Monogram ZV48R, ZV36R, ZV30R Installation Instructions Manual

Installation Instructions
If you have questions, call 800-GE-CARES or visit our website at: www.monogram.com
30", 36" and 48" Restaurant Style Vent Hoods
Models: ZV48R ZV36R ZV30R
Monogram.
®
We bring good things to life.
1
Installation Instructions
BEFORE YOU BEGIN
Read these instructions completely and carefully.
• IMPORTANT - Save these instructions for
local inspector’s use.
• IMPORTANT - Observe all governing codes
and ordinances.
• Note to Installer - Be sure to leave these instructions with the Consumer.
• Note to Consumer - Keep these instructions for future reference.
• Skill Level – Installation of this vent hood requires basic mechanical and electrical skills.
• Completion time – 1 to 3 hours.
• Proper installation is the responsibility of the installer.
• Product failure due to improper installation is not covered under the Warranty.
CAUTION:
Due to the weight and size of these vent hoods and to reduce the risk of personal injury or damage to the product, TWO PEOPLE ARE REQUIRED FOR
PROPER INSTALLATION.
PRUDENCE
À cause du poids et de la taille de ces hottes et pour reduire le risque de blessures et de dommages, IL FAUT
DEUX PERSONNES POUR FAIRE L’INSTALLATION CORRECTEMENT.
WARNING:
To reduce the risk of fire or electrical shock, do not use this range hood with any external solid-state speed control device. Any such alteration from original factory wiring could result in damage to the unit and/or create an electrical safety hazard.
ADVERTISSEMENT
Pour réduire le risque d’incendie ou de choc électrique, il ne faut pas utiliser cette hotte avec un régulateur de vitesse électronique externe. Toute modification de ce type du branchement d’usine peute endommager l’appareil ou créer un risque de choc électrique.
TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK.
WARNING:
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: A. Use this unit only in the manner intended by the
manufacturer. If you have any questions, contact the manufacturer.
B. Before servicing or cleaning unit, switch power off at
the service panel and lock service panel to prevent power from being switched on accidentally. If the service panel cannot be locked, fasten a tag or prominent warning label to the panel.
ADVERTISSEMENT
POUR RÉDUIRE LE RISQUE D’INCENDIE, DE CHOC ÉLECTRIQUE OU DE BLESSURES, IL FAUT OBSERVER LES REGLES SUIVANTES: A. Utiliser cet appareil uniquement de la maniére
prévue par le fabricant. En cas de question, consulter le fabricant.
B. Avant toute intervention ou nettoyage, couper
l’alimentation électrique au disjoncteur et verrouiller le panneau du disjoncteur pour éviter la mise sous tension accidentelle. S’il n’est pas possible de verrouiller le panneau du disconcteur, attacher un placard ou une étiquette trés visible au panneau.
• For general ventilating use only. Do not use to exhaust hazardous or explosive materials or vapors.
• Structural framing, installation work and electrical wiring must be done by qualified person(s). In accordance with all applicable codes and standards including fire-rated construction.
• Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
• Local codes vary. Installation electrical connections and grounding must comply with applicable codes. In the absence of local codes, the vent should be in­stalled in accordance with National Electrical Code ANSI/NFPA 70-1990 or latest edition.
CAUTION: To reduce risk of fire and to
properly exhaust air, be sure to duct air outside – Do not vent exhaust air into spaces within walls or ceilings or into attics, crawl spaces, or garages.
PRUDENCEIl faut prendre soin d’installer
un conduit vers l’extérieur pour réduire le risque d’incendie et pouvoir évacuer l’air correctement. Il ne faut pas évacuer l’air correctement. Il ne faut pas évacuer l’air dans l’espace entre les parois d’un mur, un plafond ou un grenier, un espace sanitaire ou un garage.
2
Installation Instructions
CONTENTS
Product Dimensions .........................................................3
Installation Clearances .....................................................4
Optional Duct Cover Accessories .................................... 4
Advance Planning .............................................................5
Power Supply .................................................................... 5
Duct Fittings...................................................................... 6
Using Duct Cover Accessories.......................................... 7
Tools and Materials Required .......................................... 8
Remove the packaging ..................................................... 8
Parts Provided ...................................................................9
PRODUCT DIMENSIONS
Each hood is shipped with a stainless steel
Warming
Shelf
Backguard
backguard and a warming shelf. Hoods may be installed with the shelf or backguard alone, or with both as shown.
Step 1, Determine Ductwork and Wiring Locations .... 10
Step 2A, Install Hood Onto Wall ................................... 11
Step 2B, Install Hood Beneath Soffit ............................ 12
Step 3, Connect Ductwork ............................................. 13
Step 4, Connect Electrical..............................................13
Step 5, Install Duct Covers ............................................. 13
Step 6, Install Motor .......................................................13
Step 7, Install Filters ....................................................... 14
Step 8, Install Backguard and Shelf............................... 14
Step 9, Install Shelf Only................................................15
Step 10, Install Implement Rods ................................... 15
12"
22-1/2"
25"
47-15/16"
47-15/16"
12"
22-1/2"
Model ZV36R
25"
35-15/16"
35-15/16"
Model ZV48R
22-1/2"
Model ZV30R
12"
25"
29-15/16"
29-15/16"
3
Advance Planning
INSTALLATION CLEARANCES
These vent hoods are designed to be installed onto a wall or beneath a soffit or cabinet.
Installation with Warming Shelf
• Hoods must be installed 32" Min., 38" Max over any type cooking surface when warming shelf is used.
Installation without Warming Shelf
• Install these hoods 30" Min. to 36" Max. above the cooking surface when installed over any professional style cooktop or range.
• These hoods may be installed 24" min. above a gas or electric drop-in style cooktop.
Note: Clearances may vary due to type of cooking product and local codes. Check with local inspectors to be sure standard is applicable.
Soffit Installation
SOFFIT
30" Min.
36" Max.
SOFFIT
32" Min.
38" Max.
OPTIONAL DUCT COVER ACCESSORIES
Decorative duct covers are available in 6" and 12" heights. Duct covers may be stacked, in various combinations, to conceal the ductwork running from the top of the hood to the ceiling.
• Before you begin, you should determine the installa­tion height of the hood and order the correct size duct cover. The duct covers should be ordered at the same time as the vent hood and be on site before installation. Order the duct cover corresponding to your model.
6" Duct Cover
12" Duct Cover
Install these hoods 30" Min. to 36" Max. over a professional style cooktop or range.
Allow 32" min. and 38" max. clearance above any cooking surface when installed with shelf.
In this installation the ductwork running from the top of the hood will be concealed in the soffit or upper cabinetry.
Wall Mount Installation
30" Min.
36" Max.
Install these hoods 30" Min. to 36" Max. over a professional style cooktop or range.
Allow 32" min. and 38" max. clearance above any cooking surface when installed with shelf.
32" Min.
38" Max.
For this installation, a decorative duct cover is avail­able to conceal the ductwork running from the top of the hood. Use of the duct cover requires special consideration to the installation height above the countertop.
6" Duct Covers Hood Model 6” Duct Cover Dimensions
ZV48R ZX48DC6 6"H x 19-11/16"W x 11-7/8"D ZV36R ZX36DC6 6"H x 15-3/4"W x 11-7/8"D ZV30R ZX36DC6 6"H x 15-3/4"W x 11-7/8"D
12" Duct Covers Hood Model 12” Duct Cover Dimensions
ZV48R ZX48DC12 12"H x 19-11/16"W x 11-7/8"D ZV36R ZX36DC12 12"H x 15-3/4"W x 11-7/8"D ZV30R ZX36DC12 12"H x 15-3/4"W x 11-7/8"D
4
Advance Planning
ADVANCE PLANNING
Ductwork Planning
• These vent hoods are equipped for 10" round ductwork. In most instances they may be transitioned to 8" round.
• This hood may be vented vertically through upper cabinets, soffit or ceiling. A duct transition piece is supplied for vertical exhaust. Use locally supplied elbows to vent horizontally through the rear wall.
• Determine the exact location of the vent hood.
• Plan the route for venting exhaust to the outdoors.
• Use the shortest and straightest duct route possible. For satisfactory performance, duct run should not exceed 150 ft. equivalent length for any duct configurations.
• Refer to “Duct Fittings” chart to compute the maxi­mum permissible length for duct runs to the out­doors.
• Use metal ductwork only.
• Install a wall cap or roof cap with damper at the exterior opening. Order the wall or roof cap and any transition needed in advance.
Wall Framing for Adequate Support
• These vent hoods are heavy. Adequate structural support must be provided. Hoods must be secured to vertical studs in the wall.
• It is strongly recommend that the vent hood with duct cover be on site before final framing and wall finishing. This will also help to accurately locate the ductwork and electrical service.
Decorative Duct Covers:
Decorative duct covers, 6" and 12" high, are available to fit all models. The duct cover conceals the ductwork running from the top of the hood to the ceiling or soffit. Stack one or more duct covers over the top of the hood to reach your ceiling height.
POWER SUPPLY
IMPORTANT - (Please read carefully)
WARNING:
FOR PERSONAL SAFETY, THIS APPLIANCE MUST BE PROPERLY GROUNDED.
ATTENTION – POUR DES RAISONS
DE SÉCURITÉ, CET APPAREIL DOIT ÊTRE CORRECTEMENT MIS À LA TERRE.
Remove house fuse or open circuit breaker before beginning installation.
Do not use an extension cord or adapter plug with this appliance. Follow National electrical codes or prevail­ing local codes and ordinances.
Electrical supply
These vent hoods must be supplied with 120V, 60Hz, and connected to an individual, properly grounded branch circuit, and protected by a 15 or 20 amp circuit breaker or time delay fuse.
• Wiring must be 2 wire with ground.
• If the electrical supply does not meet the above requirements, call a licensed electrician before proceeding.
• Route house wiring as close to the installation location as possible on the back wall or ceiling.
• Connect the wiring to the house wiring in accor­dance with local codes.
Grounding instructions
The grounding conductor must be connected to a ground metal, permanent wiring system, or an equip­ment-grounding terminal or lead on the hood.
WARNING: The improper connection of
the equipment-grounding conductor can result in a risk of electric shock. Check with a qualified electrician or service representative if you are in doubt whether the appliance is properly grounded.
ADVERTISSEMENT
Le mauvais branchement du fil de mise à la terre peut causer un choc électrique. En cas de doute, consulter un électricien qualifié ou un technicien pour déterminer si l’appareil est à la terre.
5