Monitronics VISTA-15PMT, VISTA-20PMT Programming Manual

VISTA
VISTA----15PMT
VISTAVISTA VISTA
VISTA----20PMT
VISTAVISTA
15PMT
15PMT15PMT 20PMT
20PMT20PMT
Programming Guide
STAY
3
AWAY
2
OFF
1
BYPASS
6
TEST
ARMED
READY
5
MAX
4
CHIME
9
CODE
8
INSTANT
7
#
0
READY
ARMED
OFF
ON
READY
1
OFF
2
AWAY
3
STAY
4
MAX
5
TEST
6
BYPASS
7
INSTANT
8
CODE
9
CHIME
READY
0
#
This control is a certified SIA-compliant control that meets SIA specifications for False Alarm Reduction.
K5305-1MTPRV9 3/11 Rev. A - SIA Reference: MTV15P, MTV20P
TABLE OF CONTENTS
PROGRAMMING MODE COMMANDS.................................................................................................3
DATA FIELD PROGRAMMING FORM..................................................................................................4
CONFIGURABLE ZONE TYPES WORKSHEETS...............................................................................13
56 ZONE PROGRAMMING MENU MODE........................................................................................14
∗∗ ∗
58 EXPERT ZONE PROGRAMMING MODE.....................................................................................15
∗∗
WIRELESS KEY PROGRAMMING TEMPLATES...............................................................................16
57 FUNCTION KEY PROGRAMMING...............................................................................................16
∗∗
OUTPUT DEVICE PROGRAMMING GENERAL INFORMATION (*79/*80 Menu Mode).................... 17
79 RELAY/POWERLINE CARRIER DEVICE PROGRAMMING MENU MODE.................................17
∗∗ ∗
80 OUTPUT FUNCTION MENU MODE.............................................................................................18
∗∗ ∗
81 ZONE LIST MENU MODE............................................................................................................ 19
∗∗ ∗
82 ALPHA DESCRIPTOR MENUMODE............................................................................................20
∗∗
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)....................................................... 21
SETTING SCHEDULES ......................................................................................................................22
AVS SYSTEM ENABLE and QUICK PROGRAMMING COMMANDS................................................23
SETTING THE REAL-TIME CLOCK......................................................................................................2
29 COMMUNICATION DEVICE MENU MODE (Pass-Through Programming)...............................24
∗∗
ZONE TYPE DEFINITIONS.................................................................................................................25
UL NOTICES.......................................................................................................................................26
SIA QUICK REFERENCE GUIDE.......................................................................................................26
UPLOADING/DOWNLOADING VIA THE INTERNET..........................................................................23
WORKSHEET for SCHEDULES.........................................................................................................27
WORKSHEET for ∗∗∗56 ZONE PROGRAMMING..................................................................................28
WORKSHEET for ∗∗∗57 FUNCTION KEY PROGRAMMING.................................................................29
WORKSHEET for ∗∗∗79 RELAY/POWERLINE CARRIER DEVICE PROGRAMMING..........................29
WORKSHEET for ∗∗∗81 ZONE LIST PROGRAMMING.........................................................................29
WORKSHEET for ∗∗∗80 OUTPUT FUNCTION PROGRAMMING.......................................................... 30
TABLE OF DEVICE ADDRESSES......................................................................................................31
5800 SERIES TRANSMITTER INPUT LOOP IDENTIFICATION.........................................................31
SETTING THE REAL-TIME CLOCK
IMPORTANT: The Real-Time Clock must be set before the end of the installation. NOTE: All partitions must be disarmed before the date/time can be set.
1. Master Code + [#] + [6] [3]
2. Press [] when the time/date is displayed. A cursor appears under the first digit of the hour.
To move cursor ahead, press [∗]. To go back, press [#].
Enter the 2-digit hour setting.
Enter the 2-digit minute setting.
Press [1] for PM or [2] for AM.
Enter the last two digits of the current year.
Enter the 2-digit month setting.
Enter the 2-digit day setting.
3. To exit, press [] when cursor is at the last digit, or wait 30 seconds.
2
PROGRAMMING MODE COMMANDS
TO ENTER PROGRAMMING MODE (using an alpha keypad connected to the control): A. POW ER UP, then press [✱] and [#] at the same time, within 50 seconds of powering up (this method must be used if ✱98
was used to exit program mode). OR
B. Initially, key: Installer Code (4 + 1 + 1 + 2) plus 8 + 0 + 0.
PROGRAMMING MODE COMMANDS
Task Command/Explanation
Go to a Data Field Entering Data
Review a Data Field Press [#] + [Field Number]. Deleting an Entry
Initialize Downl o ad I D Press ✱✱✱96. Initializes download ID and subscriber account number. Reset Factory Defaults Press ✱✱✱97. Sets all data f i el ds to original factory default values. Zone Programming Press ✱✱✱56. Zone characteristic s, report codes, alpha descriptors, and serial numbers for 5800 RF trans. Function Key Programming Press ✱✱✱57. Unlabeled keypad keys (known as AB CD keys) for special functions Zone Programming (Expert Mode) Output Device Mapping Press ✱✱✱79. Assign module addresses and map individual relays/powerline carrier devices Output Programming Press ✱✱✱80. 4229 or 4204 Relay modules, Powerline Carrier devi ces, or on-board triggers Zone List Programming Press ✱✱✱81. Zone Lists for relay/powerline c arri er activation, chime zones, pager zones, etc. Alpha Programming Press ✱✱✱82. Zone alpha descriptors IP/GSM Programming Exit Program Mode with installer code lockout
Exit Program Mode Press ✱✱✱99. Exits programmi ng mode and Scheduling Mode Enter code + [#] + 64. Create schedules to automat e vari ous system functions.
Site-Initiated Download Installer code + [#] + 1 (perform while system is disarmed and in normal mode)
AVS QUICK PROGRAMMING COMMANDS (for AAV sessions using the AVS system)
For controls with the following firmware revision levels, these commands automatically configure the control for AVS operation. VISTA-15PMT = version 6.0 or higher; VISTA-20PMT = version 7.0 or higher
installer code + [#] + 03: enable AVS operation
installer code + [#] + 04: enable AVS operation and enable panel sounds on the AVST speaker
installer code + [#] + 05: remove all programming options set by [#] + 03 quick command
installer code + [#] + 06: remove all programming options set by [#] + 04 quick command
Refer to the AVS SYSTEM ENABLE and QUICK PROGRAMMING COMMANDS section for details on the specific options that are set with each command, depending on the control used. To select the AAV session communication path (phone line/communication device), see field 55 Dynamic Signaling Priority. To enable AAV operation, use 91 Options field (option 4).
SPECIAL MESSAGES
OC = OPEN CIRCUIT (no communication between Keypad and Control). EE or ENTRY ERROR = ERROR (invalid field number entered; re-enter valid field number).
After powering up, AC, dI (disabled) or “Busy Standby vx.x (firmware revision) Dl will be displayed after approximately 4 seconds. This will revert to a “Ready” message in approximately 1 minute, which allows PIRS, etc. to stabilize. You can bypass this delay by pressing [#] + [0].
NOTE for CANADIAN PANELS: Power up time is 2 minutes, and Contact ID report code 305 System Reset is sent if the [#] + [0] command is not performed before the 2 minutes expires.
If E4 or E8 appears, more zones than the expansion units can handle have been programmed. The display will clear after you correct the programming.
IMPORTANT: The Real-Time Clock must be set before the end of the installation. See procedure in the Setting the Real­Time Clock section on the previous page.
Press [∗∗∗] + [Field Number], foll o wed by the required entry.
When the desired fi el d number appears, simply make the required entry. When the last entry for a field is entered, the keypad beeps three times and automatically displays the next data f i el d i n sequence. If the number of digits that you need to enter in a data field is less than the maxim um digits available (for example, the phone number fields *41, *42), enter the desired data, then press [ ] to end the entry. The next data field number is displ ayed.
Data will be displayed for that field number. No changes will be accept ed in t his mode.
Press [∗∗∗] + [Field Number] + [ ∗∗∗∗]. (Applies only to fi el ds 40 thru *46, *94, and pager fields)
Press ✱✱✱58. Same options as *56 mode, but with fewer prompts. Intended for those familiar with this t ype of programming, otherwise *56 mode is recommended.
Press ∗∗∗29. For programming the IP/GSM options. Press ✱✱✱98. Exits programmi ng mode and
To reenter programming mode, the system must be powered down, then powered up. Then use method A above. See field *88 for other *98 Program mode lockout options.
above.
prevents
allows
re-entry by: Installer Code + 8 + 0 + 0.
re-entry by: Installer Code + 8 + 0 + 0 or method A
3
DATA FIELD PROGRAMMING FORM
Entries apply to both the VISTA-15PMT and VISTA-20PMT controls, except entries shown in dashed boxes apply only to the VISTA-20PMT (partition entries) and are not applicable to the VISTA-15PMT. Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults. SIA Features: False Alarm Reduction. Fields marked with heavy borders are related to SIA requirements and have entries or operation different than non SIA-compliant controls.
20 Dealer Installer Code
∗∗
4 digits, 0000–9999 This code can perform all system functions except cannot edit the central station reporting phone numbers (fields *41, *42). For security purposes, the factory default inst al l er code should be changed.
21 Quick Arm Enable
∗∗
0 = no; 1 = yes Part. 1 Part.2
If enabled, users can press the [#] followed by an arming key to arm the system instead of using a security code. The security code is always needed to di sarm the system.
22 RF Jam Option
∗∗
0 = no RF Jam detection 1 = send RF Jam report
If enabled, a report is sent i f the system detects an RF jamming signal.
UL: must be 1 if wireless devices are used
23 Quick (Forced) Bypass
∗∗
0 = no quick bypass
1 = allow quick bypass (code + [6] + [#] ) Zones bypassed by this function will be displayed after the
bypass is initiated.
24 RF House ID Code
∗∗
00 = disable wireless keypads Part. 1 Part. 2 Common
01–31 = using 5827, 5827BD or 5804BD keypad The House ID identifies receivers and wireless keypads . If a
5827 or 5827BD Wireless Keypad or 5804BD Transmitter is being used, a House ID code must be entered and the keypad set to the same House ID. You can assign RF house ID for each partition
26 Chime By Zone
∗∗
KP (Keypad) Sound Enables 1 2
Entry 1
0 = no “entry 1” keypad trouble sounds, AND no chime by
1 = Chime by Zone enabled (l 2 = Communicati on devi ce (LRR) Trouble sounding
4 = System Low Battery sounding enabl ed 7 = select all entry 1 options
Entry 2
0 = no “entry 2” keypad trouble sounds 1 = RF Supervision sounding enabled 2 = RF Low Battery sounding enabled 4 = RF Jam sounding enabled 7 = select all entry 2 options
For each entry, enter the sum of the desired options.
Example Entry 1: for Chim e by Zone and S ystem Low Battery sounding, enter 5. To enable all options, enter 7.
Keypad (KP) Trouble Sounding can be enabled/dis abl ed for the conditions list ed i n each entry.
27
Powerline Carrier Device (X–10)
∗∗
House Code
0 = A; 1 = B ; 2 = C; 3 = D; 4 = E; 5 = F; 6 = G; 7 = H; 8 = I;
9 = J; #10 = K; #11 = L; #12 = M; #13 = N; #14 = O; #15 = P
Powerline Carrier devices require a House ID, identified in
this field. Program Powerline Carrier devices in interactive modes 79, *80 and *81.
UL: not for fire or UL installations
The VISTA-15PMT and VISTA-20PMT are certified SIA-compliant controls that meet SIA specifications for
UL: must be “0” Part. 1 Part. 2
[00,00,00]
zone (keypad chimes on fault of any entry/exit or perimeter zone when chime mode i s on)
ist chime zones on zone
list 3 using *81 Menu mode)
enabled (for communic ation devices such as 7845GSM, 7845i-GSM, GSMV)
[4112] | | |
[1,1]
[0]
[0,0]
| | |
[6, 7]
[0]
28 Access Code for Phone Module [00]
∗∗
00 = disable;
1st digit: enter 1–9; 2nd digit: enter # + 11 for "✱", or # + 12 for "#".
You must assign a 2-digit access c ode for the 4286 Phone
Module, if used. Example: If desired acc ess code is 7, then 7 is the first entry, and [ #] + 11 (for ) is the second entry.
NOTE: A 0 in either digit disabl es the phone module. UL: must be “00” for UL Commercial Burg. installations
(Partition 1 only)
∗∗∗∗29 Enable IP/GSM – Communication Device Menu
Mode (pass-through programming)
This is a Menu Mode command, not a data field, for programming IP/GSM comm uni cation device options. See 29 Menu Mode section later in this document.
31 Single Alarm Sounding Per Zone
∗∗
0 = “alarm sounding per zone” will be the same as the
“number of reports in armed peri od” set in field *93 (1 if one report, 2 if 2 reports, unlimited for zones in zone list
UL: must be “0” SIA: Must be “0” if *93 Reports i n Armed Period is set
1 = one alarm sounding per zone If enabl ed, l i mits alarm sounding on the bell output to once
32 Fire Alarm Sounder Timeout
∗∗
1 = no sounder ti meout UL: must be “1” for fire install. This c ontrol complies with NFPA requirements for temporal
33 Alarm Sounder (Bell) Timeout
∗∗
This field determines whether the external sounder will shut
34 Exit Delay
∗∗
45 - 96 = 45 - 96 secs; 97 = 120 secs Part. 1 Part. 2 NOTE: Entries less than 45 will result in a 45-second delay. UL installations: For UL Commercial Burglar Alarm and UL
Common zones use part. 1 del ay. The system waits the time entered before arming entry/exit
7)
to “2” report pairs.
per zone per armed period.
0 = sounder stops at tim eout;
pulse sounding of fire notifi cation appliances. Temporal pulse sounding for a fire alarm consists of the following: 3 pulses – pause – 3 pulses – pause – 3 pul ses.
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min; UL: For residential fire alarm installation, must be set for
a minimum of 4 min (option 1); for UL Commercial Burglary installations, must be minimum 16 m i n (option 4)
off after time all ot ted, or continue until manually turned off.
Residential Burglar Alarm installations with line security, total exit time mus t not exceed 60 seconds.
zones. If the entry/exit door is l eft open after this time expires, an alarm will occur. Common zones us e same delay as partition 1.
– 4 –
[60,60] | |
[0]
[0]
[1]
|
35 Entry Delay #1
∗∗
30 - 96 = 30 - 96 seconds Part. 1 Part. 2
97 = 120 secs 98 = 180 secs 99 = 240 secs Upon entering, t he system must be disarmed before the time
entered expires, otherwise it sounds an alarm. NOTE: Ent ries less than 30 will result in a 30-second delay. Common zones use same delay as partition 1. For UL Resident i al Burglary Alarm installations, must be set
for a maximum of 30 s econds; entry delay plus dial delay
should not exceed 1 min. For UL Commercial Burglar Alarm,
total entry delay may not exceed 45 s econds.
36 Entry Delay #2
∗∗
See *35 Entry Delay 1 for entries. Part. 1 Part. 2
37 Audible Exit Warning
∗∗
Feature always enabled; field removed in t hi s control. Warning sound consists of slow continuous beeps until the
last 10 seconds, and then i t changes to fast beeps. Sound
ends when exit time expires.
38 Confirmation Of Arming Ding
∗∗
[30,30] | |
[30,30] | |
N/A
[0,0]
0 = no Part. 1 Part. 2
1 = yes (wired keypads and RF)
2 = yes, RF only (except 5827, 5827BD) Confirmation of arming is 1/2-sec external sounder “ding.” If 1 selected, ding occurs when closing report is sent if
open/close reporting is enabled, or at the end of Exit Delay.
If 2 selected, ding occurs upon reception of the wireless
arming comm and. UL: must be “1” for UL Commercial Burglar Alarm inst .
39 Power Up In Previous State
∗∗
Feature always enabled; field removed in this control. When the system powers up armed, an alarm will occur 1
minute after armi ng i f a zone is faulted. Note that if the
previous state was armed Away or Stay, the system ignores
sensor changes for 1 minute, which allows sensors such as
PIRs to stabilize.
N/A
DIALER PROGRAMMING (✱40 – ✱42)
Do not fill unused spaces. Ent er 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2-second pause. If fewer than the maximum digits entered, exit the field by pressing []. The next data field number is displayed.
40 PABX Access Code or
∗∗
| | | | |
Call Waiting Disable
Enter up to 6 digits. To clear entries, press 40. If call
waiting is used, enter call waiting di s able digits “ (#+11) 70”
plus “# + 13” (pause) and also set Call Waiting Disable
option in field *91. NOTES: 1. The call waiting di sable feature cannot be used on a
2. Using Call W ai ting Disable on a non-call waiting line
41 Primary Phone No.
∗∗
| | | | | | | | | | | | | | | | | | |
Can be changed by c orporat e installer code only. Enter up to
PABX line. will prevent successful communication to the central
station.
20 digits. To clear entries , press ∗41∗ .
42 Secondary Phone No.
∗∗
| | | | | | | | | | | | | | | | | | |
Can be changed by c orporat e installer code only. Enter up to
20 digits. To clear entries , press ∗42∗ .
NOTE: Entry of a number other than one specified will give unpredictable results. For fields *43 thru *46: Enter 0–9; #+11 for B; #+12 for C; #+13 for
D; #+14 for E; #+15 for F. Enter [ account number (for 3+1 dialer report ing form at) is us ed. Ent er 0 as the first di git of a 4-digit account number for Nos. 0000-0999. Exit field by pressing ✱ if only 3 digits are used. E .g., For Acct. B234, enter: #+11 2 3 4 .
43 Partition 1 Primary Acct. No.
∗∗
| | | / | | | | | Enter 4 or 10 digits, depending on selection in *48 Report
Format. See box above. To clear entries, press *43
44 Partition 1 Secondary Acct. No.
∗∗
| | | / | | | | | [FFFFFFFFFF] Enter 4 or 10 digits, depending on selection in *48 Report
Format. See box above. To clear entries, press *44*.
45 Partition 2 Primary Acct. No.
∗∗
| | | / | | | | | [FFFFFFFFFF] Enter 4 or 10 digits, depending on selection in *48 Report
Format. See box above. To clear entries, press *45*.
46 Partition 2 Secondary Acct. No.
∗∗
| | | / | | | | | [FFFFFFFFFF] Enter 4 or 10 digits, depending on selection in *48 Report
Format. See box above. To clear entries, press *46*.
47 Phone System Select [3]
∗∗
If Cent. Sta. 0=Pulse Dial; 1=Tone Dial; if Cent. Sta. 2 = Pulse Dial ; 3 = Tone Dial Selec t the type of phone service for the installation.
48 Report Format [7,7]
∗∗
Primary Secondary
0 = 3+1, 4+1 ADEMCO L/S STANDARD 1 = 3+1, 4+1 RADIONICS STANDARD 2 = 4+2 ADEMCO L/S STANDARD 3 = 4+2 RADIONICS STANDARD 5 = 10-digit ADEMCO CONTACT ID® REPORTING 6 = 4+2 ADEMCO EXPRESS 7 = 4-digit ADEMCO CONTACT ID® REPORTING 8 = 3+1, 4+1 ADEMCO L/S EXPANDED 9 = 3+1, 4+1 RADIONICS EXPANDED Select the form at for primary/secondary phone numbers
49 Split/Dual Reporting [0]
∗∗
0 = Standard/backup reporting only (all to primary) Primary Phone No. 2nd Phone No. 1 = Alarms, Restore, Cancel Others 2 = All except Open/ Cl ose, Test Open/Close, Test 3 = Alarms, Restore, Cancel All 4 = All except Open/ Cl ose, Test All 5 = All All
IS NOT IS on
a WATS line:
]
as the fourth digit if a 3-digi t
[FFFFFFFFFF]
on a WATS line:
*.
5
50 Burglary Dialer Delay [2,0]
∗∗
Delay Time Dela y Disable
Delay Time: 1 = 15 sec onds; 2 = 30 seconds; 3 = 45 seconds
Provides del ay of “BURGLARY ALARM” report to the central
station, which allows time for the subscriber to avoid a false
alarm transmission. This delay does not apply to zone type
24 alarms (silent burglary) or to 24-hour zone types 6, 7, and
8 (silent panic, audible alarm, auxiliary alarm), which are
always sent as soon as they oc cur.
Delay Disable:
0 = use delay set in entry 1 1 = dial delay disabled for zones listed in zone lis t 6 (use
UL: Dial del ay pl us entry delay must not exceed one minute;
53 SESCOA/Radionics Select [0]
∗∗
0 = Radionics (0-9, B-F); enter “0” for all non-SESCOA formats 1 = SESCOA (0-9 only reporting)
54 Dynamic Signaling Delay [4]
∗∗
Selec t delay from 0 to 225 secs, in 15-sec increments. 0 = no delay (both s i gnal s sent); 1 = 15 secs; 2 = 30 secs, etc. Intended for reporting via a communication device on the ECP
55 Dynamic Signaling Priority / [0]
∗∗
AAV Path Select
0 = Primary Dialer fi rs t / AAV via phone line 1 = Communication Device (LRR) first / AAV via
This f i el d selects the primary communication path for
† Reports i ntended for the secondary phone number are not
For Dynamic Signaling Priority:
Primary Dialer First selected (
For AAV Path Select:
IMPORTANT: If option “1” is selected, a 2-way voice (AAV)
zone list 6 to enter those zones that need dial delay to be disabled; these zones ignore the setting in entry 1)
use zone list 6 to disable di al del ay from appropriate zones,
if necessary.
bus (LRR). This field lets you select the time the panel should
wait for acknowledgment from t he first reporting destination
(see 55) before it attempt s to send a message to the second
destination. Delays c an be selected from 0 to 225 seconds, in
15-second increments. Thi s delay is per message. If 0 is
entered in this field, the control panel will send redundant
reports to both Primary Di al er and LRR.
UL: If using line security, m us t be “0; Reports will be sent to
both the dialer and the communication device.
communication device pat h (s ee AAV paragraph below)
reporting (dialer or comm uni cation device) of primary phone
number events
the communication pat h used for AAV sessions (phone line
or communicat i on devi ce path). Use 29 IP/GSM menu
mode to enable the communication device being used.
sent via the communication device.
Select the initial report i ng destination for messages:
If acknowledged before delay expires (see 54), then message will not be sent via LRR.
If not acknowledged before delay expires, mess age i s sent to both the Primary Phone No. and via LRR.
Communication Devi ce (LRR) First selected (
If acknowledged before delay expires, then message will not be sent to the primary di al er.
If not acknowledged before delay expires, mess age i s sent to both the Primary Phone No. and via LRR.
If using the UVS system or AVS system with non-ECP connection, option 0 m ust always be used.
If using the AVS system with ECP connec t i on, eit her option (0 or 1) may be used, but note the following:
device compatible with t he communication device path must be used (ex. GSMV communicator). When selected, AAV sessions always occur via the GSMV communicator, even i f reporting reverts to phone line backup due t o GSMV communicator path reporting failure.
For UL Commercial Burgl ary i nstallations that use a DACT and LRR, this field must be “0”.
(see 49 Split/Dual Reporting) and selects
0
):
∗∗∗∗56, ∗∗∗∗57, ∗∗∗∗58 Menu Modes
These are Menu Mode commands, not dat a f i el ds, for Zone Programming, Funct i on K ey Programming, and Expert Mode Zone Programming respec t i vel y. See respective sections later in this document.
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (∗∗∗59 thru ∗∗∗∗68, *70 thru ∗∗∗∗76, and ∗∗∗∗89): For 3+1 or 4+1 Standard Format: Enter a code in the
9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F. A 0 (
not
in the For Expanded or 4+2 Format: Enter codes in 2nd digits) for 1–9, 0, or B–F, as described above. A 0 ( message for that report . A 0 ( the report. For Ademco Contact ID® Reporting: Enter any digit (other than 0) in the are ignored). A 0 ( UL: Report codes are required in fields *61, *65, *71, *72, for UL Commercial Burglar Alarm installations. Report codes are required in fields *60, *62, *63, *64, *70, *73, *74, *75, *76, for UL Commerci al Burglar Alarm installations and required for Residential Fire Alarm installations
#+10) in the
second
box will result in automatic advance to the next field.
not
#+10) in the
first
box, to enable zone to report (entries in the
not
#+10) in the
first
box will disable a report. A 0 (
second
box will eliminate the expanded
not
#+10) in
first
box disables the report.
both
boxes will disable
SYSTEM STATUS REPORT CODES (
59 Exit Error Alarm Report Code [1]
∗∗
SIA NOTE : Always enabled. Sends both exit error and zone
alarm reports in the event of an exit error c ondition. Also see field *69.
After arming the system, entry/exit and interior zones
remaining open after exit delay expires cause an al arm sound at the keypad and external sounder (keypad als o displays “EXIT ALARM”), and entry delay begins . Disarming
1
):
before the end of the entry delay stops the alarm sounding and no message is sent to the central station. The keypad will display “CA” (fixed-word) or “ALARM CANCELED” (alpha display).
If the system is not disarmed before entry del ay expires, an
“EXIT ALARM” message and zone alarm mess age will be sent to the central station. The k eypad will display “EA” (fixed-word ) or “EXIT ALARM” (alpha display), and alarm sounding continues until t he system is disarmed (or timeout occurs).
An Exit Alarm c ondition will also result if a fault occurs in an
exit or interior zone within 2 minutes f ol l owing the end of the exit delay, and an “EXIT ALARM” message will be sent to the central station (als o see field *69 Recent Closing report). With Contact ID format, the message will contain the zone number and error code 374 (“ALARM–EXIT ERROR”).
60 Trouble Report Code [10] |
∗∗
Sent if a zone has a trouble condition.
See UL System Reporting Not e above *59.
61 Bypass Report Code [00] |
∗∗
Sent when a zone is manually bypassed.
See UL System Reporting Not e above *59.
62 AC Loss Report Code [10] |
∗∗
Tim i ng of this report is random with up to a 4-hour delay. If
AC restores before the report goes out , there is no “AC LOSS” report. See UL System Reporting Not e above *59.
63 Low Bat Report Code [10] |
∗∗
Sent when the s ys tem’s backup battery has a low-battery
condition. See UL System Reporting Note above *59
first
both
boxes (1st and
second
59–✱ 68)
box: 1–
not
#+10)
boxes
– 6 –
64 Test Report Code [10] |
∗∗
Use Scheduling mode to set periodic test reports, or use the
following key comm ands: installer code +[#] + [0] + 0 = t est report sent every 24 hours installer code +[#] + [0] + 1 = test report sent once per week installer code +[#] + [0] + 2 = t est report sent every 28 day Each mode sets schedule 32 (VISTA-20PMT) or schedule 08
(VISTA-15PMT) to the stat ed repeat option; first test report
sent 12 hours after com mand†.
See System Reporting UL Not e above *59. NOTE: Make sure the Real-Time Clock is set to the proper
time before entering the test report sc hedule command to
ensure that test reports are sent when expected. (see Setting
the Real-Time Clock section)
65 Open Report Code [0,0,0]
∗∗
Sent upon disarming the system in the selected partitions.
See UL System Reporting Not e above *59.
66 Arm Away/Stay Rpt Code
∗∗
Away Stay Away Stay Away Stay This option allows for independent programming of Away
NOTE: “OPEN” reports are not sent if the associated closing
67 RF Trans. Low Bat Report Code [10] |
∗∗
Sent when a transmitter low-battery condition exists. UL: must be enabled if wireless devices are used
68 Cancel Report Code [10] |
∗∗
Sent upon disarming the system after an alarm c ondi tion
69 Recent Closing Report Code [11] |
∗∗
SIA NOTE : Always enabled. Sends both recent closing and
Similar to the Exit Error condition described in field *59, but
If t he system is not disarmed within two minutes, the alarm
Part. 1 Part. 2 Common
and Stay reports for each partition, including the common
lobby.
report is not enabled.
SIA NOTE: Report enabled.
was reported.
zone alarm reports if fault occurs within 2 min. after exit time
expires. Also see field *59.
occurs if any burglary zone is f aul ted within two minutes
after the initial exit delay expires. Disarming the system
within the two minutes stops the alarm sound and displays
"ALARM CANCELED " or "CA" and f aul ted zone number. No
message is sent to the Central Monitoring Station.
sound continues and a “recent cl osing” and a “zone alarm”
message are sent to t he Central Monitoring Station (after
dial delay expires).
Part. 1 Part. 2 Common
RESTORE REPORT CODES (✱70 – ✱76)
70 Alarm Restore Rpt Code [0]
∗∗
NOTE: Alarm restore si gnal s indicate that respective alarm
zone(s) are no longer faulted. Alarm restore reports are sent
to the central station at bel l timeout (field *33), if the zone(s)
in alarm are actually restored to a non-faulted state at that
time. Otherwise, alarm restore report(s) for respective alarm
zones are sent when the system is disarmed.
If Reports Per Armed Period Per Zone (*93) is also
programmed, the syst em will report alarm and restore codes
as described above until the “Report s Per Armed Period”
count is reached. Disarming and rearming will reset the
“Reports Per Armed Period” count.
71 Trouble Restore Rpt Code [10] |
∗∗
Sent when a trouble in a zone is restored and code + OFF
performed. See UL System Reporting Note above *59.
72 Bypass Restore Rpt Code [00] |
∗∗
Sent when a zone that has been bypassed is unbypassed.
See UL System Reporting Not e above *59.
[0,0,0,0,0,0]
73 AC Restore Rpt Code [10] |
∗∗
Sent after AC power has been restored after an AC power
outage. See UL System Reporting Not e above *59.
74 Low Bat Restore Rpt Code [10] |
∗∗
Sent after a system low-battery condition is rest ored to
normal. See UL System Reporting Not e above *59.
75 RF Trans. Lo Bat Rst Rpt Code [10] |
∗∗
Sent when a transmitter’s low battery condition is restored
(i.e., new battery installed). UL: must be enabled if wireles s devices are used. See UL
System Reporting Note above *59.
76 Test Restore Rpt Code [10] |
∗∗
Sent when the Test mode is exited or upon timeout (4hrs).
See UL System Reporting Not e above *59.
OUTPUT AND SYSTEM SETUP (
77 Daylight Saving Time [3][11] |
∗∗
Start\End Month
0 = Disabled 1-12 = January-Sept ember (1 = Jan, 2 = Feb, etc) #+10 = October; #+11 = November; #+12 = December Enter the start and end month for daylight saving time, if
applicable to the region.
78 Daylight Saving Time [2][1] |
∗∗
Start\End Weekend
0 = disabled; 1 = first; 2 = second; 3 = third; 4 = fourth; 5 = last; 6 = next to last; 7 = third to last Enter the start and end weekend for daylight saving time, if
applicable to the region.
∗∗∗∗79, *80, *81, *82 Menu Modes
These are Menu Mode commands, not dat a fields, for Output Device Mapping, Output Programming, Zone List Programming, and Alpha Programming res pectively. See page 2 and their respective sections in the Ins t al l ation and Setup Guide for procedures.
84 Auto Stay Arm [MTV15P = 1; MTV20P = 1]
∗∗
0 = no 1 = partit i on 1 onl y; 2 = partition 2 only; 3 = both partitions If enabled, t he system will automatically change AWAY
mode to STAY m ode i f the entry/exit door is not opened and closed within the exit delay tim e after a user arms in AWAY mode from a wired keypad (non-RF device). An Opening report followed by an Armed Stay report is sent to the Central Station.
If t he door is opened and c l osed within the exit delay period,
the system remai ns in AWAY mode.
Any RF devic e that arms the system AWAY overrides this
feature and the system remains armed AWAY.
85 Cross Zone Timer [0]
∗∗
This option not for use i n UL i nstallations. (assi gn cross zones on zone list 4, using *81 Menu mode) 0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min 1 = 30 seconds 7 = 3 min #+13 = 10 min 2 = 45 seconds 8 = 4 min #+14 = 12 min 3 = 60 seconds 9 = 5 min #+15 = 15 min 4 = 90 seconds #+10 = 6 min 5 = 2 mi nutes #+11 = 7 min NOTE: Cross zoning takes effect only after Exit Delay expires. Sets the maximum amount of tim e i n which two cross zones
must be tripped in an arm ed system to send an alarm message to the Central Station. If only one cross zone is tripped during this tim e, a trouble message (CID code 380) for that zone is sent to the Central Station.
✱✱✱✱
✱✱✱✱
77 –
93)
7
86 Cancel Verify Keypad Display [1]
∗∗
0 = no; 1 = yes This f eat ure causes a “ALARM CANCELED” display on the
LCD keypad under the following conditions:
After the kissoff of the cancel message to t he Central
Station, indicating a successful transmission.
When an alarm is successfully canceled before the
Central Station received the Al arm message. E.g., if an alarm is incorrectl y t ri ggered and the user presses code + OFF before the dial delay time has expired, t he message will never go out to the CS. When the Cancel report i s not enabled and the system is
disarmed:
a. before dial er del ay expires (al arm report not sent) b. after di aler delay expires message “Alarm Canceled”
87 Misc. Fault Delay Time [0]
∗∗
(used with Confi gurabl e Zone Types “digit 6”) 0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min 1 = 30 seconds 7 = 3 min #+13 = 10 min 2 = 45 seconds 8 = 4 min #+14 = 12 min 3 = 60 seconds 9 = 5 min #+15 = 15 min 4 = 90 seconds #+10 = 6 min 5 = 2 mi nutes #+11 = 7 min
UL: may only be used on non-burglar alarm / non-fire alarm
zones when used in fire and/or UL burglar alarm installation Used with zones assigned to a configurable zone type with fault
delay on (configurable zone type digit “6”), and sets a zone
response time of 15 seconds to 15 min. It can be assigned to
zones with sensors that provide a troubl e i ndi cation when an oil
tank is low, or simil ar appl ications for critical condition
monitoring where non-alarm response is desired.
88 Program Mode Lockout Options [0]
∗∗
0 = standard *98 installer code lockout (reentry only by [∗] +
[#] within 50 seconds after power up)
1 = lockout [] + [#] reentry af ter *98 exit (reenter via
installer code or downloader only)
2 = lockout all local programming after *98 exit (reentry via
downloader only)
This table summ ari zes the Program Mode Lockout options:
Exit *88 Reentry By: Command Entry Installer Power-up† Downloader
*99 n/a yes yes yes *98 0 no yes yes *98 1 yes no yes *98 2 no no yes
† pressing [] + [#] within 50 seconds of power up
89 Event Log Full Report Code [00] |
∗∗
See box above field *59 for report code entries. If an E vent Loggi ng selection is made in field 90, a
message can be sent t o t he central station receiver when
the log is 80% full. If the log becomes full, new messages
overwrite the oldest messages in the log.
90 Event Log Enables [15]
∗∗
NOTE:System mes sages are logged when any non-zero
entry is made. To selec t al l options, enter #15. 0 = None 1 = Alarm/Alarm Restore 2 = Trouble/Trouble Restore 4 = Bypass /Bypass Restore 8 = Open/Clos e.
Restore”, and “Open/Close”, enter 9 (1 + 8);
This system can record various events in a history log
(VISTA-20PMT = 100 events; VISTA15PMT = 50 events). At
any time, the downloader operator can then upload t he log
and view or print out all or selected cat egories of the log, or
can clear the log. Event log c an also be viewed at an alpha
keypad. The display/printout at the central s tation will show
the date, time, event , and description of the occurrences.
Data Entry Example: To selec t Alarm/Alarm Restore” and
“Open/Close”, enter 9 (1+ 8); to sel ect all events, enter #15.
NOTE
entry is made.
message “Alarm Canceled” is displayed. is not displayed.
Example:
:
System messages are logged when any non-zero
To select “Alarm/Alarm
91 Option Selection / Remote [8, 0]
∗∗
Interactive Services (RIS) Enable 1 2 Entry 1: Options 0 = None 1 = Bell Supervision Processing 4 = AAV UL: must use ADEMCO UVCM module
8 = Exit Delay Restart/Reset †† UL: must be disabled #+12 = AAV and Exit Delay Restart/Reset SIA Guidelines: Exit Delay should be enabled.
Entry 2: Call Waiting Disable / RIS Enable 0 = call waiting not used 1 = call waiting disable digits (*70) entered in field *40;
(when selected, the system di al s the entry in field *40 only on alternate dial attem pts; this allows proper dialing in the event call waiting s ervi ce is later canceled by the user).
2 = RIS (Remote Interactive Services) enabled
3 = Call Waiting disable and RIS enabled IMPORTANT: AAV should not be used when Paging or
Alarm Reports are sent to a secondary number unless the monitoring zone option is us ed (which pauses calls). Otherwise, the call to the s econdary number by the communicator after t he alarm report will prevent the AAV from taking control of the t elephone line, and the AAV “Listen in” session cannot take place.
††“Exit Delay Res tart/reset” option allows use of the [] key
to restart the exit delay at any time when the system is armed STAY or INSTANT. This feature also enables automatic exit delay reset , which resets exit delay if the entry/exit door is re-opened and closed before exit delay time expires after arming AWAY. Automatic Exit Delay Reset occurs only once during an armed AWAY period.
Remote I n teracti ve Services (RIS) Enable: This option
enables enhanced Remote Interactive Services (RIS), if supported by the comm uni cation service in use.
92 Phone Line Monitor Enable [0,0]
∗∗
Entry 1: 1 2
0 = disabled, 1-15 = 1 min - 15 min
(#+10 = 10 min; #+11 = 11 min; #+12 = 12 min; #+13 = 13 Entry 2:
0 = Keypad dis pl ay when line i s faulted 1 = Keypad dis pl ay pl us keypad trouble sound 2 = Same as “1”, plus programmed output device STARTS.
NOTE: Output Devic e must either be programmed to be
min; #+14 = 14 min; #+15 = 15 min)
If either partition is armed, external sounder activates also.
STOPPED in field 80 or STOPPED by Code + # + 8 +
output number. Entry 1: Sets the length of time a phone line fault must remain after detected before the second digit option is activated.
Entry 2: Selects the desired phone line fault response. Option 2 may be used even if a relay unit or Powerline carrier device is not connec ted to the control. Programmed Output Device must either be programm ed to be STOPPED in field 80 or STOPPED by entry of [security code] + [#] + 8 + device number. Parti tion in 80 should be set to “0,” for STOP.
UL: Field *92 must be enabled for f ire al arm installations, UL commercial burgl ar al arm installations and UL residential burglar alarm installations.
If the control unit is used on a UL commercial burglar alarm system which requires 2 m ethods of remote communicati on, then the control unit’s DACT and the other method of signal transmission must monitor each ot her against communi cation failure and line fault. The fault must be received and annunciated within 200 seconds of i ts occurrence.
– 8 –
93 Reports In Armed Period [1,0]
∗∗
Per Zone (Swinger Suppression) Restrict Unlimited
Restrict Report Pairs: Report Pairs Reports
1 = 1 report pair; 2 = 2 report pai rs NOTE: I f restricting report pairs, *70 Alarm Restore Report
Code must be enabled.
Unlimited Reports Enable:
0 = restrict reports to the setting in entry 1 1 = unlimi ted reports for zones listed in zone list 7; (use
Selec t ion limits the number of alarm/alarm restore message
zone list 7 to enter those zones that require unlimited reporting; these zones ignore the s etting in entry 1)
pairs per zone sent to the CS in an armed period. Swinger suppression applies to burgl ary zones only.
DOWNLOAD INFORMATION (✱94, ✱95)
94 Download Phone No. [18006821690]
∗∗
| | | | | | | | | | | | | | | | | | |
Enter up t o 20 di gi ts, 0–9; #+11 for '✱'; #+12 for '#'; #+13 for
a 2-second pause. Do not fill unused spaces. If fewer than 20 digits, exit field by press i ng ✱. To clear entries from field, press ✱94✱.
UL: Up/downloading via phone line may be performed only if
a technician is at the site.
Up/downloading via the Internet has not been evaluated
95 Ring Count For Downloading [15]
∗∗
Refer to the chart below and program acc ordi ngly.
phone answer down- module machine loading Set field ∗∗∗95 to
yes no no 1-14 (not 0) yes yes no greater than rings set on
yes no yes 1-14 (not 0) yes yes yes 15 (bypasses answer
no no no 0 no yes no 0 no no yes 1-14 no yes yes 15
NOTE: If “15” is entered t o bypass an answering m achi ne, and a 4286 Phone Module is included in the system , you should note
the following: When calling in from an of f-premises phone, the user should make the initial call, al l ow 1 or 2 rings onl y, then hang up, then call again. The phone module will now seize the line, and 2 long tones sound, followed by the usual voice prompt f or the access code. If this procedure is not followed, phone module operation will not be possible.
96, ∗∗∗∗97 Initialize/Reset Defaults
∗∗
This is a comm and, not a data field.
98, *99 Exit Commands
∗∗
This is a comm and, not a data field.
by UL.
NOTE: Do not enter “0” if using 4286 Phone Module. 0 = Disable Station Initi at ed Download; 1–14 = number of rings (1–9, # +10 =10, # +11 =11, # +12 =12, # +13 =13, # +14 =14); 15 = answering machine defeat (# +15 =15).
answer machine (e.g., if ans. machine is 4 rings, s et this field to 5). This allows access to the phone module if the answer machine is off.
machine†)
PAGER OPTIONS (✱160- ✱172)
The system can send various reports to several pagers (MTV20P = up to 4; MTV15P = up to 2). To program pager reporting, do the following:
1. Enter the pager phone number(s), preface characters, and pager report options in data fields *160 - *171.
2. Enable Pager Delay, if desired, in field *172 (delays alarm reporting for ALL pagers).
3. Make sure appropriate user open/clos e pager report s are enabled (see Security Codes section in User Guide). Users that perform actions in partition 1 will, if enabled, attempt to report to all pagers enabled for open/close reporting i n partition 1. Users that perform actions in partiti on 2 will, if enabled, attempt to report to all pagers enabled for open/close report i ng i n part ition 2.
4. If using latchk ey pager report, define the latchkey report schedule using Scheduling mode (master code + [#] [6] [4] then select event type Latchkey report to be sent.
5. If using a function key to manually send a message to a pager, use *57 Function Key Menu mode to defi ne the key (function
6. If reporting zone alarms and t roubl es to a pager, use *81 Zone List menu mode to assign the zones associated with each pager (zone lists 9-12†).
† MTV15P s upports zone lists 9 and 10 only.
160 Pager 1 Phone No.
∗∗
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2- If entering fewer than 20 digits, exit by pressing [∗] + next
161 Pager 1 Characters
∗∗
| | | | | | | | | | | | | | |
Enter t he optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause. Up to 16 optional characters may be sent as a prefix to the 7-digit
system status code sent to Pager #1 (if used). Phone number in field *160 must have been entered. If f ewer than 16 c haracters, exit by pressing [] and next field number. To clear entries: press 161. The 16 characters may be composed of the following: PIN number, Subsc ri ber account number, character, # character, 2-s econd pause, special character(s) the user may decide to transmit
† Some paging system s require pause(s) before the prefix. The Pager format for the 7-digit status code is defined as follows: XXX-YYYY where: XXX = 3-digit eve nt code: 911 = Alarm, 811 = Trouble, 101 =
YYYY = 4-digit user or zone number (depending on type of event).
Display Example 1. 911–1004 Indicates an alarm (911) caused by a fault in zone 4 (0004) in part. 1. Display Example 2. 102–2005 Indicates the system is reporting a closing–system arming (102) by User 5 (0005) in partition 2.
162 Pager 1 Report Options [0,0,0]
∗∗
P1 P2 common
For each parti tion, select from the following options: 0 = no reports sent 1 = Opens/ closes all users enabled for paging† 4 = All al arms and troubles 5 = All al arms / troubles, and opens/closes for all users 12 = Alarms / troubles for zones entered in zone list 9 13 = Alarms / troubles for zones entered in zone list 9, and
For each parti tion, select from the listed options . † For users enabl ed for paging. Reports to pager only when
03
). System must be armed for the
01
sec pause.
field number. To clear entri es , press 160
Opening (disarm), 102 = Closing (arm AWAY) The first digit indicat es partition (0 = system, 1 = part 1, 2 =
part 2, 3 = common), followed by the 3-digit user or zone number.
opens/closes for all users
arming (close)/dis arming (open) from a keypad using a security code; auto-arm i ng/disarming, arming with assigned button, and keyswitch arm i ng do not send pager messages.
).
– 9 –
163 Pager 2 Phone No.
∗∗
| | | | | | | | | | | | | | | | | | |
Enter up t o 20 di gi t s. 0–9; #+11 = 'Q'; #+12 = '#'; #+13 = 2-
sec pause.
If entering fewer than 20 digits, exit by pressing [∗] + next
field number. To clear entri es , press 163.
164 Pager 2 Characters
∗∗
| | | | | | | | | | | | | | |
Enter t he optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
See field 161 for explanation. If fewer than 16 characters, exit by pressing [] and next field number. To clear entries, press 164.
165 Pager 2 Report Options [0,0,0]
∗∗
P1 P2 common
See field *162 for reporting options. Select for each partition
(use zone list 10 if using opt i ons 12 or 13).
166 Pager 3 Phone No.
∗∗
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-
sec pause.
If entering fewer than 20 digits, exit by pressing [∗] + next
field number. To clear entri es , press 166.
167 Pager 3 Characters
∗∗
| | | | | | | | | | | | | | |
Enter t he optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause. See field ∗161 for explanation. If fewer than 16 characters,
exit by pressing [] and next field number. To clear entries, press 167.
168 Pager 3 Report Options [0,0,0]
∗∗
P1 P2 common
See field *162 for reporting options. Select for each partition
(use zone list 11 if using opt i ons 12 or 13).
169 Pager 4 Phone No.
∗∗
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-
sec pause.
If entering fewer than 20 digits, exit by pressing [∗] + next
field number. To clear entri es , press 169.
170 Pager 4 Characters
∗∗
| | | | | | | | | | | | | | | Enter t he optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
See field ∗161 for explanation. If fewer than 16 characters,
exit by pressing [] and next field number. To clear entries, press 170∗.
171 Pager 4 Report Options [0,0,0]
∗∗
P1 P2 common
See field *162 for reporting options. Select for each partition
(use zone list 12 if using opt i ons 12 or 13).
172 Pager Delay Option For Alarms [3]
∗∗
0 = none; 1 = 1 minute; 2 = 2 minutes; 3 = 3 minutes This delay is for ALL pagers in the system.
This field determines the delay of alarm reports to the pager. This gives the Central Station enough time to verify the alarm report it received before t he di al er at tempts to dial the pager.
MISCELLANEOUS SYSTEM FIELDS (*174-*181)
174 Clean Me Reporting Options [0]
∗∗
(for ES L smoke detectors) 0 = disable; 1 = Clean Me signal reports;
NOTE: If Clean Me is enabled, you mus t enter “3” in field
56 programming for zone 1 respons e time. This is a maintenance feature for ESL 2-wire smoke detectors on Zone 1. If used, this option limits the number of smoke detectors t o a maximum of 10, rather than 16. To enable the “clean me” feature, a time response setting of “3” (1.2 seconds) must be entered in 56 Zone Programming for zone 1.
177 Device Duration 1, 2 [0] [0]
∗∗
(used in *80 Menu mode-Device Actions 5/6) 1 2 0 = 15 seconds 6 = 2-1/2 min #+11 = 7 min 1 = 30 seconds 7 = 3 min #+12 = 8 min 2 = 45 seconds 8 = 4 min #+13 = 10 min 3 = 60 seconds 9 = 5 min #+14 = 12 min 4 = 90 seconds #+10 = 6 min #+15 = 15 min 5 = 2 mi nutes
These entries set the duration for output action options 5 (duration 1) and 6 (duration 2) programmed in 80 Output Function Programming.
181 50/60 Hertz AC Operation [0]
∗∗
0 = 60 Hz; 1 = 50 Hz
Select the type of AC power applied to the c ontrol (option is used for Real-Time Clock synchronization)
CONFIGURABLE ZONE TYPE OPTIONS (*182-*185)
(see Configurable Zone Type Work sheet on page 13)
The system al l ows you t o define custom zone types (MTV20P
supports 4 [types 90-93]; MTV15P supports 2 [types 90, 91]), based on the options described below.
All confi gurabl e zone t ypes can be programmed via the downloader.
Zone types 90-91 can also be programm ed from a keypad using data fields *182-*185.
IMPORTANT: Be careful when selecting combinations of opti ons
for configurable zone types. Cont radi ctory options can cause unpredictable results.
Configurable Zone Type Options Auto Restore (entry 2): Faults on zones set for this option are
cleared; restore messages sent upon restoral of faults. Vent Zone (entry 2): Zones set for this opti on are ignored if faulted
when arming the system, but are protected if the zone is later restored (e.g., an open window can be ignored when arming, but if the window is later closed, it will be protected; opening the window again causes an alarm.)
Bypass Disarmed (entry 4): Zones set for this option c an be bypassed only while the system is disarmed.
Bypass Armed (entry 4): Zones set for thi s option can be bypassed when the system is armed.
Dial Delay (entry 6): Alarms on zones set for this option participate in dial delay central stati on reporting, if system dial delay enabled in field *50.
Fault Delay (entry 6): Faults on zones set for this option are delayed by the time set in field *87. Do not use this option if using entry/exit delay for this zone type.
Faults Display (entry 7): Selects how faults on zones set for thi s zone type are displayed.
Power Reset/Verification (entry 7): S el ects whether the system resets power (when user enters code + OFF), and whether the system perform s alarm verification (see description f or zone type 16 in Zone Type Definitions section) when a fault occurs on t hese zones.
Us e Entry Delay (entry 8): S elects whether to use the system’s entry delay times.
Use Exit Delay (entry 8): Selects whether to use the syst em’s exit delay time.
Interior Type (entry 8): Zones set for this option are treated same as standard zone type 4 (bypasses when arm ed S T AY, faults displayed).
Alarm Sounds (entry 9): Selects the type of alarm s sound for zones set for this zone t ype.
10
Configurable Zone Type Options (continued) Bell Timeout (entry 9): Alarm sounding on zones set for thi s option
remain for the duration set i n fields *32 / *33. Fire Zone (entry 9): Zones set for this opt ion respond in the same
manner as if programmed for zone type 9. Do not set fire zones to respond as a “fault” in entries 1-6.
Trouble Sounds (entry 10): Selects the type of trouble sounds for zones set for this zone type (peri odi c beeps = once every 30 seconds; trouble beeps = rapid beeping).
Chime Enable (entry 10): Zones set f or this option cause a chime when Chime mode is on.
182 Configurable Zone Type 90
∗∗
1 2 3 4 5 6 7 8 9 10
Enter the appropriate value for each entry, 1-10, based on the charts provided on the next page. Each entry is the sum of the values of its selected options
(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
To calculate the value for each entry, add the values of the selected options in each of the entry’s columns shown in the respective chart (one option per c ol umn). For example, to program entry 2 for “alarm response to short,” “auto restore on,” but not a “vent zone,” enter 5 (“1” for alarm short + “4” for auto restore-yes + “0” for vent zone-no).
UL: Do not configure zones as a fi re al arm or UL burglar alarm zone.
183 Zone Type 90 Report Codes
∗∗
90 ALARM ID: XXX TROUBLE ID: XXX
Enter the desired 3-digit Contact ID® report codes for alarms and troubles occ urri ng on zones assigned to this zone type. Enter the codes sequent i ally (all 6 digits). When entering digits, [#] moves cursor back, [] moves forward. Press [] when done to continue. NOTE: Zone alarm report codes and trouble report code (60) and relevant restore codes must be enabled in order to report configurable zone type codes. Important Notice on Report Codes: To avoid confusion at the central station, i t is recommended that existing Contact ID® codes be used with configurable zone t ypes whenever possible. Check with the c entral station for a complete list of Contact ID® report codes. If none of the codes are suitable, choose a code in the reserved range of 750-789 and make sure to define the code with your central station.
184 Configurable Zone Type 91
∗∗
1 2 3 4 5 6 7 8 9 10
Enter the appropriate value for each ent ry, 1-10, based on the charts provided on the next page. Eac h ent ry i s the sum of the values of its s el ected options
(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14,
#+15=15).
See ∗182 for entries.
UL: Do not configure zones as a fi re al arm or UL burglar alarm zone.
185 Zone Type 91 Report Codes
∗∗
91 ALARM ID: XXX TROUBLE ID: XXX
See ∗183 for entries.
Press [] when done to continue.
∗189 AUI Device Enable [0,0,0,0]
∗∗
(for Touchscreen Keypads) AUI 1 AUI 2 AUI 3 AUI 4
System supports t ouchscreen style keypads (e.g., Symphony Advanced User Interface, and 6270 Touchscreen Keypad).
AUI Compatibility Note: To ensure proper AUI device operation, use AUI devices with the following rev levels: 6270 series use version 1.0.9 or higher; 8132/8142 (Symphony) series use vers i on 1.1.175 or higher.
Touchscreen device 1: Set device address to 1 Touchscreen device 2: Set device address to 2 Touchscreen device 3: Set device address to 5 (V20PMT) Touchscreen device 4: Set device address to 6 (V20PMT)
Note for Remote Services Device Address: Using an AUI device address for Remot e S ervi ces provides enhanced remote services f eat ures, but an actual AUI device is not used. If no AUI addresses are available (all four AUIs are being used), choose an available st andard keypad address and use the appropriate keypad address fi el d 190 - 196 to select the Remote Services operating partition (some remote access features will be unavailable).
NOTE: Use of touchscreen style keypads does not affect the number of standard keypads supported.
VISTA-20PMT: Up to four AUI devices.
To enable a touchscreen keypad, enter t he opt ion corresponding to each touchscreen’s home partition.
For Touchscreen device usage 0 = disable 1 = partition 1 2 = partition 2 3 = partition 3 (comm on)
For Remote Services device usage 5 = part. 1 (auto-stay arm dis abl ed) 6 = part. 2 (auto-stay arm dis abl ed) 7 = part. 3 (common; auto-stay arm disabled)
VISTA-15PMT: Up to two AUI devices. Select the desired
option. For Touchscreen device usage 0 = disable 1 = enable
For Remote Services device usage 5 = auto-stay arm disabled
Note for Remote Services Devices: If us i ng t he Remote Services feature of the communication device, select an option 5-7, depending on the partition t he Remote Services device is associat ed with (t hese options automatically disable auto-stay arming when the s ys tem is armed from the respective Remote Services device). Refer to the communicati on devi ce’s installation instructions for details on enabling the Remote Services feature.
KEYPAD OPTIONS *190-*196
To enable keypads:
1. Set desired address at keypad (refer to keypad’s instructions for setting the address).
2. Use data fields *190-*196 to enable k eypad addresses, assign a partition, enable sound options i n field.
3. Use fields *197, *198, and *199 to t urn on partition number display, exit time i nterval display, and select fail display mode.
4. Set keypad-related data fields as appropriate: *21 Quick Arm Enable, *23 Forced Bypass, *84 Aut o S T A Y Arm
NOTES: 1. Opti ons for keypad address 16 are set by the factory
2. Each keypad must be assigned a unique address.
and cannot be changed.) Keypads programmed with the same address will give
unpredictable results.
11
KEYPAD OPTIONS
190 Keypad 2 Device Address 17 [0] [0]
∗∗
VISTA-20PMT V20P Partition/ Sound
Enter the desi red opt i on for the keypad’s home partition.
Sound: E nt er the desired sound option for this keypad. 0 = no suppression 1 = suppress arm/disarm and E/E beeps 2 = Suppress chi me beeps only 3 = suppress arm/disarm, E/E, and chime beeps
Enable:
Sound: E nt er the desired sound option for this keypad. 0 = no suppression 1 = suppress arm/ di sarm and E/E beeps 2 = Suppress chime beeps only 3 = suppress arm/ di sarm, E/E, and chime beeps
Enable
191 Keypad 3 Device Address 18 [0] [0]
∗∗
See field 190 for entries.
192 Keypad 4 Device Address 19 [0] [0]
∗∗
See field 190 for entries.
193 Keypad 5 Device Address 20 [0] [0]
∗∗
See field 190 for entries.
194 Keypad 6 Device Address 21 [0] [0]
∗∗
See field 190 for entries.
195 Keypad 7 Device Address 22 [0] [0]
∗∗
See field 190 for entries.
196 Keypad 8 Device Address 23 [0] [0]
∗∗
See field 190 for entries.
Partition: V15P Enable
For Touchscreen device usage 0 = disable 1 = partition 1 2 = part. 2 3 = part. 3 (common)
For Remote Services device usage 5 = part. 1 (auto-stay arm dis abl ed) 6 = part. 2 (auto-stay arm dis abl ed) 7 = part. 3 (common; auto-stay arm disabled)
VISTA-15PMT
For Touchscreen device usage 0 = disable 1 = enable
For Remote Services device usage 5 = auto-stay arm disabled
Note for Remote Services Devices: If us i ng t he Remote Services feature of the communication device, select an option 5-7 (option 5 for VISTA-15P MT), dependi ng on t he partition the Remote S ervi ces device is associated with (these options automatically disable auto-stay arming when the system is arm ed from the respective Remote Services device). Refer to the communication device’s installation instructions for details on enabling the Remote Services feature.
Partition Sound
∗197 Exit Time Display Interval [2]
∗∗
0 = no display; 1-5 = seconds between display refresh
If enabled, keypads display the exit time remaining after arming the system , updated at the interval selected (i.e. if the exit delay is 30 seconds and “2” is s elected in this field, the keypad display refreshes every 2 seconds, displaying 30, 28, 26, 24, etc.). An interval greater than “1” may be necessary for some older keypads to allow users time to enter key presses between display updates.
NOTE: If enabled and using only 2-digit fixed-word keypads
(e.g., 6150RF), do not set exit delay time greater than 96 seconds. Using a longer delay t i me may cause end-user confusion because 2-digit di splay keypads cannot display times greater than “99.” If longer exit time is required by the installation, it i s recommended that the Exit Time Display option be disabled (“0”).
TOUCH SCREE N DE VICE NOTE: If using more than one
touch screen device (e.g. , 6270, Symphony) with the system, leave fiel d *197 Exit Time Display Interval set to the default value “0.” The 6270 automat i cally displays remaining exit time in one-second increments.
∗198 Display Partition Number [1]
∗∗
(VIS TA-20PMT; for Alpha Display Keypads) 0 = no; 1 = yes (partition no. appears on Alpha Display)
If selected, the part i tion number is displayed in the upper-left corner of the display. This is useful when using the GOTO partition function.
199 ECP Fail Display [0]
∗∗
0 = 3-digit di splay (“1” + device address) 1 = 2-digit fixed-display as “91”
Select “0” if using Alpha keypads and/or 3-digit Fixed-Word Display keypads. ECP faults will display “1” plus the device address (00-15) of device causing the fault (e.g., faults on device 07 display as “107”). Select “1” if using 2-digi t Fi xed-Word Display keypads (e.g., certain 6128 series keypads). If selected, ECP faults for all devices will display as “91” on 2-digit displays, and “191” on 3-digit or Alpha keypads.
12
CONFIGURABLE ZONE TYPES WORKSHEETS
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182­*185. Configurable zone types 92 and 93 (VISTA-20PMT only) can only be programmed using the downloader software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types.
ENTRY 1 (See note 5 for RF zones) ENTRY 2 (See note 5 for RF zones)
Response when system disarmed and zone is:
Intact EOL
RF zone normal
0 = normal 1 = alarm 2 = trouble 3 = fault
Open
RF zone N/A
0 = normal 4 = alarm 8 = trouble 12 = fault
Shorted
RF zn off-normal
0 = normal 1 = alarm 2 = trouble 3 = fault see note 6
Entry 1 = EOL + Open Entry 2 = Short + auto restore + vent zone
Auto
Restore
0 = no 4 = yes
Vent Zone
0 = no 8 = yes
ENTRY 3 (See note 5 for RF zones) ENTRY 4 (See note 5 for RF zones)
Response when armed STAY and zone is:
Intact EOL
RF zone normal
0 = normal 1 = alarm 2 = trouble 3 = fault
RF zone N/A
0 = normal 4 = alarm 8 = trouble 12 = fault
Open
Shorted
RF zn off-normal
0 = normal 1 = alarm 2 = trouble 3 = fault see note 6
Entry 3 = EOL + Open Entry 4 = Short + byp. disarmed + byp. armed
Byp. when
disarmed
0 = no 4 = yes
Byp. when
armed
0 = no 8 = yes
ENTRY 5 (See note 5 for RF zones) ENTRY 6 (See note 5 for RF zones)
Response when armed AWAY and zone is:
Intact EOL
RF zone normal
0 = normal 1 = alarm 2 = trouble 3 = fault
RF zone N/A
0 = normal 4 = alarm 8 = trouble 12 = fault
Open
Shorted
RF zn off-normal
0 = normal 1 = alarm 2 = trouble 3 = fault see note 6
Entry 5 = EOL + Open Entry 6 = Short + dial delay + fault delay
Dial Delay
(see field *50)
0 = no 4 = use delay
Fault Delay
(see field *87)
0 = no 8 = use delay
see note 1
ENTRY 7 ENTRY 8
Display Faults Power Reset/
Verification
0 = show alarms
when armed & disarmed
1 = don’t show
alarms when armed
alarms, trbles, faults when disarmed)
0 = no 4 = power reset
12 = verification (see zone
(show
after fault
(by code + OFF)
type 16)
3 = never show
any alarms,
trbles, faults Entry 7 = fault display + power reset/verification
Use Entry
Delay 1/2
0 = no 1 = delay 1 2 = delay 2
Use Exit
Delay
0 = no 4 = use exit
delay
Respond as
Interior Type
0 = no 8 = yes
see note 2
Entry 8 = entry delay 1/entry delay 2 + exit delay + interior zone type
ENTRY 9 ENTRY 10
Alarm Sounds Use Bell
Timeout
0 = none 1 = steady
keypad 2 = steady bell
and keypad
0 = no 4 = yes
see fields *32, *33
3 = pulsing bell
and keypad Entry 9 = alarm sounds + bell t i meout + fire zone Entry 10 = trouble sounds + c hi me
Respond as
Fire Zone
0 = no 8 = yes
see zone type 09; see note 4
Trouble Sounds
0 = none 1 = periodic
beep
2 = trouble
beeps
Chime when
Chime Mode On
0 = no 4 = yes
Entries for Fields *182 and *184
Entry Zone Type 90 Zone Type 91 (field *182) (fi eld *184)
1 2 3 4 5 6 7 8 9 10
To calculate the value for each entry: Simply add the values of the selected options in each of the entry’s columns (one option per column). For example, to program Entry 2 for “alarm response to short , ” “auto restore on,” but not a “vent zone,” enter 5 (“1” for alarm short + “4” for auto restore yes + “0” f or vent zone no).
EOL
Zone Conditions Represented
NOTES:
1. Do not us e the “fault delay” option with a configurable zone type if it is set for an entry or exit delay, otherwise unpredictable results may occur.
2. To create an i nterior type zone, select “respond as interior zone type” (entry 8, interior type = yes), and set zone response to “fault” in entries 3-4 to ensure fault displays; do not set as “normal,” “alarm,” or “trouble.”
3. Do not s et fire zones to respond as a “fault” (entries 1-6), otherwise faults will not display unless the [ ] key is pressed.
4. 4219/4229 modules must use EOLRs or unpredictable results may occur.
5. RF Zones: The “open” option in entries 1, 3, and 5 is not applicable for RF zones . Use the “intact EOL” opti on for normal RF zone conditions and “shorted” for of f­normal RF zone conditions.
6. a. Zone-Doubling/Doubl e-B al anced: A
short on either zone of a zone-doubled pair or on a double-balanced zone causes a tamper condition.
b. For double-balanced zones, this entry
must be “0.”
c. For zone-doubled zones, both zones
of the doubled pair must be as s igned the same response to a s hort .
OPEN SHORTEDINTACT
in Entries 1-6
ZONE-003-V0
– 13 –
56 ZONE PROGRAMMING MENU MODE
∗∗
(press *56 while in Program mode) The Zone Programming Worksheet is on page 28.
Zones and Partitions
Each protection zone needs to be programmed with various attributes using *56 Zone Programming mode or ✱58 Expert
Programming Mode. Using this mode, enter the zone number to be programmed and make appropriate entries at the prompts. Finally, Confirm the serial number of wireless transmitter zones.
The VISTA-20PMT system can control two independent areas of protection (known as partitions) for use by independent
users, if desired, by simply assigning zones to one or the other partition during zone programming. The VISTA-20PMT, by default, automatically distributes users between the two partitions. The master user can change the user number distributions.
Zones can also be assigned to a common partition, which is an area shared by users of both partitions (such as a lobby in a
building). This allows either partition to arm, while leaving the common partition disarmed for access into the other partition. The following describes the functioning of the VISTA-20PMT common partition:
• The common zone sounds and reports alarms only when both partitions are armed. If only one partition is armed, the system ignores faults on the common zone.
• Either partition may arm its system if the common zone is faulted, but once armed, the other partition will not be able to arm unless the common zone is first bypassed or the fault is corrected.
• Faults on the common zone are displayed on common zone keypads, and will also appear on another partition’s keypad when that partition is armed.
• Either partition can clear and restore the common zone after an alarm.
For each of the following prompts, make the desired entry, followed by the [] key to accept the entry.
SET TO CONFIRM?
0 = no (default) 1 = yes (See XMIT TO CONFIRM prompt later in this section.)
We recommend that you confirm the programming of every transmitter.
This display appears upon entry into this mode. If 1 (Yes) is entered, you will be prompted to confirm each transmitter aft er entering the serial and loop numbers (at the “XMIT TO CONFIRM” prompt later).
ENTER ZN NUM.
VISTA-20PMT:
wired 01-08 (and 09-48†) wireless 09-48; RF button zones 49-64
VISTA-15PMT:
wired 01-06 (and 07-22†) wireless 09-34; RF button zones 49-56
Both Controls:
91 = addr. device report enable 92 = duress report enable 95, 96, 99 =emerg. zones
To quit, enter 00 to quit (returns to data field m ode). Enter the zone number that you wish t o program. Enter a report code for zone 91 to enable addressable device reporting. Enter a report code for zone 92 to enable duress reporting. 95, 96, 99 are emergency (panic) k ey zones.
† if zone expanders are used.
SUMMARY SCREEN:
System displays a summary of the entered zone’s current programming. Press [] to continue. “IN: L” appears for wireless zones and indi cates input type and loop. “IN: AD” appears for hardwire expansion zones (AW) and indicates the module’ s address (AD), which is based on the zone number. “HW: RT” appears for hardwire zones and indi cates configuration (EOL, NO, NC, zone doubling, double-balanc ed) and response time selection.
ZONE TYPE
Each zone must be assigned to a zone type, which defines the way in which the system responds t o faults in that zone. Enter the Zone Type code from the list bel ow:
Note: If 00 is entered, Delete Zone ? will be displayed.
00 = Not used 07 = 24-Hr Audible 20 = Arm–STAY* 01 = Entry/exit #1 08 = 24-Hr Aux 21 = Arm–AWAY* 02 = Entry/exit #2 09 = Fire 22 = Disarm* 03 = Perimeter 10 = Interior w/Delay 04 = Interior Follower 12 = Monitor Zone 24 = Silent Burglary 05 = Trouble Day/Alarm Night 14 = Carbon Monoxide 77 = Keyswitch 06 = 24-Hr Silent 15 = Medical** 81 = AAV Monitor 16 = Fire w/Verify Zone *5800 button-type transmitters only 90-91 = Configurable **Zone type 15 is similar to zone type 08 (keypad alarm sounding, no bell output), except that Contact ID code 100 is sent to the central station. UL: Zone type 15 may not be used in UL installations.
23 = No Alarm Resp
PARTITION
1, 2, or 3-common (VISTA-20PMT)
Enter the Partition number for this zone.
REPORT CODE
1-9, 10 for 0, 11 for B, 12 for C, 13 for D, 14 for E, 15 for F For Contact ID®, enter any non-zero entry as t he first digit to enable reporting for this zone. To disable the report code for this zone, enter 00. Enter the report code for this zone, which consists of 2 hexadecimal digits, each in turn consisting of 2 numerical digits. For example, f or a report code of “10,” enter
01
and 00
HARDWIRE TYPE
Appears only for zones 02-08. Zone 1 is aut omatically set for EOL operation. Enter the desired hardwire type: 0 = EOL 3 = zone doubling (ZD)† 1 = NC 4 = double-balanced (DB )† 2 = NO († VISTA-20PMT)
RESPONSE TIME
For hardwired zones 01-08. Enter the desired response ti me for this zone: 0 = 10mSec 2 = 700mSec 1 = 350mSec 3 = 1.2 secs (see field ∗174)
NOTE: If zone doubling is being used, the response time selected for zones 02-08 automatically appl i es to each zone’s associated doubled zone.
INPUT TYPE
Skipped for zones 2-8, and for zones 10-16 i f zone-doubling enabled. Enter the input type: 2 = AW (Aux wired zone) 4 = UR (unsupervised RF) 3 = RF (supervised RF) 5 = BR (unsupervised button type)
NOTE: To change the input type of a previousl y programmed wireless device to a wired zone, you must fi rst delete the transmitter’s seri al
number. All of the RF transm i t ters have one or more unique factory-assigned input (loop) ID codes. Each of the inputs requires its own programming zone
(e.g., a 5804's four inputs requi re four programming zones).
RF Transmitters can be enrol l ed as one of the following types:
Type Description
RF
(Supervised RF)
UR
(Unsupervised RF)
BR
(Unsupervised
Button RF)
NOTE: For the built-in hardwired zones, the Input Device type is
automatically dis pl ayed as HW and cannot be edited.
Sends periodic check-in signals, as well as fault, restore, and low-battery signals. The t rans. must stay within receiver's range. Sends all the signals t hat the “RF” type does, but the control does not supervise the check-in signals. The transmitter may therefore be carried off-premises. Sends only fault signals. It will not send a low­battery signal until it i s activated. The transmitter may be carried off-prem i ses.
14
INPUT S/N
Enroll the transmitter’s serial number and loop number as follows:
1. a. Transmit two open/cl os e sequences (for button-type transmitters, press and release the button twice, waiting about 4 seconds before pressing t he button the second time).
OR b. Manually enter the 7-digi t serial number printed on the label
of the transmitt er. P ress the [] key to move to the “L” position, then enter the loop number.
Use the [A] (Advance) and [B] (Back) keys to move the
cursor forward and back within the screen. P ressing the [C] (Copy) key will insert the previously enrolled serial number, if desired (used when programming a transmitter with several input loops).
To delete an existing serial number, enter 0 in the loop number field. The serial number will change to 0's. I f 0 was entered in error, simply re-enter the l oop number or press [#], and the serial number will return to t he dis play.
2. Press [] to conti nue. The system now checks for a duplicate
serial/loop number.
If no duplicate is found, the display shows the serial number
and loop number.
3. Press [] to conti nue to confirmation screen.
Loop Number Change NOTE: If the [C] key is used to copy the previously enrolled serial
number, the cursor will move to the Loop c olumn (L) with the previous serial number displ ayed, and display a highlighted question mark for the l oop number.
Enter the loop number and press [ ]. The system will now check for a duplicate serial/loop number combination.
XMIT TO confirm
Appears if you answered “Yes” at the “S et to Confirm” prompt. Activate the loop input or button that corresponds to this zone. Press [] to continue. If the serial/loop num ber transmitted does not match the seri al number entered, a display showing the ent ered and the received serial/loop numbers appears . If so, activate t he l oop input or button on the transmitter once again. If a match i s not obtained, press the [#] key twice and then enter (or transmit) t he correct serial number. Press [] to continue If the serial number transmitted matches the serial number entered, the keypad will beep 3 times and a summary display will appear, showing that zone's programming. An “s” indicates that a transmitter’s serial number has been enrolled.
Press [] to accept the zone informati on and continue.
PROGRAM ALPHA?
Press 1 if you want to program des criptors for the zone now, and refer to the *82 Descriptor Programming section for procedure. To program descriptors lat er, enter 0 (no). Press [] to return to the ENTER ZN NUM prompt.
Completing Zone Programming
When you have finished programming all zones, test each zone
Do not use the Transmitter ID Sniffer M ode for checking
using the system’s TEST mode. wireless transmitting devices, as it will only check for
transmission of one zone on a part i cular transmitter, NOT the zones assigned to each additional l oop.
58 EXPERT ZONE PROGRAMMING MODE
∗∗
(press ∗∗∗58 while in Data Programming mode)
This method is desi gned f or use by installers with previous experience in programming HONEYWELL control panels. This mode is al so used to program wireless keys us i ng pre-defined templates.
SET TO CONFIRM?
Select whether you want confirmat i on of wireless device enrollment. (See “XMIT TO CONFIRM” prompt later in this sect i on.) We
recommend that you confirm the programming of every transmitter.
SUMMARY SCREEN
Zn ZT P RC HW: RT 01 09 1 10 EL 1
(Typical for Zone 1, initial summary screen)
Zn ZT P RC IN: L 10 00 1 10 RF: –
(Typical for entered zone number; zone 10 in this example)
System displays summary of zone 1’s current programm i ng. Enter the zone number being programmed, then press []. A summary screen for that zone is displayed, along with any current programming values, and the cursor moves to the Zone Type location. The cursor then automatically moves to the next locations after each entry is made.
Special Function Keys:
[A] (Advance) and [B ] (Back) keys on the keypad move the cursor within the screen.
[C] (Copy) key will insert the previous zone’s attributes, if desired.
[D] key starts the Wireless Key Programming Templates menu (see Wi rel ess Key Programming Templates section that follows this section).
Sequentially enter Zone Type (ZT), Partition (P)†, and Report Code (RC; 0-9 only; use *56 mode to enter hex codes ), then Hardwire Type (HW) and Response Time (RT) for basic wired zones 1-8 or Input Device Type (IN) for zones 9 and higher (Loop Number [ L] is programmed at the INPUT S/N prompt). See *56 Zone Programming Menu Mode secti on described earlier for entry values. † applies to VISTA-20PMT
Press [] to save the programming and cont i nue. If needed, press the [#] key to back up without saving.
For wireless devices (input types RF, UR, BR), continue to the INPUT S/N (serial number/l oop number) and XMIT TO CONFIRM prompts described earlier i n the *56 Zone Programming Menu Mode section. When done, the display returns to the initial summary screen prompt to let you program the next zone.
For wired devices, the dis pl ay returns to the initial summary sc reen prompt to let you program the next zone.
To Quit, enter 00 at the zone number location and press [].
15
WIRELESS KEY PROGRAMMING TEMPLATES
(press the [D] key from *58 Menu mode Summary Screen) This procedure programs the wireless keys, but a key is not active for arming/disarming until it is assigned to a user number (see
TEMPLATE ?
Enter desired templat e number 1–6 (see chart below), then press [] to continue. To exit the Template screen, press [#]. The system returns to the *58 Menu mode Summary Sc reen.
TEMPLATE SUMMARY
L 01 02 03 04 T 23 22 21 23
The selected template i s displayed. The top line represents loop numbers, the bottom line represents each loop’s zone type. Press [] to accept template and cont i nue.
PARTITION (VISTA-20PMT)
Enter the partition (1, 2) in which the key is to be active. Press [∗] to continue.
Wireless Key Predefined Default Templates
For 5804
TEMPLATE 1 1 No Response 23 TEMPLATE 4 1 No Response 23 2 Disarm 22 2 No Response 23 3 Arm Away 21 3 Arm Away 21 4 No Response 23 4 Disarm 22 TEMPLATE 2 1 No Response 23 TEMPLATE 5 1 No Response 23 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21 3 Arm Away 21 4 Arm Stay 20 4 Disarm 22 TEMPLATE 3 1 24-hour audible 7 TEMPLATE 6 1 24-hour audible 7 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21 3 Arm Away 21 4 Arm Stay 20 4 Disarm 22
System Operation
section, Assigning Attributes Command in the Installation Instructions).
Loop Function Zone Type
ENTER START ZONE
The system displays the lowest zone number of the highest available consecutive 4-zone group. To start at a different zone number, enter the zone desired, and press []. If the system has four consecutive zones beginning with that zone, the zone number is displayed. If not, t he system will again display a suggested zone that can be used. If the required number of consecutive zones is not available at all, the system will display “00”.
Press [] to accept.
Continue to the INPUT S/N (serial number/loop number) and XMIT TO CONFIRM prompts described earlier i n the *56 Menu Mode section.
IMPORTANT: When confirmed, the key is not active for arming/disarming until it is assigned to a user number (using the assigning attributes c ommand, attribute “4”). See System Operation section in Installation Instructions.
When done, the keypad beeps three times and the display returns to the ENTER START ZONE prompt t o l et you enter the starting zone for the next wireless key. To quit this mode and return to *58 Menu mode, enter 00 at this prompt and press [∗].
For 5804BD
Loop Function Zone Type
57 FUNCTION KEY PROGRAMMING
∗∗
∗∗∗∗
(press
57 while in Data Programming mode) The Function Key Worksheet is on page 29.
The system provides the ability to program each of the four keypad function keys to perform one of 12 system operations. The end user can then activate the function by simply pressing and holding the programmed key for 2 seconds. Typical functions (listed below) include single-button arming, turning lights on/off, or single-button paging.
To assign emergency key functions (function key option “00”), first program the respective emergency zone number (95 for
“A” key, 96 for “C” key, 99 for “B” key) with the desired zone type using 56 (or 58) Zone Programming mode, then use ∗57 Function Key menu mode to assign the desired key.
To use a function key to activate a relay action (57 Menu mode key function 07), use 79 Menu mode to map the output, and
use 80 Menu mode to define the output’s action; select system operation type “66.”
To use a function key for a user macro, use 57 menu mode to activate the desired key, then define the actual macro
functions using the user code + [#] + [6] [6] command.
PRESS KEY TO PGM
Press the desired func t i on key to be programmed, A-D, then press [] to continue. When done, press 0 t o exit t hi s mode and return to data field mode. NOTE: A key programmed as a function key is no longer available to be used as an end-user m acro key or panic key.
A B C D
OFF
MAX
INSTANT
READY
*
AWAY
TEST
CODE
321 654 987 #0
PARTITION (VISTA-20PMT)
Enter the partition (1-3) in which this function key will be active.
STAY
BYPASS
CHECK
keypad_keys-00-001-V0
KEY "A" FUNC
Enter the desired functi on for this key: 00 = For the Function key selected, the function will be as follows
(default): I f A selected = Zone 95 (emergency key, same as [1] [] pair) I f B selected = Zone 99 (emergency key, same as [∗] [#] pair) I f C selected = Zone 96 (emergency key, same as [3] [#] pair) I f D selected = Single-button paging 01 = Single-button paging (sends a 999-9999 message to pager) 02 = Display time 03 = Arm AWAY (reports as User 00 if closing reports are enabled) 04 = Arm STAY (reports as User 00 if cl osing reports are enabled) 05 = Arm NIGHT-STAY (reports as User 00 if closing reports enabled) 06 = Step Arm i ng
(arms STAY, then NIGHT-STAY if enabled, then AWAY)
07 = Output Device Command (for device programmed as syst em
operation type 66 in *80 Menu Mode) 08 = Communi cation Test (sends Contact ID code 601) 09 -12= Macro Keys 1-4 respectively (defi ned by [ #] [6] [6] command) NOTE: Macros 11-12 apply to VISTA -20PMT only
Press [] to continue; returns to key number prompt with the next function key letter di splayed.
16
OUTPUT DEVICE PROGRAMMING GENERAL INFORMATION (*79/*80 Menu Mode)
Output Devices: The VISTA-20PMT system supports up to 16 relays and/or Powerline Carrier devices (X-10 devices)
The VISTA-15PMT supports 8 relays and 2 built-in trigger outputs (total 10 outputs). Output Functions: The system also provides installer-defined output functions, which can be assigned to any of the physical
The control supports: V20PMT = up to 48 defined functions; V15PMT = up to 24 functions Use *80 Menu Mode to define output functions.
WARNING: Relays and output devices are not recommended for life safety applications. NOTE: When navigating the *79 and *80 menus: The [✱] key is used to accept an entry and advance to the next prompt.
The [#] key is used to revert back to the last question to check or change an entry. Press [✱] to go forward again.
Programming Output Devices
1. Use *79 Menu Mode to assign module and output numbers and map them to device addresses. NOTE: You must map output devices using *79 Menu Mode before you can use *80 menu Mode.
2. Use *80 Menu Mode to create output definitions, which control the output devices, if desired.
3. Use *81 Zone List Menu mode to define zone lists for use with output devices if the device action is based on more than
To program a device for manual activation (user code + [#] [7] / [#] [8] + 2-digit device number) or for scheduled automatic
To program a device to automatically activate upon a system event (or function key), use *79 Menu mode to map the device,
79 RELAY/POWERLINE CARRIER DEVICE PROGRAMMING MENU MODE
∗∗
(press
Use this menu to assign Relay Module device addresses and specific relay numbers, and Powerline Carrier unit numbers. The system is based on predefined module addresses for 4204 and 4229 modules. Refer to the table shown at the “Module Address” prompt and set the modules’ addresses (via module DIP switches) accordingly.
The following table shows how these outputs are identified.
Output Identification
ENTER OUTPUT NO.
01-18 = VISTA-20PMT relays/X-10; 01-08, 17, 18 = VISTA-15PMT relays / X-10 [] to continue This is the logical (or ref erenc e) relay number as used in the system. Relays and X-10 devices are numbered 01-16; the on­board triggers are numbered 17 and 18 and can be programmed for inverted output, if required.
OUT NORM LOW (appears only f or triggers 17/18)
0 = no (standard default); sets t he output level normally high 1 = yes; sets the output normally low (can be used for resetting 4-
[] to return to Output Number prompt Output Trigger 17 can be used for resett i ng 4-wire smoke detectors by connecting i t to the negative power terminal of the smoke detector, selecting 1 at this prompt, and sett i ng as zone type 54, fire zone reset, in *80 Menu mode. After entry, display ret urns to Output Number prompt. Use *80 Menu mode to program the funct i on of the trigger.
OUTPUT TYPE
0 = delete; 1 = 4204/4229 relay (skip to “B ” prompt); 2 = Powerline Carrier device (skip to “A” prompt) [] to continue.
A (if X-10 was selected) UNIT No.
Enter the unit code (01-16, set at the device). [] to return to the Output Num ber prompt continue
plus 2 built-in trigger outputs in any combination. These 18 “outputs” are assigned to system-wide output numbers (01-18). Use *79 Menu Mode to assign output numbers and map them to device addresses.
outputs. Therefore, the action of any one of the outputs can be based on as many of these defined functions as desired. This lets a single relay or X-10 device perform many functions.
one zone. activation, simply map the device using *79 Menu mode. then use *80 Menu mode to define the automated device action.
∗∗∗∗
79 while in Programming mode) The *79 Device Mapping Worksheet is on page 29.
This output is identified by
Relays the Relay Module’s device address and the relay position on that module (i.e. the physical relay
number, 1-4, on that module).
X-10 Device a house ID (entered in data field *27) and the unit number of the device. Built-in Outputs the output number assigned, 17 for Trigger 1 and/or 18 for Trigger 2.
B (if relay was selected) MODULE ADDR
Enter the predefined address for thi s module (07-15; see Table of Device Addresses). Make sure the module’s DIP switches are set to the selected address. [] to continue
Module Addresses
Address Module
07 1st 4229 (with zones 09-16) 08 2nd 4229 (with zones 17-24)
09† 3rd 4229 (with zones 25-32)
wire smoke detectors)
10† 4th 4229 (with zones 33-40) 11† 5th 4229 (with zones 41-48)
12 1st 4204 13 2nd 4204
14† 3rd 4204 15† 4th 4204
† These addresses apply to VI S T A-20PMT only.
REL POSITION (actual relay number on module)
For 4204 modules, relay numbers are 1-4. For 4229 modules, relay numbers are 1-2. [] to return to the Output Number prompt for programming the next device This is the actual (or phys i cal) relay number with respect to the Relay Module upon which it is located. For 4204 modules, relay numbers are 1-4. For 4229 modules, relay num bers are 1-2. The system returns to t he Output Number prompt for programming the next device.
– 17 –
80 OUTPUT FUNCTION MENU MODE
∗∗
∗∗∗∗
(press
80 while in Programming mode)
The Output Definition Worksheet is on page 30. Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. by an output function number, and includes the following components:
Each output definition is identified
Output Definition Components
Component Description
Output Function No. A reference number that defines an output’s characteristics. Activated By Determines whether the initiating event occurs on a zone, a zone list, or a zone type. Event Event that triggers the output action. Can be an event occurring on a specific zone number or a
zone list, or a specific zone type.
Partition If the output is activated by zone type, this defines the partition in which the programmed event is
to cause the device action.
Output Action Defines the action of the relay/X-10 device when the defined event occurs. Can close for 2
seconds, stay closed until reset, continuously pulse (1-second close-open-close-open, etc.), toggle the device state, or activate for a defined duration (set in data field *177).
Output No. Assigns this function to a specific output number (defined in *79 Menu Mode). This is the output
number that will perform this function upon the triggering event. Note that each defined function is associated with only one output number. This means that if more than one output device needs to perform this particular function, you need to define another output function number with the same attributes, but assign the appropriate output number. (i.e. output devices can be assigned more than one function number, but each function number can only be assigned a single output number.
For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to output number 2 (as programmed in *79 Menu Mode), program the following in *80 Menu Mode:
Prompt Entry
Output Funct. # = 01 (assuming this is the first output function) Activated By: = 3 (zone number) Enter Zn No. = 04 (requires 2-digit zone numbers) Output Action = 3 (continuous pulse) Output Number = 02 (device mapped in *79 Menu Mode)
OUTPUT FUNCT. #
Enter the output function number to be defined (VISTA-20PMT: 01-48; VIST A -15P MT: 01-24). [] to continue; 00 = exit
SUMMARY SCREEN
01 A E P Trig ?00 0 0 – ZL=00
This screen displays a summary of the current output programming A = Output Action; E = Triggeri ng event; P = Partition; Trig = Trigger type Question mark indicates the device shown has not been mapped. Use *79 Menu mode to map the devic e. [] to continue
ACTIVATED BY
0 = delete (deletes the output func tion and any previous
programming); a confi rmation prompt appears.
To delete this output definition, press 1. If you do not want to delete this output, press 0.
1 = zone list (go to “A” prompt ); 2 = zone type (go to “B” prompt);
3 = zone number (go to “C” prompt)
Press [] to continue Select where the initiating event f or this output definition is to occur
A (if zone list was selected) ZN LIST
Enter the desired zone list number (01-08). At the ENTER EVENT prompt, enter the zone list event that will activate this output (0 = restore; 1 = alarm; 2 = fault; 3= trouble)
Press [] to continue and skip to the “Output A ction” prompt. NOTE: For alarm, fault, and trouble, an event on ANY zone in the
list activates t he output, but ALL zones in the list must be restored before the output is res t ored.
B (if zone type was selected)
ENTER ZN TYPE
Enter the desired zone type. See list below *80 Worksheet for zone types. At the PARTITION prompt , enter the partition in which this zone type will occur (0 = any partition; 1 = part 1; 2 = part 2; 3 = part 3). Press [] to continue and skip to the “Output A ction” prompt. CHOICES FOR ZONE TYPES:
00 = Not Used 05 = Day/Night 14 = Carbon Monoxide†† 01 = Ent/Exit #1 06 = 24 Hr Silent 15 = Medical 02 = Ent/Exit #2 07 = 24 Hr Audible 16 = Fire w/verification 03 = Perimeter 08 = 24 Hr Aux 23 = No Alarm Response 04 = Interior Follower 09 = Fire 24 = Silent Burglary 10 = Interior w/Delay 77 = Keyswitch Zone 12 = Monitor Zone 81 = AAV Monitor Zone 90-91 = Configurable
CHOICES FOR SYSTEM OPERATION:
20 = Arming–Stay 36 = **At Bell Timeout*** 58 = Duress 21 = Arming–Away 38 = Chime 60 = AAV 22 = Disarming 39 = Any Fire Alarm 61 = AVS/GSMV 31 = End of Exit Time 40 = Bypassing 62 = AVS/GSMV 32 = Start of Entry Time 41 = **AC Power Failure 66 = Function Key† 33 = Any Burglary Alarm 42 = **System Battery Low 67 = Bell Fail 43 = Comm. Failure 68 = Telco Line Cut 52 = Kissoff 78 = Keyswitch Red LED 54 = Fire Zone Reset 79 = Keyswitch Green LED
** Use 0 (Any) for Partition No. (P) entry. *** Or at Disarming, whichever occurs earlier.
† Use *57 Menu Mode to assign the functi on key (function “07”). †† when used with an output function, the carbon monoxide zone type
activates upon CO alarms only. Does not activate for trouble conditions.
§ automatically set when appropriate AVS Quick Command performed.
Note: In normal operation mode: Code + # + 7 + NN Key Entry starts Device NN. Code + # + 8 + NN Key Entry stops Device NN.
session begin § session end §
18
(if zone number was selected)
C ENTER ZN NO.
Enter the desired zone number, t hen press [] to continue. At the ENTER EVENT prompt, enter the zone event that will activate this output (0 = restore; 1 = alarm/fault/trouble). Press [] to continue to the OUTPUT ACTION prompt
OUTPUT ACTION
0 = off 1 = Close for 2 seconds 2 = Close and Stay Closed 3 = Continuous Pulse 1 sec on and 1 s ec off 4 = Change Device State; 5 = Duration 1 (see dat a field *177); 6 = Duration 2 (see data field *177) Press [] to continue. Enter the desired device act i on.
ENTER OUTPUT NO.
Enter the device output num ber (programmed in *79 Menu Mode) you want associated with this output . 01-16 = VISTA-20PMT output no. 01-08 = VISTA-15PMT output no. 17-18 = on-board triggers Press [] to continue.
SUMMARY SCREEN
A summary sc reen appears showing the programmed settings. Press [] to return to OUTPUT FUNCTION NUMBER prompt.
81 ZONE LIST MENU MODE
∗∗
(press *81 while in Programming mode)
The Zone List Worksheet is on page 29.
Zone lists let you group individual zones for use with certain system actions. Using this mode, simply zone list number, then add the desired zone numbers to be included in that list. The following table shows the available zone lists and their purposes:
List No. Used for Notes 1, 2 general purpose (GP) 3 chime-by-zone (see field *26 to enable option) 4 cross zones (see note at right) 5 night stay zones 6 7
dial delay disable unlimited reports
8 general purpose 9 zones that activate Pager 1 10 zones that activate Pager 2 11 zones that activate Pager 3 (VISTA-20P) 12 zones that activate Pager 4 (VISTA-20P)
Any list may include any or all of the system's zone numbers.
A zone list can be assigned to more than one output relay.
Zone List 4: When creating zone list 4 for cross zoning,
include only zones assigned to zone types 3, 4, or 5. Do not include zones that have delays (entry/exit zones, interior w/delay) or 24-hour zones, as these zone types may produce unpredictable operation and may not function as intended. See field *85 for Cross Zone Timer option.
Zone List 6: See field *50 for Dial Delay Disable option.
Zone List 7: See field *93 for Unlimited Reports option.
ZONE LIST NO.
Enter the zone list num ber (01-12) to program (or 00 to exit this mode). Press [] t o c ontinue.
ENTER ZN NUM.
Enter each zone number (01-64†) to add to t he zone l i st, followed by pressing [] (example, 01∗, 02∗, 03). Press 00 to continue.
† VISTA-20PMT = 01-64; VISTA-15PMT = 01-06, 09-34, 49-56. IMPORTANT: Do not include fire zones in zone list s that are used to STOP device acti ons.
DEL ZN LIST?
0 = don’t delete list; c urrent zone list remains saved 1 = delete this zone list; All zones in the zone list will be deleted. [] to continue
DELETE ZONE?
0 = don’t delete zones; save the ent i re zone l i st and return to the Zone List No. prompt 1 = go to next prompt to delete zones [] to continue
ZN TO DELETE?
Enter each zone (01-64†) to be deleted from the list, following each with [∗]. 00 when done to return to the Zone List No. prompt . † VISTA-20PMT = 01-64; VISTA-15PMT = 01-06, 09-34, 49-56.
select an appropriate
– 19 –
82 ALPHA DESCRIPTOR MENU MODE
∗∗
The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervision faults. Each description can be composed of a combination of up to 3 words selected from a vocabulary of words stored in memory (see Alpha Vocabulary List page). In addition, up to 10 installer-defined words can be added to those already in memory, plus 3 additional words can be assigned as partition descriptors. Thus, when an alarm or trouble occurs in a zone, an appropriate description for that zone's location can be displayed at the keypad. Zone descriptors are recommended for systems using Alpha display keypads, and are necessary if a 4286VIP Phone Module is used.
NOTE: You can also enter zone descriptors when the zone is being defined in ✱56 Menu mode. 4286 NOTE: If using a 4286VIP Phone Module, select from those words in the Alpha Vocabulary List shown in boldface
type. The phone module will not provide annunciation of the other words.
If a Phone Module is added to an existing system, the Alpha descriptors presently in the system should be reprogrammed, selecting from those words shown in boldface type in the Alpha Vocabulary List. The phone module will not provide annunciation of any other words.
PRE-DEFINED DESCRIPTORS PROGRAM ALPHA
0 = no (quit Alpha mode) 1 = yes Press [] or [#] to continue.
CUSTOM WORDS
0 = no (continue to descriptor programming) 1 = yes (go to custom word programming) Press 0 to program standard alpha descriptors. The system will then display the descript or for zone 1. To program custom words, press 1 (custom words are described later). Press [] to continue.
∗∗∗∗ ZN 01
Descriptor screen for zone 1 appears. To program a descriptor (up to 3 words) for a zone, do the following:
1. Press [] plus the desired zone number (existing descriptor, if any, is displayed), then pres s [] plus the zone number again (flashing cursor appears).
2. a. Press [#] plus the 3-digit number from the Alpha Vocabulary
List on page 21 for the first word.
b. Press [6] to accept the word and move the cursor for the
next word.
3. Repeat steps 2a and 2b for the second and third words (if used).
4. When all words have been entered, press [8] to save the descriptor for that zone. The fl ashing cursor disappears.
5. Repeat steps 1-4 to ass i gn a descriptor for the next zone.
6. When all descriptors have been entered, press [] + 0 + 0 (or simply press [#] ) after the last descriptor has been saved to return to the PROGRAM ALPHA? prompt.
Enter 0 (no) at t he prompt to exit this mode and return to Data
Field mode.
ADDING CUSTOM WORDS (up to 10 words)
You can add up to 10 installer-defined words t o t he bui l t-in vocabulary, which can then be used when programming zone descriptors. Each of t he 10 words c an actually consist of a word string of one or more words, but no more than used for each word or word string. For custom words, the k eys have the following functions:
[4] moves cursor one space to the left. [6] m oves cursor one space to the right. [8] saves the new word in the system's memory.
1. Select Cus t om Word mode (enter 1) when the prompt “CUSTOM WORD ?” is dis played.
2. Enter the number (01–10, or 11, 12, 13 for partition descriptors– see below) of the custom word or word string to be creat ed, corresponding to index numbers 245 - 254 respec tively. A cursor appears at the beginning of the second l i ne.
NOTE: Cust om words 8, 9, and 10 are “reminder words” that can be
programmed to display using Scheduling Mode.
3. Refer to the Character (ASCI I) Chart on the next page.
Press [#], followed by the two-digit entry for the first lett er you would
like to display (e.g., # 6 5 for “A”). The cursor moves to the right, in position for the next character.
To delete a character, simply enter the SPACE character (#32) at
the unwanted character’s location.
4. Repeat Step 3 to create the desired word(s). Each word can be a maximum of 10 charac t ers (except custom message/partition descriptor word numbers 11, 12, and 13, which can be a maximum of 16 characters).
5. When the word is complete, press the [8] key to save the c ustom word(s) in the vocabulary list and return t o the “CUSTOM WORD ?” display.
6. Repeat Steps 1–5 for other cus tom words to be entered. To change a custom word, just overwrite i t . When all words have been programmed, enter 0 at t he “CUS TOM WORD ?” prompt to return to the Program Alpha prompt . Enter 0 again to exit Descriptor mode.
To Assign Partition/Custom Message Descriptors, use Adding Custom W ords procedure, but: VISTA-15PMT: Use word number 11 in s t ep 2. The custom message
replaces the standard “DISARMED Ready to Arm”
message. VISTA-20PMT: Use the f ol lowing word numbers in step 2: 11 = partition 1; 12 = part i tion 2; 13 = common lobby
ten
characters can be
20
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)
000
– A –
001 AIR
002 ALARM
004 ALLEY 005 AMBUSH
006 AREA
007 APARTMENT
009 ATTIC
010 AUDIO – B –
012 BABY
013 BACK
014 BAR
016 BASEMENT
017 BATHROOM
018 BED
019 BEDROOM
020 BELL
021 BLOWER
022 BOILER
023 BOTTOM 025 BREAK
026 BUILDING
C – 028 CABINET
029 CALL 030 CAMERA 031 CAR 033 CASH 034 CCTV 035 CEILING 036 CELLAR
037 CENTRAL
038 CIRCUIT
040 CLOSED
046 COMPUTER
047 CONTACT D
048 DAUGHTERS
049 DELAYED
050 DEN
051 DESK
052 DETECTOR
053 DINING
054 DISCRIMINATOR 055 DISPLAY
Note: Bulleted () words in boldface type are those that are also available for use by t he 4286 Phone Module. I f us ing a P hone m odule,
(Word Space)
057 DOOR
059 DOWN
060 DOWNSTAIRS
∗∗∗∗
∗∗∗∗
∗∗∗∗ ∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
061 DRAWER
062 DRIVEWAY
064 DUCT E
065 EAST
066 ELECTRIC
067 EMERGENCY
068 ENTRY
069 EQUIPMENT
071 EXIT
072 EXTERIOR F
∗∗∗∗
073 FACTORY
∗∗∗∗
075 FAMILY
076 FATHERS
077 FENCE
079 FIRE
080 FLOOR
081 FLOW 082 FOIL
083 FOYER
084 FREEZER
085 FRONT
G
089 GARAGE
090 GAS
091 GATE
092 GLASS
093 GUEST 094 GUN – H –
095 HALL
096 HEAT
098 HOLDUP
099 HOUSE
100 INFRARED
101 INSIDE
102 INTERIOR 103 INTRUSION J
∗∗∗∗
104 JEWELRY K
105 KITCHEN
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
L
106 LAUNDRY
107 LEFT
108 LEVEL
109 LIBRARY
110 LIGHT
111 LINE
113 LIVING
114 LOADING
∗∗∗∗
115 LOCK 116 LOOP 117 LOW
118 LOWER M
119 MACHINE
121 MAIDS
122 MAIN
123 MASTER
125 MEDICAL
126 MEDICINE 128 MONEY 129 MONITOR
130 MOTHERS
131 MOTION
132 MOTOR N
134 NORTH
135 NURSERY O
136 OFFICE
138 OPEN
139 OPENING
140 OUTSIDE
142 OVERHEAD P – 143 PAINTING
144 PANIC
145 PASSIVE
146 PATIO
147 PERIMETER
148 PHONE 150 POINT
151 POLICE 152 POOL
153 POWER
R
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
155 RADIO
156 REAR
157 RECREATION 159 REFRIGERATION 160 RF
161 RIGHT
162 ROOM
163 ROOF S – 164 SAFE 165 SCREEN 166 SENSOR
167 SERVICE
168 SHED
169 SHOCK
170 SHOP
171 SHORT
173 SIDE
174 SKYLIGHT
175 SLIDING
176 SMOKE
178 SONS
179 SOUTH
180 SPRINKLER
182 STATION 184 STORE
185 STORAGE
186 STORY
190 SUPERVISED
191 SUPERVISION 192 SWIMMING 193 SWITCH T – 194 TAMPER 196 TELCO 197 TELEPHONE
199 TEMPERATURE
200 THERMOSTAT
201 TOOL
202 TRANSMITTER
U
205 UP
206 UPPER
207 UPSTAIRS
208 UTILITY
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
and words other than these are selected for Alpha descriptors, the module will not provide annunciation of those words.
Italicized
32 (space) 33 ! 34 " 35 # 36 $ 37 % 38 & 39 ' 40 (
words followed by an asterisk indicat e those words supported by the 6160V/6150V Voice Keypads
CHARACTER (ASCII) CHART (For Adding Custom Words)
41 ) 42 * 43 + 44 , 45 – 46 . 47 / 48 0 49 1
50 2 51 3 52 4 53 5 54 6 55 7 56 8 57 9 58 :
59 ; 60 < 61 = 62 > 63 ? 64 @ 65 A 66 B 67 C
68 D 69 E 70 F 71 G 72 H 73 I 74 J 75 K 76 L
77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U
V – 209 VALVE 210 VAULT 212 VOLTAGE W – 213 WALL 214 WAREHOUSE
216 WEST
217 WINDOW
219 WING
220 WIRELESS X – 222 XMITTER Y – 223 YARD Z – 224 ZONE (No.)
225 ZONE
226 0
227 1
228 1ST
229 2
230 2ND
231 3
232 3RD
233 4
234 4TH
235 5
236 5TH
237 6
238 6TH
239 7
240 7TH
241 8
242 8TH
243 9
244 9TH
245 Custom Word #1 246 Custom Word #2 247 Custom Word #3 248 Custom Word #4 249 Custom Word #5 250 Custom Word #6 251 Custom Word #7 252 Custom Word #8 253 Custom Word #9 254 Custom Word #10
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
86 V 87 W 88 X 89 Y 90 Z
21
SETTING SCHEDULES
(Installer Code + [#] + [6] [4])
The system provides schedules, which can be used to automatically control 11 types of system events at pre-defined times. Some events are reserved for the installer only. NOTES:
The master code can only access schedules 01-16 (VISTA-15PMT = 01-04) and events 00-07.
System clock must be set before schedules can take effect.
Programmed schedules do not take effect until the next scheduled “start” time. (e.g., if programming a schedule time window
for 8AM to 5PM, the schedule does not take effect until 8AM after the schedule has been programmed.)
ENTER SCHED NO.
VISTA-20PMT: 01-16 = end-user schedules 17-32 = installer-onl y schedules VISTA-15PMT: 01-04 = end-user schedules 05-08- = installer-onl y schedules [] to continue. To Quit, enter 00.
Enter the desired schedule number.
ENTER EVENT
00 = clear event 01 = Relay On/Off 02 = User Access 03 = Latch Key Report to Pager (sent to all pagers in the user’s
partition; mess age sent is 777-7777. User must be enabled for paging and system m ust be armed before reporting can occur.)
04 = Forced Stay Arming
enabled regardless of setting i n f i el d *23)
05 = Forced Away Arming
enabled regardless of setting i n f i el d *23) 06 = Auto Disarm 07 = Display “Reminder” 10 = Display custom words (if selected, system displays custom
words 8, 9, and 10 at defined time. Can be used as installer’s remi nder message to the end user); programmable by instal l er onl y
11 = Periodic Test Report (see k ey commands in Test Report
Code, data field *64, to quickly set periodic test reporting intervals); programmable by installer only
[] to continue.
Enter the desired event number for event you want to occur at a specified time. Events 10-11 are reserved for the inst al ler only.
Latch key report (option 03) is sent to all pagers in the user’s partition and is active onl y when the s ys tem is armed (message sent is 777-7777). User must be enabled for paging.
NOTE: Events 07 and 10 cause the k eypad to beep every 30 seconds when messages are dis pl ayed. Stop the beeps by pressing any key.
(
Forced bypass is automatically
(
Forced bypass is automatically
DEVICE NUMBER (for event 1 relay on/off)
VISTA-20PMT: 01-18; VISTA-15PMT: 01-08, 17, 18 [] to continue.
Enter the physical devic e number as programmed in 79 Menu Mode, then press [*] to cont i nue to the “Start” prompt.
Device numbers 17 and 18 designate bui l t-in triggers 1 and 2 respectively.
GROUP NUMBER (for event 2 user access)
1-8; [] to continue.
PARTITION (VISTA-20PMT; for events 3-7,10,12)
0 = all partitions 1 = partition 1 2 = partition 2 3 = common [] to continue
START
01-12 = hour 00-59 = minute 0 = AM; 1 = PM To select days, posit i on t he cursor under the desired days using the [] key to move forward, t hen press “1” to select the day. [] to continue
Enter the event’s start time and days of the week to occur.
STOP (for events 1 relay on/off; 2 user access; 3 latch key report)
See START for entries. [] t o continue. Enter the event’s stop time and days of the week to occur.
REPEAT
0 = do not repeat 1 = repeat schedule weekly 2 = repeat schedule biweekly (every other week) 3 = repeat schedule every third week 4 = repeat schedule every fourth week (28 days) [] to continue
Enter the desired repeat option for t hi s schedule.
e.g., To make a sc hedul e that happens everyday you would select all days with a repeat count of 1. To make a schedule that runs for one week then stops, s el ect everyday with a repeat count of 0.
RANDOMIZE (for events 01 and 11)
0 = no; 1 = yes [] to continue and return to ENTER SCHED NO. prompt to program the next schedule.
If selected, the scheduled start and stop times will vary within 60 minutes of the “hour” time. For example, if a schedule is set to start at 6:15pm, it will do so the f i rst time 6:15pm arrives, but on subsequent days it will start anytime between 6:00 and 6:59 p.m.
NOTE: Do not use the random option i f the start and stop times are within the same “hour” setti ng, otherwise unpredictable results may occ u r (e. g . , the randomized stop time may occ ur before the start time).
– 22 –
AVS SYSTEM ENABLE and QUICK PROGRAMMING COMMANDS
Applies to an AVS system using an ECP connection to the control.
1. Install the AVS module according to its instructions.
2. Use one of the control’s AVS Quick Program commands as follows (see Quick Program Command Results below for
results of each command):
installer code + [#] + 0 + 3: enable AVS operation without panel sounds on the AVST speaker
installer code + [#] + 0 + 4: enable AVS operation and enable panel sounds on the AVST speaker
3. Use data field 55 Dynamic Signaling Priority to select the desired reporting paths (phone line and/or GSMV) and path for
AAV communication.
To undo the Quick Command programming if necessary, use the following commands:
installer code + [#] + 0 + 5: remove all options set by [#] + 03 quick command
installer code + [#] + 0 + 6: remove all options set by [#] + 04 quick command
Quick Program Command Results
When either the #03 or #04 Quick Program command is used, the following are automatically programmed and no longer available for other control panel purposes.
Pre-Programmed #03 Command #04 Command
Output Function No. (80 mode)
Output Relay No. (79 mode)
Protection Zone (56/58 mode) Device Address address 08 (AVS module) address 11 (AVS m odule) Same as #03 command Sam e as #03 command Data Field ∗91
VISTA-15PMT series
22 (zone type 60, relay 07) 23 (zone type 61, relay 08) 24 (zone type 62, relay 08)
07 (addr 08, relay pos 2) 08 (addr 08, relay pos 1)
4229 zn 24 (zt 81, addr 08) 4229 zn 48 (zt 81, addr 11) Sam e as #03 command Sam e as #03 command
AAV enabled AAV enabled AAV enabled AAV enabled
VISTA-20PMT series
46 (zone type 60, relay 15) 47 (zone type 61, relay 16) 48 (zone type 62, relay 16)
15 (addr 11, relay pos 2) 16 (addr 11, relay pos 1)
VISTA-15PMT series
Same as #03 plus: 17 (zone type 14, relay 05) 18 (zone type 22, relay 05) 19 (zone type 39, relay 06) 20 (zone type 33, relay 06) 21 (zone type 36, relay 06) Same as #03 plus: 05 (addr 08, relay pos 4) 06 (addr 08, relay pos 3)
VISTA-20PMT series
Same as #03 plus: 41 (zone type 14, relay 13) 42 (zone type 22, relay 13) 43 (zone type 39, relay 14) 44 (zone type 33, relay 14) 45 (zone type 36, relay 14) Same as #03 plus: 13 (addr 11, relay pos 4) 14 (addr 11, relay pos 3)
UPLOADING/DOWNLOADING VIA THE INTERNET
UL: Up/downloading via the Internet has not been evaluated by UL.
The control, when used with an appropriate communication device (ex. 7845i-ent, 7845i-GSM), supports upload/download programming capability via the Internet or a Private local area network (Intranet) instead of using telephone lines. This allows site maintenance independent of central station monitoring, and modification to sites globally via the Internet or through a private LAN.
Refer to the instructions provided with the communication device for information regarding its installation, programming, and registration. The System Requirements table below lists two sets of system requirements, depending upon whether you intend to communicate over the Internet using AlarmNet Services, or whether you are communicating over a Private LAN (Intranet).
System Requirements
Internet Communication
At the Installation Site:
Appropriate Internet/Intranet Communication Module
7720P Programmer
Internet Access and Cable/DSL Modem
Cable/DSL Router (optional, if connecting more than one
device)
Control Panel
To set up the control panel, do the following:
1. Connect the communication device to the control panel’s ECP (keypad) terminals.
2. Internet Users: Connect the communication device to the Internet via a cable/DSL modem and router. Intranet Users: Connect the communication device to the Intranet (LAN) via the appropriate Ethernet connection.
3. Enable the communication device in the control panel (using 29 Menu mode) to enable alarm reporting and module
supervision.
4. Using the communication device’s programming menus (via 29 Menu mode or 7720P programmer), program the
communication device for address 3 and program the device’s other options as required.
5. Register the communication device with AlarmNet. The communication device must be registered before downloading or
alarm reporting can take place.
To perform upload/download functions:
1. Connect the computer to the Internet and start the Compass downloading software.
2. Open the control’s account, then select the Communications function and click the Connect button.
3. At the Connect screen, check that the control’s MAC address is entered and the TCP/IP checkbox is checked.
4. Click Connect. The Internet connection to the control is made automatically via AlarmNet.
5. Once connected, use the Compass downloading software as normal to perform upload/download functions.
Intranet (Private LAN) Communication
At the Installation Site:
Appropriate Internet/Intranet Communication Module
7720P Programmer
Ethernet Network Connection
Control Panel
– 23 –
29 COMMUNICATION DEVICE MENU MODE (Pass-Through Programming)
∗∗
This mode is for programming an IP, GSM, or IP/GSM Communicator Module using an alpha keypad. Alternatively, these options can be programmed via the AlarmNet Direct website. After programming is complete, the module must be registered with AlarmNet before reporting via the communication device can occur. Refer to the device’s instructions for registration procedures.
NOTE: The module must be set to device address 3.
IMPORTANT: The use of an IP/GSM Communicator Module
requires an AlarmNet–I account. Please obtain the account information from the central station pri or to programming this module.
Using an Alpha Keypad as a 7720P Programming Tool
When programming with 29 menu mode, the alpha keypad mimics the functions of the 7720P Programming Tool. See figure to right and table below for 7720P key functions. Each key has two possible functions: a normal function and a SHIFT function.
Normal functions: The numeric values labeled directly
on the keys and the left-hand functions shown in diagram on the ABC keys. To perform a normal key function, simply press the desired key.
SHIFT functions: Those functions shown in diagram
above the numerical keys and the right-hand functions shown on the ABC keys. To perform a SHIFT key function, press SHIFT key (D key), then press the
ARMED
READY
SHIFT
FUNCTION
WHEN LIT
(A) (B) (C) (D)
BS/ESC
/
N / Y
SHIFT
A
1
D
4
S
INSTANT
7
SPACE
READY
OFF
2
MAX
5 8 0
7720P Emulation Template for Alpha Keypads
B
AWAY
E
T
CODE
TEST
C
STAY
3
F
BYPASS
6
X
CHIME
9
ENTER
#
6160-7720P-001-V0
desired function key (shift function is indicated by the lit READY LED).
∗∗∗∗29 IP/GSM Program Mode
Press 29 while in Data Field Programming mode. The following prompts appear.
ENABLE IP/GSM? 0=No, 1=Yes
1=PROG 2=DIAG 0=QUIT
Enable IP/GSM?
0 = no, not using IP or GSM; 1 = yes using IP and/or
GSM module
[] to continue
[Default = 0 (no IP and/or GSM)]
Programming / Diagnostics Select
1= Prog (program the
IP/GSM options)
2 = Diag (enter diagnostic
mode)
0 = Quit; returns to data field
programming mode
Normal and SHIFT key Functions While in ∗∗∗29 Menu Mode
Key Normal Key Function SHIFT Key Function
(A) = BS/ESC [BS]: Press to delete entry [ESC]: Press to quit Program Mode
Also, can reset EEPROM defaults † (B) = ↓/↑ [↓]: Scroll down programming [↑]: Scroll up programming (C) = N/Y [N]: Press for "NO" answer [Y]: Press SHIFT-Y for "YES" answer (D) = SHIFT Press before pressing a SHIFT key function. Will light READY LED. LED goes out once a
key is pressed. Press again for each SHIFT function desired. 1/A [1]: For entering the number 1 [A]: Used for entering C.S. ID number 2/B [2]: For entering the number 2 [B]: Used for entering C.S. ID number 3/C [3]: For entering the number 3 [C]: Used for entering C.S. ID number 4/D [4]: For entering the number 4 [D]: Used for entering C.S. ID number 5/E [5]: For entering the number 5 [E]: Used for entering C.S. ID number 6/F [6]: For entering the number 6 [F]: Used for entering C.S. ID number 7/S [7]: For entering the number 7 [S]: Press to display diagnostic status 8/T [8]: For entering the number 8 [T]: Press to send TEST messages 9/X [9]: For entering the number 9 [X]: Press to reset the IP/GSM [] / SPACE []: Used to select programming options 0 [0]: For entering the number 0 [#] / ENTER [#] / ENTER: Press to accept entries No SHIFT function
Active onl y when the "REVIEW?" prompt is displayed
If using a communication device, enter 1 at this prompt and enter 1-Prog at the next prompt to program the device. Use the communication device’s Installation Guide for details of the device’s programming prompts and instructions for registration.
Select whether you want to program the communication device or enter the device’s diagnostic mode.
Diagnostic Mode Note: Diagnostic mode option available only for communicators with firmware version 2.4.16 or higher.
[SPACE]: Not used
– 24 –
ZONE TYPE DEFINITIONS
Zone types define the way in which the system responds to faults in each zone.
Type 00 Zone Not Used
Program a zone with this zone type if the zone is not used.
Type 01 Entry/Exit Burglary #1
Assign to zones that are used for primary entry and exit.
Provides entry delay when zone is f aul ted if control is armed in
the Away, Stay, or Night-Stay modes.
No entry delay provided when the panel is armed in the Instant/Maximum mode.
Entry delay #1 is programmable for each partition (field *35).
Exit delay begins whenever the control i s armed, regardless of
the arming mode selec ted, and is programmable (field ✱34).
Type 02 Entry/Exit Burglary #2
Assign to zones that are used for entry and exit and require more time than the pri mary entry/exit point.
Provides a secondary entry delay, similar to entry delay #1.
Entry delay #2 is programmable for each partition (field *36).
Exit delay is same as described for Type 01.
Type 03 Perimeter Burglary
Assign to all sensors or contacts on exterior doors and windows.
Provides an instant alarm if the zone is faulted when the panel is
armed in the Away, Stay, Night -Stay, Instant or Maximum modes.
Type 04 Interior Follower
Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon ent ry (to and from the keypad).
Provides a delayed alarm (using the programmed entry 1 time) if the entry/exit zone is fault ed first. Otherwise this zone type gives an instant alarm .
Active when the panel is armed in the Away mode.
Bypassed autom atically when the panel is armed in the Stay or
Instant modes; i f armed in Night-Stay mode, zones assigned t o zone list 05 (night-stay zone li st) are not bypassed when system armed in Ni ght-Stay mode.
Type 05 Trouble by Day/Alarm by Night
Assign to a zone t hat contains a foil-protected door or window (such as in a store), or t o a zone covering a sensitive area such as a stock room, drug supply room, etc.
Can also be used on a sensor or contact in an area where immediate notification of an entry is desired.
Provides an inst ant al arm if faulted when armed in the Away, Stay, Night-Stay, I nstant or Maximum (night) modes.
During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a central station report, if desired).
Type 06 24-hr Silent Alarm
Usually assigned to a zone contai ni ng an emergency button.
Sends a report to the central station but provides no keypad
display or sounding.
Type 07 24-hour Audible Alarm
Assign to a zone that has an emergency button.
Sends a report to the central station, and provides an alarm
sound at the keypad, and an audible external alarm .
Type 08 24-hour Auxiliary Alarm
Assign to a zone containing an emergency button, or to a zone containing monitoring devi c es such as water or temperature sensors.
Sends a report to the central station and provides an alarm sound at the keypad. (No bell output . )
Type 09 Supervised Fire
Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm produces a pulsing bell output.
This zone type is always active and c annot be bypassed.
Type 10 Interior w/Delay
Provides entry delay (using the programmed entry time), if tripped when the panel is armed in the Away mode.
Entry Delay 1 begins whenever sensors in thi s zone are violated, regardless of whether or not an ent ry/exit delay zone was tripped first.
Bypassed when the panel is armed in the Stay or Instant modes; if armed i n Ni ght-Stay mode, zones assigned to zone list 05 (night-stay zone li st) are not bypassed when system armed in Night-Stay m ode.
Type 12 Monitor Zone
Works as a dynamic monitor of a zone fault/trouble (not alarm). In the case of a short/open, t he message, "*ALARM*-24 Hr. Non-Burg.
-#XXX " (where XXX is the zone number) will be sent to the Central Station. The system k eypad will display a “check ” message indicating the appropriate zone (but k eypad beepi ng does not occur). Upon restoral of the zone, the message, "*RESTORE*-24 Hr. Non-Burg. -#XXX " will be sent to the Central Station.
The “check” message will automat ic ally dis appear from the keypad dynamically, when the zone restores; a user code + off sequence is not needed to reset the zone.
Faults of this zone type are independent of the system, and can exist at the time of arming without interference.
Since this i s a “trouble” zone type, do not use this zone type with relays set to activate upon “alarm.”
Type 14 24 Hour Carbon Monoxide Monitor
Assigned to any zone with a carbon monoxide detector.
A carbon monoxide alarm produces keypad and detector sounding
(does not affect bell output ).
Always active and cannot be bypassed.
Type 15 Medical
Usually assigned to a zone contai ni ng an emergency button.
Sends report to the central station (CID code 100) and sounds alarm
at the keypad (no bell output).
UL Installations: may not use this zone type in UL installations .
Type 16 Fire w/Verification
Causes a fire alarm when zone is shorted, but only after alarm verified.
Verifies alarm by resetting smoke detectors after short is detected
(removes power 7 seconds for zone 1, 3 s econds for trigger output). Another short circuit withi n 90 seconds triggers fire alarm.
Provides a trouble response when zone is open.
Type 20 Arm-Stay (BR only)
Arms the syst em in Stay mode when the zone is activated.
Pushbutton units send the user number to the central station when
arming or disarming.
User number for button m ust be assigned.
Type 21 Arm-Away (BR only)
Arms the syst em in Away mode when the zone is activated.
Pushbutton units send the user number to the central station when
arming or disarming.
User number for but t on must be assigned.
Type 22 Disarm (BR only)
Disarms the system when the zone is activated.
User number for but t on must be assigned.
Type 23 * No Alarm Response
Can be used on a zone when an output relay action i s desired, but with no accompanying alarm (e.g., lobby door access).
Type 24 Silent Burglary
Usually assigned t o al l sensors or contacts on exterior doors and windows where bells and/or sirens are NOT desired.
Provides an inst ant al arm, with NO audible indication at any keypad or external sounder, if the zone is fault ed when the s ys tem is armed in the Away, Stay, Instant, or Maximum modes.
A report is sent t o the central station.
Type 77 Keyswitch
Assign to zone wired to a keyswitch.
Do not use input type “B R” devi ces with this zone type.
Type 81 AAV Monitor Zone
Assign to zone connected t o AAV module.
Monitors 2-way voice sessions as follows:
- When the zone i s faulted, all alarm sounding and dialer reporting
stops, except for fire alarms, which immediately termi nate the voice session and cause a f i re report to be sent.
- When t he zone i s restored (session ended), sounding resumes (i f
bell timeout not expired) and reports t hat were st opped are sent.
Types 90-93 Configurable
Allows for various custom responses. Options include response to
entry/exit delays, response opens/shorts, types of alarm/trouble sounding, dial delay, and unique Contact ID report codes. Types 92 and 93 can only be programmed via downloader. UL ins tallations: Zone Types 90 -93 may not be used as fire or burgl ar al arm zones on fire or UL burglar alarm instal l ations.
The system can still be armed when these zone types are faulted.
– 25 –
UL NOTICES
1. Entry Delay No. 1 and No. 2 (fields ∗35, ∗36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds.
2. For UL Commercial Burglar Alarm and UL Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60 seconds.
3. The maximum number of reports per armed period (field ∗93) must be set to “0” (unlimited) for UL installations.
4. Periodic testing (see scheduling mode) must be at least every 24 hours.
5. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations (Aux power 500mA max.).
6. All partitions must be owned and managed by the same person(s).
7. All partitions must be part of one building at one street address.
8. If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.
9. For UL commercial burglar alarm installations the control unit must be protected from unauthorized access. The tamper switch installed to protect the control unit enclosure door is suitable for this purpose.
10. Remote downloading without an alarm company technician on-site (unattended downloading) is not permissible for UL installations.
11. Auto-disarming is not a UL Listed feature.
12. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and residential applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to a remote monitoring
location, or to delay the energizing of a local alarm sounding device to permit the alarm system user to enter and disarm the system, or to arm the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security, b) 120 seconds for a system without standard line security or encrypted line security, or c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
13. This control is not intended for bank safe and vault applications.
SIA QUICK REFERENCE GUIDE
1. 31 Single Alarm Sounding per Zone: If “0” selected, “alarm sounding per zone” will be the same as the “number of
reports in armed period” set in field 93 (1 if one report, 2 if 2 reports, unlimited for zones in zone list 7).
2. 34 Exit Delay: Minimum exit delay is 45 seconds.
3. 35/*36 Entry Delay 1 and 2: Minimum entry delay is 30 seconds.
4. 37 Audible Exit Warning: Feature always enabled; field does not exist.
5. 39 Power Up in Previous State: Must be “1,” power up in previous state.
6. 40 PABX Access Code or Call Waiting Disable: If call waiting is used, call waiting disable option in field *91 must be
set.
7. 50 Burglary Dial Delay: Delay must be minimum of 30 seconds.
8. 59 Exit Error Alarm Report Code: Always enabled.
9 68 Cancel Report Code: Default is “code enabled.”
10. 69 Recent Closing Report Code: Always enabled.
11. 91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call Waiting Disable must be set to
“1” (enabled).
12. 93 No. reports in Armed Period: Must be set for 1 or 2 report pairs.
13. Cross zone timer programming is set in field 85; cross zone pairs are assigned in zone list 4 using 81 Zone List
mode.
14. Duress code is assigned by using the “add a user code” procedure found in the User Guide. Enable Duress code
reporting by programming zone 92 using 56 Zone Programming mode.
15. Fire alarm verification is a built-in system feature when a zone is programmed for zone type 16.
– 26 –
WORKSHEET for SCHEDULES
(installer code + [#] + [6] [4];
for both controls; VISTA-15PMT supports up to 8 schedules, VISTA-20PMT supports up to 32 schedules
No. Event Device No. Group No. Partition Start Time/ Stop Time/ Repeat Random
(see list below) for “01” events: for “02” events: for “04-06” events: Days Days (1-4) (yes/no) enter 01-18 enter 1-8 enter 1, 2, or 3
(VISTA-20PMT)
01 02 03 04 05 06 07 08 [V15P: 11] [V15P: 5am/tue] [V15P: 4] [V15P: 1] 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 [V20P: 11] [V20P: 5am/fri] [V20P: 4] [V20P: 1]
Events: Master/Installer Installer Only 00 = clear event 04 = forced STAY arm 10 = display custom words 8-10 01 = device on/off 05 = forced AWAY arm 11 = periodic test report 02 = user access 06 = auto disarm 03 = latch key report 07 = display “reminder” Repeat Options: 0 = none; 1 = repeat weekly; 2 = repeat every other week; 3 = repeat every third week; 4 = repeat every fourth week
master code can only acces s schedules 01-16 for VISTA-20PMT, 01-04 for VI S T A-15PMT, and events 00-07
)
– 27 –
WORKSHEET for ∗∗∗56 ZONE PROGRAMMING
(VISTA-15PMT supports up to 32 zones: 1-6, 9-34, 49-56) [default shown in brackets]
NOTES:
Zone Type: see chart in 56 Zone Programming Menu Mode section;
Report Code: enabled if any digit entered as 1st digit;
Hardwire Type (zns 2-8):
0 = EOL 3 = ZD 1 = NC 4 = DB 2 = NO
Input Type:
2 = AW (zones 9-48) 3 = RF (zones 9-48) 4 = UR (zones 9-48) 5 = BR (zones 49-64) NOTE: Zones 9-16 not available if zone doubling enabled.
Response Time:
0 = 10msec 1 = 350msec 2 = 700msec 3 = 1.2 sec
Reserved Zones
91 = addressable device
report enable/disable
default zone type =
[05].
92 = Duress report
enable/disable
Zone Zn Type Part. Report Hardwire
1 2 3 4 5 6 7 8
Zone Zn Type Part. Report Input Type Loop Serial No. Location
[09] [1] [10] [EOL] [1] [01] [1] [10] [EOL] [1] [03] [1] [10] [EOL] [1] [03] [1] [10] [EOL] [1] [03] [1] [10] [EOL] [1] [03] [1] [10] [EOL] [1] [03] [1] [10] [EOL] [1] [03] [1] [10] [EOL] [1]
Type
Rsp. Time Location
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 95 96 99
[1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1]
[1] [09] N/A [15] N/A [06] N/A
[01,00] [01,00] [01,00]
[BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR]
N/A N/A N/A
keypad [1] / [∗] N/A N/A N/A keypad [3] / [#] N/A N/A N/A
keypad [∗] / [#]
– 28 –
WORKSHEET for ∗∗∗57 FUNCTION KEY PROGRAMMING
Option Function
01 Paging 02 Time Display 03 Arm AWAY 04 Arm STAY 05 Arm NIGHT-STAY 06 Step Arming 07 Device Activation Device: 08 Comm. Test 09 Macro Key 1 Assign each macro key to only a single partition. 10 Macro Key 2 Assign each macro key to only a single partition. 11 Macro Key 3 Assign each macro key to only a single partition. 12 Macro Key 4 Assign each macro key to only a single partition. 00 Emergency Keys: zone 95 zone 99 zone 96 paging
Personal Emergency n/a Silent Alarm n/a Audible Alarm n/a Fire n/a
Emergency Keys: A = paired keys [1] / [] (zone 95); B = paired keys [] / [#] (zone 99); C = paired keys [3] / [#] (zone 96) † There are only four macros system-wide.
A
P1 P2 com B P1 P2 comC P1 P2 comD P1 P2 com
Comments
WORKSHEET for ∗∗∗79 RELAY/POWERLINE CARRIER DEVICE PROGRAMMING
(Must program before using *80)
OUTPUT TYPE Relay X10 Output No. 01
02 03 04 05 06 07 08
Module Addr.
Pos
(1-4)
Unit
Description
No.
OUTPUT TYPE (09-16 apply to VISTA-20PMT only) Relay X10 Output
Module
No.
Addr.
09 10 11 12 13 14 15 16
On-Board Trigger 1 norm output =
17
On-Board Trigger 2 norm output =
18
Pos
(1-4)
Unit No.
Description
WORKSHEET for ∗∗∗81 ZONE LIST PROGRAMMING
Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the data during the displays and prompts that appear in sequence.
NOTE: Record desired zone numbers below, noting that a list may include
List No. Used For Contains These Zones
01 General Purpose (GP) 02 General Purpose 03 Chime-by-Zone or GP (see field *26 for Chime-by-Zone option) 04 Cross Zones
NOTE: Cross zoning takes effect only after Exit Delay expires. See field *85 for Timer option.
05 Night-Stay Zones or GP 06 Dial Delay Disable (see field *50 for Dial Delay Disable option)
07 Unlimited Reports (see field *93 for Unlimited Reports option) 08 General Purpose
09 Zones activating pager 1 10 Zones activating pager 2 11 Zones activating pager 3 (VISTA-20PMT) 12 Zones activating pager 4 (VISTA-20PMT)
any
or
all
of system's zone numbers.
– 29 –
WORKSHEET for ∗∗∗80 OUTPUT FUNCTION PROGRAMMING
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you
enter the data during the displays and prompts that appear in sequence.
1. For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
Notes:
2. For Powerline Carrier devices (plcd), field
27 must be programmed with a House Code.
3. Tampers of expansion units cannot be used to operate devices.
Function
Number (V20P=1-48) (V15P=1-24)
ZONE TYPE/SYSTEM OPERATION – Choices for Zone Types are:
00 = Not Used 05 = Trouble Day/Alarm Night 10 = Interior w/Delay 23 = No Alarm Response 01 = Entry/Exit#1 06 = 24 Hr Silent 12 = Monitor Zone 24 = Silent Burglary 02 = Entry/Exit#2 07 = 24 Hr Audible 14 = Carbon Monoxide§§ 77 = Keyswitch 03 = Perimeter 08 = 24 Hr Aux 15 = Medical 81 = AAV Monitor Zone
04 = Interior Follower 09 = Fire 16 = Fire w/Verification 90-91 = Configurable
Choices for System Operation are: 20 = Arming–Stay 38 = Chime 58 = Duress 21 = Arming–Away 39 = Any Fire Alarm 60 = AAV Trigger 22 = Disarming (Code + OFF) 40 = Bypassing 61 = AVS/GSMV session begin § 31 = End of Exit Time 41 = **AC Power Failure 62 = AVS/GSMV session end § 32 = Start of Entry Time 42 = **System Battery Low 66 = Function key† 33 = Any Burglary Alarm 43 = Communication Failure 67 = Bell Failure
36 = **At Bell Timeout*** 52 = Kissoff 68 = TELCO Line Fault 54 = Fire Zone Reset 78 = Keyswitch red LED††† 79 = Keyswitch green LED†††
Activated by 0=delete 1=zn list 2=zn type 3=zn no.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
Activation Type and Detail Event (for zone list/activated by)Output
Zone List
1-8 = list
(ZL)
Zone Type
(ZT)
(see table
below)
Zone No.
(ZN)
00=none
V20P: 01-64 V15P: 01-06,
09-34, 49-56
Partition
Number
(P)
(if using ZT trig)
0 = any 1 = partition 1 2 = partition 2 3 = common
By Zone List
0 = restore 1 = alarm 2 = fault 3 = trouble
Action
By Zone No.
0 = restore 1 = alrm/flt/trbl
** Use 0 (any) for Partition No. (P) entry. *** Or at Disarming, whichever occurs earlier. † Use *57 Menu mode to assign the function key. †† Duration is set in program field *177. ††† Device action not used for these choices.
§ automatically set when appropriate AVS Quick Command performed.
0 = off 1 = close 2 secs 2 = stay closed 3 = pulse 4 = toggle 5 = duration 1 6 = duration 2
§§ when used with an output function, the carbon monoxide zone type activates only upon CO alarms. Does not activate for trouble conditions.
Note: In normal operation mode: Code + # + 7 + NN Key Entry starts Device Code + # + 8 + NN Key Entry stops Device
V20P=1-18 V15P=1-8,
17, 18
†† ††
Output
Number
Device
Type
R = relay T = trigger X = X10
30
TABLE OF DEVICE ADDRESSES
This Device Uses Address Reports as †† Enabled By
RF Receiver 00 100 *56 zone programming: input device type entry AUI (touchscreen) 1 01 n/a Automatic if field *189 enabled for AUI 1 AUI (touchscreen) 2 02 n/a Automatic if field *189 enabled for AUI 2 AUI (touchscreen) 3 05** n/a Automatic if field *189 enabled f or AUI 3 AUI (touchscreen) 4 06** n/a Automatic if field *189 enabled f or AUI 4 Communication Devi ce (LRR) 03 103 automatic if communication device enabled in *29 menu mode 4286 Voice Module 04 104 autom at i c if phone module access code field *28 enabled Zone Expanders (4219/4229):
module 1 (for zones 09 - 16) module 2 (for zones 17 - 24) module 3 (for zones 25 - 32) module 4 (for zones 33 - 40) module 5 (for zones 41 - 48)
Relay Modules (4204):
module 1 module 2 module 3 module 4
Keypads:
keypad 1 keypad 2 keypad 3 keypad 4 keypad 5 keypad 6 keypad 7 keypad 8
07
08 09** 10** 11**
12
13 14** 15**
16
17
18
19
20
21
22
23
107 108 109 110 111
112 113 114 115
n/a n/a n/a n/a n/a n/a n/a
n/a RIS Communication 25 n/a automatic 5800TM Module 28 n/a automatic
** These module addresses apply to VISTA-20PMT only. †† Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable addressable device
reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification keypad display options.
*56 zone programming: input device type entry, then:
automatic if zone no. 9-16 entered as AW type or relay assigned automatic if zone no. 17-24 entered as AW type or relay assigned automatic if zone no. 25-32 entered as AW type or relay assigned automatic if zone no. 33-40 entered as AW type or relay assigned automatic if zone no. 41-48 entered as AW type or relay assigned
*79 output device programmi ng: device address prompt:
entered at device address prompt entered at device address prompt entered at device address prompt entered at device address prompt
data field programming as listed below:
always enabled, all sounds enabled. data field *190 data field *191 data field *192 data field *193 data field *194 data field *195 data field *196
5800 SERIES TRANSMITTER INPUT LOOP IDENTIFICATION
All of the transmitters illustrated have one or more unique factory assigned input (loop) ID numbers. Each of the inputs requires its own programming zone transmitter not shown, refer to the instructions accompanying that transmitter for details regarding loop numbers, etc.
UL NOTE: The following transmitt ers are not intended for use in UL installations: 5802MN, 5802MN2, 5804, 5804B D, 5814, 5816TEMP,
5819, 5819WHS & BRS, and 5850. The 5827BD and 5800TM can be used in UL Listed Residenti al Burglar installations.
LOOP
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
1
5800CO
ENROLL AS "RF"
ON
OFF
5804/5804E
ENROLL AS "BR"
5816
ENROLL AS
5821
ENROLL AS
LOOP 3
LOOP 2 LOOP 1
LOOP 2 (REED)
LOOP 1 (TERMINALS)
"RF"
LOOPS
1 - 3
"RF"
LOOP
1
5800Micra
ENROLL AS "RF"
LOOP 2
LOOP 4 YOU MUST ENROLL
ENROLL AS
SET HOUSE ID
LOOP 2
5816MN
ENROLL AS
ARMED
READY
5828/5828V
SET HOUSE ID
THIS BUTTON
LOOP 1
"BR"
LOOP 2 (REED)
LOOP 1 (TERMINALS)
"RF"
MIC
MESSAGE
LOOP
3
5804BD/5804BDV
ALTERNATE
POSITION FOR
(e.g., a 5804's four inputs require four programming zones). For information on any
5801
ENROLL AS "UR OR"RF"
LOOP 1
5809
ENROLL AS
5819
"RF"
LOOP 3
LOOP 2
LOOP 1
"RF"
LOOP 1 (TERMINALS)
LOOP 1 (MOTION)
"RF"
LOOP 1
5802 MN
ENROLL AS
"UR" OR "RF"
5814
ENROLL AS
LOOP 2 (REED)
LOOP 3
(TERMINALS)
5819S (WHS & BRS)
ENROLL AS
5894PI
ENROLL AS
"RF"
"RF"
"RF"
LOOP 1
LOOP 1 (INTERNAL SHOCK SENSOR
LOOP 1
LOOP 1
5802 MN2
"UR" OR "RF"
LOOP 2 (REED)
ENROLL AS
5820/5820L
ENROLL AS
ENROLL AS
ENROLL AS
5815
5897-35
LOOP 2 (REED)
LOOP 1 (TERMINALS)
"RF"
LOOP 1
"RF"
LOOP 1
"RF"
LOOP 1
5800SS1
ENROLL AS "RF"
SERIAL #1
LOOP 3
SERIAL #1
LOOP 4
SERIAL #2
LOOP 3
SERIAL #2 - LOOP 1 = ON + 4 BUTTONS
5817
ENROLL AS
LOOP
1
5853
ENROLL AS
SERIAL #1
OFFON
LOOP 2
21
SERIAL #1
43
LOOP 1 SERIAL #2
LOOP 2
LOOP 4 = 3 + 4 BUTTONS
5805-6
ENROLL AS
"BR"
LOOP 1 (PRIMARY)
LOOP 2 (AUX. CENTER)
LOOP 3 (AUX. RIGHT)
"RF"
SERIAL #2 - LOOP 1 = ON + 4 BUTTONS
"RF"
SERIAL #1
SERIAL #1
SERIAL #2
5800WAVE
SET HOUSE ID
ENROLL AS"RF"
5806/5806W3
5808/5808LST/5808W3
ENROLL AS
LOOP 1
5818MNL
ENROLL AS
LOOP 3
AWAY
STAY
1
LOOP 4
2
3
4
LOOP 3
LOOP 4 = 3 + 4 BUTTONS
5878
ENROLL AS
"RF"
"BR"
LOOP 1
LOOP 1
SERIAL #1 LOOP 2
SERIAL #1 LOOP 1
SERIAL #2 LOOP 2
"RF"
(TERMINALS)
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
LOOP 2
(REED)
LOOP 3
ENROLL AS
5890/5890PI
ENROLL AS
5800-004-V0
– 31 –
EOL
POWER
RED
+
BLK
4-WIRE SMOKE DETECTOR CONNECTIONS
RELAY
5
AS ZONE TYPE 54
PROGRAM RELAY
+
(FIRE ZONE RESET)
OUTPUT
AUX PWR
TERMINALS
SET UNITS
DIP SWITCH
FOR DEVICE
ADDRESSES
-AND/OR-
ADEMCO No. 4229
ADEMCO No. 4219
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
WIRED EXPANSION/RELAY MODULE
TRANSFORMER
8-PIN CONNECTOR
USED FOR 1361X10
SEE INSTRUCTIONS.
ON-BOARDTRIGGERS
CONNECTIONS AND FOR
FUSE NOTE
MAY HAVE PTC IN
BATTERY FUSE
(IF INSTALLED)
FOR REPLACEMENT,
USE SAME VALUE
(e.g. ADEMCO No. 90-12)
3A
SUPERVISION
RELAY MODULE
EOLR-1
USE N.O.
CONTACT,
WHICH CLOSES
WHEN POWER
IS APPLIED.
N.O.
VIOLET
2000
OHMS
EOLR
+
DETECTOR
4-WIRE SMOKE
OR COMBUSTION
N.C.
TO OUTPUT 17
4
CONTACT OPENS MOMENTARILY
UPON FIRE ALARM RESET
MAX. CURRENT = 100 mA
"OUT NORM LOW" = YES IN
PROGRAM OUTPUT 17 FOR
TYPE 54 IN 80 MENU MODE
OR
79 MENU MODE AND AS ZONE
7 - 15
SEE
INSTRUCTIONS.
SET
RECEIVERS
DIP SWITCH
FOR DEVICE
AND/OR
-AND/OR-
RF RECEIVER
ADEMCO 5881*Type
OUTPUT RELAYS)
(4 OUTPUT RELAYS)
ADEMCO No. 4204 RELAY MODULE
(8 ADD'L EOLR WIRED ZONES PLUS 2
BLK
RED
GRN
YEL
OPTIONAL
TO
TRANS.
CABLE)
(USE SA4120XM-1
COM
DATA
SYNC
78
1234 5 6
PLACE OF FUSE.
GND
FLYING LEADS
FOR BATTERY
BLACK
RED
(TRIG. 2)
+12 AUX
(TRIG. 1)
CONNECTION
HEAT
DETECTOR
TO ZONE TERM. ( )
TO ZONE TERM. ( )
(ZONES 2 8 ONLY)
ADDRESS
OF 0.
SEE
INSTRUCTIONS.
WIRELESS ZONES
*5882 IN CANADA
5881L: UPTO 8
5881M: UPTO 16
5881H: UPTO 56
BLK
RED
GRN
YEL
( FROM EITHER OR BOTH GROUPS)
FOR UPTO 40 ADDITIONAL ZONES
BLK
YEL
RED
GRN
TOTERM 4
TOTERM 5
TOTERM 6
TOTERM 7
OUTPUT 18
OUTPUT 17
RING
(RED)
}
TIP
(GREEN)
RING
(GRAY)
}
21 22 23 24 25
TIP
(BROWN)
HI
20
LO
19
LO HI
18
HI
17
LO
16
LO
HI
15
HI
14
LO
13
LO
HI
12
HI
11
LO
10
9
LO
HI
78
6
5
4
3
12
EARTH
GROUND
INCOMING
PHONE LINE
HANDSET
}
AUX. POWER
SEE
GROUNDING
FOR PROPER
INSTRUCTIONS
CONNECT CORD)
*CA38A IN CANADA
TELEPHONEWIRING
(VIA RJ31X* JACK AND DIRECT
+
)
FOR UL
OUTPUT
600mA MAX.
(500mA MAX.
10.5-13.8VDC
TO 110VAC
UNSWITCHED
OUTLET (24hr)
DOC LOAD NO.: 3
FOR CONNECTION OF OPTIONAL 4286 VIP MODULE
VISTA-20PMT ONLY
ZONE 8
ZONE 7
ZONE 6
ZONE 5
ZONE 4
ZONE 3
ZONE 2
ZONE 1
LIMITED.
ARE POWER
ALL OUTPUTS
INSTALLATIONS)
ALARM OUTPUT
10.5–13.8VDC, 2A MAX. (600mA
TO PREVENT RISK OF SHOCK,
COMPLIES WITH FCC RULES, PART 68.
FCC REGISTRATION NO. 5GBUSA-44003-AL-E
DISCONNECT TELEPHONE LINE ATTELCO
WARNING:
TO PHONETERMINALS, SEE INSTRUCTIONS.
2000
EOLR
OHMS
2000
EOLR
OHMS
2000
EOLR
OHMS
2000
EOLR
OHMS
2000
EOLR
OHMS
MAXIMUM LOOP RESISTANCE:(EACH ZONE) 300 OHMS (PLUS EOLR)
RESPONSE, ZONES 1-8:10, 350, OR 700 MSEC (PROGRAMMABLE)
2000
EOLR
OHMS
2000
EOLR
OHMS
2000
EOLR
OHMS
YELLOW: KEYPAD DATA OUT GREEN: DATA IN FROM KEYPAD
RED: KEYPAD PWR (
REMOTE
BLK
BLACK: KEYPAD GROUND (- ) RETURN
NOTE:
KEYPAD (S)
CURRENT (IN
OR 12V BELL. SEE
MAX. FOR UL USAGE,
INCLUDING AUX POWER)
TEMPORAL PULSE SOUNDING
FOR FIRE. CAN USE 702 SIREN,
STEADY FOR BURGLARY/PANIC,
RINGER EQUIVALENCE: 0.1B.
JACK BEFORE SERVICINGTHIS UNIT.
POWER SHUTDOWN NOTE:
SYSTEM SHUTS DOWN SENSOR
DETECTION PROCESSING IF
ZONE
PAIRS
10 11
MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16;
DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".
2k
1312 14
TAMPER
CONTACTS
2k
CAN BE USED FOR 2-WIRE SMOKE DETECTORS
DEVICES
KEYPADS
4286, GSMV,
AND OTHER
(e.g. 5800TM,
ADDRESSABLE
BOTH
PARTITIONS)
AND ALL
OTHER DEVICES
DRAWING
POWER FROM
SUPERVISION, ENABLE
FIELD 91 AND CONNECT
INSTRUCTIONS. FOR BELL
820 OHM RESISTOR DIRECTLY
ACROSS EXTERNAL SOUNDER.
WEEKLYTESTING IS REQUIRED TO ENSURE PROPER OPERATION OFTHIS
SYSTEM. IN ADDITION,THIS SYSTEM MUST BE CHECKED BY A QUALIFIED
TECHNICIAN AT LEAST ONCE EVERYTHREE (3)YEARS.
CONTROL'SVOLTAGE DROPS
BELOW 9.6V.
2 / 10
3 / 11
4 / 12
5 / 13
6 / 14
7 / 15
3k
ZONE 2
2k
TAMPER
CONTACTS
2k
4219, 4229,
4204, 5881)
REMOTE KEYPADS
CAN USE 6150 OR 6160
TERMS 4 & 5
MUST BE
INCLUDED IN
AUX CURRENT
DRAIN
FOR COMPLETE
INFORMATION, SEE
AND K0681V1 OR LATER.
INSTRUCTIONS K5305-1V9
V20PMT_V15PMT-SOC-V5
ALL DEVICES AND ACCESSORIES USED IN A CANADIAN
INSTALLATION MUST BE LISTED FOR USE IN CANADA
8 / 16
6.2k
ZONE DOUBLING
(VISTA-20PMT ONLY)
TYPICALWIRING FOR
ZONE 10
2k
ZONE 4
VIST A-20PMT , VIST A-15PMT
2k
(VISTA-20PMT ONLY)
TYPICALWIRING FOR
ZONE 3
KEYPADS. LOCAL
PROGRAMMING
MUST BE DONE WITH A
6160, BUT NEED NOT
CALCULATIONS.
Reference: MTV15P
SUMMARY OF CONNECTIONS
DOUBLE BALANCED ZONE
REMAIN IN THE SYSTEM
(SET TO ADDRESS 16).
MTV20P
AT LEAST ONE UL LISTED KEYPAD
UL LISTED LOCAL BELL
(e.g. 6160PL2, 6150PL2)
SIA CP-01 MINIMUM REQUIREMENTS:
12V, 4AH
BATTERY
CHARGING VOLTAGE
13.8VDC. MAXIMUM
CHARGING CURRENT
BURGLARY STANDBY USE AT LEAST 4 HRS
650mA.
24-HR BATTERY STANDBY REQUIRED FOR
FIRE INSTALLATIONS. USE 12V, 17.2AH
BATTERY FOR 600mA AUX POWER. SEE
INSTRUCTIONS.
BATTERY CAPACITY FOR EMERGENCY
ÊK5305-1MTPRV9LŠ
K5305-1MTPRV9 3/11 Rev. A - SIA
16.5VAC, 25VA (e.g. ADEMCO No. 1321).
(USE No. 1321CN IN CANADA)
USE 1361X10 TRANSFORMER
INTERFACEIN PLACE OF 1321 OR
1321CN WHEN POWER LINE CARRIER
DEVICES ARE BEING USED. (SEE
INSTRUCTIONS FOR CONNECTIONS)
THIS EQUIPMENT SHOULD BE INSTALLED
IN ACCORDANCE WITH THE NATIONAL
FIRE PROTECTION ASSOCIATION'S
STANDARD 72 (NATIONAL FIRE
SEALED LEAD-ACIDTYPE.
BATTERY NORMALLY NEED NOT BE
REPLACED FOR AT LEAST 3YRS.
TO DETERMINETOTAL STANDBY LOAD
ON BATTERY, ADD 100mATO TOTAL OF
AUX. POWER OUTPUT AND REMOTE
KEYPAD CURRENTS.
USE UL LISTED LIMITED ENERGY
CABLE FOR ALL CONNECTIONS
CLASS 2 PLUG-INTRANSFORMER
PROTECTION ASSOCIATION,
12801 North Stemmons Freeway, Sui te 821
Dallas, Texas 75234
Copyright © 2006 Honeywell International Inc.
BATTERY-MARCH PARK, QUINCY,
MA 02169).
PRINTED INFORMATION DESCRIBING
INSTALLATION, TESTING, MAINTENANCE,
EVACUATION PLANNING AND REPAIR
SERVICE IS TO BE PROVIDED WITH THIS
EQUIPMENT.
CONNECTION OF THE FIRE ALARM
SIGNAL TO A FIRE ALARM
HEADQUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLYWITH THE
PERMISSION OF THE LOCAL AUTHORITY
HAVING JURISDICTION.THE BURGLAR
ALARM SIGNAL SHALL NOT BE
CONNECTED TO A POLICE EMERGENCY
NUMBER.
Loading...