Hood Must Use an
6 Round Duct. It Can
Transition to 3-1/4 x 10
or 3-1/4 x 12 Duct.
Use this chart to compute maximum permissible lengths for duct runs to outdoors.
NOTE: Do not exceed maximum permissible equivalent lengths!
Maximum duct length: 100 foot for range hoods.
Flexible ducting:
If flexible metal ducting is used, all the equivalent feet values in the table should be doubled. The flexible metal duct should be straight and smooth and extended as much as possible.
DO NOT use flexible plastic ducting.
NOTE: Any home ventilation system, such as a ventilation hood, may interrupt the proper flow of combustion air and exhaust required by fireplaces, gas furnaces, gas water heaters and other naturally vented systems. To minimize the chance of interruption of such naturally vented systems, follow the heating equipment manufacturer’s guidelines and safety standards such as those published by NFPA and ASHRAE. When applicable, install any makeup (replacement) air system in accordance with local building code requirements. Visit GEAppliances.com for available makeup air solutions.
Total Equivalent Quantity Equivalent Duct Piece Dimensions Length* Used Length
Round, 1 ft. (per straight foot length)
3-1/4″ x 10″ 1 ft. (per straight foot length)
90° elbow 12 ft.
45° elbow 7 ft.
3-1/4″ x 10″ 14 ft. 3-1/4″ x 12″ 10 ft.
90° elbow
3-1/4″ x 10″ 8 ft. 3-1/4″ x 12″ 6 ft.
45° elbow
3-1/4″ x 10″ 33 ft. 3-1/4″ x 12″ 24 ft.
90° flat elbow
6″ round to 2 ft. rectangular
Rectangular to 8″ 2 ft. round
3-1/4″ x 10″ 4 ft. 3-1/4″ x 12″ 4 ft. 6″ round to rectangular
transition 90° elbow
3-1/4″ x 10″ 4 ft. 3-1/4″ x 12″ 4 ft. Rectangular to 6″ round
transition 90° elbow
Round wall cap 24 ft. with damper
3-1/4″ x 10″ 24 ft. 3-1/4″ x 12″ 18 ft.
Rectangular wall cap with damper
Round roof cap 33 ft.
* Actual length of straight duct plus duct fitting
equivalent. Equivalent length of duct pieces are based on actual tests conducted by GE Appliances Evaluation Engineering and reflect requirements for good venting performance with any ventilation hood.
31-10724-7 5
Total Duct Run
Installation Preparation
POWER SUPPLY
IMPORTANT – (Please read carefully)
WARNING
APPLIANCE MUST BE PROPERLY GROUNDED. Remove house fuse or open circuit breaker before
beginning installation. Do not use an extension cord or adapter plug with
this appliance. Follow National Electrical Code or prevailing local codes and ordinances.
Electrical supply
This vent hood must be supplied with 120V, 60Hz, and connected to an individual, properly grounded branch circuit, and protected by a 15- or 20-amp circuit breaker or time-delay fuse.
Wiring must be 2-wire with ground.
If the electrical supply does not meet the above
requirements, call a licensed electrician before proceeding.
Route house wiring as close to the installation location as possible. Wiring can enter from the ceiling or rear wall. Route additional length from the ceiling or wall to reach the junction box.
Connect the wiring to the house wiring in accordance with local codes.
Grounding instructions
The grounding conductor must be connected to a ground metal, permanent wiring system, or an equipment-grounding terminal or lead on the hood.
FOR PERSONAL SAFETY, THIS
TOOLS AND MATERIALS REQUIRED (Not Supplied)
Pencil and tape
measure
Spirit level
Phillips screwdriver
Electric drill with 1/8″ bits,
#2 Phillips and flat head
Safety glasses
Utility Knife
Masking tape
Wire cutter/stripper
Gloves
Hammer
Flashlight
Metal snips
Pliers
WARNING
equipment-grounding conductor can result in a risk
The improper connection of the
Stepladder
of electric shock. Check with a qualified electrician or service representative if you are in doubt whether the appliance is properly grounded.
UL-listed wire nuts
Aluminized
duct tape
Strain relief for
junction box
Saber saw or Key Hole saw
6″ round metal duct, length
to suit installation
120V 60Hz. 15- or 20-Amp,
2-wire with ground, properly grounded
branch circuit
6 31-10724-7
Installation Preparation
REMOVE THE PACKAGING
CAUTION
edges. The vent hood is shipped secured to a shipping board
with 4 screws.
Remove the duct cover, parts box and foam packaging.
Lift the hood out of the box.
Remove and properly discard the plastic wrapping.
Remove metal grease filters and side bar packaging.
Wear gloves to protect against sharp
To remove the shipping board, locate and remove 2 screws at the top of the assembly and 2 screws inside the hood behind the filter guides on the left and right sides. Discard the shipping board.
Junction box
Mounting screw
Knockout
Mounting screw
Shipping board
Remove junction box cover.
Remove knockout from junction box.
Install strain relief onto junction box.
Mounting screw
Shipping board
CHECK INSTALLATION HARDWARE
Locate the hardware accessory box packed with the hood and check contents.
2 Mounting brackets
10 wood
screws
10 metal wall
fasteners
2 Large
flat washers
• Drill 1/8" Pilot Holes For Mounting Brackets.
• Drill 1/8" Pilot Holes.
Align edge 25-1/2" above Cooking Surface.
2-5/32"
5-7/8"
13-9/16"
17-5/16"
C L
• Drill 1/8" Pilot Holes.
3-15/16"
3 Stainless
steel grease
filters
Wall-mount template
2 Utensil rods with 4 machine screws
Additional Parts for Recirculation Operation
Duct cover bracket (not required
for recirculating operation)
NOTE: Additional tools, materials and hardware are required to construct your wall framing support.
31-10724-7 7
2 Phillips-head
duct cover
screws
Decorative
duct covers
Air deflector with upper
duct connector
3 charcoal filters
Installation Preparation
DETERMINE INSTALLATION HEIGHT
Telescopic duct covers are provided to conceal the ductwork running to the ceiling.
This hood can be installed for vented or recirculating operation. All necessary parts are shipped with the hood.
24” Min.
30” Max.
36" Min.
NOTE: Installation height should be measured from the cooking surface to the bottom of the hood.
The vent hood must be installed 24″ min. and 30″ max.
above the cooking surface. The hood installation height, from the cooking surface to the bottom of the hood, depends upon ceiling height and duct cover limitations.
DUCT COVER DIMENSIONS
9-1/4″
11-7/8″
ZX7510SPSS Duct Cover Accessory
This accessory is available for installation with ceiling heights above 9 feet to 10 feet and higher. This
accessory consists of one 31-1/2″ lower duct cover.
ZV750/ZV755 Installation Heights
Upper (Inner) Duct Cover (B) 24.25″ Lower (Outer) Duct Cover (A) 18.5″ Accessory Lower (Outer) Duct Cover (A) 31.5″ Actual *VENTED *RECIRCULATING
Ceiling Installation Installation Height Height Height
7′ 11″ 24” to 28” 24” to 28” 8′ 0” 24” to 29” 24” to 29” 8′ 1” 24” to 30” 24” to 30” 8′ 2” 24” to 30” 24” to 30” 8′ 3” 24” to 30” 24” to 30” 8′ 4” 24” to 30” 24” to 30” 8′ 5” 24” to 30” 24” to 30” 8′ 6” 24” to 30” 24” to 30” 8′ 7” 24″ to 30” 24” to 30” 8′ 8” 24” to 30” 24” to 30” 8′ 9” 25” to 30” 24” to 30” 8′ 10” 26” to 30” 24” to 30” 8′ 11” 27” to 30” 24” to 30” 9′ 0” 28” to 30” 2” to 30” 9′ 1” 29” to 30” 25” to 30” 9′ 2” 30” 26” to 30” 9′ 3” 27” to 30” 9′ 4” 28” to 30” 9′ 5” 29” to 30” 9′ 6” 30”
9′ 0″ 24″ to 30″ 24″ to 28″ 9′ 1″ 24″ to 30″ 24″ to 29″ 9′ 2″ 24″ to 30″ 24″ to 30″ 9′ 3″ 24″ to 30″ 24″ to 30″ 9′ 4″ 24″ to 30″ 24″ to 30″ 9′ 5″ 24″ to 30″ 24″ to 30″ 9′ 6″ 24″ to 30″ 24″ to 30″ 9′ 7″ 24″ to 30″ 24″ to 30″ 9′ 8″ 24″ to 30″ 24″ to 30″ 9′ 9″ 24″ to 30″ 24″ to 30″ 9′ 10″ 25″ to 30″ 24″ to 30″ 9′ 11″ 26″ to 30″ 24″ to 30″ 10′ 0″ 27″ to 30″ 24″ to 30″ 10′ 1″ 28″ to 30″ 24″ to 30″ 10′ 2″ 29″ to 30″ 24″ to 30″ 10′ 3″ 30″ 25″ to 30″ 10′ 4″ 26″ to 30″ 10′ 5″ 27″ to 30″ 10′ 6″ 28″ to 30″ 10′ 7″ 29″ to 30″ 10′ 8″ 30″
*Based on 36 countertop height.
ZX7510SPSS (Need Accessory Lower Duct Cover 31.5″) ACCESSORY ZX90010 SUPPLIED
8 31-10724-7
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
DUCTWORK, WIRING LOCATIONS
Determine the exact location of the vent hood.
Locate the template packed with the literature.
–Measure 36″ from the floor to the top of the
cooking surface. Add hood installation height determined on page 8. Mark that location.
–Use a level to draw a straight pencil line on the
wall.
–Tape the template in position along the penciled line. CHECK TO BE SURE THE TEMPLATE IS LEVEL.
3-3/4″ c enterline to wall
• Drill 1/8" Pilot Holes For Mounting Brackets.
FOR CEILING VENT
DUCTING
FOR WALL
VENT DUCT
Centerline 6″ min. above
bracket location
2-5/32"
5-7/8"
13-9/16"
1
INSTALL FRAMING FOR HOOD
SUPPORT
IMPORTANT: The vent hood must be secured to rear support framing or a wall stud. Framing must be capable of supporting 100 lbs.
6-1/2″ min. opening for ductwork
View from
rear cleats
1″ x 12″ min.
mounting
support
Centerline of
installation
space
17-5/16"
C L
• Drill 1/8" Pilot Holes.
Align edge 25-1/2" above Cooking Surface.
• Drill 1/8" Pilot Holes.
3-15/16"
Ceiling ducting:
If ductwork will vent straight up to the ceiling:
Use a level to draw a line straight up, from the centerline on the template to the ceiling.
■ Measure 3-3/4″ from the back wall to the centerline of an 6-1/2″ hole on the ceiling.
NOTE: If drywall is not present, add drywall thickness
to the 3-3/4″ dimension.
Wall Ducting:
If ductwork will vent to the rear:
Use a level to draw a line straight up from the centerline on the template.
■ Measure at least 6″ above the bracket location shown on the template to the centerline of a 6-1/2″-dia. duct
hole. (Hole may be elongated for duct elbow.)
HOUSE WIRING LOCATION:
The junction box is located on the top left side of the hood.
Wiring can enter from the back wall or ceiling above the top bracket location. Route additional wiring length to reach the junction box.
NOTE: 2 horizontal supports
will be needed if there is a
stud located between the
horizontal screw locations.
If drywall is present, mark the screw hole locations for the top mounting brackets. Remove the template.
Cut away enough drywall to expose 2 vertical studs at the bracket location indicated on the template.
■ Install a horizontal support at least 1″ x 12″ between
two wall studs at the mounting screw location. The horizontal support must be flush with the room side of the studs. Use cleats behind both sides of
the support to secure to wall studs.
IMPORTANT: Reinstall drywall for an even mounting surface.
31-10724-7 9
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
2
INSTALL MOUNTING BRACKETS
The vent hood must be secured to rear support framing or a wall stud.
With the template taped in place, use a punch to mark all mounting screw locations.
■ Drill 1/8″ pilot holes at the 6 punched locations.
Remove the template.
■ Enlarge holes that did not enter studs to 3/8″ and tap
anchors for wall fasteners into the holes.
– Drive screws into the fasteners to allow anchors to
expand against the wall material. Remove the screws for final installation.
Secure the mounting brackets to the wall studs with wood screws provided.
3
INSTALL THE HOOD
Place the hood on the brackets and slide left to right to align with rectangular slots at the top.
Adjust the installation height by tightening or loosening the screws “A” at the bottom of the brackets.
Align the hood lower mounting holes with pilot holes in the wall.
Using two large washers (supplied), install wood screws or wall-fastener screws, loosely, into lower mounting holes. Do not tighten.
Level the hood by tightening or loosening the screws “A” located on the bottom mounting brackets.
Tighten the lower mounting screws.
Tighten screws “B” located at the top of the mounting
bracket against the hood to adjust position. Do not overtighten screws.
Screws “B”
Screws “A”
NOTE: Screws “A” and “B” are preassembled onto the brackets. Do not remove these screws.
Screws “B” to adjust
hood against wall
Level and height
adjustment
screws “A”
Lower mounting
screws
10 31-10724-7
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
4
INSTALL DUCT BRACKET
VENTING TO THE REAR (HORIZONTAL EXHAUST) OR STRAIGHT UP TOP (VERTICAL EXHAUST)
Temporarily install the 2 small screws into the sides of the duct bracket. Remove the screws. This will ensure ease of final installation.
Position the upper duct bracket against the wall and ceiling, aligned with CL pencil mark and CL on the bracket.
Mark the 4 screw locations of the bracket.
Remove the bracket.
■ Drill 1/8″ pilot holes in marked bracket location.
■ If pilot holes do not enter studs, enlarge the holes 3/8″
and install wall-fastener anchors. Drive screws into the fasteners to allow anchors to expand against the wall material. Remove the screws.
Secure the bracket to the ceiling and wall with wood screws and/or wall-fastener screws.
Top or
vertical
exhaust
Duct bracket
Rear or
horizontal
exhaust
31-10724-7 11
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
5
CONNECT DUCTWORK
Remove shipping tape from the damper.
Install ductwork, making connections in the direction
of airflow as illustrated.
Push duct over the exhaust outlet and damper.
Airflow
Duct tape
over seam
and screw
CAUTION
exhaust outlet connection. Doing so will prevent proper damper operation. Seal connection with tape only.
Secure joints in ductwork with sheet metal screws.
Wrap all duct joints and the flange connections with
aluminized duct tape for an airtight seal.
Do not use sheet metal screws at the
Screw
6
CONNECT ELECTRICAL
Verify that power is turned off at the source.
WARNING
a ground wire, a ground must be provided by the installer. When house wiring is aluminum, be sure to use U.L.-approved antioxidant compound and aluminum-to-copper connectors.
Remove the junction box cover and the selected knockout.
Knockout
Junction
box cover
Secure the house wiring to the junction box with a strain relief (not provided).
Connect the white lead to the branch circuit white lead.
Connect the black lead to the branch circuit black lead.
Connect the green/yellow lead to the branch circuit green lead or bare ground lead.
Secure all the connections with wire nuts on each electrical connector.
Push the wires into the junction box and replace the cover. Be sure the wires are not pinched.
Secure the junction box cover with the 2 original screws.
If house wiring is not 2-wire with
12 31-10724-7
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
7
INSTALL DUCT COVER AND
UTENSIL RODS
Assemble the duct covers as shown.
For this vented installation, place upper duct piece inside the lower duct piece. The inner duct cover venting holes should be positioned toward the bottom end and should not be visible.
Insert the assembled duct covers into the impression on the top of the hood.
Extend the inner duct cover upwards to meet the ceiling and bracket. (The vent holes should not be visible in this installation.)
Secure the duct cover to the bracket with the 2 small duct cover screws provided.
Install the side utensil rods as shown with screws provided.
Mounting Screws
Bottom Notches
Install optional accessory ZX7510SPSS
(if needed to reach taller ceiling heights)
Separate the supplied duct cover into pieces. Discard the lower (outer) section.
Slide the new ZX7510SPSS duct cover onto the original upper section. Be sure that the longer section is outside the shorter original section. The notches will be at the bottom and the screw holes at the top as illustrated.
Secure the duct cover to the bracket with the 2 small duct cover screws provided.
8
INSTALL FILTERS
Lower charcoal
filter channel
Remove protective film on filters.
Tip the filter into the lower channel at the rear of the
opening, push back, lift and pull the knob forward until the filter rests on the channel.
9
FINALIZE INSTALLATION
Remove protective film covering the control panel on the front face of the hood and any remaining packaging materials.
Make sure the filters are seated properly when installed and the filter light is not on.
Lower
filter slots
Install all three metal grease filters.
Turn power on. If the filter light on the control panel
glows, adjust the right-side filter in the channel to engage the switch arm.
Be sure fan and lights operate correctly. Refer to the Owner’s Manual for operating instructions and Problem Solver.
31-10724-7 13
Installation Instructions
INSTALLATION – RECIRCULATING
DUCTWORK, WIRING LOCATIONS
Determine the exact location of the vent hood.
Locate the template packed with the literature.
■ Measure 36″ from the floor to the top of the cooking
surface. Add hood installation height determined on page 8. Mark that location.
Tape the template in position along the penciled line. CHECK TO BE SURE THE TEMPLATE IS LEVEL.
Use a level to draw a line straight up, from the centerline on the template to the ceiling.
• Drill 1/8" Pilot Holes For Mounting Brackets.
• Drill 1/8" Pilot Holes.
Align edge 25-1/2" above Cooking Surface.
2-5/32"
5-7/8"
13-9/16"
17-5/16"
C L
• Drill 1/8" Pilot Holes.
3-15/16"
1
INSTALL FRAMING FOR HOOD
SUPPORT
IMPORTANT: The vent hood must be secured to rear support framing or a wall stud. Framing must be capable of supporting 100 lbs.
View from
rear cleats
1″ x 12″ min.
mounting
support
Centerline of
installation
space
HOUSE WIRING LOCATION:
The junction box is located on the top left side of the hood.
Wiring can enter from the back wall or ceiling above the top bracket location. Route additional wiring length to reach the junction box.
NOTE: 2 horizontal supports
will be needed if there is a
stud located between the
horizontal screw locations.
If drywall is present, mark the screw hole locations for the top mounting brackets. Remove the template.
Cut away enough drywall to expose 2 vertical studs at the bracket location indicated on the template.
■ Install a horizontal support at least 1″ x 12″ between
two wall studs at the mounting screw location. The horizontal support must be flush with the room side of the studs. Use cleats behind both sides of
the support to secure to wall studs.
IMPORTANT: Reinstall drywall for an even mounting surface.
14 31-10724-7
Installation Instructions
INSTALLATION – RECIRCULATING
2
INSTALL MOUNTING BRACKETS
The vent hood must be secured to rear support framing or a wall stud.
With the template taped in place, use a punch to mark all mounting screw locations.
■ Drill 1/8″ pilot holes at the 6 punched locations.
Remove the template.
■ Enlarge holes that did not enter studs to 3/8″ and tap
anchors for wall fasteners into the holes.
– Drive screws into the fasteners to allow anchors to
expand against the wall material. Remove the screws for final installation.
Secure the mounting brackets to the wall studs with wood screws provided.
3
INSTALL THE HOOD
Place the hood on the brackets and slide left to right to align with rectangular slots at the top.
Adjust the installation height by tightening or loosening the screws “A” at the bottom of the brackets.
Align the hood lower mounting holes with pilot holes in the wall.
Using two large washers (supplied), install wood screws or wall-fastener screws, loosely, into lower mounting holes. Do not tighten.
Level the hood by tightening or loosening the screws “A” located on the bottom mounting brackets.
Tighten the lower mounting screws.
Tighten screws “B” located at the top of the mounting
bracket against the hood to adjust position. Do not overtighten screws.
Screws “B”
Screws “A”
NOTE: Screws “A” and “B” are preassembled onto the brackets. Do not remove these screws.
Screws “B” to adjust
hood against wall
Level and height
adjustment
screws “A”
Lower mounting
screws
31-10724-7 15
Installation Instructions
INSTALLATION – RECIRCULATING
4
ASSEMBLE DEFLECTOR
AND CONNECTOR
A. The duct connector is shipped
inside the deflector.
B. Snap the plastic connector out
of the deflector and remove.
C. Turn over the plastic
connector. From the bottom, snap the connector over the opening as shown.
B
Remove plastic connector
5
SIZE DUCT PIECE
Hold air deflector with duct connector against the ceiling. Align window on the back of the deflector with the marked centerline.
Measure from the bottom of the deflector to the top of the hood as shown. Reduce this dimension
by 1″ to facilitate installation.
The duct will cover/overlap the duct connector and the exhaust outlet.
Cut the duct piece to size and slip onto the bottom of the duct connector.
Use duct tape to secure the duct piece to the connector.
Temporarily install the 2 small duct cover screws into the sides of the deflector. Remove the screws. This will ensure ease of final installation.
Centerline
A
C
Snap into place
Duct
length
Measure
Screws
Air deflector assembly
length
6
INSTALL AIR DEFLECTOR
ASSEMBLY
Place the assembly over the hood outlet.
Hold the assembly against the ceiling. The penciled centerline should show through the slot on the deflector. Mark the two screw holes on the back of the assembly.
Remove the assembly and drill
1/8″ pilot holes into
the wall studs.
Enlarge holes that did not enter studs to 3/8″ and tap plastic or metal
anchors into the holes, flush with the wall.
Mount the assembly onto the hood outlet, push up against the ceiling and install the screws provided.
Use duct tape to seal the connection.
CAUTION
the hood duct flange connection. Doing so will prevent proper damper operation. Seal connections with tape only.
Do not use sheet metal screws at
16 31-10724-7
Installation Instructions
INSTALLATION – RECIRCULATING
7
CONNECT ELECTRICAL
Verify that power is turned off at the source.
WARNING
a ground wire, a ground must be provided by the installer. When house wiring is aluminum, be sure to use U.L. approved antioxidant compound and aluminum-to-copper connectors.
Remove the junction box cover and the selected knockout.
Knockout
Junction
box cover
Secure the house wiring to the junction box with a strain relief.
Connect the white lead to the branch circuit white lead.
Connect the black lead to the branch circuit black lead.
Connect the green/yellow lead to the branch circuit green lead or bare ground lead.
Secure all the connections with wire nuts on each electrical connector.
Push the wires into the junction box and replace the cover. Be sure the wires are not pinched.
Secure the junction box cover with the 2 original screws.
If house wiring is not 2-wire with
8
INSTALL DUCT COVERS AND
UTENSIL RODS
Assemble the duct covers as shown.
Mounting screw holes
For this recirculating installation, the vent holes must be positioned at the top. The vent holes must be
fully exposed to allow airflow into the room.
Insert the duct cover assembly into the impressions on the top of the hood.
Extend the inner duct cover upwards to meet the ceiling and support frame.
Install optional accessory ZX7510SPSS
(if needed to reach taller ceiling heights)
Separate the supplied duct cover. Discard the lower (outer) section.
Slide the new ZX7510SPSS duct cover into the original upper section. Be sure that the vent holes are positioned toward the top.
Insert the duct cover assembly into the impressions on the top of the hood.
Secure the duct cover at the top to the air deflector with 2 screws provided.
Install the side utensil rods as shown with screws provided.
31-10724-7 17
Loading...
+ 39 hidden pages