INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
Contact your dealer with questions regarding installation, operation or service.
NOTICE: DO NOT discard this manual!
Natural Blaze Series
Models:
NB18NV/PV
NB24NV/PV
NB18NIF/PIF
NB24NIF/PIF
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly
could result in serious injury, death, or
property damage.
• DO NOT store or use gasoline or other am-
mable vapors and liquids in the vicinity of this
or any other appliance.
• What to do if you smell gas
- DO NOT try to light any appliance.
- DO NOT touch any electrical switch. DO
NOT use any phone in your building.
- Leave the building immediately.
- Immediately call your gas supplier from
a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call
the re department.
• Installation and service must be performed
by a qualied installer, service agency, or the
gas supplier.
In the Commonwealth of Massachusetts installation must be
NOTE: Monessen vent free gas logs are hand painted
for ultimate beauty and realism. As a result, some
variation in color and shading will occur from set to set.
This is intentional and designed to make each product
unique, as found in nature.
Installation Standard Work Checklist
ATTENTION INSTALLER:
This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in this
installation manual.
Customer:
Lot/Address:
Model
(circle one): NB18NV,NB18PV,NB18NIF,NB18PIF
WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions could
lead to a fire or explosion.
Gas Log Install Sections 2 and 5
Verified that the chimney has been cleaned. (pg. 13)
Verifi ed clearances to combustibles.
Gas Logs are leveled and secured.
See page 8 for adequate provisions for combustion and ventilation
air have been verified.
Gas Section 4
Proper appliance for fuel type.
Leak check performed and inlet pressure verified.
Verified proper air shutter setting for installation type.
All packaging and protective materials removed (inside & outside ofappliance).
Embers and logs installed correctly.
Accessories installed properly.
Finishing Section 3
Verifi ed all clearances meet installation manual requirements.
Mantels and wall projections comply with installation manual requirements.
Manual bag and all of its contents are removed and the log set
given to party responsible for use and operation.
Started log set and veried no gas leaks exist.
Hearth & Home Technologies recommends the following:
• Photographing the installation and copying this checklist for your file.
• That this checklist remain visible at all times on the appliance until the installation is complete.
Comments: Further description of the issues, who is responsible (Installer/ Builder/ Other Trades, etc) and corrective
action needed _____________________________________________________________________________________
Comments Communicated to party responsible ____________________ by ______________________on ___________
Gas Appliances for Installation in Solid-Fuel
Burning Fireplaces)
This product is listed to ANSI standards for "Unvented
Room Heaters” and applicable sections of "Gas Burning
Heating Appliances for Manufactured Homes" and "Gas
Fired Appliances for Use at High Altitude."
NOTICE: This installation must conform with local codes.
In the absence of local codes you must comply with the
National Fuel Gas Code, ANSI Z223.1-latest edition in
the U.S.A.
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.
This appliance is tested and approved as either supplemental room heater or as a decorative appliance. It should not
be factored as primary heat in residential heating calcula-
tions.
NOTE: For LP models an external regulator is required
to reduce supply pressure to a maximum of 13" w.c.
C. Gas Pressures
NATURALPROPANE (LP)
Inlet Minimum5.0" w.c.11.0" w.c.
Inlet Maximum10.5" w.c.13.0" w.c.
Gas Valve Manifold
Pressure Setting
Pilot Regulator3.5" w.c.—
NATURAL GAS: An external regulator is required to reduce
supply pressure to a maximum of 101⁄2" w.c. on natural gas
systems operating at higher pressure.
PROPANE/LPG: An external regulator is required to reduce
supply pressure to a maximum of 13" w.c.
Pilot/ODS
The gas log heater is tted with a specially designed safety
pilot (ODS assembly) which senses the amount of oxygen
available in the room and shuts the gas log heater off if the
oxygen level begins to drop below a satisfactory level. The
pilot can only be relit when adequate fresh air is available.
3.5" w.c.10" w.c.
B. BTU Specications
Maximum
Models
NB18NV(0-2000 FT)28,00019,000#38
NB18PV(0-2000 FT)27,00022,000#52
NB24NV(0-2000 FT)37,00025,0003.00 mm
NB24PV(0-2000 FT)36,00028,000#49
NB18NIF(0-2000 FT)28,00019,000#38
NB18PIF(0-2000 FT)27,00022,000#52
NB24NIF(0-2000 FT)37,00025,0003.00 mm
NB24PIF(0-2000 FT)36,00028,000#49
Input
BTU/h
Minimum
Input
BTU/h
Orice
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility
or authorities having jurisdiction.
When installing above 2000 feet elevation: Reduce input
rate 4% for each 1000 feet above sea level.
Check with your local gas utility to determine proper
orice size.
E. Non-Combustible Materials Specication
Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in
a Vertical Tube Furnace at 750 ºC shall be considered
Installation MUST comply with local, regional, state and
national codes and regulations. Consult insurance carrier,
local building inspector, re ofcials or authorities having
jurisdiction over restrictions, installation inspection and
permits.
Before installing, determine the following:
• Where burner assembly and log set are to be installed.
• Gas supply piping.
• Whether optional accessories—devices such as a wall
switch or remote control—are desired.
• Approved wood burning masonry replace or vent-free
replace.
Installation and service of this appliance should
be performed by qualied personnel. Hearth
& Home Technologies recommends HHT
Factory Trained or NFI certied professionals.
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. For
assistance or additional information, consult a qualied
service technician, service agency or your dealer.
B. Tools and Supplies Needed
Before beginning the installation be sure that the following
tools and building supplies are available.
• Tape measure
• Gloves
• Voltmeter
• Manometer
• Phillips screwdriver
• Safety glasses
• Flat blade screwdriver
• Soapy water solution for gas leak testing
• Electric drill and bits (1/4 in. magnetic)
• External regulator (for propane/LPG only & 1/2 psi
Natural gas system
• Piping which complies with local codes
• Pipe sealant approved for use with propane/LPG
(Resistant to sulfur compounds)
• Manual shutoff valve
• Sediment trap
• Tee joint
• Pipe wrench
C. Inspect Appliance and Components
• Carefully remove the appliance and components from
the packaging.
• Logs are packaged and sold separately.
• Report to your dealer any parts damaged in shipment.
• Read all of the instructions before starting the instal-
lation. Follow these instructions carefully during the
installation to ensure maximum safety and benet.
WARNING! Risk of Fire or Explosion! Damaged parts
could impair safe operation. DO NOT install damaged, incomplete or substitute components. Keep appliance dry.
Hearth & Home Technologies disclaims any responsibility
for, and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance.
• Modication of the appliance.
• Installation other than as instructed by Hearth & Home
Technologies.
• Installation and/or use of any component part not approved
by Hearth & Home Technologies.
Any such action may cause a re hazard.
WARNING! Risk of Fire, Explosion or Electric Shock!
DO NOT use this appliance if any part has been under
water. Call a qualied service technician to inspect the
appliance and to replace any part of the control system
and/or gas control which has been under water.
WARNING: This product and the
fuels used to operate this product (liquid
propane or natural gas), and the products
of combustion of such fuels, can expose
you to chemicals including benzene, which
is known to the State of California to cause
cancer and reproductive harm. For more
information go to: www.P65Warnings.
ca.gov.
Gloves are recommended when handling
refractory and logs to prevent skin irritation
Verify contents to ensure you have received all parts. You
should have the following:
NB Models
C
• Unvented gas log burner assembly
• Two (2) bags of crushed volcanic rock
• Installation/operating instructions
• Two (2) Anchoring Screws
• Ceramic ber or refractory logs
• Rock wool
• Grate assembly
• On/off log switch assembly (MV models only)
• RC300 remote control (IFP models only)
• Double A batteries (IFP models only)
The following options may be used with the millivolt controlled heater. These options are not packaged with the
log set.
• Hand-held remote with receiver (MV)
• Wall switch with 15' wire
• HILOKTN/P (an accessory kit for ame adjustment
from a hand held remote)
Carefully inspect the contents for shipping damage. If any
parts are missing or damaged, immediately inform the
dealer from whom you purchased the appliance. Do not
attempt to install any part of the appliance unless you
have all parts in good condition.
D
A
B
ModelABCD
NB18 w/18" Log26"13"18"17"
NB24 w/24" Log29"13"22
NB24 w/30" Log33"13"25
NB18IF w/18" Log28
NB24IF w/24" Log31"13"25
NB24IF w/30" Log35"13"25
Figure 2.1 - Minimum Dimensions for Engine, Logs &
Firebox
1
⁄2"13"201⁄4"17"
1
⁄4"17"
1
⁄4"17"
1
⁄4"17"
1
⁄4"17"
E. Installation Information
WARNING
This appliance is for installation only in a solid-fuel
burning masonry or UL127 factory-built replace
or in listed ventless rebox enclosure. It has been
design certied for these installations.
Exception: DO NOT install this appliance in a factory-
built replace that includes instructions stating
it has not been tested or should not be used with
unvented gas logs.
Use manufacturer's installation and clearance require-
ments as dened in their manual.
The NB18, 24, 30 series unvented room heaters are
approved for installation into the following unvented reboxes: MCUF, LCUF, GCUF, GRUF, BUF and Exacta.
The Natural Blaze Series unvented room heaters may
also be installed into a Ventless Firebox Enclosure for
Gas Fired Decorative Type Unvented Room Heaters per
ANSI Z21.91 (typically referred to as a "universal rebox"),
as long as rebox hearth dimensions meet the minimum
hearth dimensions shown below. See Figure 2.1.
Placement in Fireplace with a Restrictive Barrier
The following are guidelines for placing a gas log set in a
replace that has a restrictive barrier on the replace for
vented appliance only. See Figure 2.2.
Height of Restriction
(x)
No Restriction13"
0" to 3"16"
Greater than 3"*
*Any barrier greater than 3" placed in front of the gas log set is not
recommended by the manufacturer.
NOTE: Non-combustible material such as refractory brick
may be used to line the oor of the replace in order to raise
the height of the gas log set in relation to a restrictive barrier.
If the unit is raised, the minimum height dimension listed
in the homeowner’s manual must be met or exceeded.
NOTE: If the log set is equipped with a remote receiver, a
restrictive barrier may reduce the battery life by increasing
the ambient temperature inside the replace. Placement
of the receiver outside of the replace will extend the
battery life.
Barriers such as the bottom of a glass door frame
placed in front of a gas log set can change the air
ow characteristics of the replace which in turn
can cause the unit to overheat and malfunction when
installed as a vented log set.
Height of restrictive barrier caused by glass
door frames, recessed replaces, etc. from
the base or bottom surface of the unit.
(Refer to table)
Glass door frames with adjustable louvers
should have the louvers fully open while
the unit is in operation
Figure 2.2 - Reference Drawing of a Natural Flame Log Set in
an Enclosure with Glass Door or Barrier Installed
The log set should be placed against
or as near as possible to the rear
wall of the replace/rebox.
Depth of replace/rebox
(Refer to table)
F. Adequate Combustion Ventilation Air
This heater shall not be installed in a conned space or
unusually tight construction unless provisions are provided
for adequate combustion and ventilation air.
The National Fuel Gas Code, (ANSI Z223.1/NFPA54),
denes a conned space as a space whose volume is less
than 50 cubic feet per 1,000 BTU per hour (4.8m
of the aggregate input rating of all appliances installed in
that space, and an unconned space as a space whose
volume is not less than 50 cubic feet per 1,000 BTU per
hour (4.8 m3 per kw) of the aggregate input rating of all
appliances installed in that space. Rooms communicat-
ing directly with the space in which the appliances are
installed, through openings not furnished with doors, are
considered a part of a conned space.
Unusually tight construction is dened as construction
where:
a. Walls and ceilings exposed to the outside atmosphere
have a continuous water vapor retarder with a rating of
11
1 perm (6 x 10
kg per pa/sec-m2) or less with openings
gasketed or sealed, and
b. Weather stripping has been added to windows and
doors, and
c. Caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates
and oors, between wall-ceiling joints, between wall
panels, at penetrations for plumbing, electrical and gas
lines and other openings.
3
per kw)
WARNING
Do not install the heater:
• Where curtains, furniture, clothing, or
other ammable objects are less than
36" from the front of the heater.
• In high trafc areas.
• In windy or drafty areas.
WARNING
Gloves are recommended when handling
logs to prevent skin irritation from loose
bers. Logs are fragile—handle with care.
The following formula can be used to determine the maximum heater rating per the denition of unconned space:
Refer to Figure 2.3.
BTU/Hr = (L1 + L2) Ft x (W) Ft x (H) Ft
50
Consider two connecting rooms with an open area
between, with the following dimensions:
L1 = 151/2 Ft., L2 = 12 Ft., W = 12 Ft., H = 8 Ft.
BTU/Hr = (151/2 + 12) x (12) x (8)
50
If there were a door between the two rooms the calculation
If the area in which the heater may be
operated does not meet the required volume
for indoor combustion air, combustion and
ventilation air shall be provided by one
of the methods described in the National
Fuel Gas Code, ANSI Z223.1/NFPA 54, the
International Fuel Gas Code or applicable
3.8 and defined in the fireplace manufacturer's
instructions are minimum clearances to maintain
when installing this heater. Left and right clearances
are determined when facing the front of the heater.
When heater is installed into a ventless rebox,
minimum clearances, as specied by the ventless
rebox manufacturer, must be met.
Follow these instructions carefully to ensure safe
installation. Failure to follow instructions exactly
can create a re hazard.
Sidewall and ceiling clearances: The sides of the re-
place opening must be at least 16" from any combustible
wall. The ceiling must be at least 42" from the top of the
replace opening.
Heat resistant material (minimum requirements) with
no wooden mantel or other combustible projection:
To install the gas logs into a replace with no wooden
mantel, shelf or other combustible projection above the
replace opening, measure the heat resistant material
height, according to Figure 3.2 and TABLE A.
Heat resistant materials such as slate and marble must be
at least 1/2" thick. Sheet metal should not be installed
onto combustible material.
IMPORTANT: If you cannot meet these minimum clear-
ances you must operate the heater with chimney ue
damper open. Refer to “Installing Vented Applications”
found on page 13.
Heat resistant
Material
Measure
This
42"
16"
Figure 3.2 - Measure Heat Resistant Material
Figure 3.1 - Sidewall and Ceiling Clearances
Table A — Heat Resistant Material Requirements with No Mantel or Combustible Projection
Heat Resistant Material
Measurement
12" or moreHood not requiredHood not required
8" or less than 12"Hood not requiredExtend heat resistant material to 12" or install hood. Figure 3.3
Extend heat resistant material to 8" AND install hood Figure 3.5.
OR Extend heat resistant material to a height of at least 12".
9
Heat resistant material (minimum requirements) with
wooden mantel or other combustible projection:
To install the heater with a wooden mantel, shelf or other
combustible projection above, rst measure the heat resistant material shown in Figure 3.3, then refer to Table B.
8" or More
Hood
Heater in Fireplace
or Firebox
of Heat
Resistant
Material
Figure 3.3 - Measuring Heat Resistant Material for Mantel
Table B - Heat Resistant Material Requirements Height and Mantel Location
Heat Resistant
Material
Measurement
Requirements for Safe Installation with Wooden Mantel, Shelf or other Combustible
Projection
NB18NB24
12" or moreHood not required. Observe proles (side
elevations) shown in Figure 3.6 .
8" or less than 12"Install hood and observe proles shown
in Figure 3.5 OR Extend heat resistant
material to at least 12" and observe proles
shown in Figure 3.6.
Less than 8"Extend heat resistant to at least 8", install
hood and observe proles shown in Figure
3.5 . OR Extend heat resistant material to
at least 12" and observe proles shown in
Figure 3.6.
Hood not required. Observe prole (side
elevations shown in Figure 3.6 .
Install hood and observe proles shown
in Figure 3.5 . OR Extend heat resistant
material to at least 12" and observe proles
shown in Figure 3.6.
Extend heat resistant material to least 8",
install hood and observe proles shown
in Figure 3.5 . OR Extend heat resistant
material to at least 12" and observe proles
shown in Figure 3.6.
Figure 3.4 - Minimum Mantel Clearance with No Hood —
NB18
Example: A mantel may project from the wall a maximum
of 21⁄2" at a minimum of 14" above the opening, and a
maximum of 6" at a minimum of 201⁄2" above the opening.
12"
10"
8"
6"
Heat
Resistant
Material
2¹⁄₂"
8" 14¹⁄₂" 18⁵⁄₈" 22¹⁄₂" 26"
Heater in
Fireplace or
Firebox
Figure 3.6 -Minimum Mantel Clearance with No Hood —
NB18/24
Example: The bottom of the mantel may project from the
wall a maximum of 10" at a minimum of 28" above the
opening.
Hood
Heater in
Fireplace or
Firebox
Figure 3.5 - Minimum Mantel Clearance with Hood — All
Models
Example: A mantel may project from the wall a maximum of 21⁄2" at a minimum of 8" above the opening, and a maximum of 6" at a minimum of 141⁄2" above the opening.
The gas log heater must be installed at least 13⁄8" above
any combustible ooring material, such as carpeting or
tile, which is closer than 14" to the base of the replace.
The minimum distance must be maintained from the top
surface of carpeting, tile, etc. Figure 3.7
OR
The gas log heater may be installed nearer to the oor if a
minimum of 14" of noncombustible material such as slate
or marble is installed between the base of the replace and
the combustible ooring. Figure 3.8
Before installing in a solid fuel burning replace,
The chimney ue and rebox must be cleaned of
soot, creosote, ashes and loose paint by a qualied
chimney cleaner.
WARNING
This log set can be installed in a solid fuel burning
fireplace (masonry fireplace or manufactured
replace) with a working ue and constructed of
non combustible material or in a vent-free rebox.
Exception: DO NOT install this appliance in a factory-
built replace that includes instructions stating that
it has not been tested or should not be used with
unvented gas logs. This log set may be installed as
a vented log set.
WARNING
The use of thermostat is not allowed on vented log
application. It is only allowed on unvented room
heater classication.
B. Before installing the appliance:
• Turn off gas supply to replace or rebox.
• Have the replace oor and chimney professionally
cleaned to remove ashes, soot, creosote or other
obstructions. Have this cleaning performed annually
after installation.
• Seal any fresh air vents or ash clean-out doors
located on oor or wall of replace. If not, drafting
may cause pilot outage or sooting. Use a heatresistant sealant.
Install and operate the appliance as directed in this
manual.
C. Damper stop installation:
A damper stop must be provided with the unit. Contact your
dealer to obtain one. The damper stop must be installed as
shown in Figure 3.9 to prevent full closure of the replace
damper blade and provide a minimum 29 square inch ue
opening.
Damper Stop
Before Fully Installing the Unit:
Turn OFF the gas supply to the replace or rebox.
•
• Seal any fresh air vents and/or ash clean-out doors
located on the oor or wall of the replace. If left
unsealed, drafting may cause pilot outage or soot-
ing. Use a heat resistant sealant. Do not seal the
chimney ue damper.
Vented Application Installations —
NB & NBIF Only
Intellire Plus ODS (IFP) and millivolt controlled gas logs
may be installed as a vented decorative log set in com-
pliance with ANSI Z21.60 and National Fuel Gas Code,
Section 6.6. Since, the gas logs are operated with the
damper open, non-combustible material and minimum
mantel requirements do not apply.
NOTE: The use of a thermostat is prohibited in vented
log installations.
Damper
Figure 3.9 - Damper Stop Installation.
WARNING
When this log set is installed in a vented application,
the damper must be clamped to be fully open.
1. Center the burner assembly inside the fireplace or
firebox. Make certain that the front of the burner
assembly sits inside the front edge of the replace or
the rebox.
2. Anchor holes are located on the right and left sides of the
brackets attached to the engine base. After centering
the burner assembly correctly, mark the holes on the
replace or rebox oor. Drill two (2) 5/32” diameter holes
approximately 1 ¼” deep. Anchor the two anchoring
screws shipped with the unit using ¼” hex head chuck
and secure the burner assembly to the replace through
the holes drilled earlier. See Figure 3.10.
3. Anchor the grate to the replace/rebox oor using the
screws provided. See Figure 3.10.
Proper installation of the grate is essential to prevent
any movement of the gas logs and controls during
operation.
WARNING
You must secure the gas log heater to the replace
oor. If not, the entire unit may move when you
adjust the controls. Movement of unit may cause
shifting of the gas logs which leads to sooting and
improper burning. Grate movement could cause a
gas leak.
Special care is required if you are installing the unit
into a sunken replace. You must raise the replace
oor to allow access to gas log controls. This will
ensure adequate air ow and guard against sooting.
Raise the fireplace floor using noncombustible
materials, as described in Placement in a Fireplace
with Restrictive Barrier on Page 6.
Screw
Screw
Anchor Hole
Figure 3.10 - Securing Heater to Floor of Fireplace/Firebox
Use new black iron or steel pipe. Internally tinned
copper or copper tubing can be used per National
Fuel Code, section 2.6.3, providing gas meets
hydrogen sulde limits, and where permitted by local
codes. Gas piping system must be sized to provide
minimum inlet pressure (Listed on Data Plate) at the
maximum ow rate (BTU/hr). Undue pressure loss
will occur if the pipe is too small.
A manual shutoff valve must be installed upstream
of the appliance. Union tee and plugged 1/8" NPT
pressure tapping point should be installed upstream
of the appliance.
A. Gas Line Connection
NOTICE: A qualied gas appliance installer must connect
the heater to the gas supply. Consult all local codes.
IMPORTANT: Hold heater valve rmly with a wrench to
prevent movement when connecting to inlet pipe.
Always use an external regulator for all propane/LPG
heaters and high pressure one to two-pound systems
only, to reduce the supply tank pressure to a maximum of
13" w.c. This is in addition to the internal regulator in the
heater valve.
WARNING
Connecting directly to an unregulated propane/
LPG tank can cause an explosion.
The heater gas inlet connection is a 3/8" NPT at the valve.
On all control type units, the inlet connection is on the right
side of unit. To connect from the opposite side, route the
pipe around the back portion of the unit.
When tightening up the joint to the valve, hold the valve
securely to prevent movement.
Test all gas joints from the gas meter to the heater valve for
leaks using a gas analyzer or soap and water solution after
completing connection. DO NOT USE AN OPEN FLAME.
Check the gas pressure with the appliance burning and
the control set to HIGH.
B. Fuel Type
• This appliance is equipped for either natural or propane
gas. Field conversion is not permitted.
• Make sure the appliance is compatible with available gas
• Gas line sizing requirements will be determined in ANSI
Z223.1 National Fuel Gas Code in the USA.
• Pressure requirements are:
Figure 4.1 Gas Connection
WARNING
CHECK GAS TYPE: The gas supply must be the
same as stated on the heater’s rating plate. If the
gas supply is different, DO NOT INSTALL THE
HEATER. Contact your dealer for the correct model.
WARNING! Risk of Fire or Explosion! High pressure
will damage valve. Low pressure could cause explosion.
• Verify inlet pressures. Verify minimum pressures when
other household gas appliances are operating.
• Install regulator upstream of valve if line pressure is
greater than 1/2 psig.
• Valve pressure taps are accessible by removing the right
side log. See Figure 4.2.
3.5" w.c.10" w.c.
15
Note: Have the gas supply line installed in accordance with
local codes, if any. If not, follow ANSI Z223.1. Installation
should be done by a qualied installer approved and/or
licensed as required by the locality. (In the Commonwealth
of Massachusetts installation must be performed by a
licensed plumber or gas tter).
D. Gas Service Access
Depending upon local code, a manual gas shutoff, in
a readily accessible area may be required and located
upstream from the appliance.
WARNING
Fire Risk.
Explosion Hazard.
High pressure will damage valve.
• Disconnect gas supply piping BEFORE
pressure testing gas line at test pressures
above 1/2 psig.
• Close the manual shutoff valve BEFORE
pressure testing gas line at test pressures
equal to or less than 1/2 psig.
Intellire Plus ODS (IFP)
Check the gas pressure with the appliance burning and
the control set to HIGH.
The valve regulator controls the burner pressure which
should be checked at the pressure test point.
Turn captured screw counterclockwise two or three turns
and then place tubing to pressure gauge over test point.
Use test point “A” closest to gas inlet. After taking pres-
sure reading, be sure and turn captured screw clockwise
rmly to reseal. Do not over torque. Check for gas leaks.
See Figure 4.3.
E. Check Gas Pressure
Millivolt
The valve regulator controls the burner pressure which
should be checked at the pressure test point.
Turn captured screw counter clockwise two or three turns
and then place tubing to pressure gauge over test point
(use test point “OUT” closest to control knob). After taking
pressure reading, be sure and turn captured screw clock-
wise rmly to re-seal. Do no over torque. Check for gas
leaks. See Figure 4.2.
Test Port “OUT”
Test Port ‘A’
Figure 4.3 Pressure Test Point Location
Figure 4.2 - Pressure Test Point Location Millivolt Control
WARNING! Risk of Shock or Explosion! DO NOT wire
110-120 VAC to the valve or to the appliance wall switch.
Incorrect wiring will damage controls.
NOTICE: This appliance must be electrically wired and
grounded in accordance with local codes or, in the absence
of local codes, with National Electric Code ANSI/NFPA 70-latest edition.
• Wire the appliance junction box to unswitched 110120 VAC. This is required for proper operation of the
appliance.
• A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in
compliance with the applicable electrical codes, when
it is installed in locations such as in bathrooms or near
sinks.
• Low voltage and 110/120 VAC voltage cannot be shared
within the same wall box.
Electrical Service and Repair
WARNING! Risk of Shock! Label all wires prior to disconnection when servicing controls. Wiring errors can
cause improper and dangerous operation. Verify proper
operation after servicing.
WARNING! Risk of Shock! Replace damaged wire with
type 105º C rated wire. Wire must have high temperature
insulation.
Label all wires before disconnecting when
servicing controls. Wiring errors can cause
improper and dangerous operation.
CAUTION
WARNING
Do not connect wall switch to 110 V circuit.
WARNING
Electrical connections should only be performed
by a qualied, licensed electrician. Main power
must be off when connecting to main electrical
power supply or performing service. All wiring
shall be in compliance with all local, city and
state codes. The appliance, when installed,
must be electrically grounded in accordance
with local codes or in the absence of local
codes, with the National Electrical Code ANSI/
NFPA 70 (latest edition) and Canadian Electrical
Code, CSA C22.1.
Accessories Requirements
• This appliance may be used with a wall switch, or optional
wall mounted thermostat and/or a remote control.
Wiring for optional Hearth & Home Technologies approved
accessories should be done now to avoid reconstruction.
Follow instructions that come with those accessories.
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify
proper operation after servicing.
CAUTION
The millivolt valve is a self-powered combination gas control THAT DOES NOT REQUIRE 110 VAC TO OPERATE.
On/Off Switch
or Optional Wall
Switch, Remote
or T-Stat
B. Connect Optional Wall Switch or
Thermostat (vent free application only)
1. Use 18 awg, two-wire cable, 15 feet maximum length.
2. At one end of the cable, connect both wires to the wall
switch or thermostat. At the other end, connect one
wire to TP/TH and one wire to TH, using fork terminal
or connect the wall switch/thermostat to the two male
(0.25") terminals on the left side of the unit. The color
of the wires does not matter.
ODS Pilot
Thermopile
Wires
ODS
Pilot
TH = 3
TP = 1
TP/TH = 2
Log Switch
Figure 5.1 - Wiring Diagram
NOTE: Log switch wires are not factory connected. Connect log switch wires to the TP/TH and TH valve
terminals as shown.
• Wire the appliance junction box to 110-120 VAC for
proper operation of the appliance.
WARNING! Risk of Shock or Explosion! DO NOT wire
IFP ODS controlled appliance junction box to a switched
circuit. Incorrect wiring will override IFP ODS safety lockout.
• Refer to Figure 5.4, IFP ODS Wiring Diagram.
• This appliance is equipped with an Intellire™ Plus
control valve which operates on a 6 volt/1.5 AMP system.
• Install 4 AA cell batteries into the battery pack before use.
See Figure 5.3
THERMOCOUPLE MODULE
Battery Pack
Figure 5.3 Battery Pack Location
PILOT
IGNITOR
THERMOCOUPLE
BLACK
(GROUND)
ORANGE
(PILOT)
19093-Thermocouple Module Wire
FLAME
MODULATION
CONTROL MODULE
RED
BLACK
BROWN
GREEN
(MAIN)
ORANGE
I
WHITE
RED
S
BROWN/BLACK
OPTIONAL ON/OFF
SWITCH
THERMOCOUPLE
IGNITOR
GRAY
19026-GM931 Control Box ODS
BATTERY PACK
RC300 4.5V DC
(AAA X 3)
6V DC
Figure 5.4 IntelliFire™ Plus ODS Wiring Diagram (Battery Only)
and in the event that the control goes into LOCK-OUT
mode as a result of an error code.
ON Position: Appliance will ignite and run continuously
in the HI ame setting, with no adjustment in ame
output. This mode of operation is primarily used for
initial installation.
REMOTE Position: Appliance will initiate commands
from an optional wired wall switch and/or the wireless
remote (RC300).
2. If using a wired wall switch with the module in REMOTE
mode, the appliance will ignite and run continuously in
the HI ame setting, with no adjustment in ame output.
3. The control module has safety feature that automatically
shuts down the heater after 9 hours of continuous
operation without receiving a command from the RC300
remote.
4. If you intend to use both an optional wired wall switch
and the RC300 remote control to operate your replace,
the wall switch will override any commands given by
the remote.
5. Battery life will be shortened if the ame adjustment
feature is used frequently on the RC300 remote control.
6. Module Reset
This module may lock-out under certain conditions.
When this occurs, the appliance will not ignite or
respond to commands. The module will go into
lock-out mode by emitting three audible beeps, then
continuously displaying a RED/GREEN error code at
its status indicator LED.
• Locate the module selector switch. (See Figure 5.5).
• Set the module selector switch to the OFF position.
• Wait ve (5) minutes to allow possible accumulated gas
to clear.
• Set the module selector switch to ON or REMOTE
position.
• Start the appliance.
WARNING! Risk of Explosion! DO NOT press the mod-
ule reset switch more than one time within a ve minute time period. Gas could accumulate in rebox. Call a
qualied service technician.
MODULE
SELECTOR SWITCH
STATUS
INDICATOR LED
Figure 5.5 Control Module
NG/LP GAS-TYPE
SELECTOR SWITCH
Nine Hour Safety Shutdown Feature
The appliance has a safety feature that automatically
shuts down the heater after nine hours of continuous
operation without receiving a command from the wall
switch or optional remote.
Appliance ON/OFF
Use the IntelliFire™ Plus Remote Control to control the
ON/OFF function of the appliance. Follow instructions
included with the remote control. If desired, a wall switch
may be installed to control the ON/OFF function of the
appliance.
The positioning of the logs is critical to the safe and
clean operation of this heater. Sooting and other
problems may result if the logs are not properly
and rmly positioned in the appliance. Never add
additional logs or embellishments such as pine
cones, vermiculite or rock wool to the heater. Only
use the logs and rock wool supplied with the unit.
Failure to position the parts in accordance with
diagrams below or to use only parts specically
approved for this heater may result in property
damage or personal injury.
Key Hole
Slot
BEFORE YOU BEGIN
This unit is supplied with ceramic ber logs. Do not handle
these logs with your bare hands. Always wear gloves to
prevent skin irritation from ceramic bers. After handling the logs, wash your hands gently with soap and water
to remove any traces of bers.
CAST IRON GRATE INSTALLATION
Install the cast iron grate by inserting screw head on back
of right side of grate into the “I” shaped slot on front right
corner of unit. After moving screw head to the bottom of
the “I” slot, insert the screw head on the back of the left
side of grate into the keyhole slot on the left front of unit.
See Figure 6.1.
Wash hands after placing rock wool. Itching may occur.
Right Front Log #2
NOTE: Installation instructions are the same for 18",
24" and 30" log sets. Pictures used in this instruction
illustrate the 24" set. Some variation may exist between
the images and the set included with the instructions.
Dime-sized pieces
of rock wool
Figure 6.2 - Rock Wool Placement
B. INSTALL 18", 24" AND 30" (F, R) BERKLEY
OAK LOGS PLACEMENT
1. Place the #1 log (the “chunk”) on the grate bar right side
of the burner adjacent to the controls. See Figure 6.3 .
2. Place front right log (#2) on right pin located on burner
and right grate bar. See Figure 6.4. Slide Log #1 for-
ward so that it is tight against log #2.
Figure 6.4 - Log #2 Placement
3. Place right rear log (#3) on pin located on rear support
bracket and rest left side of log on front right log. See
Figure 6.5.
Right Rear
Log #3
Figure 6.5 - Log #3 Placement
4. Place left rear log (#4) on pin located on rear support
bracket on left side. See Figure 6.6.