Moffat E89M-8 Service Manual

Page 1
E89M / MS PROOFER AND
HOLDING CABINET
SERVICE
MANUAL
Revision 1/F3608
October, 2003
Manual P/N MOME89
Page 2
CONTENTS
This manual is designed to take a more in depth look at the E89M / MS prover and holding cabinets for the purpose of making the unit more understandable to service people.
There are settings explained in this manual that should never require to be adjusted, but for completeness and those special cases where these settings are required to change, this manual gives a full explanation as to how, and what effects will result.
SECTION PAGE NO.
1. SPECIFICATIONS .............................................................................................................................. 5
2. INSTALLATION.................................................................................................................................. 8
3. OPERATION....................................................................................................................................... 9
3.1 Description of Controls
3.2 Explanation of Control System
4. MAINTENANCE ................................................................................................................................. 12
4.1 Cleaning
4.2 Routine Procedures
5. TROUBLE SHOOTING GUIDE .......................................................................................................... 14
6. SERVICE PROCEDURES .................................................................................................................. 16
6.1 Fault Diagnosis
6.2 Access
6.3 Replacement
6.4 Adjustment / Calibration
7. ELECTRICAL SCHEMATICS ............................................................................................................ 27
8. ELECTRICAL WIRING DIAGRAMS .................................................................................................. 29
9. SPARE PARTS .................................................................................................................................. 31
10. ACCESSORIES / OPTIONS............................................................................................................... 32
IMPORTANT: MAKING ALTERATIONS MAY VOID WARRANTIES AND APPROVALS.
Revision 1/F3608
-3-
Page 3
11. PARTS DIAGRAM.............................................................................................................................. 33
11.1 Main Assembly
11.2 Control Panel Assembly (E89M)
11.3 Control Panel Assembly (E89MS)
11.4 Door Assembly (E89M)
11.5 Door Assembly (E89MS)
12. SERVICE CONTACTS........................................................................................................................ 39
APPENDIX A. Auto Water Fill Kit Instructions ........................................................................................ 41
Revision 1/F3608
-4-
Page 4
MODEL: E89M
1. SPECIFICATIONS
710
(28”)
515
1
(20
/4”)
FRONT
710
(28”)
51.5
(2”)
68
(22/8”)
WATER ENTRY
ELECTRICAL ENTRY
355
(14”)
200
810
(32”)
(8”)
(45/8”) (24”)
SIDE
”)
2
/
1
900
(35
”)
8
/
5
66.5
(2
610117.5
PLAN
LEGEND
- Electrical connection entry point
- Water entry - 3/4” BSP (Autofill models only)
1
(
/2” ID Hose adapter supplied)
Dimensions shown in millimetres. Dimensions in inches shown in brackets.
Revision 1/F3608
-5-
Page 5
MODEL: E89MS
710
(28”) (32”)
WATER ENTRY
ELECTRICAL ENTRY
355
(14”)
(8”)
200
515
(201/4”)
FRONT
710
(28”)
51.5
(2”)
(45/8”)
68
(22/8”)
SIDE
810
610117.5
(24”)
66.5
”)
2
/
1
900
(35
”)
8
/
5
(2
PLAN
LEGEND
- Electrical connection entry point
- Water entry - 3/4” BSP (Autofill models only)
1
(
/2” ID Hose adapter supplied)
Dimensions shown in millimetres. Dimensions in inches shown in brackets.
Revision 1/F3608
-6-
Page 6
LOCATION
To ensure correct operation the following minimum installation clearances are to be adhered to:
Rear 0mm / 0” Left-hand side 0mm / 0” Right-hand side 25mm / 1”
Provision must be allowed for the door opening.
PROVER INTERNAL DIMENSIONS
E89M / MS
Width 460mm / 18” Height 675mm / 26 Depth 700mm / 27
5
5
/8” /8”
Prover Volume 0.22m³ / 7.8ft³
PROVER RACK/PAN SIZE CAPACITY
Width 460mm / 18” or 405mm / 16” Depth 660mm / 26”
RACK POSITIONS
Spacing 74mm / 3” No. of rack positions: 8
ELECTRICAL SUPPLY SPECIFICATION OPTIONS
100-120 Volts A.C. 60 Hz, 12.5 A, 1.5kW 208-220 Volts A.C. 50/60 Hz, 6.5A, 1.45kW 220-240 Volts A.C. 50/60 Hz, 7.1 A, 1.7kW
ELECTRICAL PLUG SPECIFICATION REQUIREMENTS
Australia 3-pin 250V 10A, AS/NZ 3112 Canada 3-pin 125V 15A, NEMA 5-15 New Zealand 3-pin 250V 10A, AS/NZ 3112 United Kingdom 3-pin 250V 13A fused, BS 1363A United States 3-pin 125V 15A, NEMA 5-15 Other Countries 3-pin 250V 10A minimum, type
to meet country standards
WATER SUPPLY CONNECTION
(Autofill Models Only)
Max Pressure 550 kPa / 5.5 bar / 80 psi Min Pressure 100 kPa / 1.0 bar / 15 psi
Revision 1/F3608
-7-
Page 7
2. INSTALLATION
WARNING: THIS APPLIANCE MUST BE GROUNDED.
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED OUT BY QUALIFIED PERSONS ONLY.
It is most important that the prover is installed correctly and that the operation is correct before use. Installation shall comply with local electrical, health and safety requirements.
BEFORE CONNECTION TO POWER SUPPLY
Unpack and check unit for damage and report any damage to the carrier and dealer. Report any deficiencies to your dealer. Check that the available power supply is correct to that shown on the rating plate located on the right-hand side panel.
100-120 Volts A.C. 60 Hz, 12.5 A, 1.5kW 208-220 Volts A.C, 50/60 Hz, 6.5A, 1.45kW 220-240 Volts A.C. 50/60 Hz, 7.1A, 1.7kW
LOCATION
To ensure correct operation the following minimum installation clearances are to be adhered to:
Rear 0mm / 0” Left-hand side 0mm / 0” Right-hand side 25mm / 1”
Provision must be allowed for the door opening.
ELECTRICAL CONNECTION
E89 models are supplied with pre-fitted cords. Ensure unit is fitted with correct cord and plug for the installation (refer specifications section).
Should changing of the cord be necessary, gain access to the electrical connection terminal block and strain relief clamp by removing the RH side panel.
WATER CONNECTION (AUTOFILL MODELS ONLY)
A connection elbow and sealing washer is supplied with this unit for direct connection of a ½” ID hose, and is recommended for easy installation and service.
Connect water supply - Max inlet pressure 550kPa / 80psi.
Turn on water supply to check for leaks.
DOUBLE STACKING UNITS
When it is desired to mount a Turbofan E32 convection oven on an E89, a double stacking kit must be used. Available from your dealer or Turbofan distributor (see Spare Parts). For stacking kit assembly instructions, refer Appendix B.
RACK WIDTH POSITIONS
The E89 prover has been designed to accept either 460mm (18”) or 405mm (16”) wide trays, 1/1 GN,
1
/2 /1 GN trays or USA steam pans.
The prover comes factory set for 460mm (18”) trays, a rack spacer kit (Part no. 025685) is required to change to 405mm (16”) trays, Gastronorm pans or USA steam pans.
RATING PLATE LOCATION
The rating plate for the E89 prover is located at the bottom left corner of the RH side panel.
L1 L2
Phase
RED
BROWN
BLACK
WARNING:
Revision 1/F3608
Neutral
BLACK
BLUE
WHITE
THIS APPLIANCE MUST
BE GROUNDED / EARTHED
Figure 2.1
Ground
GREEN
GREEN/YELLOW
Rating Plate
Figure 2.3
-8-
Page 8
3. OPERATION
NOTE: A full user’s operation manual is supplied with the product and can be used for further referencing
of installation, operation and service.
3.1 DESCRIPTION OF CONTROLS - E89 PROVER / HOLDING CABINETS
1. FUNCTION
OFF Unit is off.
PROOF Unit is in proofing mode. (Indicator
illuminates when switched to this position)
HOLD Unit is in holding mode. (Indicator illuminates when switched to this position)
2. THERMOSTAT
Temperature range 0 - 85°C (32 - 185°F).
Indicator illuminates when elements are cycling ON to maintain set temperature.
Controls the prover air temperature.
3. HUMIDITY CONTROL
1 to 5 Setting for butter based pastries (croissants, Danish pastries etc.)
5 to 8 Settings for yeast based breads and doughs.
Indicator illuminates when elements are cycling ON to maintain set temperature.
(Controls the cabinet humidity in PROOF mode only)
Manual Water Fill Models: Open the prover door. Fill the water trough at the filling spout, located at the front of the right hand side rack, to approximately 20mm / ¾” from the top of the trough. Remember to top up the water trough when the water level is below the halfway level in the trough and before the heating element is exposed.
Auto Water Fill Models: Check that the water trough is filling, and the heating element is well covered.
4. THERMOMETER
Indicates cabinet temperature. Dual Centigrade and Fahrenheit scale.
CONDENSATION CHANNEL
Below the door there is a condensation channel and removable water collection drawer for the purpose of collecting door condensation run-off.
1
2
3
4
89
P R
O
O
F
D
L
O
H
Revision 1/F3608
-9-
Page 9
3.2 EXPLANATION OF CONTROL SYSTEM
The E89M/MS Prover/Holding Cabinets feature operator controls and an electrical circuit for which a direct understanding of their operation is required before carrying out any service work or fault repair work. The control device functions and electrical circuit are explained as follows:
Function Switch
A rotary switch on the control panel of these models functions as the power On/Off switch of the unit by isolating the Line 1 phase supply. This switch is a 3 position, 4 pole, multi-function switch which in the Off position opens circuits all poles and isolates power from all control and heating systems. The switch should operate as illustrated below.
P1 – No function / not used. P2 – Additional air heating element. P3 – Humidity control thermostat. (Auto-fill models only - water solenoid, float switch, solenoid relay) P4 – Air heating thermostat, cabinet lights, air circulation fan motor and control panel power indicator.
P1
H
P2
P
P
P4
The air circulation fan, cabinet lights and control panel power indicator are On continuously on all E89 models when the function switch is in either of the PROOF or HOLD positions. The air circulation fan mounted at the top of the air delivery ducting ensures that the temperature and humidity throughout the cabinet is even by creating a low velocity air circulation system throughout the prover cabinet.
Proof Mode
In the ‘Proof’ position the function switch poles P1, P3 and P4 are closed, supplying power to the dry heat circuit, humidity circuit, cabinet lights and fan.
1
P1
D
L
O
2
F
O
O
R
3P3
R
W
4
OFF PROOF HOLD
H
P2
PROOF
P3 3
PWR
P4 4
1
P1
D
L
O
2
HOLD
P2
P
P3 3
PWR
P4 4
1
2
F
O
O
R
Figure 3.2.1
The proofing system controls air temperature and humidity levels by way of an air heating element and a water tank heating element.
The air heating element is positioned in the bottom of the air circulation ducting inside the cabinet and is directly controlled by the user-adjustable thermostat mounted to the control panel. The thermostat sensing bulb is mounted inside the cabinet to control the cabinet air temperature to the control panel setting. An indicator light on the control panel above this thermostat will illuminate when the thermostat has the air heating element operating and will cycle Off with the thermostat to indicate when the temperature reaches set point. The main thermostat is adjustable up to 85°C (185°F).
The humidity thermostat mounted on the control panel controls the water tank heating element, which in turn maintains the water temperature between 20°C (68°F) and 85°C (185°F). The evaporation of the water provides the cabinet humidity. The setting of the humidity thermostat (between 1 - 8) controls the rate of water evaporation and therefore the level of humidity in the cabinet.
An indicator light on the control panel above the humidity dial illuminates when the water tank element is On, and cycles Off when the thermostat switches the heating element Off to provide an indication of the humidity control. The sensing bulb of the humidity thermostat is mounted to the water tank heating element, which is immersed in the water tank. Should the water tank level drop below the heating element the humidity thermostat will cycle Off due to the sensing bulb reacting to the radiated heat off the heating element and will prevent the humidity water tank heating element burning out through excessive temperature.
Hold Mode
When the function switch is turned to the ‘Hold’ position the function switch pole P3 opens to turn off the humidity control circuit, and pole P2 closes to connect an additional air heating element to the air temperature thermostat circuit. In this mode the air temperature thermostat operates as it does in the proofing mode, however, in this case there is an additional air heating element switched On and Off to provide extra heating power in this mode. The additional air heating element is also mounted in the air circulation ducting.
E89M/MS Prover/Holding Cabinets are provided with a thermometer dial on the control panel to
Revision 1/F3608
-10-
Page 10
provide an indication of the cabinet temperature. The sensing bulb of this thermometer dial is mounted next to the sensing bulb of the main thermostat inside the cabinet.
Auto water fill (option)
E89 Auto-Water fill models provide for a mains cold water supply connection for automatic water tank filling and level control. Non Auto-Water fill models require the operator to manually fill the water tank and maintain the water tank level as the water evaporates through operation.
On Auto-Water fill models an electric solenoid valve, float switch and relay maintain the water level in the humidity tank. The float switch is mounted at the rear of the water tank, and when the water is below the full level it open circuits, removing power from the coil. When de­energised, the relay removes power from the humidity thermostat circuit (therefore switching off the humidity element), and switches power to the water solenoid. As the water level reaches the full level position the float switch contact will close, re-energising the water solenoid relay, thereby closing the water solenoid valve and providing power back to the humidity thermostat. Accordingly this system will automatically maintain a full water tank whenever the function switch is in the “PROOF” position and the mains water supply is turned on.
Ensuring that the function switch is in the Off position is necessary whenever removing the water tank for cleaning as when the water tank is removed the float switch drops and the water solenoid valve will open (if the unit is on). Therefore as a precaution the mains water supply should also be turned Off whenever removing the water tank.
Revision 1/F3608
-11-
Page 11
4. MAINTENANCE
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED OUT BY QUALIFIED PERSONS ONLY.
4.1 CLEANING
WARNING: ALWAYS TURN THE
POWER SUPPLY OFF BEFORE CLEANING.
IMPORTANT: THIS UNIT IS NOT
WATER PROOF. DO NOT USE A WATER JET SPRAY TO CLEAN INTERIOR OR EXTERIOR OF THIS UNIT.
CABINET
A good quality stainless steel cleaning compound is recommended for cleaning the inside and outside of the cabinet. Harsh abrasive cleaners may damage the surface.
SIDE RACKS
To remove, take hold of the centre rung and lift towards the prover top. To replace, hold horizontally, engage in holes and push down.
DOOR
Wash with warm water and detergent solution using a soft sponge in straight lines up and down the door.
Rinse with clean, warm water to remove detergent. Dry off.
Clean door seal with warm water and detergent solution using a soft sponge when required.
WATER TROUGH
Open right hand side rack and remove trough. Clean with warm, soapy water. Rinse thoroughly.
WATER TROUGH ELEMENT
When the element becomes limed / scaled, remove water trough and clean. Replace water trough and half fill with white vinegar or acetic acid then fill to the normal level with water. Switch unit on. Set humidity control to ‘8’ and run for approximately 30 minutes. Remove trough and clean element with damp cloth when cooled. Wash out trough and refit.
This procedure is recommended to be done once a week. Frequency of cleaning the element may be increased or decreased depending on the lime depositing on the element.
Revision 1/F3608
-12-
Page 12
4.2 ROUTINE PROCEDURES
PROCEDURE INTERVAL
WET ELEMENT Remove scaling (refer section 4.1). As required
DOOR SEALS Inspect door seal on door inside for wear and tear. 6 months
DOOR HINGES Check for wear. 12 months
ELEMENTS Check that elements are operating. 12 months
Revision 1/F3608
-13-
Page 13
5. TROUBLE SHOOTING
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED OUT BY QUALIFIED PERSONS ONLY.
FAULT POSSIBLE CAUSE REMEDY
THE UNIT DOES NOT OPERATE / START
FAN DOES NOT OPERATE Fan motor faulty.
PROVER CABINET LIGHT(S) DO NOT OPERATE
NO DRY HEAT Thermostat faulty.
The unit is not plugged into the wall socket.
The mains isolating switch on the wall, circuit breaker or fuses are “off” at the power board.
The power switch on the unit is off.
Incorrect electrical supply.
(Refer fault diagnosis 6.1.1)
Power / Function switch faulty.
(Refer fault diagnosis 6.1.1)
(Refer fault diagnosis 6.1.2)
Bulb blown. Replace bulb
(Refer fault diagnosis 6.1.3)
Element blown.
(Refer fault diagnosis 6.1.3)
Plug in.
Turn on.
Turn switch on. Indicator will illuminate.
Ensure electrical supply correct.
Replace.
(Refer service section 6.3.2)
Replace.
(Refer service section 6.3.9)
(Refer service section 6.3.8)
Replace.
(Refer service section 6.3.3)
Replace.
(Refer service section 6.3.6)
NO DRY HEAT TEMPERATURE CONTROL
NO HUMIDITY Unit is in “HOLD” mode.
NO HUMIDITY CONTROL Humidity thermostat faulty.
Thermostat faulty.
(Refer fault diagnosis 6.1.4)
No water in trough.
Humidity thermostat faulty.
(Refer fault diagnosis 6.1.5)
Power / Function switch faulty.
(Refer fault diagnosis 6.1.5)
Water tank element blown.
(Refer fault diagnosis 6.1.5)
(Refer fault diagnosis 6.1.6)
Replace.
(Refer service section 6.3.3)
Humidity only operates when unit is in “PROOF” mode.
Manual Fill: Fill trough with water. Auto fill: (refer fault: Auto-fill not filling)
Replace.
(Refer service section 6.3.4)
Replace.
(Refer service section 6.3.2)
Replace.
(Refer service section 6.3.6)
Replace. (Refer service section 6.3.4)
Revision 1/F3608
-14-
Page 14
FAULT POSSIBLE CAUSE REMEDY
SLOW RECOVERY Overloading of product.
Door opened unnecessarily.
Incorrect electrical supply. (Refer fault diagnosis 6.1.1)
Door seals deteriorated.
Fan motor faulty.
(Refer fault diagnosis 6.1.2)
Power / Function faulty (“HOLD” mode only)
(Refer fault diagnosis 6.1.1)
Element faulty (“HOLD” mode only)
(Refer fault diagnosis 6.1.3)
NO HEATING / HUMIDITY INDICATOR
DOOR DOES NOT CLOSE Tray in way of door.
Indicator faulty.
(Refer fault diagnosis 6.1.7)
Interference with door.
Hinges damaged.
Reduce batch size.
Do not open unnecessarily.
Check supply voltage is as per rating plate voltage.
Inspect and replace.
Replace.
(Refer service section 6.3.9)
Replace.
(Refer service section 6.3.2)
Replace. (Refer service section 6.3.6)
Replace.
(Refer service section 6.3.1)
Correctly position tray in rack.
Inspect and repair.
Replace. (Refer service section 6.3.13)
AUTOFILL WATER NOT FILLING (Autofill models only)
AUTOFILL WATER OVERFLOWING (Autofill models only)
Water supply not turned on.
Blockage in water supply.
Water connection filter blocked.
Water solenoid faulty.
(Refer fault diagnosis 6.1.9)
Water level float switch faulty. (Refer fault diagnosis 6.1.9)
Solenoid relay faulty. (Refer fault diagnosis 6.1.9)
Water level float switch faulty. (Refer fault diagnosis 6.1.9)
Solenoid relay faulty. (Refer fault diagnosis 6.1.9)
Water tank not fitted.
Solenoid valve dirty.
Turn water supply on.
Disconnect water supply and inspect.
Clean filter.
(Refer service section 6.3.17)
Replace. (Refer service section 6.3.16)
Replace.
(Refer service section 6.3.18)
Replace.
(Refer service section 6.3.15)
Replace.
(Refer service section 6.3.18)
Replace.
(Refer service section 6.3.15)
Fit water tank.
Clean solenoid valve.
Revision 1/F3608
-15-
Page 15
6. SERVICE PROCEDURES
WARNING: ENSURE POWER SUPPLY IS SWITCHED OFF BEFORE SERVICING.
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED OUT BY QUALIFIED PERSONS ONLY.
SECTION PAGE NO.
6.1 FAULT DIAGNOSIS ........................................................................................................................... 17
6.1.1 Unit Does Not Operate / Start.................................................................................................. 17
6.1.2 Fan Does Not Operate ............................................................................................................ 17
6.1.3 No Heat ................................................................................................................................... 17
6.1.4 No Dry Heat Temperature Control........................................................................................... 17
6.1.5 No Humidity ............................................................................................................................. 17
6.1.6 No Humidity Control ................................................................................................................ 18
6.1.7 No Heating / Humidity Indicator............................................................................................... 18
6.1.8 Autofill Not Filling or Overflowing (Autofill Models Only) ......................................................... 18
6.2 ACCESS ............................................................................................................................................. 19
6.2.1 Control Panel ........................................................................................................................... 19
6.2.2 Right Hand Side Panel ............................................................................................................ 19
6.2.3 Left Hand Side Panel............................................................................................................... 19
6.2.4 Control Panel (Rear)................................................................................................................ 19
6.3 REPLACEMENT................................................................................................................................. 20
6.3.1 Indicator Light .......................................................................................................................... 20
6.3.2 Power /Function Switch ........................................................................................................... 20
6.3.3 Thermostat .............................................................................................................................. 20
6.3.4 Humidity Thermostat ............................................................................................................... 21
6.3.5 Thermometer ........................................................................................................................... 21
6.3.6 Dry Element ............................................................................................................................. 22
6.3.7 Wet Element............................................................................................................................ 22
6.3.8 Light Bulb / Glass .................................................................................................................... 22
6.3.9 Fan ......................................................................................................................................... 23
6.3.10 Door Handle ............................................................................................................................ 23
6.3.11 Door Catch Magnet ................................................................................................................. 23
6.3.12 Door......................................................................................................................................... 23
6.3.13 Door Glass............................................................................................................................... 23
6.3.14 Door Pivot bushes ................................................................................................................... 24
6.3.15 Relay ....................................................................................................................................... 24
6.3.16 Water Solenoid - Autofill models only...................................................................................... 24
6.3.17 Water Solenoid Cleaning......................................................................................................... 25
6.3.18 Float Switch - Autofill models only........................................................................................... 25
6.4 ADJUSTMENT / CALIBRATION........................................................................................................ 26
6.4.1 Door Reversal.......................................................................................................................... 26
Revision 1/F3608
-16-
Page 16
6.1 FAULT DIAGNOSIS
6.1.1 UNIT DOES NOT OPERATE / START
Incorrect electrical supply
Check that the supply voltage across phase and neutral (L1 and L2) terminals of terminal block is correct as per the voltage stated on the unit’s electrical rating plate. If incorrect, check electrical connection of supply cord, and/or check electrical supply.
Power / Function switch on unit faulty
Ensure that power is isolated from the unit. Check for continuity through the switch terminals in each of the settings. The switch should operate as illustrated below. If not then the switch is faulty - replace.
P1
1
P1
P1
1
1
wiring. Check power at terminal 2. If there is no power then the thermostat is faulty - replace.
Alternatively the thermostat indicator light should illuminate when thermostat set to max.
Element blown
With thermostat on and heating check voltage across dry element terminals. If there is no voltage check wiring. If voltage is correct, element is faulty - replace.
To test element, disconnect terminals and check resistance across element.
Resistances;
208 - 240V models 72 ±3.6 110 - 120V models 20.5 ±1
6.1.4 NO DRY HEAT TEMPERATURE CONTROL
P2
P4
P
P
2
P2
F
O
O
R
3P3
P3 3
R
W
4
P4 4
OFF PROOF HOLD
D
L
O
H
D
L
O
H
PROOF
PWR
2
P2
P3 3
P4 4
HOLD
O
R
P
PWR
2
F
O
Figure 6.1.1
If checks are ok and the unit still does not operate, check the unit’s wiring and/or re-diagnose exact fault with unit and refer to trouble-shooting guide.
6.1.2 FAN DOES NOT OPERATE
Fan motor faulty
Check the supply voltage across motor terminals. If there is no voltage with function switch on then check the electrical connections of supply wiring.
If voltage is correct then isolate unit from power, then check the oven fan for free rotation. Remove any obstruction.
If fan is free to spin and the voltage supply is correct, then the motor is faulty—replace.
Thermostat faulty
With thermostat in off position (fully counter­clockwise), the heating indicator should be off. If not, then the thermostat is faulty - replace.
6.1.5 NO HUMIDITY
Humidity thermostat faulty
With cold proofer, set humidity to ‘8’. Check power to terminal 1 of bottom (humidity) thermostat. If there is no voltage then check wiring. Check power at terminal 2. If there is no power then the thermostat is faulty - replace.
Alternatively the humidity thermostat indicator light should illuminate when thermostat set to max.
Power / Function switch faulty
Ensure that power is isolated from the unit. Check for continuity through the switch terminals as illustrated below. If not then the switch is faulty - replace.
P1
P2
H
1
D
L
O
2
6.1.3 NO HEAT
Thermostat faulty
With cold prover, set thermostat to maximum position. Check power to terminal 1 of top thermostat. If there is no power then check
Revision 1/F3608
-17-
PROOF
P3 3
PWR
P4 4
PROOF
Figure 6.1.2
Page 17
Element blown
With humidity thermostat on and heating check voltage across wet element terminals. If there is no voltage check wiring. If voltage is correct, element is faulty - replace.
To test element, disconnect terminals and check resistance across element.
Resistances;
208 - 240V models 72 ±3.6 110 - 120V models 20.5 ±1
6.1.6 NO HUMIDITY CONTROL
Humidity thermostat faulty
Switch the prover on and set the humidity to ‘4’. Check that the humidity thermostat cycles on / off, and using a suitable probe measure the temperature of the water in the trough. The water temperature should be 50°C/120°F ± 10%. If the temperature continues to rise above this then the humidity thermostat is faulty - replace.
Water level float switch faulty
To check correct operation of float switch remove the float switch wire connections from terminal 8 and terminal 5 on relay. With full water tank (float switch in raised position) float switch should be closed circuit. With empty water tank (float switch in lower position) float switch should be open circuit. If not, float switch is faulty— replace.
Solenoid relay faulty
E89 auto-fill models are fitted with a 2 pole change over relay, with its coil controlled by the float switch located in the water through / tank. When the water level is below the full position the coil is not energised, allowing the relay to supply power to the water solenoid. In this position the relay should have no power at terminals 3,4 and 8, but power at terminals 1,2,5, and 6,
2 4
7
6
6.1.7 NO HEATING / HUMIDITY INDICATOR
Indicator faulty
Check voltage across indicator terminals with controls on and appropriate thermostat turned on fully. If the voltage is correct and indicator is not illuminated then the indicator is faulty - replace. If there is no voltage then check wiring.
6.1.8 AUTOFILL NOT FILLING OR OVER FLOWING (AUTOFILL MODELS ONLY)
Water solenoid faulty
Empty water tank so float switch is in lowest position. With power ON check voltage across water solenoid coil terminals. If voltage is correct (refer electrical rating plate) but solenoid is not operating, disconnect electrical supply and remove wire connections from solenoid. Check solenoid coil windings resistance.
Correct coil resistance: 208 - 240 volt models 3650 110 - 120 volt models 1100
NOTE:
If open circuit/high resistance, then the
coil is faulty– replace.
If coil is correct, rewire and listen for audible solenoid click when power is supplied. If solenoid can be heard functioning and water supply is turned on but no water is entering tank, remove water solenoid and fittings and check for blockages.
13
SOLENOID RELAY - TANK FILLING
5
8
Figure 6.1.3
When the water level reaches the full position the float switch supply’s power to the relay coil, which in turn cuts power to the water solenoid and supply’s power to the humidity tank. In this position the relay should have no power at terminals 1 and 2, but power at terminals 3,4,5,6, and 8.
2 4
13
SOLENOID RELAY - TANK FULL
7
6
5
8
Figure 6.1.4
Revision 1/F3608
-18-
Page 18
6.2 ACCESS
6.2.1 CONTROL PANEL
1) Remove two screws at bottom of control panel.
6.2.4 CONTROL PANEL—REAR
Power Indicator
Two Screws
Figure 6.2.1
2) Control panel can now be lowered and hinged on lower bracket.
3) When closing control panel ensure no wires are trapped.
6.2.2 RH SIDE PANEL
1) Undo the four screws holding the panel in place.
2) Pull out at bottom, lower to remove.
Four
Screws
Power / Function Switch
Dry Heating Indicator
Dry Thermostat
Wet Heating Indicator
Wet Thermostat
Figure 6.2.2
6.2.3 LH SIDE PANEL
1) Undo the four screws holding the panel in place.
2) Pull out at bottom, lower to remove.
Four Screws
Figure 6.2.3
Revision 1/F3608
Thermometer
Figure 6.2.4
-19-
Page 19
6.3 REPLACEMENT
6.3.1 INDICATOR LIGHT
1) With control panel open (refer 6.2.1)
remove the wires from the back of the neon.
Neon Wires
Figure 6.3.1
2) From back push neon through front of panel
rotating clockwise.
3) Push new neon in from front of panel, and
reconnect wires.
6.3.2 POWER / FUNCTION SWITCH
1) Remove knob off front of power switch.
2) Open control panel (refer 6.2.1).
3) Remove two screws, remove switch.
Two Screws
Thermostat Phial
Support
Bracket Screw
Figure 6.3.3
4) Withdraw old thermostat phial through hole under bracket in side of proofer.
5) Remove sleeving from old thermostat and fit to replacement thermostat.
Fibreglass Sleeve
Thermostat Phial
Figure 6.3.4
6) Undo two screws securing thermostat to control panel and remove.
Figure 6.3.2
4) Mount new switch and transfer wires from the old switch.
6.3.3 THERMOSTAT
1) Pull knob off front of thermostat.
2) Open control panel (refer 6.2.1).
3) With door open, remove right hand side rack.
Undo thermostat support bracket screw and remove bracket.
Revision 1/F3608
Two Screws
Figure 6.3.5
7) Attach new thermostat to control panel and transfer wires to new thermostat.
8) Re-assemble in reverse order.
9) Ensure hole in prover wall through which the thermostat capillary passes is re-sealed with RTV silicone sealant.
-20-
Page 20
6.3.4 HUMIDITY THERMOSTAT
1) Pull knob off front of thermostat
2) Open control panel (refer 6.2.1).
3) With door open, remove right hand side rack and water trough. Undo humidity thermostat support bracket screw and remove bracket. Remove clip holding capillary to element.
7) Attach new thermostat to control panel, and transfer wires to new thermostat.
8) Re-assemble in reverse order.
9) Ensure hole in prover wall through which the thermostat capillary passes is re-sealed with RTV silicone sealant.
Capillary
Clip
Humidity
Support
Bracket
Screw
Figure 6.3.6
4) Remove thermostat support bracket in side wall, withdraw old humidity thermostat phial through hole under the bracket.
5) Remove plastic sleeving from old thermostat and fit to replacement thermostat.
Plastic Sleeve
Thermostat Phial
6.3.5 THERMOMETER
1) Open control panel (refer 6.2.1)
2) With door open, remove right hand side rack (Lift off supports, and remove).
3) Undo thermometer support bracket screw and remove bracket.
Support
Bracket Screw
Figure 6.3.9
4) Withdraw old thermometer phial through hole under bracket in side of cabinet.
5) Undo 2 nuts securing thermometer to control panel and remove.
Figure 6.3.7
6) Undo two screws securing thermostat to control panel and remove.
Two Screws
Figure 6.3.8
Revision 1/F3608
Two Nuts
Figure 6.3.10
6) Attach new thermometer to control panel.
7) Insert new thermometer phial through cabinet side and re-attach bracket.
8) Re-assemble in reverse order.
9) Ensure hole in prover wall through which the thermostat capillary passes is re-sealed with RTV silicone sealant.
-21-
Page 21
6.3.6 DRY ELEMENT
1) Remove RH side panel (refer 6.2.2), remove wires from element terminals, noting position.
2) With door open, remove right hand side rack.
Element
cover
Screws
Figure 6.3.11
3) Undo the two screws holding the element cover and remove cover.
Capillary
Clip
Support
Bracket
Screw
Figure 6.3.13
5) Unscrew the element from RH side (outside) of proofer.
Element
Screws
Proofing Element Terminals
Hold Element Terminals
Figure 6.3.12
4) Unscrew the element from RH side (outside) of prover. Pull element carefully to remove from inside of proofer.
5) Replace and re-assemble in reverse order.
Dry Element Ratings
208 - 240 Volt Models 72 ±3.6 .
110 - 120 Volt Models 20.5 ±1
Figure 6.3.14
6) Pull element carefully into prover to remove.
7) Replace and reassemble in reverse order.
Wet Element Ratings
208 - 240 Volt Models 72 ±3.6 .
110 - 120 Volt Models 20.5 ±1
6.3.8 LIGHT BULB / GLASS
1) Open the prover door.
2) Pull off lamp cover.
Lamp Covers
6.3.7 WET ELEMENT
1) Remove RH side panel (refer 6.2.2), and remove wires from (rear) element terminals.
2) With door open, remove right hand side rack and water tank.
3) Remove thermostat support bracket screw (on element) and remove bracket.
4) Remove clip securing thermostat capillary to element.
Revision 1/F3608
Figure 6.3.15
3) Unscrew bulb out of fitting.
4) Screw in replacement bulb.
5) Refit lamp cover.
-22-
Page 22
6.3.9 FAN
6.3.11 DOOR CATCH MAGNET
1) Remove RH side panel (refer 6.2.2)
2) Remove wires from fan motor, noting their
positions.
Fan
Fan Motor Terminals
Motor Bracket Screw
Figure 6.3.16
3) Remove fan motor bracket, one screw.
4) Slide fan assembly out of proofer.
5) Replace and re-assemble in reverse order.
6.3.10 DOOR HANDLE
1) Open prover door.
2) Remove two screws (E89M) or four screws
(E89MS), remove handle.
1) Open prover door.
2) Unscrew two screws securing magnet to door.
3) Replace magnet catch and re-assemble in reverse order.
Door
Magnet
Two Screws
Figure 6.3.19
6.3.12 DOOR
1) Remove two screws from top of door holding hinge to door.
Hinge Pivot (Two Screws)
Hinge Body
Two Screws (E89M)
Figure 6.3.17
Two Screws top and bottom (E89MS)
Figure 6.3.18
3) Replace and re-assemble in reverse order.
Revision 1/F3608
Figure 6.3.20
2) Slide door out at top and remove hinge pivot.
3) Lift door vertically off bottom hinge body (if sticky loosen bottom hinge body two screws).
4) Remove bottom hinge pivot from door.
5) Fit hinge pivots (top and bottom) to new door.
6) Re-assemble in reverse order.
6.3.13 DOOR GLASS
1) Remove door as per steps one to three of section 6.3.12
2) Lay door face down on bench and remove door seal.
-23-
Page 23
3) Remove door inner (14 screws) and remove glass.
4) Clean glass and replace in reverse order. Ensure silicone seals have not been displaced from door outer and door inner.
Door Outer
Door Inner
Door Glass
14 Screws
Door Seal
Figure 6.3.21
5) Reassemble and refit door in reverse order.
6.3.14 DOOR PIVOT BUSHES
1) Remove door as per steps one to three of section 6.3.12.
2) Remove two screws (top and bottom) holding hinge body to proofer.
6.3.15 RELAY - AUTOFILL MODELS ONLY
1) Remove RH side panel (refer 6.2.2).
2) Remove two screws securing relay to bracket.
Two Screws
Figure 6.3.24
3) Secure new relay to bracket.
4) Transfer wires from old relay to new relay.
5) Replace RH side panel.
6.3.16 WATER SOLENOID - AUTOFILL MODELS ONLY
1) Remove RH side panel (refer 6.2.2).
2) Remove wires from solenoid, noting their
positions.
Two Screws
Figure 6.3.22
3) Door pivot bush can now be removed and replaced.
Door Pivot Bush
Figure 6.3.23
Solenoid Wires
Two screws
Brass Fitting
Figure 6.3.25
3) Remove brass fitting from solenoid.
4) Remove two screws securing solenoid to bracket, and withdraw solenoid.
5) Secure new solenoid with screws, and re-assemble in reverse order.
4) Re-assemble in reverse order.
Revision 1/F3608
-24-
Page 24
6.3.17 WATER SOLENOID CLEANING
1) Disconnect water supply from the water solenoid.
2) Remove the sieve from the water valve assembly by pulling firmly away from the assembly with a pair of pliers.
Float Switch
Sleeve
Float Switch
Nut
Float Switch
Figure 6.3.28
Sieve
Figure 6.3.26
3) Clean the sieve, removing all dirt and grime.
4) Replace the sieve and reconnect the water supply.
6.3.18 FLOAT SWITCH - AUTOFILL
MODELS ONLY
1) Remove RH side panel (refer 6.2.2).
2) Remove float switch wires from relay, noting their positions.
3) Remove brass fitting from rear of float switch.
4) Remove RH side rack and water trough from inside proofer.
Two Nuts
8) Remove the float switch from the bracket, replace, and reassemble in reverse order.
NOTE:
Ensure float switch bracket is RTV
silicone sealed to prevent steam leakage.
Brass Fitting
Figure 6.3.27
5) Undo two nuts from outside cabinet, and two screws inside cabinet securing float switch bracket to proofer.
6) Remove float switch assembly from proofer.
NOTE:
The float switch bracket has been silicone sealed, so it may therefore be necessary to cut around the bracket with a sharp knife to assist with removal. Clean off all remaining silicone.
7) Remove the float switch sleeve, and undo the nut securing the float switch to the bracket.
Revision 1/F3608
-25-
Page 25
6.4 ADJUSTMENT / CALIBRATION
6.4.1 DOOR REVERSAL
1) Whilst supporting door remove bottom hinge body (two screws) and remove door.
Two Screws
Hinge Body
Figure 6.4.1
2) Remove top hinge body (two screws).
3) Remove four cover screws covering alternate hinge holes. Refit cover screws on opposite side.
When changing to LH hinged door.
Remove magnet plate and transfer to
opposite side.
Important: Redundant plate holes in LH side
wall must be filled to stop steam ingress into wall cavity.
6) Fit bottom hinge body to top on opposite side, centre hinge on slots.
7) Whilst holding door in place fit remaining hinge body to bottom, securing door in position.
8) Remove door handle (E89M only) (refer
6.3.10) and refit in the higher setting, using the extra screw position.
9) Ensure door seal is removed and refitted with join at bottom, centred over middle screw head when closed.
10) Refit LH side panel.
Cover Screws
Figure 6.4.2
4) Remove LH side panel (refer 6.2.3).
5) When changing to RH hinged door.
Remove LH magnet plate cover screws and
clips from inside LH wall (Do not fit cover screws to old magnet position).
Transfer door magnet plate to opposite side.
Magnet Cover Screws
Magnet Plate
Figure 6.4.3
Revision 1/F3608
-26-
Page 26
7. ELECTRICAL CIRCUIT SCHEMATIC
7.1 E89 Manual Water Fill Holding / Prover Cabinet
LIGHT
LIGHT
2x 15W 110V
2x 25W 240V
FAN
POWER
PILOT
LIGHT
HUMIDITY
ELEMENT
600W 110V
2
1
THERMOSTAT
HUMIDITY
PILOT
LIGHT
800W 240V
600W 110V
800W 240V
DRY
2
1
4
2
F
O
O
O
H
P2P4P3
3
R
R
W
P
P
OFF
4
P4
34
3
P3P2
21
2
1
P1
FUNCTION SWITCH OPERA TION
PROOF
HOLD
4
3
21
P2P1 P3 P4
P2P1 P3 P4
1
D
L
FUNCTION SWITCH
P1
THERMOSTAT
ELEMENT
HOLD
600W 110V
800W 240V
ELEMENT
GROUND
Revision 1/F3608
-27-
Page 27
7.2 E89A Auto Water Fill Prover / Holding Cabinet
7
2 4 6
N/C
FLOAT
8
SWITCH
5
1 3
RELAY
WATER
SOLENOID
LIGHT
LIGHT
2x 15W 110V
2x 25W 240V
POWER
PILOT
LIGHT
2
1
1
THERMOSTAT
HUMIDITY
PILOT
LIGHT
2
THERMOSTAT
HUMIDITY
DRY
FAN
ELEMENT
ELEMENT
800W 240V
600W 110V
800W 240V
600W 110V
OFF
P4
34
P3P2
21
P1
HOLD
P2P1 P3 P4
4
3
2
1
FUNCTION SWITCH OPERA TION
Revision 1/F3608
1
P1
2
F
O
D
L
O
O
R
H
P2
PROOF
4
3
21
P2P1 P3 P4
FUNCTION SWITCH
3
P
P3
4
800W 240V
600W 110V
HOLD
ELEMENT
R
W
P
P4
GROUND
-28-
Page 28
8. ELECTRICAL WIRING DIAGRAM
8.1 E89 Manual Water Fill
600W 110V
600W 110V
800W 240V
800W 240V
600W 110V
800W 240V
26
FAN MOTOR
32
25
WET
ELEMENT
WIRE MARKING
"VIVID" PEN
11
27
28
HOLD
ELEMENT
7
29
31
DRY
ELEMENT
EARTH
POWER SUPPLY CORD
6
35
30
26
25
27
24
32
LIGHT
282329
16
33
34
LNE
LIGHT
POWER
INDICATOR
3
2
2
1
P2
P1
SWITCH
FUNCTION
1
Revision 1/F3608
25W 240V
LIGHTS
15W 110V
14
TEMP
INDICATOR
15
HUMIDITY
INDICATOR
1
MAINS
BLOCK
TERMINAL
17
5
7
18
8
3
4
P3
P4
4
6
2
DRY
3
23
1
(0-85°C)
THERMOSTAT
WET
10
(30-85°C)
THERMOSTAT
13
11
2
1
EARTH
18
12
4
-29-
Page 29
8.2 E89A Auto Water Fill
800W 240V
800W 240V
600W 110V
2626
FAN MOTOR
WET
ELEMENT
600W 110V
HOLD
ELEMENT
800W 240V
600W 110V
DRY
ELEMENT
32
WIRE MARKING
"VIVID" PEN
27
11
28
7
29
6
31
EARTH
POWER SUPPLY CORD
35
E
30
25 25
27
24
32
LIGHT
28
29
23
33
16
34
L N
LIGHT
25W 240V
LIGHTS
15W 110V
22
14
POWER
INDICATOR
TEMP
INDICATOR
15
HUMIDITY
INDICATOR
1
MAINS
BLOCK
TERMINAL
17
5
7
3
2
2
1
P2
P1
SWITCH
FUNCTION
1
18
8
4
3
P3
P4
4
6
2
DRY
THERMOSTAT
3
23
1
(0-85°C)
WET
THERMOSTAT
10
(30-85°C)
13
12
4
11
2
1
9
WIRE MAKING
"VIVID" PEN
EARTH
7
8
18
9
21
20
5
6
3
4
1
2
RELAY
19
19
Revision 1/F3608
-30-
WATER
22
SOLENOID
FLOAT SWITCH
Page 30
9. SPARE PARTS
REPLACEMENT PARTS LIST
CONTROLS
022789 Switch - Function 020823 Knob - Function 022787 Thermostat (Temperature) 024527 Thermostat (Humidity) 020823 Knob - Temperature Thermostat 021472 Knob - Humidity Thermostat 020849 Neon Indicator (240V) 023857 Neon Indicator (110V) 022788 Thermometer (Dual °C & °F)
AUTO FILL OPTION
020851 Solenoid Valve (240V) 021617 Solenoid Valve (110V) 021534 Relay (240V) 021535 Relay (110V) 022250 Float Switch
MOTOR & ELEMENTS
013998 Fan / Motor (240V) 013999 Fan / Motor (110V) 014001 Dry Element - 800W (240V) 015759 Dry Element - 600W (110V) 015224 Wet Element - 800W (240V) 015320 Wet Element - 600W (110V)
DOOR
SA1686 Door Assembly (E89M) SA1687 Door Assembly (E89MS) 021468 Handle (E89M) 025519 Handle (E89MS) 020082 Hinge Top Assembly (Assembled with bush) 020083 Hinge Bottom Assembly (Assembled with bush) 017905 Hinge Bush 018947 Magnetic Catch 025988 Door Seal
RACKS
025604 Rack RH 025608 Rack LH 025685 Rack Spacer Kit
Revision 1/F3608
-31-
Page 31
11.1 MAIN ASSEMBLY
AUTO-FILL
UNITS ONLY
33
32
11. PARTS DIAGRAMS
38
37
36
17
31
30
18
29
28
19
22
20
34
24
35
25
27
26
23
21
16
15
14
13
12
11
Revision 1/F3608
9
10
7
8
6
5
3
2
1
4
-33-
Page 32
Pos Part No. Description
1 - - - - - - DOOR ASSEMBLY (REFER SECTION 11.4 & 11.5) 2 025598 DOOR SEAL 3 020082 HINGE TOP (ASSEMBLED WITH BUSH) 4 020083 HINGE BOTTOM (ASSEMBLED WITH BUSH) 017905 HINGE BUSH 5 025609 RACK SPACER (OPTIONAL EXTRA) 025685 RACK SPACER KIT 6 025608 LH RACK WA 7 025604 RH RACK WA 8 - - - - - - CONTROL PANEL ASSEMBLY (REFER SECTION 11.2 & 11.3) 9 025566 HANGER STUD 10 022758 CATCH PLATE 11 025732 CONDENSATE DRAWER 12 025601 RACK STANDOFF 13 013890 CASTOR - SWIVEL 14 014001 DRY ELEMENT - 800W (240V) 015759 DRY ELEMENT - 600W (110V) 15 013885 CASTOR - RIGID 16 021342 LAMP HOLDER (c/w 25W 240V BULB) 014218 BULB 24W (240V) 014219 BULB 15W (115V) 17 025575 SIDE PANEL 18 025567 WATER TANK 19 012271 CLAMP BOTTOM 012275 CLAMP TOP 20 015224 WET ELEMENT - 800W (240V) 015230 WET ELEMENT - 600W (110V) 21 019238 SNAP BUSH 19mm 22 025573 TERMINAL BLOCK PANEL 23 013586 TERMINAL BLOCK 24 002441 INSULATOR 25 002138 CABLE CLAMP 26 025580 FAN MOTOR BRACKET 27 013998 MOTOR - (240V) 013999 MOTOR - (110V)
Auto-fill units only
28 022097 SENSOR BRACKET 29 022252 FLOAT SWITCH SLEEVE 30 022253 ADAPTOR & LOCKNUT 31 022998 REDUCING SOCKET 3/8” x 1/8” 32 025574 WATER TUBE 33 020851 WATER SOLENOID - (240V) 021617 WATER SOLENOID - (110V) 34 022250 FLOAT SWITCH 35 021534 RELAY - (240V) 021535 RELAY - (110V) 36 020869 CONNECTOR 3/8”F x 1/4” COMPRESSION 37 024702 WATER SOLENOID BRACKET 38 021619 REAR SERVICE PANEL TOP
Revision 1/F3608
-34-
Page 33
11.2 E89M CONTROL PANEL ASSEMBLY
1
5
6
6
2
3
4
7
8
Pos Part No. Description
1 004995 Control panel (Blue Seal) 005002 Control panel (Bakbar) 2 022789 Selector switch 3 022787 Thermostat 0-85°C (Dry) 4 024527 Thermostat 30-85°C (Wet) 5 020849 Pilot light (240V) 6 020823 Knob 7 021472 Knob (Humidity) 8 022788 Thermometer 9 024694 Control panel hook
9
Revision 1/F3608
-35-
Page 34
11.3 E89MS CONTROL PANEL ASSEMBLY
1
2
6
7
7
8
3
4
5
9
Pos Part No. Description
1 025582 Control panel 2 025585 Overlay °C (Bakbar) 025586 Overlay °C (Blue Seal) 025584 Overlay °F (Moffat) 3 022789 Selector switch 4 022787 Thermostat 0-85°C (Dry) 5 024527 Thermostat 30-85°C (Wet) 6 023857 Pilot light (110V) 020849 Pilot light (240V) 7 020823 Knob 8 021472 Knob (Humidity) 9 022788 Thermometer 10 024694 Control panel hook
10
Revision 1/F3608
-36-
Page 35
11.4 E89M DOOR ASSEMBLY
2
3
1
4
5
6
7
8
9
10
Pos Part No. Description
1 020082 HINGE TOP ASSEMBLY 2 025603 DOOR HANDLE BRACKET 3 021468 DOOR HANDLE 4 025597 DOOR OUTER POWDER COATED 5 090202 DOOR OUTER SEAL - 2.02m 6 025599 DOOR GLASS 7 020083 HINGE BOTTOM ASSEMBLY 8 025593 DOOR INNER FRAME 9 018947 MAGNETIC CATCH (INNER) 10 025600 MAGNET MOUNTING PLATE 11 090203 DOOR INNER FRAME SEAL - 2.00m 12 025598 DOOR SEAL
11
12
Revision 1/F3608
-37-
Page 36
11.5 E89MS DOOR ASSEMBLY
2
1
3
4
5
6
7
8
9
10
Pos Part No. Description
1 025519 DOOR HANDLE 2 020082 HINGE TOP ASSEMBLY 3 025588 DOOR OUTER 4 090202 DOOR OUTER SEAL - 2.02m 5 025599 DOOR GLASS 6 025593 DOOR INNER FRAME 7 020083 HINGE BOTTOM ASSEMBLY 8 018947 MAGNETIC CATCH (INNER) 9 025600 MAGNET MOUNTING PLATE 10 090203 DOOR INNER FRAME SEAL - 2.00m 11 025598 DOOR SEAL
11
Revision 1/F3608
-38-
Page 37
11. SERVICE CONTACTS
AUSTRALIA
VICTORIA - MOFFAT PTY HEAD OFFICE AND MAIN WAREHOUSE 740 Springvale Road Tel (03) 9518 3888 Mulgrave VIC 3170 Fax (03) 9518 3838 Spare Parts Department Free Call 1800 337 963 Fax (03) 9518 3895
NEW SOUTH WALES - MOFFAT PTY Unit 8/142 James Ruse Drive Rosehill NSW 2142 Spare Parts Free Call 1800 337 963 Fax (03) 9518 3895
QUEENSLAND - MOFFAT PTY 30 Prosperity Place Geebung QLD 4034 Spare Parts Free Call 1800 337 963 Fax (03) 9518 3895
SOUTH AUSTRALIA - MOFFAT PTY 28 Greenhill Rd Tel (08) 8274 2116 Wayville SA 5034 Spare Parts Free Call 1800 337 963
WESTERN AUSTRALIA - MOFFAT PTY PO Box 689 Tel (08) 9305 8855 Joondalup Business Centre WA 6027 Spare Parts Free Call 1800 337 963
NATIONAL COVERAGE FOR 24 HOUR SERVICE OR MAINTENANCE DIAL
FREE CALL 1800 622 216 (AUSTRALIA ONLY)
CANADA
Lessard Agencies Limited Tel (416) 766 2764 PO Box 97 Fax (416) 760 0394 Stn “D” Free Call 1 888 537 7273 Toronto, ONT M6P 3J5
NEW ZEALAND
CHRISTCHURCH - MOFFAT LTD 16 Osborne St Free Call 0800 Moffat PO Box 10-001 (0800 663 328) Christchurch Spare Parts Tel (03) 389 1007 Fax (03) 389 1276
AUCKLAND - MOFFAT LTD 4 Waipuna Road Tel (09) 570 6630 Mt Wellington Fax (09) 570 0099 Auckland Spare Parts Free Call 0800 Moffat (0800 663 328)
Revision 1/F3608
-39-
Page 38
UNITED KINGDOM
BLUESEAL LTD Units 6-7 Mount St Tel 0121-327 5575 Business Park Fax 0121-327 9711 Birmingham B7 5QU England
UNITED STATES OF AMERICA
MOFFAT INC. 3765 Champion Blvd Tel 1-800 551 8795 P.O. Box 4129 Fax 336 661 9546 Winston-Salem NC27115
NATIONAL COVERAGE FOR SERVICE OR MAINTENANCE DIAL
FREE CALL 1800 551 8795 (USA ONLY)
Revision 1/F3608
-40-
Page 39
APPENDIX A. AUTOFILL KIT
WARNING: ENSURE POWER SUPPLY IS SWITCHED OFF BEFORE COMMENCING.
To convert a manual fill E89 prover to an auto-fill model, upgrade kit #025683 (240V) or #025752 (110V) needs to be installed as follows.
A. PROVER PREPARATION
1) Remove RH side panel (four screws), pull out at bottom and lower to remove.
2) Remove water inlet blanking plate from rear of unit (four screws). (H).
3) Open RH side rack and remove water trough.
4) Remove blanking plate from inside prover (Two bolts). (A). Note: plate with a sharp knife to assist with removal. Clean off all remaining silicone.
Blanking plate has been silicone sealed, therefore it maybe necessary to cut around the blanking
B
A B
E
C
D
F
G H
EXTERNAL VIEW INTERNAL VIEW
B. KIT INSTALLATION
1) Install the float switch bracket and assembly to inside of prover (B). Place a bead of RTV silicon sealant around back face of float switch bracket before securing to liner to ensure prover is sealed.
2) Fit water solenoid and mounting bracket (F) to rear panel as shown (two screws).
3) Fit 1/4” copper tube (C) to outlet tube (B) and water solenoid (F) tighten all fittings.
4) Fit relay (D) to terminal block panel (two screws).
5) Connect wiring as per wiring diagram provided (refer overleaf).
6) Fit new rear service panel (G) to rear of prover.
7) Affix max water pressure label (E) to rear panel above water inlet.
8) Connect cold water supply (1/2” ID hose) to water connection elbow. Ensure leak free connection. Maximum water pressure is 550 kPa (80psi).
9) Fit elbow to water solenoid, ensure supplied washer is used. Turn water supply on and check for leaks, no water should be flowing into trough.
C. RE-COMMISSIONING
1) Re-fit RH side panel (four screws)
2) Replace water trough.
3) Turn the power on, check that water trough fills, and stops filling approximately 20mm from the top of the tank. (Note: Humidity element will not heat until tank is filled to correct level).
4) Turn power supply off, empty water trough and repeat step 3 above.
5) Close RH side rack.
Revision 1/F3608
-41-
Page 40
WIRING DIAGRAM - AUTOFILL KIT
Wiring changes in bold.
800W 240V
800W 240V
600W 110V
2626
FAN MOTOR
WET
ELEMENT
600W 110V
HOLD
ELEMENT
800W 240V
600W 110V
DRY
ELEMENT
32
WIRE MARKING
"VIVID" PEN
11
27
28
7
29
6
31
EARTH
POWER SUPPLY CORD
35
E
30
25 25
27
24
32
LIGHT
28
29
23
33
16
34
L N
LIGHT
25W 240V
LIGHTS
15W 110V
22
14
POWER
INDICATOR
TEMP
INDICATOR
15
HUMIDITY
INDICATOR
1
MAINS
BLOCK
TERMINAL
17
5
7
3
2
1
P1
SWITCH
FUNCTION
1
18
8
2
3
4
P2
P3
P4
4
6
2
DRY
THERMOSTAT
3
23
1
(0-85°C)
WET
(30-85°C)
THERMOSTAT
13
12
4
11
10
2
1
9
WIRE MAKING
"VIVID" PEN
EARTH
7
8
18
21
20
22
5
6
9
3
4
1
2
RELAY
19
19
WATER
SOLENOID
FLOAT SWITCH
Revision 1/F3608
-42-
Loading...