VFC Vent Free Fireplace System
Installation & Operating Instructions
Models: VFC24C, VFC24L, VFC32C & VFC32L
WARNING: If the information in this
manual is not followed exactly, a fi re or
explosion may result causing property
damage, personal injury or loss of life.
• Do not store or use gasoline or other
fl ammable vapors and liquids in the
vicinity of this or any other appliance.
• WHAT TO DO IF YOU SMELL GAS
– Do not try to light any appliance.
– Do not touch any electrical switch; do
not use any phone in your building.
– Leave the buildling immediately.
– Immediately call your gas supplier from
a neighbor's phone. Follow the gas
supplier's instructions.
– If you cannot reach your gas supplier,
call the fi re department.
• Installation and service must be performed
by a qualifi ed installer, service agency or
the gas supplier.
This is an unvented gas-fi red heater. It uses air
(oxygen) from the room in which it is installed.
Provisions for adequate combustion and ventilation air must be provided. Refer to Page 8.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future
reference.
20308011 08/15 Rev. 1
VFC Vent Free Fireplace System
CONTENTS
Thank you and congratulations on your purchase of a Vermont Castings Group Fireplace.
PLEASE READ THE INSTALLATION AND OPERATION INSTRUCTIONS
BEFORE USING THE APPLIANCE.
IMPORTANT: Read all instructions and warnings carefully before starting installation.
Failure to follow these instructions may result in a possible fi re hazard and will void the warranty.
Important Safety Information .....................................3
Please leave these instructions with the appliance.
OWNER
Please retain these instructions for future reference
.
WARNING:
• Any change to this heater or its controls can be dangerous.
• Improper installation or use of the heater can cause serious injury or death from fi re, burns,
explosion or carbon monoxide poisoning.
• Do not allow fans to blow directly into the fi replace. Avoid any drafts that alter burner fl ame
patterns.
• Do not use a blower insert, heat exchanger insert or other accessory , not approved for use with
this heater where applicable.
1. Due to high temperatures, the appliance should be
located out of traffi c and away from furniture and
draperies.
2. Children and adults should be alerted to the hazard
of high surface temperature and should stay away
to avoid burns or clothing ignition.
3. Y oung children should be carefully supervised when
they are in the same room with the appliance.
4. Do not place clothing or other fl ammable material
on or near the appliance.
5. Any safety screen or guard removed for servicing
an appliance, must be replaced prior to operating
the heater.
6. Installation and repair should be done by a qualifi ed
service person.
7. T o prevent malfunction and/or sooting, an unvented
gas heater should be cleaned before use and at
least annually by a professional service person.
More frequent cleaning may be required due to
excessive lint from carpeting, bedding materials,
etc. It is imperative that control compartments,
burners and circulating air passageways be kept
clean.
8. CARBON MONOXIDE POISONING: Early signs of
carbon monoxide poisoning are similar to the fl u with
headaches, dizziness and/or nausea. If you have these
signs, obtain fresh air immediately. Have the heater
serviced as it may not be operating properly.
9. The installation must conform with local codes or, in
the absence of local codes, with the National Fuel
Gas Code, ANSI Z223.l/NFPA54.
10. This unit complies with the latest edition of ANSI
Z21.11.2–2013, Unvented Heaters.
11. Do not install the heaters in a bathroom or bedroom.
12. Correct installation of the refractory cement logs,
proper location of the heater, and annual cleaning are
necessary to avoid potential problems with sooting.
Sooting, resulting from improper installation or operation, can settle on surfaces outside the fi replace. See
log placement instructions for proper installation.
20308011
13. Avoid any drafts that alter burner fl ame patterns. Do not
allow fans to blow directly into fi replace. Do not place
a blower inside burn area of fi rebox. Ceiling fans may
create drafts that alter burner fl ame patterns. Sooting
and improper burning will occur.
14. CAUTION: Candles, incense, oil lamps, etc. produce
combustion byproducts including soot. Vent-free
appliances will not fi lter or clean soot produced by
these types of products. In addition, the smoke and/
or aromatics (scents) may be reburned in the vent-free
appliance which can produce odors. It is recommended
to minimize the use of candles, incense, etc. while the
vent-free appliance is in operation.
15. This is an unvented gas-fired heater. It uses air
(oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must
be provided.
16. This heater shall not be installed in a room or space
unless the required volume of indoor combustion air is
provided by the method described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, the International
Fuel Gas Code or applicable local codes.
17. Keep room area clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
18. Unvented gas heaters are a supplemental zone heater.
They are not intended to be the primary heating appliance.
19. Unvented gas heaters emit moisture into the living
area. In most homes of average construction, this
does not pose a problem. In houses of extremely
tight construction, additional mechanical ventilation is
recommended.
20. During manufacturing, fabricating and shipping, various
components of this appliance are treated with certain
oils, fi lms or bonding agents. These chemicals are not
harmful but may produce annoying smoke and smells
as they are burned off during the initial operation of the
appliance; possibly causing headaches or eye or lung
irritation. This is a normal and temporary occurrence.
3
VFC Vent Free Fireplace System
IMPORTANT SAFETY INFORMATION
The initial break-in operation should last six hours with
the burner at the highest setting. Provide maximum
ventilation by opening windows or doors to allow
odors to dissipate. Any odors remaining after this initial
break-in period will be slight and will disappear with
continued use.
21. Input ratings are shown in BTU per hour and are for
elevations up to 2,000 feet. For elevations above 2,000
feet, input ratings should be reduced 4 percent for each
1,000 feet above sea level. Refer to the National Fuel
Gas Code.
22. The appliance must be isolated from the gas supply
piping system by closing its equipment shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 psig
(3.5 kPa).
23. Do not use this room heater if any part has been under
water. Immediately call a qualifi ed service technician
to inspect the room heater and to replace any part of
the control system and any gas control which has been
under water.
24. Never burn solid fuels in a fi replace where a unvented
room heater is installed.
25. Always have a fi replace screen in place when the
appliance is in operation and, unless other provisions
for combustion air are provided, the screen must have
an opening(s) for induction of combustion air.
THIS APPLIANCE MAY BE INSTALLED IN AN
AFTER-MARKET, PERMANENTLY LOCATED,
MANUFACTURED (MOBILE) HOME, WHERE
NOT PROHIBITED BY LOCAL CODES.
THIS APPLIANCE IS ONL Y FOR USE WITH THE
TYPE OF GAS INDICATED ON THE RATING
PLATE. THIS APPLIANCE IS NOT CONVERTIBLE FOR USE WITH OTHER GASES.
WARNING: Never connect unit to
private (non-utility) gas wells. This gas
is commonly known as wellhead gas.
CODES
Adhere to all local codes or, in their absence, the latest edition of THE NATIONAL FUEL GAS CODE ANSI Z223.1 or
NFPA54 which can be obtained from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
or
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
4
20308011
PRODUCT FEATURES
VFC Vent Free Fireplace System
GAS SPECIFICATIONS AND ORIFICE SIZES
Fireplace
Screen
On/Off Switch
Piezo Ignition
Control Knobs
Figure 1 VFC Shown with Control Access Door Open
OPERATION
This unvented gas heater requires no outside venting
and burns cleanly with excellent heating effi ciency. As a
zero-clearance appliance, it can be installed against (or
recessed into) any wall that is accessible to a gas line.
GAS PRESSURES
ControlFuelMillivolt and IPI
Regulator PressureNat.3.5" w.c.
Pilot RegulatorNat.3.5" w.c.
Max. Inlet PressureNat.10.5" w.c.
Min. Inlet PressureNat.5.0" w.c.
Regulator PressureLP10.0" w.c.
Max. Inlet PressureLP13.0" w.c.
Min. Inlet PressureLP11.0" w.c.
NOTE: For LP models an external regulator is required
to reduce supply pressure to a maximum of 13" w.c.
IGNITION CONTROLS
Piezo ignitor allows ignition of the pilot without the use of
matches or batteries.
Millivolt and EcoLogic® 2.0 controls have four (4)
positions:
OFF - All gas to the gas logs is shut off at the
valve.
IGN - Valve position to light/maintain a standing
pilot.
ON - Valve position to turn ON/OFF log set with
remote switch/thermostat.
LOW/HI - Variable position to control fl ame height
(heat output).
20308011
PILOT
The gas log heater is fi tted with a specially designed safety
pilot light (ODS assembly) which senses the amount of
oxygen available in the room and shuts the gas log heater
off if the oxygen level begins to drop below a satisfactory
level. The pilot can only be re-lit when adequate fresh air
is available.
THERMAL GENERATOR
The millivolt gas log pilot is fi tted with a millivolt generator
to provide power for remote activation.
5
VFC Vent Free Fireplace System
COLD CLIMATE OPTION
COLD CLIMATE OPTION (IPI Models Only)
NOTE: If you live in a cold climate, seal all cracks around
your appliance and wherever cold air could enter the room,
with noncombustible material. It is especially important to
insulate the outside chase cavity between the studs and
under the fl oor on which the appliance rests, if the fl oor is
above ground level.
Your fi replace is equipped with an intermittent pilot ignition
(IPI) control. An IPI control with a standing pilot option provides the dual benefi t of an economical and environmentally
responsible product and one which lights easily even in
the coldest climates. When in intermittent pilot mode (as
it comes from the factory), your pilot remains unlit until
needed, saving you fuel. Standing pilot mode, by comparison, is characterized by a continuously burning pilot.
The benefi t of a pilot which lights only when needed is fuel
savings. However, with no pilot burning in your fi replace,
units operating in colder climates may experience delayed
start up or lock out. Because colder air is heavier than
milder air and there is no pilot burning to maintain a warm
stable temperature in your fi rebox, establishing a draft to
aid ignition becomes diffi cult. This is perfectly normal but
can be somewhat frustrating.
T o remedy this issue, your fi replace has been designed with
a cold climate pilot option, which, when active, maintains
a warmer temperature inside your fi rebox to make ignition
faster and more effi cient. Operating your appliance in cold
climate (aka standing) pilot mode will prohibit the need for
multiple ignition attempts and will prevent the system from
delaying start up or locking out.
To activate the cold climate option, simply move the cold
climate toggle switch located on the right side of the black
control center to the “On” (left) position. (Figure 2) Y ou can
operate your appliance in this mode regardless of whether
you are using a remote control, wall switch or thermostat.
Figure 2 Cold Climate Option
6
Cold Climate
Switch
Master Switch
20308011
FIREPLACE AND FRAMING DIMENSIONS
VFC Vent Free Fireplace System
S
R
S
Q
Figure 3 Fireplace and Framing Dimensions
1/2”
or 5/8”
Min. Rough
Opening
Height
D
L
M
O - Min. Rough Opening Width
N
I
B
A
G
E
F
Min. Rough
Opening
Depth
P
H
C
J
K
Ref.VFC24VFC32
A24
B22
C26
5
⁄8"(625 mm)32"(813 mm)
5
⁄8"(575 mm)283⁄4"(730 mm)
1
⁄2"(673 mm)30"(762 mm)
D19"(482 mm)253⁄4"(654 mm)
E16
F4
G4
H14
1
⁄4"(413 mm)191⁄2"(495 mm)
1
⁄2"(114 mm)53⁄4"(146 mm)
7
⁄8"(124 mm)5"(127 mm)
1
⁄2"(368 mm)141⁄2"(368 mm)
I1"(25 mm)15⁄8"(41 mm)
J13
K11
1
⁄8"(333 mm)131⁄8"(333 mm)
3
⁄8"(289 mm)113⁄8"(289 mm)
L16"(406 mm)171⁄2"(445 mm)
M22
3
⁄4"(578 mm)283⁄4"(730 mm)
Framing Dimensions
N26
O25
P13
Q44
3
⁄4"(680 mm)301⁄4"(768 mm)
1
⁄8"(638 mm)321⁄2"(826 mm)
3
⁄8"(340 mm)133⁄8"(340 mm)
7
⁄8"(1140 mm)58"(1478 mm)
R24"(610 mm)291⁄4"(743 mm)
S32
1
⁄2"(826 mm)41"(1041 mm)
20308011
7
VFC Vent Free Fireplace System
PRE-INSTALLATION INFORMATION
WARNING:
• Gloves are recommended when handling
refractory cement logs to prevent skin
irritation from loose fi bers. Logs are fragile
— handle with care.
GETTING STARTED
Make sure you have received all parts:
Check your packing list to verify that all listed parts have
been received. You should have the following:
• Unvented gas heater
• Installation/operating instruction
• Four (4) black screws
• Canopy and three (3) screws
• Two (2) anchoring screws
• Refractory cement logs or glass media
Carefully inspect the contents for shipping damage. If any
parts are missing or damaged, immediately inform the
dealer from whom you purchased the appliance. Do not
attempt to install any part of the appliance unless you
have all parts in good condition.
WARNING—Do not install the heater:
• Where curtains, furniture, clothing, or
other fl ammable objects are less than
42" from the front of the heater.
• In high traffi c areas.
• In windy or drafty areas.
NOTE: Be sure all packing material has been removed
from underside the unit.
2. Install canopy and logs per instructions found in this
manual. The canopy MUST be installed for safe operation of the unit.
3. Field wire main power supply to units with fan kit. Refer
to the Electrical Section found in this manual. (Electrical
connections should only be performed by an experienced, licensed certifi ed tradesman).
4. Install optional ON/OFF kit on units with millivolt control.
Refer to the installation instructions included with the
kit and also refer to the Electrical Wiring section found
in this manual.
5. Plumb gas line. Refer to the Connecting the Gas
section found in this
manual. (Gas connections should only be performed
by an experienced,
licensed/certifi ed tradesman).
6. Complete fi nish wall material and/or surround.
WHA T YOU WILL NEED FOR INSTALLA TION:
You must have the following items available before proceeding with installation:
• External regulator (for propane/LPG only)
• Manual shutoff valve
• Piping which complies with local codes
• Sediment trap
• Phillips head screwdriver
• Tee joint
• Pipe sealant approved for use with propane/LPG
• Pipe wrench (resistant to sulfur compounds)
When planning the installation for the fi replace it is nec-
essary to determine where the unit is to be installed and
whether optional accessories are desired. Gas supply
piping should also be planned. The following steps represent the normal sequence of installation. Each installation
is unique, however, and might require a dif ferent sequence.
1. Position fireplace in desired location. Refer to the
Location of Fireplace and Clearances and Height
Requirements, and Firebox Framing sections found in
this manual.
ADEQUATE COMBUSTION AND VENTILATION AIR
This heater shall not be installed in a confi ned space or
unusually tight construction unless provisions are provided
for adequate combustion and ventilation air.
The National Fuel Gas Code, (ANSI Z223.1/NFPA54),
defi nes a confi ned space as a space whose volume is less
than 50 cubic feet per 1,000 BTU per hour (4.8m
the aggregate input rating of all appliances installed in that
pace, and an unconfi ned space as a space whose volume
is not less than 50 cubic feet per 1,000 BTU per hour (4.8
3
m
per kw) of the aggregate input rating of all appliances
installed in that space. Rooms communicating directly with
WARNING: If the area in which the heater
is operated does not meet the required
volume for indoor combustion air, combustion
and ventilation air shall be provided by one of
the methods described in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, the International
Fuel Gas Code or applicable local codes.
3
per kw) of
8
20308011
FIREPLACE INSTALLATION
VFC Vent Free Fireplace System
the space in which the appliances are installed, through
openings not furnished with doors, are considered a part
of a confi ned space.
Unusually tight construction is defi ned as construction
where:
a. walls and ceilings exposed to the outside atmosphere
have a continuous water vapor retarder with a rating of
1 perm (6 x 10
gasketed or sealed, and
b. weather stripping has been added on openable windows
and doors, and
c. caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates
and fl oors, between wall-ceiling joints, between wall
panels, at penetrations for plumbing, electrical and gas
lines and other openings.
The following formula can be used to determine the maximum heater rating per the defi nition of unconfi ned space:
BTU/Hr = (L1 + L2) Ft x (W) Ft x (H) Ft
Consider two connecting rooms with an open area
between, with the following dimensions:
L1 = 151/2 Ft., L2 = 12 Ft., W = 12 Ft., H = 8 Ft.
If there were a door between the two rooms the calculation
would be based only on the room with the heater.
11
kg per pa/sec-m2) or less with openings
50
BTU/Hr = (151/2 + 12) x (12) x (8)
50
FIREPLACE LOCATION
Carefully select the best location for installation of your
unvented fi replace. The following factors should be taken
into consideration.
• Clearance to side wall, ceiling, woodwork and
window or other combustibles. Refer to “Clearances”
section. Minimum clearances to combustibles must
be maintained.
• Location must not be affected by drafts caused by
kitchen exhaust fans, ceiling fans, return air registers
for forced air furnaces / air conditioners, windows or
doors.
• Installation must provide adequate ventilation and
combustion air.
• DO NOT INSTALL THESE MODELS IN A BED-
ROOM OR BATHROOM.
• Location should be out of high traffi c areas and
away from furniture and draperies due to heat
from fi rebox.
• Never obstruct the front opening of the unvented
fi replace or restrict the fl ow of combustion and ven-
tilation air.
• Minimize modifi cations to existing construction. Refer
to Figure 5 below for location suggestions.
• Do not install in the vicinity where gasoline or other
fl ammable liquids may be stored. The unvented fi re-
box must be kept clear and free from the combustible
materials.
BTU/Hr = (151/2) x (12) x (8)
Figure 4 Combustion Air Calculation
20308011
50
Counter
Fireplace
H
W
Figure 5 Possible Fireplace Locations
9
VFC Vent Free Fireplace System
FIREPLACE INSTALLATION
CLEARANCES
Ensure that minimum clearances shown in Figures 6 and
7 are maintained. Left and right clearances are determined
when facing the front of the fi rebox.
Follow these instructions carefully to ensure safe instal-
lation. Failure to follow these requirements may create a
fi re hazard.
Sidewall Clearances — The clearance from the inside of
the appliance to any combustible adjacent wall should not
be less than 9" for the VFC24 and VFC32. Figure 6
Ceiling Clearance — The ceiling must be at least 42" from
the top of the fi rebox opening. Figure 6
Back Wall Clearance — The appliance may be placed
against a combustible back wall.
Floor Clearance — The fi replace may be installed directly
on a combustible fl oor or a raised platform of an appropri-
ate height. Do not place fi replace on carpeting, vinyl, tile or
other soft fl oor coverings. It may , however , be placed on fl at
wood, plywood, particle board or other hard surfaces. Be
sure fi replace rests on a solid continuous fl oor or platform
with appropriate framing for support and so that no cold
air can enter from under the fi rebox.
Mantel clearances — The canopy supplied with the unit
must be installed. If a combustible mantel is installed. It
must meet the clearance requirements detailed in Figure 6.
NOTE: The Vermont Castings Group Barrington cabinet model series BWC300, BWC400 and BWC500 are
specially designed to comply with all mantel temperature
requirements. Any custom-built mantel must comply with all
clearance requirements shown in this instruction manual.
42" Minimum
9"
Minimum
9"
Minimum
12”
19”
256O”
10”
Canopy
FP2508
Figure 7 Mantel Clearances
WARNING: The dimensions shown in
Figures 6 and 7 are minimum clearances
to maintain in installing this heater. Left and
right clearances are determined when facing
the front of the heater.
Follow these instructions carefully to ensure
safe installation. Failure to follow instructions
exactly can create a fi re hazard.
FRAMING AND ANCHORING
If unit is to be “built in”, fi replace framing can be built before
or after the appliance is set in place. BE SURE THA T ALL
P ACKING MATERIAL HAS BEEN REMOVED FROM THE
UNDERSIDE OF THE UNIT PRIOR TO SETTING THE
FIREBOX IN PLACE. Construct fi replace framing following
Fireplace and Framing Dimensions. The framing headers
may rest directly on top of the fi rebox.
The fi replace may be installed directly on a combustible fl oor or a raised platform of an appropriate height. Do
not place fi replace on carpeting, vinyl, tile or other soft fl oor coverings. It may, however, be placed on fl at wood,
plywood, particle board or other hard surfaces. Be sure
fi replace rests on a solid continuous fl oor or platform with
appropriate framing for support and so that no cold air can
enter from under the fi rebox.
Figure 6 Sidewall and Ceiling Clearances
10
WARNING: The fi replace must be installed
giving full consideration to the clearance
and height requirements identified in this
manual.
20308011
FIREPLACE INSTALLATION
VFC Vent Free Fireplace System
Anchor fi replace to the side framing members using nailing
fl anges.
1. Bend out the nailing fl anges located on each side of the
fi rebox.
2. Slide the fi rebox into prepared framing or position fi rebox
in its fi nal position and frame later.
3. Level the fi rebox by checking the top edge of the fi rebox.
Shim if necessary.
4. Anchor fi rebox to the side framing members using 8d
nails or other suitable fasteners. Figure 8
5. The canopy must be installed for safe operation of the
heater. Refer to canopy installation details.
Nail Sides
Through Nailing
Flanges
SECURING HEATER TO FLOOR OR
HEARTH
NOTE: Clearance requirements as detailed in the
Clearances section on of this manual, must be met before
securing the heater in place.
To prevent movement, the heater must be secured to the
fl oor or hearth.
1. Open the control access door and remove the screen.
Secure the fi rebox with two anchoring screws (3⁄16
2.
length) supplied with the fi replace system. Figure 9
NOTE: If the unit is mounted on carpeting, tile or
combustible material without the hearth, a metal or wooden
base covering the entire width and depth of the base must
be installed.
" x 11⁄4
"
Figure 8 Nailing Flanges
Anchor Screws
3
⁄16" x 11⁄4"
Figure 9 Secure Fireplace to Floor or Hearth
20308011
11
VFC Vent Free Fireplace System
GAS LINE & PRESSURE
CONNECTING THE GAS LINE
NOTICE: A qualifi ed gas appliance installer must connect
the heater to the gas supply. Consult all local codes.
WARNING: Use new black iron or
steel pipe. Internally tinned copper or
copper tubing can be used per National
Fuel Code, section 2.6.3, providing gas meets
hydrogen sulfi de limits, and where permitted by
local codes. Gas piping system must be sized to
provide minimum inlet pressure (Listed on Data
Plate) at the maximum fl ow rate (BTU/hr). Undue
pressure loss will occur if the pipe is too small.
A manual shutoff valve must be installed
upstream of the appliance. Union tee and
plugged 1/8" NPT pressure tapping point should
be installed upstream of the appliance. Figure 10
To Fireplace
Pipe Coupling
Pipe
Stainless
Flexible Tube
Manual Shutoff
Valve
Figure 10 Gas Connection
IMPORTANT: Loosen the pipe adapter on the fl ex tube
before installing to the system piping.
Always use an external regulator for all propane/LPG heaters only , to reduce the supply tank pressure to a maximum
of 13" w.c. This is in addition to the internal regulator in the
heater valve.
To reach factory installed fl ex line, go through access door
on right or left side of fi rebox.
WARNING: CHECK GAS TYPE: The
gas supply must be the same as stated
on the heater’s rating plate. If the gas
supply is different, DO NOT INSTALL THE
HEATER. Contact your dealer for the correct
model. Connecting to the wrong gas type may
result in property damage or personal injury.
12
Locations Pressure
Tapping Point Installation
Gas Supply
Inlet
WARNING: Connecting directly to an
unregulated propane/LPG tank can
cause an explosion
Access Door
for Gas Line
Manual Gas Shutoff
Stainless Flex Line
Figure 11 Access Holes
(Recommended Outlet
Positioned Vertical)
The stainless fl ex line is on the right side facing the fi re-
place and can connect to either a 3/8 NPT female or 1/2
NPT male pipe. To connect from the opposite side, route
the pipe under the rear portion of the unit.
T est all gas joints from the gas meter to the heater valve for
leaks using a gas analyzer or soap and water solution after
completing connection. DO NOT USE AN OPEN FLAME.
Check the gas pressure with the appliance burning and
the control set to HIGH.
Open control access door on either side of unit to fi nd valve
and regulator referred to below. Figure 11
CHECKING GAS PRESSURE – MILLIVOLT
CONTROL
Figure 12
The valve regulator controls the burner pressure which
should be checked at the pressure test point.
Turn captured screw counter clockwise two or three turns
and then place tubing
to pressure gauge over
test point (Use test point
“OUT” closest to control knob). After taking
pressure reading, be
sure and turn captured
screw clockwise firmly
to re-seal. Do not over
torque. Check for gas
leaks.
Figure 12 Pressure Test Point Location Millivolt Control
Test Port
"OUT"
20308011
FINAL INSTALLATION
VFC Vent Free Fireplace System
CHECK GAS PRESSURE – IPI
1. Check gas type. The gas supply must be the same as
stated on the appliance’s rating decal. If the gas supply
is different from the fi replace, STOP! Do not install the
appliance. Contact your dealer immediately.
2. To facilitate easier installation, a 18" (610 mm) fl ex line
with manual shut-off valve has been provided with this
appliance. Install and attach 1/2" gas line onto shut-off
valve.
3. After completing gas line connection, purge air from
gas line and test all gas joints from the gas meter to the
fi replace for leaks. Use a solution of 50/50 water and
soap solution or a gas sniffer.
4. To check gas pressures at valve, turn captured screw
counter clockwise 2 or 3 turns and then place tubing
to pressure gauge over test point. Turn unit to high.
Figure 13. After taking pressure reading, be sure and
turn captured screw clockwise fi rmly to reseal. Do not
over torque. Check test points for gas leaks.
WARNING: Do NOT use open fl ame
to check for gas leaks.
REMOVE SCREEN
NOTE: Fireplace screen must be removed to access log
box and to install canopy.
Figure 14
1. Remove bottom access panel.
2. Removing fi replace screen frame panel by pushing
screen frame panel up and out.
Canopy
Fireplace
Screen
Figure 13 –
IPI Valve
Pressure Inlet
Pressure
Outlet
FP3034
Pilot Adjustment Screw
Figure 14 Remove Fireplace Screen Panel
INSTALL CANOPY
Figure 15
1. Align the black canopy with the holes in the top frame
assembly.
2. Install the three (3) screws (in owner’s manual packaging) which attach the canopy to the top frame assembly .
3. Tighten all screws. Make sure the canopy is level and
secure.
Canopy
20308011
WARNING: Do not operate the unit without the screen frame panel and canopy
installed.
Screws
Figure 15 Install Canopy
13
VFC Vent Free Fireplace System
ELECTRICAL WIRING — MILLIVOLT
ODS Pilot
On/Off
Switch
Field Installed Optional
Wall Switch or
Remote Receiver
Figure 16 Wiring Diagram
On/Off
Switch
TH = 3
TP = 1
TP/TH = 2
Switch
ODS
Pilot
Valve
Spade
Terminal
FP2112a
WARNING: Label all wires prior to
disconnection when servicing controls.
Wiring errors can cause improper and
dangerous operation. Verify proper operation
after servicing.
The millivolt valve is a self-powered combination gas control THAT DOES NOT REQUIRE 1 10V AC TO OPERATE.
Refer to Figure 16 and installation instructions provided
with optional wall switch, thermostat or remote control for
wiring instructions. A maximum length of 15 feet of 18awg
two conductor wire is to be used for wall switch or thermostat installations.
NOTE: Thermostats and switches must be suitable for
millivolt operation.
14
WARNING: Do NOT connect wall
switch to 110 V circuit.
CONNECT OPTIONAL WALL SWITCH OR
THERMOSTAT
1. Use 18 awg, two-wire cable, 15 feet maximum length.
2. At one end of the cable, connect both wires to the wall
switch or thermostat. At the other end, connect one
wire to TP/TH and one wire to TH, or connect the wall
switch/thermostat to the two male (0.25") terminals on
the left side of the unit. The color of the wires does not
matter.
20308011
ELECTRICAL WIRING — MILLIVOLT
CONNECT REMOTE RECEIVER
THESE INSTRUCTIONS SUPERCEDE THE SECTION
ENTITLED “HEARTH MOUNT” IN THE MILLIVOLT
HAND-HELD REMOTE INSTRUCTIONS SUPPLIED
WITH THE REMOTE.
Figure 17
1. Remove bottom control door.
2. Connect the remote connector wires located in the unit
to the remote receiver.
®
3. Stick Velcro
pads with self-adhesive backing to bottom
of remote receiver and to fl oor of compartment behind
access panel.
4. Attach remote receiver to fi rebox with Velcro® pads.
Control switch must face forward.
NOTE: Do not place remote in combustion chamber,
only the remote receiver.
CHECK SYSTEM OPERATION
The millivolt system and individual components may be
checked with a millivolt meter having a 0-1000 mV range.
Conduct each check shown in chart below by connection
meter test leads to terminals as indicated.
VFC Vent Free Fireplace System
Remote Receiver
Figure 17 Install Remote Receiver
A. COMPLETE MILLIVOLT SYSTEM CHECK
(“A” Reading: Thermostat contacts CLOSED,
control knob “ON,” main burner should turn ON)
a. If the reading is more than 100 millivolts and the
automatic valve still does not come on, replace the
control.
b. If the closed circuit reading (“A” reading) is less than
100 millivolts, determine cause for low reading, proceed to Section B below.
Connect Meter
Check
Test
A
B
To
Test
Complete
System
Thermopile
Output
Leads to
Terminals
B. Thermopile Output Reading Check
(“B” Reading: Thermostat contacts OPEN, main
burner OFF)
1. Check gas pressure to the unit. If gas pressure is
within minimum and maximum on data plate, then
check pilot voltage, 325 millivolts minimum. If the
minimum millivolt reading is not obtainable, replace
pilot.
Switch or
Thermostat
Contacts
Meter Reading
Should Be
2 & 3ClosedClosed
1 & 2OpenOpen
20308011
15
VFC Vent Free Fireplace System
OPERATING INSTRUCTIONS—MILLIVOLT
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instruction exactly, a fi re or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance is equipped with a pilot which must be lit with built-in piezo ignitor while following these
instructions exactly.
B. BEFORE OPERA TING smell all around the appliance area for gas. Be sure to smell next to the fl oor
because some gas is heavier than air and will settle on the fl oor.
WHAT TO DO IF YOU SMELL GAS:
•Turn off all gas to the appliance.
• Open windows.
•Do not attempt to light any appliance.
•Do not touch any electric switch; do not use any phone in your building.
•Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
•If you cannot reach your gas supplier, call the fi re department.
C. Use only your hand to push in, or turn the gas control knob. Never use tools. If the knob will not push
in or turn by hand, don't try to repair it. Call a qualifi ed service technician. Force or attempted repair
may result in a fi re or explosion.
D. Do not use this appliance if any part of it has been under water. Immediately call a qualifi ed service
technician to inspect the appliance and to replace any part of the control system and any gas control
that has been under water.
LIGHTING PILOT FOR THE FIRST TIME
INITIAL LIGHTING
Purge air from the supply line as follows:
• Open main shutoff valve.
• Unscrew main pressure test point.
• Leave inlet test screw open until gas comes in.
• When gas is fl owing, tighten inlet screw immediately.
LEAK TESTING
1. Follow the pipe from the gas supply line connection to the gas valve. Check connection for leaks
with soap and water mixture.
2. Next check for gas leaks at the burner with soap and water mixture.
3. Check the pilot for gas leaks with soap and water mixture.
16
WARNING: NEVER use open fl ame
to check for gas leaks.
20308011
OPERATING INSTRUCTIONS—MILLIVOLT
T
VFC Vent Free Fireplace System
LIGHTING PILOT FOR THE FIRST TIME
APPROVED LEAK TESTING METHOD
You may check for gas leaks with the following methods only:
• Soap and water solution
• An approved leak testing spray
• Electronic sniffer
NOTE: Remove any excessive pipe compound from the connections. Excessive pipe compound
can set off electronic sniffers.
WARNING: NEVER use open fl ame
to check for gas leaks.
WARNING: If using a soap and water
solution to test for leaks, DO NOT
spray solution onto control body.
Check for gas leaks in each of the following locations:
• Pipe from the gas supply line connection to the gas valve
• Burner connections • Field made joints / gas shutoff valve
• Pilot • Factory made joints
• Each joint or connection • All joints on valve and control body
LIGHTING PILOT
WARNING: The control has an interlock device that does not allow the lighting of the
fi replace up to the moment the safety device of the fl ame has not interrupted the gas
fl ow. After that period of time (when the magnet is closed), it is possible to start the
lighting operation.
The gas control knob is designed to be operated by hand. DO NOT use any tools during this
operation. Damaged knobs may result in serious injury.
1. Depress and turn knob counterclockwise
to pilot position.
2. Depress fully and hold pilot gas knob. Depress piezo igniter as many times as needed to ignite pilot.
Keep knob fully depressed for a few seconds. Release and check that pilot continues to burn.
If the pilot does not stay lit, repeat steps 1 and 2.
O
N
T
O
L
I
P
F
F
O
PILO
Pilot Position
20308011
Continued on next page
17
VFC Vent Free Fireplace System
OPERATING INSTRUCTIONS – MILLIVOLT
LIGHTING BURNER
LIGHTING THE BURNER
Depress and turn the knob counterclockwise to the “ON” position.
It will take less than four (4) seconds for the burner to ignite.
MAIN BURNER SWITCH
This switch allows you to turn on and to turn off the main burner
without using the gas valve knob. is in the “ON” position to light the
main burner.
O
N
T
O
L
I
P
F
F
O
PILOT
N
O
O
F
F
P
I
L
T
O
PILOT
Wall Switch
Pilot Position
Depress and turn knob clockwise
Off Position
On Position
TO TURN OFF GAS
to “OFF” position.
I
L
P
O
T
F
F
O
O
N
PILOT
18
20308011
ELECTRICAL INSTALLATION — IPI
VFC Vent Free Fireplace System
Label all wires before disconnecting when
servicing controls. Wiring errors can cause
improper and dangerous operation.
CAUTION
WARNING: Electrical connections should
only be performed by a qualifi ed, licensed
electrician. Main power must be off
when connecting to main electrical power
supply or performing service. All wiring shall
be in compliance with all local, city and state
codes. The appliance, when installed, must be
electrically grounded in accordance with local
codes or in the absence of local codes, with
the National Electrical Code ANSI/NFPA 70
(latest edition) and Canadian Electrical Code,
CSA C22.1.
ELECTRICAL WIRING
General
1. This fi replace is equipped with an IPI control valve which
operates on 6 volts. The 6 volt DC adapter plugs into
the fi replace junction box A/C power supply.
2. The IPI system can also be operated without A/C power .
The system can run on four (4) “AA” batteries using the
optional battery backup for approximately six (6) months
under normal use.
Optional Accessories
This fi replace may be used with a wall switch, wall mounted
thermostat or IPI hand held remote control.
WARNING: Do NOT connect to a
110V circuit.
JUNCTION BOX WIRING
1. This should be done before framing the fi replace. Wire
the receptacle into an electrical circuit. Wire with minimum 60° C wire in accordance with prevailing codes.
2. Remove the external junction box cover by removing
the screw from the side of the outside fi rebox wall.
Junction box was installed at the factory.
3. The junction box cover has a factory installed “romex”
style strain relief connector. After connecting the wires,
route the wire leads through this connector. Refer to
the wiring diagram in Figure 18.
120V AC
60Hz
Factory Supplied
Not Supplied
Junction Box
Figure 18 –
Junction Box Wiring Diagram
20308011
19
VFC Vent Free Fireplace System
ELECTRICAL INSTALLATION – IPI
WALL SWITCH INSTALLATION
The wall switch wire connection is located off the wire
harness coming out of the IPI Control Board. The label is
wired 'wall switch'. Connect the low voltage switch wires to
the two (2) terminals labeled "wall switch" from the control
IPI SYSTEM WIRING DIAGRAM
ORANGE
YELLOW
BLACK
board. Run wire to desired location on wall. Up to 50 feet
of 18 gauge wire may be used if necessary. Attach wires
to wall switch. Mount the wall switch in a junction box and
screw on cover. Figure 19
BLACK
RED
RED
RED
BLACK
RED
BROWN
RED
GROUND
RED
BLACK
GREEN
D/C POWER
BLACK
Figure 19 –
IPI System Wiring Diagram
Electrical connections should only be performed by a qualifi ed, licensed electrician. Main
power supply must be turned off before connecting fans to the main electrical power supply
or performing service.
CAUTION
20
20308011
OPERATING INSTRUCTIONS – IPI
2.0
OPERATIONS AND INDICATIONS
System Set Up Chart
NOTE: When using ON/OFF wall switch, the master switch, located in bottom of fi replace must be in the
ON position to perform all confi guration setup operations.
FUNCTIONOPERATION
Cold Climate Pilot On/Off Flip the toggle switch to ON.OFF
Operations
FUNCTIONOPERATION
Power UpFlip the Master Switch to ON position to power up the system.
Fireplace On
Fireplace Off
®
2
Cold
Climate
CONTROL
BOARD
Turn on wall switch to turn the fi replace on. NOTE: If master switch was
just switched to ON, then at fi rst use of wall switch, it may need to be
turned ON - OFF - ON to synchronize the two switch settings.
Turn the wall switch to the OFF position, or turn the ON/OFF master
switch to the OFF position
Switch
Master
Switch
DEFAULT
SETTING
VFC Vent Free Fireplace System
Self Diagnostics Chart
The fi replace has a self diagnostic LED on the control board enabling you to troubleshoot problems and
potentially avoid a service call. Please refer to the chart below for indicator reference.
FUNCTIONOPERATION
Sparking errorRed LED, Flash 2 times
Flame errorRed LED, Flash 3 times
Ignition failRed LED, Flash 4 times
Re-ignite warningRed LED, Flash 5 times
Pilot valve voltage errorRed LED, Flash 6 times
Main valve voltage errorRed LED, Flash 7 times
Low batteryRed LED 2.5 sec, Flash once
Remote Operations
The following functions are available on the RMSC hand held remote.
NOTE: Flame height control is only available with purchase and installation of a stepper motor kit with RF
receiver
REMOTE FUNCTIONOPERATIONICON
Fireplace OnPress the ON button on the transmitter.
Fireplace Off
Flame Height Up
Flame Height Down
Count Down Timer Mode
Press the OFF button 3 times or hold the OFF button 3
seconds for memory off.
Press the ON button once to turn on the fi replace with
maximum fl ame setting.
Press the OFF button to lower the fl ame height to
medium and low.
Press TIMER button to enter the timer mode. Keep
pressing the TIMER button to set the desired time or
press TIMER button to “0” to exit timer mode.
20308011
21
VFC Vent Free Fireplace System
OPERATING INSTRUCTIONS – IPI
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fi re or explosion may
result causing property damage, personal injury or loss of lie.
A. This appliance is equipped with an ignition device which automatically lights the pilot. Refer to the
instructions.
B. BEFORE OPERA TING smell all around the appliance area for gas. Be sure to smell next to the fl oor
because some gas is heavier than air and will settle on the fl oor.
WHAT TO DO IF YOU SMELL GAS:
• Do not attempt to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fi re department.C. Turn Master Switch to ON position by hand. Never use tools. If the switch will not function by hand,
do not try to repair it. Call a qualifi ed service technician. Force or attempted repair may result in a fi re
or explosion.
D. Do not use this appliance if any part of it has been under water. Immediately call a qualifi ed service
technician to inspect the appliance and to replace any part of the control system and any gas control
that has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to
light the burner by hand.
3. Wait fi ve (5) minutes to clear out any gas. Then smell for gas, including near
the fl oor . If you smell gas, STOP! Follow "B" in the safety information on page
38. If you do not smell gas, go to next step.
4. Press the wall switch to the "ON" (-) position. Sparker will spark and pilot
fl ame will light.
5. Once pilot fl ame is established, the main burner fl ame will light automatically.
6. If the pilot will not stay lit after several tries, turn the master switch to "OFF"
and call your service technician or gas supplier.
Wall Switch
Master Switch
TO TURN OFF GAS TO APPLIANCE
1. Turn Wall Switch to "OFF".
2. Turn Master Switch to "OFF".
3. Turn off all electrical power to the appliance if service is to be performed.
22
20308011
ELECTRICAL WIRING
– FAN
VFC Vent Free Fireplace System
WARNING: This fi replace has a three-
prong, grounded electrical plug. This
plug helps protect you against electrical
shock. Only connect plug to a properly
grounded, three-prong receptacle. Do not cut
or remove the grounded prong from this plug.
IMPORTANT: Always check local building codes. The
installation must comply with local regulations as well as
the national electric codes.
If any of the original wire as supplied with the fi replace must
be replaced, contact dealer for proper replacement wiring
harness. (Refer to parts list for correct part number). 120
volts, 60Hz, 1 amp.
Fan Switch
OFF
110/115
V.A.C.
Black
White
Green
ON
WARNING: Never attempt to service
heater while it is plugged in, operating,
or hot. Burns and/or electrical shock could
result.
Electrical power cord (plug) can be routed to exit the VFC24
or VFC32 on either the left side or the right side. Remove
cord protector from side of unit, route power cord through
hole opposite side. Reinstall cord protector.
Thermostat
Control
Blower
Motor
Black
Figure 20 VFC Wiring Diagram
20308011
23
VFC Vent Free Fireplace System
LOG AND MEDIA PLACEMENT
WARNING: The positioning of the logs is critical to the safe and clean operation of this heater .
Sooting and other problems may result if the logs are not properly and fi rmly positioned in
the appliance. Never add additional logs or embellishments such as pine cones, vermiculite
or rock wool to the heater. Only use the logs and 2G-RW rock wool supplied with the unit.
Failure to position the parts in accordance with diagrams below or to use only parts specifi cally
approved for this heater may result in property damage or personal injury.
CAST IRON GRATE INSTALLATION
Install the cast iron grate by inserting screw head on back
of right side of grate into the “I” shaped slot on front right
corner of unit. After moving screw head to the bottom of the
“I” slot, insert the screw head on the back of the left side of
grate into the keyhole slot on the left front of unit. Figure 21
A.
B.
Key Hole Slot
Cast Iron Grate
I Slot
ROCK WOOL PLACEMENT
Before installing logs, place rock wool in dime size pieces
evenly over small burner ports starting in the rear of the
burner going towards the front. A void placing rock wool on
slots on each side of rear burner and on large yellow fl ame
ports on front of burner. After covering small burner ports,
discard any excess rock wool. Figure 22
Dime-sized
pieces of rock wool
Figure 22 Place Rock Wool
Cast Iron Grate
Figure 21 Install Cast Iron Grate
24
WARNING: Use only rock wool
provided with log set. Do not add
additional rock wool. Place rock wool on
burner ports only. Keep air gap between rear
log and burner clean.
20308011
LOG AND MEDIA PLACEMENT
VFC Vent Free Fireplace System
LOG PLACEMENT (VFC24L AND VFC32L
ONLY)
Before you begin — This unit is supplied with six (6) refractory cement logs. Do not handle these logs with your
bare hands. Always wear gloves. After handling the logs,
wash your hands gently with soap and water.
1. Place bottom right front log #1 on right pin located on
burner. Rear of log will make slight contact with the front
grate slot bracket. Figure 23
DO NOT sprinkle volcanic rock on the logs
or around the pilot or the main burner. This
may cause sooting. Only place volcanic
rock on the fl oor of the fi replace.
During initial operation of the new heater,
burning logs will give off a paper burning
CAUTION
smell and orange fl ames will be present.
Simply open the windows for a few hours
to vent the odor.
3. Place the middle rear log #3 with the center log placed
behind the right fl ame bracket. T he rear log will rest on
the back log support. Figure 25
Figure 23
2. Place the right rear log #2 behind #1 locking the two
logs together with the male notch into the back of log
#1. Figure 24
Figure 24
Figure 25
4. Place the left front log #4 on the front left pin located
on the burner. Left front edge of the log will make slight
contact with the front grate slot bracket. Figure 26
20308011
Figure 26
25
VFC Vent Free Fireplace System
LOG AND MEDIA PLACEMENT
5. Place the left middle log #5 with the C channel locking
the front and middle log in place. Figure 27
Figure 27
6. Place the left rear log #6 by aligning the rear support
bracket to the cut out on the rear of log #6. The left side
will also align with the channel cut into log #5. Figure
28
7. Place the top center log #7 by aligning the notch from
log #3 to the bottom. The front edge of the log #7 will
rest on the front grate horizontal bar. Figure 29
Figure 29
Log placement complete.
GLASS ONLY PLACEMENT
NOTE: T wo (2) bags of glass are supplied with the fi replace.
Both bags may be used to cover the entire fl oor and burner .
We advise against using additional glass as too much can
cut off the proper amount of air the burner needs to operate
cleanly. This may cause sooting.
1. Spread glass evenly in one layer over the entire fl oor
and burner. Be sure to use a single layer only over the
ported area so as not to impinge the fl ame.
2. Turn burner on and adjust glass over ported areas to
achieve an even, clean fl ame.
Figure 28
26
Figure 30
20308011
FLAME APPEARANCE
VFC Vent Free Fireplace System
PILOT AND BURNER FLAME APPEARANCE
Flames from the pilot, front and rear burner should be
visually checked as soon as the heater is installed.
In addition, periodically check the fl ames visually during
operation.
MILLIVOLT CONTROL
Thermocouple
for Natural Gas
Thermocouple
for LP
CHECKING THE PILOT FLAME
The pilot fl ame must always be present when the
heater is in operation. It should just touch the top of the
thermocouple tip for natural. Refer to Figures 31 & 32 for
correct pilot fl ame.
If the pilot fl ame does not touch the thermocouple, then
the main burner cannot function reliably. Refer to Figures 31 & 32 for incorrect shape of pilot fl ame.
Thermocouple
for Natural Gas
Thermocouple
for LP
Correct Pilot Flame AppearanceIncorrect Pilot Flame Appearance
Figure 31 Millivolt Control Pilot Flame Appearance
20308011
27
VFC Vent Free Fireplace System
FLAME APPEARANCE
CHECKING BURNER FLAME
VFC24L/VFC32L MODELS
In normal operation at full rate after 15 minutes, the
following fl ame appearances should be observed:
Burner will have a random pattern of yellow fl ames. Figure
32. There should be glowing embers in front of burner.
NOTE: The front fl ames and embers will be an opaque
orange color during the burn off time.
VFC24C/VFC32C MODELS
In normal operation at full rate after 15 minutes, the
following fl ame appearances should be observed:
Burner will have a random pattern of yellow fl ames. Figure
33
OPERATING INSTRUCTIONS
Avoid any drafts that alter burner fl ame patterns. Do
not allow fans to blow directly into the fi replace. Do not
place a blower inside the burn area of the fi rebox. Ceiling
fans may create drafts that alter fl ame patterns. Sooting
and improper burning will result.
During manufacturing, fabricating and shipping, various
components of this appliance are treated with certain oils,
fi lms or bonding agents. These chemicals are not harmful,
but may produce annoying smoke and smells as they are
burned off during the initial operation of the appliance,
possibly causing headaches or eye or lung irritation. This
is a normal and temporary occurrence.
The initial break-in operation should last two to three hours
with the burner at the highest setting. Provide maximum
ventilation by opening windows or doors to allow odors to
dissipate. Any odors remaining after this initial break-in will
be slight and will disappear with continued use.
This appliance must not be used with glass doors in the
closed position. This can lead to pilot outages and severe
sooting outside the fi replace.
Figure 32 VFC Traditional Flame Appearance
Figure 33 VFC Contemporary Flame Appearance
28
20308011
OPERATING INSTRUCTIONS
VFC Vent Free Fireplace System
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instruction exactly, a fi re or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance is equipped with a piezo ignition device which automatically lights the pilot. If the piezo
is not working properly see Match Lighting Instructions.
B. BEFORE OPERA TING smell all around the appliance area for gas. Be sure to smell next to the fl oor
because some gas is heavier than air and will settle on the fl oor.
WHAT TO DO IF YOU SMELL GAS:
• Do not attempt to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fi re department.C. Use only your hand to push in, or turn the gas control knob. Never use tools. If the knob will not push
in or turn by hand, don't try to repair it. Call a qualifi ed service technician. Force or attempted repair
may result in a fi re or explosion.
D. Do not use this appliance if any part of it has been under water. Immediately call a qualifi ed service
technician to inspect the appliance and to replace any part of the control system and any gas control
that has been under water.
On/Off Switch
Piezo Ignitor Control Knobs
Blower Control
Location of Piezo Ignitor, Control Knobs and Switch on Millivolt Unit, Hi/Lo Remote Control and Manual Unit
20308011
29
VFC Vent Free Fireplace System
OPERATING INSTRUCTIONS
MILLIVOLT/THERMOSTAT CONTROL
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information label.
2. Make sure the manual shutoff valve is fully open.
3. This gas log set is equipped with an ignition device (piezo) which automatically lights the pilot. If piezo
ignitor does not light the pilot, refer to instructions for Match Lighting Instructions on the following page.
4. Turn gas control knob clockwise to the OFF position and turn ON/OFF switch to OFF position.
5. Wait (5) minutes to clear out any gas. Then smell for gas, including near the fl oor. If you smell gas,
STOP! Follow "B" in the safety information label. If you don't smell gas, go to next step.
6. From OFF position, turn the gas control knob counterclockwise
knob for 5 seconds. NOTE: If you are running the heater for the fi rst time, it will be necessary to
press in the control knob for 30 seconds to allow air to bleed out of the gas piping.
7. With the control knob pushed in, push in and release the piezo ignitor button to light the pilot.
8. Continue pushing the control knob in for a further 60 seconds to prevent the fl ame detector from shut-
ting off the gas while the probe is warming up. Release the control knob.
9. Turn gas control knob counterclockwise
to the ON position.
10. After the pilot has been lit for one minute, the burners can be turned on. Turn the ON/OFF switch to
ON position or adjust thermostat to desired setting.
11. If the gas logs will not operate, follow the instructions “To Turn Off Gas To Appliance” below and call
your service technician or gas supplier.
to IGN position. Push in control
On/Off Switch
Piezo Ignitor
Pilot
Control Knobs
Millivolt Controls
Blower Control
TO TURN OFF GAS TO HEATER
1. Turn control knob clockwise to OFF position to completely shut off the heater.
2. If applicable: Turn ON/OFF switch to OFF position and/or set thermostat (if present) to lowest setting.
3. If applicable: Turn off all electric power to the heater.
30
20308011
OPERATING INSTRUCTIONS
VFC Vent Free Fireplace System
MATCH LIGHTING INSTRUCTIONS
1. Remove any items necessary for easy access to the pilot (for example: logs, screens, etc.).
2. Follow appropriate lighting instructions found previously. Instead of pushing and releasing the piezo
button, light a match and hold the fl ame to the end of the pilot and ignite the pilot.
3. After control knob has been released and pilot stays lit, reinstall any items that were removed for pilot
access.
4. Call a qualifi ed service technician for repair or replacement of the piezo ignitor.
BLOWER OPERATION
Blower Control
Figure 34 Location of Blower Control
Locate the blower control by opening control access door.
The variable controlled thermostat blower is located to the
right of heater controls. .
In the OFF position, the blower will not operate; however,
the heater can be operated without the blower being ON. In
the ON (AUTO) position, the blower will start when the thermostat senses a suffi cient increase in fi rebox temperature.
20308011
NOTE: Your gas logs and blower will not turn on and off
at the same time. The gas logs may burn several minutes
before blower turns on. The blower will continue to run for
several minutes after the fl ames have turned off.
31
VFC Vent Free Fireplace System
WARNING: Turn off heater and allow to cool before cleaning. Disconnect electrical
power before cleaning or servicing.
CLEANING AND SERVICING
ANNUAL CLEANING/INSPECTION
Refer to parts diagram for location of items discussed
below.
Annual inspection and cleaning by your dealer or qualifi ed
service technician is recommended to prevent malfunction
and/or sooting.
Remove logs, handling carefully by holding gently at each
end. Gloves are recommended. If skin becomes irritated,
wash gently with soap and water. Refer to manual for
correct log placement.
• Inspect and clean burner air intake holes. Remove
lint or particles with vacuum, brush or pipe cleaners.
Failure to keep air intake holes clean will result in
sooting and poor combustion.
• Inspect and clean all burner ports.
• Inspect ODS pilot for operation and accumulation of
lint at air intake holes.
• Verify fl ame pattern and log placement for proper
operation.
• Verify smooth and responsive ignition of main burner
and rear burner.
PERIODIC CLEANING
Refer to parts diagram for location of items discussed
below.
• Do not use cleaning fl uid to clean logs or any part of
heater.
• Brush logs with soft bristle brush or vacuum with
brush attachment.
• V acuum loose particles and dust from the front and
rear burner, control and piezo covers and grate
weldment.
• Inspect and clean burner air intake holes. Remove
lint or particles with vacuum, brush, or pipe cleaners.
Failure to keep air intake holes clean will result in
sooting and poor combustion.
• External case should be dusted and wiped with a
wet soapy cloth.
32
20308011
OPTIONAL ACCESSORIES
FORCED AIR KIT
If you are installing the forced air kit (Mo dels BLO24T or
BLOT), see the installation instructions provided with the
kit for electrical wir ing requirements or the blower installation section.
Model VFC24 uses blower model BLO24T.
Model VFC32 uses blower model BLOT.
The fi rebox must be connected to main power supply at
time of fi rebox installati on. The blower must be installed
prior to the installation of the unv ented heater . The electrical connections must be made before the fi rebox is framed
and enclosed in the fi nished walls.
INSTALLING OPTIONAL FIREBRICK
PANELS
NOTE: Firebrick liner kits may be used only with the VFC
vent free fi replace systems. Please verify the size and
model number of your insert to be certain the kit you purchased is correct.
VFC Vent Free Fireplace System
Retainer
Brackets
Figure 36 Install Side Firebrick Panel
KIT CONTENTS:
• One (1) Center panel
• Two (2) self-drilling #8 screws
• One (1) Left panel
• Two (2) Brick retainer brackets
• One (1) Right panel
TOOLS REQUIRED:
Drill with 1/4" hex head or Phillips bit
INSTRUCTIONS:
1. Remove screen frame, stones, fi reglass or logs (if ap-
plicable) per the VFC Installation and Operating Instructions.
2. Place rear ceramic fi rebrick panel against the center of
the rear wall of the fi rebox. Place on rear log support
bracket.
3. Place left and right ceramic fi rebrick panels against fi rebox sides and attach at the top with retainer bracket
with supplied self drilling screws.
4. Replace fi reglass, stones and/or logs as applicable
and re-install screen frame.
Figure 37 Install Back Firebrick Panel
20308011
33
VFC Vent Free Fireplace System
INSTALLING OPTIONAL PORCELAIN
PANELS
NOTE: Porcelain liner kits are approved for use with op-
tional fi reglass and log kits. These kits are designed to fi t
VFC vent free fi replace systems. Please verify the size
and model number of your fi replace to be certain the kit
you purchased is correct.
2. Place rear panel against the center of the rear wall of
the fi rebox.
3. Place left and right panels against fi rebox sides and at-
tach top fl anges of the panels using self-drilling screws
provided.
4. Replace fi reglass or logs as applicable and re-install
screen frame.
INSTALLING OPTIONAL BLACK MAGIC
PANELS
NOTE: Black Magic glass liner kits are approved for
use with optional fi reglass and log kits. These kits are
designed to fi t VFC vent free fi replace systems. Please
verify the size and model number of your fi replace to be
certain the kit you purchased is correct.
KIT CONTENTS:
• One (1) Center panel
• One (1) Left panel
• One (1) Right panel
• Two (2) Glass retainer brackets
• Two (2) Self drilling #8 screws
INSTALLATION INSTRUCTIONS:
1. Remove screen frame, fi reglass or logs (if applicable).
2. NOTE: All panels will be installed with the dimples in
the glass facing the fi rebox.
Place rear glass liner panel against the center of the
rear wall of the fi rebox.
3. Place left and right glass liner panels against fi rebox
sides and attach at the top with retainer bracket using
supplied screws.
4. Replace fi reglass or logs as applicable and re-install
screen frame.
Figure 38 Install Porcelain Panels
34
Figure 39 Install Black Magic Glass Panels
20308011
TROUBLESHOOTING
WARNING: Turn appliance OFF and allow to cool before servicing. Only a qualifi ed
service person should service and repair the heater.
NOTE: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEMPOSSIBLE CAUSESOLUTION
When ignitor button is pressed,
there is no spark at ODS/pilot.
Appliance produces unwanted
odors.
Appliance shuts off during use. 1. Not enough fresh air is available for
Gas odor even when control
knob is in OFF position.
1. Ignitor electrode positioned wrong.
2. Ignitor electrode is broken.
3. Ignitor electrode not connected to
ignitor cable.
4. Ignitor cable pinched or wet. Keep
ignitor cable dry.
5. Broken ignitor cable.
6. Bad piezo ignitor.
1. Appliance burning vapors from paint,
hair spray, glues, etc.
2. Gas leak.
3. Initial burn off.
ODS/ pilot to operate.
2. Low line pressure.
3. ODS/pilot is partially clogged.
4. Defective Thermopile.
5. Restrictions in incoming air fl ow
1. Gas leak.
2. Control valve defective.
1 Replace ignitor.
2. Replace ignitor.
3. Reconnect ignitor cable.
4. Free ignitor cable if pinched by any metal or
tubing.
5. Replace ignitor cable.
6. Replace piezo ignitor.
1. Ventilate room. Stop using odor causing products while heater is running.
2. Locate and correct all leaks.
3. Ventilate room and turn unit on high until odor
is gone. Odor should be gone after 6 hours of
continuous use.
1. Open window and/or door for ventilation.
2. Contact local gas company.
3. Clean ODS/pilot.
4. Check pilot fl ame, check wire connections, check
output, should be 325 millivolts across TH/TP and
TP Terminals with ON/OFF switches off.
5. Check for bottom riser on glass door, sunken
fi replace, excessive lava rock/cinders densely
packed against grate.
1. Locate and correct all leaks.
2. Replace control valve.
VFC Vent Free Fireplace System
When ignitor button is pressed,
there is spark at ODS pilot, but
no ignition.
20308011
1. Gas supply turned off or manual
shutoff valve closed.
2. Control knob not in PILOT position.
3. Control knob not pressed in while in
PILOT position.
4. Air in gas lines when installed.
5. ODS/pilot is clogged.
6. Gas regulator setting is not correct.
1. Turn on gas supply or open manual shutoff
valve.
2. Turn control knob to PILOT position.
3. Press in control knob while in PILOT position.
4. Continue holding down control knob. Repeat
igniting operation until air is removed.
5. Replace ODS/pilot assembly or get it serviced.
6. Replace gas regulator.
continued on following page
35
VFC Vent Free Fireplace System
OBSERVED PROBLEMPOSSIBLE CAUSESOLUTION
ODS/pilot lights, but flame
goes out when control knob is
released.
Burner does not light after
ODS/pilot is lit.
Burner backfi res during com-
bustion.
Slight smoke or odor during
initial operation.
Logs appear to smoke after
initial operation.
Heater produces a whistling
noise when burner is lit.
No gas to pilot.1. LP-regulator shut down due to inlet
Blower does not work.1. Power cord not plugged in.
1. Control knob not fully pressed in.
2. Control knob not pressed in long
enough.
3. Manual shutoff valve not fully open.
4. Thermocouple connection loose at
control valve.
5. Pilot fl ame not touching thermocou-
ple, which allows thermocouple to
cool, causing pilot fl ame to go out.
This problem could be caused by
either low gas pressure, or a dirty
or partially clogged ODS/pilot.
6. Thermocouple damaged.
7. Control valve damaged.
1. Burner orifi ce is clogged.
2. Burner orifi ce diameter is too small.
3. Inlet gas pressure is too low.
1. Manifold pressure is too low.
2. Burner orifi ce is clogged.
1. Burner orifi ce is clogged or dam-
aged.
2. Burner is damaged.
3. Gas regulator defective.
1. Vapors from paint or curing process of
logs.
2. Vapors or smoke continue after
heater is run with damper or window
open for several hours.
1. Turning control knob to HIGH position when burner is cold.
2. Air in gas line.
3. Dirty or partially clogged burner orifi ces.
pressure too high.
2. Loose wire connections.
3. Defective blower thermostat.
1. Press in control knob fully.
2. After ODS/pilot lights, keep control knob pressed
3. Fully open manual shutoff valve.
4. Hand tighten thermocouple connection until
5a.Contact local gas company.
5b.Clean pilot with vacuum cleaner.
6. Replace thermocouple.
7. Replace control valve.
1. Clean orifi ce.
2.
3.
1. Contact local gas company.
2. Clean burner or replace burner orifi ce.
1. Clean burner or replace burner orifi ce.
2. Replace burner.
3. Replace gas regulator.
1. Problem will stop after a few hours of operation.
2. Log heater is intended to be smokeless. Turn
1. Turn control knob to LOW position and let warm
2. Operate burner until air is removed from line.
3. Clean burner or replace burner orifi ce.
1. Verify LP tank regulator is installed and set at
2. Replace regulator on heater.
1. Plug power cord into junction box found in lower
2. Check wire connections, reconnect if loose.
3. Replace thermostat.
in for 30 seconds.
snug, then tighten 1/4 turn more.
Replace burner orifi ce.
Contact qualifi ed service person.
Run the heater with the damper open if you have
one, or open a window for the fi rst few hours.
OFF heater and call qualifi ed service person.
up for a minute.
Have gas line checked by local gas company.
11" to 13" w.c.
access level.
TROUBLESHOOTING
36
WARNING: If the gas quality is bad, your pilot may not stay lit, the burners may produce
soot and the heater may backfi re when lit. If the gas quality or pressure is low, contact
your local gas supplier immediately.
WARNING: Failure to position the parts in accordance with these diagrams or failure to
use only parts specifi cally approved with this appliance may result in property damage
or personal injury.
20308011
REPLACEMENT PARTS
seconds
connected to battery pack wire
adaptor is plugged into control
Battery polarity wrong?
Reinstall batteries correctly.
Batteries low?
Change batteries.
Plug the AC adaptor in
ON position
Correct wiring if necessary
opened
between valve and board
Correct wiring if necessary
No spark at pilot
Replace ignitor wire if damaged.
Check gas supply.
Check that ground
connection
pilot.
IPI SYSTEM
VFC Vent Free Fireplace System
Flip the master switch to the
ON position
Press the wall switch to the
No beep or flashing
green light in about 5
No beep
No sound from
valve indicating
pilot solenoid
Pilot doesn't light
Main burner
doesn't light
Make sure control board is
harness. Make sure AC
Check wiring connections
between switch and board
Check wiring connections
Inspect gray ignitor wire
connection at board and pilot.
Flame not engulfing flame
sensor or pilot flame too
AC adaptor plugged into
junction box?
wire has solid
Reconnect wire if disconnected.
Adjust sparker position such that the
spark is in the path of the gas flow or
replace the pilot
Adjust sensor position or replace the
Cold climate switch
No functionCheck the cold climate switch and control
Replace cold climate switch
20308011
37
VFC Vent Free Fireplace System
VFC FIREBOX PARTS
REPLACEMENT PARTS
1
3
2
REF. DESCRIPTIONQTYVFC24VFC32
1.CANOPY12030803820307978
2.SCREEN ASSEMBL Y12030806120307979
3.LEFT FIREBRICK (OPTIONAL)1
4.CENTER FIREBRICK (OPTIONAL)1
5.RIGHT FIREBRICK (OPTIONAL)1
6.BLOWER (OPTIONAL)1BLOT24TBBLOT
N/A LEFT PORCELAIN PANEL (OPTIONAL)12030793920307814
N/A CENTER PORCELAIN PANEL (OPTIONAL)12030793720307812
N/A RIGHT PORCELAIN PANEL (OPTIONAL)12030793820307813
N/A LEFT BLACK MAGIC GLASS PANEL (OPTIONAL)12030794420307941
N/A CENTER BLACK MAGIC GLASS PANEL (OPTIONAL)12030794320307940
N/A RIGHT BLACK MAGIC GLASS PANEL (OPTIONAL)12030794520307942
4
5
6
20308191
(CINNAMON)
20308190
(CINNAMON)
20308192
(CINNAMON)
20307935
(COLONIAL RED)
20307934
(COLONIAL RED)
20307936
(COLONIAL RED)
20307926
(CINNAMON)
20307925
(CINNAMON)
20307927
(CINNAMON)
(COLONIAL RED)
(COLONIAL RED)
(COLONIAL RED)
20307929
20307928
20307930
38
WARNING: Failure to position the parts in accordance with these diagrams or failure to
use only parts specifi cally approved with this appliance may result in property damage
or personal injury.
Flex ConnectorFLEXCON18
Wall Switch KitMVWS
Wall Thermostat KitWT
Hand Held RemoteRCB, RCMT, TSMT
Hand Held Thermostat RemoteRCST, TSST
Thermostat Sensor KitTS
Rock Wool81D2011 (TRADITIONAL ONLY)
20308011
WARNING: Failure to position the parts in accordance with these diagrams or failure to
use only parts specifi cally approved with this appliance may result in property damage
or personal injury.
Wall Switch KitMVWS
Wall Thermostat KitWT
Hand Held RemoteRCB, RCMT, TSMT
Hand Held Thermostat RemoteRCST, TSST
Thermostat Sensor KitTS
Rock Wool81D2011 (TRADITIONAL ONLY)
40
WARNING: Failure to position the parts in accordance with these diagrams or failure to
use only parts specifi cally approved with this appliance may result in property damage
or personal injury.
Flex ConnectorFLEXCON18
Wall Switch KitMVWS
Wall Thermostat KitWT
Hand Held RemoteRCB, RCMT, TSMT
Hand Held Thermostat RemoteRCST, TSST
Thermostat Sensor KitTS
Rock Wool81D2011 (TRADITIONAL ONLY)
20308011
WARNING: Failure to position the parts in accordance with these diagrams or failure to
use only parts specifi cally approved with this appliance may result in property damage
or personal injury.
Wall Switch KitMVWS
Wall Thermostat KitWT
Hand Held RemoteRCB, RCMT, TSMT
Hand Held Thermostat RemoteRCST, TSST
Thermostat Sensor KitTS
Rock Wool81D2011 (TRADITIONAL ONLY)
42
WARNING: Failure to position the parts in accordance with these diagrams or failure to
use only parts specifi cally approved with this appliance may result in property damage
or personal injury.
WARNING: Failure to position the parts in accordance with these diagrams or failure to
use only parts specifi cally approved with this appliance may result in property damage
or personal injury.
43
VFC Vent Free Fireplace System
LIMITED LIFETIME WARRANTY POLICY
LIFETIME WARRANTY
The following components are warranted for life to the original owner, subject to proof of purchase:
Firebox, Combustion Chamber, Heat Exchanger, Grate and Stainless Steel Burners.
FIVE YEAR WARRANTY
The following components are warranted for 5 years to the original owner, subject of proof of purchase: Refractory cement Logs, Catalytic Filter and Aluminized Burners.
BASIC WARRANTY
Vermont Castings Group warrants the components and materials in your gas appliance to be free from
manufacturing and material defects for a period of one year from date of installation. After installation,
if any of the components manufactured by Vermont Castings Group in the appliance are found to be
defective in materials or workmanship, Vermont Castings Group will, at its option, replace or repair
the defective components at no charge to the original owner. Vermont Castings Group will also pay
for reasonable labor costs incurred in replacing or repairing such components for a period of one
year from the date of installation. Any products presented for warranty repair must be accompanied
by a dated proof of purchase.
This Limited Warranty will be void if the appliance is not installed by a qualifi ed installer in accordance
with the installation instructions. The Limited Lifetime Warranty will also be void if the appliance is
not operated and maintained according to the operating instructions supplied with the appliance,
and does not extend to (1) fi rebox/burner assembly damage by accident, neglect, misuse, abuse,
alteration, negligence of others, including the installation thereof by unqualifi ed installers, (2) the costs
of removal, reinstallation or transportation of defective parts on the appliance, or (3) incidental or
consequential damage. All service work must be performed by an authorized service representative.
This warranty is expressly in lieu of other warranties, express or implied, including the warranty of
merchantability of fi tness for purpose and of all other obligations or liabilities. Vermont Castings
Group does not assume for it any other obligations or liability in connection with the sale or use of
the appliance. In states that do not allow limitations on how long an implied warranty lasts, or do not
allow exclusion of indirect damages, those limitations of exclusions may not apply to you. You may
also have additional rights not covered in this Limited Warranty.
Vermont Castings Group reserves the right to investigate any and all claims against the Limited
Warranty and decide upon method of settlement.
IF WARRANTY SERVICE IS NEEDED...
1. Contact your supplier. Make sure you have your warranty, your sales receipt and the model/
serial number of your Vermont Castings Group product.