This manual is designed to take a more in depth look at the E89M / MS prover and holding cabinets for the
purpose of making the unit more understandable to service people.
There are settings explained in this manual that should never require to be adjusted, but for
completeness and those special cases where these settings are required to change, this manual gives a
full explanation as to how, and what effects will result.
100-120 Volts A.C. 60 Hz, 12.5 A, 1.5kW
208-220 Volts A.C. 50/60 Hz, 6.5A, 1.45kW
220-240 Volts A.C. 50/60 Hz, 7.1 A, 1.7kW
ELECTRICAL PLUG SPECIFICATION
REQUIREMENTS
Australia 3-pin 250V 10A, AS/NZ 3112
Canada 3-pin 125V 15A, NEMA 5-15
New Zealand 3-pin 250V 10A, AS/NZ 3112
United Kingdom 3-pin 250V 13A fused, BS 1363A
United States 3-pin 125V 15A, NEMA 5-15
Other Countries 3-pin 250V 10A minimum, type
to meet country standards
WATER SUPPLY CONNECTION
(Autofill Models Only)
Max Pressure 550 kPa / 5.5 bar / 80 psi
Min Pressure 100 kPa / 1.0 bar / 15 psi
Revision 1/F3608
-7-
2. INSTALLATION
WARNING: THIS APPLIANCE MUST BE GROUNDED.
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED OUT BY
QUALIFIED PERSONS ONLY.
It is most important that the prover is installed
correctly and that the operation is correct before
use. Installation shall comply with local electrical,
health and safety requirements.
BEFORE CONNECTION TO POWER SUPPLY
Unpack and check unit for damage and report
any damage to the carrier and dealer. Report
any deficiencies to your dealer. Check that the
available power supply is correct to that shown on
the rating plate located on the right-hand side
panel.
100-120 Volts A.C. 60 Hz, 12.5 A, 1.5kW
208-220 Volts A.C, 50/60 Hz, 6.5A, 1.45kW
220-240 Volts A.C. 50/60 Hz, 7.1A, 1.7kW
LOCATION
To ensure correct operation the following
minimum installation clearances are to be
adhered to:
Rear 0mm / 0”
Left-hand side 0mm / 0”
Right-hand side 25mm / 1”
Provision must be allowed for the door opening.
ELECTRICAL CONNECTION
E89 models are supplied with pre-fitted cords.
Ensure unit is fitted with correct cord and plug for
the installation (refer specifications section).
Should changing of the cord be necessary, gain
access to the electrical connection terminal block
and strain relief clamp by removing the RH side
panel.
WATER CONNECTION (AUTOFILL MODELS
ONLY)
A connection elbow and sealing washer is
supplied with this unit for direct connection of a
½” ID hose, and is recommended for easy
installation and service.
Connect water supply - Max inlet pressure
550kPa / 80psi.
Turn on water supply to check for leaks.
DOUBLE STACKING UNITS
When it is desired to mount a Turbofan E32
convection oven on an E89, a double stacking kit
must be used. Available from your dealer or
Turbofan distributor (see Spare Parts). For
stacking kit assembly instructions, refer Appendix
B.
RACK WIDTH POSITIONS
The E89 prover has been designed to accept
either 460mm (18”) or 405mm (16”) wide trays,
1/1 GN,
1
/2 /1 GN trays or USA steam pans.
The prover comes factory set for 460mm (18”)
trays, a rack spacer kit (Part no. 025685) is
required to change to 405mm (16”) trays,
Gastronorm pans or USA steam pans.
RATING PLATE LOCATION
The rating plate for the E89 prover is located at
the bottom left corner of the RH side panel.
L1L2
Phase
RED
BROWN
BLACK
WARNING:
Revision 1/F3608
Neutral
BLACK
BLUE
WHITE
THIS APPLIANCE MUST
BE GROUNDED / EARTHED
Figure 2.1
Ground
GREEN
GREEN/YELLOW
Rating Plate
Figure 2.3
-8-
3. OPERATION
NOTE: A full user’s operation manual is supplied with the product and can be used for further referencing
of installation, operation and service.
3.1 DESCRIPTION OF CONTROLS - E89 PROVER / HOLDING CABINETS
1. FUNCTION
OFF Unit is off.
PROOF Unit is in proofing mode. (Indicator
illuminates when switched to this position)
HOLDUnit is in holding mode. (Indicator
illuminates when switched to this position)
2. THERMOSTAT
Temperature range 0 - 85°C (32 - 185°F).
Indicator illuminates when elements are cycling
ON to maintain set temperature.
Controls the prover air temperature.
3. HUMIDITY CONTROL
1 to 5 Setting for butter based pastries
(croissants, Danish pastries etc.)
5 to 8 Settings for yeast based breads and
doughs.
Indicator illuminates when elements are cycling
ON to maintain set temperature.
(Controls the cabinet humidity in PROOF mode
only)
Manual Water Fill Models: Open the prover
door. Fill the water trough at the filling spout,
located at the front of the right hand side rack, to
approximately 20mm / ¾” from the top of the
trough. Remember to top up the water trough
when the water level is below the halfway level in
the trough and before the heating element is
exposed.
Auto Water Fill Models: Check that the water
trough is filling, and the heating element is well
covered.
4. THERMOMETER
Indicates cabinet temperature.
Dual Centigrade and Fahrenheit scale.
CONDENSATION CHANNEL
Below the door there is a condensation channel
and removable water collection drawer for the
purpose of collecting door condensation run-off.
1
2
3
4
89
P
R
O
O
F
D
L
O
H
Revision 1/F3608
-9-
3.2 EXPLANATION OF CONTROL
SYSTEM
The E89M/MS Prover/Holding Cabinets feature
operator controls and an electrical circuit for
which a direct understanding of their operation is
required before carrying out any service work or
fault repair work. The control device functions
and electrical circuit are explained as follows:
Function Switch
A rotary switch on the control panel of these
models functions as the power On/Off switch of
the unit by isolating the Line 1 phase supply.
This switch is a 3 position, 4 pole, multi-function
switch which in the Off position opens circuits all
poles and isolates power from all control and
heating systems. The switch should operate as
illustrated below.
P1 – No function / not used.
P2 – Additional air heating element.
P3 – Humidity control thermostat.
(Auto-fill models only - water solenoid, float
switch, solenoid relay)
P4 – Air heating thermostat, cabinet lights, air
circulation fan motor and control panel
power indicator.
P1
H
P2
P
P
P4
The air circulation fan, cabinet lights and control
panel power indicator are On continuously on all
E89 models when the function switch is in either
of the PROOF or HOLD positions. The air
circulation fan mounted at the top of the air
delivery ducting ensures that the temperature and
humidity throughout the cabinet is even by
creating a low velocity air circulation system
throughout the prover cabinet.
Proof Mode
In the ‘Proof’ position the function switch poles
P1, P3 and P4 are closed, supplying power to the
dry heat circuit, humidity circuit, cabinet lights and
fan.
1
P1
D
L
O
2
F
O
O
R
3P3
R
W
4
OFF PROOF HOLD
H
P2
PROOF
P33
PWR
P44
1
P1
D
L
O
2
HOLD
P2
P
P33
PWR
P44
1
2
F
O
O
R
Figure 3.2.1
The proofing system controls air temperature and
humidity levels by way of an air heating element
and a water tank heating element.
The air heating element is positioned in the
bottom of the air circulation ducting inside the
cabinet and is directly controlled by the
user-adjustable thermostat mounted to the control
panel. The thermostat sensing bulb is mounted
inside the cabinet to control the cabinet air
temperature to the control panel setting. An
indicator light on the control panel above this
thermostat will illuminate when the thermostat
has the air heating element operating and will
cycle Off with the thermostat to indicate when the
temperature reaches set point. The main
thermostat is adjustable up to 85°C (185°F).
The humidity thermostat mounted on the control
panel controls the water tank heating element,
which in turn maintains the water temperature
between 20°C (68°F) and 85°C (185°F). The
evaporation of the water provides the cabinet
humidity. The setting of the humidity thermostat
(between 1 - 8) controls the rate of water
evaporation and therefore the level of humidity in
the cabinet.
An indicator light on the control panel above the
humidity dial illuminates when the water tank
element is On, and cycles Off when the
thermostat switches the heating element Off to
provide an indication of the humidity control. The
sensing bulb of the humidity thermostat is
mounted to the water tank heating element, which
is immersed in the water tank. Should the water
tank level drop below the heating element the
humidity thermostat will cycle Off due to the
sensing bulb reacting to the radiated heat off the
heating element and will prevent the humidity
water tank heating element burning out through
excessive temperature.
Hold Mode
When the function switch is turned to the ‘Hold’
position the function switch pole P3 opens to turn
off the humidity control circuit, and pole P2 closes
to connect an additional air heating element to
the air temperature thermostat circuit. In this
mode the air temperature thermostat operates as
it does in the proofing mode, however, in this
case there is an additional air heating element
switched On and Off to provide extra heating
power in this mode. The additional air heating
element is also mounted in the air circulation
ducting.
E89M/MS Prover/Holding Cabinets are provided
with a thermometer dial on the control panel to
Revision 1/F3608
-10-
provide an indication of the cabinet temperature.
The sensing bulb of this thermometer dial is
mounted next to the sensing bulb of the main
thermostat inside the cabinet.
Auto water fill (option)
E89 Auto-Water fill models provide for a mains
cold water supply connection for automatic water
tank filling and level control. Non Auto-Water fill
models require the operator to manually fill the
water tank and maintain the water tank level as
the water evaporates through operation.
On Auto-Water fill models an electric solenoid
valve, float switch and relay maintain the water
level in the humidity tank. The float switch is
mounted at the rear of the water tank, and when
the water is below the full level it open circuits,
removing power from the coil. When deenergised, the relay removes power from the
humidity thermostat circuit (therefore switching off
the humidity element), and switches power to the
water solenoid. As the water level reaches the
full level position the float switch contact will
close, re-energising the water solenoid relay,
thereby closing the water solenoid valve and
providing power back to the humidity thermostat.
Accordingly this system will automatically
maintain a full water tank whenever the function
switch is in the “PROOF” position and the mains
water supply is turned on.
Ensuring that the function switch is in the Off
position is necessary whenever removing the
water tank for cleaning as when the water tank is
removed the float switch drops and the water
solenoid valve will open (if the unit is on).
Therefore as a precaution the mains water supply
should also be turned Off whenever removing the
water tank.
Revision 1/F3608
-11-
4. MAINTENANCE
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED OUT BY
QUALIFIED PERSONS ONLY.
4.1 CLEANING
WARNING: ALWAYS TURN THE
POWER SUPPLY OFF BEFORE
CLEANING.
IMPORTANT: THIS UNIT IS NOT
WATER PROOF.
DO NOT USE A WATER JET SPRAY TO
CLEAN INTERIOR OR EXTERIOR OF
THIS UNIT.
CABINET
A good quality stainless steel cleaning compound
is recommended for cleaning the inside and
outside of the cabinet. Harsh abrasive cleaners
may damage the surface.
SIDE RACKS
To remove, take hold of the centre rung and lift
towards the prover top. To replace, hold
horizontally, engage in holes and push down.
DOOR
Wash with warm water and detergent solution
using a soft sponge in straight lines up and down
the door.
Rinse with clean, warm water to remove
detergent. Dry off.
Clean door seal with warm water and detergent
solution using a soft sponge when required.
WATER TROUGH
Open right hand side rack and remove trough.
Clean with warm, soapy water. Rinse thoroughly.
WATER TROUGH ELEMENT
When the element becomes limed / scaled,
remove water trough and clean. Replace water
trough and half fill with white vinegar or acetic
acid then fill to the normal level with water.
Switch unit on. Set humidity control to ‘8’ and run
for approximately 30 minutes. Remove trough
and clean element with damp cloth when cooled.
Wash out trough and refit.
This procedure is recommended to be done once
a week. Frequency of cleaning the element may
be increased or decreased depending on the lime
depositing on the element.
Revision 1/F3608
-12-
4.2 ROUTINE PROCEDURES
PROCEDURE INTERVAL
WET ELEMENT Remove scaling (refer section 4.1). As required
DOOR SEALS Inspect door seal on door inside for wear and tear. 6 months
DOOR HINGES Check for wear. 12 months
ELEMENTS Check that elements are operating. 12 months
Revision 1/F3608
-13-
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.