VFC Vent Free Fireplace System
Installation & Operating Instructions
Models: VFC24C, VFC24L, VFC32C & VFC32L
WARNING: If the information in this
manual is not followed exactly, a re or
explosion may result causing property
damage, personal injury or loss of life.
• Do not store or use gasoline or other
ammable vapors and liquids in the
vicinity of this or any other appliance.
• WHAT TO DO IF YOU SMELL GAS
– Do not try to light any appliance.
– Do not touch any electrical switch; do
not use any phone in your building.
– Leave the building immediately.
– Immediately call your gas supplier from
a neighbor's phone. Follow the gas
supplier's instructions.
– If you cannot reach your gas supplier,
call the re department.
• Installation and service must be performed
by a qualied installer, service agency or
the gas supplier.
This is an unvented gas-red heater. It uses air
(oxygen) from the room in which it is installed.
Provisions for adequate combustion and ventilation air must be provided. Refer to Page 8.
Please leave these instructions with the appliance.
OWNER
Please retain these instructions for future reference
.
WARNING:
• Any change to this heater or its controls can be dangerous.
• Improper installation or use of the heater can cause serious injury or death from re, burns,
explosion or carbon monoxide poisoning.
• Do not allow fans to blow directly into the replace. Avoid any drafts that alter burner ame
patterns.
• Do not use a blower insert, heat exchanger insert or other accessory, not approved for use with
this heater where applicable.
1. Due to high temperatures, the appliance should be
located out of trafc and away from furniture and
draperies.
2. Children and adults should be alerted to the hazard
of high surface temperature and should stay away
to avoid burns or clothing ignition.
3. Young children should be carefully supervised when
they are in the same room with the appliance.
4. Do not place clothing or other ammable material
on or near the appliance.
5. Any safety screen or guard removed for servicing
an appliance, must be replaced prior to operating
the heater.
6. Installation and repair should be done by a qualied
service person.
7. To prevent malfunction and/or sooting, an unvented
gas heater should be cleaned before use and at
least annually by a professional service person.
More frequent cleaning may be required due to
excessive lint from carpeting, bedding materials,
etc. It is imperative that control compartments,
burners and circulating air passageways be kept
clean.
8. CARBON MONOXIDE POISONING: Early signs of
carbon monoxide poisoning are similar to the u with
headaches, dizziness and/or nausea. If you have these
signs, obtain fresh air immediately. Have the heater
serviced as it may not be operating properly.
9. The installation must conform with local codes or, in
the absence of local codes, with the National Fuel
Gas Code, ANSI Z223.l/NFPA54.
10. This unit complies with the latest edition of ANSI
Z21.11.2–2013, Unvented Heaters.
11. Do not install the heaters in a bathroom or bedroom.
12. Correct installation of the refractory cement logs,
proper location of the heater, and annual cleaning are
necessary to avoid potential problems with sooting.
Sooting, resulting from improper installation or operation, can settle on surfaces outside the replace. See
log placement instructions for proper installation.
13. Avoid any drafts that alter burner ame patterns. Do not
allow fans to blow directly into replace. Do not place
a blower inside burn area of rebox. Ceiling fans may
create drafts that alter burner ame patterns. Sooting
and improper burning will occur.
14. CAUTION: Candles, incense, oil lamps, etc. produce
combustion byproducts including soot. Vent-free
appliances will not lter or clean soot produced by
these types of products. In addition, the smoke and/
or aromatics (scents) may be reburned in the vent-free
appliance which can produce odors. It is recommended
to minimize the use of candles, incense, etc. while the
vent-free appliance is in operation.
15. This is an unvented gas-fired heater. It uses air
(oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must
be provided.
16. This heater shall not be installed in a room or space
unless the required volume of indoor combustion air is
provided by the method described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, the International
Fuel Gas Code or applicable local codes.
17. Keep room area clear and free from combustible materials, gasoline and other ammable vapors and liquids.
18. Unvented gas heaters are a supplemental zone heater.
They are not intended to be the primary heating appliance.
19. Unvented gas heaters emit moisture into the living
area. In most homes of average construction, this
does not pose a problem. In houses of extremely
tight construction, additional mechanical ventilation is
recommended.
20. During manufacturing, fabricating and shipping, various
components of this appliance are treated with certain
oils, lms or bonding agents. These chemicals are not
harmful but may produce annoying smoke and smells
as they are burned off during the initial operation of the
appliance; possibly causing headaches or eye or lung
irritation. This is a normal and temporary occurrence.
3
IMPORTANT SAFETY INFORMATION
VFC Vent Free Fireplace System
The initial break-in operation should last six hours with
the burner at the highest setting. Provide maximum
ventilation by opening windows or doors to allow
odors to dissipate. Any odors remaining after this initial
break-in period will be slight and will disappear with
continued use.
21. Input ratings are shown in BTU per hour and are for
elevations up to 2,000 feet. For elevations above 2,000
feet, input ratings should be reduced 4 percent for each
1,000 feet above sea level. Refer to the National Fuel
Gas Code.
22. The appliance must be isolated from the gas supply
piping system by closing its equipment shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 psig
(3.5 kPa).
23. Do not use this room heater if any part has been under
water. Immediately call a qualied service technician
to inspect the room heater and to replace any part of
the control system and any gas control which has been
under water.
24. Never burn solid fuels in a replace where a unvented
room heater is installed.
25. Always have a replace screen in place when the
appliance is in operation and, unless other provisions
for combustion air are provided, the screen must have
an opening(s) for induction of combustion air.
THIS APPLIANCE MAY BE INSTALLED IN AN
AFTER-MARKET, PERMANENTLY LOCATED,
MANUFACTURED (MOBILE) HOME, WHERE
NOT PROHIBITED BY LOCAL CODES.
THIS APPLIANCE IS ONLY FOR USE WITH THE
TYPE OF GAS INDICATED ON THE RATING
PLATE. THIS APPLIANCE IS NOT CONVERTIBLE FOR USE WITH OTHER GASES.
WARNING: Never connect unit to
private (non-utility) gas wells. This gas
is commonly known as wellhead gas.
CODES
Adhere to all local codes or, in their absence, the latest edition of THE NATIONAL FUEL GAS CODE ANSI Z223.1 or
NFPA54 which can be obtained from:
This unvented gas heater requires no outside venting
and burns cleanly with excellent heating efciency. As a
zero-clearance appliance, it can be installed against (or
recessed into) any wall that is accessible to a gas line.
GAS PRESSURES
ControlFuelMillivolt and IPI
Regulator PressureNat.3.5" w.c.
Pilot RegulatorNat.3.5" w.c.
Max. Inlet PressureNat.10.5" w.c.
Min. Inlet PressureNat.5.0" w.c.
Regulator PressureLP10.0" w.c.
Max. Inlet PressureLP13.0" w.c.
Min. Inlet PressureLP11.0" w.c.
MAX
MODELFUEL CONTROL
VFC24CNV NATMILLIVOLT 22,000 16,000 2.35mm
VFC24CPVLPMILLIVOLT 22,000 20,000 1.45mm
VFC24CNIN ATIPI22,000 16,000 2.35mm
VFC24CPILPIPI22,000 20,000 1.45mm
VFC24LNVNATMILLIVOLT 22,000 16,000 2.35mm
VFC24LPVLPMILLIVOLT 22,000 20,000 1.45mm
VFC24LNIN ATIPI22,000 16,0002.35mm
VFC24LPILPIPI22,000 20,0001.45mm
VFC32CNV NATMILLIVOLT 28,000 19,000#38
VFC32CPVLPMILLIVOLT 27,000 22,000#52
VFC32CNIN ATIPI28,000 19,000#38
VFC32CPILPIPI27,000 22,000#52
VFC32LNVNATMILLIVOLT 28,000 19,000#38
VFC32LPVLPMILLIVOLT 27,000 22,000#52
VFC32LNIN ATIPI28,000 19,000#38
VFC32LPILPIPI27,000 22,000#52
BTU
MIN
BTU
ORIFICE
SIZE
NOTE: For LP models an external regulator is required
to reduce supply pressure to a maximum of 13" w.c.
IGNITION CONTROLS
Piezo ignitor allows ignition of the pilot without the use of
matches or batteries.
Millivolt and EcoLogic® 2.0 controls have four (4)
positions:
OFF - All gas to the gas logs is shut off at the valve.
IGN - Valve position to light/maintain a standing pilot.
ON - Valve position to turn ON/OFF log set with remote switch/thermostat.
LOW/HI - Variable position to control ame height (heat output).
The gas log heater is tted with a specially designed safety
pilot light (ODS assembly) which senses the amount of
oxygen available in the room and shuts the gas log heater
off if the oxygen level begins to drop below a satisfactory
level. The pilot can only be re-lit when adequate fresh air
is available.
THERMAL GENERATOR
The millivolt gas log pilot is tted with a millivolt generator
to provide power for remote activation.
5
PRODUCT FEATURES
VFC Vent Free Fireplace System
COLD CLIMATE OPTION (IPI Models Only)
NOTE: If you live in a cold climate, seal all cracks around
your appliance and wherever cold air could enter the room,
with noncombustible material. It is especially important to
insulate the outside chase cavity between the studs and
under the oor on which the appliance rests, if the oor is
above ground level.
Your replace is equipped with an intermittent pilot ignition
(IPI) control. An IPI control with a standing pilot option provides the dual benet of an economical and environmentally
responsible product and one which lights easily even in
the coldest climates. When in intermittent pilot mode (as
it comes from the factory), your pilot remains unlit until
needed, saving you fuel. Standing pilot mode, by comparison, is characterized by a continuously burning pilot.
The benet of a pilot which lights only when needed is fuel
savings. However, with no pilot burning in your replace,
units operating in colder climates may experience delayed
start up or lock out. Because colder air is heavier than
milder air and there is no pilot burning to maintain a warm
stable temperature in your rebox, establishing a draft to
aid ignition becomes difcult. This is perfectly normal but
can be somewhat frustrating.
To remedy this issue, your replace has been designed with
a cold climate pilot option, which, when active, maintains
a warmer temperature inside your rebox to make ignition
faster and more efcient. Operating your appliance in cold
climate (aka standing) pilot mode will prohibit the need for
multiple ignition attempts and will prevent the system from
delaying start up or locking out.
To activate the cold climate option, simply move the cold
climate toggle switch located on the right side of the black
control center to the “On” (left) position. (Figure 2) You can
operate your appliance in this mode regardless of whether
you are using a remote control, wall switch or thermostat.
irritation from loose bers. Logs are fragile
— handle with care.
GETTING STARTED
Make sure you have received all parts:
Check your packing list to verify that all listed parts have
been received. You should have the following:
• Unvented gas heater
• Installation/operating instruction
• Four (4) black screws
• Canopy and three (3) screws
• Two (2) anchoring screws
• Refractory cement logs or glass media
Carefully inspect the contents for shipping damage. If any
parts are missing or damaged, immediately inform the
dealer from whom you purchased the appliance. Do not
attempt to install any part of the appliance unless you
have all parts in good condition.
WARNING—Do not install the heater:
• Where curtains, furniture, clothing, or
other ammable objects are less than
42" from the front of the heater.
• In high trafc areas.
• In windy or drafty areas.
NOTE: Be sure all packing material has been removed
from underside the unit.
2. Install canopy and logs per instructions found in this
manual. The canopy MUST be installed for safe operation of the unit.
3. Field wire main power supply to units with fan kit. Refer
to the Electrical Section found in this manual. (Electrical
connections should only be performed by an experienced, licensed certied tradesman).
4. Install optional ON/OFF kit on units with millivolt control.
Refer to the installation instructions included with the
kit and also refer to the Electrical Wiring section found
in this manual.
5. Plumb gas line. Refer to the Connecting the Gas sec-
tion found in this
manual. (Gas connections should only be performed
by an experienced,
licensed/certied tradesman).
6. Complete nish wall material and/or surround.
WHAT YOU WILL NEED FOR INSTALLATION:
You must have the following items available before proceeding with installation:
• External regulator (for propane/LPG only)
• Manual shutoff valve
• Piping which complies with local codes
• Sediment trap
• Phillips head screwdriver
• Tee joint
• Pipe sealant approved for use with propane/LPG
• Pipe wrench (resistant to sulfur compounds)
When planning the installation for the replace it is necessary to determine where the unit is to be installed and
whether optional accessories are desired. Gas supply
piping should also be planned. The following steps represent the normal sequence of installation. Each installation
is unique, however, and might require a different sequence.
1. Position fireplace in desired location. Refer to the
Location of Fireplace and Clearances and Height
Requirements, and Firebox Framing sections found in
this manual.
ADEQUATE COMBUSTION AND VENTILATION AIR
This heater shall not be installed in a conned space or
unusually tight construction unless provisions are provided
for adequate combustion and ventilation air.
The National Fuel Gas Code, (ANSI Z223.1/NFPA54),
denes a conned space as a space whose volume is less
than 50 cubic feet per 1,000 BTU per hour (4.8m3 per kw)
of the aggregate input rating of all appliances installed in
that space, and an unconned space as a space whose
volume is not less than 50 cubic feet per 1,000 BTU per
hour (4.8 m3 per kw) of the aggregate input rating of all
appliances installed in that space. Rooms communicating
directly with the space in which the appliances are installed,
through openings not furnished with doors, are considered
a part of a conned space.
WARNING: If the area in which the heater
is operated does not meet the required
volume for indoor combustion air, combustion
and ventilation air shall be provided by one of
the methods described in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, the International
Fuel Gas Code or applicable local codes.
Unusually tight construction is dened as construction
where:
a. walls and ceilings exposed to the outside atmosphere
have a continuous water vapor retarder with a rating of
1 perm (6 x 10
gasketed or sealed, and
b. weather stripping has been added on openable windows
and doors, and
c. caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates
and oors, between wall-ceiling joints, between wall
panels, at penetrations for plumbing, electrical and gas
lines and other openings.
The following formula can be used to determine the maximum heater rating per the denition of unconned space:
BTU/Hr = (L1 + L2) Ft x (W) Ft x (H) Ft
Consider two connecting rooms with an open area
between, with the following dimensions:
L1 = 151/2 Ft., L2 = 12 Ft., W = 12 Ft., H = 8 Ft.
If there were a door between the two rooms the calculation
would be based only on the room with the heater.
11
kg per pa/sec-m2) or less with openings
50
BTU/Hr = (151/2 + 12) x (12) x (8)
50
BTU/Hr = (151/2) x (12) x (8)
50
FIREPLACE LOCATION
Carefully select the best location for installation of your
unvented replace. The following factors should be taken
into consideration.
• Clearance to side wall, ceiling, woodwork and
window or other combustibles. Refer to “Clearances”
section. Minimum clearances to combustibles must
be maintained.
• Location must not be affected by drafts caused by
kitchen exhaust fans, ceiling fans, return air registers
for forced air furnaces / air conditioners, windows or
doors.
• Installation must provide adequate ventilation and
combustion air.
• DO NOT INSTALL THESE MODELS IN A BED-
ROOM OR BATHROOM.
• Location should be out of high trafc areas and
away from furniture and draperies due to heat
from rebox.
• Never obstruct the front opening of the unvented
replace or restrict the ow of combustion and ventilation air.
• Minimize modications to existing construction. Refer
to Figure 5 below for location suggestions.
• Do not install in the vicinity where gasoline or other
ammable liquids may be stored. The unvented rebox must be kept clear and free from the combustible
materials.
Ensure that minimum clearances shown in Figure 6 and
Figure 7 are maintained. Left and right clearances are
determined when facing the front of the rebox.
Follow these instructions carefully to ensure safe installation. Failure to follow these requirements may create a
re hazard.
Sidewall Clearances — The clearance from the inside of
the appliance to any combustible adjacent wall should not
be less than 9" for the VFC24 and VFC32. Figure 6
Ceiling Clearance — The ceiling must be at least 42" from
the top of the rebox opening. Figure 6
Back Wall Clearance — The appliance may be placed
against a combustible back wall.
Floor Clearance — The replace may be installed directly
on a combustible oor or a raised platform of an appropriate height. Do not place replace on carpeting, vinyl, tile or
other soft oor coverings. It may, however, be placed on at
wood, plywood, particle board or other hard surfaces. Be
sure replace rests on a solid continuous oor or platform
with appropriate framing for support and so that no cold
air can enter from under the rebox.
Mantel clearances — The canopy supplied with the unit
must be installed. If a combustible mantel is installed. It
must meet the clearance requirements detailed in Figure 7
NOTE: The Monessen Barrington cabinet model series
BWC300, BWC400 and BWC500 are specially designed
to comply with all mantel temperature requirements. Any
custom-built mantel must comply with all clearance requirements shown in this instruction manual.
12”
19”
2¹⁄₂”
10”
Canopy
FP2508
Figure 7. Mantel Clearances
WARNING: The dimensions shown
in Figures 6, 7 and 8 are minimum
clearances to maintain in installing this heater.
Left and right clearances are determined when
facing the front of the heater.
Follow these instructions carefully to ensure
safe installation. Failure to follow instructions
If unit is to be “built in”, replace framing can be built before
or after the appliance is set in place. BE SURE THAT ALL
PACKING MATERIAL HAS BEEN REMOVED FROM THE
UNDERSIDE OF THE UNIT PRIOR TO SETTING THE
FIREBOX IN PLACE. Construct replace framing following
Fireplace and Framing Dimensions. The framing headers
may rest directly on top of the rebox.
The replace may be installed directly on a combustible
oor or a raised platform of an appropriate height. Do
not place replace on carpeting, vinyl, tile or other soft
oor coverings. It may, however, be placed on at wood,
plywood, particle board or other hard surfaces. Be sure
replace rests on a solid continuous oor or platform with
appropriate framing for support and so that no cold air can
enter from under the rebox.
Anchor replace to the side framing members using nailing
anges.
1. Bend out the nailing anges located on each side of the
rebox.
2. Slide the rebox into prepared framing or position rebox
in its nal position and frame later.
3. Level the rebox by checking the top edge of the rebox.
Shim if necessary.
4. Anchor rebox to the side framing members using 8d
nails or other suitable fasteners. Figure 9
5. The canopy must be installed for safe operation of the
heater. Refer to canopy installation details.
SECURING HEATER TO FLOOR OR
HEARTH
NOTE: Clearance requirements as detailed in the
Clearances section on of this manual, must be met before
securing the heater in place.
To prevent movement, the heater must be secured to the
oor or hearth.
1. Open the control access door and remove the screen.
2.
Secure the rebox with two anchoring screws (3⁄16
length) supplied with the replace system. Figure 10
NOTE: If the unit is mounted on carpeting, tile or
combustible material without the hearth, a metal or wooden
base covering the entire width and depth of the base must
be installed.
" x 11⁄4
"
WARNING: The replace must be installed
giving full consideration to the clearance
NOTICE: A qualied gas appliance installer must connect
the heater to the gas supply. Consult all local codes.
WARNING: Use new black iron or
steel pipe. Internally tinned copper or
copper tubing can be used per National
Fuel Code, section 2.6.3, providing gas meets
hydrogen sulde limits, and where permitted by
local codes. Gas piping system must be sized to
provide minimum inlet pressure (Listed on Data
Plate) at the maximum ow rate (BTU/hr). Undue
pressure loss will occur if the pipe is too small.
A manual shutoff valve must be installed
upstream of the appliance. Union tee and
plugged 1/8" NPT pressure tapping point should
be installed upstream of the appliance. Figure 11
To Fireplace
Pipe Coupling
Pipe
Stainless
Flexible Tube
Manual Shutoff
Valve
Figure 11. Gas
Connection
IMPORTANT: Loosen the pipe adapter on the ex tube
before installing to the system piping.
Always use an external regulator for all propane/LPG heaters only, to reduce the supply tank pressure to a maximum
of 13" w.c. This is in addition to the internal regulator in the
heater valve.
To reach factory installed ex line, go through access door
on right or left side of rebox.
WARNING: CHECK GAS TYPE: The
gas supply must be the same as stated
on the heater’s rating plate. If the gas
supply is different, DO NOT INSTALL THE
HEATER. Contact your dealer for the correct
model. Connecting to the wrong gas type may
result in property damage or personal injury.
Locations Pressure
Tapping Point Installation
Gas Supply
Inlet
WARNING: Connecting directly to an
unregulated propane/LPG tank can
cause an explosion
Access Door
for Gas Line
Manual Gas Shutoff
Stainless Flex Line
Figure 12. Access Holes
(Recommended Outlet
Positioned Vertical)
The stainless ex line is on the right side facing the replace and can connect to either a 3/8 NPT female or 1/2
NPT male pipe. To connect from the opposite side, route
the pipe under the rear portion of the unit.
Test all gas joints from the gas meter to the heater valve for
leaks using a gas analyzer or soap and water solution after
completing connection. DO NOT USE AN OPEN FLAME.
Check the gas pressure with the appliance burning and
the control set to HIGH.
Open control access door on either side of unit to nd valve
and regulator referred to below. Figure 12
CHECKING GAS PRESSURE – MILLIVOLT
CONTROL
Figure 12
The valve regulator controls the burner pressure which
should be checked at the pressure test point.
Turn captured screw counter clockwise two or three turns
and then place tubing
to pressure gauge over
test point (Use test point
“OUT” closest to control knob). After taking
pressure reading, be
sure and turn captured
screw clockwise firmly
to re-seal. Do not over
torque. Check for gas
leaks.
Figure 13. Pressure Test Point Location Millivolt Control
1. Check gas type. The gas supply must be the same as
stated on the appliance’s rating decal. If the gas supply
is different from the replace, STOP! Do not install the
appliance. Contact your dealer immediately.
2. To facilitate easier installation, a 18" (610 mm) ex line
with manual shut-off valve has been provided with this
appliance. Install and attach 1/2" gas line onto shut-off
valve.
3. After completing gas line connection, purge air from
gas line and test all gas joints from the gas meter to the
replace for leaks. Use a solution of 50/50 water and
soap solution or a gas sniffer.
4. To check gas pressures at valve, turn captured screw
counter clockwise 2 or 3 turns and then place tubing to
pressure gauge over test point. Turn unit to high. Figure 14 After taking pressure reading, be sure and turn
captured screw clockwise rmly to reseal. Do not over
torque. Check test points for gas leaks.
WARNING: Do NOT use open ame
to check for gas leaks.
REMOVE SCREEN
NOTE: Fireplace screen must be removed to access log
box and to install canopy.
Figure 14
1. Remove bottom access panel.
2. Removing replace screen frame panel by pushing
screen frame panel up and out.
Canopy
Fireplace
Screen
Figure 14. IPI Valve
Pressure Inlet
Pressure
Outlet
FP3034
Pilot Adjustment Screw
Figure 15. Remove Fireplace Screen Panel
INSTALL CANOPY
Figure 15
1. Align the black canopy with the holes in the top frame
assembly.
2. Install the three (3) screws (in owner’s manual packaging) which attach the canopy to the top frame assembly.
3. Tighten all screws. Make sure the canopy is level and
secure.
Field Installed Optional
Wall Switch or
Remote Receiver
Figure 17. Wiring
Diagram
On/Off
Switch
TH = 3
TP = 1
TP/TH = 2
Switch
ODS
Pilot
Valve
Spade
Terminal
FP2112a
WARNING: Label all wires prior to
disconnection when servicing controls.
Wiring errors can cause improper and
dangerous operation. Verify proper operation
after servicing.
The millivolt valve is a self-powered combination gas control THAT DOES NOT REQUIRE 110V AC TO OPERATE.
Refer to Figure 17 and installation instructions provided
with optional wall switch, thermostat or remote control for
wiring instructions. A maximum length of 15 feet of 18awg
two conductor wire is to be used for wall switch or thermostat installations.
NOTE: Thermostats and switches must be suitable for
millivolt operation.
WARNING: Do NOT connect wall
switch to 110 V circuit.
CONNECT OPTIONAL WALL SWITCH OR
THERMOSTAT
1. Use 18 awg, two-wire cable, 15 feet maximum length.
2. At one end of the cable, connect both wires to the wall
switch or thermostat. At the other end, connect one
wire to TP/TH and one wire to TH, or connect the wall
switch/thermostat to the two male (0.25") terminals on
the left side of the unit. The color of the wires does not
matter.
VFC Vent Free Fireplace System
CONNECT REMOTE RECEIVER
THESE INSTRUCTIONS SUPERCEDE THE SECTION
ENTITLED “HEARTH MOUNT” IN THE MILLIVOLT
HAND-HELD REMOTE INSTRUCTIONS SUPPLIED
WITH THE REMOTE.
Figure 17
1. Remove bottom control door.
2. Connect the remote connector wires located in the unit
to the remote receiver.
3. Stick Velcro® pads with self-adhesive backing to bottom
of remote receiver and to oor of compartment behind
access panel.
®
4. Attach remote receiver to rebox with Velcro
pads.
Control switch must face forward.
NOTE: Do not place remote in combustion chamber,
only the remote receiver.
CHECK SYSTEM OPERATION
The millivolt system and individual components may be
checked with a millivolt meter having a 0-1000 mV range.
Conduct each check shown in chart below by connection
meter test leads to terminals as indicated.
ELECTRICAL WIRING — MILLIVOLT
Remote Receiver
Figure 18. Install Remote Receiver
A. COMPLETE MILLIVOLT SYSTEM CHECK
(“A” Reading: Thermostat contacts CLOSED,
control knob “ON,” main burner should turn ON)
a. If the reading is more than 100 millivolts and the
automatic valve still does not come on, replace the
control.
b. If the closed circuit reading (“A” reading) is less than
100 millivolts, determine cause for low reading, proceed to Section B below.
Connect Meter
Check
Test
A
B
To
Test
Complete
System
Thermopile
Output
Leads to
Terminals
B. Thermopile Output Reading Check
(“B” Reading: Thermostat contacts OPEN, main
burner OFF)
1. Check gas pressure to the unit. If gas pressure is
within minimum and maximum on data plate, then
check pilot voltage, 325 millivolts minimum. If the
minimum millivolt reading is not obtainable, replace
pilot.
WARNING: NEVER use open ame
to check for gas leaks.
VFC Vent Free Fireplace System
PILOT
OPERATING INSTRUCTIONS—MILLIVOLT
LIGHTING PILOT FOR THE FIRST TIME
APPROVED LEAK TESTING METHOD
You may check for gas leaks with the following methods only:
• Soap and water solution
• An approved leak testing spray
• Electronic sniffer
NOTE: Remove any excessive pipe compound from the connections. Excessive pipe compound
can set off electronic sniffers.
WARNING: NEVER use open ame
to check for gas leaks.
WARNING: If using a soap and water
solution to test for leaks, DO NOT
spray solution onto control body.
Check for gas leaks in each of the following locations:
• Pipe from the gas supply line connection to the gas valve
• Burner connections • Field made joints / gas shutoff valve
• Pilot • Factory made joints
• Each joint or connection • All joints on valve and control body
LIGHTING PILOT
WARNING: The control has an interlock device that does not allow the lighting of the
replace up to the moment the safety device of the ame has not interrupted the gas
ow. After that period of time (when the magnet is closed), it is possible to start the
lighting operation.
The gas control knob is designed to be operated by hand. DO NOT use any tools during this
operation. Damaged knobs may result in serious injury.
1. Depress and turn knob counterclockwise
2. Depress fully and hold pilot gas knob. Depress piezo igniter as many times as needed to ignite pilot.
Keep knob fully depressed for a few seconds. Release and check that pilot continues to burn.
If the pilot does not stay lit, repeat steps 1 and 2.
WARNING: Electrical connections should
only be performed by a qualied, licensed
electrician. Main power must be off
when connecting to main electrical power
supply or performing service. All wiring shall
be in compliance with all local, city and state
codes. The appliance, when installed, must be
electrically grounded in accordance with local
codes or in the absence of local codes, with
the National Electrical Code ANSI/NFPA 70
(latest edition) and Canadian Electrical Code,
CSA C22.1.
ELECTRICAL WIRING
General
1. This replace is equipped with an IPI control valve which
operates on 6 volts. The 6 volt DC adapter plugs into
the replace junction box A/C power supply.
2. The IPI system can also be operated without A/C power.
The system can run on four (4) “AA” batteries using the
optional battery backup for approximately six (6) months
under normal use.
Optional Accessories
This replace may be used with a wall switch, wall mounted
thermostat or IPI hand held remote control.
WARNING: Do NOT connect to a
110V circuit.
JUNCTION BOX WIRING
1. This should be done before framing the replace. Wire
the receptacle into an electrical circuit. Wire with minimum 60° C wire in accordance with prevailing codes.
2. Remove the external junction box cover by removing
the screw from the side of the outside rebox wall.
Junction box was installed at the factory.
3. The junction box cover has a factory installed “romex”
style strain relief connector. After connecting the wires,
route the wire leads through this connector. Refer to
the wiring diagram in Figure 19
The wall switch wire connection is located off the wire
harness coming out of the IPI Control Board. The label is
wired 'wall switch'. Connect the low voltage switch wires to
the two (2) terminals labeled "wall switch" from the control
IPI SYSTEM WIRING DIAGRAM
ORANGE
YELLOW
BLACK
board. Run wire to desired location on wall. Up to 50 feet
of 18 gauge wire may be used if necessary. Attach wires
to wall switch. Mount the wall switch in a junction box and
screw on cover. Figure 20
BLACK
RED
RED
RED
BLACK
RED
BROWN
RED
GROUND
RED
BLACK
GREEN
D/C POWER
BLACK
Figure 20. IPI System Wiring Diagram
Electrical connections should only be performed by a qualied, licensed electrician. Main
power supply must be turned off before connecting fans to the main electrical power supply
NOTE: When using ON/OFF wall switch, the master switch, located in bottom of fireplace must be in the
ON position to perform all configuration setup operations.
FUNCTIONOPERATION
Cold Climate Pilot On/Off Flip the toggle switch to ON.OFF
Operations
FUNCTIONOPERATION
Power UpFlip the Master Switch to ON position to power up the system.
Fireplace On
Fireplace Off
OPERATING INSTRUCTIONS – IPI
®
2.
OPERATIONS AND INDICATIONS
Cold
Climate
CONTROL
BOARD
Turn on wall switch to turn the fireplace on. NOTE: If master switch was
just switched to ON, then at first use of wall switch, it may need to be
turned ON - OFF - ON to synchronize the two switch settings.
Turn the wall switch to the OFF position, or turn the ON/OFF master
switch to the OFF position
Switch
Master
Switch
DEFAULT
SETTING
Self Diagnostics Chart
The fireplace has a self diagnostic LED on the control board enabling you to troubleshoot problems and
potentially avoid a service call. Please refer to the chart below for indicator reference.
FUNCTIONOPERATION
Sparking errorRed LED, Flash 2 times
Flame errorRed LED, Flash 3 times
Ignition failRed LED, Flash 4 times
Re-ignite warningRed LED, Flash 5 times
Pilot valve voltage errorRed LED, Flash 6 times
Main valve voltage errorRed LED, Flash 7 times
Low batteryRed LED 2.5 sec, Flash once
Remote Operations
The following functions are available on the RMSC hand held remote.
NOTE: Flame height control is only available with purchase and installation of a stepper motor kit with RF
receiver
REMOTE FUNCTIONOPERATIONICON
Fireplace OnPress the ON button on the transmitter.
Fireplace Off
Flame Height Up
Flame Height Down
Count Down Timer Mode
Press the OFF button 3 times or hold the OFF button 3
seconds for memory off.
Press the ON button once to turn on the fireplace with
maximum flame setting.
Press the OFF button to lower the flame height to
medium and low.
Press TIMER button to enter the timer mode. Keep
pressing the TIMER button to set the desired time or
press TIMER button to “0” to exit timer mode.
WARNING: If you do not follow these instructions exactly, a re or explosion may
result causing property damage, personal injury or loss of lie.
A. This appliance is equipped with an ignition device which automatically lights the pilot. Refer to the
instructions.
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the oor
because some gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS:
• Do not attempt to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the re department.
C. Turn Master Switch to ON position by hand. Never use tools. If the switch will not function by hand,
do not try to repair it. Call a qualied service technician. Force or attempted repair may result in a re
or explosion.
D. Do not use this appliance if any part of it has been under water. Immediately call a qualied service
technician to inspect the appliance and to replace any part of the control system and any gas control
that has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to
light the burner by hand.
3. Wait ve (5) minutes to clear out any gas. Then smell for gas, including near
the oor. If you smell gas, STOP! Follow "B" in the safety information on page
38. If you do not smell gas, go to next step.
4. Press the wall switch to the "ON" (-) position. Sparker will spark and pilot
ame will light.
5. Once pilot ame is established, the main burner ame will light automatically.
6. If the pilot will not stay lit after several tries, turn the master switch to "OFF"
and call your service technician or gas supplier.
Wall Switch
Master Switch
TO TURN OFF GAS TO APPLIANCE
1. Turn Wall Switch to "OFF".
2. Turn Master Switch to "OFF".
3. Turn off all electrical power to the appliance if service is to be performed.
plug helps protect you against electrical
shock. Only connect plug to a properly
grounded, three-prong receptacle. Do not cut
or remove the grounded prong from this plug.
IMPORTANT: Always check local building codes. The
installation must comply with local regulations as well as
the national electric codes.
If any of the original wire as supplied with the replace must
be replaced, contact dealer for proper replacement wiring
harness. (Refer to parts list for correct part number). 120
volts, 60Hz, 1 amp.
Fan Switch
OFF
110/115
V.A.C.
Black
White
Green
ON
WARNING: Never attempt to service
heater while it is plugged in, operating,
or hot. Burns and/or electrical shock could
result.
Electrical power cord (plug) can be routed to exit the VFC24
or VFC32 on either the left side or the right side. Remove
cord protector from side of unit, route power cord through
hole opposite side. Reinstall cord protector.
WARNING: The positioning of the logs is critical to the safe and clean operation of this heater.
Sooting and other problems may result if the logs are not properly and rmly positioned in
the appliance. Never add additional logs or embellishments such as pine cones, vermiculite
or rock wool to the heater. Only use the logs and 2G-RW rock wool supplied with the unit.
Failure to position the parts in accordance with diagrams below or to use only parts specically
approved for this heater may result in property damage or personal injury.
CAST IRON GRATE INSTALLATION
Install the cast iron grate by inserting screw head on back
of right side of grate into the “I” shaped slot on front right
corner of unit. After moving screw head to the bottom of the
“I” slot, insert the screw head on the back of the left side of
grate into the keyhole slot on the left front of unit. Figure 22
A.
Key Hole Slot
Cast Iron Grate
I Slot
ROCK WOOL PLACEMENT
Before installing logs, place rock wool in dime size pieces
evenly over small burner ports starting in the rear of the
burner going towards the front. Avoid placing rock wool on
slots on each side of rear burner and on large yellow ame
ports on front of burner. After covering small burner ports,
discard any excess rock wool. Figure 23
Dime-sized
pieces of rock wool
Figure 23. Place Rock Wool
B.
Cast Iron Grate
Figure 22. Install Cast Iron Grate
24
WARNING: Use only rock wool
provided with log set. Do not add
additional rock wool. Place rock wool on
burner ports only. Keep air gap between rear
log and burner clean.
Before you begin — This unit is supplied with six (6) refractory cement logs. Do not handle these logs with your
bare hands. Always wear gloves. After handling the logs,
wash your hands gently with soap and water.
1. Place bottom right front log #1 on right pin located on
burner. Rear of log will make slight contact with the front
grate slot bracket. Figure 24
DO NOT sprinkle volcanic rock on the logs
or around the pilot or the main burner. This
may cause sooting. Only place volcanic
rock on the oor of the replace.
During initial operation of the new heater,
burning logs will give off a paper burning
CAUTION
smell and orange ames will be present.
Simply open the windows for a few hours
to vent the odor.
3. Place the middle rear log #3 with the center log placed
behind the right ame bracket. T he rear log will rest on
the back log support. Figure 26
Figure 24.
2. Place the right rear log #2 behind #1 locking the two
logs together with the male notch into the back of log
#1. Figure 25
Figure 25.
Figure 26.
4. Place the left front log #4 on the front left pin located
on the burner. Left front edge of the log will make slight
contact with the front grate slot bracket. Figure 27
5. Place the left middle log #5 with the C channel locking
the front and middle log in place. Figure 28
Figure 28.
6. Place the left rear log #6 by aligning the rear support
bracket to the cut out on the rear of log #6. The left side
will also align with the channel cut into log #5. Figure
29
7. Place the top center log #7 by aligning the notch from
log #3 to the bottom. The front edge of the log #7 will
rest on the front grate horizontal bar. Figure 30
Figure 30.
Log placement complete.
GLASS ONLY PLACEMENT
NOTE: Two (2) bags of glass are supplied with the replace.
Both bags may be used to cover the entire oor and burner.
We advise against using additional glass as too much can
cut off the proper amount of air the burner needs to operate
cleanly. This may cause sooting.
1. Spread glass evenly in one layer over the entire oor
and burner. Be sure to use a single layer only over the
ported area so as not to impinge the ame.
2. Turn burner on and adjust glass over ported areas to
Flames from the pilot, front and rear burner should be
visually checked as soon as the heater is installed.
In addition, periodically check the ames visually during
operation.
MILLIVOLT CONTROL
Thermocouple
for Natural Gas
Thermocouple
for LP
CHECKING THE PILOT FLAME
The pilot ame must always be present when the
heater is in operation. It should just touch the top of the
thermocouple tip for natural. Refer to Figure 32 for correct
pilot ame.
If the pilot ame does not touch the thermocouple, then
the main burner cannot function reliably. Refer to Figure
33 for incorrect shape of pilot ame.
Thermocouple
for Natural Gas
Thermocouple
for LP
Correct Pilot Flame AppearanceIncorrect Pilot Flame Appearance
Figure 32. Millivolt Control Pilot Flame Appearance
Figure 33. Millivolt Control Incorrect Pilot Flame Appearance
VFC24L/VFC32L MODELS
In normal operation at full rate after 15 minutes, the
following ame appearances should be observed:
Burner will have a random pattern of yellow ames. Figure
34 There should be glowing embers in front of burner.
NOTE: The front ames and embers will be an opaque
orange color during the burn off time.
VFC24C/VFC32C MODELS
In normal operation at full rate after 15 minutes, the
following ame appearances should be observed:
Burner will have a random pattern of yellow ames. Figure
35
OPERATING INSTRUCTIONS
Avoid any drafts that alter burner ame patterns. Do
not allow fans to blow directly into the replace. Do not
place a blower inside the burn area of the rebox. Ceiling
fans may create drafts that alter ame patterns. Sooting
and improper burning will result.
During manufacturing, fabricating and shipping, various
components of this appliance are treated with certain oils,
lms or bonding agents. These chemicals are not harmful,
but may produce annoying smoke and smells as they are
burned off during the initial operation of the appliance,
possibly causing headaches or eye or lung irritation. This
is a normal and temporary occurrence.
The initial break-in operation should last two to three hours
with the burner at the highest setting. Provide maximum
ventilation by opening windows or doors to allow odors to
dissipate. Any odors remaining after this initial break-in will
be slight and will disappear with continued use.
This appliance must not be used with glass doors in the
closed position. This can lead to pilot outages and severe
sooting outside the replace.
2. Make sure the manual shutoff valve is fully open.
3. This gas log set is equipped with an ignition device (piezo) which automatically lights the pilot. If piezo
ignitor does not light the pilot, refer to instructions for Match Lighting Instructions on the following page.
4. Turn gas control knob clockwise to the OFF position and turn ON/OFF switch to OFF position.
5. Wait (5) minutes to clear out any gas. Then smell for gas, including near the oor. If you smell gas,
STOP! Follow "B" in the safety information label. If you don't smell gas, go to next step.
6. From OFF position, turn the gas control knob counterclockwise
knob for 5 seconds. NOTE: If you are running the heater for the rst time, it will be necessary to
press in the control knob for 30 seconds to allow air to bleed out of the gas piping.
7. With the control knob pushed in, push in and release the piezo ignitor button to light the pilot.
8. Continue pushing the control knob in for a further 60 seconds to prevent the ame detector from shutting off the gas while the probe is warming up. Release the control knob.
9. Turn gas control knob counterclockwise
to the ON position.
10. After the pilot has been lit for one minute, the burners can be turned on. Turn the ON/OFF switch to
ON position or adjust thermostat to desired setting.
11. If the gas logs will not operate, follow the instructions “To Turn Off Gas To Appliance” below and call
your service technician or gas supplier.
to IGN position. Push in control
Pilot
TO TURN OFF GAS TO HEATER
1. Turn control knob clockwise to OFF position to completely shut off the heater.
2. If applicable: Turn ON/OFF switch to OFF position and/or set thermostat (if present) to lowest setting.
3. If applicable: Turn off all electric power to the heater.
1. Remove any items necessary for easy access to the pilot (for example: logs, screens, etc.).
2. Follow appropriate lighting instructions found previously. Instead of pushing and releasing the piezo
button, light a match and hold the ame to the end of the pilot and ignite the pilot.
3. After control knob has been released and pilot stays lit, reinstall any items that were removed for pilot
access.
4. Call a qualied service technician for repair or replacement of the piezo ignitor.
BLOWER OPERATION
Figure 36. Location of Blower Control
Locate the blower control by opening control access door.
The variable controlled thermostat blower is located to the
right of heater controls. .
In the OFF position, the blower will not operate; however,
the heater can be operated without the blower being ON. In
the ON (AUTO) position, the blower will start when the thermostat senses a sufcient increase in rebox temperature.
NOTE: Your gas logs and blower will not turn on and off
at the same time. The gas logs may burn several minutes
before blower turns on. The blower will continue to run for
several minutes after the ames have turned off.
31
CLEANING AND SERVICING
WARNING: Turn off heater and allow to cool before cleaning. Disconnect electrical
power before cleaning or servicing.
VFC Vent Free Fireplace System
ANNUAL CLEANING/INSPECTION
Refer to parts diagram for location of items discussed
below.
Annual inspection and cleaning by your dealer or qualied
service technician is recommended to prevent malfunction
and/or sooting.
Remove logs, handling carefully by holding gently at each
end. Gloves are recommended. If skin becomes irritated,
wash gently with soap and water. Refer to manual for
correct log placement.
• Inspect and clean burner air intake holes. Remove
lint or particles with vacuum, brush or pipe cleaners.
Failure to keep air intake holes clean will result in
sooting and poor combustion.
• Inspect and clean all burner ports.
• Inspect ODS pilot for operation and accumulation of
lint at air intake holes.
• Verify ame pattern and log placement for proper
operation.
• Verify smooth and responsive ignition of main burner
and rear burner.
PERIODIC CLEANING
Refer to parts diagram for location of items discussed
below.
• Do not use cleaning uid to clean logs or any part of
heater.
• Brush logs with soft bristle brush or vacuum with
brush attachment.
• Vacuum loose particles and dust from the front and
rear burner, control and piezo covers and grate
weldment.
• Inspect and clean burner air intake holes. Remove
lint or particles with vacuum, brush, or pipe cleaners.
Failure to keep air intake holes clean will result in
sooting and poor combustion.
If you are installing the forced air kit (Models BLO24T or
BLOT), see the installation instructions provided with the
kit for electrical wiring requirements or the blower installation section.
Model VFC24 uses blower model BLO24T.
Model VFC32 uses blower model BLOT.
The rebox must be connected to main power supply at
time of rebox installation. The blower must be installed
prior to the installation of the unvented heater. The electrical connections must be made before the rebox is framed
and enclosed in the nished walls.
INSTALLING OPTIONAL FIREBRICK
PANELS
NOTE: Firebrick liner kits may be used only with the VFC
vent free replace systems. Please verify the size and
model number of your insert to be certain the kit you purchased is correct.
OPTIONAL ACCESSORIES
Retainer
Brackets
Figure 37. Install Side Firebrick
Panel
KIT CONTENTS:
• One (1) Center panel
• Two (2) self-drilling #8 screws
• One (1) Left panel
• Two (2) Brick retainer brackets
• One (1) Right panel
TOOLS REQUIRED:
Drill with 1/4" hex head or Phillips bit
INSTRUCTIONS:
1. Remove screen frame, stones, reglass or logs (if applicable) per the VFC Installation and Operating Instructions.
2. Place rear ceramic rebrick panel against the center of
the rear wall of the rebox. Place on rear log support
bracket.
3. Place left and right ceramic rebrick panels against
rebox sides and attach at the top with retainer bracket
with supplied self drilling screws.
4. Replace reglass, stones and/or logs as applicable
and re-install screen frame.
NOTE: Porcelain liner kits are approved for use with op-
tional reglass and log kits. These kits are designed to t
VFC vent free replace systems. Please verify the size
and model number of your replace to be certain the kit
you purchased is correct.
KIT CONTENTS:
• One (1) Right panel
• One (1) Left panel
• One (1) Rear panel
• Four (4) Self-drilling #8 screws
INSTALLATION INSTRUCTIONS:
1. Remove screen frame, stones, reglass or logs (if applicable).
2. Place rear panel against the center of the rear wall of
the rebox.
3. Place left and right panels against rebox sides and attach top anges of the panels using self-drilling screws
provided.
4. Replace reglass or logs as applicable and re-install
screen frame.
INSTALLING OPTIONAL BLACK MAGIC
PANELS
NOTE: Black Magic glass liner kits are approved for
use with optional reglass and log kits. These kits are
designed to t VFC vent free replace systems. Please
verify the size and model number of your replace to be
certain the kit you purchased is correct.
KIT CONTENTS:
• One (1) Center panel
• One (1) Left panel
• One (1) Right panel
• Two (2) Glass retainer brackets
• Two (2) Self drilling #8 screws
INSTALLATION INSTRUCTIONS:
1. Remove screen frame, reglass or logs (if applicable).
2. NOTE: All panels will be installed with the dimples in
the glass facing the rebox.
Place rear glass liner panel against the center of the
rear wall of the rebox.
3. Place left and right glass liner panels against rebox
sides and attach at the top with retainer bracket using
supplied screws.
4. Replace reglass or logs as applicable and re-install
screen frame.
1. Gas supply turned off or manual
shutoff valve closed.
2. Control knob not in PILOT position.
3. Control knob not pressed in while in
PILOT position.
4. Air in gas lines when installed.
5. ODS/pilot is clogged.
6. Gas regulator setting is not correct.
1. Turn on gas supply or open manual shutoff
valve.
2. Turn control knob to PILOT position.
3. Press in control knob while in PILOT position.
4. Continue holding down control knob. Repeat
igniting operation until air is removed.
5. Replace ODS/pilot assembly or get it serviced.
6. Replace gas regulator.
continued on following page
35
TROUBLESHOOTING
OBSERVED PROBLEMPOSSIBLE CAUSESOLUTION
ODS/pilot lights, but flame
goes out when control knob is
released.
Burner does not light after
ODS/pilot is lit.
Burner backres during combustion.
Slight smoke or odor during
initial operation.
Logs appear to smoke after
initial operation.
Heater produces a whistling
noise when burner is lit.
No gas to pilot.1. LP-regulator shut down due to inlet
Blower does not work.1. Power cord not plugged in.
1. Control knob not fully pressed in.
2. Control knob not pressed in long
enough.
3. Manual shutoff valve not fully open.
4. Thermocouple connection loose at
control valve.
5. Pilot ame not touching thermocouple, which allows thermocouple to
cool, causing pilot ame to go out.
This problem could be caused by
either low gas pressure, or a dirty
or partially clogged ODS/pilot.
6. Thermocouple damaged.
7. Control valve damaged.
1. Burner orice is clogged.
2. Burner orice diameter is too small.
3. Inlet gas pressure is too low.
1. Manifold pressure is too low.
2. Burner orice is clogged.
1. Burner orice is clogged or damaged.
2. Burner is damaged.
3. Gas regulator defective.
1. Vapors from paint or curing process of
logs.
2. Vapors or smoke continue after
heater is run with damper or window
open for several hours.
1. Turning control knob to HIGH position when burner is cold.
2. Air in gas line.
3. Dirty or partially clogged burner orices.
pressure too high.
2. Loose wire connections.
3. Defective blower thermostat.
1. Press in control knob fully.
2. After ODS/pilot lights, keep control knob pressed
in for 30 seconds.
3. Fully open manual shutoff valve.
4. Hand tighten thermocouple connection until
snug, then tighten 1/4 turn more.
5a.Contact local gas company.
5b.Clean pilot with vacuum cleaner.
6. Replace thermocouple.
7. Replace control valve.
1. Clean orice.
2.
Replace burner orice.
3.
Contact qualied service person.
1. Contact local gas company.
2. Clean burner or replace burner orice.
1. Clean burner or replace burner orice.
2. Replace burner.
3. Replace gas regulator.
1. Problem will stop after a few hours of operation.
Run the heater with the damper open if you have
one, or open a window for the rst few hours.
2. Log heater is intended to be smokeless. Turn
OFF heater and call qualied service person.
1. Turn control knob to LOW position and let warm
up for a minute.
2. Operate burner until air is removed from line.
Have gas line checked by local gas company.
3. Clean burner or replace burner orice.
1. Verify LP tank regulator is installed and set at
11" to 13" w.c.
2. Replace regulator on heater.
1. Plug power cord into junction box found in lower
access level.
2. Check wire connections, reconnect if loose.
3. Replace thermostat.
VFC Vent Free Fireplace System
WARNING: If the gas quality is bad, your pilot may not stay lit, the burners may produce
soot and the heater may backre when lit. If the gas quality or pressure is low, contact
your local gas supplier immediately.
WARNING: Failure to position the parts in accordance with these diagrams or failure to
use only parts specically approved with this appliance may result in property damage
or personal injury.
The following components are warranted for life to the original owner, subject to proof of purchase:
Firebox, Combustion Chamber, Heat Exchanger, Grate and Stainless Steel Burners.
FIVE YEAR WARRANTY
The following components are warranted for 5 years to the original owner, subject of proof of purchase: Refractory cement Logs, Catalytic Filter and Aluminized Burners.
BASIC WARRANTY
Monessen warrants the components and materials in your gas appliance to be free from manufacturing and material defects for a period of one year from date of installation. After installation, if any
of the components manufactured by Monessen in the appliance are found to be defective in materials or workmanship, Monessen will, at its option, replace or repair the defective components at no
charge to the original owner. Monessen will also pay for reasonable labor costs incurred in replacing
or repairing such components for a period of one year from the date of installation. Any products
presented for warranty repair must be accompanied by a dated proof of purchase.
This Limited Warranty will be void if the appliance is not installed by a qualied installer in accordance
with the installation instructions. The Limited Lifetime Warranty will also be void if the appliance is
not operated and maintained according to the operating instructions supplied with the appliance,
and does not extend to (1) rebox/burner assembly damage by accident, neglect, misuse, abuse,
alteration, negligence of others, including the installation thereof by unqualied installers, (2) the costs
of removal, re-installation or transportation of defective parts on the appliance, or (3) incidental or
consequential damage. All service work must be performed by an authorized service representative.
This warranty is expressly in lieu of other warranties, express or implied, including the warranty of
merchantability of tness for purpose and of all other obligations or liabilities. Monessen does not
assume for it any other obligations or liability in connection with the sale or use of the appliance. In
states that do not allow limitations on how long an implied warranty lasts, or do not allow exclusion of
indirect damages, those limitations of exclusions may not apply to you. You may also have additional
rights not covered in this Limited Warranty.
Monessen reserves the right to investigate any and all claims against the Limited Warranty and decide upon method of settlement.
IF WARRANTY SERVICE IS NEEDED...
1. Contact your supplier. Make sure you have your warranty, your sales receipt and the model/
serial number of your Monessen product.
2. DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELF.