Monessen Hearth Systems PH18NM, PH18NV, PH24NM, PH24NV, PH18PM Installation Manual

...
PH Gas Logs
INSTALLATION
BEFORE FULLY INSTALLING THE UNIT:
Turn OFF the gas supply to the replace or re-
box.
located on the oor or wall of the replace. If left
unsealed, drafting may cause pilot outage or soot-
ing. Use a heat resistant sealant. Do not seal the
chimney ue damper.
Before installing in a solid fuel burning fireplace, The chimney flue and firebox must be cleaned of soot, creosote, ashes and loose paint by a qualified chimney
WARNING
cleaner.
INSTALLING VENTED APPLICATIONS
Manual and millivolt controlled gas logs may be installed as
a vented decorative log set in compliance with ANSI Z21.60 and National Fuel Gas Code, Section 6.6 Since, the gas
logs are operated with the damper open, non-combustible
material and minimum mantel requirements do not apply.
NOTE: The use of a thermostat is prohibited in vented log
applications.
This appliance is for installation only in a solid fuel burning replace (masonry replace or manufactured fireplace) with a working ue and constructed of noncombustible
material.
Exception: DO NOT install this appliance in a factory-built fireplace that includes
WARNING
instructions stating that it has not been tested or should not be used with unvented gas logs. This log set may be installed as a
vented log set.
BEFORE INSTALLING THE APPLIANCE:
Turn off gas supply to replace or rebox.
Have the replace oor and chimney professionally
cleaned to remove ashes, soot, creosote or other
obstructions. Have this cleaning performed annually after installation.
Seal any fresh air vents or ash clean-out doors lo-
cated on oor or wall of replace. If not, drafting may cause pilot outage or sooting. Use a heat-resistant sealant. Do not seal chimney ue damper.
Install and operate the appliance as directed in this
manual.
DAMPER STOP INSTALLATION:
A damper stop must be provided with the unit. Contact your dealer to obtain one. The damper stop must be installed as shown in Figure 11 to prevent full closure of the replace damper blade and provide a minimum 29 square inch ue opening.
Damper Stop
Damper
FP2538
Figure 11 ­Damper Stop Installation (See Warning)
The replace and gas logs function as a system. If the replace is spilling into the room (check with a match or a smoke stick), reposition the damper clamp until a positive draft is obtained by opening the damper. If negative pressure in home prevents having
WARNING
a positive draft, contact your dealer for
assistance.
PLACE AND SECURE APPLIANCE
You must secure the gas log heater to
the replace oor. If not, the entire unit
may move when you adjust the controls. Movement of unit may cause shifting of the gas logs which leads to sooting and
improper burning.
Special care is required if you are installing the unit into a sunken replace. You must raise the replace oor to allow access to
WARNING
gas log controls. This will insure adequate air ow and guard against sooting. Raise the replace oor using noncombustible materials, as described in Placement in a
Fireplace with Restrictive Barrier on Page
7.
12
Monessen • PH18/24 Installation/Owner's Manual • 65D2035 • Rev E • 01/19
INSTALLATION
PH Gas Logs
ASSEMBLY PROCEDURE
1. Center the gas log unit in the replace or rebox.
2. Install Grate: Insert longest middle grate bar in one of the two square holes in control panel. Figure 12. Be sure grate is centered. Sit horizontal bar inside two hooks on front of control panel. Figure 12. Make certain front feet of grate are located inside front edge of replace or rebox.
3. Anchor holes are located on the ange of the unit. Figure
12. After centering the burner correctly, mark the hole positions on the replace/rebox oor. Drill two (2) 5/32"
diameter holes approximately 11⁄2" deep.
4. Anchor the unit to the replace/rebox oor using the screws provided. Figure 13.
Screws
Hole for Grate Bar
Use new black iron or steel pipe. Internally tinned copper or copper tubing can be used per National Fuel Code, section 2.6.3, providing gas meets hydrogen sulfide limits, and where permitted by local codes. Gas piping system must be sized to provide minimum inlet pressure (Listed on Data Plate) at the maximum ow rate (BTU/Hr). Undue pressure loss will occur if the pipe
is too small.
CAUTION
A manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pressure tapping point should be installed upstream of the appliance. Figure 13
Stainless Flexible Tube
To Heater Valve
Pipe
Possible Locations for Pressure Tapping Point
Middle Grate Bar
Hooks for Grate
Horizontal Grate Bar
Figure 12 ­Install Grate and Secure Heater to Floor of Fireplace/Firebox
Anchor Hole
CONNECT THE GAS LINE
NOTICE: A qualied gas appliance installer must
connect the heater to the gas supply. Consult all local codes.
Pipe Coupling
Manual Shutoff Valve
Figure 13 ­Gas Connection
Gas Supply Inlet
FP2371
IMPORTANT: Hold heater valve rmly with a wrench to prevent movement when connecting to inlet pipe.
CHECK GAS TYPE: The gas supply must be the same as stated on the heater’s rat­ing plate. If the gas supply is different, DO
NOT INSTALL THE HEATER. Contact your
WARNING
dealer for the correct model.
Connecting directly to an unregulated pro­pane/LPG tank can cause an explosion.
WARNING
Always use an external regulator for all propane/LPG heaters and high pressure one to two-pound systems
only, to reduce the supply tank pressure to a maximum of
13" w.c. This is in addition to the internal regulator in the heater valve.
Monessen • PH18/24 Installation/Owner's Manual • 65D2035 • Rev E • 01/19
13
Loading...
+ 1 hidden pages