This manual is designed to take a more in depth look at the E89M / MS prover and holding cabinets for the
purpose of making the unit more understandable to service people.
There are settings explained in this manual that should never require to be adjusted, but for
completeness and those special cases where these settings are required to change, this manual gives a
full explanation as to how, and what effects will result.
100-120 Volts A.C. 60 Hz, 12.5 A, 1.5kW
208-220 Volts A.C. 50/60 Hz, 6.5A, 1.45kW
220-240 Volts A.C. 50/60 Hz, 7.1 A, 1.7kW
ELECTRICAL PLUG SPECIFICATION
REQUIREMENTS
Australia 3-pin 250V 10A, AS/NZ 3112
Canada 3-pin 125V 15A, NEMA 5-15
New Zealand 3-pin 250V 10A, AS/NZ 3112
United Kingdom 3-pin 250V 13A fused, BS 1363A
United States 3-pin 125V 15A, NEMA 5-15
Other Countries 3-pin 250V 10A minimum, type
to meet country standards
WATER SUPPLY CONNECTION
(Autofill Models Only)
Max Pressure 550 kPa / 5.5 bar / 80 psi
Min Pressure 100 kPa / 1.0 bar / 15 psi
Revision 1/F3608
-7-
Page 7
2. INSTALLATION
WARNING: THIS APPLIANCE MUST BE GROUNDED.
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED OUT BY
QUALIFIED PERSONS ONLY.
It is most important that the prover is installed
correctly and that the operation is correct before
use. Installation shall comply with local electrical,
health and safety requirements.
BEFORE CONNECTION TO POWER SUPPLY
Unpack and check unit for damage and report
any damage to the carrier and dealer. Report
any deficiencies to your dealer. Check that the
available power supply is correct to that shown on
the rating plate located on the right-hand side
panel.
100-120 Volts A.C. 60 Hz, 12.5 A, 1.5kW
208-220 Volts A.C, 50/60 Hz, 6.5A, 1.45kW
220-240 Volts A.C. 50/60 Hz, 7.1A, 1.7kW
LOCATION
To ensure correct operation the following
minimum installation clearances are to be
adhered to:
Rear 0mm / 0”
Left-hand side 0mm / 0”
Right-hand side 25mm / 1”
Provision must be allowed for the door opening.
ELECTRICAL CONNECTION
E89 models are supplied with pre-fitted cords.
Ensure unit is fitted with correct cord and plug for
the installation (refer specifications section).
Should changing of the cord be necessary, gain
access to the electrical connection terminal block
and strain relief clamp by removing the RH side
panel.
WATER CONNECTION (AUTOFILL MODELS
ONLY)
A connection elbow and sealing washer is
supplied with this unit for direct connection of a
½” ID hose, and is recommended for easy
installation and service.
Connect water supply - Max inlet pressure
550kPa / 80psi.
Turn on water supply to check for leaks.
DOUBLE STACKING UNITS
When it is desired to mount a Turbofan E32
convection oven on an E89, a double stacking kit
must be used. Available from your dealer or
Turbofan distributor (see Spare Parts). For
stacking kit assembly instructions, refer Appendix
B.
RACK WIDTH POSITIONS
The E89 prover has been designed to accept
either 460mm (18”) or 405mm (16”) wide trays,
1/1 GN,
1
/2 /1 GN trays or USA steam pans.
The prover comes factory set for 460mm (18”)
trays, a rack spacer kit (Part no. 025685) is
required to change to 405mm (16”) trays,
Gastronorm pans or USA steam pans.
RATING PLATE LOCATION
The rating plate for the E89 prover is located at
the bottom left corner of the RH side panel.
L1L2
Phase
RED
BROWN
BLACK
WARNING:
Revision 1/F3608
Neutral
BLACK
BLUE
WHITE
THIS APPLIANCE MUST
BE GROUNDED / EARTHED
Figure 2.1
Ground
GREEN
GREEN/YELLOW
Rating Plate
Figure 2.3
-8-
Page 8
3. OPERATION
NOTE: A full user’s operation manual is supplied with the product and can be used for further referencing
of installation, operation and service.
3.1 DESCRIPTION OF CONTROLS - E89 PROVER / HOLDING CABINETS
1. FUNCTION
OFF Unit is off.
PROOF Unit is in proofing mode. (Indicator
illuminates when switched to this position)
HOLDUnit is in holding mode. (Indicator
illuminates when switched to this position)
2. THERMOSTAT
Temperature range 0 - 85°C (32 - 185°F).
Indicator illuminates when elements are cycling
ON to maintain set temperature.
Controls the prover air temperature.
3. HUMIDITY CONTROL
1 to 5 Setting for butter based pastries
(croissants, Danish pastries etc.)
5 to 8 Settings for yeast based breads and
doughs.
Indicator illuminates when elements are cycling
ON to maintain set temperature.
(Controls the cabinet humidity in PROOF mode
only)
Manual Water Fill Models: Open the prover
door. Fill the water trough at the filling spout,
located at the front of the right hand side rack, to
approximately 20mm / ¾” from the top of the
trough. Remember to top up the water trough
when the water level is below the halfway level in
the trough and before the heating element is
exposed.
Auto Water Fill Models: Check that the water
trough is filling, and the heating element is well
covered.
4. THERMOMETER
Indicates cabinet temperature.
Dual Centigrade and Fahrenheit scale.
CONDENSATION CHANNEL
Below the door there is a condensation channel
and removable water collection drawer for the
purpose of collecting door condensation run-off.
1
2
3
4
89
P
R
O
O
F
D
L
O
H
Revision 1/F3608
-9-
Page 9
3.2 EXPLANATION OF CONTROL
SYSTEM
The E89M/MS Prover/Holding Cabinets feature
operator controls and an electrical circuit for
which a direct understanding of their operation is
required before carrying out any service work or
fault repair work. The control device functions
and electrical circuit are explained as follows:
Function Switch
A rotary switch on the control panel of these
models functions as the power On/Off switch of
the unit by isolating the Line 1 phase supply.
This switch is a 3 position, 4 pole, multi-function
switch which in the Off position opens circuits all
poles and isolates power from all control and
heating systems. The switch should operate as
illustrated below.
P1 – No function / not used.
P2 – Additional air heating element.
P3 – Humidity control thermostat.
(Auto-fill models only - water solenoid, float
switch, solenoid relay)
P4 – Air heating thermostat, cabinet lights, air
circulation fan motor and control panel
power indicator.
P1
H
P2
P
P
P4
The air circulation fan, cabinet lights and control
panel power indicator are On continuously on all
E89 models when the function switch is in either
of the PROOF or HOLD positions. The air
circulation fan mounted at the top of the air
delivery ducting ensures that the temperature and
humidity throughout the cabinet is even by
creating a low velocity air circulation system
throughout the prover cabinet.
Proof Mode
In the ‘Proof’ position the function switch poles
P1, P3 and P4 are closed, supplying power to the
dry heat circuit, humidity circuit, cabinet lights and
fan.
1
P1
D
L
O
2
F
O
O
R
3P3
R
W
4
OFF PROOF HOLD
H
P2
PROOF
P33
PWR
P44
1
P1
D
L
O
2
HOLD
P2
P
P33
PWR
P44
1
2
F
O
O
R
Figure 3.2.1
The proofing system controls air temperature and
humidity levels by way of an air heating element
and a water tank heating element.
The air heating element is positioned in the
bottom of the air circulation ducting inside the
cabinet and is directly controlled by the
user-adjustable thermostat mounted to the control
panel. The thermostat sensing bulb is mounted
inside the cabinet to control the cabinet air
temperature to the control panel setting. An
indicator light on the control panel above this
thermostat will illuminate when the thermostat
has the air heating element operating and will
cycle Off with the thermostat to indicate when the
temperature reaches set point. The main
thermostat is adjustable up to 85°C (185°F).
The humidity thermostat mounted on the control
panel controls the water tank heating element,
which in turn maintains the water temperature
between 20°C (68°F) and 85°C (185°F). The
evaporation of the water provides the cabinet
humidity. The setting of the humidity thermostat
(between 1 - 8) controls the rate of water
evaporation and therefore the level of humidity in
the cabinet.
An indicator light on the control panel above the
humidity dial illuminates when the water tank
element is On, and cycles Off when the
thermostat switches the heating element Off to
provide an indication of the humidity control. The
sensing bulb of the humidity thermostat is
mounted to the water tank heating element, which
is immersed in the water tank. Should the water
tank level drop below the heating element the
humidity thermostat will cycle Off due to the
sensing bulb reacting to the radiated heat off the
heating element and will prevent the humidity
water tank heating element burning out through
excessive temperature.
Hold Mode
When the function switch is turned to the ‘Hold’
position the function switch pole P3 opens to turn
off the humidity control circuit, and pole P2 closes
to connect an additional air heating element to
the air temperature thermostat circuit. In this
mode the air temperature thermostat operates as
it does in the proofing mode, however, in this
case there is an additional air heating element
switched On and Off to provide extra heating
power in this mode. The additional air heating
element is also mounted in the air circulation
ducting.
E89M/MS Prover/Holding Cabinets are provided
with a thermometer dial on the control panel to
Revision 1/F3608
-10-
Page 10
provide an indication of the cabinet temperature.
The sensing bulb of this thermometer dial is
mounted next to the sensing bulb of the main
thermostat inside the cabinet.
Auto water fill (option)
E89 Auto-Water fill models provide for a mains
cold water supply connection for automatic water
tank filling and level control. Non Auto-Water fill
models require the operator to manually fill the
water tank and maintain the water tank level as
the water evaporates through operation.
On Auto-Water fill models an electric solenoid
valve, float switch and relay maintain the water
level in the humidity tank. The float switch is
mounted at the rear of the water tank, and when
the water is below the full level it open circuits,
removing power from the coil. When deenergised, the relay removes power from the
humidity thermostat circuit (therefore switching off
the humidity element), and switches power to the
water solenoid. As the water level reaches the
full level position the float switch contact will
close, re-energising the water solenoid relay,
thereby closing the water solenoid valve and
providing power back to the humidity thermostat.
Accordingly this system will automatically
maintain a full water tank whenever the function
switch is in the “PROOF” position and the mains
water supply is turned on.
Ensuring that the function switch is in the Off
position is necessary whenever removing the
water tank for cleaning as when the water tank is
removed the float switch drops and the water
solenoid valve will open (if the unit is on).
Therefore as a precaution the mains water supply
should also be turned Off whenever removing the
water tank.
Revision 1/F3608
-11-
Page 11
4. MAINTENANCE
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED OUT BY
QUALIFIED PERSONS ONLY.
4.1 CLEANING
WARNING: ALWAYS TURN THE
POWER SUPPLY OFF BEFORE
CLEANING.
IMPORTANT: THIS UNIT IS NOT
WATER PROOF.
DO NOT USE A WATER JET SPRAY TO
CLEAN INTERIOR OR EXTERIOR OF
THIS UNIT.
CABINET
A good quality stainless steel cleaning compound
is recommended for cleaning the inside and
outside of the cabinet. Harsh abrasive cleaners
may damage the surface.
SIDE RACKS
To remove, take hold of the centre rung and lift
towards the prover top. To replace, hold
horizontally, engage in holes and push down.
DOOR
Wash with warm water and detergent solution
using a soft sponge in straight lines up and down
the door.
Rinse with clean, warm water to remove
detergent. Dry off.
Clean door seal with warm water and detergent
solution using a soft sponge when required.
WATER TROUGH
Open right hand side rack and remove trough.
Clean with warm, soapy water. Rinse thoroughly.
WATER TROUGH ELEMENT
When the element becomes limed / scaled,
remove water trough and clean. Replace water
trough and half fill with white vinegar or acetic
acid then fill to the normal level with water.
Switch unit on. Set humidity control to ‘8’ and run
for approximately 30 minutes. Remove trough
and clean element with damp cloth when cooled.
Wash out trough and refit.
This procedure is recommended to be done once
a week. Frequency of cleaning the element may
be increased or decreased depending on the lime
depositing on the element.
Revision 1/F3608
-12-
Page 12
4.2 ROUTINE PROCEDURES
PROCEDURE INTERVAL
WET ELEMENT Remove scaling (refer section 4.1). As required
DOOR SEALS Inspect door seal on door inside for wear and tear. 6 months
DOOR HINGES Check for wear. 12 months
ELEMENTS Check that elements are operating. 12 months
Revision 1/F3608
-13-
Page 13
5. TROUBLE SHOOTING
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED OUT BY
QUALIFIED PERSONS ONLY.
FAULT POSSIBLE CAUSE REMEDY
THE UNIT DOES NOT
OPERATE / START
FAN DOES NOT OPERATE Fan motor faulty.
PROVER CABINET LIGHT(S) DO
NOT OPERATE
NO DRY HEAT Thermostat faulty.
The unit is not plugged into the
wall socket.
The mains isolating switch on the
wall, circuit breaker or fuses are
“off” at the power board.
The power switch on the unit is off.
Incorrect electrical supply.
(Refer fault diagnosis 6.1.1)
Power / Function switch faulty.
(Refer fault diagnosis 6.1.1)
(Refer fault diagnosis 6.1.2)
Bulb blown. Replace bulb
(Refer fault diagnosis 6.1.3)
Element blown.
(Refer fault diagnosis 6.1.3)
Plug in.
Turn on.
Turn switch on. Indicator will
illuminate.
Ensure electrical supply correct.
Replace.
(Refer service section 6.3.2)
Replace.
(Refer service section 6.3.9)
(Refer service section 6.3.8)
Replace.
(Refer service section 6.3.3)
Replace.
(Refer service section 6.3.6)
NO DRY HEAT TEMPERATURE
CONTROL
NO HUMIDITY Unit is in “HOLD” mode.
NO HUMIDITY CONTROL Humidity thermostat faulty.
Thermostat faulty.
(Refer fault diagnosis 6.1.4)
No water in trough.
Humidity thermostat faulty.
(Refer fault diagnosis 6.1.5)
Power / Function switch faulty.
(Refer fault diagnosis 6.1.5)
Water tank element blown.
(Refer fault diagnosis 6.1.5)
(Refer fault diagnosis 6.1.6)
Replace.
(Refer service section 6.3.3)
Humidity only operates when unit
is in “PROOF” mode.
Manual Fill: Fill trough with water.
Auto fill: (refer fault: Auto-fill not filling)
6.4.1 Door Reversal.......................................................................................................................... 26
Revision 1/F3608
-16-
Page 16
6.1 FAULT DIAGNOSIS
6.1.1 UNIT DOES NOT OPERATE / START
Incorrect electrical supply
Check that the supply voltage across phase and
neutral (L1 and L2) terminals of terminal block is
correct as per the voltage stated on the unit’s
electrical rating plate. If incorrect, check electrical
connection of supply cord, and/or check electrical
supply.
Power / Function switch on unit faulty
Ensure that power is isolated from the unit.
Check for continuity through the switch
terminals in each of the settings. The switch
should operate as illustrated below. If not then
the switch is faulty - replace.
P1
1
P1
P1
1
1
wiring. Check power at terminal 2. If there is no
power then the thermostat is faulty - replace.
Alternatively the thermostat indicator light should
illuminate when thermostat set to max.
Element blown
With thermostat on and heating check voltage
across dry element terminals. If there is no
voltage check wiring. If voltage is correct,
element is faulty - replace.
To test element, disconnect terminals and check
resistance across element.
If checks are ok and the unit still does not
operate, check the unit’s wiring and/or
re-diagnose exact fault with unit and refer to
trouble-shooting guide.
6.1.2 FAN DOES NOT OPERATE
Fan motor faulty
Check the supply voltage across motor
terminals. If there is no voltage with function
switch on then check the electrical connections of
supply wiring.
If voltage is correct then isolate unit from power,
then check the oven fan for free rotation.
Remove any obstruction.
If fan is free to spin and the voltage supply is
correct, then the motor is faulty—replace.
Thermostat faulty
With thermostat in off position (fully counterclockwise), the heating indicator should be off. If
not, then the thermostat is faulty - replace.
6.1.5 NO HUMIDITY
Humidity thermostat faulty
With cold proofer, set humidity to ‘8’. Check
power to terminal 1 of bottom (humidity)
thermostat. If there is no voltage then check
wiring. Check power at terminal 2. If there is no
power then the thermostat is faulty - replace.
Alternatively the humidity thermostat indicator
light should illuminate when thermostat set to
max.
Power / Function switch faulty
Ensure that power is isolated from the unit.
Check for continuity through the switch
terminals as illustrated below. If not then the
switch is faulty - replace.
P1
P2
H
1
D
L
O
2
6.1.3 NO HEAT
Thermostat faulty
With cold prover, set thermostat to maximum
position. Check power to terminal 1 of top
thermostat. If there is no power then check
Revision 1/F3608
-17-
PROOF
P33
PWR
P44
PROOF
Figure 6.1.2
Page 17
Element blown
With humidity thermostat on and heating check
voltage across wet element terminals. If there is
no voltage check wiring. If voltage is correct,
element is faulty - replace.
To test element, disconnect terminals and check
resistance across element.
Switch the prover on and set the humidity to ‘4’.
Check that the humidity thermostat cycles on /
off, and using a suitable probe measure the
temperature of the water in the trough. The water
temperature should be 50°C/120°F ± 10%. If the
temperature continues to rise above this then the
humidity thermostat is faulty - replace.
Water level float switch faulty
To check correct operation of float switch
remove the float switch wire connections from
terminal 8 and terminal 5 on relay. With full water
tank (float switch in raised position) float switch
should be closed circuit. With empty water tank
(float switch in lower position) float switch should
be open circuit. If not, float switch is faulty—
replace.
Solenoid relay faulty
E89 auto-fill models are fitted with a 2 pole
change over relay, with its coil controlled by the
float switch located in the water through / tank.
When the water level is below the full position the
coil is not energised, allowing the relay to supply
power to the water solenoid. In this position the
relay should have no power at terminals 3,4 and
8, but power at terminals 1,2,5, and 6,
24
7
6
6.1.7 NO HEATING / HUMIDITY INDICATOR
Indicator faulty
Check voltage across indicator terminals with
controls on and appropriate thermostat turned on
fully. If the voltage is correct and indicator is not
illuminated then the indicator is faulty - replace. If
there is no voltage then check wiring.
6.1.8 AUTOFILL NOT FILLING OR OVER
FLOWING (AUTOFILL MODELS ONLY)
Water solenoid faulty
Empty water tank so float switch is in lowest
position. With power ON check voltage across
water solenoid coil terminals. If voltage is correct
(refer electrical rating plate) but solenoid is not
operating, disconnect electrical supply and
remove wire connections from solenoid. Check
solenoid coil windings resistance.
Correct coil resistance:
208 - 240 volt models 3650 Ω 110 - 120 volt models 1100 Ω
NOTE:
If open circuit/high resistance, then the
coil is faulty– replace.
If coil is correct, rewire and listen for audible
solenoid click when power is supplied. If solenoid
can be heard functioning and water supply is
turned on but no water is entering tank, remove
water solenoid and fittings and check for
blockages.
13
SOLENOID RELAY - TANK FILLING
5
8
Figure 6.1.3
When the water level reaches the full position the
float switch supply’s power to the relay coil, which
in turn cuts power to the water solenoid and
supply’s power to the humidity tank. In this
position the relay should have no power at
terminals 1 and 2, but power at terminals 3,4,5,6,
and 8.
24
13
SOLENOID RELAY - TANK FULL
7
6
5
8
Figure 6.1.4
Revision 1/F3608
-18-
Page 18
6.2 ACCESS
6.2.1 CONTROL PANEL
1) Remove two screws at bottom of control
panel.
6.2.4 CONTROL PANEL—REAR
Power Indicator
Two
Screws
Figure 6.2.1
2) Control panel can now be lowered and hinged
on lower bracket.
3) When closing control panel ensure no wires
are trapped.
6.2.2 RH SIDE PANEL
1) Undo the four screws holding the panel in
place.
2) Pull out at bottom, lower to remove.
Four
Screws
Power / Function Switch
Dry Heating Indicator
Dry Thermostat
Wet Heating Indicator
Wet Thermostat
Figure 6.2.2
6.2.3 LH SIDE PANEL
1) Undo the four screws holding the panel in
place.
2) Pull out at bottom, lower to remove.
Four
Screws
Figure 6.2.3
Revision 1/F3608
Thermometer
Figure 6.2.4
-19-
Page 19
6.3 REPLACEMENT
6.3.1 INDICATOR LIGHT
1) With control panel open (refer 6.2.1)
remove the wires from the back of the neon.
Neon Wires
Figure 6.3.1
2) From back push neon through front of panel
rotating clockwise.
3) Push new neon in from front of panel, and
reconnect wires.
6.3.2 POWER / FUNCTION SWITCH
1) Remove knob off front of power switch.
2) Open control panel (refer 6.2.1).
3) Remove two screws, remove switch.
Two
Screws
Thermostat Phial
Support
Bracket Screw
Figure 6.3.3
4) Withdraw old thermostat phial through hole
under bracket in side of proofer.
5) Remove sleeving from old thermostat and fit
to replacement thermostat.
Fibreglass Sleeve
Thermostat Phial
Figure 6.3.4
6) Undo two screws securing thermostat to
control panel and remove.
Figure 6.3.2
4) Mount new switch and transfer wires from the
old switch.
6.3.3 THERMOSTAT
1) Pull knob off front of thermostat.
2) Open control panel (refer 6.2.1).
3) With door open, remove right hand side rack.
Undo thermostat support bracket screw and
remove bracket.
Revision 1/F3608
Two Screws
Figure 6.3.5
7) Attach new thermostat to control panel and
transfer wires to new thermostat.
8) Re-assemble in reverse order.
9) Ensure hole in prover wall through which the
thermostat capillary passes is re-sealed with
RTV silicone sealant.
-20-
Page 20
6.3.4 HUMIDITY THERMOSTAT
1) Pull knob off front of thermostat
2) Open control panel (refer 6.2.1).
3) With door open, remove right hand side rack
and water trough. Undo humidity thermostat
support bracket screw and remove bracket.
Remove clip holding capillary to element.
7) Attach new thermostat to control panel, and
transfer wires to new thermostat.
8) Re-assemble in reverse order.
9) Ensure hole in prover wall through which the
thermostat capillary passes is re-sealed with
RTV silicone sealant.
Capillary
Clip
Humidity
Support
Bracket
Screw
Figure 6.3.6
4) Remove thermostat support bracket in side
wall, withdraw old humidity thermostat phial
through hole under the bracket.
5) Remove plastic sleeving from old thermostat
and fit to replacement thermostat.
Plastic Sleeve
Thermostat Phial
6.3.5 THERMOMETER
1) Open control panel (refer 6.2.1)
2) With door open, remove right hand side rack
(Lift off supports, and remove).
3) Undo thermometer support bracket screw and
remove bracket.
Support
Bracket Screw
Figure 6.3.9
4) Withdraw old thermometer phial through hole
under bracket in side of cabinet.
5) Undo 2 nuts securing thermometer to control
panel and remove.
Figure 6.3.7
6) Undo two screws securing thermostat to
control panel and remove.
Two Screws
Figure 6.3.8
Revision 1/F3608
Two Nuts
Figure 6.3.10
6) Attach new thermometer to control panel.
7) Insert new thermometer phial through cabinet
side and re-attach bracket.
8) Re-assemble in reverse order.
9) Ensure hole in prover wall through which the
thermostat capillary passes is re-sealed with
RTV silicone sealant.
-21-
Page 21
6.3.6 DRY ELEMENT
1) Remove RH side panel (refer 6.2.2), remove
wires from element terminals, noting position.
2) With door open, remove right hand side rack.
Element
cover
Screws
Figure 6.3.11
3) Undo the two screws holding the element
cover and remove cover.
Capillary
Clip
Support
Bracket
Screw
Figure 6.3.13
5) Unscrew the element from RH side (outside)
of proofer.
Element
Screws
Proofing
Element
Terminals
Hold Element
Terminals
Figure 6.3.12
4) Unscrew the element from RH side (outside)
of prover. Pull element carefully to remove
from inside of proofer.
5) Replace and re-assemble in reverse
order.
Dry Element Ratings
208 - 240 Volt Models 72 Ω ±3.6 Ω.
110 - 120 Volt Models 20.5 Ω ±1 Ω
Figure 6.3.14
6) Pull element carefully into prover to remove.
7) Replace and reassemble in reverse order.
Wet Element Ratings
208 - 240 Volt Models 72 Ω ±3.6 Ω.
110 - 120 Volt Models 20.5 Ω ±1 Ω
6.3.8 LIGHT BULB / GLASS
1) Open the prover door.
2) Pull off lamp cover.
Lamp
Covers
6.3.7 WET ELEMENT
1) Remove RH side panel (refer 6.2.2), and
remove wires from (rear) element terminals.
2) With door open, remove right hand side rack
and water tank.
3) Remove thermostat support bracket screw
(on element) and remove bracket.
4) Remove clip securing thermostat capillary to
element.
Revision 1/F3608
Figure 6.3.15
3) Unscrew bulb out of fitting.
4) Screw in replacement bulb.
5) Refit lamp cover.
-22-
Page 22
6.3.9 FAN
6.3.11 DOOR CATCH MAGNET
1) Remove RH side panel (refer 6.2.2)
2) Remove wires from fan motor, noting their
positions.
Fan
Fan Motor
Terminals
Motor
Bracket
Screw
Figure 6.3.16
3) Remove fan motor bracket, one screw.
4) Slide fan assembly out of proofer.
5) Replace and re-assemble in reverse order.
6.3.10 DOOR HANDLE
1) Open prover door.
2) Remove two screws (E89M) or four screws
(E89MS), remove handle.
1) Open prover door.
2) Unscrew two screws securing magnet to
door.
3) Replace magnet catch and re-assemble in
reverse order.
Door
Magnet
Two
Screws
Figure 6.3.19
6.3.12 DOOR
1) Remove two screws from top of door holding
hinge to door.
Hinge Pivot
(Two Screws)
Hinge Body
Two Screws
(E89M)
Figure 6.3.17
Two Screws top
and bottom
(E89MS)
Figure 6.3.18
3) Replace and re-assemble in reverse order.
Revision 1/F3608
Figure 6.3.20
2) Slide door out at top and remove hinge pivot.
3) Lift door vertically off bottom hinge body (if
sticky loosen bottom hinge body two screws).
4) Remove bottom hinge pivot from door.
5) Fit hinge pivots (top and bottom) to new door.
6) Re-assemble in reverse order.
6.3.13 DOOR GLASS
1) Remove door as per steps one to three of
section 6.3.12
2) Lay door face down on bench and remove
door seal.
-23-
Page 23
3) Remove door inner (14 screws) and remove
glass.
4) Clean glass and replace in reverse order.
Ensure silicone seals have not been
displaced from door outer and door inner.
Door Outer
Door Inner
Door Glass
14 Screws
Door Seal
Figure 6.3.21
5) Reassemble and refit door in reverse order.
6.3.14 DOOR PIVOT BUSHES
1) Remove door as per steps one to three of
section 6.3.12.
2) Remove two screws (top and bottom) holding
hinge body to proofer.
6.3.15 RELAY - AUTOFILL MODELS ONLY
1) Remove RH side panel (refer 6.2.2).
2) Remove two screws securing relay to bracket.
Two Screws
Figure 6.3.24
3) Secure new relay to bracket.
4) Transfer wires from old relay to new relay.
5) Replace RH side panel.
6.3.16 WATER SOLENOID - AUTOFILL
MODELS ONLY
1) Remove RH side panel (refer 6.2.2).
2) Remove wires from solenoid, noting their
positions.
Two
Screws
Figure 6.3.22
3) Door pivot bush can now be removed and
replaced.
Door Pivot
Bush
Figure 6.3.23
Solenoid
Wires
Two screws
Brass Fitting
Figure 6.3.25
3) Remove brass fitting from solenoid.
4) Remove two screws securing solenoid to
bracket, and withdraw solenoid.
5) Secure new solenoid with screws, and
re-assemble in reverse order.
4) Re-assemble in reverse order.
Revision 1/F3608
-24-
Page 24
6.3.17 WATER SOLENOID CLEANING
1) Disconnect water supply from the water
solenoid.
2) Remove the sieve from the water valve
assembly by pulling firmly away from the
assembly with a pair of pliers.
Float Switch
Sleeve
Float Switch
Nut
Float Switch
Figure 6.3.28
Sieve
Figure 6.3.26
3) Clean the sieve, removing all dirt and grime.
4) Replace the sieve and reconnect the
water supply.
6.3.18 FLOAT SWITCH - AUTOFILL
MODELS ONLY
1) Remove RH side panel (refer 6.2.2).
2) Remove float switch wires from relay,
noting their positions.
3) Remove brass fitting from rear of float switch.
4) Remove RH side rack and water trough from
inside proofer.
Two Nuts
8) Remove the float switch from the bracket,
replace, and reassemble in reverse order.
NOTE:
Ensure float switch bracket is RTV
silicone sealed to prevent steam leakage.
Brass Fitting
Figure 6.3.27
5) Undo two nuts from outside cabinet, and two
screws inside cabinet securing float switch
bracket to proofer.
6) Remove float switch assembly from proofer.
NOTE:
The float switch bracket has been
silicone sealed, so it may therefore be
necessary to cut around the bracket with a
sharp knife to assist with removal. Clean off
all remaining silicone.
7) Remove the float switch sleeve, and undo the
nut securing the float switch to the bracket.
Revision 1/F3608
-25-
Page 25
6.4 ADJUSTMENT / CALIBRATION
6.4.1 DOOR REVERSAL
1) Whilst supporting door remove bottom hinge
body (two screws) and remove door.
Two Screws
Hinge Body
Figure 6.4.1
2) Remove top hinge body (two screws).
3) Remove four cover screws covering alternate
hinge holes. Refit cover screws on opposite
side.
When changing to LH hinged door.
Remove magnet plate and transfer to
opposite side.
Important: Redundant plate holes in LH side
wall must be filled to stop steam ingress into
wall cavity.
6) Fit bottom hinge body to top on opposite side,
centre hinge on slots.
7) Whilst holding door in place fit remaining
hinge body to bottom, securing door in
position.
8) Remove door handle (E89M only) (refer
6.3.10) and refit in the higher setting, using
the extra screw position.
9) Ensure door seal is removed and refitted with
join at bottom, centred over middle screw
head when closed.
10) Refit LH side panel.
Cover Screws
Figure 6.4.2
4) Remove LH side panel (refer 6.2.3).
5) When changing to RH hinged door.
Remove LH magnet plate cover screws and
clips from inside LH wall (Do not fit cover
screws to old magnet position).
Transfer door magnet plate to opposite side.
Magnet Cover
Screws
Magnet Plate
Figure 6.4.3
Revision 1/F3608
-26-
Page 26
7. ELECTRICAL CIRCUIT SCHEMATIC
7.1 E89 Manual Water Fill Holding / Prover Cabinet
LIGHT
LIGHT
2x 15W 110V
2x 25W 240V
FAN
POWER
PILOT
LIGHT
HUMIDITY
ELEMENT
600W 110V
2
1
THERMOSTAT
HUMIDITY
PILOT
LIGHT
800W 240V
600W 110V
800W 240V
DRY
2
1
4
2
F
O
O
O
H
P2P4P3
3
R
R
W
P
P
OFF
4
P4
34
3
P3P2
21
2
1
P1
FUNCTION SWITCH OPERA TION
PROOF
HOLD
4
3
21
P2P1P3 P4
P2P1P3 P4
1
D
L
FUNCTION SWITCH
P1
THERMOSTAT
ELEMENT
HOLD
600W 110V
800W 240V
ELEMENT
GROUND
Revision 1/F3608
-27-
Page 27
7.2 E89A Auto Water Fill Prover / Holding Cabinet
7
246
N/C
FLOAT
8
SWITCH
5
13
RELAY
WATER
SOLENOID
LIGHT
LIGHT
2x 15W 110V
2x 25W 240V
POWER
PILOT
LIGHT
2
1
1
THERMOSTAT
HUMIDITY
PILOT
LIGHT
2
THERMOSTAT
HUMIDITY
DRY
FAN
ELEMENT
ELEMENT
800W 240V
600W 110V
800W 240V
600W 110V
OFF
P4
34
P3P2
21
P1
HOLD
P2P1P3 P4
4
3
2
1
FUNCTION SWITCH OPERA TION
Revision 1/F3608
1
P1
2
F
O
D
L
O
O
R
H
P2
PROOF
4
3
21
P2P1P3 P4
FUNCTION SWITCH
3
P
P3
4
800W 240V
600W 110V
HOLD
ELEMENT
R
W
P
P4
GROUND
-28-
Page 28
8. ELECTRICAL WIRING DIAGRAM
8.1 E89 Manual Water Fill
600W 110V
600W 110V
800W 240V
800W 240V
600W 110V
800W 240V
26
FAN MOTOR
32
25
WET
ELEMENT
WIRE MARKING
"VIVID" PEN
11
27
28
HOLD
ELEMENT
7
29
31
DRY
ELEMENT
EARTH
POWER SUPPLY CORD
6
35
30
26
25
27
24
32
LIGHT
282329
16
33
34
LNE
LIGHT
POWER
INDICATOR
3
2
2
1
P2
P1
SWITCH
FUNCTION
1
Revision 1/F3608
25W 240V
LIGHTS
15W 110V
14
TEMP
INDICATOR
15
HUMIDITY
INDICATOR
1
MAINS
BLOCK
TERMINAL
17
5
7
18
8
3
4
P3
P4
4
6
2
DRY
3
23
1
(0-85°C)
THERMOSTAT
WET
10
(30-85°C)
THERMOSTAT
13
11
2
1
EARTH
18
12
4
-29-
Page 29
8.2 E89A Auto Water Fill
800W 240V
800W 240V
600W 110V
2626
FAN MOTOR
WET
ELEMENT
600W 110V
HOLD
ELEMENT
800W 240V
600W 110V
DRY
ELEMENT
32
WIRE MARKING
"VIVID" PEN
27
11
28
7
29
6
31
EARTH
POWER SUPPLY CORD
35
E
30
2525
27
24
32
LIGHT
28
29
23
33
16
34
LN
LIGHT
25W 240V
LIGHTS
15W 110V
22
14
POWER
INDICATOR
TEMP
INDICATOR
15
HUMIDITY
INDICATOR
1
MAINS
BLOCK
TERMINAL
17
5
7
3
2
2
1
P2
P1
SWITCH
FUNCTION
1
18
8
4
3
P3
P4
4
6
2
DRY
THERMOSTAT
3
23
1
(0-85°C)
WET
THERMOSTAT
10
(30-85°C)
13
12
4
11
2
1
9
WIRE MAKING
"VIVID" PEN
EARTH
7
8
18
9
21
20
5
6
3
4
1
2
RELAY
19
19
Revision 1/F3608
-30-
WATER
22
SOLENOID
FLOAT SWITCH
Page 30
9. SPARE PARTS
REPLACEMENT PARTS LIST
CONTROLS
022789 Switch - Function
020823 Knob - Function
022787 Thermostat (Temperature)
024527 Thermostat (Humidity) 020823 Knob - Temperature Thermostat
021472 Knob - Humidity Thermostat
020849 Neon Indicator (240V)
023857 Neon Indicator (110V)
022788 Thermometer (Dual °C & °F)
013998 Fan / Motor (240V)
013999 Fan / Motor (110V)
014001 Dry Element - 800W (240V)
015759 Dry Element - 600W (110V)
015224 Wet Element - 800W (240V)
015320 Wet Element - 600W (110V)
DOOR
SA1686 Door Assembly (E89M)
SA1687 Door Assembly (E89MS)
021468 Handle (E89M)
025519 Handle (E89MS)
020082 Hinge Top Assembly (Assembled with bush)
020083 Hinge Bottom Assembly (Assembled with bush)
017905 Hinge Bush
018947 Magnetic Catch
025988 Door Seal
1 025582 Control panel
2 025585 Overlay °C (Bakbar)
025586 Overlay °C (Blue Seal)
025584 Overlay °F (Moffat)
3 022789 Selector switch
4 022787 Thermostat 0-85°C (Dry)
5 024527 Thermostat 30-85°C (Wet)
6 023857 Pilot light (110V)
020849 Pilot light (240V)
7 020823 Knob
8 021472 Knob (Humidity)
9 022788 Thermometer
10 024694 Control panel hook
10
Revision 1/F3608
-36-
Page 35
11.4 E89M DOOR ASSEMBLY
2
3
1
4
5
6
7
8
9
10
Pos Part No. Description
1 020082 HINGE TOP ASSEMBLY
2 025603 DOOR HANDLE BRACKET
3 021468 DOOR HANDLE
4 025597 DOOR OUTER POWDER COATED
5 090202 DOOR OUTER SEAL - 2.02m
6 025599 DOOR GLASS
7 020083 HINGE BOTTOM ASSEMBLY
8 025593 DOOR INNER FRAME
9 018947 MAGNETIC CATCH (INNER)
10 025600 MAGNET MOUNTING PLATE
11 090203 DOOR INNER FRAME SEAL - 2.00m
12 025598 DOOR SEAL
11
12
Revision 1/F3608
-37-
Page 36
11.5 E89MS DOOR ASSEMBLY
2
1
3
4
5
6
7
8
9
10
Pos Part No. Description
1 025519 DOOR HANDLE
2 020082 HINGE TOP ASSEMBLY
3 025588 DOOR OUTER
4 090202 DOOR OUTER SEAL - 2.02m
5 025599 DOOR GLASS
6 025593 DOOR INNER FRAME
7 020083 HINGE BOTTOM ASSEMBLY
8 018947 MAGNETIC CATCH (INNER)
9 025600 MAGNET MOUNTING PLATE
10 090203 DOOR INNER FRAME SEAL - 2.00m
11 025598 DOOR SEAL
11
Revision 1/F3608
-38-
Page 37
11. SERVICE CONTACTS
AUSTRALIA
VICTORIA - MOFFAT PTY
HEAD OFFICE AND MAIN WAREHOUSE
740 Springvale Road Tel (03) 9518 3888
Mulgrave VIC 3170 Fax (03) 9518 3838
Spare Parts Department Free Call 1800 337 963
Fax (03) 9518 3895
NEW SOUTH WALES - MOFFAT PTY
Unit 8/142 James Ruse Drive
Rosehill NSW 2142
Spare Parts Free Call 1800 337 963
Fax (03) 9518 3895
BLUESEAL LTD
Units 6-7 Mount St Tel 0121-327 5575
Business Park Fax 0121-327 9711
Birmingham B7 5QU
England
UNITED STATES OF AMERICA
MOFFAT INC.
3765 Champion Blvd Tel 1-800 551 8795
P.O. Box 4129 Fax 336 661 9546
Winston-Salem
NC27115
NATIONAL COVERAGE FOR SERVICE OR MAINTENANCE DIAL
FREE CALL 1800 551 8795 (USA ONLY)
Revision 1/F3608
-40-
Page 39
APPENDIX A. AUTOFILL KIT
WARNING: ENSURE POWER SUPPLY IS SWITCHED OFF BEFORE COMMENCING.
To convert a manual fill E89 prover to an auto-fill model, upgrade kit #025683 (240V) or #025752 (110V)
needs to be installed as follows.
A. PROVER PREPARATION
1) Remove RH side panel (four screws), pull out at bottom and lower to remove.
2) Remove water inlet blanking plate from rear of unit (four screws). (H).
3) Open RH side rack and remove water trough.
4) Remove blanking plate from inside prover (Two bolts). (A).
Note:plate with a sharp knife to assist with removal. Clean off all remaining silicone.
Blanking plate has been silicone sealed, therefore it maybe necessary to cut around the blanking
B
A B
E
C
D
F
G H
EXTERNAL VIEW INTERNAL VIEW
B. KIT INSTALLATION
1) Install the float switch bracket and assembly to inside of prover (B). Place a bead of RTV silicon
sealant around back face of float switch bracket before securing to liner to ensure prover is sealed.
2) Fit water solenoid and mounting bracket (F) to rear panel as shown (two screws).
3) Fit 1/4” copper tube (C) to outlet tube (B) and water solenoid (F) tighten all fittings.
4) Fit relay (D) to terminal block panel (two screws).
5) Connect wiring as per wiring diagram provided (refer overleaf).
6) Fit new rear service panel (G) to rear of prover.
7) Affix max water pressure label (E) to rear panel above water inlet.
8) Connect cold water supply (1/2” ID hose) to water connection elbow. Ensure leak free connection.
Maximum water pressure is 550 kPa (80psi).
9) Fit elbow to water solenoid, ensure supplied washer is used. Turn water supply on and check for leaks,
no water should be flowing into trough.
C. RE-COMMISSIONING
1) Re-fit RH side panel (four screws)
2) Replace water trough.
3) Turn the power on, check that water trough fills, and stops filling approximately 20mm from the top of
the tank. (Note: Humidity element will not heat until tank is filled to correct level).
4) Turn power supply off, empty water trough and repeat step 3 above.
5) Close RH side rack.
Revision 1/F3608
-41-
Page 40
WIRING DIAGRAM - AUTOFILL KIT
Wiring changes in bold.
800W 240V
800W 240V
600W 110V
2626
FAN MOTOR
WET
ELEMENT
600W 110V
HOLD
ELEMENT
800W 240V
600W 110V
DRY
ELEMENT
32
WIRE MARKING
"VIVID" PEN
11
27
28
7
29
6
31
EARTH
POWER SUPPLY CORD
35
E
30
2525
27
24
32
LIGHT
28
29
23
33
16
34
LN
LIGHT
25W 240V
LIGHTS
15W 110V
22
14
POWER
INDICATOR
TEMP
INDICATOR
15
HUMIDITY
INDICATOR
1
MAINS
BLOCK
TERMINAL
17
5
7
3
2
1
P1
SWITCH
FUNCTION
1
18
8
2
3
4
P2
P3
P4
4
6
2
DRY
THERMOSTAT
3
23
1
(0-85°C)
WET
(30-85°C)
THERMOSTAT
13
12
4
11
10
2
1
9
WIRE MAKING
"VIVID" PEN
EARTH
7
8
18
21
20
22
5
6
9
3
4
1
2
RELAY
19
19
WATER
SOLENOID
FLOAT SWITCH
Revision 1/F3608
-42-
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.