IF THE INFORMATION IN THESE INSTRUCTIONS ARE
NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION
MAY RESULT CAUSING PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF LIFE.
– Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance.
– WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call the
fi re department.
– Installation and service must be performed
by a qualifi ed installer, service agency or the
gas supplier.
WARNING: Improper installation, adjustment,
alteration, services or maintenance can cause injury or
property damage. Refer to this manual. For assistance
or additional information consult a qualifi ed installer,
service agency or the gas supplier.
This appliance may be installed in an aftermarket*,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a
certifi ed kit is used.
* Aftermarket: Completion of sale, not for purpose of resale,
from the manufacturer.
WARNINGS
OPERATING INSTRUCTIONS
DUE TO HIGH TEMPERATURES, THE
APPLIANCE SHOULD BE LOCATED
OUT OF TRAFFIC AND AWAY FROM
FURNITURE AND DRAPERIES.
CHILDREN AND ADULTS SHOULD
BE ALERTED TO THE HAZARDS OF
HIGH SURFACE TEMPERATURE AND
SHOULD STAY AWAY TO AVOID BURNS
OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE
SUPERVISED WHEN THEY ARE IN THE
SAME ROOM AS THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE
MATERIAL SHOULD NOT BE PLACED ON
OR NEAR THE APPLIANCE.
KEEP THE ROOM AREA CLEAR AND
FREE FROM COMBUSTIBLE MATERIALS,
GASOLINE, AND OTHER FLAMMABLE
VAPORS AND LIQUIDS.
READ BEFORE INSTALLING. SAVE THESE INSTRUCTIONS
Page 2
CONTENTS
Important Safety Information .......................... 3
Product Features .............................................. 5
Please leave these instructions with the appliance.
• Read this owner’s manual carefully and completely before trying to assemble, operate,
or service this fi replace.
• Any change to this fi replace or its controls can be dangerous.
• Improper installation or use of this fi replace can cause serious injury or death from
WARNING
fi re, burns, explosions, electrical shock and carbon monoxide poisoning.
This fireplace is a vented product. This fireplace must be
properly installed by a qualified service person. The glass door
must be properly seated and sealed. If this unit is not properly
installed by a qualified service person with glass door properly
seated and sealed, combustion leakage can occur.
CARBON MONOXIDE POISONING: Early signs of
carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, the
fireplace may not have been installed properly. Get fresh
air at once! Have the fireplace inspected and serviced by a
qualified service person. Some people are more affected by
carbon monoxide than others. These include pregnant women,
people with heart or lung disease or anemia, those under the
influence of alcohol, and those at high altitudes.
Propane/LP gas and natural gas are both odorless. An odormaking agent is added to each of these gases. The odor helps
you detect a gas leak. However, the odor added to these gases
can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep
this manual for reference. It is your guide to safe and proper
operation of this fireplace.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible
for use with other gases unless a certified kit is used.
2. For propane/LP fireplace, do not place propane/LP supply
tank(s) inside any structure. Locate propane/LP supply
tank(s) outdoors. To prevent performance problems, do
not use propane/LP fuel tank of less than 100 lbs. capacity.
3. If you smell gas
• shut off gas supply.
• do not try to light any appliance.
• do not touch any electrical switch; do not use any
phone in your building .
• immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
OWNER
Please retain these instructions for future reference
4. Never install the fireplace
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable
objects are less than 42" from the front, top, or sides
of the fireplace
• in high traffic areas
• in windy or drafty areas
5. This fireplace reaches high temperatures. Keep children
and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after
shutdown. Allow surfaces to cool before touching.
6. Carefully supervise young children when they are in the
room with fireplace.
7. Do not modify fireplace under any circumstances. Any
parts removed for servicing must be replaced prior to
operating fireplace.
8. Turn fireplace off and let cool before servicing, install-
ing, or repairing. Only a qualified service person should
install, service, or repair the fireplace. Have burner system
inspected annually by a qualified service person.
9. You must keep control compartments, burners, and cir-
culating air passages clean. More frequent cleaning may
be needed due to excessive lint and dust. Turn off the gas
valve and pilot light before cleaning fireplace.
10. Have venting system inspected annually by a qualified
service person. If needed, have venting system cleaned
or repaired. See Cleaning and Maintenance, page 39.
11. Keep the area around your fireplace clear of combustible
materials, gasoline, and other flammable vapor and liquids. Do not run fireplace where these are used or stored.
Do not place items such as clothing or decorations on or
around fireplace.
Continued on page 4
.
54D5031 3
Page 4
IMPORTANT SAFETY INFORMATION
Continued from page 3
12. Do not use this fireplace to cook food or burn paper or
other objects.
13. Never place anything on top of fireplace.
14. Do not use any solid fuels (wood, coal, paper, cardboard,
etc.) in this fireplace. Use only the gas type indicated on
rating plate.
15. This appliance, when installed, must be electrically
grounded in accordance with local codes or in the absence
of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
16. Do not obstruct the flow of combustion and ventilation
air in any way. Provide adequate clearances around
air openings into the combustion chamber along with
adequate accessibility clearance for servicing and proper
operation.
17. When the appliance is installed directly on carpeting, tile
or other combustible material other than wood flooring,
you must set appliance on a metal or wood panel or hearth
pad extending the full width and depth of the appliance.
IMPORTANT:
PLEASE READ THE FOLLOWING CAREFULLY
It is normal for fi replaces fabricated of steel to
give off some expansion and/or contraction noises
during the start up or cool down cycle. Similar
noises are found with your furnace heat exchanger
or car engine.
IMPORTANT:
PLEASE READ THE FOLLOWING CAREFULLY
It is not unusual for gas fi replaces to give off some
odor the fi rst time it is burned. This is due to the
manufacturing process.
Please ensure that your room is well ventilated
during burn off — open all windows.
It is recommended that you burn your fi replace for
at least ten (10) hours the fi rst time you use it. Place
the fan switch in the “OFF” position during this time.
18. Do not use fireplace if any part has been exposed to or
has been under water. Immediately call a qualified service
person to arrange for replacement of the unit.
19. Do not operate fireplace if any log is broken.
20. Do not use a blower insert, heat exchanger insert, or any
other accessory not approved for use with this fireplace.
21. Do not operate the fireplace with glass door removed,
cracked, or broken.
Never connect unit to private
(non-utility) gas wells. This
gas is commonly known as
wellhead gas.
WARNING
We suggest that our gas hearth
products be installed and
serviced by professionals who
are certifi ed in the U.S. by the
National Fireplace Institute
(NFI) as Gas Specialists.
www.nfi certifi ed.org
®
4 54D5031
Page 5
PRODUCT SPECIFICATIONS
• This appliance has been certified for use with either natural or
propane gas. See appropriate data
plates.
• This appliance is not for use with
solid fuels.
• The appliance is approved for
bedroom or bedsitting room
installations.
• The appliance must be installed
in accordance with local codes if
any. If none exist use the current
installation code. ANSI Z223.1/
NFPA 54 in the USA, CAN/CGA
B149 in Canada.
• This appliance is mobile home
approved.
PRODUCT FEATURES AND CODE APPROVAL
• The appliance must be properly
connected to a venting system.
• The appliance is not approved for
closet or recessed installations.
The efficiency rating of this appliance is a product thermal efficiency
rating determined under continuous
operating conditions and was determined independently of any installed
system.
Thermal efficiency up to 75%
AFUE efficiency up to 71%
Hi/Lo Knob
Off/Pilot/On Knob
On/Off/RS Switch
Figure 1 - HBDV300 and HBDV400 Fireplace
Ignitor
Blower Control
Optional Remote
Receiver
CODE APPROVAL
Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe.
These appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS
FIREPLACE HEATERS in the USA and Canada as follows:
LISTED VENTED GAS FIREPLACE HEATER
TESTED TO: ANSI Z21.88-2007/CSA 2.33-2007 STANDARDS
A manufactured home (USA only) or mobile home OEM installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or when such a standard is not applicable, the Standard for
Manufactured Home Installations, ANSI/NCSBCS A225.1, or Standard for Gas Equipped Recreational Vehicles and
Mobile Housing, CSA Z240.4.
54D5031 5
Page 6
PRE-INSTALLATION INFORMATION
HIGH ELEVATIONS
Input ratings are showin in BTU per hour adn are certified without deration for elevations up to 4,500 feet (1,370m) above
sea level.
For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA
54 and/or local codes having jurisdiction.
In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4,500
fee (1,370m).
Read this homeowner manual thoroughly and follow all instructions carefully. Inspect all contents for shipping damage and
immediately inform your dealer if any damage is found. Do not install any unit with damaged, incomplete, or substitute parts.
Check your packing list to verify that all listed parts have been received. You should have the following:
• Fireplace (Firebox and Burner System)
• Rock Wool
• Log Set
ITEMS REQUIRED FOR INSTALLATION
Tools: Building Supplies:
• Phillips Screwdriver • Framing Materials
• Hammer • Wall Finishing Materials
• Saw and/or saber saw • Caulking Material (Noncombustible)
• Level • Fireplace Surround Material (Noncombustible)
• Measuring Tape • Piping Complying with Local Codes
• Electric Drill and Bits • Tee Joint
• Pliers • Pipe Sealant Approved for use with Propane/LPG
• Square (Resistant to Sulfur Compounds)
• Pipe Wrench
6 54D5031
Page 7
PRE-INSTALLATION INFORMATION
FIREPLACE FRAMING
Firebox framing can be built before or after the appliance is set in place. Construct firebox framing following Figure 2 and
the chart below for your specific installation requirements. See Figure 3 on Page 8 for firebox dimensions. The framing
headers may rest on the top of the firebox standoffs. Do not bring headers below top of standoffs.
The firebox may be installed directly on a combustible floor or raised on a platform of an appropriate height. When the
firebox is installed directly on carpeting, tile, or other combustible material, other than wood flooring, the firebox shall be
installed on a metal or wood panel extending the full width and depth of the enclosure.
Do not fi ll spaces around fi rebox with insulation or other materials. This could cause
a fi re.
WARNING
1/2” or 5/8”
H
C
A
E
Corner Installation
A 331/2" 371/2"
D
F
B 371/4" 407/8"
C 281/4" 291/4"
D 141/8" 131/2"
E 5511/16" 607/8"
F 2713/16" 307/16"
G 133/4" 161/2"
H 393/8" 431/16"
Plan for the installation of your appliance. This includes determining where the unit is to be installed, the vent configuration
to be used, framing and finishing details, and whether any optional accessories (i.e. blower, wall switch, or remote control)
are desired. Consult your local building code agency to ensure compliance with local codes, including permits and inspections.
The following factors should be taken into consideration:
• Clearance to side-wall, ceiling, woodwork, and windows. Minimum clearances to combustibles must be maintained.
• This fireplace may be installed along a wall, across a corner, or use an exterior chase. See Figure 4 for suggested locations.
• Location should be out of high traffic areas and away from furniture and draperies due to heat from appliance.
• Never obstruct the front opening of the fireplace.
• Do not install in the vicinity where gasoline or other flammable liquids may be stored.
• Vent pipe routing. See Venting section found in this manual for allowable venting configurations.
• These units can be installed in a bedroom. See National Fuel Gas Code ANSI Z233.1/NFPA 54 — (current edition), the
Uniform Mechanical Code — (current edition), and Local Building Codes for specific installation requirements.
A Flat on Wall
B Cross Corner
C Island**
E
Y
A
B
D Room Divider*
E Flat on Wall Corner*
C
X
F Chase Installation
Y 4" Minimum
D
Y
F
Figure 4 - Locating Gas Fireplace
** Island (C) and room divider (D) installation is possible as long as the horizontal portion of vent system (X)
does not exceed 20'. See Installing Horizontal Termination Confi guration on pages 18 and 19.
* When you install your fi replace in (D) room divider or (E) fl at on wall corner positions (Y), a minimum of 6"
clearance must be maintained from perpendicular wall and front of fi replace.
54D5031 9
Page 10
L
CLEARANCES
CLEARANCES TO COMBUSTIBLES
Follow these instructions carefully to ensure safe installation. Failure to follow
in struc tions exactly can create a fi re hazard.
The appliance cannot be installed on a carpet, tile or other combustible material other
than wood fl ooring. If installed on carpet or vinyl fl ooring, the appliance shall be installed
on a metal, wood or noncombustible material panel ex tend ing full width and depth of
WARNING
the appliance.
71"Minimum
12" Minimum
All mantel shelves, regardless of depth, should be a minimum of 12" from top opening of fireplace. Mantel shelf
shall not exceed 12" maximum depth at 12" minimum
height from opening.
NOTE
0"–12"
Maximum
Depth
STUD
COMBUSTIB
MATERIAL
AREA
45°
Minimum 4"
From Both
Side Walls
Figure 5 - Clearances
MANTEL CLEARANCES
FIREPLACE
WALL
1"
1.5"
1.5"
2.5"
2.5"
2.5"
3"
4"
Figure 5a - Mantel clearances.
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it does,
it is considered a mantel and must meet the mantel requirements listed in this manual.
10 54D5031
Page 11
SECURING FIREPLACE TO FLOOR OR FRAMING
The fireplace must be secured to the floor and/or to framing studs as shown in Figure 5. Use two (2) wood screws or masonry/
concrete screws to secure fireplace to the floor. Use four (4) screws to attach fireplace to framing. The side nailing flanges
are 1/2" or 5/8" to accommodate different wall thickness.
DO NOT REMOVE
Framing
Screws
Nail
Flange
WARNING
INSULATION BOARD
Insulation
Board
Screws
Screws
Nail
Flange
Screws
Screws
Figure 6 - Securing Fireplace to Floor and Framing Studs
54D5031 11
Page 12
INSTALLATION INFORMATION
FINISHING MATERIAL
NOTE: Any remote wiring (i.e. remote control, wall switch, and optional fan) must be done prior to fi nal
fi nishing to avoid costly reconstruction.
Never obstruct or modify the air inlet or outlet grills (louvers). This may create a
fi re hazard.
WARNING
Only noncombustible materials (i.e. brick, tile, slate, steel, or other materials with a UL fire rating of Zero) may be used to
cover the black surface of the appliance. A 300°F minimum adhesive may be used to attach facing materials to the black
surface. If joints between the finished wall and the fireplace surround are sealed, a 300°F minimum sealant material (General
Electric RTV103 or equivalent) must be used.
Read all instructions completely and thoroughly before attempting installation. Failure
to do so could result in serious injury, property damage or loss of life. Operation of
improperly installed and maintained venting system could result in serious injury,
property damage or loss of life.
WARNING
Failure to follow these instructions will
void the warranty.
NOTICE
INSTALLATION PRECAUTIONS
Consult local building codes before beginning the installation. The installer must make sure to select the proper vent system
for installation. Before installing vent kit, the installer must read this fireplace manual and vent kit instructions.
Only a qualified installer/service person should install venting system. The installer must follow these safety rules:
• Wear gloves and safety glasses for protection.
• Use extreme caution when using ladders or when on rooftops.
• Be aware of electrical wiring locations in walls and ceilings.
The following actions will void the warranty on your venting system:
• Installation of any damaged venting component.
• Unauthorized modification of the venting system.
• Installation of any component part not manufactured or approved by MHS.
• Installation other than permitted by these instructions.
12 54D5031
Page 13
VENT INSTALLATION
This fireplace must be vented to the outside. The venting system must NEVER be
attached to a chimney serving a separate solid fuel burning appliance. Each gas
appliance must use a separate vent system. Do not use common vent systems.
WARNING
Horizontal sections of this vent system require a minimum of 3" clearances to
combustibles at the top of the flue and 1" clearance at the sides and bottom until
the flue penetrates the outside wall. A minimum 1" clearance all around the flue is
acceptable at this point of penetration.
Vertical sections of this vent system require a minimum of 1" clearance to combustibles
WARNING
on all sides of the pipe.
WARNING
A Minimum of 3" Clearance
to the Top Is Required Along
Horizontal Length until Flue
Pipe Penetrates Outside Wall.
3"
A Minimum 1" Clearance to
Combustibles Permitted All
Around Flue at Outside Wall
1"
1"
3"
1"
1"
1"
Figure 7 - Combustible Clearances for Vent Pipe
54D5031 13
Page 14
VENT INSTALLATION
OPTIONAL TOP VENT APPLICATION
The appliance is shipped as a rear vent unit. If the installation
layout requires the unit to be a top vent configuration the
appliance can be converted by following the steps below.
NOTE: REMOVE AND DISCARD TOP BOX AND
INSULATION ON TOP OF THE UNIT BETWEEN
THE STAND-OFFS. THIS BOX IS ONLY UTILIZED
WITH REAR-VENT APPLICATIONS.
When removing and refitting the plates and adapter be sure the
associated gaskets are undamaged and refitted as required.
1. Remove the eight (8) screws securing the flue pipe adapter
to the fireplace body. See Figure 9.
2. Set the flue pipe adapter aside, complete with the gasket.
Do not damage the gaskets as the adapter and gasket must
be refitted.
3. Remove the eight (8) screws securing the flue pipe cover to
the top of the intake box and remove the cover and gasket.
See Figure 9.
4. Remove the six (6) screws securing the flue pipe to the
back of the intake box and remove the pipe and gasket. See
Figure 10.
After conversion to top vent
confi guration the 4" (100mm) fl ue pipe
should be concentric within the 6
1
(175mm) outer collar (within
/4").
WARNING
5
/8"
5. Replace flue pipe to top of firebox. Ensure the gasket is
in place and undamaged. Secure with six (6) screws. See
Figure 11.
6. Place the flue pipe cover and gasket removed in step 3 over
the flue opening in back of the intake box.
7. Refit the flue pipe adapter and gasket to the top of fireplace. Secure the adapter with eight (8) screws removed in
step 1.
Flue Pipe
Cover
Flue Pipe
Adapter
Screws
Flue Cover
Flue Pipe
HBDV300 HBDV400
Figure 8 - Removing top box and insulation
Screws
Screws
Flue Pipe
Figure 9 - Removing Screws from Flue
Pipe Adapter and Flue Pipe Cover
14 54D5031
Figure 10 - Removing
Flue Pipe
Figure 11 - Attaching Flue Pipe to
Top Vent Confi gurations
Page 15
INSTALLATION PLANNING
VENT INSTALLATION
There are two basic types of direct-vent installation:
• Horizontal Termination
• Vertical Termination
It is important to select the proper length of vent pipe for the
type of termination you choose. It is also important to note the
wall thickness.
FOR HORIZONTAL TERMINATION
Select the amount of vertical rise desired. All horizontal run of venting must have
termination.
You may use up to three 90° elbows in this vent configuration. See Horizontal Termination Configurations on pages 20 and
21.
FOR VERTICAL TERMINATION
Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical rise in an attic or second
story, and allow for sufficient vent height above the roof line.
NOTE: You may use two 45° elbows in place of a 90° elbow . You must follow rise to run ratios when using
45° elbows. The appliance is approved for use with three 90° elbows maximum or a combination of 90°
and 45° elbows up to a maximum of 270°.
For two-story applications, firestops are required at each floor level. If an offset is needed in the attic, additional pipe and
elbows will be required.
Never run the vent pipe level or
downward. This may cause excessive
temperatures which could cause
a fi re.
WARNING
1
/4" rise for every 12" of run towards the
You may use a chase with a vent termination with exposed pipe on the exterior of the house. See Installing Vent System in
a Chase below. If pipe is enclosed in chase, it is not exposed.
It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust.
Certain limitations apply to vent configurations and must be strictly followed.
INSTALLING A VENT SYSTEM IN AN OUTSIDE CHASE
A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a building. A chase is required
for such venting.
Treatment of fi restops and construction of the chase may vary from building type to
building type. These instructions are not substitutes for the requirements of local
building codes. You must follow all local building codes.
NOTICE
When installing in a chase, you should insulate the chase as you would the outside walls of
your home. This is especially important in cold climates. Insulation should be considered
a combustible material. Maintain proper clearances to all combustible materials.
NOTICE
54D5031 15
Page 16
VENT INSTALLATION
Inside Corner Detail FOR HORIZONTAL TERMINATION
G
V
H
D
E
B
L
Vent TerminalAir Supply InletArea Where Terminals Not Permitted
V
C
Fixed
V
Closed
F
Operable
V
B
A
BB
B
Opera-
ble
V
A
V
Fixed
Closed
J
V
A
B
Figure 12 - Horizontal Vent Termination Location
MINIMUM DISTANCES
A = Clearance above the grade, a veranda, porch, deck, or balcony [*12" (305mm) minimum].
B = Clearance to window or door that may be opened [*12" (305mm) minimum].
C = Clearance to permanently closed window [*minimum 12" (305mm) recommended to prevent condensation on
window]
= Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of two (2) feet (610mm)
D
from the centerline of the terminal [18" (457mm) minimum].
E = Clearance to unventilated soffits [12" (305mm) minimum]. Clearance to vinyl soffit [30" (762mm)].
F = Clearance to an outside corner. See Figure 12.
G = Clearance to an inside corner. See Figure 12.
H = *Not to be installed above a gas meter/regulator assembly within three (3) feet (914mm) horizontally from the centerline
of the regulator.
I = Clearance to service regulator vent outlet [*3' (914mm) minimum].
J = Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance [*12"
(305mm)minimum].
K = Clearance to a mechanical air supply inlet [*6' (1829mm) minimum].
L = Clearance above a paved sidewalk or paved driveway located on public property [**7' (2133mm) minimum].
M = Clearance under veranda, porch, deck, or balcony. See Figure 13, page 17. [For Canada *12" (305mm)
***
minimum
].
* As specified in CAN/CGA B149 Installation Codes. Note: Local codes or regulations may require different
clearances.
** A vent must not terminate directly above a sidewalk or paved driveway, which is located between two single-family
dwellings and serves both dwellings.
A
G
I
M
V
A
K
A
Always maintain minimum clearances around vent systems. The minimum clearances
to combustibles for horizontal vent pipe are 3" at the top and 1" at the sides and bottom
of the vent system until the pipe penetrates the nearest vertical wall (1" required). A
1" minimum clearance all around the pipe must be maintained at outside wall and on
vertical runs. Do not pack the open air spaces with insulation or other materials. This
WARNING
could cause high temperatures and may present a fi re hazard.
16 54D5031
Page 17
TERMINATION CLEARANCES FOR BUILDINGS WITH COMBUSTIBLE
AND NONCOMBUSTIBLE EXTERIORS
VENT INSTALLATION
GG=6" (152mm)
V
Inside Corner
V
F
Outside Corner
F=6" (152mm)
H
G
V
Combustible &
G = Combustible 24"(610mm)
Noncombustible 18"(457mm)
Balcony with No Side WallBalcony with Perpendicular
Noncombustible
H = 24" (610mm)
J = 20" (508mm)
V
J
Side Wall
Figure 13 - Allowable Venting Chart
HOW TO USE THE VENT GRAPH
The Vent Graph should be read in conjunction with the following
vent installation instructions to determine the relationship between
the vertical and horizontal dimensions of the vent system.
1. Determine the height of the center of the horizontal vent pipe
exiting through the outer wall. Using this dimension on the
Sidewall Vent Graph below, locate the point intersecting with
the slanted graph line.
2. From the point of this intersection, draw a vertical line to the
bottom of the graph.
3. Select the indicated dimension, and position the fireplace in
accordance with same.
Example: If the vertical dimension from the fl oor of the
fi replace is 1 1' (3.4m) the horizontal run to the face of the
outer wall must not exceed 14' (4.3m).
Example: If the vertical dimension from the fl oor of the unit
is 7’ (2.14m), the horizontal run to the face of the outer
wall must not exceed 8
Sidewall Vent Graph showing the relationship between vertical and
horizontal dimensions for a Direct Vent flue system.
Vertical Dimension From the Floor of Unit to the Center of the
Horizontal Vent Pipe
Figure 13 - Rear Wall Venting Graph
54D5031 17
Page 18
VENTING INSTALLATION
REAR (THROUGH THE WALL) APPLICATIONS
When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind
the appliance
• The maximum horizontal distance between the rear of the appliance and the outside of termination is 20" (508 m). See
Figure 15.
• Only one 45° elbow is allowed in these installations.
Maximum
20"
Top View Flat Installation
Figure 15 - Rear Vent Application,
Maximum Horizontal Distance
Sealant is not required to assemble HBDV/DVBH
fireplace venting. Do not use silicone sealant at
the flue exhaust connections.
1. Find the pipe section’s direction label. The
label arrow shall be pointed away from the firebox and toward the termination. Firmly insert
the initial rigid section/elbow into the firebox
outer collar. Simpson “GS” and Selkirk “DT”
outer walls are hemmed and will snap into the
collar’s tabs. Attach Simpson’s DirectVent Pro
by fully inserting into the collar and securing
with self tapping screws. The screws shall only
penetrate the flue outer wall.
Female
Locking Lugs
Note: Horizontal runs of vent
must be supported every three
feet (914mm). Use wall straps
for this purpose.
Male Slots
Figure 16 - Rigid Vent Pipe Connections
91/2"
(241mm)
Refer to vent manufacturer’s installation
instructions to properly assemble flue.
2. Locate and cut the vent opening in the
wall. For combustible walls first frame in
opening.
Combustible Interior Walls: Cut a 11
1
x 9
/2" W hole through the interior wall.
Combustible Exterior Walls: Cut a 9
1
/2"H
1
/2"H
91/2"
(241mm)
33/4"
(92mm)
x 91/2"W square hole through the exterior
wall frame. See Figure 17.
Noncombustible Walls: Hole opening
71/2"
(190mm)
should be 71/2" (190mm) in diameter.
3. The center of the hole should line up with the
center line of the horizontal rigid vent pipe
end. Pipe shall always run level or uphill on
Figure 17 - Exterior Wall Framing Dimensions
horizontal runs. Never run pipe down hill. See
Figure 17.
18 54D5031
Page 19
REAR WALL VENT INSTALLATION (continued)
4. Apply a bead of non-hardening mastic around the outside
edge of vent cap. Position the vent cap in the center of hole
on the exterior wall with the word “HOT” on the vent cap
facing up. Insure proper clearance of 1" to combustibles is
maintained to the flue. Attach the vent cap with four wood
screws supplied. See Figure 18.
Do not recess vent termination
into any wall. This will cause a
fi re hazard.
WARNING
NOTE: Replace the wood screws with appropriate
fasteners for stucco, brick, concrete, or other types
of siding.
VENT INSTALLATION
Vent Cap
HOT
Wood
Screw
Apply Mastic to
All Four Sides
Figure 18 - Installing Horizontal Termination
A vinyl siding standoff (part #950) must be used with the Simpson/Selkirk Horizontal Termination (part #985) on vinyl,
stucco or wood-clad exterior walls. Apply non-hardening mastic around outside edge of the standoff instead of the vent cap
assembly. See Figure 19.
5. Slide the firestop over the vent pipe before connecting the horizontal run to the vent cap. See Figure 20.
6. The termination should overlap the flue a minimum of 1
1
/4" Apply silicone to the outer pipe/termination connection.
Fasten termination with screws provided.
7. Slide the firestop against the interior wall surface and attach with screws. See Figure 20.
Cut Vinyl Siding
Away to Fit Standoff
Interior Wall
Surface
Standof #950
Firestop
Simpson
Termination
#985
Vent Cap
(Horizontal
Apply
Mastic to
All Four
Sides
Nut
Wood Screw
HOT
Bolt
Termination)
Screw
Horizontal
Vent Pipe
Figure 19 - Installing Simpson/Selkirk Vinyl
Siding Standoff and Termination
54D5031 19
Figure 20 - Installing Firestop on
Horizontal Vent Pipe
Page 20
VENT INSTALLATION
HORIZONTAL TERMINATION CONFIGURATIONS
Since it is very important that the venting system maintain its balance between the combustion air intake and the flue
gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.
The Vent Graph, showing the relationship between vertical and horizontal side wall venting, will help to determine the various dimensions allowable. See Figure 13, page 17.
NOTE: Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the
fl ue and 1" clearance at the sides and bottom until the fl ue penetrates the outside wall. A minimum 1" clearance all
around the fl ue is acceptable at this point of penetration.
Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.
When vent exits through foundations less than 20" below outcrop, the termination must be flush up with outcropped wall
above.
It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace (or the top of the Transition
Elbow) to the face of the outer wall.
When installing the appliance as a rear vent unit, the 90° or 45° transition elbow
attached directly to the rear of the unit is NOT INCLUDED in the following criteria and
calculations, and unless specifi cally mentioned should be ignored when calculating
venting layouts.
WARNING
• The maximum number of 90° elbows per side wall installation is three (3). See Figure 21.
• If a 90° elbow is fitted directly on top of the fireplace flange the maximum horizontal vent run before the termination
or a vertical rise is 36” (914 mm). See Figure 22.
3 x 90°
Elbows
3 x 90°
Elbows
Figure 21 - Maximum Three (3) 90° Elbows
Per Installation
Figure 22 - Maximum Horizontal Run with No Rise
36"
Max.
36"
Max.
20 54D5031
Page 21
VENT INSTALLATION
HORIZONTAL TERMINATION CONFIGURATION
(Continued)
• If a 90° elbow is used in the horizontal vent run (level height
maintained) the horizontal vent length is reduced by 36".
See Figures 21 and 22, page 20. This does not apply if the
90° elbows are used to increase or redirect a vertical rise.
See Figure 24.
Example: According to the vent graph (page 17) the
maximum horizontal vent length in a system with a 7.5'
vertical rise is 20’ (6m) and if a 90° elbow is required in
the horizontal vent it must be reduced to 17' (5.2 m).
In Figures 23 and 24, Dimension A plus B must not be greater
than 17' (5.2m).
• The maximum number of 45° elbows permitted per side
wall installation is two (2). These elbows can be installed
in either the vertical or horizontal run.
• For each 45° elbow installed in the horizontal run, the length
of the horizontal run MUST be reduced by 18" (45cm). This
does not apply if the 45° elbows are installed on the vertical
part of the vent system.
• The maximum number of elbow degrees in a system is 270°.
When it is not possible to meet the required vent terminal clearances of 12" above grade level, a snorkel kit is recommended.
It allows installation depth down to 7" (178mm) below grade level. The 7" (178mm) is measured from the center of the
horizontal vent pipe as it penetrates through the wall.
Ensure that sidewall venting clearances are observed. If venting system is installed below ground, we recommend a
window well with adequate and proper drainage to be installed around the termination area.
If installing a snorkel, a minimum 24" vertical rise is necessary. The maximum horizontal run with the 24” vertical pipe is
36". This measurement is taken from the collar of the fireplace (or transition elbow) to the face of the exterior wall. See the
Sidewall Venting Graph for extended horizontal run if the vertical exceeds 24".
1. Establish vent hole through the wall. See Figure 16, page 18.
2. Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe. Install window well (not supplied).
Refill hole with 12" of coarse gravel leaving a clearance of approximately 4" below snorkel. See Figure 26.
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe coming through the wall.
5. Apply high temperature sealant caulking (supplied) around the 4" and 7" snorkel collars.
6. Slide the snorkel into the vent pipes and secure to the wall.
7. Level the soil so as to maintain a 4" clearance below snorkel. See Figure 26.
• Do not back fi ll around snorkel.
• A clearance of at least 4" must be
maintained between the snorkel and
the soil.
WARNING
If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to
wall first, then secure to snorkel with self drilling #8x1/2 sheet metal screws. It will be necessary to extend vent pipes out as
far as the protruding wall face. See Figure 27.
Screws
Firestop
24"
Minimum
Foundation Wall
Minimum
4" Clearance
Ground
Window Well
Gravel
Drain
Foundation
Recess
Watertight Seal
Around Pipe
Snorkel
Wall Screws
Sheet Metal
Screws
Figure 27 - Snorkel Installation,
Figure 26 - Below Grade Installation
22 54D5031
Recessed Foundation
Page 23
VENT INSTALLATION
VERTICAL (THROUGH-THE-ROOF) APPLICATIONS
This Gas Fireplace has been approved for,
• Vertical installations up to 40' (12m) in height. Up to a 10' (3m) horizontal vent run can be installed within the vent system
using a maximum of two 90° elbows. See Figure 28.
NOTE: Horizontal sections of this vent system require a
minimum of 3" clearances to combustibles at the top of
the fl ue and 1" clearance at the sides and bottom until the fl ue penetrates the outside wall. A minimum 1" clearance all
around the fl ue is acceptable at this point of penetration.
Vertical sections of this vent system require a minimum of
1" clearance to combustibles on all sides of the pipe.
Support
10'
Maximum
40' Maximum Height
8' Minimum Height
• Up to two 45° elbows may be used within the
horizontal run. For each 45° elbow used on the
horizontal plane, the maximum horizontal length
must be reduced by 18" (450mm).
Support Straps
Every 3'
Straps
Every
5'Vertical
Figure 28 - Support Straps for Horizontal Runs
40' Maximum Height
8' Minimum Height
1
2
3
4
10'
Maximum
Support Straps
Every 3'
Example: Maximum horizontal lengthNo elbows = 10’ (3m)
1. Determine the route your vertical venting will take. If ceiling joist,
roof rafters or other framing will obstruct the venting system,
consider an offset. See Figure 30 to avoid cutting load bearing
members.
Roof
Flashing
For optimal flame appearance, a restrictor disk is necessary on straight
vertical runs of 20' of more.
• Runs may not incorporate elbows.
• The disk is part number 45D0551 and is included in installation manual packet.
• Drop the disk into a 4" inner collar before installing the first
section of flue or install at the last section before installing the
termination.
• An additional disk may be installed on runs of 35' or more.
Rotate disks perpendicular to each other.
NOTE: Pay special attention to these installation instructions
for required clearances (air space) to combustibles when
passing through ceilings, walls, roofs, enclosures, attic
rafters, etc. Do not pack air spaces with insulation. Also
note maximum vertical rise of the venting system and any
maximum horizontal offset limitations. Offsets must fall
within the parameters shows in Figure 13, page 20.
2. Set fireplace in desired location. Drop a line plumb down from
the ceiling to the position of the flue exit. Mark the center point
where the vent will penetrate the ceiling. Drill a small locating
hole a this point.
Wall
Strap
45° Elbows
Ceiling Firstop
Figure 30 - Offset with Wall Strap and 45°
Elbows
Nails
Drop a plumb line from the inside of the roof to the ceiling locat-
ing hole in the ceiling. Mark the center point where the vent will
penetrate the roof. Drill a small locating hole at this point.
FLAT CEILING INSTALLATION
1
1. Cut a 9
/2" (241mm) square hole in the ceiling using the locating
hole as a center point The opening should be framed to 91/2"x91/2"
(241mm x 241mm) inside dimensions as shown in Figure 32using
framing lumber the same size as the ceiling joist. If the area
above the ceiling is an insulated ceiling or a room, nail firestop
from the top side. This prevents loose insulation from falling into
the required clearance space. See Figure 31. Otherwise, install
firestop below the framed hole. See Figure 32.
2. Assemble the desired lengths of pipe and elbows necessary to
reach from the burner system flue up through the firestop. Be sure
pipe and elbow connections are fully twist-locked. See Figure
15, page 18.
Firestop
Figure 31 - If Area Above is a Room, Install
Firestop above Framed Hole as Shown
1
9
/
2
"
Firestop
Nails
"
1
2
/
9
Figure 32 - If Area Above is Not a Room, Install
Firestop above Framed Hole as Shown
24 54D5031
Page 25
VENT INSTALLATION
3. Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole
1
1/
in roof). The 9
/2"x9
2
" (241mm x 241mm) hole must be measured on the horizontal. Actual length may be larger
depending on the pitch of the roof. There must be a 1" minimum clearance from the vent pipe to combustible materials.
(Insulation should be considered a combustible material).
4. Connect a section of pipe and extend up through the hole.
NOTE: If an offset is needed to avoid obstructions, you must support the vent pipe every three (3) feet.
Use wall straps for this purpose. See Figure 28, page 23. Whenever possible, use 45° elbows instead of
90° elbows. The 45° elbow offers less restriction to the fl ow of the fl ue gases and intake air.
5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and
framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing. There must be a 1" clearance
from the vent pipe to combustible materials.
6. Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements.
NOTE: You must increase vent height for steep roof pitches. Nearby trees, adjoining roof lines, steep
pitched roofs, and other similar factors may cause poor draft or down-drafting in high winds. Increasing
the vent height may solve this problem.
NOTE: If the vent pipe passes through any occupied areas above the fi rst fl oor, including storage spaces
and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction
material. Make sure to meet the minimum allowable clearances to combustibles. Do not fi ll any of the
required clearance spaces with insulation.
CATHEDRAL CEILING INSTALLATION
1. Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box. Mark the outline of
the cathedral ceiling support box on the roof sheathing using the locating hole as a center point.
2. Cut the hole 1/8" larger than the support box outline. See Figure 32.
3. Lower the support box through the hole in the roof until the bottom of the box extends at least 2" below the ceiling. See Figure 32. Align the support box vertically and horizontally using a level. Temporarily tack the support box in place
through the inside walls and into the roof sheeting.
4. Using tin snips, cut the support box from the top corners down to the roof line and fold the resulting flaps over the roof
sheeting. See Figure 33. Apply a bead of non-hardening, mastic around the top edges of the support box to make a seal
between the box and the roof. Nail in place with roofing nails. Remove any combustible material that might be inside
the support box.
5. Complete the cathedral ceiling installation by following the same procedures outlines in steps 2 through 6 for Flat Ceiling
Installation, page 24 and above.
ROOF PITCHH (feet)
Flat to 6/121.0
Over 6/12 to 7/121.25
Over 7/12 to 8/121.5
Over 8/12 to 9/122.0
Over 9/12 to 10/122.5
Over 10/12 to 11/123.25
Over 11/12 to 12/124.0
*H = Minimum height from roof to lowest
discharge opening of vent.
Figure 33 - Minimum chimney clearance
54D5031 25
Page 26
FLEX VENT INSTALLATION
1. Flexible UL1777 listed venting may be used in any venting
UL1777
Flex vent
application where rigid direct vent components can be used.
All restrictions, clearances and allowances that pertain to
the rigid piping apply to the fl exible venting. Flex kits may
not be modifi ed. Flex kits may be added to the end of a vent
run made of rigid vent sections using pipe manufacturer’s
approved fl ex to pipe adapters. This may occur only if doing
so does not violate any of the venting length, height,
routing, horizontal to vertical ratio requirements or
clearance considerations detailed in this manual.
2. The fl ex adapter starter kit (DVFA/8) is used to attach fl ex
venting to the appliance starting collar. It includes 4" inner
1¾ in. fl exible pipe
and adapter outer
collar overlap
DVFA/8
inner adapter
outer adapter
Gear clamps
Securing screws
(3 places
equidistant just
above gear
clamp)
and 7" outer adapter rings (refer to Figure 1).
• The inner and outer adaptor rings are required to start
all fl ex runs.
• Never install damaged or torn fl exible venting.
• Over tightening clamps may rip, tear, or otherwise
Appliance starting
collar
damage fl exible venting.
• The adaptor kit does not include individual pipe
sections which may be purchased separately. (UL1777
listed type fl ex venting only.)
3. Start the fl exible vent as follows—
A. Installing the inner fl ex adaptor and pipe (see Figure 1).
1. Insert the long side of the 4" inner ring inte exhaust
Typical appliance connection
Figure 1 —
pipe, gently tap to seat into place, and secure with
screws.
2. Slide the small gear clamp over the inner fl exible vent pipe, and push out of the way.
3. Pull and extend the inner fl exible vent.
4. Slide the inner vent onto the adapter collar, for a minimum 1¾" overlap.
5. Locate the clamp at approximately ¾" from the fl ex end and tighten.
6. Secure the clamped inner section with three self tapping screws, drilled equidistance, just above the clamp
perimeter.
B. Installing the outer fl ex pipe (refer to Figure 1).
1. Firmly insert the outer adapter ring into the outer appliance starting collar and secure with screws.
2. Slide the large gear clamp over the outer fl exible vent pipe, and push out of the way.
3. Pull and extend the outer fl exible vent.
4. Slide the outer vent onto the appliance collar outer adapter for a minimum 1¾" overlap.
5. Locate the clamp at approximately ¾" from the fl ex end and tighten.
6. Secure the clamped outer section with three self tapping screws, drilled
equidistant, just above the clamp perimeter.
C. Routing UL1777 fl ex pipe.
1. Always maintain the required clearance when routing the fl ex vent assembly.
2. Install fi restop spacers (see Figure 3) when penetrating ceilings, attic spaces, or walls.
UL1777
Flex vent
5" radius
Flex vent pipe spacers: Refer to manufacturer’s
specifi cations for correct positioning of the spacer springs to
maintain proper distance between inside and outside pipe.
NOTE
Minimum radius for fl ex vent section
Figure 2 —
26 54D5031
Page 27
FLEX VENT INSTALLATION
3. Do not allow the fl exible vent to bend in radius tighter than 5" (127mm). Refer to Figure 2.
4. Horizontal runs of fl exible vent shall be supported at maximum 2 foot intervals; vertical runs, fi ve feet intervals. Metal strapping, properly secured, is an acceptable means to support the fl exible vent.
5. Flexible vent spacers are to be installed at intervals prescribed by the fl exible vent manufacture; and in such a way as to maintain concentric inner and outer vent spacing.
D. Attaching fl exible venting to vertical termination assemblies.
1. When using Simpson pipe, a MHS fl ex-to-pipe adaptor and/or rigid pipe section(s) is required to connect the fl exible vent assembly to the vertical termination by using three self penetrating screws.
2. Review Figure 4 and corresponding instructions for proper overlap, clamp and screw placement.
3. Three each self penetrating screws are drilled opposite one another and below the gear clamp.
4. Use only listed and approved terminations and accessories, installed per the installation instructions and Figure 3.
E. Installing fl exible venting to horizontal termination assemblies.
1. Connect the 4" fl exible vent to the horizontal termination as in Figure 5.
2. Slide termination cap adapter ring over the termination cap’s outside pipe and secure with three screws.
3. Connect the 7" fl exible vent to the termination adapter ring as in Figure 5.
4. Review Figure 5 for proper overlap and clamp placement
5. Three each self penetrating screws are drilled opposite one another and below the gear clamp.
6. Use only listed and approved terminations and accessories, installed per the termination instructions
and Figure 5.
Rigid pipe
length
Flex to pipe
adapter
(FPA/8)
1¾ in. fl exible pipe
and adapter outer
collar overlap
Flashing
Rigid pipe
length
Termination
cap
Storm collar
Roof support
Securing
screws
(3 places
equidistant
just above
gear clamp)
Gear
clamp
Flex to pipe
adapter
(FPA/8)
UL1777 fl ex pipe
Fire stop
DVFA/8 Adapter
Figure 3 —
Typical vertical fl ex vent installation
Securing screws
(three places
equidistant, just
above gear clamp)
UL1777
Flex vent
Typical horizontal fl ex vent installation
Gear clamp
UL1777
Flex vent
Figure 4 — Typical pipe connection
Monessen horizontal
vent termination
Termination to fl ex
adapter (FTA7/8)
Gear
clamps
1¾ in. fl exible pipe
and termination outer
collar overlap
Figure 5 —
54D5031 27
Page 28
FIREPLACE INSTALLATION
CHECK GAS TYPE
Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install fireplace. See dealer
where you purchased the fireplace for proper fireplace for your gas type or conversion kit.
INSTALLING GAS PIPING TO FIREPLACE / BURNER SYSTEM LOCATION
INSTALLATION ITEMS NEEDED
Before installing fireplace and burner system, make sure you have the items listed below.
• External regulator (supplied by installer) • Piping (check local codes) • Sealant (resistant to propane/LP gas)
• approved flexible gas line with gas connector (if allowed by local codes — not provided)
1
* A CSA design-certified equipment shutoff valve with
Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming
gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not reduce incoming
gas pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown
in Figure 39. Pointing the vent down protects it from freezing rain or sleet.
/8" NPT tap is an acceptable alternative to test gauge connection.
A qualifi ed installer or service person
must connect appliance to gas supply.
Follow all local codes.
WARNING
For propane/LP units, never connect fi replace directly to the propane/LP supply. This
burner system requires an external regulator (not supplied). Install the external regulator
between the burner system and propane/LP supply.
CAUTION
External
Regulator
100 lb. (min)
Propane/LP
Supply Tank
Vent
Pointing
Down
Use only new black iron or steel pipe.
Internally tinned copper or copper
tubing can be used per National Fuel
Code, section 2.6.3, providing gas
meets hydrogen sulfide limits, and
where permitted by local codes. Gas
piping system must be sized to provide
CAUTION
minimum inlet pressure (listed on
data plate) at the maximum fl ow rate
(BTU/hr). Undue pressure loss will
occur if the pipe is too small.
When using copper of flex connectors use only fittings
approved for gas connections. The gas control inlet is
Figure 39 - External Regulator with Vent Pointing
Down (Propane/LP Only)
28 54D5031
3
/8" NPT.
Page 29
FIREPLACE INSTALLATION
Only persons licensed to work with
gas piping may make the necessary
gas connections to this appliance.
A manual shutoff valve must be installed
upstream of the appliance. Union tee
1
and plugged
/8" NPT pressure tapping
point should be installed upstream of
WARNING
NOTE : The gas line connection may be made using
some municipalities have additional local codes it is always best to consult your local authorities and
the current edition of the National Fuel Gas Code ANSI.Z223.1, NFPA54. In Canada CAN/CGA-B149 (1 or
2) Installation Code.
A listed manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pressure tapping
point should be installed upstream of the appliance. See Figure 39.
IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is
for turning on or shutting off the gas to the fi replace.
Check your building codes for any special requirements for
locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male threads. This will
prevent excess sealant from going into pipe. Excess sealant in
pipe could result in clogged burner system valves.
1
/2" rigid tubing or an approved fl ex connector. Since
the appliance. See Figure 40.
CAUTION
Use pipe joint sealant that is resistant
to liquid petroleum (LP) gas.
CAUTION
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 40. Locate sediment trap/drip
leg where it is within reach for cleaning. Install in piping system between fuel supply and burner system. Locate sediment
trap/drip leg where trapped matter is not likely to freeze. A sediment trap collects moisture and contaminants and keeps
them from going into the burner system gas controls. If sediment trap/drip leg is not installed or is installed wrong, burner
system may not run properly.
Approved Flexible
Gas Line
Sediment Trap/Drip Leg
Tee Joint
Pipe Nipple
Cap
CSA Design-Certifi ed Equipment
Shutoff Valve with
3" Minimum
1
/8" NPT Tap*
Natural Gas
From Gas Meter
(4.5" W.C. to 10.5" W.C. Pressure)
Propane/LP
From External Regulator
(11" W.C. to 13" W.C. Pressure)
Figure 40 - Gas Connection
54D5031 29
Page 30
CHECKING GAS PRES SURE AND ELECTRICAL INSTALLATION
1. Check gas type. The gas supply must be the same as
stated on the appliance’s rating decal. If the gas supply
is different from the fireplace, STOP! Do not install
the appliance. Contact your dealer immediately.
2. To ease installation, a 30" (mm) flex line with manual
shut-off valve has been provided with on this appliance.
Install and attach
3. After completing gas line connection, purge air from
gas line and test all gas joints from the gas meter to
the fireplace for leaks. Use a solution of 50/40 water
and soap or a gas sniffer.
4. To adjust flame height, turn HI/LO knob to HI to get
maximum pressure to burner. Turn HI/LO knob to LO
to get minimum pressure.
5. To check gas pressures at valve, turn captured screw
counter clockwise 2 or 3 turns and then place tubing to
pressure gauge over test point. Turn unit to high. See Figure 41. After taking pressure reading, be sure and
turn captured screw clockwise firmly to reseal. Do not
over torque. Check test points for gas leaks.
1
/2" gas line onto shut-off valve.
Pressure
Test “IN”
Pressure
Test “OUT”
HI/LO
Knob
Figure 41 - Gas Pressure Check at Gas Valve
Pilot Adjustment
Screw
Do not use open fl ame to check
for gas leaks.
WARNING
ELECTRICAL WIRING
This fireplace will work without any electrical supply except to operate blower and electronic ignition system.
NOTE: If installed in mobile home, fireplace must be bolted securely to floor.
Electrical connections should only be performed by a qualified, licensed electrician.
Main power must be off when connecting to main electrical power supply or performing
service. All wiring shall be in compliance with all local, city, and state codes. The
appliance, when installed, must be electrically grounded in accordance with local
codes, or in the absence of local codes, with the National Electrical Code ANSI/ NFPA
WARNING
70 (latest edition) and Canadian Electrical Code, CSA C22.1.
Label all wires before disconnecting when servicing controls. Wiring errors can cause
improper and dangerous operation.
CAUTION
Verify proper operation after servicing.
30 54D5031
Page 31
ELECTRICAL INSTALLATION
REMOTE WALL MOUNTED SWITCH
A remote wall switch and up to fifteen (15) feet of 18
gauge wire may be used with this appliance. Attach the
wall switch in a junction box at the desired location on the wall. See Figure 42. Do not extend beyond the wall switch wire
length provided.
NOTE: Extended lengths of wire may cause the fi replace not to function properly. Longer length of wire
is permitted if the wire is made out of larger gauge (diameter) wire. Always check with local code.
RS
OPTIONAL WALL
SWITCH
ON
OFF
WHITE
BLACK
PILOT
OFF
Do not connect 110V to wall switch.
WARNING
OFF
ON
BLUE
ON
BLACK
HI
LO
TH
TP
TH/TP
GRAY
BLUE
BLACK
OPTIONAL REMOTE
RECEIVER
ON
RS
OFF
Figure 42 - Wiring Diagram for Wall Switch
REMOTE WALL SWITCH
Position the wall switch. Do not extend beyond the 15 feet of wire.
OPTIONAL DC REMOTE SYSTEMS
These instructions replace the section entitled Hearth Mount in the Millivolt hand held remote instructions supplied with
the remote.
1. Plug in remote connector wire to remote receiver.
2. Connect the wire terminal from the remote receiver. This replaces the 15' wall switch connection to the switch. See Figure 42.
3. Mount remote control receiver at junction box (for your wall switch).
OPTIONAL FAN/BLOWER
SYSTEMS
The junction box for the fan/blower
systems has been factory installed. This
system requires that 110-120 VAC to be
wired to the factory installed junction
box before the fireplace is permanently
installed. See Figure 43.
BLACKBLACK
BLACK
GREEN
TANTANWHITE
SPEED CONTROL
OPTIONAL THERMOSTATIC SWITCH
Figure 43 - Blower Wiring Diagram
54D5031 31
Page 32
GLASS REMOVAL & BRICK INSTALLATION
GLASS FRAME REMOVAL
1. Release two clamps on bottom of fireplace. See Figure 44.
2. Tilt glass frame out and lift glass frame up until it clears three tabs on top of fireplace.
3. Set glass frame aside.
Glass Frame
Clamps
Figure 44 - Removing Glass Frame
CAUTION: Each clamp has a quick spring force. When reinstalling
clamps, keep fi ngers clear.
BRICK INSTALLATION
1. Remove glass door frame and log set.
2. Remove the glass heat shield, baffle and rear bracket.
3. Install the center fi rebrick panel on the back wall fi rst. Stand fi rebrick panel straight up against the back of fireplace
with the bottom edge at bottom of inner fi rebox.
4. Repeat Step 3 with the left and right side firebrick panels. Secure the top of each side fi rebrick panel to the fi replace with
one retainer bracket and one screw.
5. Use a screw gun to drive in the self-drilling screw into the sheet metal through the hole in the retainer bracket.
6. Re-install glass heat shield, baffle and rear bracket.
7. Re-install glass door frame and log set.
32 54D5031
Page 33
PLACEMENT OF LAVA ROCK, ROCK WOOL
AND LOGS
1. Make sure that the grate is hooked onto the rear
bracket.
2. Sprinkle the lava rocks around and in front of the burner
at bottom of firebox.
3. Place rock wool in a dime size pieces over the small
holes and partially over large size holes. Do not place
any over slots at rear of burner. The rock wool over
the large holes may need adjustment after firing the
unit to establish yellow flame in the front. See Figure
46.
4. Place log #1 into place by setting the log over the two
pins on the grate toward the back. The two round holes
on the bottom of the logs should go over the two pins
on the grate. See Figure 47.
Cover with
Rock Wool
FINAL INSTALLATION
HBDV300
Burner
HBDV400
5. Place log #2 into place by matching the two holes on
the bottom of the log with the two pins located on top
of the burner. When this log is in place it is positioned
at an angle and the right side of the log is seated over
the right tong of the grate. See Figure 48.
Do not use the entire bag of rock wool to
cover the burner. This could cause the fl ame
to burn poorly and may lead to sooting.
WARNING
Do not sprinkle the lava rock or ember
chunks on top of the burner. This may cause
potential sooting, glass breakage and a fi re
hazard.
WARNING
Figure 45 a & b - Placement of Rock Wool
on Burners
Figure 46 - Placement of Rock Wool on Burner
Log #1
Figure 47 - Placement of Log 1.
54D5031 33
Page 34
FINAL INSTALLATION
Log #3
Log #2
Figure 48 - Placement of Log 2
6a. For 400 models, place log #3 into place by matching the notch on the side of the log with the protrusion on the rear log.
Set the left side of the log over the cross bar of grate by placing the notch of the log on the grate bar. Be sure the log is
tilted backward. When this log is in place, it is seated sideways. See Figure 49.
6b. For 300 models, place log #3 into place by matching the notch on the side of the log with the protrusion on the rear log.
Set the left side of the log over the grate bar in the front by placing the notch of the log on the grate bar. Make sure the
log is tilted backward. When this log is in place, it is seated sideways. See Figure 49.
Log #4
Log #5
Figure 50 - Placement of Log 4
Figure 49 - Placement of Log 3
Figure 51 - Placement of Log 5
7. Place log #4 into place by matching the two notches on the bottom of this log with the two protrusions on log #1&2.
This log, when seated, fits in the middle above logs 1 & 2. See Figure 50.
8. Place log #5 into place by matching the two notches on the bottom of this log with the two protrusions on log #1&2.
This log, when seated, is positioned toward the right. See Figure 51.
9a. For 400 models, place log #6 into place toward the left by sitting the notch on this log on the left tong of the grate and
set the tips of the log on the burner in front the large round holes. See Figure 52.
9b. For 300 models, place log #6 into place toward the left by sitting the notch on this log on the left tong of the grate and
set the tips of the log on the burner. See Figure 52.
10. For 400 models only, place log #7 into place by hooking the end of the log on the second right tong of the grate and
resting the other end over the lava rock. See Figure 53. (There is no seventh log on 300 models.)
11. Adjust the screws and set the andirons over the cross bar of the grate between the two outer tongs on the right and left
sides of the grate.
34 54D5031
Page 35
Log #6
FINAL INSTALLATION
Log #7
Figure 52 - Placement of Log 6
Figure 53 - Placement of Log 7 (HBDV400 only).
Figure 54 a & b - Andiron Placement (400DVBH and 300DVBH).
INSTALLING UNIVERSAL ANDIRONS
Bolt bracket through lower slot into top andiron hole. Slide clip over horizontal fi replace grate bar. SeeFigure 55.
Top andiron hole
Lower andiron hole
Horizontal fi replace grate bar
Top bracket slot
Lower bracket slot
Figure 55 - Universal Andirons
54D5031 35
Page 36
OPERATING INSTRUCTIONS (MILLIVOLT)
FOR YOUR SAFETY READ BEFORE LIGHTING
If you do not follow these instruction
exactly, a fi re or explosion may result
causing property damage, personal
injury or loss of life.
WARNING
A. This appliance is equipped with a pilot which must be lit with built-in piezo ignitor while following these
instructions exactly.
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Turn off all gas to the appliance.
• Open windows.
• Do not attempt to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in, or turn the gas control knob. Never use tools. If the knob will not push in
or turn by hand, don't try to repair it. Call a qualified service technician. Force or attempted repair may
result in a fire or explosion.
D. Do not use this appliance if any part of it has been under water. Immediately call a qualified service tech-
nician to inspect the appliance and to replace any part of the control system and any gas control that has
been under water.
LIGHTING PILOT FOR THE FIRST TIME
INITIAL LIGHTING
Purge air from the supply line as follows:
• Open main shutoff valve.
• Unscrew main pressure test point.
• Leave inlet test screw open until gas comes in.
• When gas is flowing, tighten inlet screw immediately.
LEAK TESTING
1. Follow the pipe from the gas supply line connection to the gas valve. Check connection for leaks with
soap and water mixture.
2. Next check for gas leaks at the burner with soap and water mixture.
Never use an open fl ame to
check for gas leak.
WARNING
3. Check the pilot for gas leaks with soap and water mixture.
36 54D5031
Page 37
OPERATING INSTRUCTIONS (MILLIVOLT)
LIGHTING PILOT FOR THE FIRST TIME
APPROVED LEAK TESTING METHOD
You may check for gas leaks with the following methods only:
• Soap and water solution
• An approved leak testing spray
• Electronic sniffer
Never check for gas leak with open fl ame!
DANGER
Check for gas leaks in each of the following locations:
• Pipe from the gas supply line connection to the gas valve
If using a soap and water
solution to test for leaks,
DO NOT spray solution onto
control body.
WARNING
NOTE: Remove any excessive pipe
compound from the connections.
Excessive pipe compound can set off
electronic sniffers.
• Burner connections • Field made joints / gas shutoff valve
• Pilot • Factory made joints
• Each joint or connection • All joints on valve and control body
LIGHTING PILOT
The control has an interlock device that does not allow the lighting of the fi replace up
to the moment the safety device of the fl ame has not interrupted the gas fl ow. After
that period of time (when the magnet is closed), it is possible to start the lighting
operation.
The gas control knob is designed to be operated by hand. DO NOT use any tools
WARNING
during this operation. Damaged knobs may result in serious injury.
1. Depress and turn knob counterclockwise
to pilot position.
2. Depress fully and hold pilot gas knob. Depress
piezo igniter as many times as needed to ignite pilot.
Keep knob fully depressed for a few seconds.
Release and check that pilot continues to burn.
O
N
T
O
L
I
P
F
F
O
PILOT
If the pilot does not stay lit, repeat steps 1 and 2.
Figure 56 - Pilot Position
Continued on next page
54D5031 37
Page 38
OPERATING INSTRUCTIONS (MILLIVOLT)
LIGHTING BURNER
MAIN BURNER SWITCH
The “ON/OFF/RS” switch for the main burner can be found behind door of the
fireplace. This switch allows you to turn on and to turn off the main burner without
using the gas valve knob. Make sure the button is in the “ON” position to light
the main burner. See Figure 57.
LIGHTING THE BURNER
Depress and turn the knob counterclockwise to the “ON” position. See
Figure 58.
PILOT POSITION
Depress and turn knob to pilot position to keep burner off while maintaining the
pilot light. See Figure 59.
It will take less than four (4) seconds for the burner to ignite.
O
N
T
O
L
I
P
F
F
O
PILOT
ON
OFF
RS
Figure 57 -
On/Off/RS Switch
N
O
PILOT
O
F
F
P
T
I
L
O
Figure 58 - On Position
T
Depress and turn knob clockwise
Figure 59 - Pilot Position
TO TURN OFF GAS
to “OFF” position. See Figure 60.
P
I
L
O
T
F
F
O
O
N
PILOT
Figure 60 - Off Position
38 54D5031
Page 39
CLEANING AND MAINTENANCE
Turn off gas before servicing fi replace. It is recommended that a qualifi ed service
technician perform these check-ups at the beginning of each heating season
WARNING
BURNER, PILOT AND CONTROL COMPARTMENT
Keep the control compartment, logs, and burner areas surrounding the logs clean by vacuuming or brushing at least twice
a year. Make sure the burner porting, pilot air opening and burner air opening are free of obstructions at all times.
Thermocouple
PILOT FLAME
The flames from the pilot should be visually checked as soon as the
heater is installed and periodically during normal operation. The pilot
flame must always be present when the fireplace is in operation. See
Figure 61. The pilot flame has three distinct flames, one engulfing the
thermopile, one engulfing the thermocouple, and the other reaching
to the main burner.
Thermopile
BURNER
Inspect area around the injector. Remove any lint or foreign material
with a brush or vacuum.
BURNER FLAME
The flames from the burner should be visually checked
as soon as the heater is installed and periodically during
normal operation. In normal operation, at full rate, and after
operating for about 15 to 30 minutes, the flame should be
yellow and slightly taller than the rear log. See Figure 62.
If the flame is blue and only in the center, turn off unit and
let cool. After unit is cool, remove logs and check to make
sure the back holes in the burner are not covered with rock
wool. If the back holes are clear, add more rock wool to the
center of the burner. Replace logs.
NOTE: The type of installation, vent system
confi guration, and wind effects may cause the fl ame
patterns to vary.
Figure 61 - Pilot Flame
Figure 62 - Burner Flame Appearance
54D5031 39
Page 40
CLEANING AND MAINTENANCE
VENT SYSTEM
The fireplace and venting system should be inspected before initial use and at least annually by a qualified field service
person. Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the airflow. Inspect
entire venting system to ensure proper function.
GLASS DOOR
Thoroughly clean the inside of the glass door after using the fireplace for ten hours. Periodically clean the glass door as
necessary.
When cleaning the glass, remember:
• Do not remove the glass when hot. Allow glass to cool before removal.
• NEVER use abrasive materials.
• Keep children and pets a safe distance away.
• Never operate the fireplace without the glass door properly secured.
• Never operate the fireplace if the glass is broken.
• Replace any glass that is chipped, cracked, or broken. Replacement glass door assemblies MUST be supplied by the
fireplace manufacturer – No substitute materials may be used.
• Handle glass door with care to avoid striking or scratching it on hard objects.
To clean glass door, follow “Glass Removal” procedure outlined in the Final Installation section. Film deposit on the inside
of the glass should be cleaned off using a nontoxic, non-corrosive, non-abrasive, mild-cleaning solution. Simply apply an
adequate amount to the glass and wipe off with a damp cloth. After all maintenance has been completed, re-install glass
door.
LOGS
Leave logs installed in the fireplace for cleaning. Vacuum surface of the logs with a brush attachment. If logs must be removed
for cleaning, handle carefully by holding gently at each end. Gloves are recommended to prevent skin irritation from ceramic
fibers. If skin becomes irritated, wash gently with soap and water. Vacuum surface of logs with brush attachment or brush
logs with a soft bristle brush (i.e. clean, dry paintbrush). To place logs back in the fireplace, see “Log Placement” found in
the Final Installation section.
NOTE: Do not use fl uids to clean ceramic fi ber logs.
ROCK WOOL
Replace or add rock wool as required following installation instructions in the Final Installation section of this manual.
40 54D5031
Page 41
STANDING PILOT IGNITION
SYMPTOM POSSIBLE CAUSE ACTION
TROUBLESHOOTING
1. Spark ignitor will
not light pilot after
repeated triggering of
piezo.
2. Pilot will not stay lit
after carefully following lighting instructions.
. Pilot burning, valve
knob turned to “ON”,
switch is turned to
“ON” or “RS”, but
burner will not ignite.
A. Wire disconnected.
B. Defective ignitor.
C. No gas or low gas pressure.
D. No Propane/LPG in tank
A. Defective thermocouple
B. Defective valve
A. Defective switch, wall
switch, remote control or
wire
B. Pilot flame too small
C. Defective or malfunction-
ing thermopile
D. Defective valve
A. Open door and check to make sure wire is connected to ignitor.
B. Check for spark at electrode and pilot. If no spark and electrode
wire is properly connected, replace pilot assembly.
C. Check remote/manual shut off valve from fireplace. Low pres-
sure can be caused by bent lines, restricted lines, low pressure
line pressure. Consult with plumber or gas supplier.
D. Check Propane/LPG tank. Refill tank.
A. Check that thermocouple flame impinges on thermocouple.
Clean and/or adjust pilot for maximum flame impingement.
Ensure that the thermocouple connection at the gas valve is fully
inserted and tight.
Disconnect the thermocouple from the valve, place one millivolt
lead wire on the tip of the thermocouple and the other meter lead
wire on the thermocouple copper lead. Start the pilot and hold
the valve knob in. If the millivolt reading is less than 15 mV,
replace pilot assembly.
B. If thermocouple is producing more than 15 mV, replace faulty
valve.
A. Check switch and wire for proper connection. Place jumper
wires across terminals of switch. If burner comes on, replace
defective switch.If the switch is OK, repeat the same procedure
on remote control If burner comes on, replace remote control.
Place jumper wire across wire at gas valves (terminals marked
TH and TP/TH). If burner comes on, wires are faulty or connections are bad. Replace wire.
B. If pilot flame is not close enough to the thermopile, adjust pilot
flame.
C. Check thermopile wire connections to make sure all are tight
and that the thermopile is fully inserted into pilot assembly.
Check thermopile with a millivolt meter. Connect leads to TP
and TP/TH terminals on the control valve. If meter reading is
below 325 mV, replace pilot assembly.
D. Turn valve knob to “On” and switch to “ON.” Take a reading at
the thermopile leads (TP & TP/TH) on the valve. If the meter
reads greater than 175 mV and the burner does not light, replace
defective valve.
54D5031 41
Page 42
TROUBLESHOOTING
STANDING PILOT IGNITION
SYMPTOM POSSIBLE CAUSE ACTION
4. Frequent pilot outage
problem.
5. The pilot and main
burner extinguish
while in operation
6. Glass Soots
7. Flame burn blue and
lifts off burner (ghosting)
A. Pilot flame may be too high or
too low, causing pilot safety
to drop out
A. Inner vent pipe leaking
exhaust gases back into
system
B. Horizontal vent improperly
pitched
C. Improper vent cap installation
A. Flame impingement on logs
A. Insufficient oxygen being
supplied
A. Clean and adjust the pilot flame for maximum flame impinge-
ment on thermocouple.
A. Check for flue product leak. Replace defective pipe section.
B. Check horizontal-venting piping is running upward 1/4" per foot.
Do not run the pipe level or downward.
C. Check for proper installation and freedom from debris or block-
age.
A. Install log set per the instructions
Inspect the injector and air intake area. Make sure this area does
not have any blockage from debris and clean.
Check gas supply.
A. Ensure that the vent cap is installed properly and free of debris.
Ensure that the vent system joints are tight and have no leaks.
Ensure that no debris has been blocking the inner air intake at the
bottom back of the combustion chamber. Ensure that the glass is
properly secure and latch.
Rear Vent Termination Kit includes Termination Cap with built in vinyl
siding standoff, heat defl ector, fi restop and adj 11" to 14 5/8" pipe.
Side Wall Termination Kit. Includes termination cap with built in vinyl
siding standoff, heat defl ector, fi restops, adj 11" to 14 5/8" pipe, and
90° elbow.
Side Wall Flexible Pipe Termination Kit. Includes termination cap
with built-in vinyl siding standoff, heat defl ector, fi restop, 20" to 48" fl exible pipe and adapter.
Thru-Roof Flexible Pipe Termination Kit w/fl ex adapter 24" rigid pipe
and roof support 4" x 6 5/8"
Round Horizontal Termination Cap Square Base (aluminum)46DVA-HRCS——
Sconce Termination Cap (aluminum)46DVA-HSC——
3 Left Log 1 54D5121 54D5025
4 Mid Top Log 1 54D5123 54D5026
5 Right Top Log 1 54D5122 54D5027
6 Left Front Log 1 54D5124 54D5028
7 Right Front Twig 1 N/A 54D5029
3
4
6
7
1
5
2
48 54D5031
Page 49
NOTES
MASSACHUSETTS RESIDENTS ONLY:
PLEASE READ AND FOLLOW THESE
SPECIAL REQUIREMENTS
NOTE REGARDING VENTED PRODUCTS
This product must be installed by a licensed plumber or gas fi tter when installed within the Commonwealth of Massachu-
setts.
Any residence with a direct vent product must have a CO detector installed in the residence.
Installation of the fi replace or vented gas log in the State of Massachusetts requires the damper to be permanently removed
or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have a T shutoff valve.
NOTE REGARDING VENT FREE PRODUCTS
This product must be installed by a licensed plumber or gas fi tter when installed within the Commonwealth of Massachu-
setts.
In addition, vent free products may not be installed in a bedroom or bathroom regardless of size or type in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have a T shutoff valve.
CARBON MONOXIDE DETECTOR REQUIREMENTS
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side
wall exhaust vent termination is less than seven (7) feet above fi nished grade in the area of the venting, including but
not limited to decks and porches, the following requirements shall be satisfi ed:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber or gasfi tter shall observe that a hard wired carbon monoxide
detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed.
In addition, the installing plumber or gasfi tter shall observe that a battery operated or hard wired carbon monoxide
detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services
of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent
fl oor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation,
the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however,
that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
54D5031 49
Page 50
SPECIAL REQUIREMENTS CONTINUED
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certifi ed.
3. SIGNAGE. A metal or plastic identifi cation plate shall be permanently mounted to the exterior of the building at
a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch
in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage
installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer
of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system
components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the
venting system shall include:
NOTES
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the
manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts
for venting the fl ue gases, but identifi es “special venting systems,” the following requirements shall be satisfi ed by the
manufacturer:
1. The identifi cation of each “special venting system” shall include either the listing of the website, phone number or
manufacturer's address where the venting system installation instructions can be obtained; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions provided with that
system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for the Product Approved side wall horizontally vented gas fueled equipment and
all the venting instructions, parts lists, and/or all design instructions for the venting system shall remain with the appliance or equipment at the completion of the installation.
50 54D5031
Page 51
NOTES
54D5031 51
Page 52
NOTES
52 54D5031
Page 53
NOTES
54D5031 53
Page 54
LIMITED LIFETIME WARRANTY POLICY
LIFETIME WARRANTY
The following components are warranted for life to the original owner, subject to proof of purchase: Firebox, Combustion
Chamber, Heat Exchanger, Grate and Stainless Steel Burners.
FIVE YEAR WARRANTY
The following components are warranted five (5) years to the original owner, subject of proof of purchase: Ceramic Fiber
Logs.
BASIC WARRANTY
Monessen Hearth Systems (MHS) warrants the components and materials in your gas appliance to be free from manufacturing
and material defects for a period of two years from date of installation. After installation, if any of the components manufactured by MHS in the appliance are found to be defective in materials or workmanship, MHS will, at its option, replace or
repair the defective components at no charge to the original owner. MHS will also pay for reasonable labor costs incurred
in replacing or repairing such components for a period of two years from date of installation. Any products presented for
warranty repair must be accompanied by a dated proof of purchase.
This Limited Lifetime Warranty will be void if the appliance in not installed by a qualified installer in accordance with the
installation instructions. The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained
according to the operating instructions supplied with the appliance, and does not extend to (1) firebox/burner assembly
damage by accident, neglect, misuse, abuse, alterations, negligence of others, including the installation thereof by unqualified installers, (2) the costs of removal, reinstallation or transportation of defective parts on the appliance, or (3) incidental
or consequential damage. All service work must be performed by an authorized service representative.
This warranty is expressly in lieu of other warranties, express or implied, including the warranty of merchantability of fitness
for purpose and of all other obligations or liabilities. MHS does not assume for it any other obligations or liabilities in connection with sale or use of the appliance. It states that do not allow limitations on how long an implied warranty lasts, or do
not allow exclusion of indirect damage, those limitations of exclusions may not apply to you. You may also have additional
rights not covered in the Limited Lifetime Warranty.
MHS reserves the right to investigate any and all the claims against the Limited Lifetime Warranty and decide upon method
of settlement.
For information about this warranty, contact:
Technical Services
Monessen Hearth Systems
149 Cleveland Drive
Paris, Kentucky 40361
JULY 2008 P/N 54D5031 • Rev. 4
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.