Mohlenhoff Alpha Thermostat AR 2010 C2, Alpha Thermostat AR 4110 C2, Alpha Thermostat AR 4010 C2, Alpha Thermostat AR 2110 C2 Technical Information

Technical Information
AR 4010 C2
1025
Alpha-Thermostat
Alpha-Thermostat Control AR 20.. C2 (230 V) | AR 40.. C2 (24 V)
The Alpha-Thermostat Control is a digital room thermostat for the control of surface heating systems with thermal actuators (e. g. OEM actuator: A 2004 / A 4004). This thermostat is equipped with microprocessor technology; it shows excellent PI controlling behaviour with increased regulating comfort for the user. Temperature pre-selection is in 1/4 degree steps. The selector switch (switching ball) allows the setting of the desired operating mode (DAY, NIGHT or AUTOMATIC). The plug-in digital clock can be removed for programming. The thermostat must be mounted to the pre-installed Alpha Mounting Base AS 1000, onto which it can be plugged at any time and to which it must be electrically connected. In order to avoid damage to this valuable thermostat during the construction phase, the system base is not included in the scope of delivery; it can be ordered already in advance for the necessary electric installation.
Features
l Precise control response l Antifreeze function 5 °C l Valve protection function l Overcharge protection l Designs normally closed (NC) and normally open (NO) l Operating mode selector switch l Adjustment of temperature setback 2-6 K l Limitation of set room temperature l Illuminated "Moon" symbol for temperature setback l Just-in-time installation concept l Simple screwed connection technology in the Alpha System Base l Functional design l 12 housing colours available
Control functions
l Digital timer Control for manual programming l Day and week programming l 7 days power reserve l 1 channel with 42 memory locations (21 ON and 21 OFF switching
times).
l Free block formation and summer time conversion
Application
l Individual room control, specially designed in connection with
surface, radiator and convector heating systems.
General information
Type
AR 2010 C2: Version 230 V  normally closed (pure white) AR 4010 C2: Version 24 V  normally closed (pure white)
Scope of delivery (Standard)
Version: Alpha-Thermostat Control 230 V / 24 V  normally closed: 1 x AR 2010 C2 or AR 4010 C2 1 x Installation instruction
Alternative design:
AR 2110 C2: Version 230 V  normally open (pure white) AR 4110 C2: Version 24 V  normally open (pure white) Housing colour on request
Accessories
Alpha Mounting Base AS 1000
Connection recommendations
-OEM actuator NC A 2004 / NC A 4004
-OEM base without pump control: B 2012 / B 4012
Customer-specific version:
Customer-specific versions are available on request
Ordering information
Our staff will be glad to assist you in finding the Alpha-Thermostat fitting your application. Call us under: +49 (0) 53 41 - 84 75 - 0
NO A 2104 / NO A 4104
with pump control: B 2022 / B 4022
Mikrocontroller Technology
Functions
The Alpha-Thermostat 20../40.. C2 is a PI thermostat for the control of thermoelectric actuators (e. g. OEM actuator). The output voltage is switched on or off depending on the difference between the room temperature measured by the thermostat (actual value) and the desired temperature (set value). The bigger the difference is between set value and actual value, the longer are the switching cycles. When the room temperature approaches the set temperature, the switching cycles of the output voltage are reduced and find their balance at an almost constant value corresponding to the heating power for this room.
Selector switch
The desired operating mode can be selected with the selector switch. The operating modes Normal (sun symbol), Economy (moon symbol, e. g. for night operation) and Timer (clock symbol) are available.
Valve protection function (only NC)
If an actuator is not triggered during more than 24 hours of normal operation, the electronic system switches the actuator for 6 minutes once every 24 hours. This prevents the thermostat valves from clogging outside the heating season.
Antifreeze protection
If the set value element of the Alpha-Thermostat is set to the right stop (symbol ), a room temperature of 5 °C is set as target value in order to prevent the installation from freezing.
Overcharge protection
The switching output of all Alpha-Thermostats with microprocessor technology is protected by an internal temperature monitoring system in order to prevent the system from overcharge damage. In case of an internal temperature rise due to overcharge the electronic system automatically disconnects the output until the inside temperature has dropped again to normal values.
Control panel
4
5
3
2
6
1.
2.
OPEN
CLOSE
Lock (for locking the thermostat on the system base)
Temperature setback pre-selection
°C
T 1A
Selector switch
Room thermostats
Technical Information
Alpha-Thermostat
Technical data
Type AR 20.. C2 AR 40.. C2
Version Control Contact rating max 5 OEM actuators 230 V Operating voltage 230 V +/- 10%, 50 Hz Switched current 0,2 A (ohmic load) Control range (heating zone) 10 to 28°C Temperature setback (heating zone) 2 - 6 K Hunting approx. 0,2 K
Room thermostats
Valve interval switching if output is inactive for 24 h, once a day Antifreeze protection on position* 5°C Storage temperature -25 to +70 °C Ambient temperature 0 to +50 °C Relative humidity max. 80%
1)
Degree / class of protection IP 30 / II CE conformity according to EN 60730 Housing ABS Number of housing colours 12 Weight 74 g without Alpha Mounting Base
Note! The digital timer of the thermostats AR 20.. / 40.. C and AR 20.. / 40.. C2 are not electrically compatible. However, a confusion
does not lead to any damage of the devices.
Control max 5 OEM actuators 24 V 24 V, (19,2 - 35 V) 50/60 Hz 1 A (ohmic load) 10 to 28°C 2 - 6 K approx. 0,2 K
5°C
-25 to +70 °C 0 to +50 °C max. 80%
1)
IP 30 / III EN 60730 ABS 12 74 g without Alpha Mounting Base
80 mm
2)
27 mm
118 mm
1)
not condensing
2)
with Alpha Mounting Base + 8,5 mm
Installation note
Installation and electric connection are only possible using the system base AS 1000. The system base is not included in the scope of supply and must be ordered separately; it fits all wired types of the Alpha­Thermostat scope.
1.
2.
Installation can be performed directly to the wall or on a flush-type box. A 5-wire line (5 x 1.5 NYM) is recommended for the electric connection.
Recommended place of installation
ca. 30cm
ca.150cm
Note!
In order to ensure a trouble-free and thus optimum control operation, a room thermostat should be installed behind the door in a quiet zone - free from environment influence as draught, humidity, direct sunlight exposure or other sources of heat; furthermore, it should not be covered by curtains. Otherwise it may occur that the set room temperature is exceeded or not achieved, depending on the respective environment influence.
Electric installation
Alpha-Thermostat AR 20.. C2 / AR 40.. C2
Alpha-Thermostat AR 20.. K2 / AR 40.. K2
230V
24V
24V
230V
230V
24V
24V
230V
max. 5 OEM actuator
A 2004 / A 4004
max. 5 OEM actuator
A 2004 / A 4004
further Alpha-Thermostats
230 V AC
24 V AC
LN
L1L2
Diagram for automatic temperature setback with Alpha-Thermostat Control
Möhlenhoff Wärmetechnik GmbH Museumstraße 54a 38229 Salzgitter - Germany
Telephone +49 (0) 53 41· 8475-0 Fax +49 (0) 53 41·8475-99
E-Mail: contact@moehlenhoff.de Internet: www.moehlenhoff.de
Technical changes reserved.
8-D58-40-387. Reprint, in whole or in part, is only admissible with our approval.