Campana de ventilación de 36”
Instrucciones de instalación
La sección en español empieza en la página 37
monogram.com
Safety Information
READ AND SAVE THESE INSTRUCTIONS
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT — Save these instructions
■
for local inspector’s use.
■
IMPORTANT — Observe all governing
codes and ordinances.
■Note to Installer — Be sure to leave these
instructions with the Consumer.
■Note to Consumer — Keep these instructions with
your Owner’s Manual for future reference.
■Skill Level — Installation of this appliance requires
basic mechanical and electrical skills.
■ Completion Time — 1 to 3 hours.
■ Proper installation is the responsibility of the
installer. Product failure due to improper installation
is not covered under the warranty. See Owner’s
Manual for warranty information.
For Monogram local service in your area, call
1.800.444.1845.
For Monogram service in Canada, call
1.800.561.3344.
For Monogram Parts and Accessories, call
1.800.626.2002.
CAUTION
vent hoods and to reduce the risk of personal injury
or damage to the product, TWO PEOPLE ARE
REQUIRED FOR PROPER INSTALLATION.
WARNING
shock, do not use this range hood with any external
solid-state speed control device. Any such alteration
from original factory wiring could result in damage to
the unit and/or create an electrical safety hazard.
TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCTWORK.
Due to the weight and size of these
To reduce the risk of fire or electrical
B. Before servicing or cleaning the unit, switch the
power off at the service panel and lock the service
disconnecting means to prevent the power from
being switched on accidentally. When the service
disconnecting means cannot be locked, securely
fasten a prominent warning device,such as a tag,
to the service panel.
CAUTION
ONLY. DO NOT USE TO EXHAUST HAZARDOUS
MATERIALS, EXPLOSIVE MATERIALS OR VAPORS.
WARNING
ELECTRICAL SHOCK OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
■ Installation work and electrical wiring must be
done by qualified person(s) in accordance with
all applicable codes and standards, including firerated construction.
■
Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of
fuel burning equipment to prevent back-drafting.
Follow the heating equipment manufacturer’s
guidelines and safety standards, such as
those published by the National Fire Protection
Association (NFPA), the American Society for
Heating, Refrigeration and Air Conditioning
Engineers (ASHRAE) and the local code authorities.
When applicable, install any makeup (replacement)
air system in accordance with local building code
requirements. Visit GEAppliances.com for available
makeup air solutions.
■ When cutting or drilling into walls or ceilings, do not
damage electrical wiring and other hidden utilities.
■ Ducted systems must always be vented to the
outdoors.
■
Local codes vary. Installation of electrical
connections and grounding must comply with
applicable codes. In the absence of local codes, the
vent should be installed in accordance with National
Electrical Code ANSI/NFPA 70-1990 or latest edition.
FOR GENERAL VENTILATING USE
TO REDUCE THE RISK OF FIRE,
WARNING
ELECTRICAL SHOCK OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
A. Use this unit only in the manner intended by the
manufacturer. If you have any questions, contact
the manufacturer.
TO REDUCE THE RISK OF FIRE,
CAUTION
exhaust air, be sure to duct air outside—do not vent
exhaust air into spaces within walls or ceilings or into
attics, crawl spaces or garages.
To reduce risk of fire and to properly
231-10724-7
Design Information
to Ceiling
CONTENTS
Design Information
Models Available ........................................................... 3
These hoods may be installed to vent to the outdoors,
or they may be installed for recirculating operation. All
necessary parts for recirculating operation are supplied
with the hood. No kits required.
• These vent hoods can be installed over any 30″ or 36″
Monogram electric or gas cooktop except Monogram
Professional cooktops or ranges larger than 30″.
PRODUCT DIMENSIONS AND
CLEARANCES
The vent hood must be
installed 24″ minimum,
and 30″ maximum above
the cooking surface.
NOTE: Installation
height should be
measured from the
cooking surface to the
lowest part of the hood.
This accessory is available for installations with ceiling
heights above 9’ to 10’ and higher. See the table on page 8.
The duct cover accessory must be on-site with the hood
at the time of installation.
31-10724-73
Advance Planning
DUCTWORK PLANNING
■ This hood is designed to be vented vertically
through the ceiling. Use locally supplied elbows to
vent horizontally through the rear wall.
■ Determine the exact location of the vent hood.
■ Plan the route for venting exhaust to the outdoors.
■ Use the shortest and straightest duct route possible.
For satisfactory performance, duct run should
not exceed 10′ equivalent length for any duct
configurations.
■ Refer to “Duct Fittings” chart to compute the maximum
permissible length for duct runs to the outdoors.
■ Use rigid metal ductwork only.
■ This vent hood must use a 6” round duct. The 6” round
duct can transition to 3-1/4” x 10” or 3-1/4” x 12”.
■ Install the house duct to run horizontally between
ceiling joists or straight up through the roof.
■ Install a wall or roof cap with damper at the exterior
opening. Order the wall or roof cap and any
transition and length of duct needed in advance.
■ When applicable, install any makeup (replacement)
air system in accordance with local building code
requirements. Visit GEAppliances.com for available
makeup air solutions.
WALL FRAMING FOR ADEQUATE
SUPPORT
■ This vent hood is heavy. Adequate structural support
must be provided. The hood must be secured to
vertical studs in the wall. See page 9 or 14.
■ We strongly recommend that the vent hood with
duct cover be on site before final framing and wall
finishing. This will also help to accurately locate the
ductwork and electrical service.
■ Installation will be easier if the vent hood is installed
before the cooktop and countertop are installed.
ADVANCE PLANNING
A duct cover accessory may be required for your hood
installation depending on ceiling height.
WARNING
USE ONLY RIGID METAL DUCTWORK.
TO REDUCE THE RISK OF FIRE,
431-10724-7
Installation Preparation
DUCT FITTINGS
This Hood Must Use an
6″ Round Duct. It Can
Transition to 3-1/4″ x 10″
or 3-1/4″ x 12″ Duct.
Use this chart to compute
maximum permissible lengths for
duct runs to outdoors.
NOTE: Do not exceed maximum
permissible equivalent lengths!
Maximum duct length:
100 foot for range hoods.
Flexible ducting:
If flexible metal ducting is used,
all the equivalent feet values in
the table should be doubled. The
flexible metal duct should be
straight and smooth and extended
as much as possible.
DO NOT use flexible plastic
ducting.
NOTE: Any home ventilation
system, such as a ventilation
hood, may interrupt the proper
flow of combustion air and
exhaust required by fireplaces,
gas furnaces, gas water heaters
and other naturally vented
systems. To minimize the chance
of interruption of such naturally
vented systems, follow the
heating equipment manufacturer’s
guidelines and safety standards
such as those published by NFPA
and ASHRAE. When applicable,
install any makeup (replacement)
air system in accordance with local
building code requirements. Visit
GEAppliances.com for available
makeup air solutions.
Total
Equivalent Quantity Equivalent
Duct Piece Dimensions Length* Used Length
Round, 1 ft. (per
straight foot length)
3-1/4″ x 10″ 1 ft. (per straight foot length)
90° elbow 12 ft.
45° elbow 7 ft.
3-1/4″ x 10″ 14 ft.
3-1/4″ x 12″ 10 ft.
90° elbow
3-1/4″ x 10″ 8 ft.
3-1/4″ x 12″ 6 ft.
45° elbow
3-1/4″ x 10″ 33 ft. 3-1/4″ x 12″ 24 ft.
90° flat elbow
6″ round to 2 ft.
rectangular
Rectangular to 8″ 2 ft.round
3-1/4″ x 10″ 4 ft.
3-1/4″ x 12″ 4 ft.
6″ round to rectangular
transition 90° elbow
3-1/4″ x 10″ 4 ft.
3-1/4″ x 12″ 4 ft.
Rectangular to 6″ round
transition 90° elbow
Round wall cap 24 ft.
with damper
3-1/4″ x 10″ 24 ft.
3-1/4″ x 12″ 18 ft.
Rectangular wall cap
with damper
Round roof cap 33 ft.
* Actual length of straight duct plus duct fitting
equivalent. Equivalent length of duct pieces are
based on actual tests conducted by GE Appliances
Evaluation Engineering and reflect requirements for
good venting performance with any ventilation hood.
31-10724-75
Total Duct Run
Installation Preparation
POWER SUPPLY
IMPORTANT – (Please read carefully)
WARNING
APPLIANCE MUST BE PROPERLY GROUNDED.
Remove house fuse or open circuit breaker before
beginning installation.
Do not use an extension cord or adapter plug with
this appliance. Follow National Electrical Code or
prevailing local codes and ordinances.
Electrical supply
This vent hood must be supplied with 120V, 60Hz, and
connected to an individual, properly grounded branch
circuit, and protected by a 15- or 20-amp circuit
breaker or time-delay fuse.
■ Wiring must be 2-wire with ground.
■ If the electrical supply does not meet the above
requirements, call a licensed electrician before
proceeding.
■ Route house wiring as close to the installation
location as possible. Wiring can enter from the
ceiling or rear wall. Route additional length from the
ceiling or wall to reach the junction box.
■ Connect the wiring to the house wiring in
accordance with local codes.
Grounding instructions
The grounding conductor must be connected to
a ground metal, permanent wiring system, or an
equipment-grounding terminal or lead on the hood.
FOR PERSONAL SAFETY, THIS
TOOLS AND MATERIALS REQUIRED
(Not Supplied)
Pencil and tape
measure
Spirit level
Phillips screwdriver
Electric drill with 1/8″ bits,
#2 Phillips and flat head
Safety glasses
Utility Knife
Masking tape
Wire cutter/stripper
Gloves
Hammer
Flashlight
Metal snips
Pliers
WARNING
equipment-grounding conductor can result in a risk
The improper connection of the
Stepladder
of electric shock. Check with a qualified electrician or
service representative if you are in doubt whether the
appliance is properly grounded.
UL-listed wire nuts
Aluminized
duct tape
Strain relief for
junction box
Saber saw or Key Hole saw
6″ round metal duct, length
to suit installation
120V 60Hz. 15- or 20-Amp,
2-wire with ground, properly grounded
branch circuit
631-10724-7
Installation Preparation
REMOVE THE PACKAGING
CAUTION
edges.
The vent hood is shipped secured to a shipping board
with 4 screws.
■ Remove the duct cover, parts box and foam
packaging.
■ Lift the hood out of the box.
■ Remove and properly discard the plastic wrapping.
■ Remove metal grease filters and side bar packaging.
Wear gloves to protect against sharp
■ To remove the shipping board, locate and remove 2
screws at the top of the assembly and 2 screws inside
the hood behind the filter guides on the left and right
sides. Discard the shipping board.
Junction box
Mounting screw
Knockout
Mounting
screw
Shipping board
■ Remove junction box cover.
■ Remove knockout from junction box.
■ Install strain relief onto junction box.
Mounting screw
Shipping board
CHECK INSTALLATION HARDWARE
Locate the hardware accessory box packed with the
hood and check contents.
2 Mounting brackets
10 wood
screws
10 metal wall
fasteners
2 Large
flat washers
• Drill 1/8" Pilot Holes For Mounting Brackets.
• Drill 1/8" Pilot Holes.
Align edge 25-1/2" above Cooking Surface.
2-5/32"
5-7/8"
13-9/16"
17-5/16"
C
L
• Drill 1/8" Pilot Holes.
3-15/16"
3 Stainless
steel grease
filters
Wall-mount template
2 Utensil rods with 4 machine screws
Additional Parts for Recirculation Operation
Duct cover bracket (not required
for recirculating operation)
NOTE: Additional tools, materials and hardware are required to
construct your wall framing support.
31-10724-77
2 Phillips-head
duct cover
screws
Decorative
duct covers
Air deflector with upper
duct connector
3 charcoal filters
Installation Preparation
DETERMINE INSTALLATION HEIGHT
■ Telescopic duct covers are provided to conceal the
ductwork running to the ceiling.
■ This hood can be installed for vented or recirculating
operation. All necessary parts are shipped with the
hood.
24” Min.
30” Max.
36" Min.
NOTE: Installation height should be measured from
the cooking surface to the bottom of the hood.
The vent hood must be installed 24″ min. and 30″ max.
above the cooking surface. The hood installation height,
from the cooking surface to the bottom of the hood,
depends upon ceiling height and duct cover limitations.
DUCT COVER DIMENSIONS
9-1/4″
11-7/8″
ZX7510SPSS Duct Cover Accessory
This accessory is available for installation with
ceiling heights above 9 feet to 10 feet and higher. This
accessory consists of one 31-1/2″ lower duct cover.
7′ 11″ 24” to 28” 24” to 28”
8′ 0” 24” to 29” 24” to 29”
8′ 1” 24” to 30” 24” to 30”
8′ 2” 24” to 30” 24” to 30”
8′ 3” 24” to 30” 24” to 30”
8′ 4” 24” to 30” 24” to 30”
8′ 5” 24” to 30” 24” to 30”
8′ 6” 24” to 30” 24” to 30”
8′ 7” 24″ to 30” 24” to 30”
8′ 8” 24” to 30” 24” to 30”
8′ 9” 25” to 30” 24” to 30”
8′ 10” 26” to 30” 24” to 30”
8′ 11” 27” to 30” 24” to 30”
9′ 0” 28” to 30” 2” to 30”
9′ 1” 29” to 30” 25” to 30”
9′ 2” 30” 26” to 30”
9′ 3” 27” to 30”
9′ 4” 28” to 30”
9′ 5” 29” to 30”
9′ 6” 30”
9′ 0″ 24″ to 30″ 24″ to 28″
9′ 1″ 24″ to 30″ 24″ to 29″
9′ 2″ 24″ to 30″ 24″ to 30″
9′ 3″ 24″ to 30″ 24″ to 30″
9′ 4″ 24″ to 30″ 24″ to 30″
9′ 5″ 24″ to 30″ 24″ to 30″9′ 6″ 24″ to 30″ 24″ to 30″
9′ 7″ 24″ to 30″ 24″ to 30″
9′ 8″ 24″ to 30″ 24″ to 30″9′ 9″ 24″ to 30″ 24″ to 30″
9′ 10″ 25″ to 30″ 24″ to 30″
9′ 11″ 26″ to 30″ 24″ to 30″
10′ 0″ 27″ to 30″ 24″ to 30″
10′ 1″ 28″ to 30″ 24″ to 30″
10′ 2″ 29″ to 30″ 24″ to 30″
10′ 3″ 30″ 25″ to 30″
10′ 4″ 26″ to 30″
10′ 5″ 27″ to 30″
10′ 6″ 28″ to 30″
10′ 7″ 29″ to 30″
10′ 8″ 30″
cooking surface. Add hood installation height
determined on page 8. Mark that location.
–Use a level to draw a straight pencil line on the
wall.
–Tape the template in position along the penciled
line. CHECK TO BE SURE THE TEMPLATE IS
LEVEL.
3-3/4″ c enterline to wall
• Drill 1/8" Pilot Holes For Mounting Brackets.
FOR CEILING VENT
DUCTING
FOR WALL
VENT DUCT
Centerline 6″ min. above
bracket location
2-5/32"
5-7/8"
13-9/16"
1
INSTALL FRAMING FOR HOOD
SUPPORT
IMPORTANT: The vent hood must be secured to
rear support framing or a wall stud. Framing must be
capable of supporting 100 lbs.
6-1/2″ min. opening for ductwork
View from
rear cleats
1″ x 12″ min.
mounting
support
Centerline of
installation
space
17-5/16"
C
L
• Drill 1/8" Pilot Holes.
Align edge 25-1/2" above Cooking Surface.
• Drill 1/8" Pilot Holes.
3-15/16"
Ceiling ducting:
If ductwork will vent straight up to the ceiling:
■ Use a level to draw a line straight up, from the
centerline on the template to the ceiling.
■ Measure 3-3/4″ from the back wall to the centerline
of an 6-1/2″ hole on the ceiling.
NOTE: If drywall is not present, add drywall thickness
to the 3-3/4″ dimension.
Wall Ducting:
If ductwork will vent to the rear:
■ Use a level to draw a line straight up from the
centerline on the template.
■ Measure at least 6″ above the bracket location shown
on the template to the centerline of a 6-1/2″-dia. duct
hole. (Hole may be elongated for duct elbow.)
HOUSE WIRING LOCATION:
■ The junction box is located on the top left side of the
hood.
■ Wiring can enter from the back wall or ceiling above
the top bracket location. Route additional wiring
length to reach the junction box.
NOTE: 2 horizontal supports
will be needed if there is a
stud located between the
horizontal screw locations.
If drywall is present, mark the screw hole locations for
the top mounting brackets. Remove the template.
■ Cut away enough drywall to expose 2 vertical studs
at the bracket location indicated on the template.
■ Install a horizontal support at least 1″ x 12″ between
two wall studs at the mounting screw location. The
horizontal support must be flush with the room
side of the studs. Use cleats behind both sides of
the support to secure to wall studs.
IMPORTANT: Reinstall drywall for an even mounting
surface.
31-10724-79
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
2
INSTALL MOUNTING BRACKETS
The vent hood must be secured to rear support framing
or a wall stud.
■ With the template taped in place, use a punch to mark
all mounting screw locations.
■ Drill 1/8″ pilot holes at the 6 punched locations.
■ Remove the template.
■ Enlarge holes that did not enter studs to 3/8″ and tap
anchors for wall fasteners into the holes.
– Drive screws into the fasteners to allow anchors to
expand against the wall material. Remove the screws
for final installation.
■ Secure the mounting brackets to the wall studs with
wood screws provided.
3
INSTALL THE HOOD
Place the hood on the brackets and slide left to right to
align with rectangular slots at the top.
■ Adjust the installation height by tightening or loosening
the screws “A” at the bottom of the brackets.
■ Align the hood lower mounting holes with pilot holes in
the wall.
■ Using two large washers (supplied), install wood
screws or wall-fastener screws, loosely, into lower
mounting holes. Do not tighten.
■ Level the hood by tightening or loosening the screws
“A” located on the bottom mounting brackets.
■ Tighten the lower mounting screws.
■ Tighten screws “B” located at the top of the mounting
bracket against the hood to adjust position. Do not
overtighten screws.
Screws “B”
Screws “A”
NOTE: Screws “A” and “B” are preassembled onto the
brackets. Do not remove these screws.
Screws “B” to adjust
hood against wall
Level and height
adjustment
screws “A”
Lower mounting
screws
1031-10724-7
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
4
INSTALL DUCT BRACKET
VENTING TO THE REAR (HORIZONTAL EXHAUST)
OR STRAIGHT UP TOP (VERTICAL EXHAUST)
■ Temporarily install the 2 small screws into the sides of
the duct bracket. Remove the screws. This will ensure
ease of final installation.
■ Position the upper duct bracket against the wall and
ceiling, aligned with CL pencil mark and CL on the
bracket.
■ Mark the 4 screw locations of the bracket.
■ Remove the bracket.
■ Drill 1/8″ pilot holes in marked bracket location.
■ If pilot holes do not enter studs, enlarge the holes 3/8″
and install wall-fastener anchors. Drive screws into the
fasteners to allow anchors to expand against the wall
material. Remove the screws.
■ Secure the bracket to the ceiling and wall with wood
screws and/or wall-fastener screws.
Top or
vertical
exhaust
Duct bracket
Rear or
horizontal
exhaust
31-10724-711
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
5
CONNECT DUCTWORK
■ Remove shipping tape from the damper.
■ Install ductwork, making connections in the direction
of airflow as illustrated.
■ Push duct over the exhaust outlet and damper.
Airflow
Duct tape
over seam
and screw
CAUTION
exhaust outlet connection. Doing so will prevent proper
damper operation. Seal connection with tape only.
■ Secure joints in ductwork with sheet metal screws.
■ Wrap all duct joints and the flange connections with
aluminized duct tape for an airtight seal.
Do not use sheet metal screws at the
Screw
6
CONNECT ELECTRICAL
Verify that power is turned off at the source.
WARNING
a ground wire, a ground must be provided by the
installer. When house wiring is aluminum, be sure
to use U.L.-approved antioxidant compound and
aluminum-to-copper connectors.
■ Remove the junction box cover and the selected
knockout.
Knockout
Junction
box cover
■ Secure the house wiring to the junction box with a
strain relief (not provided).
■ Connect the white lead to the branch circuit white
lead.
■ Connect the black lead to the branch circuit black
lead.
■ Connect the green/yellow lead to the branch circuit
green lead or bare ground lead.
■ Secure all the connections with wire nuts on each
electrical connector.
■ Push the wires into the junction box and replace the
cover. Be sure the wires are not pinched.
■ Secure the junction box cover with the 2 original
screws.
If house wiring is not 2-wire with
1231-10724-7
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
7
INSTALL DUCT COVER AND
UTENSIL RODS
Assemble the duct covers
as shown.
For this vented installation,
place upper duct piece
inside the lower duct
piece. The inner duct
cover venting holes should
be positioned toward the
bottom end and should not
be visible.
■ Insert the assembled
duct covers into the
impression on the top of
the hood.
■ Extend the inner duct cover upwards to meet the
ceiling and bracket. (The vent holes should not be
visible in this installation.)
■ Secure the duct cover to the bracket with the 2 small
duct cover screws provided.
■ Install the side utensil rods as shown with screws
provided.
Mounting Screws
Bottom
Notches
Install optional accessory ZX7510SPSS
(if needed to reach taller ceiling heights)
■ Separate the supplied duct cover into pieces. Discard
the lower (outer) section.
■ Slide the new ZX7510SPSS duct cover onto the
original upper section. Be sure that the longer section
is outside the shorter original section. The notches will
be at the bottom and the screw holes at the top as
illustrated.
■ Secure the duct cover to the bracket with the 2 small
duct cover screws provided.
8
INSTALL FILTERS
Lower charcoal
filter channel
■ Remove protective film on filters.
■ Tip the filter into the lower channel at the rear of the
opening, push back, lift and pull the knob forward until
the filter rests on the channel.
9
FINALIZE INSTALLATION
■ Remove protective film covering the control panel
on the front face of the hood and any remaining
packaging materials.
■ Make sure the filters are seated properly when
installed and the filter light is not on.
Lower
filter slots
■ Install all three metal grease filters.
■ Turn power on. If the filter light on the control panel
glows, adjust the right-side filter in the channel to
engage the switch arm.
■ Be sure fan and lights operate correctly. Refer to
the Owner’s Manual for operating instructions and
Problem Solver.
31-10724-713
Installation Instructions
INSTALLATION – RECIRCULATING
DUCTWORK, WIRING LOCATIONS
■ Determine the exact location of the vent hood.
■ Locate the template packed with the literature.
■ Measure 36″ from the floor to the top of the cooking
surface. Add hood installation height determined on
page 8. Mark that location.
■ Tape the template in position along the penciled line.
CHECK TO BE SURE THE TEMPLATE IS LEVEL.
■ Use a level to draw a line straight up, from the
centerline on the template to the ceiling.
• Drill 1/8" Pilot Holes For Mounting Brackets.
• Drill 1/8" Pilot Holes.
Align edge 25-1/2" above Cooking Surface.
2-5/32"
5-7/8"
13-9/16"
17-5/16"
C
L
• Drill 1/8" Pilot Holes.
3-15/16"
1
INSTALL FRAMING FOR HOOD
SUPPORT
IMPORTANT: The vent hood must be secured to
rear support framing or a wall stud. Framing must be
capable of supporting 100 lbs.
View from
rear cleats
1″ x 12″ min.
mounting
support
Centerline of
installation
space
HOUSE WIRING LOCATION:
■ The junction box is located on the top left side of the
hood.
■ Wiring can enter from the back wall or ceiling above
the top bracket location. Route additional wiring
length to reach the junction box.
NOTE: 2 horizontal supports
will be needed if there is a
stud located between the
horizontal screw locations.
If drywall is present, mark the screw hole locations for
the top mounting brackets. Remove the template.
■ Cut away enough drywall to expose 2 vertical studs
at the bracket location indicated on the template.
■ Install a horizontal support at least 1″ x 12″ between
two wall studs at the mounting screw location. The
horizontal support must be flush with the room
side of the studs. Use cleats behind both sides of
the support to secure to wall studs.
IMPORTANT: Reinstall drywall for an even mounting
surface.
1431-10724-7
Installation Instructions
INSTALLATION – RECIRCULATING
2
INSTALL MOUNTING BRACKETS
The vent hood must be secured to rear support framing
or a wall stud.
■ With the template taped in place, use a punch to mark
all mounting screw locations.
■ Drill 1/8″ pilot holes at the 6 punched locations.
■ Remove the template.
■ Enlarge holes that did not enter studs to 3/8″ and tap
anchors for wall fasteners into the holes.
– Drive screws into the fasteners to allow anchors to
expand against the wall material. Remove the screws
for final installation.
■ Secure the mounting brackets to the wall studs with
wood screws provided.
3
INSTALL THE HOOD
Place the hood on the brackets and slide left to right to
align with rectangular slots at the top.
■ Adjust the installation height by tightening or loosening
the screws “A” at the bottom of the brackets.
■ Align the hood lower mounting holes with pilot holes in
the wall.
■ Using two large washers (supplied), install wood
screws or wall-fastener screws, loosely, into lower
mounting holes. Do not tighten.
■ Level the hood by tightening or loosening the screws
“A” located on the bottom mounting brackets.
■ Tighten the lower mounting screws.
■ Tighten screws “B” located at the top of the mounting
bracket against the hood to adjust position. Do not
overtighten screws.
Screws “B”
Screws “A”
NOTE: Screws “A” and “B” are preassembled onto the
brackets. Do not remove these screws.
Screws “B” to adjust
hood against wall
Level and height
adjustment
screws “A”
Lower mounting
screws
31-10724-715
Installation Instructions
INSTALLATION – RECIRCULATING
4
ASSEMBLE DEFLECTOR
AND CONNECTOR
A. The duct connector is shipped
inside the deflector.
B. Snap the plastic connector out
of the deflector and remove.
C. Turn over the plastic
connector. From the bottom,
snap the connector over the
opening as shown.
B
Remove plastic connector
5
SIZE DUCT PIECE
■ Hold air deflector
with duct connector
against the ceiling.
Align window on
the back of the
deflector with the
marked centerline.
■ Measure from
the bottom of the
deflector to the
top of the hood as
shown. Reduce
this dimension
by 1″ to facilitate installation.
The duct will cover/overlap
the duct connector and the
exhaust outlet.
■ Cut the duct piece to size and
slip onto the bottom of the
duct connector.
■ Use duct tape to secure the
duct piece to the connector.
■ Temporarily install the 2 small
duct cover screws into the
sides of the deflector. Remove the screws. This will
ensure ease of final installation.
Centerline
A
C
Snap into place
Duct
length
Measure
Screws
Air deflector assembly
length
6
INSTALL AIR DEFLECTOR
ASSEMBLY
■ Place the assembly
over the hood outlet.
■ Hold the assembly
against the ceiling.
The penciled
centerline should
show through the
slot on the deflector.
Mark the two screw
holes on the back of
the assembly.
■ Remove the
assembly and drill
1/8″ pilot holes into
the wall studs.
■ Enlarge holes that
did not enter studs to 3/8″ and tap plastic or metal
anchors into the holes, flush with the wall.
■ Mount the assembly onto the hood outlet, push up
against the ceiling and install the screws provided.
■ Use duct tape to seal the connection.
CAUTION
the hood duct flange connection. Doing so will prevent
proper damper operation. Seal connections with tape
only.
Do not use sheet metal screws at
1631-10724-7
Installation Instructions
INSTALLATION – RECIRCULATING
7
CONNECT ELECTRICAL
Verify that power is turned off at the source.
WARNING
a ground wire, a ground must be provided by the
installer. When house wiring is aluminum, be sure
to use U.L. approved antioxidant compound and
aluminum-to-copper connectors.
■ Remove the junction box cover and the selected
knockout.
Knockout
Junction
box cover
■ Secure the house wiring to the junction box with a
strain relief.
■ Connect the white lead to the branch circuit white
lead.
■ Connect the black lead to the branch circuit black
lead.
■ Connect the green/yellow lead to the branch circuit
green lead or bare ground lead.
■ Secure all the connections with wire nuts on each
electrical connector.
■ Push the wires into the junction box and replace the
cover. Be sure the wires are not pinched.
■ Secure the junction box cover with the 2 original
screws.
If house wiring is not 2-wire with
8
INSTALL DUCT COVERS AND
UTENSIL RODS
■ Assemble the duct covers as shown.
Mounting screw holes
For this recirculating installation, the vent holes must
be positioned at the top. The vent holes must be
fully exposed to allow airflow into the room.
■ Insert the duct cover assembly into the impressions
on the top of the hood.
■ Extend the inner duct cover upwards to meet the
ceiling and support frame.
Install optional accessory ZX7510SPSS
(if needed to reach taller ceiling heights)
■ Separate the supplied duct cover. Discard the lower
(outer) section.
■ Slide the new ZX7510SPSS duct cover into the
original upper section. Be sure that the vent holes
are positioned toward the top.
■ Insert the duct cover assembly into the impressions
on the top of the hood.
■ Secure the duct cover at the top to the air deflector
with 2 screws provided.
■ Install the side utensil rods as shown with screws
provided.
31-10724-717
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.