Monitor SiloPatrol Operation Manual

BUL L E T I N
344F
I N S T A L L A T I O N & O P E R A T I O N
SiloPatrol
®
Auxiliary Output Enclosure (AOE)
AOE
This manual contains the information necessary to ensure a safe and successful installation. Please read and comply with the section on page 6 of this manual pertaining to SAFETY. Doing so will ensure proper oper­ation of the equipment and the safety of all personnel.
In the event that information contained herein does not completely satisfy your requirements or answer your questions, you may contact Technical Support on our website www.monitortech.com, by telephone at 800-766-6486 (630-365-9403), or by e-mail at techsupport@monitortech.com. If your AOE ever requires service either in or out of warranty, please contact us and obtain an RMA number prior to shipping the unit to us.
®
www.monitortech.com
PR E-I N STA L LA T ION C ONS I DER A TIO N S
ME CHA N IC A L I NS T A LL ATIO N
Product Identification
n the AOE, observe the specification label on the top of the
O enclosure. Verify the voltage indicated.
Choosing a Location for the AOE
1) Environment - This product is suitable for ordinary loca-
tions only. It can be used in either indoor or outdoor envi­ ronments. Note the temperature limits in the specifications.
) Placement - The hardened communication network used to
2
interconnect the SMUs, Flexars, HMI2s, and AOEs permits the ends of the network to be extended as much as 4000 feet. This permits placement of the particular product in the area best suited. For example, the HMI2 could be mounted in the main control room, and the AOEs could be mounted closest to the equipment to be controlled by the outputs thereby minimizing installation cost.
IMENSIONS ARE SHOWN IN INCHES WITH MILLIMETER EQUIVALENT IN BRACKETS
D
AOE Mounting (See Figure 1)
1) Location: Select a mounting location in accordance with the
Pre-Installation Considerations.
2) Preparation: Open the AOE cover and locate the four cor­ ner mounting locations. These mounting points are located
outside of the environmentally protected area of the enclo­ sure. Use the AOE as a template to mark the locations of the four corner mounting points.
3) Mounting: Secure the AOE to the wall with 1/4" bolts. Note
head size must be smaller than 1/2" and the bolts must be at least 1" long to reach through enclosure.
4) Accessory Mounting Brackets: If mounting through the
enclosure is undesirable, external mounting brackets can be purchased as an accessory. The brackets can be oriented vertically or horizontally.
Figure 1
2
EL ECT R IC A L I NS T A LL ATIO N
1) Permanently Connected Equipment - Disconnecting devices shall by included in the system installation. In instal-
lations where multiple circuits are used (i.e. independent cir­ cuits for power input, cycle, count and sound), individual disconnects are required. The disconnects shall be within close proximity of the equipment, accessible to operators, and marked appropriately as the disconnect for the associated circuit. Assure the disconnect ratings are appropriately sized for the circuit protected (See Specifications).
2) Circuit Separation - Two cable entry locations are provid­ ed to aid in maintaining separation of "hazardous live" (typi­ cally mains voltages such as 115Vac and 230Vac) and lim­ ited circuits (typically control voltages less than 30Vrms or
42.4VDC). However, since the SMU's single wiring com­ partment can not absolutely protect against physical contact between multiple circuits, it is required that all wiring have an insulation rating of 300v minimum, and a temperature rating of 80˚C (176˚F) minimum.
3) Protective Earthing - Each AOE is provided with a "protective conductor terminal" which shall be terminated to the local earth ground potential. This terminal shall be used to eliminate shock hazard in the unlikely event of inter­ nal insulation breakdown. Select wire size that can carry in excess of the sum of all circuit's maximum amperage.
4) Power Input - The AOE is designed to accept either 115 VAC or 230 VAC (factory set). Verify the intended voltage
supply is compatible with the voltage configuration indicated on the electronics and the external nameplate. Connect power as shown to "L1" and "N" being sure to observe polar­ ity. The AOE features a specific cord connector entry for
power suitable for a cable with a diameter of .17" through
.47". The cord connector can be removed leaving a .875 through-hole suitable for 1/2" conduit fittings.
5) Communications Link - The AOE features a cord connec-
tor entry for communications suitable for a cable with a diameter of .17" through .47". The cord connector can be removed leaving a .875 through-hole suitable for 1/2" con­ duit fittings. Interconnection of the network is performed by a 2-conductor shielded cable (such as Belden 9322). All products are interconnected in a daisy-chain, multi-drop configuration. Order of connection is not important. Communication networks such as this operate best when the interconnection has only two ends. "T"s should be avoided whenever possible. Observe polarity when making the communication interconnection (D+ and D-). Attach cable shield in terminal provided.
6) Sensor Compatibility - When using an HMI2 as the
Operator Interface, SiloPatrol SMUse’s and Flexar guided wave radar sensors may coexist on a common RS-485 com­ munication buss with an Auxiliary Output Enclosure (AOE) and the Auxiliary Output Enclosure will function properly.
When using SiloTrack Server Inventory Management software, the AOE will only function properly when connect­ ed on an RS-485 communication buss configured for the
SMU
SMU, HMI 2, AO E SYSTEM CO NNE CTI ONS
HMI2
HMI2
Figure 2
3
SiloPatrol protocol. AOE outputs can be assigned to Flexar guided wave radar sensors that reside on a separate RS-
485 communication bus properly configured for the Flexar protocol in the SiloTrack network setup screen. Please consult Bulletin 344J (SiloTrack Server).
7) Output Connections - The AOE features additional access ports for connection of required outputs. The two-card sys-
tem has eight (8) ports, four on each side of the enclosure. The four-card system has sixteen (16) ports, eight on each side of the enclosure. Each port is plugged to exclude dust and water infiltration. When needed, the plug can be removed leaving a .875 through-hole suitable for 1/2" con-
duit fittings. The output connection cabling utilized should be suitable for the environment and electrical requirements of the loads. The analog outputs are non-isolated and self­ powered. Observe polarity when making interconnection. The relay outputs are non-powered (dry) and are SPST.
SE TUP
(See Figure 3, 4, 5 and 6)
1) AOE Address Selection Switch - Each AOE must be given a unique network address that is determined by the rotary switch setting within the AOE. The network address will cor­ respond with the output link established in the operator inter­ face (HMI2 or SiloTrack network address, communication will be successful to each without error indication, however each AOE will have identical outputs. Note that the selected switch setting is denoted by the selection pointer, not the screwdriver slot (See Figure 5). Switch selections "1, 2, 3, 4" are acceptable address selections and refer to AOE addresses 1-4. Switch selection "8" will force all relays "off". Switch selection "9" will force all relays "on". Switch selection "A" will force all analog outputs to "4mA". Switch selection "B" will force all analog outputs to "20mA".
2) AOE Network Termination Switch - Each AOE has a network termination switch in close proximity to the RS-485 network terminal block. The two products of the SMU/ Flexar/ HMI2/AOE system positioned at both network ends must have their termination switches "on". The rest of the devices
on the network must have their termination switches "off".
TM
). If multiple AOEs have the same
Figure 4
Figure 3
(ARROW or DOT)
Figure 5
4
3) AOE Indicators - Three LEDs depict the status of the AOE. "Power" (green): When lit, it indicates that the AOE power
supply and firmware is functioning.
"Com Error" (yellow)
: When lit, it indicates that no network communication is being made with the AOE. This can be caused by a the absence of any operator interface (HMI2 or SiloTrackTM) links to the AOE address selected, or the halting of
communication caused by the HMI2 exiting the DSPLY mode.
"Config Error" (red)
: When lit, it indicates that an instruction being received via the network communication is being sent to an AOE card location that is "empty" or occupied by a dif­ ferent output type. A "blink" condition means two instruc tions are for the same card, one being valid (the correct out­ put type) and the second being invalid (the incorrect output type).
4) AOE System Reset Switch - Momentary closure of the pushbutton switch will "restart" the entire AOE system. All relay outputs are "shut off" and all analog outputs are forced to "4mA" until new conditions are received via the network communication and sent to the respective outputs.
5) AOE Card Positions - The analog and relay cards are uni­ versal and can be placed in any position within the AOE.
However, the card position numbers are fixed and must be ref­ erenced when establishing the link between channel number and output within the operator interface (HMI2 or SiloTrack
M
T
). Card position #1 must be in place in order to use Card position #3. Card position #2 must be in place in order to use
Card position #4.
TR O UBL ESH O OTI NG
PROBLEM: AOE's green LED is "off" indicating
operational problem
CAUSE/SOLUTION:
1) This condition is caused by the AOE unable to boot its internal software.
2) Verify electrical power is connected to the AOE.
3) Verify proper alignment of PCB-to-PCB connectors.
4) Press and release "system reset switch" to restart the AOE.
PROBLEM: AOE's yellow LED is "on" indicating a communication error CAUSE/SOLUTION:
1) This error is caused by the AOE's inability to receive any commands designated for the particular AOE address. The yellow LED will be "off" when the AOE detects that an incoming message belongs to it.
2) Verify communication connection has been made to the AOE from HMI2 or SiloTrack.
3) Verify polarity of the communication connection.
4) Verify electrical power is connected to the HMI2 or SiloTrack.
5) Verify that the HMI2 or SiloTrack has been programmed to
send data to the AOE address.
6) Verify the AOE's address selection switch matches that of the HMI2 or SiloTrack programmed link.
7) Verify that the HMI2 is in "DSPLY" mode, otherwise no AOE updates are sent resulting in this error condition after a 3­ second timeout.
Figure 6
PROBLEM: AOE red LED is "on" or "blinks" indicating a configuration error CAUSE/SOLUTION:
1) This error is caused by the mismatch of incoming data and the type of output (empty, analog or relay) that is located at the particular link location.
2) Verify the links assigned from HMI2 or SiloTrack match the
type of cards positioned in AOE. The address convention if controlled by an HMI2 is AOE # (1, 2, 3, or 4), Card Position
# (1, 2, 3, or 4), and Output # (1-4 for an analog card and 1­ 8 for a relay card). When using SiloTrack, this convention is preceded by the network # (1-8).
MA INT E NAN CE
No periodic maintenance is required for an AOE.
5
B U L L E T I N
ME CHA N IC A LS
DIMENSIONS ARE SHOWN IN INCHES WITH MILLIMETER EQUIVALENT IN BRACKETS
344F
S A FET Y
General Safety
CAUTION: It is essential that all instructions in this manual be followed to ensure proper operation of the equipment and safe­ty of operating personnel. The use of this symbol is used throughout this manual to highlight important safety issues. Please pay particular attention to these items.
Electrical Shock Caution
AOE Auxiliary Output Enclosures are powered with HIGH VOLTAGE. No operator serviceable parts are inside. All ser­vicing is to be performed by qualified personnel. Each AOE is provided with a "protective conductor terminal" which shall be terminated to earth ground potential (see Electrical Installation). This product's design complies with EN61010-1 installation category II and pollution degree 2.
Electromagnetic Compatibility (EMC)
The AOE was tested and found to comply with the standards listed below. The AOE should not be used in residential or commercial environments. Compliance to the EMC standards was demonstrated by means of a test setup using the following installation methods.
1) AOE enclosure was connected to earth ground (protective earth) .
2) Shielded cable was used to interconnect the RS-485 net­ work (connections D+ and D -). The shield drain was con­ nected to earth ground (SHD terminal) at each end.
EMC Emissions:
Meets EN 61326-1 Electrical Equipment for Control Use, EMC
EN 55011 Radiated and conducted emissions
(Class A- industrial)
EN 61000-3 Fluctuation/Flicker
Meets FCC Part 15B RF Devices, Unintentional Radiators
CISPR 11 Radiated and conducted emissions
(Class A- industrial)
EMC Immunity:
Meets EN 61326-1 Electrical Equipment for Control Use, EMC
IEC 1000-4-2 Electrostatic discharge (industrial) IEC 1000-4-3 RF radiated EM fields (industrial) IEC 1000-4-4 Electrical fast transients (industrial)
Power Requirements: 115 VAC or 230 VAC, 50/60 Hz
Power Consumption: 25 VA Max Operating Temp: -4° F to 131° F (-20° C to 55° C) Communication: RS-485 half-duplex, isolated,
proprietary protocol
Analog Outputs: 4-20mA, 16 max, 4 per card, non-
isolated, 500 ohm, 10 bit resolution, zero/span set via HMI2 or
Relay Outputs: SPST, 5A @ 250 VAC, 32 max, 8
per card, visual LED per relay, assignment and action set via HMI2
or Enclosure: Painted Aluminum Overall Dimensions: 11.02" x 9.05" x 4.33" (280mm x
230mm x 110mm)(2-card) (Hght x Wdth x Dpth) 15.74" x 9.05" x 4.33" (400mm x
230mm x 110mm)(4-card) Certifications/Protection: NEMA 4, IP66, CE Mark
IEC 1000-4-5 Electrical surges (industrial) IEC 1000-4-6 RF conducted EM energy (industrial) IEC 1000-4-8 Power frequency magnetic fields
(industrial)
IEC 1000-4-11 Source voltage deviation
Monitor Technologies LLC warrants each AOE it manufactures to be free from defects in material and workmanship under normal use and service for two (2) years from the date of purchase. The purchaser must notify Monitor of any defects within the warranty period, return the product intact, and prepay transportation charges. The obligation of Monitor Technologies LLC under this warranty is limited to repair or replacement at its factory. This warranty does not apply to any product which is repaired or altered outside of Monitor Technologies’ factory, or which has been subject to misuse, negligence, accident, incor­rect wiring by others, or improper installation. Monitor Technologies LLC reserves the right to change the design and/or specifications without prior notice.
Monitor Technologies LLC
44W320 Keslinger Rd. tElburn, IL 60119 t630-365-9403 t800-766-6486 ttechsupport@monitortech.com twww .mon itortech.co m
GDR JSC AUG 04 2017 DOC-001-344F 3
SP ECI F IC A TIO N S
SiloTrack
CHINA RoHS 2
WA R RAN T Y
SiloTrack
Loading...