If you have questions, call 800-GE-CARES or visit our website at: www.monogram.com
Downdraft Vent Systems
36" Wide Models:
ZVB36
30" Wide Models:
ZVB30
Monogram.
®
We bring good things to life.
Page 2
CAUTION
WARNING
Before you begin—Read these instructions completely and carefully.
IMPORTANT: Save these instructions for local inspector’s use.
IMPORTANT: OBSERVE ALL GOVERNING CODES AND ORDINANCES.
Note to Installer: Be sure to leave these instructions with the Consumer.
Note to Consumer: Keep these instructions with your Owner’s Manual for future reference.
This appliance must be properly grounded. See “Power Supply”, page 10.
If you received a damaged vent, you should
immediately contact your dealer or builder.
Proper installation is the responsibility of the
installer. Product failure due to improper
installation is not covered under the GE
Appliance Warranty. See the Owner’s Manual
for warranty information.
For Monogram local service in your area,
1-800-444-1845.
For Monogram service in Canada,
1-888-880-3030.
For Monogram Parts and Accessories, call
1-800-626-2002.
www.monogram.com
WARNING:
To reduce the risk of fire, electric shock, or
injury to persons, observe the following.
A. Use this unit only in the manner intended
by the manufacturer. If you have questions,
contact the manufacturer.
B. Before service or cleaning unit, switch
power off at service panel and lock the
service disconnecting means to prevent
power from being switched on accidentally.
When the service disconnecting means
cannot be locked, securely fasten a prominent warning device, such as a tag, to the
service panel.
• Do not attempt to repair or replace any part
of the downdraft system unless it is specifically recommended in this book. All other
servicing should be performed by a qualified technician.
• For general ventilating use only. Do not use
the exhaust hazardous or explosive materials
and vapors.
• Installation work and electrical wiring must
be done by a qualifed person(s). In accordance with all applicable codes and standards including fire-rated construction.
To reduce the risk of fire and to properly
exhaust air, be sure to duct air outdoors. Do
not vent exhaust air into spaces within walls or
ceilings or into attics, crawl spaces or garages.
WARNING: TO REDUCE THE RISK OF
FIRE, USE ONLY METAL DUCTWORK.
Do not attempt to repair or replace any part
of the downdraft system unless it is specifically
recommended in this book. All other servicing should be performed by a qualified
technician.
Contents
2
Design Information
Models Available ........................................................... 3
JXRB57 Kit for Indoor Remote Blower Locations ... 17
JXBC57 Kit for Outdoor Remote Blower Locations 20
Page 3
Design Information
2-1/4"
3-1/4"
7"
12-3/8"
5-3/8"
3-1/4"
7-1/2"
6-3/8"
2"
8-1/2" Lift
Downdraft Vent Systems
Models
Available
Accessories
Product
Dimensions
These downdraft vents systems can be
retracted when not in use.
1
1
8
8
7
6
5
8
7
8
2
2
7
7
3
3
6
6
4
4
5
5
UNIT ON
1
8
2
7
ZVB36
1
2
3
4
1
2
36" Wide Downdraft Vent
in white, black and stainless steel
• JXRB57 optional accessory for indoor
remote location of the blower/motor
assembly. Use this kit when the blower and
motor assembly will be located outside or
below the cabinet floor.
30" Models30"28-3/8"
36" Models36"33-3/4"
A
ZVB30
30" Wide Downdraft Vent
in white, black and stainless steel
• JXBC57 optional outdoor cover accessory
for remote installation of blower and motor
assembly on an outside wall.
AB
1
1
2
3
1
2
3
4
1
8
8
7
6
4
5
8
7
6
5
8
2
2
7
7
3
3
6
6
4
4
5
5
UNIT ON
1
8
2
7
3
6
4
5
B
14-3/4"
27"
26"
3
Page 4
Design Information
Base
Cabinet
Filler Panel
Base Sink
BS30 Min. For ZVB30
BS36 Min. For ZVB36
Filler Panel
Maintain Cutout Clearances
to Front Edge as Specified
Downdraft Vent Systems
Advance
Planning
The installation of these downdraft vents with
any Monogram cooktop requires careful
consideration. For accurate planning, this
book provides individual dimension drawings
for the vent and the Monogram cooktop
installation.
Countertop Requirements:
The countertop must have a deep flat surface
to accommodate the cooktop and the vent.
Countertops with a rolled front edge and
backsplash may not provide the flat surface
area required.
Base Cabinet Requirements:
The base cabinet must be deep enough to
accommodate the min. clearance to the front
edge of the countertop, the cooktop burner
box and the vent.
Creative Solutions
√ When the kitchen design calls for an against the wall
installation, move the base cabinet forward, 3” to 5”.
Filler panels or complimentary moldings can be
added to the exposed cabinet sides.
Before you begin you must:
1. Review countertop dimension illustrations
to be sure you will have enough flat
countertop surface.
2. Check to be sure that the total countertop
depth required (including min. cutout to
front edge depth) allows enough space for a
backsplash.
3. Review the cabinet illustration. Check to be
sure that the interior cabinet depth will
house the cooktop burner box, the vent and
the cutout clearance from the front.
4. When countertop and cabinet depth
present a problem, review Creative Solutions.
5. Read this book completely to accurately
plan the installation location, clearances and
ductwork requirements.
With careful planning you can achieve a
custom look with minimal adjustments.
√ In an island or pennisula, use an extra deep
countertop. The countertop overhang at the front can
be adjusted to meet setback to cutout requirements.
√ When the cutout to front edge of the countertop
requirement is more than 2”, add a bullnose trim to
the front edge of the countertop. Include the trim
thickness when measuring front edge to cutout
requirement. By adding the trim, the cooktop can be
moved forward, providing additional countertop depth
and interior cabinet space.
B18
Base Sink
BS30 to BS42
B18
End
Panel
Countertop
Overhang
per Cooktop
Clearances
Must be
Maintained
Trim
Add a Bullnose Trim
or Other Decorative
Molding to Increase
Countertop Depth
and to Maintain
Required Clearance
From Front Edge to
Cutout.
1-7/8"
DOWNDRAFT
VENT
4
Cover Panel
Page 5
Design Information
Downdraft Vent Systems
Advance
Planning
(continued)
Clearances
• The downdraft system with blower, motor
and ductwork will occupy the cabinet below
the countertop and cooktop.
• The blower/motor assembly can be located
below the cabinet floor. The assembly will fit
between 16" floor joists. Order JXRB57 for
indoor remote locations.
– In this installation a transition to 6" round
is required.
• The blower motor assembly can also be
installed outdoors. Order JXBC57 for
remote blower installations outdoors.
– In this installation one or two 3-1/4"x10"
to 6" round transitions may be required.
• Refer to “Cooktop Clearances” for information on appropriate placement and necessary clearances when planning installation.
• Refer to your specific cooktop installation
instruction for other appropriate clearances.
• Avoid placing cabinetry directly above the
cooking surface when possible.
Ductwork
Prepare ductwork to vent to the outdoors.
• Use the shortest and straightest duct run
possible.
– The maximum permissible length for duct
run is 150 feet.
– Refer to “Duct Fittings” chart to calculate
equivalent length for various duct
configurations.
• If cabinetry is used above the cooking
surface:
– Use cabinets no more than 13" deep.
– Maintain 30" minimum clearance between
cooktop and unprotected cabinets directly
above cooktop.
– If clearance is less than 30", protect
cabinet bottoms with flame-retardant
millboard at least 1/4" thick or gypsum
board at least 3/16" thick covered with 28
gauge sheet steel or .02" thick copper.
– Clearance between cooktop and protected
cabinetry must not be less than 24."
EXCEPTION: Installation of a listed microwave oven or cooking appliance over the
cooktop shall conform to the installation
instructions packed with that appliance.
– Working areas adjacent to the cooktop
should have 18" minimum clearance
between countertop and cabinet bottom.
• Installation must conform with local codes.
• The downdraft blower system is designed to
use 3-1/4" x 10" ductwork. It can be
transitioned to 6" round.
• Ductwork MUST be vented to the outside–
never into a crawl space, attic or other
enclosed space.
• Determine the need for a wall cap or roof
cap. Order the cap in advance.
Electrical and Gas Locations
Plan the placement of the electrical outlet and
gas (if used) carefully. Gas or electrical outlets
cannot be placed on the back wall of the
cabinet because it may interfere with the
downdraft plenum.
• Install a standard electrical outlet within
reach of the vents’ two foot long power
cord.
– The vent and a Monogram gas cooktop
combination can operate from the same
120 volt standard duplex outlet.
– Electric cooktops must operate from a
separate 240 volt junction box.
5
Page 6
Installation Preparation
Downdraft Vent Systems
Cutouts and
Clearances
ZEU769
Electric Cooktops
with 36” Vent
• Measure carefully when cutting the
countertop. Make sure sides of the opening
are parallel and rear and front cuts are
exactly perpendicular to sides.
• Measure to be sure there is room for
clearances to the front edge of the
countertop.
• Refer to cooktop installation instructions
to be sure that models fit into the base
cabinets being used.
1-3/4" Min. Cooktop Cutout to Rear
Vertical Combustible Surface
36"
21-3/4"
Cutout
Depth
Front Edge
of Countertop
34" Cooktop and Vent Cutout
5/8" Cooktop Overlap
2-1/2" Min. Clearance to Cutout
2" Min. Cutout
to Side Walls
• Identify the cutout illustration for the
cooktop model you are installing.
– Draw lines on the countertop to follow as a
cutting guide. Measure and mark cooktop
and vent overlaps to be sure there is
enough flat countertop depth.
1/4" Overlap
1/8" Gap
22-1/2"
Total Flat
Surface
Required
Countertop Cutout: Requires 22-1/2" flat countertop
surface and 24-3/8" total countertop depth.
flat countertop surface. Requires 24-1/4" (B,W) and
24-3/8" (SS) total countertop depth.
2-1/2" Min.
Clearance to Cutout
2" Min. Cutout
to Side Walls
Cabinet: Requires 22-1/2" inside
cabinet depth.
–Remove rear support rail.
7
Page 8
Installation Preparation
1"
22-3/4" to Back Wall
22" to Support Rail
24-3/4"
2-3/4" to
Cutout
ZGU375 Cooktop
1-7/8"
3/4"
Thick
Support
Rail
19-7/16"
DOWNDRAFT VENT
Downdraft Vent Systems
ZGU36GG
Gas Cooktops
with 36" Vent
ZGU375
Gas Cooktop
with 36" Vent
2-1/4" Min. Cooktop Cutout to Rear
Vertical Combustible Surface
36"
21-3/4"
Cutout
Depth
Front Edge
of Countertop
34" Cooktop and Vent Cutout
13/16" Cooktop Overlap
(1-1/2" at Center)
2-1/2" Min.
Clearance to Cutout
6" Min. Cutout
to Side Walls
Countertop Cutout: Requires 23-3/8" (B,W) 23-1/2"
(SS) flat countertop surface. Requires 24-3/8" (B,W) and
24-1/2" (SS) total countertop depth.
3-3/8" Min. Cooktop Cutout to Rear
Vertical Combustible Surface
9/16"
21-7/16"
Cutout
Depth
2-9/16"
18-7/8"
Cooktop
Cutout
9/16"
36-1/2"
34" Vent Cutout
35-5/16"Cooktop
Area Cutout
7/16" Cooktop Overlap
(1-1/4" At Center)
1/4" Overlap
1/8" Gap
23-1/2" (SS)
23-3/8" (B,W)
Total Flat
Surface
Required
at Center
1/4" Overlap
1/8" Gap
22-3/4"
Total Flat
Surface
Required
2-1/2" to
Cutout
ZGU36 Cooktop
20-1/16"
3/4"
DOWNDRAFT VENT
22-3/4" to Back Wall
22" to Support Rail
24-3/4"
1-7/8"
Cabinet: Requires 22-11/16" inside
cabinet depth.
–Remove rear support rail.
3/4"
Thick
Support
Rail
Front Edge
of Countertop
8
Countertop Cutout: Requires 22-3/4” flat countertop
surface and 24-1/4" total countertop depth.
2-3/4" Min.
Clearance to Cutout
7-9/16" Min. Cutout
to Side Walls
Cabinet: Requires 22-5/16" inside
cabinet depth.
–Remove rear support rail.
Page 9
Clearances
Caution:
Wall coverings,
countertops and cabinets
should withstand 200° heat
generated by any cooktop.
Installation Preparation
Downdraft Vent Systems
Gas - 8-13/16" min.
Electric - 2"
Clearance to Sidewall
Tools and
Materials
Required
Parts
Supplied
30"
Min.
13"
Max.
18"
Min.
2" Min. to
Wall When
Installed
2" Min. to
Wall When
Installed
30"
Min.
13"
Max.
18"
Min.
8" Min. to
Wall When
Installed
Electric Cooktop ModelsGas Cooktop Models
• Large flat-blade screwdriver.
• Jig saw
• Carpenter’s square
• Ductwork to suit the installation
Open the carton and remove parts package.
Check contents to be sure all pieces are
present.
8" Min. to
Wall When
Installed
4 Stablizing Brackets
Remote Raise/Lower Assembly
Switch Cover Plate
Plastic Strain ReliefWire box and screwsWire and White Connector
Attachment Bracket
9
Page 10
Installation Preparation
Plastic Ties
34" for 36" Models
28-1/2" for 30" Models
29-1/2"
Electrical
Outlet
12" Above
Cabinet Floor
Do Not Locate Gas or Electrical
Connections Within Shaded Area
Downdraft Vent Systems
Remove
Packaging
Power
Supply
• Remove the shipping materials and the
carton, set carton aside. The carton can be
used as a pad when changing or adjusting
vent direction.
• Remove the plastic ties on both ends at the
top of the vent.
WARNING
FOR PERSONAL SAFETY:
Remove house fuse or open circuit breaker
before beginning installation.
Do not use an extension cord or adapter plug
with this appliance. Follow National electrical
codes or prevailing local codes and ordinances.
This downdraft vent must be supplied with
120V, 60Hz., and connected to an individual,
properly grounded branch circuit, protected
by a 15 or 20 ampere circuit breaker or time
delay fuse.
Gas Cooktops
If this vent is installed in combination with a
Monogram gas cooktop, it may operate from
the same duplex outlet.
Electric Cooktops
If this vent is installed in combination with a
Monogram electric cooktop, the vent must
operate from a separate 120V outlet.
• A properly grounded 3-prong receptacle
should be located within reach of the vents’
two foot power cord.
– Locate the receptacle inside the cabinet on
the right side wall. The receptacle cannot be
placed on the back of the cabinet wall where
it may interfere with the downdraft plenum.
See illustration.
IMPORTANT: (Please read carefully).
The power cord of this appliance is equipped
with a three-prong (grounding) plug which
mates with a standard three-prong grounding
wall receptacle to minimize the possibility of
electric shock. The customer should have the
wall receptacle and circuit checked by a
qualified electrician to make sure the receptacle is properly grounded and has correct
polarity.
• Where a standard two-prong wall receptacle
is encountered, it is the personal responsibility and obligation of the customer to have it
replaced with a properly grounded threeprong wall receptacle.
Do not, under any circumstances, cut or
remove the third (ground) prong from the
power cord.
DO NOT USE AN EXTENSION CORD.
10
Page 11
Installation Preparation
Downdraft Vent Systems
Venting
Options
Loosen Screws
to Adjust
Blower Left
to Right
Nut
Location
Inside
the Blower
Discharge
• The downdraft vent is shipped with the
discharge outlet pointing straight down and
can be changed to the left or right side.
• The blower outlet is sized for 3-1/2" x 10"
and can be transitioned to 6" round.
Loosen Screws to Rotate
30° to Left or 30° to Right
30° Rotation Left or Right
Side to side adjustments:
The entire blower mounting plate can be
adjusted 3-1/2" to the left or right. This will
help to align vent discharge to house
ductwork.
30° Rotation
For even more flexibility, the entire blower
can be rotated up to 30° towards the left or
30° towards to right.
Discharge direction
The blower assembly may be removed and
turned 90° for a left or right side discharge.
11
Page 12
Installation Preparation
Discharge Left
Downdraft Vent Systems
Venting
Options
• A left or right 90° direction adjustment
should be performed before dropping into
the countertop opening.
• Flatten the shipping box to use as a pad.
• Lay the vent on its back onto the pad.
To change to a left or right discharge:
• Remove 4 nuts holding the blower to the
mounting plate. See illustration. One nut is
just inside the blower discharge.
• Remove and turn the blower to the right or
left.
• Reinstall the 4 nuts.
To locate the ductwork holes in the cabinet
floor or side walls:
• Temporarily, place vent into the countertop
opening.
• Push the vent all the way to the back of the
opening.
• If you are transitioning to 6" round, place
transition piece over the discharge outlet.
– Mark the location and remove the
assembly.
– Cut holes and install ductwork
connections.
Order JXRB57 for installation of the blower and motor
below the floor.
Order JXBC57 for installation of the blower and motor
outdoors.
12
Discharge Down
(as Supplied)
Discharge Right
Page 13
Ductwork
Downdraft Vent Systems
Duct
Fittings
Use this form to
compute maximum
permissible lengths
for duct runs to
outdoors.
Note: Do not exceed
maximum permissible
equivalent lengths!
Flexible ducting:
If flexible metal
ducting is used, all the
equivalent feet values
in the table should be
doubled. The flexible
metal duct should be
straight and smooth
and extended as much
as possible.
Do NOT use flexible
plastic ducting.
Downdraft Vent
150' maximum
equivalent length
Note: Any home
ventilation system,
such as a cooktop with
a downdraft exhaust
mechanism, may
interrupt the proper
flow of combustion air
and exhaust required
by fireplaces, gas
furnaces, gas water
heaters and other
naturally vented
systems. To minimize
the chance of interruption of such
naturally vented
systems, follow the
heating equipment
manufacturer’s
guidelines and safety
standards such as those
published by NFPA
and ASHRAE.
Equivalent QuantityEquivalent
Duct PieceDimensionsLength*UsedLength
1 ft.
6" round,(per foot
straightlength)
1 ft.
3-1⁄4" x 10"(per foot
straightlength)
6"
90° elbow15 ft.
6"
45° elbow9 ft.
3-1⁄4" x 10"
90° elbow16 ft.
3-1⁄4" x 10"
45° elbow5 ft.
3-1⁄4" x 10"
90° flat elbow18 ft.
6" round
to 3-1⁄4" x 10"
transition7 ft.
3-1⁄4" x 10"
round to 6"
transition5 ft.
6" round to
1
⁄4" x 10"
3
transition
90° elbow20 ft.
3-1⁄4" x 10" to 6"
round transition
90° elbow12 ft.
6" round
wall cap
with damper21 ft.
3-1⁄4" x 10"
wall cap
with damper27 ft.
6" round
roof cap20 ft.
6" round
roof vent24 ft.
*Actual length of straight duct plus duct fitting
equivalent. Equivalent length of duct pieces are based
on actual tests conducted by GE Evaluation Engineering and reflect requirements for good venting
performance with any downdraft cooktop.
Total Duct Run
Total
13
Page 14
Installation
Duct Tape
Over Seam and Screw
Screw
Air
Flow
Downdraft Vent Systems
Step
1
Install
Downdraft
Vent
Optional Method
Secure to Cabinet
Side With Top
Screw on Case
Or Use Second Screw
Secure the Lower Brackets
to Blower Housing
Place the downdraft vent into the countertop
cutout, against the back side.
• Secure the downdraft to the countertop
supplied brackets. See illustration.
– Fasten brackets to top screws on the front
side of the vent, secure to cabinet side wall
just below the countertop. Or,
– Fasten one bracket to vent side and secure
to cabinet back wall.
Preferred Method
Secure the Upper
Brackets With Screws
Located on the side of
Case and Attach to
Back Wall of Cabinet
– Install two brackets on the bottom of the
vent. Attach brackets to slide screws on the
vent and to the floor using wood screws
(not supplied).
• When installing in a tile countertop surface,
it may be necessary to apply a locally
approved caulking to cover any gaps.
• The downdraft blower system is designed for
Step
2
Install the
Ductwork
14
use with 3-1/4" x 10" ductwork. It can be
transitioned to 6" round.
•Ductwork MUST be vented to the outside –
never into a crawl space, attic or other
enclosed space.
•6" PVC duct should be used when installing
under a concrete slab.
Note: Local building code must be followed
for installation and in specifying approved
type and schedule of PVC duct used.
• DO NOT USE flexible plastic ducting.
• Always use appropriate roof or wall cap with
damper. Laundry type wall caps should
never be used.
• Use the straightest duct run possible.
• For satisfactory performance the duct run
should not exceed 150 ft. or its equivalent
length when bends or various fittings are
used. Refer to the table of equivalent
lengths to calculate your installation.
• Install ductwork so the piece of duct nearest
the downdraft unit slots INTO the next
piece of the duct. Secure the joints with selftapping screws and apply duct tape around
the joints to ensure an airtight seal.
Page 15
Step
3
Install
Raise/Lower
Switch
WARNING: Disconnect electrical power from
unit before beginning switch installation.
Failure to do so could result in personal
injury or damage to the electrical controls.
Determine the location for the RAISE/
LOWER switch. The wiring lead is 72" long.
• Drill a 3/16" hole into the desired location.
– If switch is mounted into a tile surface, drill
the hole between tiles. Use locally approved
caulking to cover any gaps.
• Center the mounting bracket over the hole
and mark pilot holes. Remove and drill pilot
holes.
• Mount the metal switch bracket with screws
(not provided, choose screws for your type
of countertop or use locally approved
adhesive).
• Tie a knot in the lead as close to the switch
as possible. This will prevent the lead from
being pulled away from the switch.
• Thread the wire lead through the hole in
the top of the countertop.
Installation
Downdraft Vent Systems
Trim
Knot
Mounting
Bracket
3/16" Hole
Thread Electrical
Leads Through Hole
• Pull wire through hole from underside of
countertop and thread the wire lead into
the end of the wire box.
• Peal film from the back of the switch trim to
expose the adhesive.
• Press trim onto the mounting bracket to set
the adhesive.
• Peal film from the back of the RAISE/
LOWER pad to expose adhesive. Align with
impression and press to set adhesive.
•Remove protective coating from the top of
the trim frame.
Important: Do not connect wire leads to white
connector until you have threaded the lead
through the countertop hole and through the
end of the wire box.
• Push wire metal leads into the white connector plug. Pull wire through box leaving
about 2" additional length. See illustration.
• Place plastic strain relief over wire, the wire
should be flat and fit into the area. Do not
pinch or twist the wire. Snap the strain relief
closed.
• Push the strain relief into the hole on the
wire box. It will snap into position.
• Secure wire box to vent with screws
provided.
•Coil the excess wire and position away from
moving parts and cabinet contents.
Leads
2 Pin Connector
Pull 2" Length
Out of Box
Strain
Relief
15
Page 16
Installation
Downdraft Vent Systems
Step
4
Connect
Power
Step
5
Install Filters,
Check
Operation
• Plug power cord into properly grounded
receptacle.
To raise the vent, press the RAISE/LOWER
switch.
– On 30" models, the switch is located on the
top right side of the vent.
– On 36" models, the switch is installed in a
separate location.
• Tip filter into the opening and pull straight
down so that the filter rests on slides.
• Slide the filter to the right side.
• Tip the other filter into the opening and
pull straight down.
• To turn the fan on, slide control to HIGH.
– Select desired speed by sliding control
between HI and LO settings.
Cleaning
Note: It is not necessary to turn the fan OFF
before lowering the vent. The fan will automatically turn off when the vent is lowered.
When the fan is not turned off before lowering the vent, it will automatically come on at
the previously set speed when the vent is fully
raised.
To lower the vent, press the RAISE/LOWER
switch and hold until the vent begins to lower.
Cleaning the Stainless Steel Downdraft Vent
Stainless steel has some unique cleaning
characteristics. In order to keep you vent
looking like new, we suggest cleaning it with
Stainless Steel Magic or a similar product.
Stainless Steel Magic is available at Ace, True
Value, Servistar, HWI and other leading
stores. It is also available through GE Parts by
calling 1-800-626-2002. Order part number
WX10X15.
16
Page 17
This kit provides for the installation of the
blower and motor outside of the cabinet, such
as below the floor. Use this kit for indoor
remote installations only.
JXRB57 Kit
For Indoor Remote Blower Locations
Tools and Materials required:
• Pencil
• Measuring tape
• Drill with appropriate bits
• Nut driver
• Junction box
• Wire nuts
• Safety glasses
• 3-1/4" x 10" to 6" round transition.
• 3-1/4 x 10" duct, (or 6" round) sufficient length to reach
the outdoor wall cap or roof cap.
• Electrical cable and connectors, sufficient length to
connect the downdraft vent to the remote blower
location. 14-guage min. is recommended, must conform
to local codes.
Parts Supplied
Step
1
Prepare
the Vent
Note: A 3-1/4" x 10 transtion to 6" round is
required.
3"
Blower Wire Box
Loosen
Screw
Blower Conduit
Hanger Brackets
Package of screws
Cover Plate
• Flatten the shipping box to use as a pad.
• Place the unit on its back onto the protective pad.
• Remove the wire box on the plenum.
• Cut the blower leads approximately 3" from
the plug on the end of the vent.
• Remove the blower conduit by loosening the
screw on the fitting.
• Set aside the 3" wire leads with plug, wire
box and screws.
Outlet Plate
17
Page 18
JXRB57 Kit
14-1/2"
For Indoor Remote Blower Locations
Step
1
(continued)
• Remove the 4 nuts holding the blower to the
mounting plate. One nut is hidden inside
the outlet. Remove blower.
• Remove the blower mounting plate.
• Remove 2 screws along the bottom of the
blower box which are visible once blower
plate is removed.
• Carefully, turn the unit over to access the
back side.
• Remove 4 screws along the top of the blower
box.
• Turn unit over and remove the 4 screws
along the top.
• Remove the blower box.
• Retain all screws.
Important:
unused parts. If the
appliance is relocated at
a later time, parts may be
needed.
Save any
Hidden
Screws
Step
2
Determine
Blower
Location
• Determine location of the blower and
motor.
– The blower will fit between floor joists, 16”
on center. Or, provide a surface to attach
the entire assembly to the underside of the
floor.
• Secure mounting brackets to the top of the
blower with screws and nuts. One bracket in
each corner, as illustrated.
– Set the bracket at the ends of the curved
slots to reach a 14-1/2” span between floor
joists, or adjust for your installation
situation.
• Mark the installation location and cut hole
for 6” round duct.
• Secure the blower to the joists.
Blower
Blower Box
Blower
Mounting
Plate
18
Page 19
Step
Wiring to Blower Junction Box
Provided
Mounting
Screws
Blower
Wire
Box
Wire Nuts
3-Wire
Connectors
Plenum
JXRB57 Kit
For Indoor Remote Blower Locations
3
Connect
Ductwork
Downdraft
Duct Adapter
Outlet Cover
• The downdraft plenum can discharge from
either the right or left side. Select the side
that provides the best alignment to
ductwork extending to the blower assembly
below.
– For a left side discharge, install the outlet
plate to the bottom of the plenum on the
left side. Install the cover plate to the
bottom of the right side. Reverse plates for
a right side discharge.
.
• Connect the plenum to the ductwork. A
transition is required to connect the 3-1/4"
x 10" duct to the 6" round inlet on the
blower.
• Tape to seal all joints.
Step
4
Connect
Electrical
• Use electrical cable and connectors that
conform to local codes (14 gauge min. is
recommended). Use a length to reach
between the vent and the blower/motor
location.
• Attach the wire box removed from the
blower conduit to the end of new wiring.
• Use wire nuts to secure the wire to the 3"
remaining wires with plug.
• Insert the plug into the mating plug on the
vent.
• Reinstall wire box with original screws.
• Install a junction box withing reach of the
blower conduit.
• Use a conduit fitting to secure conduit to
junction box. The red plastic anti-short
bushing should be secured to the end of the
conduit.
• Use wire nuts to connect wires.
19
Page 20
The blower and motor assembly can be
Base
Assembly
Outlet Pan
mounted on an outside wall. This kit provides
a means to mount the blower outside with a
protective cover.
JXBC57 Kit
For Outdoor Remote Blower Locations
Materials Required
(not supplied)
• Approved liquid tight service connections for use
between the wire compartment on the base and inside
the structure.
• 7 wire nuts or other approved connectors.
• Six 5/16" dia. fasteners compatible with the type of
material the base is being fastened to.
• 3-1/4" x 10" to 6" round transition.
• 3-1/4 x 10" duct, (or 6" round) sufficient length to reach
the outdoor installation location.
• Electrical cable and connectors, sufficient length to
connect the downdraft vent to the remote blower
location. 14-guage min. is recommended, must
conform to local codes.
Tools required:
• Pencil or chalk
• Measuring tape
• Drill with appropriate bits
• Phillips head screwdriver
• 1/4" Nut driver
• Wire nuts
• Safely glasses
Step
1
Check
Parts
Supplied
• Separate the cover from the base assembly
by removing 5 screws. Retain screws.
• Check to be sure all parts are present.
Cover
Junction Box
Package of screws
Cover Plate
Outlet Plate
Damper
20
Page 21
3"
Blower Wire Box
Blower Conduit
Loosen
Screw
10" Min
Above Ground
6-11/16"
16"
4-3/4"
6"
12"
Align
With Duct
Opening
On Outside
Wall
1-13/16"
12-15/16"
6 Holes
For 5/16
Fastners
6-1/8" Dia.
Step
2
Mark
Mounting
Location
JXBC57 Kit
For Outdoor Remote Blower Locations
• The base is designed to be mounted to studs
on 16" centers. Use the dimensions shown to
determine the location of the ducting and
wiring through the wall.
– Or, place the base against the exterior wall
and mark the 6 mounting locations, the 6"
duct location and the hole for the wiring.
Use pencil or chalk.
• The bottom of the base assembly must be
10" min. above the ground. There should be
no obstructions to the discharge from the
damper.
• Cut a 6-1/8" dia. hole in the vertical structure to accommodate a 6" round duct and
another hole for the wiring.
• Drill 6 pilot holes through the wall for the
5/16" fasteners.
Step
3
Prepare
the Vent
CAUTION:
do not damage electrical wiring or hidden utilities.
Check for interference with floor joists and stud walls. If
necessary, locate the base to provide a secure
installation.
• Place a 6" round duct through the hole
extending approximately 3" from the wall to
provide a proper seal with the blower.
Secure the duct to the building structure to
prevent it from being pushed back when the
blower is installed.
• Flatten the shipping box to use as a pad.
• Place the unit on its back onto the protective
pad.
• Remove the wire box on the plenum.
• Cut the blower leads approximately 3" from
the plug on the end of the vent.
• Remove the blower conduit by loosening the
screw on the fitting.
• Set aside the 3" wire leads with plug, wire
box and screws.
When cutting or drilling into a wall or ceiling,
21
Page 22
Step
3
(continued)
• Remove the 4 nuts holding the blower to the
mounting plate. One nut is hidden inside
the outlet. Remove blower.
• Remove the blower mounting plate.
• Remove 2 screws along the bottom of the
blower box which are visible once blower
plate is removed.
• Carefully, turn the unit over to access the
back side.
• Remove 4 screws along the top of the blower
box.
• Turn the unit over and remove the 4 screws
along the top.
• Remove the blower box.
• Retain all screws.
Important: Save any unused parts. If the
appliance is relocated at a later time, parts
may be needed.
JXBC57 Kit
For Outdoor Remote Blower Locations
Hidden
Screws
Blower
Blower
Mounting
Plate
Blower Box
• The downdraft plenum can discharge from
either the right or left side. Select the side
that provides the best alignment to
ductwork extending to the blower assembly.
– For a left side discharge, install the outlet
plate to the bottom of the plenum on the
left side. Install the cover plate to the
bottom of the right side. Reverse plates for
a right side discharge.
.
• A transition is required to connect the
3-1/4" x 10" duct to the 6" round inlet on
the blower.
• Tape to seal all joints.
Step
4
Connect
Blower
Wires
22
• Check that the red plastic anti-short bushing
is secured in the end of the conduit. Install
the blower conduit into the conduit connector on the junction box and tighten the screw.
• Install a liquid tight fitting in the hole of the
wire compartment on the base, sized to fit
wire being used.
• Run the electrical wiring from the downdraft
vent to the wire compartment.
• Attach the green ground leads from the wire
compartment, connecting one to the green
ground lead on the blower and the other to
the ground lead of the wiring from the
downdraft vent.
• Connect the neutral (white) and power lead
(black) from the blower to the leads from the
downdraft vent.
• Use wire nuts to connect wires.
Duct Adapter
Base
Assembly
Wires
to Vent
Strain
Relief
Downdraft
Outlet Cover
Blower
Conduit
Red AntiShort Bushing
Conduit
Connector
Wire
Compartment
Green Ground
Leads
Page 23
JXBC57 Kit
For Outdoor Remote Blower Locations
Step
5
Connect
Electrical
Step
6
Mount
Blower
• Use electrical cable and connectors that
conform to local codes (14 gauge min. is
recommended). Use a length to reach
between the vent and the blower/motor
location.
• Attach the wire box removed from the
blower conduit to the end of new wiring.
• Use wire nuts to secure the wire to the 3"
remaining wires with plug.
• Insert the plug into the mating plug on the
vent.
• Reinstall wire box with original screws.
• Mount the blower onto the mounting plate.
Secure with original nuts.
• Install damper to bottom of outlet with 4
screws.
Blower
Wire
Box
Plenum
Provided
Mounting
Screws
Wire Nuts
Wiring to Blower Junction Box
3-Wire
Connectors
• Place the cover over the the assembled kit
Step
and secure with 16 screws.
7
Finalize
Installation
23
Page 24
®
Monogram.
General Electric Company
Louisville, KY 40225
NOTE: While performing installations described in this book,
safety glasses or goggles should be worn.
For Monogram local service in your area, call
1-800-444-1845.
NOTE: Product improvement is a continuing endeavor at General
Electric. Therefore, materials, appearance and specifications are
subject to change without notice.
Pub. No. 49-80126
Dwg. No. 164D4290P084
(N.D. 397) 2/02
959-0344-000Rev.B
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.