Monessen 624BVSTNV, 624BVPFNE, 624BVCLNV, 624BVCLNE, 624BVCRNV Installation And Operation Manual

...
DESIGNER SERIES
624BVSTNV/624BVSTNE, 624BVPFNV/624BVPFNE
624BVCLNV/624BVCLNE, 624BVCRNV/624BVCRNE,
624BVBYNV/624BVBYNE
B-VENT SPECIALTY GAS FIREPLACE SYSTEM
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
WARNING: IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION
MAY
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR
ANY
WHAT TO DO IF YOU SMELL GAS
• DO NOT TRY TO LIGHT ANY APPLIANCE.
• D
O NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE IN YOUR BUILDING.
• I
MMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBORS PHONE. FOLLOW THE GAS
SUPPLIER
• I
F YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE DEPARTMENT.
INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS
SUPPLIER
S INSTRUCTIONS.
.
53D9019. Rev 3 11/07
"WARNING: IF NOT INSTALLED, OPERATED AND MAINTAINED IN ACCORDANCE WITH THE MANUFATURERS
INSTRUCTIONS
CAN CAUSE DEATH OR SERIOUS ILLNESS AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO
WHICH
CAUSE
SERVICING
THE
CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM. ALSO, OPERATION, INSTALLATION AND
STATE OF CALIFORNIA TO CAUSE CANCER THROUGH INHALATION."
, THIS PRODUCT COULD EXPOSE YOU TO SUBSTANCES IN FUEL OR FROM FUEL COMBUSTION
OF THIS PRODUCT COULD EXPOSE YOU TO AIRBORN PARTICLES OF GLASS WOOL FIBERS KNOWN TO
IMPORTANT INFORMATION
The gas fireplace must be installed and serviced by a qualified installer to conform with local codes. In the absence of local codes, install to the current National Fuel Gas Code, ANSI Z223.1 or the current CAN/CGA B149, installation codes.
T
HE FIREPLACE MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS INDIVIDUAL MANUAL SHUTOFF VALVE
DURING
PRESSURES IN EXCESS OF 1/2 PSIG WILL CAUSE DAMAGE TO CONTROL VA LVE AND MAY CAUSE DAMAGE TO THE SHUTOFF VALV E.
ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG.
Maximum input is 42,000 BTU/h for both natural and propane gases.
Minimum inlet gas supply pressure is 4.5 inches water column for natural gas ansd 11 inches water
column for propane.
Maximum inlet gas supply pressure is 7.0 inches water column for natural gas and 13.0 inches water column for propane.
Manifold pressure under flow conditions is 3.5 inches water column for natural gas and 10.0 inches
water column for propane.
D
ANGER: DO NOT OPERATE THIS APPLIANCE UNDER ANY CIRCUMSTANCES SHOULD THE AIR TERMINAL BE COVERED TO ANY
DEGREE
OR IN ANY MANNER SUCH AS BY SNOW, LEAVES OR ANY SUBSTANCE.
• The fireplace is a decorative gas appliance. Do not burn wood or other materials in this fireplace.
• Adults and especially children should be alerted to the hazards of high temperatures and should stay away to avoid burns or clothing ignition.
• Supervise young children when they are in the same room as the fireplace.
• Due to high temperatures, the fireplace should be located out of traffic and away from furniture and draperies.
• Clothing or other flammable material should not be placed on or near the fireplace.
• The fireplace glass door must be in place when the appliance is operating.
• It is imperative that the control compartments, burners and circulating air passage ways of the fireplace and venting system are kept clean. The fireplace and its venting system should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.
• The fireplace area must be kept clear and free from combustible materials, gasoline and other flammable vapors and liquids.
• This fireplace must not be connected to a chimney flue serving a separate solid fuel burning appliance.
• Under no circumstances should the fireplace be modified.
• The fireplace is not intended for use with a thermostat.
• Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and replace all parts of the control system and gas controls that has been under water.
• The fireplace is only to be used with the glass door certified with the fireplace.
For Massachusetts Residences Only:
• This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts. Flexline installation must not exceed 36 inches.
53D9019. Rev 3 11/07
TABLE OF CONTENTS
2
CONGRATULATIONS!
You have chosen the finest decorative gas appliance available. Your 6-IN-1 Specialty Gas Fireplace has been designed for years of heating and viewing enjoyment. Please take time to read this entire manual before installing or operating your system.
Parts
C22
Diagram...................................................................................................3
List
..........................................................................................................4
Appliance System Components.......................................................................5
Fireplace Configuration Installation
Framing Instructions
Fireplace Installation..........................................................................................8
Fireplace Installation and Venting Diagrams. ...........................................................9
Venting Requirements.....................................................................................10
Log Installation..............................................................................................11
Wall Switch Installation....................................................................................12
Adjustments and Maintenance...............................................................................13 -14
Combustion Air Precautions..............................................................................15
Combustion Air Assembly......................................................................16
Operating Instructions. ...............................................................................17-18
Safety Checklist............................................................................................19
Troubleshooting.............................................................................................20
LISTING AND CODE APPROVALS U.S. and Canada Certification
The B Vent Designer Series Gas Appliance has been tested in accordance with the ANSI Z21.50-2007.CSA 2-22-2007 Standard for Vented Gas Fireplaces and have been LISTED by OMNI-Test Laboratories, Inc. for installation
and operation described in these installation and Operating Instructions. All components are UL, AGA, CGA or CSA safety certified.
.......................................................................... . . .............7
...................................................................6
Local Codes
Check with your local building code agency prior to installing this appliance to ensure compliance with local codes, including the need for permits and follow-up inspections. This installation must conform with local codes or, in the absence of local codes, in the USA with the National Fuel Gas Code, ANSI Z223.1 - latest edition.
Your specialty gas fireplace is identified by model number, serial number, and gas type. For your convenience, complete this section for future reference when contacting your dealer.
Model Dealer
Serial No. Dealer Phone No.
Gas Type: Propane Natural Date of Purchase
53D9019. Rev 3 11/07
PARTS DIAGRAM
MV
MV
PV
PV
N
O
C
F
F
O
16
15
17
19
18
8
11
13
12
14
10
14
13
ON
OFF
PILOT
TH
TPTH
TP
3
17
19
16
18
15
9
7
10
14
13
12
14
13
11
1
2
3
5
4
6
53D9019. Rev 3 11/07
PARTS LIST
4
All repair part orders should be placed through your local dealer. To ensure prompt and accurate service, please provide the following information when placing a repair part order: Model num­ber of your Fireplace, Part Name, Part Number, and Quantity of parts needed.
Technical Service Department
2813 W. Mall Drive, Unit B.
Florence, Alabama 35630.
Tel. - 1-866-500-5671
www.monessenhearth.com
6-IN-1 PART LIST
KEY NO.KEY NO.
1 2 3 4
5 6 7 8
9 1010 1111 1212
1313
PART NAMEPART NAME
TWIG, TOPTWIG, TOP TWIG, ENDTWIG, END
TWIG, FRONT YTWIG, FRONT Y LOG, BACKLOG, BACK LOG, FRONTLOG, FRONT LOG, MIDDLELOG, MIDDLE FRONT DOOR ASSYFRONT DOOR ASSY HANDLE PACKAGEHANDLE PACKAGE
END DOOR ASSYEND DOOR ASSY HEARTH PAN PNTDHEARTH PAN PNTD
BURNER ASSYBURNER ASSY ACCESS PANEL PNTDACCESS PANEL PNTD HEARTH PAN EDGE SHORT PNTDHEARTH PAN EDGE SHORT PNTD
QTY.QTY.
1 1 1
1 1
1 2
1 2 1
1 1 2
PART NO.PART NO.
074270074270 074269074269
074268074268
074266074266 074265074265 074267074267 069484069484 037438037438 069485069485 071584071584
071459071459 071585071585 071567071567
1414 1515 1616 1717 1818
1919
HEARTH PAN EDGE LONG PNTDHEARTH PAN EDGE LONG PNTD RADIATION SHIELD ASSYRADIATION SHIELD ASSY TRANSITION SECTIONTRANSITION SECTION GAS CONTROL ASSY E.I.GAS CONTROL ASSY E.I. GAS CONTROL ASSY NATGAS CONTROL ASSY NAT LIMIT SWITCH
LIMIT SWITCH
2 1 1
1 1 1
071568071568 070945070945
070989070989 077620077620
076673076673 071589071589
53D9019. Rev 3 11/07
42 3/8
HEIGHT
UNIT
SIDE VIEW
24 1/8
22 1/8
APPLIANCE SYSTEM COMPONENTS
The table below is a list of components which may be safely used with this product.
Configuration Kits
6BK Bay Kit 6CK Corner Kit (works for left or right side) 6IK Island Kit 6PNK Peninsula Kit 6SK See-Thru Kit
Control Kits
6CN Control Kit Natural Gas Standing Pilot 6CLP Control Kit Propane/LP Gas Standing Pilot 6CEN Control Kit Natural Gas Electronic Ignition
Accessories
GCKDV6E 6CEN LP Conversion Kit GCK6CLP 6CN LP Conversion Kit GCK6CN 6CLP Natural Conversion Kit 6AK Outside Air Kit 6BKB Back Refractory Look Panel 6BKS Side Refractory Look Panel RC2 Hand Held Remote Control
5
FIGURE 1
4" O.A. INLET
12 1/16
6 1/4
19
TOP VIEW
ELECTRICAL BOX
BOTTOM VIEW
53D9019. Rev 3 11/07
8 1/8
6" B-VENT FLUE
GAS LINE
8
6 1/2
8 7/8
37 1/4
7 1/2
22 1/4
7 1/2
1
36 38
FRONT VIEW
40 1/4
1
53 1/8
42 3/8
UNIT
HEIGHT
1
22 1/8 24 1/8
SIDE VIEW
1
FIREPLACE CONFIGERATION INSTALLATION
6
PART 1
Remove front glass door by removing the cardboard fillers at the top and lifting up and away from the appliance.
Install the handles onto the door using screws from the handle package.
Keep front glass door off of the appliance until installation of Configuration Kit (Part 2) and Control Kit (Part 3) are completed.
Remove carton containing logs. Retain for later installation.
Remove and dispose of the cardboard support for log carton.
Remove burner pan be removing two (2) screws. Replace screws in holes for later use.
Remove the hearth pan that burner was secured to by lifting it up and off of its four (4) locating pins.
PART 2
The appliance is now ready for one of the following configuration kits:
6BK Bay Kit 6CK Corner Kit (Does left or right side open.) 6IK Island Kit 6PNK Peninsula Kit 6SK See-Thru Kit
Complete installation instructions are included with each kit.
PART 3
After installing the Configuration Kit (Part 2), the appliance is ready for one of the following control kits:
6CN Control Kit Natural Gas Standing Pilot 6CLP Control Kit Propane/LP Gas Standing Pilot 6CEN Control Kit Natural Gas Electronic Ignition
Complete installation instructions are included with each kit.
Once your Configuration Kit and Control Kit have been installed, install the hearth pan by positioning it down onto the four (4) locating pins, making sure the access panel is positioned over the controls.
The burner may now be installed onto the hearth pan. This is done by positioning the large opening in the burner, over the pilot protruding up from the control panel. Lower the burner around the pilot down onto the firebox bottom.
Looking through the large opening in the burner pan, positon the burner tube with air shutter onto the orifice mounted on the control panel.
The burner may now be secured at both ends with screws removed earlier.
Proceed with Installation.
53D9019. Rev 3 11/07
FRAMING INSTRUCTIONS
7
It is best to frame your fireplace after it is positioned and the vent system installed. Use 2x4’s and frame to local building codes.
To install the fireplace facing flush with the finished wall, position the framework to accommodate the thickness of the finished wall.
It is not necessary to install a hearth extension with this fireplace system.
The junction box should be wired to the electrical system at the time of installation of the fireplace. Wiring must be performed by a qualified person in a manner to conform with National Electrical Code ANSI/NFPA 70 and all applicable local codes.
CAUTION: ALWAYS CHECK AND MAKE SURE POWER IS OFF BEFORE ATTEMPTING TO INSTALL OR SERVICE ANY ELECTRICAL
WIRING
OR COMPONENTS.
FIGURE 2
3636 3838
38 1/238 1/2
(FRAMING MIN.)(FRAMING MIN.)
3939
(FRAMING MIN.)(FRAMING MIN.)
(SEE-THRU)(SEE-THRU)
FRONT VIEW
FRONT VIEW
12 1/1612 1/16
4 1/24 1/2
9 3/49 3/4
6" B-VENT FLUE6" B-VENT FLUE
4" O.A. INLET4" O.A. INLET
1919
TOP VIEWTOP VIEW
FRAMING 
FRAMING 
DIM. FORDIM. FOR
SEE THRUSEE THRU
23 1/8
7 1/27 1/2
22 1/422 1/4
37 1/437 1/4
7 1/27 1/2
1/21/2
MIN. CLEARANCEMIN. CLEARANCE
(CORNER, 
(CORNER, 
SEE-THRU, SEE-THRU,  AND PENINSULA)AND PENINSULA)
1
(PENINSULA & CORNER)(PENINSULA & CORNER)
Clearance to Combustible Construction. See Figure 2.
40 1/440 1/4
1
42 1/242 1/2
(FRAMING MIN.)(FRAMING MIN.)
(ALL UNITS)(ALL UNITS)
42 3/842 3/8
1
22 1/822 1/8 24 1/824 1/8 24 5/824 5/8
SIDE VIEWSIDE VIEW
1 1/2 MIN. 1/2 MIN. 
CLEARANCECLEARANCE
(BAY AND (BAY AND  CORNER UNIT)CORNER UNIT)
Sides - 1/2 inches Top - 0 to Top of Spacers Bottom - 0 inches
Back - 1/2 inches Front - 37 inches
When the fireplace is installed directly on carpeting, vinyl tile or other combustible material (other than wood flooring) it shall be installed on a metal or wood panel extending the full width and depth of the fireplace.
Provide adequate ventilation air.
Provide adequate accessibility clearance for servicing and operating the fireplace.
Never obstruct the front opening of the fireplace.
53D9019. Rev 3 11/07
FIREPLACE INSTALLATION
8
To accommodate the various configurations, we have provided access openings in the bottom of the unit for gas line and wall switch wires. This may not be convenient for some installations, if so you may drill an access opening into the lower face of the unit (1" for gas line, 1/2" for the grommet).
1. Route the 3/8 inch N.P.T. black iron gas line or equivalent to the fireplace. Include a manual shut-off valve and union in the line so the control may be disconnected for servicing. A drip leg is also recommended in the gas supply line.
2. Install a rigid black pipe or if local codes permit a 3/8 inch flex connector and shutoff valve to the gas line and the fireplace gas valve. Seal and tighten securely. An adapter fitting is required between the gas valve and flex connector if used. Do not kink flex connector (Figure 3).
3. Check for gas leaks with a soap and water solution. D
O NOT USE AN OPEN FLAME.
NOTE: PURGE ALL GAS LINES WITH THE GLASS DOOR OF THE FIREPLACE REMOVED. ASSURE THAT A CONTINUOUS GAS
FLOW
IS AT THE BURNER BEFORE INSTALLING THE DOOR.
FIGURE 3
FLEXIBLE CONNECTOR
ADAPTER FITTING
SHUT OFF VALVE
BLACK IRON PIPE
FIGURE 4
COMBUSTIBLE MANTLECOMBUSTIBLE MANTLE
AND TRIM ALLOWEDAND TRIM ALLOWED
ABOVE DOTTED LINEABOVE DOTTED LINE
8 1/2
12
MEASURE FROM TOPMEASURE FROM TOP
OF OPENINGOF OPENING
FRONT OFFRONT OF
FIREPLACEFIREPLACE
9
2 1/4
53D9019.Rev 3 11/07
FIREPLACE INSTALLATION AND VENTING
APPROVED COWL
MIN.
6 FT.
SUPPORT
4 FT.
MAX.
APPROVED THIMBLE FOR 6" TYPE "B" GAS VENT
CHIMNEY
GAS APPLIANCE
WALL
FLOOR
THROUGH WALL
AS SPECIFIED BY VENT
6" TYPE "B" GAS VENT
MANUFACTURER.
1/2" AIR SPACE TO SIDES AND REAR OF FIREPLACE.
7 FT.
METAL SCREWS.
ATTACH 6" "B" VENT PIPE TO TRANSITION USING (4) SHEET
ATTACH TRANSITION TO FLUE COLLAR USING (3) SHEET METAL SCREWS.
UNITS FLUE COLLAR
FIGURE 5FIGURE 6
APPROVED COWL
ATTACH 6" "B" VENT PIPE TO TRANSITION USING (4) SHEET METAL SCREWS.
ATTACH TRANSITION TO FLUE COLLAR USING (3) SHEET METAL SCREWS.
UNITS FLUE COLLAR
6" TYPE "B" GAS VENT
LISTED CEILING SUPPORT
FLOOR
STORM COLLAR
FLASHING
MINIMUM CLEARANCE AS SPECIFIED BY VENT MANUFACTURER.
"B" VENT CLEARANCE AS SPECIFIED BY VENT MANUFACTURER.
1/2" AIR SPACE TO SIDES AND REAR OF FIREPLACE.
WALL
GAS APPLIANCE
7 FT.
MIN.
9
FIGURE 7
APPROVED THIMBLE FOR 6" TYPE "B" GAS VENT THROUGH WALL
FLOOR
4 FT.
MAX.
AS SPECIFIED BY VENT MANUFACTURER.
6" TYPE "B" GAS VENT CHIMNEY
WALL
1/2" AIR SPACE TO SIDES AND REAR OF FIREPLACE.
GAS APPLIANCE
APPROVED COWL
SUPPORT
6 FT.
MIN.
53D9019.Rev 3 11/07
VENTING REQUIREMENTS
10
WARNING: DO NOT CONNECT THIS APPLIANCE TO A CHIMNEY FLUE SERVING A SEPARATE SOLID FUEL BURNING APPLIANCE. CARBON DEPOSITS (SOOT) AND CREOSOTE FROM SOLID FUELS CAN CLOG THE VENT FROM THE APPLIANCE CAUSING POISONOUS
CARBON
MONOXIDE TO BE RELEASED INTO THE ROOM IN WHICH THE APPLIANCE IS INSTALLED.
All vented gas-fired appliances when operating correctly produce small concentrations of carbon monoxide along with other combustion products. Should something interfere with the operation of the appliance, it is possible for the appliance to produce deadly quantities of poisonous carbon monoxide. A
PRODUCTS
TO
BE VENTED WITHOUT A CORRECTLY WORKING VENT SYSTEM CONNECTED TO THE APPLIANCE.
W
ARNING: VENTING OF THIS APPLIANCE IS ONE FO THE MOST IMPORTANT PARTS OF THE INSTALLATION. VENTING SYSTEMS
MUST
CODES
INSTALLER
FROM THIS APPLIANCE MUST BE VENTED TO THE OUTSIDE AT ALL TIMES. NEVER OPERATE AN APPLIANCE DESIGNED
BE INSTALLED AND INSPECTED ACCORDING TO THESE ISNTRUCTIONS AND LOCAL CODES OR IN THE ABSENCE OF LOCAL
, ACCORDING TO THE NATIONAL FUEL GAS CODE Z223.1 - LATEST EDITION, BY A LICENSED OR OTHERWISE QUALIFED
.
LL FLUE
Your local gas company should have copies of the National Fuel Code Z223.1 or other installation codes applicable to your area.
Venting requirements and accepted methods vary greatly depending on the particular installation. It is impossible to thoroughly define all possible installation circumstances in this manual. The following instructions and illustrations are general guidelines only. A
TO
LOCAL CODES, OR IN THE ABSENCE OF SUCH CODES, ACCORDING TO THE NATIONAL FUEL GAS CODE Z223.1.
LL VENTING MATERIAL MUST BE INSTATLLED ACCORDING
WARNING: AN IMPROPERLY VENTED GAS-FIRED APPLIANCE CAN LEAD TO DEATH FROM CARBON MONOXIDE POSIONING.
Venting materials are not provided with this appliance and must be purchased separately.
This appliance must be installed using 6" type “B” vent.
NOTE: TRANSITION REQUIRED.
53D9019.Rev 3 11/07
LOGS AND TWIGS.
TOP VIEW OF
LOG INSTALLATION
Position logs and twigs onto burner as shown in Figure 8.
FIGURE 8
TOP VIEW OF
LOGS AND TWIGS.
11
Apply ember material near the grate bars as shown in Figure 9.
TOP VIEW - FRONT LOG AND GRATE BARSTOP VIEW - FRONT LOG AND GRATE BARS
FOR PENINSULA AND SEE-THRU CONFIGURATIONS.
EMBER MATERIAL
Curing Instructions
Note: When lit for the first time the fireplace may emit a slight odor for several hours. This is due to the curing and "burn in" of external parts and lubricants used in the manufacturing process. This condition is temporary. Open doors and window to ventilate the room(s) sufficiently.
TYPICAL BOTH SIDES
PORTING
FIGURE 9
SPECIAL EMBER MATERIAL PROVIDED MAY BE PLACED BETWEEN FRONTSPECIAL EMBER MATERIAL PROVIDED MAY BE PLACED BETWEEN FRONT PORTING AND GRATE BARS WITH A RECOMMENDED 3/8" SPACING FREEPORTING AND GRATE BARS WITH A RECOMMENDED 3/8" SPACING FREE OF EMBER MATERIAL DIRECTLY IN FRONT OF THE FRONT BURNER PORTSOF EMBER MATERIAL DIRECTLY IN FRONT OF THE FRONT BURNER PORTS AS SHOWN FOR BEST PERFORMANCE AND EFFECT. BLOCKAGE OF THEAS SHOWN FOR BEST PERFORMANCE AND EFFECT. BLOCKAGE OF THE BURNER PORTS MAY CREATE INCREASED SOOT AND CARBON BUILDUP.BURNER PORTS MAY CREATE INCREASED SOOT AND CARBON BUILDUP.
NOTE:NOTE: TO FURTHER ENHANCE THE HEARTH LAVA ROCK MATERIAL MAY BE PLACEDTO FURTHER ENHANCE THE HEARTH LAVA ROCK MATERIAL MAY BE PLACED
3/8"
ON THE HEARTH PAN AREA TO SIMULATE ASHES. LAVA ROCK MUST NOTON THE HEARTH PAN AREA TO SIMULATE ASHES. LAVA ROCK MUST NOT BE PLACED ON TOP OF THE BURNER. ONLY ROCKWOOD IS PERMITTEDBE PLACED ON TOP OF THE BURNER. ONLY ROCKWOOD IS PERMITTED IN THE BURNER FLAME.IN THE BURNER FLAME.
53D9019. Rev 3 11/07
WALL SWITCH INSTALLATION
COMMON
LINE
OFF
PV
ON
IN
PV
MV
MV
GAS CONTROL/ELECTRONIC IGNITION ROUTING
8
9
SPARK
S8600H
24V, 60 Hz
100% SHUTOFF IP
90 SEC. L.O.
TH-W
(OPT)
7
24V
24V
(GND)
5 6
Explosion hazard. Can cause serious injury or death. This device can malfunction if it gets wet. Never try to use a
WARNING
GND
(BURNER)
PV
3
4
MV
1 2
MV/PV
device that has been wet - replace it.
PV-1A MAX. MV-1A MAX.
WIRE TYPE 105 DEGREE C. REPLACE WITH SAME OR EQUIVALENT.
O
F
F
P
I
L
O
T
LIMIT SWITCH
TP TH TP TH
O
N
WALL SWITCH
12
Units with 6CEN Controls
FIGURE 10
GAS CONTROL/ELECTRONIC IGNITION ROUTING
1. Determine a convenient location within twenty (20) feet and cut a hole large enough to accommodate the wall switch yet be covered with a wall plate. It is not necessary to use a wall box, but one may be used.
2. Route the wire provided through the 1/2 inch black plastic grommet in the unit.
3. Route the wire into the wall box, connect
WIRE TYPE 105 DEGREE C. REPLACE WITH SAME OR EQUIVALENT.
 
GAS LINE-OUT
TO BURNER
PILOT GAS SUPPLY
OUTLET PRESSURE TAP
PILOT
MV
MV
PILOT BURNER GROUND
PV
PV
GAS CONTROL VALVE
OFF
ON
IN
CONTROL ADJUST SCREW
ELECTRONIC CONTROL
WARNING
Explosion hazard. Can cause serious injury or death. This device can malfunction if it gets wet. Never try to use a device that has been wet - replace it.
GAS SUPPLY - IN
INLET PRESSURE
TAP
S8600H
100% SHUTOFF IP
90 SEC. L.O.
24V, 60 Hz
PV-1A MAX. MV-1A MAX.
POWER SUPPLY 120V. 60 Hz.
it to the switch, mount the switch and cover.
4. Set the wall switch to “OFF”.
5. Light the pilot according to instructions.
IGNITION WIRE
LIMIT SWITCH
WALL SWITCH
TRANSFORMER
LINE
COMMON
GND
Units with 6CN and 6CLP Controls
The control system on this fireplace is powered by the thermocouple and operates on approximately 500mv (one-half volt). All connections in the wiring must be clean and tight. The wall switch should be located as near the fireplace as practical. Do not locate the wall switch so that more than the 25 feet of wire provided must be used. Additional wire and splices will cause a voltage drop and may cause the control system to not operate.
1. Determine a convenient location within twenty (20) feet and cut a hole large enough to accommodate the
wall switch yet be covered with a wall plate. It is not necessary to use a wall box, but one may be used.
2. Route the wire provided through the 1/2 inch black plastic grommet in the unit.
3. Route the wire into the wall box, connect it to the switch, mount the switch and cover.
4. Set the wall switch to “OFF”.
5. Light the pilot according to instructions.
IGURE 11
F
TO THERMOCOUPLE
GENERATOR
MANIFOLD TUBING
PILOT TUBING
LIMIT SWITCH
WALL SWITCH
TO PIEZO ELECTRODE
OFF/PILOT/ON CONTROL KNOB
INLET PRESSURE TAP
S.I.T.- 820 NOVA CONTROL
TO THERMOCOUPLE
53D9019. Rev 3 11/07
ADJUSTMENTS AND MAINTENANCE
Pilot Burner Adjustment
1. Adjust the pilot screw to provide a properly sized flame.
2. Do not adjust the pilot screw all the way out counterclockwise because it will leak gas.
Flame Switch (For Units with 6CN and 6CLP Controls)
Your fireplace has been equipped with a thermocouple which senses the flame and shuts of the gas flow to the pilot and main burner in the event that the pilot flame is unstable or becomes extinguished.
D
ANGER: BYPASSING THE THERMOCUPLE MAY LEAD TO AN EXPLOSION
WHICH
COULD RESULT IN PERSONAL INJURY.
Do NOT alter the wiring of the control. Replace the thermo­couple only with components approved by the manufacturer.
13
FIGURE 12
Flame Switch (For Units with 6CEN Controls)
Your fireplace has been equipped with a thermocouple which senses the flame and shuts of the gas flow to the pilot and main burner in the event that the pilot flame is unstable or becomes extinguished.
D
ANGER: BYPASSING THE THERMOCUPLE MAY LEAD TO AN EXPLOSION
WHICH
COULD RESULT IN PERSONAL INJURY.
Do NOT alter the wiring of the control. Replace the thermo­couple only with components approved by the manufacturer.
Venturi Adjustment
Natural gas models have a closed shutter. Opening the air shutter will cause a more blue flame, but can cause flame lifting from the burner ports. Propane gas models have an air shutter set at 3/16 (.188) inch open. The same conditions as above apply for propane gas.
IGURE 14
F
FIGURE 13
3/8 TO 1/2 INCH
PROPERPROPER FLAMEFLAME ADJUSTMENTADJUSTMENT
IGNITER-SENSOR
OTE: AIR SHUTTER AJUSTMENT MUST ONLY BE DONE BY A QUALIFIED
N
INSTALLER.
GAS
53D9019. Rev 3 11/07
ADJUSTMENTS AND MAINTENANCE
14
Maintenance of the Appliance
Air flowing through the appliance will cause dust and lint to collect on the grate, burner and logs. Exessive buildup of dust and lint can cause the pilot and burner to operate improperly and produce hazardous levels of carbon monoxide, a poisonous gas. The appliance may produce carbon (soot) during operation. This carbon (soot) may collect on some logs, some areas of the grate and on the fireplace and vent. Slight carbon buildup is acceptable.
The following is a recommended monthly maintenance program:
1. Turn the gas OFF at the line cut-off valve and allow the appliance to cool.
2. Blow or vacuum all dust and lint out of the appliance, paying particular attention to the pilot, air shutter
end of the burner, air passage into and through the appliance and control.
3. Vacuum or brush away all dust, carbon or lint on the logs and grate.
4. Turn the gas ON at the line cut-off valve and light the appliance according to the isntructions on the
chain.
5. Check all piping, pilot tubing, and manifold connections for leaks with a soap and water or liquid leak
detecting solution. If any leaks are observed, turn the gas OFF immediately and make the necessary repairs.
6. Light the pilot and visually inspect the flame appearance. Note: Any maintenance of the appliance
that requires disconnection of the appliance from the gas line or removal of the control, burner or pilot should only be performed by a qualified person.
53D9019. Rev 3 11/07
OMBUSTION AIR PRECAUTIONS
C
NOTE: The use of outside air for combustion is optional unless required by building codes. It is only necessary to
supply outside combustion air to one side of the fireplace. Use the model OAC4 combustion air kit.
1. Extremely long runs and numerous turns in the duct leading from the fireplace to the combustion air assembly should be avoided. These conditions will increase the resistance to the free flow of air through the duct. Refer to Figure 9 for methods of installing the outside air for combustion assemblies.
2. The combustion air assembly should be located at an exterior location, which is not likely to be accidentally blocked in any manner. The assembly should be located above the snow line to prevent blockage by snow accumulation.
3. The combustion air inlet assembly should never be mounted in a garage or storage area where combustible fumes such as gasoline might be drawn into the fireplace.
4. Combustion air can be drawn from the crawl space under a house when an adequate supply of air is provided by open ventilation.
5. Do not take combustion air from attic space or garage space.
15
DUCT EXTENDEDDUCT EXTENDED TO MISS JOISTTO MISS JOIST
TO OUTSIDE WALLTO OUTSIDE WALL
INSTALLATION ABOVE BASEMENTINSTALLATION ABOVE BASEMENT OR CRAWL SPACE OR CRAWL SPACE
8' MAX.8' MAX.
INLET GRILLEINLET GRILLE IN SOFFIT IN SOFFIT (OVERHANG)(OVERHANG)
CONCRETE SLAB INSTALLATION CONCRETE SLAB INSTALLATION  (OPTIONAL OUTSIDE AIR RUNS) (OPTIONAL OUTSIDE AIR RUNS)
53D9019. Rev 3 11/07
COMBUSTION AIR ASSEMBLY
16
MODEL AK4 COMBUSTION AIR ASSEMBLY
1. Remove the cover plate from the 4-inch outlet opening location on the left outside of the fireplace. DO NOT remove the cover if the outside air will not be connected.
2. Place the starting collar (4 inch) into the hole on the left side of the fireplace. Fasten it in place with the four sheet metal screws provided.
3. Cut a 6-inch diameter opening for model AK4 in the outside wall covering where the outside vent is to be located.
4. Select and cut a piece of duct sufficient length to attach to the fireplace and protrude at least three inches beyond the face of the wall to which the inlet air vent will be attached. The duct may be cut with a standard pocket knife (use FP-4 U duct for maximum efficiency and safety). Do not use a combustible duct. Always use UL Listed Class 0 or 1 duct material. If it is necessary to splice the duct, a Model 403 duct connector should be used to splice duct sections.
5. If the duct is the insulated type, push the insulation back from one end of the duct approximately two inches.
6. Slip the exposed end of the duct over the starting collar on the fireplace.
7. Using the sheet metal screws or duct clamps, secure the duct to the starting collar and to the outside vent.
8. Nail or screw the outside vent to the surface of the wall.
6" DIA. HOLE FOR OAC4 6" DIA. HOLE FOR OAC4
INSERT SHORTEST SIDE OFINSERT SHORTEST SIDE OF THE TUBE THROUGH THE THE TUBE THROUGH THE  FIREPLACE OUTER WRAP.FIREPLACE OUTER WRAP.
NAIL NAIL HOLESHOLES
SCREWSSCREWS
STEP 1: SECURE OUTSIDE AIR STARTINGSTEP 1: SECURE OUTSIDE AIR STARTING COLLAR TO LEFT SIDE OF FIREPLACE WITHCOLLAR TO LEFT SIDE OF FIREPLACE WITH FOUR SHEET METAL SCREWS PROVIDED. FOUR SHEET METAL SCREWS PROVIDED.   
LONGER LENGTH OF THE TUBELONGER LENGTH OF THE TUBE TO OUTSIDE.TO OUTSIDE.
STEP 2: SECURE OUTSIDE STEP 2: SECURE OUTSIDE  DUCT TO STARTING COLLARDUCT TO STARTING COLLAR WITH DUCT CLAMP OR SCREWS.WITH DUCT CLAMP OR SCREWS.
53D9019. Rev 3 11/07
OPERATING INSTRUCTIONS
FOR UNITS WITH 6CEN CONTROLS INSTALLED
FOR YOUR SAFETY READ BEFORE LIGHTINGFOR YOUR SAFETY READ BEFORE LIGHTING
17
WARNING:
A. THIS APPLIANCE IS EQUIPPED WITH AN IGNITION
DEVICE WHICH AUTOMATICALLY LIGHTS THE PILOT.
DO NOT TRY TO LIGHT THE PILOT BY HAND.
B. BEFORE LIGHTING SMELL ALL AROUND THE APPLIANCE
AREA FOR GAS AND NEXT TO THE FLOOR BECAUSE SOME GAS IS HEAVIER THAN AIR AND WILL SETTLE ON THE FLOOR. WHAT TO DO IF YOU SMELL GAS
DO NOT TRY TO LIGHT ANY APPLIANCE. DO NOT TOUCH ANY ELECTRIC SWITCH; DO NOT USE ANY PHONE IN YOUR BUILDING. IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR'S PHONE. FOLLOW THE GAS SUPPLIER'S INSTRUCTIONS.
CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
OPERATING INSTRUCTIONSOPERATING INSTRUCTIONS
1. STOP! READ THE SAFETY INFORMATION ABOVE ON THIS LABEL.
2. SET THE ROCKER SWITCH TO "OFF".
3. TURN OFF THE ELECTRIC POWER TO THE APPLIANCE.
4. THIS APPLIANCE IS EQUIPPED WITH AN IGNITION DEVICE WHICH AUTOMATICALLY LIGHTS THE PILOT.
ON
OFF
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULTIF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT
IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL
THE FIRE DEPARTMENT.
C. USE ONLY YOUR HAND TO PUSH IN OR TURN THE GAS
CONTROL KNOB. NEVER USE TOOLS. IF THE KNOB WILL NOT PUSH IN OR TURN BY HAND, DO NOT TRY TO REPAIR IT. CALL A QUALIFIED SERVICE TECHNICIAN.
FORCE OR ATTEMPTED REPAIR MAY RESULT IN A FIRE
OR EXPLOSION.
D. DO NOT USE THIS APPLIANCE IF ANY PART HAS
BEEN UNDER WATER. IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE APPLIANCE AND REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL WHICH HAS BEEN UNDER WATER.
5. REMOVE CONTROL ACCESS PANEL.
6. TURN GAS CONTROL KNOB CLOCKWISE TO "OFF".
7. WAIT FIVE (5) MINUTES TO CLEAR OUT ANY GAS. IF YOU THEN SMELL GAS, STOP! FOLLOW "B" IN THE
SAFETY INFORMATION ABOVE ON THIS LABEL. IF YOU DON'T SMELL GAS, GO TO NEXT STEP.
8. TURN GAS CONTROL KNOB COUNTERCLOCKWISEDO NOT TRY TO LIGHT THE PILOT BY HAND.
TO "ON".
9. REPLACE CONTROL ACCESS PANEL.
10. TURN ON ALL ELECTRIC POWER TO THE APPLIANCE.
11. SET THE ROCKER SWITCH TO "ON".
12. IF THE APPLIANCE WILL NOT OPERATE, FOLLOW THE INSTRUCTIONS "TO TURN OFF GAS TO APPLIANCE" AND CALL YOUR SERVICE TECHNICIAN OR GAS SUPPLIER.
POSITION POSITION INDICATORINDICATOR
GAS CONTROLGAS CONTROL KNOBKNOB
TO TURN OFF GAS TO APPLIANCETO TURN OFF GAS TO APPLIANCE
1. SET THE ROCKER SWITCH OR WALL SWITCH TO "OFF".
2. REMOVE CONTROL ACCESS PANEL.
3. DEPRESS THE CONTROL KNOB INWARD SLIGHTLY AND TURN CLOCKWISE TO OFF.
53D9019. Rev 3 11/07
4. REPLACE CONTROL ACCESS PANEL.
5. IF THE APPLIANCE IS EQUIPPED WITH AN AUTOMATIC IGNITION DEVICE OR OPTIONAL BLOWER, TURN OFF ALL ELECTRICAL POWER TO THE APPLIANCE IF SERVICE IS TO BE PERFORMED.
068059068059
OPERATING INSTRUCTIONS
FOR UNITS WITH 6CN AND 6CLP CONTROLS INSTALLED
FOR YOUR SAFETY READ BEFORE LIGHTING
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT
WARNING:
A.A.
THIS APPLIANCE HAS A PILOT WHICH MUST BE LIT BYTHIS APPLIANCE HAS A PILOT WHICH MUST BE LIT BY HAND WHILE FOLLOWING THESE INSTRUCTIONS EXACTLY.HAND WHILE FOLLOWING THESE INSTRUCTIONS EXACTLY. BEFORE LIGHTING SMELL ALL AROUND THE APPLIANCEBEFORE LIGHTING SMELL ALL AROUND THE APPLIANCE
B.B.
AREA FOR GAS AND NEXT TO THE FLOOR BECAUSEAREA FOR GAS AND NEXT TO THE FLOOR BECAUSE SOME GAS IS HEAVIER THAN AIR AND WILL SETTLE ONSOME GAS IS HEAVIER THAN AIR AND WILL SETTLE ON THE FLOOR.
WHAT TO DO IF YOU SMELL GAS
DO NOT TRY TO LIGHT ANY APPLIANCE. DO NOT TOUCH ANY ELECTRIC SWITCH; DO NOT
USE ANY PHONE IN YOUR BUILDING. IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A
IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A
NEIGHBOR'S PHONE. FOLLOW THE GAS SUPPLIER'S INSTRUCTIONS.
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
LIGHTING INSTRUCTIONS
IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALLIF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE DEPARTMENT.
USE ONLY YOUR HAND TO PUSH IN OR TURN THE GAS
USE ONLY YOUR HAND TO PUSH IN OR TURN THE GAS
C.C.
CONTROL KNOB. NEVER USE TOOLS. IF THE KNOB WILLCONTROL KNOB. NEVER USE TOOLS. IF THE KNOB WILL NOT PUSH IN OR TURN BY HAND, DO NOT TRY TO REPAIRNOT PUSH IN OR TURN BY HAND, DO NOT TRY TO REPAIR IT. CALL A QUALIFIED SERVICE TECHNICIAN. FORCE ORIT. CALL A QUALIFIED SERVICE TECHNICIAN. FORCE OR ATTEMPTED REPAIR MAY RESULT IN A FIRE OR EXPLOSION. DO NOT USE THIS APPLIANCE IF ANY PART HAS BEENDO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN
D.D.
UNDER WATER. IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE APPLIANCE AND REPLACETECHNICIAN TO INSPECT THE APPLIANCE AND REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GASANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL WHICH HAS BEEN UNDER WATER.
18
WHEN LIGHTING AND RELIGHTING, THE GAS KNOB CANNOTWHEN LIGHTING AND RELIGHTING, THE GAS KNOB CANNOT BE TURNED FROM PILOT TO OFF UNLESS THE KNOB ISBE TURNED FROM PILOT TO OFF UNLESS THE KNOB IS DEPRESSED.
1. STOP! READ THE SAFETY INFORMATION ON THE FIRST1. STOP! READ THE SAFETY INFORMATION ON THE FIRST LABEL.
2. TURN OFF ALL ELECTRICAL POWER TO THE APPLIANCE.
2. TURN OFF ALL ELECTRICAL POWER TO THE APPLIANCE.
3. TURN GAS KNOB CLOCKWISE TO OFF.
OFF
ON
T
O
P
L
I
GAS KNOB "OFF"GAS KNOB "OFF"
4. WAIT FIVE (5) MINUTES TO CLEAR OUT ANY GAS. THEN4. WAIT FIVE (5) MINUTES TO CLEAR OUT ANY GAS. THEN SMELL FOR GAS, INCLUDING NEAR THE FLOOR. IF YOU SMELL FOR GAS, INCLUDING NEAR THE FLOOR. IF YOU SMELL GAS, STOP! FOLLOW "B" IN THE SAFETY INFOR- SMELL GAS, STOP! FOLLOW "B" IN THE SAFETY INFOR-
MATION ON THE FIRST LABEL. IF YOU DON'T SMELL MATION ON THE FIRST LABEL. IF YOU DON'T SMELL
GAS GO TO THE NEXT STEP.
TO TURN OFF GAS TO APPLIANCE
1. TURN OFF ALL ELECTRICAL POWER TO THE APPLIANCE
1. TURN OFF ALL ELECTRICAL POWER TO THE APPLIANCE IF SERVICE IS TO BE PERFORMED.
5. IF APPLIANCE IS EQUIPPED WITH HI-LO ADJUSTMENT  VALVE TURN COUNTERCLOCKWISE TO HIGH. VALVE TURN COUNTERCLOCKWISE TO HIGH.
6. FIND PILOT LOCATED IN FRONT OF THE MIDDLE LOG.6. FIND PILOT LOCATED IN FRONT OF THE MIDDLE LOG. PILOTPILOT
PIEZO ELECTRODEPIEZO ELECTRODE
THERMOCOUPLETHERMOCOUPLE
7. TURN GAS KNOB COUNTERCLOCKWISE TO PILOT.7. TURN GAS KNOB COUNTERCLOCKWISE TO PILOT.
8. DEPRESS AND HOLD GAS KNOB WHILE LIGHTING THE8. DEPRESS AND HOLD GAS KNOB WHILE LIGHTING THE
PILOT WITH THE PUSH BUTTON IGNITOR. KEEP KNOB PILOT WITH THE PUSH BUTTON IGNITOR. KEEP KNOB FULLY DEPRESSED FOR ONE MINUTE, THEN RELEASE. FULLY DEPRESSED FOR ONE MINUTE, THEN RELEASE. IF PILOT DOES NOT CONTINUE TO BURN REPEAT STEPS
IF PILOT DOES NOT CONTINUE TO BURN REPEAT STEPS
3 THRU 7.
9. WITH PILOT LIT TURN GAS KNOB COUNTERCLOCKWISE
TO ON.
10. IF EQUIPPED WITH REMOTE ON-OFF SWITCH MAIN10. IF EQUIPPED WITH REMOTE ON-OFF SWITCH MAIN BURNER MAY NOT COME ON WHEN YOU TURN THE BURNER MAY NOT COME ON WHEN YOU TURN THE
VALVE TO ON OR HIGH. REMOTE SWITCH MUST BE IN
VALVE TO ON OR HIGH. REMOTE SWITCH MUST BE IN THE ON POSITION TO IGNITE BURNER.
11. TURN ON ALL ELECTRICAL POWER TO THE APPLIANCE.11. TURN ON ALL ELECTRICAL POWER TO THE APPLIANCE.
2. PUSH IN GAS CONTROL KNOB SLIGHTLY AND TURN
2. PUSH IN GAS CONTROL KNOB SLIGHTLY AND TURN
CLOCKWISE TO OFF. DO NOT FORCE.
GENERATORGENERATOR
068058068058
53D9019. Rev 3 11/07
SAFETY CHECKLIST
Correct installation and safe operation of this appliance require, but are not limited to the following:
Do's:
1. Do use this appliance only on type of gas it is designed, certified and equipped.
2. Do install this appliance and all gas piping according to local codes, or in the absence of local codes, according to the current National Fuel Gas Code, ANSI Z223.1 latest edition.
3. Do disconnect or isolate the appliance during supply line pressure testing.
4. Do locate the appliance out of traffic patterns as much as possible.
5. Do keep in mind that some furniture materials such as vinyl or plastic may deform at the temperatures near this appliance and must be kept at greater distances.
6. Do use joint compound (pipe dope) on threaded joints of gas piping that is resistant to the action of liquified petroleum gas.
7. Do include a manual shutoff valve and union ahead of the controls so that the controls and appliance may be removed for servicing if necessary.
8. Do use only ground joint unions in gas piping.
9. Do include a drip leg in the gas supply connection to the appliance.
10. Do use only soap-water solution or liquid gas leak solution when checking for leaks in the gas plumbing. Never use matches, candles or other ignition sources when checking for leaks.
11. Do connect the appliance only to an agency listed vent system.
12. Do adjust the air shutter as required to produce the proper flame as described in this manual.
13. Do keep the area around the appliance clear and free from combustible materials, gasoline and other flammable vapors and liquids.
14. Do follow the lighting and operation procedures given in this manual.
15. Do periodically inspect the pilot and burner flame as described in the maintenance section of this manual.
16. Do clean the appliance as specified in the maintenance section of this manual.
17. Do provide electrical grounding of appliance in accordance with local codes and/or the National Electric Code ANSI NFPA 70 latest edition.
18. Do inspect the entire venting system at least once a year and replace all parts that show evidence of damage or deterioration.
19
Don’ts
1. Don’t modify or alter the appliance cabinet (jacket) in any way.
2. Don’t use this appliance on any gas other than the type for which it is equipped. The type of gas for which the appliance was equipped at the factory is stamped on the rating plate located on the bottom of the appliance.
3. Don’t install the appliance in areas where gasoline or any flammable liquid or any explosive materials may be used or stored.
4. Don’t obstruct the flow of air for combustion and ventilation into or away from the appliance at any time.
5. Don’t use this appliance if any part has been underwater. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
6. Don’t operate this appliance without proper electrical grounding according to local codes or the National Electric Code ANSI NFPA 70 latest edition.
7. Don’t operate this appliance without a proper vent.
8. Don’t connect this appliance to a chimney flue serving a solid fuel burning appliance.
9. Don’t use thermostats or automatic burner cycling devices.
53D9019. Rev 3 11/07
TROUBLESHOOTING
20
While the manufacturer has made every reasonable effort to ensure that this appliance operates properly and satisfactorily, sometimes problems do arise. The following troubleshooting chart lists several problems with their probable cause and remedy. Any adjustments and/or replacements must be by a qualified person. Do not replace any component with a different type. Use only components supplied by the manufacturer for this appliance.
Trouble
Flame too Large
Noisy Flame
Yellow or Excessive Flame
Floating Flame
Delayed Ignition
Probable Cause
1. Pressure Regulator Set too Hi
2. Defective Regulator
3. Burner Orifice too Large
1. Too Much Primary Air
2. Noisy Pilot
3. Burr in Orifice
1. Too Little Primary Air
2. Clogged Burner Ports
3. Misaligned Orifices
4. Clogged Vent System
1. Blocked Venting
2. Insufficient Primary Air
1. Improper Pilot Location
2. Pilot Flame too Small
3. Burner Ports Clogged
4. Low Pressure
Remedy
1. Reset, Using Manometer
2. Replace
3. Replace with Correct Size
1. Adjust Air Shutters
2. Reduce Pilot Gas
3. Remove Burr or Replace
1. Adjust Air Shutters
2. Clean Ports
3. Realigned or Replace Burner
4. Clean
1. Clean
2. Adjust Air Shutter
1. Reposition Pilot
2. Check Orifice, Increase Gas
3. Clean Ports
4. Adjust Pressure Regulator
Failure to Ignite
Burner Won’t Turn Off
Burner Won’t Turn On
Burner & Pilot Flame Go Out
1. Main Gas Off
2. Defect in Gas Valve
1. Defective Auto Valve
1. Defective Auto Valve
2. Defective Thermocouple
3. Defective Switch
4. Defective Auto Pilot Valve
1. Poorly Functioning Vent System
2. Gas Supply Interrupted
3. Defective Thermocouple or Control
1. Open Manual Valve
2. Replace
1. Clean or Replace
1. Replace
2. Replace
3. Repair or Replace
4. Replace
1. If Pilot can be Relit but Main Burner & Pilot Go Off After Ignition, Have Vent System Checked and Corrected Immediately.
2. Try Relighting Pilot and Main Burner. If Pilot won’t Relight, Check Thermocouple & Control
3. Replace
53D9019. Rev 3 11/07
MASSACHUSETTS RESIDENTS ONLY:
PLEASE READ AND FOLLOW THESE
SPECIAL REQUIREMENTS
NOTE REGARDING VENTED PRODUCTS
This product must be installed by a licensed plumber or gas fi tter when installed within the Commonwealth of Massachusetts.
Any residence with a direct vent product must have a CO detector installed in the residence. Installation of the fi replace or vented gas log in the State of Massachusetts requires the damper to be permanently
removed or welded in the fully open position. In addition, a naturally vented gas log may not be installed in a bedroom or bathroom in the State of
Massachusetts. Flex line installation must not exceed 36 inches and must have a T shutoff valve.
NOTE REGARDING VENT FREE PRODUCTS
This product must be installed by a licensed plumber or gas fi tter when installed within the Commonwealth of Massachusetts.
In addition, vent free products may not be installed in a bedroom or bathroom regardless of size or type in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have a T shutoff valve.
CARBON MONOXIDE DETECTOR REQUIREMENTS
(2) Revise 10.8.3 by adding the following additional requirements: (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure
used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above fi nished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfi ed:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall hori­zontal vented gas fueled equipment, the installing plumber or gasfi tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed. In addition, the installing plumber or gasfi tter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space
or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent fl oor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of
installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detec­tor with an alarm shall be installed.
SPECIAL REQUIREMENTS CONTINUED
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accor-
dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certi­ ed.
3. SIGNAGE. A metal or plastic identifi cation plate shall be permanently mounted to the exterior of the build-
ing at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUC-
TIONS.”
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detec­tors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current
edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure
separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUF ACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manu-
facturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components;
and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the
manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the fl ue gases, but identifi es “special venting systems,” the following requirements shall be satisfi ed by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment
installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system
shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equip-
ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
NOTES
21
53D9019. Rev 3 11/07
NOTES
22
53D9019. Rev 3 11/07
ATTENTION
APPLIANCE
INSTALLER
PLEASE RETURN THESE OPERATING
AND
53D9019. Rev 3 11/07
INSTALLATION INSTRUCTIONS
TO THE APPLIANCE FOR
CONSUMER USE.
Loading...