Monessen Hearth CSVF20SNV, CSVF30SPV, CSVF20SPV, CSVF30SNV User Manual

ON
OFF
UNVENTED GAS
CAST IRON STOVE
INSTALLATION AND OPERATING
INSTRUCTIONS
MODELS:
CSVF20SNV CSVF30SNV CSVF20SPV CSVF30SPV
Natural Gas or
Propane/LPG
Milli-Volt Control
WARNINGS
WARNINGS
This appliance may be installed in an aftermarket, permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appli ance is onl y for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to page 8.
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
– Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
– WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
– Installation and service must be performed by
a qualified installer, service agency or the gas supplier.
READ AND SAVE THESE INSTRUCTIONS
CONTENTS
Important Safety Information ..........................3
Product Features .............................................. 5
Dimensions ....................................................... 6
Getting Started .................................................. 7
Product Specifications..................................... 8
Ignition Controls ............................................ 8
Pilot ............................................................... 8
Thermal Generator ....................................... 8
General Installation Information ..................... 9
Codes ........................................................... 9
Adequate Combustion and Ventilation Air .... 9
Clearances / Height Requirements ............... 11
Removing Unit from Crate ............................. 13
Connecting the Gas ........................................ 14
Checking Gas Pressure ................................. 15
Connecting Remote Receiver ....................... 15
Log Placement ................................................ 19
Installing Logs on Grate .............................. 19
Rock Wool Installation ................................... 20
Flame Appearance .......................................... 20
Checking Pilot Flame .................................. 20
Checking the Burner Flame ........................ 21
Operating Instructions ................................... 21
For Your Safety Read Before Lighting ........ 22
Milli-Volt Control Lighting Instructions ......... 23
To Turn Off Gas to Heater ........................... 23
Match Lighting Instructions ......................... 24
Cleaning and Servicing .................................. 24
Replacement Parts List .................................. 25
Logs ............................................................ 25
Burner Assembly ......................................... 26
Troubleshooting ............................................. 28
Warranty .......................................... Back Cover
Electrical Wiring ............................................. 16
Connecting Optional Wall Switch or
Thermostat .................................................. 16
Checking System Operation ....................... 16
Installing Thermostat Sensor ...................... 17
Operating Thermostat Sensor ..................... 18
2 58D6002
IMPORTANT SAFETY INFORMATION
INSTALLER
Please leave these instructions with the owner.
IMPORTANT
Read these instructions carefully before installing or trying to operate this vent-free gas heater.
• Any change to this heater or its controls can be dangerous.
• Improper installation or use of the heater can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
• Do not allow fans to blow directly into the stove. Avoid any drafts that alter burner flame patterns.
WARNING
• Do not use a blower insert, heat exchanger insert or other accessory, not approved for use with this heater where applicable.
1. Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
2. Children and adults should be alerted to the hazard of high surface temperature and should stay away to avoid burns or clothing ignition.
3. Young children should be carefully supervised when they are in the same room with the apli ance.
4. Do not place clothing or other flammable material on or near the appliance.
5. Any safety screen or guard removed for servicing an appliance, must be replaced prior to operating the heater.
6. Installation and repair should be done by a qualified service person.
7. To prevent malfunction and/or sooting, an unvented gas heater should be cleaned before use and at least annually by a professional service person. More frequent cleaning may be required due to exces­sive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageways be kept clean.
8. CARBON MONOXIDE POISONING: Early signs of
carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immediately. Have the heater serviced as it may not be operating properly.
-
OWNER
Please retain these instructions for future reference
9. The installation must conform with local codes or, in
the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.l/NFPA54.
10. This unit complies with ANSI Z21.11.2-2001 Unvented Heaters.
11. Do not install heater in a bathroom or bedroom unless approved for bedroom use.
12. Correct installation of the ceramic fiber logs, proper location of the heater, and annual cleaning are neces­sary to avoid potential problems with sooting. Sooting, resulting from improper installation or operation, can settle on surfaces outside the fireplace. See log placement instructions for proper installation.
13. Avoid any drafts that alter burner flame patterns. Do not allow fans to blow directly into fireplace. Do not place a blower inside burn area of firebox. Ceiling fans may create drafts that alter burner flame patterns. Sooting and improper burning will occur.
14. Caution: Candles, incense, oil lamps, etc. produce com- bustion by-products including soot. Vent-free appliances will not filter or clean soot produced by these types of products. In addition, the smoke and/or aromatics (scents) may be reburnt in the vent-free appliance which can produce odors. It is recommended to minimize the use of candles, incense, etc. while the vent-free appliance is in operation.
Continued on page 4
.
58D56002 3
IMPORTANT SAFETY INFORMATION
Continued from page 3
15. This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be pro­vided. See page 8.
16. Keep room area clear and free from combustible materi­als, gasoline and other flammable vapors and liquids.
17. Unvented gas heaters are a supplemental zone heater. They are not intended to be a primary heating appli­ance.
18. Unvented gas heaters emit moisture into the living area. In most homes of average construction, this does not pose a problem. In houses of extremely tight construction, addition mechanical ventilation is recommended.
19. During manufacturing, fabricating and shipping, various components of this appliance are treated with certain oils, films or bonding agents. These chemicals are not harmful but may produce annoying smoke and smells as they are burned off during the initial operation of the appliance; possibly causing headaches or eye or lung irritation. This is a normal and temporary occurrence.
The initial break-in operation should last two to three
hours with the burner at the highest setting. Provide maximum ventilation by opening windows or doors to allow odors to dissipate. Any odors remaining after this initial break-in period will be slight and will disappear with continued use.
20. Input ratings are shown in BTU per hour and are for elevations up to 2,000 feet. For elevations above 2,000 feet, input ratings should be reduced 4 percent for each 1,000 feet above sea level. Refer to the National Fuel Gas Code.
21. The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
22. The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
23. Do not use this room heater if any part has been under water. Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.
24. Never burn solid fuels in an unvented room heater, fire place or stove.
25. Do not set kettles or humidifying devices on top of stove.
26. The stove door/screen must be closed when the appli­ance is operating. The screen shall have openings for induction of combustion air.
-
4 58D6002
ON
OFF
Handle
PRODUCT FEATURES
On/Off Switch
Optional
Remote
Receiver
Piezo
Hi/Lo Knob
Off/Pilot/On
Knob
Optional
Door
Thermostat
Sensor
Figure 1 - Cast Iron Stove
58D56002 5
A
C
B
DIMENSIONS
Figure 2 - Dimensions
CSVF20S CSVF30S
A 211/4" 263/4" B 23" 281/2" C 161/2" 193/4"
6 58D6002
GETTING STARTED
MAKE SURE YOU HAVE RECEIVED ALL PARTS:
Check your packing list to verify that all listed parts have been received. You should have the following:
• Cast Iron Stove with Burner Assembly
• Installation/Operating Instructions
• Ceramic Fiber Logs
• Touch-up Paint
Millivolt controlled heater designed to be operated with optional devices for ON/OFF functions.
• Hand-Held Remote with Receiver, Manual or Thermostat
• Wall Switch with 15' Wire
• Wall T-stat with 15' Wire
• Stove Mounted Thermostat Control
Gloves are recommended when handling ceramic fiber logs to prevent skin irritation from loose fibers. Logs are fragile--handle with care.
CAUTION
Carefully inspect the contents for shipping damage. If any parts are missing or damaged, immediately inform the dealer from whom you purchased the appliance. Do not attempt to install any part of the appliance unless you have all parts
in good condition.
WHAT YOU WILL NEED FOR INSTALLATION:
You must have the following items available before proceeding with installation:
• External regulator (for propane/L.P.G.) or high pressure natural gas (1 to 2 PSI system)
• Piping which complies with local codes • Manual shutoff valve
• Sediment trap (recommended) • Tee joint
• Pipe wrench or appropriate wrench set • Screwdrivers
• Pipe sealant approved for use with propane/L.P.G. (Resistant to sulfur compounds)
58D56002 7
PRODUCT SPECIFICATIONS
NATURAL GAS
NOTE: An external regulator is required to reduce supply pressure to a maximum of 101/2" w.c. on Natural Gas systems operating at higher pressure.
MILLIVOLT PRESSURE
Regulator Pressure Setting: 3.5" w.c. Pilot Regulator: 3.5" w.c. Gas Inlet Pressure: Max. 10 1/2" w. c. Min. 5" w.c.
Gas Rate
Model Number Type Max. BTU/Hr Min. BTU/Hr
CSVF20SNV(G-EBL-ES-EMB) Milli-Volt 10,000 6,000 CSVF30SNV(G-EBL-ES-EMB) Milli-Volt 32,000 20,000
PROPANE / LPG
Note: An external regulator is required to reduce supply pressure to a maximum of 13" w.c.
MILLIVOLT PRESSURE
Regulator Pressure Setting: 10" w.c. Gas Inlet Pressure: Maximum 13" w.c. Minimum 11" w.c.
Gas Rate
Model Number Type Max. BTU/Hr Min. BTU/Hr
CSVF20SPV(G-EBL-ES-EMB) Milli-Volt 10,000 6,000 CSVF30SPV(G-EBL-ES-EMB) Milli-Volt 32,000 26,000
IGNITION CONTROLS
Piezo ignitor allows ignition of the pilot without the use of matches.
Milli-Volt control has four (4) positions:
OFF - All gas to the burner is shut off at the valve. IGN - Valve position to light/maintain a standing pilot. ON - Valve position to turn burners ON/OFF with remote switch/thermostat. LOW/HI - Variable position to control flame height (heat output). Both front and rear burners are in operation to
provide realistic glow and yellow flame.
PILOT/ODS
The gas log heater is fitted with a specially designed safety pilot (ODS assembly) light which senses the amount of oxygen available in the room and shuts the gas log heater off if the oxygen level begins to drop below a satisfactory level. The pilot can only be relit when adequate fresh air is available.
THERMAL GENERATOR
The millivolt gas log pilot is fitted with a millivolt thermopile generator to provide power for remote activation.
8 58D6002
GENERAL INSTALLATION INFORMATION
Do not install the heater …
• Where curtains, furniture, clothing, or other flammable objects are less than 42" from the front of the heater.
• In high traffic areas.
WARNING
• In windy or drafty areas.
CODES
Adhere to all local codes or, in their absence, the latest edition of THE NATIONAL FUEL GAS CODE ANSI Z223.1 or NFPA54 which can be obtained from…
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
or
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
ADEQUATE COMBUSTION AND VENTILATION AIR
This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.
The National Fuel Gas Code, (ANSI Z223.1/NFPA54), defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 BTU per hour (4.8 m an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 BTU per hour (4.8 m aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.
UNUSUALLY TIGHT CONSTRUCTION IS DEFINED AS CONSTRUCTION WHERE…
a) walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of 1 perm
(6 x 1011 kg per pa-sec-m2) or less with openings gasketed or sealed;
b) weather stripping has been added on openable windows and doors, and
c) caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors,
between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.
3
per kw) of the aggregate input rating of all appliances installed in that space and
3
per kw) of the
58D56002 9
O
N
O
FF
L
2
L
1
W
H
GENERAL INSTALLATION INFORMATION
Figure 3 - Example of a Large Room with 1/2 Wall Divider
Counter
Cast Iron Stove
The following formula can be used to determine the maximum heater rating per the definition of unconfined space:
BTU/Hr = (L1 + L2) Ft x (W) Ft x (H) Ft
x 1000
50
Consider two connecting rooms with an open area between, with the following dimensions:
L1 = 151/2 Ft., L2 = 12 Ft., W = 12 Ft., H = 8 Ft.
BTU/Hr = (151/2 + 12) x (12) x (8)
x 1000 = 52800 BTU/Hr
50
If there were a door between the two rooms the calculation would be based only on the room with the heater.
BTU/Hr = (151/2) x (12) x (8)
x 1000 = 29760 BTU/Hr
50
If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel
10 58D6002
Gas Code, ANSI Z223.1, NFPA54, Section 5.3 or applicable local codes.
WARNING
D
Minimum
to Either
Side Wall
E
Minimum
A
G
G
D
Minimum
to Either
Side Wall
F Minimum
F
Minimum
36"
in Front
C
B
CLEARANCES / HEIGHT REQUIREMENTS
The dimensions shown in Figure 4 are minimum clearances to maintain in installing this heater. Left and right clearances are determined when facing the front of the heater.
Follow these instructions carefully to ensure safe installation. Failure to follow instructions exactly can create a fire hazard.
The appliance cannot be installed on a carpet, tile or other combustible material other
WARNING
than wood flooring, the appliance shall be installed on a metal, wood or noncombustible material panel extending full width and depth of the appliance.
Side
Wall
Ceiling
Front View
Mantel
Floor
Ceiling
Side Wall
Side View
Floor
Corner Installation
Wall Installation
Figure 4 - Minimum Clearance to Walls and Ceiling
Mantel Clearance from
Top of Unit
Min. Ceiling
from Floor
Product
VF20 72" 12" 16" 1" 1" ½" 1½"
58D56002 11
VF30 72" 12" 18" 2" 2" 1" ½"
A B C D E F G
Max.
Protrusion Min. Height Right Left
Side, Measured from Top
Rear
Measured
from Back
Corner Measured From Top
Corners
ON
OF
F
A
C
B
CLEARANCES / HEIGHT REQUIRMENTS
Figure 5 - Placing Stove in Alcove
Tested Minimum Alcove Dimensions
Height From
Hearth
A
VF20 38½" 23" 36"
Width
B
Depth
C
VF30 52" 34" 36"
Note: Maintain minimum side and back clearances when placing stove in alcove.
12 58D6002
PILOT
OFF
REMOTE CONTROL
LOGS
ON
OFF
LOGS
PILOT
OFF
REMOTE CONTROL
LOGS
REMOVING UNIT FROM CRATE
1. Remove two (2) straps. See Figure 6.
2. Open plastic bag and slide to bottom of unit. See
Figure 7.
3. Lift up on ash lip and pivot down to open control door. See Figure 8.
4. Lift up on front. Pivot bottom of front out. Remove front. See Figure 8.
5. Lift screen to remove.
6. Remove log box from inside of unit.
7. Lift unit off pallet. Lift unit up high enough to clear upright supports unit is sitting on.
Note: You will need at least two (2) strong people to lift unit off of pallet.
Pallet
Straps
Plastic
Bag
Hearth
Door
Ash Lip
Control
Door
Figure 6 - Removing Straps and Plastic from Unit
Log Box
Figure 7 - Opening Control Door and Removing
Figure 8 - Removing Log Box
Hearth Door
58D56002 13
CONNECTING THE GAS
NOTICE: A qualified gas appliance installer must connect the heater to the gas supply. Consult all local codes.
Use new black iron or steel pipe. Internally tinned copper or copper tubing can be used per National Fuel Code, section 2.6.3, providing gas meets hydrogen sulfide limits, and where permitted by local codes. Gas piping system must be sized to provide minimum inlet pressure (Listed on Data Plate) at the maximum flow rate (BTU/Hr). Undue pressure loss will occur if the pipe is too small.
A manual shutoff valve must be installed upstream of the appliance. Union tee and
CAUTION
plugged 1/8" NPT pressure tapping point should be installed upstream of the appliance.
See Figure 9.
To Heater
Valve
Stainless
Flexible Tube
Manual Shutoff
IMPORTANT: Hold heater valve firmly with a wrench to prevent movement when connecting to inlet pipe.
Pipe Coupling
Pipe
Valve
Figure 9 - Gas Connection
Locations that the Pressure
Tapping Point May Be Installed
Gas Supply
Inlet
CHECK GAS TYPE: The gas supply must be the same as stated on the heater’s rating plate. If the gas supply is different, DO NOT INSTALL THE HEATER. Contact your dealer for the correct model.
CAUTION
Always use an external regulator for all propane/LPG heaters and high pressure one to two-pound systems only, to reduce the supply tank pressure to a maximum of 13" w.c. This is in addition to the internal regulator in the heater valve.
14 58D6002
ON
OFF
CHECKING GAS PRESSURE AND CONNECTING REMOTE RECEIVER
The heater gas inlet connection is 3/8" NPT at the valve. The inlet is located on left side of stove. Remove front control plate to better access the inlet.
Connecting directly to an unregulated propane/L.P.G. tank can cause an
When tightening up the joint to the valve, hold the valve securely with a wrench to prevent movement.
explosion.
WARNING
Test all gas joints from the gas meter to the heater valve for leaks using a gas analyzer or soap and water solution after completing connection. DO NOT USE AN OPEN FLAME.
Check the gas pressure with the appliance burning and the control set to HIGH.
MILLIVOLT CONTROL (FIGURE 10)
The valve regulator controls the burner pressure which should be checked at the pressure test point.
If outlet pressure is low, check inlet pressure against data plates or manual.
Turn captured slotted screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point (Use test point “OUT” closest to control knob). After taking pressure reading, be sure and turn captured screw clockwise firmly to re-seal. Do not over torque. Check for gas leaks.
NOTE: Remove control panel to access gas valve and ignitor battery module.
CONNECTING REMOTE RECEIVER
1. Remove cover on control panel to show opening for remote receiver. See Figure 11.
2. Cut cable to length (approximately 12") for placement in the fireplace.
3. Strip back wire. Do not cut off wire connector.
1
/4" of the insulation from free end of each
Test Port “OUT”
Figure 10 - Pressure Test Point Location
Milli-Volt Control
Remote Receiver
4. Connect two .25 female connectors to the wires at free end of the cable.
5. Insert the wire connector into the receiver. If remote does not have plug-in connector, strip back 1/4" of insulation.
Cover
Insert wire into terminal and tighten screws.
6. Connect the connectors to the two .25" male connectors located on the left side when facing the unit. See Figure
11. Do not let the wire touch the grate or burners.
7. Slide remote receiver in the opening of control panel. Use two screws provided to attach remote receiver to the control panel. See Figure 11.
8. Replace Cover. See Figure 11.
Figure 11 - Installing Remote Receiver
NOTE: Do not place remote in combustion chamber.
58D56002 15
ELECTRICAL WIRING (MILLI-VOLT)
The milli-volt valve is a self-powered combination gas control THAT DOES NOT REQUIRE 110 VAC TO OPERATE.
ODS Pilot
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation
CAUTION
Wall
Switch
after servicing.
On/Off Switch
Optional Wall
CONNECTION 1 = TP 2 = TP, TH 3 = TH
Switch, Wall Thermostat,
Thermostat Sensor or
Remote
Figure 12 - Wiring Diagram
CONNECTING OPTIONAL WALL SWITCH OR THERMOSTAT
3 1 2
On/Off Switch
ODS
Pilot
Millivolt
Valve
Spade Terminal
Switch
1. Use 18 awg, two-wire cable, 15 feet maximum length.
2. At one end of the cable, connect both wires to the wall switch or thermostat. At the other end, connect one wire to TP/TH and one wire to TH, or connect the wall switch/thermostat to the two male (0.25") terminals on the left side of the unit. The color of the wires does not matter.
CONNECT
CHECKING SYSTEM OPERATION
The millivolt system and individual compo
CHECK TO METER THERMOSTAT METER TEST TEST LEADS TO CONTACTS READING
-
TERMINALS SHOULD BE
nents may be checked with a millivolt meter having a 0-1000mv range. Conduct each check shown in chart by connecting meter test leads to terminals as indicated.
A COMPLETE 2 & 3 CLOSED MINIMUM SYSTEM 175mv
B THERMOPILE 1 & 2 OPEN 500mv OUTPUT OR MORE
A. COMPLETE MILLIVOLT SYSTEM CHECK
("A" Reading - Thermostat contacts CLOSED - Control Knob “ON” - Main Burners should turn ON)
a. If the reading is more than 175 millivolts and the automatic valve still does not come on - replace the valve.
b. If the closed circuit reading ("A" reading) is less than 175 millivolts, determine cause for low reading - proceed as
follows:
B. THERMOPILE OUTPUT READING CHECK
(“B” Reading - Thermostat contacts OPEN - Main burner OFF)
Check gas pressure to the unit. If gas pressure is within minimum and maximum on data plate, then replace pilot. If the minimum
millivolt reading is not obtainable, replace pilot.
16 58D6002
PILOT
HEAT
THERMOSTAT
REMOTE C
ONTROL
INSTALLING THERMOSTAT SENSOR (OPTION SOLD SEPARATELY)
1. Lift up on ash lip and pivot down to open control door.
2. Remove the face plate by removing the six (6) screws holding the faceplate in place. This will allow you to pull the faceplate away from the unit about 3" to 4". See Figure 13.
3. Slip the t-stat sensor behind the faceplate. Attach the t-stat sensor to the faceplate with 2 screws provided. Make sure the thermo bulb wire is on the bottom of the t-stat sensor. See Figure 14.
4. Attach wiring harnesses to back of t-stat sensor. See Figure 14. Attach the other ends of the har­ness to either TP/TH and TH on control valve or to existing wiring harness with two (2) 0.250" male spade terminals for remote t-stat operation.
See Figure 12, page 16.
Screws
ELECTRICAL WIRING (MILLI-VOLT)
Control
Door
Ash
Lip
Screws
Face Plate
Figure 13 - Removing Face Plate from Unit
Screws
T-Stat
Sensor
Knob
Thermo
Bulb
Wiring
Harnesses
Figure 14 - Installing T-Stat Sensor and Control Knob
58D56002 17
PILOT
OFF
REMOTE CONTROL
ELECTRICAL WIRING (MILLI-VOLT)
4. Remove adhesive backing from plastic clip. Press
Valve
clip to bottom of valve. Clip thermo bulb into plastic clip. See Figure 15.
5. Reattach faceplate or reinstall base.
6. Install knob to shaft of t-stat sensor. See Figure 14,
page 17.
Thermo
Bulb
Plastic Clip
Figure 15 - Clipping Thermo Bulb into
Plastic Clip.
OPERATING THERMOSTAT SENSOR
1. Follow millivolt lighting instructions on lighting plate attached to unit or in homeownerʼs manual.
2. With control knob in the “ON” position make sure the ON/OFF switch is in the “OFF” position. See Figure 16.
3. The unit is now being controlled by the thermostat sensor. The sensor will now cycle the burners on and off. You can adjust how often the unit cycles by turning the control knob on the sensor.
Piezo
Ignitor
Hi/Lo
Knob
Pilot
Optional
Fan
Figure 16 - Control Knob in “ON” Position and ON/OFF Switch in “OFF” Position
18 58D6002
PILOT
OFF
REMOTE CONTROL
LOG PLACEMENT
Before you begin — This unit is supplied with four ceramic fiber logs. Do not handle these logs with your bare hands.
Always wear gloves to prevent skin irritation from ceramic fibers. After handling the logs, wash your hands gently with soap and water to remove any traces of fibers.
The positioning of the logs are critical to the safe and clean operation of this heater. Sooting and other problems may result if the logs are not properly and firmly positioned in the appliance. Never add additional logs or embellishments such as pine cones, vermiculite or rock wool to the heater. Only use the logs supplied with the unit.
Failure to position the parts in accordance with diagrams below or to use only parts specifically approved for this heater may result in property damage or personal
WARNING
injury.
Top Left
Log #4
Left
Bottom
Log #2
Left Log Support
Bracket
Right
Top Log
#5
Right
Bottom
Log #3
Back Log
#1
Rear Log
Support Bracket
INSTALLING LOGS ON GRATE (See Figure 17)
1. Install back log (#1) on rear log support bracket.
2. Install left bottom log (#2) on left log support bracket in front of back log.
3. Install right bottom log (#3) on right log support bracket in front of back log.
4. Install top left log (#4) on top of left bottom log.
5. Install top right log (#5) on top of right bottom log.
During initial operation of the new heater, burning logs will give off a paper burning smell and orange flames will be present. Simply open the windows for a few hours to vent the odor.
CAUTION
Right Log
Support Bracket
Figure 17 - Installing Logs to Grate
58D56002 19
PILOT
OFF
REMOTE CONTROL
ROCK WOOL INSTALLATION
1. Break rock wool into dime-sized pieces.
2. Place rock evenly across rock wool tray and front burner as shown in
Figure 18.
• Rock wool depth must not be more than 1".
• Do not place rock wool past the bend in rock wool tray.
• Do not place rock wool on rear burner.
Ro ck wo ol mu st be pl ac ed
Bend in Rock
Wool Tray
correctly. Placing rock wool in wrong area will create high
Rock Wool
carbon monoxide.
WARNING
Rock Wood
Tray
Figure 18 - Rock Wool Installation
FLAME APPEARANCE
Flames from the pilot, front and rear burner should be visually checked as soon as the heater is installed.
In addition, periodically check the flames visually during operation.
CHECKING PILOT FLAME
The pilot flame must always be present when the heater is in operation. It should just touch the top of the ther-
mocouple tip for natural. See Figure 19 for correct pilot flame.
If the pilot flame does not touch the thermocouple, then the burners cannot function reliably. See Figure 20 for incorrect shape of pilot flame.
MILLI-VOLT CONTROL
Thermocouple
for Natural
Thermocouple
for LP
Thermocouple
for Natural
Thermocouple
for LP
Figure 19 - Correct Appearance of Pilot Flame
20 58D6002
Figure 20 - Incorrect Appearance of Pilot Flame
PILOT
OFF
REMOTE CONTROL
FLAME APPEARANCE
CHECKING BURNER FLAME
In normal operation at full rate after 15 minutes, the following flame appearances should be observed:
The left and right rear flames should be yellow and extend 1"-2" above middle logs. The yellow flames should not contact the logs. There should be glowing embers on the front surface of the middle log. Note: The flames and embers will be
an opaque orange color during the burn off time.
Middle Log
Middle Log
Figure 21 - Correct Flame Appearance
OPERATING INSTRUCTIONS
Avoid any drafts that alter burner flame patterns. Do not allow fans to blow directly into the stove. Do not place
a blower inside the burn area of the stove. Ceiling fans may create drafts that alter flame patterns. Sooting and improper burning will result.
During manufacturing, fabricating and shipping, various components of this appliance are treated with certain oils, films or bonding agents. These chemicals are not harmful, but may produce annoying smoke and smells as they are burned off during the initial operation of the appliance, possibly causing headaches or eye or lung irritation. This is a normal and temporary
occurrence.
The initial break-in operation should last two to three hours with the burner at the highest setting. Provide maximum ventila tion by opening windows or doors to allow odors to dissipate. Any odors remaining after this initial break-in will be slight and will disappear with continued use.
58D56002 21
-
PILOT
OFF
REMOTE CONTROL
OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
If you do not follow these instruction exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
WARNING
A. This appliance is equipped with an ignition device which automatically lights the pilot. If the piezo is not
working properly, see Match Lighting Instructions, page 24.
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Do not attempt to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in, or turn the gas control knob. Never use tools. If the knob will not push in or
turn by hand, don't try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part of it has been under water. Immediately call a qualified service tech-
nician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
Data and Instruction
Plates Located on
Back of Burner
Optional
Remote
Receiver
Hi/Lo Knob
Off/Pilot/On Knob
Figure 22 - Location of Piezo Ignitor, Control Knobs and Switch on Milli-volt Unit
22 58D6002
Optional
Thermostat
Sensor
OF
F
ON
OPERATING INSTRUCTIONS
MILLI-VOLT AND THERMOSTAT
CONTROL LIGHTING INSTRUCTIONS
1. STOP! Read the safety information label.
2. Make sure the manual shutoff valve is fully open.
3. This gas log set is equipped with an ignition device (piezo) which automatically lights the pilot. If piezo ignitor does not light the pilot, refer to instructions for Match Lighting Instructions, page 24.
4. Turn gas control knob clockwise to the OFF position, set the thermostat to the lowest setting and turn ON/OFF switch to OFF position.
5. Wait (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow the instructions under “What To Do If You Smell Gas,” page 29.
6. From OFF position, turn the gas control knob counterclockwise control knob for 5 seconds. NOTE: If you are running the heater for the first time, it may be
necessary to press in the control knob for 30 seconds or longer to allow air to bleed out of the gas piping.
7. With the control knob pushed in, push in and release the piezo ignitor button to light the pilot.
8. Continue pushing the control knob in for a further 10 seconds to prevent the flame detector from shutting off the gas while the probe is warming up. Release the control knob.
9. Turn gas control knob counterclockwise to the ON position.
10. After the pilot has been lit for one minute, the burners can be turned on. Turn the ON/OFF switch to ON position or adjust thermostat to desired setting. NOTE: To use the thermostat function (if
installed) the control knob must be set to “ON” and ON/OFF switch must be in the “OFF” position.
11. If the gas logs will not operate, follow the instructions “To Turn Off Gas To Heater” below and call your service technician or gas supplier.
Hi/Lo Control
to IGN position. Push in
On/Off Switch
Ignitor/Pilot Control
Figure 23 - Pilot
TO TURN OFF GAS TO HEATER
1. Turn control knob clockwise to OFF position to completely shut off the heater.
2. If applicable: Turn ON/OFF switch to OFF position and/or set thermostat (if present) to lowest setting.
3. If applicable: Turn off all electric power to the heater.
Figure 24 - Control Cover Plate for Milli-Volt
(Located on Side
of Stove)
58D56002 23
OPERATING INSTRUCTIONS AND CLEANING AND SERVICING
MATCH LIGHTING INSTRUCTIONS
1. Open stove door. Remove any items necessary for easy access to the pilot (for example: logs, screens, etc.).
2. Follow appropriate lighting instructions found previously. Light a match and hold the flame to the end of the pilot and ignite the pilot.
3. After control knob has been released and pilot stays lit, reinstall any items that were removed for pilot access. Close and latch stove door.
4. Replace ignitor battery. If ignitor still does not work, then call a qualified service technician for repair or replacement of the piezo ignitor.
CLEANING AND SERVICING
Annual inspection and cleaning by your dealer or qualified service technician is recommended to prevent malfunction and/or sooting.
Turn off heater and allow to cool before cleaning. Disconnect electrical power before cleaning or servicing.
WARNING
Remove logs, handling carefully by holding gently at each end. Gloves are recommended to prevent skin irritation from ceramic fibers. If skin becomes irritated, wash gently with soap and water. Refer to manual for correct log placement.
PERIODIC CLEANING - See parts diagram for location of items discussed below.
• Do not use cleaning fluid to clean logs or any part of heater.
• Brush logs with soft bristle brush or vacuum with brush attachment.
• Vacuum loose particles and dust from the front and rear burners, control and piezo covers and grate weldment.
• Inspect and clean burner air intake holes. Remove lint or particles with vacuum, brush, or pipe cleaners. Failure to keep air intake holes clean will result in sooting and poor combustion.
• External case should be dusted and wiped with a moist cloth.
ANNUAL CLEANING/INSPECTION - Refer to parts diagram for location of items discussed below.
• Inspect and clean burner air intake holes. Remove lint or particles with vacuum, brush or pipe cleaners. Failure to keep air intake holes clean will result in sooting and poor combustion.
• Inspect and clean all burner ports.
• Inspect ODS pilot for operation and accumulation of lint at air intake holes.
• Verify flame pattern and log placement for proper operation.
• Verify smooth and responsive ignition of main burner and rear burner.
• Replace AA battery in ignition module.
24 58D6002
1
2
3
4
5
REPLACEMENT PARTS ARE AVAILABLE THROUGH YOUR RETAILER.
LOGS
Item Description Qty
1 Back Log 1 58D1901
2 Bottom Left Log 1 58D1902
REPLACEMENT PARTS LIST
3 Bottom
4 Left Top Log 1
5 Right Top Log 1
Right Log 1 58D1903
58D1904
58D1905
Failu re to po si tio n th e pa rt s in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal
WARNING
injury.
58D56002 25
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
REPLACEMENT PARTS
BURNER ASSEMBLY
Failu re to po si tio n th e pa rt s in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal
WARNING
injury.
26 58D6002
REPLACEMENT PARTS LIST
REPLACEMENT PARTS ARE AVAILABLE THROUGH YOUR RETAILER.
BURNER ASSEMBLY
CSVF20 CSVF30
Item Description Qty Natural Propane Natural Propane
Piezo Ignition Module
1
Piezo Switch
2
Piezo Wire
3
Front Burner
4
Rear Burner
5
Control Valve
6
Front Burner Injector
7
Rear Burner Injector
8
ODS Pilot Assembly
9
On/Off Control Knob
10
Hi/Lo Control Knob
11
On/Off Switch
12
1 1 1 1 33D0070 33D0071 58D0193 58D0193 1 58D0435 58D0435 1 1 58D0061 58D0056 1 58D0061 62D3005 1 1 1
1 13 VF Valve Tube 1 58D0427 58D0427 14 VF Rear Burner Tube 1 58D0428 58D0428 15 VF Front Burner Tube 1 58D0429 58D0429 16 5/16 Union Tee 1 43D0181 43D0181
45D0077 45D0077 45D0077 45D0077
45D0078 45D0078 45D0078 45D0078
00K0632 00K0632 00K0632 00K0632
14D0467 14D0468 14D0467 14D0468
14D0473 14D0474 14D0473 14D0474
43D0094 43D0094 43D0094 43D0094
43D0095 43D0095 43D0095 43D0095
32D0232 32D0232 32D0232 32D0232
Accessories
Flex Connector Flexcon 30
Wall Switch Kit
Wall Thermostat Kit
Hand Held Remote RCM
Hand Held Thermostat Remote
Thermostat Control Sensor TS
MVWS
MVWTS
RCT
58D56002 27
TROUBLESHOOTING
Note: All troubleshooting items are listed in order of operation.
Turn appliance OFF and allow to cool before servicing. Only a qualified service person should service and repair the heater.
WARNING
WARNING
OBSERVED PROBLEM
When ignitor button is pressed, there is no spark at ODS/pilot.
Appliance produces unwanted odors.
Appliance shuts off during use.
POSSIBLE CAUSE
1. Ignitor electrode positioned wrong.
2. Ignitor electrode is broken.
3. Ignitor electrode not connected to ignitor cable.
4. Ignitor cable pinched or wet. Keep ignitor cable dry.
5. Broken ignitor cable.
6. Bad piezo ignitor.
7. No battery power (auto spark).
1. Appliance burning vapors from paint, hair spray, glues, etc.
2. Gas leak.
3. Initial burn off.
1. Not enough fresh air is available for ODS/ pilot to operate.
2. Low line pressure.
3. ODS/pilot is partially clogged.
4. Defective Thermopile.
5. Restrictions in incoming air flow.
REMEDY
1 Replace ignitor.
2. Replace ignitor.
3. Reconnect ignitor cable.
4. Free ignitor cable if pinched by any metal or tubing.
5. Replace ignitor cable.
6. Replace piezo ignitor.
7. Replace battery.
1. Ventilate room. Stop using odor causing products while heater is running.
2. Locate and correct all leaks.
3. Ventilate room and turn unit on high until odor is gone. Odor should be gone after 2 to 3 hours of continuous use.
1. Open window and/or door for ventila tion.
2. Contact local gas company.
3. Clean ODS/pilot.
4. Check pilot flame. Check wire connec­tions. Check thermopile output — should be 500 milli-volts across TH/TP and TP Terminals with ON/OFF switch off.
5. Check for obstructions on bottom of unit. Check for improper log placement.
-
Gas odor even when control knob is in OFF position.
When ignitor button is pressed, there is spark at ODS pilot, but no ignition.
28 58D6002
1. Gas leak.
2. Control valve defective.
1. Gas supply turned off or appliance shutoff valve closed.
2. Air in gas lines when installed.
3. ODS/pilot is clogged.
4. Gas regulator setting is not correct (LPG).
1. Locate and correct all leaks.
2. Replace control valve.
1. Turn on gas supply or open manual shutoff valve.
2. Continue holding down control knob. Repeat igniting operation until air is removed.
3. Replace ODS/pilot assembly or get it serviced.
4. Replace gas regulator at tank.
TROUBLESHOOTING
If the gas quality is bad, your pilot may not stay lit, the burners may produce soot and the heater may backfire when lit. If the gas quality or pressure is low, contact your local gas supplier immediately.
WARNING
OBSERVED PROBLEM
OD S /pilot ligh t s, but flame goes out when control knob is
released.
Burner does not light after ODS/ pilot is lit.
Burner backfires during com bustion.
Slight smoke or odor during initial operation.
POSSIBLE CAUSE
1. Control knob not fully pressed in.
2. Control knob not pressed in long enough.
3. Appliance shutoff valve not fully open.
4. Thermocouple connection loose at control valve.
5. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out.
6. Thermocouple damaged.
7. Control valve damaged.
1. Inlet gas pressure is too low.
2. Burner orifice diameter is too small.
3. Burner orifice is clogged.
-
1. Manifold pressure is too low.
2. Burner orifice is clogged.
1. Burner orifice is clogged or damaged.
2. Burner is damaged.
3. Gas regulator defective.
REMEDY
1. Press in control knob fully.
2. After ODS/pilot lights, keep control knob pressed in for 30 seconds.
3. Fully open manual shutoff valve.
4. Hand tighten thermocouple connection until snug, then tighten 1/4 turn more.
5. Contact local gas company. This prob­lem could be caused by either low gas pressure, or a dirty or partially clogged ODS/pilot.
6. Replace pilot.
7. Replace control valve.
1.
Contact qualified service person.
2.
Replace burner orifice.
3. Clean orifice.
1. Contact local gas company.
2. Clean burner or replace burner orifice.
1. Clean burner or replace burner orifice.
2. Replace burner.
3. Replace gas regulator.
Logs appear to smoke after ini tial operation.
Heater produces a whistling noise when burner is lit.
No gas to pilot.
58D56002 29
-
1. Vapors from paint or curing process of logs.
1. Turning control knob to HIGH position when burner is cold.
2. Air in gas line.
3. Dirty or partially clogged burner orifices.
1. LP-regulator shut down due to inlet pressure too high.
1. Problem will stop after a few hours of operation. Open a window for the first few hours.
2. Log heater is intended to be smokeless. Turn OFF heater and call qualified ser­vice person.
1. Turn control knob to LOW position and let warm up for a minute.
2. Operate burner until air is removed from line. Have gas line checked by local gas company.
3. Clean burner or replace burner orifice.
1. Verify LP tank regulator is installed and set at 11" to 13" w.c.
NOTES
30 58D6002
NOTES
58D56002 31
LIMITED LIFETIME WARRANTY
Monessen Hearth Systems warrants its products to be free of defects in material and workmanship and backs each product with a Limited Lifetime Warranty. This warranty is to the original purchaser of a Monessen Hearth Systems product and is not transferable.
LIFETIME WARRANTY
Covered under this warranty are the stove body, combustion chamber, door frame, gold plating (manufacturing defects only), glass (thermal breakage only), heat exchange system, and burner. This coverage includes parts and reasonable labor during the first five years of ownership and parts only thereafter.
FIVE YEAR WARRANTY
Ceramic fiber logs, firebrick panels and secondary air tubes are covered for a period of five years from the date of pur chase.
TWO YEAR WARRANTY
Gas valves, pilot assemblies, thermopiles, thermocouples, regulators, electrical components, cast iron grates and blowers are covered for a period of two years from the date of purchase.
EXCLUSIONS
Items that are not covered under this warranty include but are not limited to damage or chipping to any component surfaces, gasketing, refractory material, or trim. It does not cover installation or operational problems related to venting systems, inadequate draft, inadequate gas pressure, adjustments to the appliance, the cost of inspection, components which have been altered or modified, labor costs, removal and re-installation costs, shipping to or from the factory or authorized service center, shipping damage, damage from improper use or neglect, installation damage, damage from unauthorized service, incidental or consequential damage or negative pressure caused by mechanical systems such as furnaces, fans, clothes dryers etc.
TERMS
This warranty shall be void if the appliance is not installed a by qualified installer in accordance with the installation instruc tions provided with the appliance and state and local codes. The warranty shall also be void if the appliance is not operated and maintained in accordance with the operating instructions supplied with the appliance. All service work must be performed by an authorized service representative. Any part or parts, which we deem defective, will be repaired or replaced at Monessen Hearth Systemsʼs option, through an authorized dealer or service provider.
This warranty is expressly in lieu of other warranties, express or implied, including the warranty of merchantability of fitness for purpose and of all other obligations or liabilities. Monessen Hearth Systems does not assume for it any other obligations or liability in connection with the sale or use of the appliance. In states that do not allow limitations on how long an implied warranty lasts, or do not allow exclusion of indirect damages, those limitations of exclusions may not apply to you. You may also have additional rights not covered in this Limited Warranty.
-
-
Monessen Hearth Systems reserves the right to investigate any and all claims against the Limited Warranty and decide upon the method of settlement.
Monessen Hearth Systems • 149 Cleveland Drive • Paris, KY • 40361
July 2004 P/N 58D6002 • Rev. 1
Loading...