This manual is designed to take a more in depth look at the E87 prover for the purpose of making
the unit more understandable to service people.
There are settings explained in this manual that should never require to be adjusted, but for
completeness and those special cases where these settings are required to change, this manual
gives a full explanation as to how, and what effects will result.
IMPORTANT: MAKING ALTERATIONS MAY VOID WARRANTIES AND APPROVALS.
Revision 2/F3520
-3-
Page 3
MODEL: E87
1. SPECIFICATIONS
FRONT
710
(28.0)
50
(1.95)
SIDE
770
(30.3)
150
(5.9)
890
(35.0)
130
(5.1)
PLAN
LEGEND
- Electrical connection entry point
Dimensions shown in millimetres.
Dimensions in inches shown in brackets.
Revision 2/F3520
-5-
Page 4
LOCATION
To ensure correct operation the following
minimum installation clearances are to be
adhered to:
Rear: 25 mm / 1”
Left-hand side: 25 mm / 1”
Right-hand side: 25 mm / 1”
PROVER INTERNAL DIMENSIONS
Width: 460 mm / 18”
Height: 610 mm / 24”
Depth: 660 mm / 26”
Oven Volume: 0.19 m³ / 6.5 ft³
PROVER RACK SIZE
Width: 460 mm / 18”
Depth: 660 mm / 26”
No. of rack positions: 8
Rack position spacing: 75 mm / 3”
ELECTRICAL SUPPLY SPECIFICATION
OPTIONS
100-120 V AC 60 Hz, 12.5 A, 1.5 kW @ 120 V
220-240 V AC 50 Hz, 7.5 A, 1.8 kW @ 240 V
ELECTRICAL PLUG SPECIFICATION
REQUIREMENTS
Australia 3-pin 250V 10A, AS/NZ 3112
Canada 3-pin 250V 15A, NEMA 6-15
New Zealand 3-pin 250V 10A, AS/NZ 3112
United Kingdom 3-pin 250V 13A fused, BS
1363A
United States 3-pin 250V 15A, NEMA 6-15
Other Countries 3-pin 250V 10A minimum, type
to meet country standards
Revision 2/F3520
-6-
Page 5
2. INSTALLATION
WARNING: THIS APPLIANCE MUST BE GROUNDED.
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED
OUT BY QUALIFIED PERSONS ONLY.
It is most important that the prover is installed
correctly and that the operation is correct
before use. Installation shall comply with local
electrical, health and safety requirements.
BEFORE CONNECTION TO POWER
SUPPLY
Unpack and check unit for damage and report
any damage to the carrier and dealer. Report
any deficiencies to your dealer. Fit the
castors which are packed inside the unit.
Check that the available power supply is
correct to that shown on the rating plate
located on the right-hand side panel.
220-240 V AC 50 Hz, 7.5 A, 1.8 kW @ 240 V
100-120 V AC 60 Hz, 12.5 A, 1.5 kW @ 120 V
LOCATION
To ensure correct operation the following
minimum installation clearances are to be
adhered to:
Rear 25mm / 1”
Left-hand side 25mm / 1”
Right-hand side 25mm / 1”
ELECTRICAL CONNECTION
E87 provers are supplied with pre-fitted cords.
Ensure unit is fitted with correct cord and plug
for the installation (refer to the specifications
section).
Should changing of the cord be necessary,
gain access to the electrical connection
terminal block and strain relief clamp by
removing the control panel.
ASSEMBLY OF CASTORS
1. Remove the castors from inside the
prover.
2. Remove side racks and water trough.
3. Lift and place the prover onto its back.
Attach the two swivel castors (with brake)
to the front of the prover with the screws
provided. Attach the two rigid castors to
the rear.
4. Lift the prover onto its castors and refit the
water trough and side racks.
DOUBLE STACKING UNITS
When it is desired to mount a Turbofan
Countertop Convection Oven on an E87
prover, a double stacking kit may be used.
Available from your dealer or Turbofan
distributor (see Spare Parts).
When mounting one prover on top of another,
a double stacking kit is also required.
RATING PLATE LOCATION
The rating plate for the E87 prover is located
at the bottom left corner of the RH side panel.
Rating Plate
Revision 2/F3520
Figure 2.2
Figure 2.1
-7-
Page 6
3. OPERATION
NOTE: A full user’s operation manual is supplied with the product and can be used for further
referencing of installation, operation and service.
3.1 DESCRIPTION OF CONTROLS
1. POWER
Depress to switch power on or off (switch
illuminates when power is on).
2. THERMOSTAT
1
2
3
Temperature range 25 - 40°C (75 - 105°F).
Light illuminates when elements are cycling
ON to maintain set temperature.
Controls the prover air temperature.
3. HUMIDITY CONTROL
(Light illuminates when elements are cycling
ON to maintain set humidity).
Controls prover humidity.
LO - Humidity setting for butter based pastries
(croissants, Danish pastries etc).
MED / HI - Humidity setting for yeast based
breads and dough.
WATER
Open the prover door. Fill the water trough to
the halfway level in the trough front filling
snout, located on the right hand side.
Remember to top up the water trough when
the level is below the front snout.
Revision 2/F3520
-8-
Page 7
3.2 EXPLANATION OF CONTROL
SYSTEM
The E87 Prover has a power On/Off switch on
the control panel and isolates power to the
humidity and heating fan and light circuits
when switched Off. When switched On the
switch will illuminate to indicate that the unit is
On and operational. The air circulation fan is
On continuously on all E87 models when the
power switch is in an On position.
The proofing system operates on all models,
controls air temperature and humidity levels
by way of an air heating element controlled by
a mechanical bulb and capillary thermostat
and a water tank heating element controlled
by a mechanical bulb and capillary
thermostat.
The air heating element is positioned in the
bottom of the air circulation ducting inside the
cabinet and is directly controlled by the
user-adjustable thermostat mounted to the
control panel. The thermostat sensing bulb is
mounted inside the cabinet to control the
cabinet air temperature to the control panel
setting. An indicator light on the control panel
above this thermostat will illuminate when the
thermostat has the air heating element
operating and will cycling Off with the
thermostat to indicate when the temperature
reaches set point.
The water tank heating element controlled by
the humidity level thermostat mounted to the
control panel is used to heat the water tank
water and maintain water tank temperature
between 50°C (122°F) and 80°C (176°F).
This water tank temperature is controlled by
the humidity level thermostat setting between
the adjustments of low and high humidity.
The evaporation rate of the water in the water
tank dependent on its temperature, provides
humidity into the cabinet and accordingly the
setting of the humidity thermostat controls the
rate of evaporation and therefore the humidity
level in the cabinet.
An indicator light on the control panel above
the humidity dial illuminates when the water
tank element is On, and cycles Off when the
thermostat switches the heating element Off
to provide an indication of the humidity
control. The sensing bulb of the humidity
thermostat is mounted directly on the water
tank heating element which are both
immersed in the water tank. Should the water
tank level drop below the heating element the
humidity thermostat will cycle Off due to the
sensing bulb reacting to the radiated heat off
the heating element and will prevent the
humidity water tank heating element burning
out through excessive temperature.
E87 models require the operator to manually
fill the water tank and maintain the water tank
level as the water evaporates through
operation.
With all E87 models butter based products
such as croissants and danish pastries should
have the cabinet proofing temperature set
around 25°C (77°F) as higher proofing
temperatures will cause the butter to melt out
of the product, and for yeast based doughs
and breads the proofing temperature should
be set higher at around 40°C (105°F) in order
to activate the yeast in these products.
On all models the air circulation fan mounted
at the top of the air delivery ducting ensures
that the temperature and humidity throughout
the cabinet is even by creating a low velocity
air circulation system throughout the prover
cabinet. This system overcomes the natural
occurrence of hot air rising and therefore
higher humidity and temperature in the upper
positions of the cabinet as found with proofing
units without forced air circulation.
The user-adjustable thermostat and humidity
controls are required to allow adjustment of
cabinet temperature and humidity levels for
the variations of temperature and humidity
that different product types require.
Two cabinet illumination lights are provided in
the E87 models and these 15 watt each
incandescent filament lamps are On
whenever the control panel power switch is
switched on.
To prevent the formation of condensation on
the aluminium frame around the front of the
cabinet and to assist in minimising the
condensation occurring on the door frame and
door glass inner face a resistance wire
heating element is fitted into the cabinet
aluminium extrusion frame. This heating wire
is on whenever the power switch is switched
on and will heat the aluminium frame to a
warm-to-touch temperature.
Revision 2/F3520
-9-
Page 8
4. MAINTENANCE
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED
OUT BY QUALIFIED PERSONS ONLY.
4.1 CLEANING
WARNING: ALWAYS TURN THE
POWER SUPPLY OFF BEFORE
CLEANING.
IMPORTANT: THIS UNIT IS NOT
WATER PROOF.
DO NOT USE A WATER JET SPRAY TO
CLEAN INTERIOR OR EXTERIOR OF
THIS UNIT.
CABINET
A good quality stainless steel cleaning
compound is recommended for cleaning the
inside and outside of the cabinet. Harsh
abrasive cleaners may damage the surface.
SIDE RACKS
To remove, take hold of the centre rung and
lift towards the prover top. To replace, hold
horizontally, engage in holes and push down.
DOOR
Open the door and lift up off its hinges. Wash
with warm water and detergent solution using
a soft sponge.
To refit the door, simply fit onto its hinges.
WATER TROUGH
Remove right hand side rack and remove
trough. Clean with warm, soapy water. Rinse
thoroughly.
WATER TROUGH ELEMENT
When the element becomes limed / scaled,
remove water trough and clean. Replace
water trough and half fill with white vinegar or
acetic acid then fill to the normal level with
water. Switch unit on. Set humidity control to
‘Hi’ and run for approximately 30 minutes.
Remove trough and clean element with damp
cloth when cooled. Wash out trough and refit
to unit.
This procedure is recommended to be done
once a week. Frequency of cleaning the
element may be increased or decreased
depending on the lime depositing on the
element.
Revision 2/F3520
-10-
Page 9
4.2 ROUTINE PROCEDURES
PROCEDURE INTERVAL
DOOR HINGES Check for wear. 12 months
DOOR CATCH Ensure that catch is adjusted such that the door
closes properly.
ELEMENTS Check that element resistances are correct to their
ratings. (refer 6.3.6, 6.3.7).
WET ELEMENT Remove scaling (refer section 4.1). As required
HOTWIRE Check that hotwire is working. 12 months
12 months
12 months
Revision 2/F3520
-11-
Page 10
5. TROUBLE SHOOTING
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED
OUT BY QUALIFIED PERSONS ONLY.
FAULT POSSIBLE CAUSE REMEDY
THE PROVER DOES NOT
OPERATE / START
OVEN LIGHT NOT
ILLUMINATING
FAN DOES NOT OPERATE Faulty fan.
The prover is not plugged into
the wall socket.
The mains isolating switch on
the wall, circuit breaker or fuses
are “off” at the power board.
The power switch on the prover
is off.
Incorrect electrical supply.
(Refer fault diagnosis 6.1.1)
Power switch on unit faulty.
(Refer fault diagnosis 6.1.1)
Blown bulb.
No power to light.
(Refer fault diagnosis 6.1.2)
(Refer fault diagnosis 6.1.3)
Plug in.
Turn on.
Depress switch. Switch will
illuminate.
Ensure electrical supply correct.
Replace.
(Refer service section 6.3.3)
Replace.
(Refer service section 6.3.1)
Correct fault.
Replace.
(Refer service section 6.3.8)
NO HEAT Thermostat faulty.
(Refer fault diagnosis 6.1.4)
Element blown.
(Refer fault diagnosis 6.1.4)
NO TEMPERATURE
CONTROL
NO HUMIDITY No water in trough.
NO HUMIDITY CONTROL Faulty thermostat.
SLOW RECOVERY Overloading of prover.
Faulty thermostat.
(Refer fault diagnosis 6.1.5)
Faulty thermostat.
(Refer fault diagnosis 6.1.6)
Element blown.
(Refer fault diagnosis 6.1.6)
(Refer fault diagnosis 6.1.7)
Door opened unnecessarily.
Electrical supply incorrect.
Fan faulty.
(Refer fault diagnosis 6.1.3)
Replace.
(Refer service section 6.3.4)
Replace.
(Refer service section 6.3.6)
Replace.
Refer service section 6.3.4)
Fill trough with water.
Replace.
(Refer service section 6.3.5)
Replace.
(Refer service section 6.3.7)
Replace.
(Refer service section 6.3.5)
Reduce batch size.
Do not open unnecessarily.
Check supply voltage is as per
rating plate voltage.
Replace.
(Refer service section 6.3.8)
Revision 2/F3520
-12-
Page 11
FAULT POSSIBLE CAUSE REMEDY
NO HEATING / HUMIDITY
INDICATOR
CONDENSATION ON TOP OF
FRAME
DOOR DOES NOT CLOSE Tray in way of door.
Indicator faulty.
(Refer fault diagnosis 6.1.8)
Hot wire faulty.
(Refer fault diagnosis 6.1.9)
Damaged door magnet.
Replace.
(Refer service section 6.3.2)
Replace.
(Refer service section 6.3.12)
Correctly position tray in rack.
Replace.
(Refer service section 6.3.11)
Revision 2/F3520
-13-
Page 12
6. SERVICE PROCEDURES
WARNING: ENSURE POWER SUPPLY IS SWITCHED OFF BEFORE SERVICING.
WARNING: ALL INSTALLATION AND SERVICE REPAIR WORK MUST BE CARRIED
OUT BY QUALIFIED PERSONS ONLY.
Check that the voltage across phase and
neutral (L1 and L2) terminals of terminal block
is the voltage as stated on the unit’s electrical
rating plate.
If incorrect, check electrical connection of
supply wiring and / or check electrical supply.
Power switch faulty
Check if power switch latches. If the switch
does not latch, then switch is faulty—replace.
With switch latched, check voltage across
terminal 1 to terminal 3. If there is no voltage,
check for fault in wiring.
Check voltage across terminal 2 to terminal 3.
If there is no voltage, then switch is faulty—
replace.
NOTE: When power switch is latched, it
should illuminate if operating correctly.
6.1.2 PROVER LIGHTS NOT ILLUMINATING
No power to light
Check voltage across light bulb terminals. If
there is no voltage then check wiring. If there
is voltage then the lamp is faulty - replace.
6.1.3 FAN DOESN’T OPERATE
Fan motor faulty
Check the supply voltage across the motor
terminals. If there is no voltage then check
the electrical connections of supply wiring.
If voltage is correct then check the oven fan
for free rotation. Remove any obstruction.
If fan is free to spin and the voltage supply is
correct, then the motor is faulty—replace.
6.1.4 NO HEAT
Thermostat faulty
With cold prover, set thermostat to 40°C /
105°F. Check power to terminal 1 of top
thermostat. If there is no power then check
wiring.
Check power at terminal 2. If there is no
power then the thermostat is faulty - replace.
Element blown
With thermostat on and heating check voltage
across dry element terminals. If there is no
voltage check wiring. If voltage is correct,
element is faulty - replace.
6.1.5 NO TEMPERATURE CONTROL
Thermostat faulty
With thermostat in off position (fully counterclockwise), the heating indicator should be off.
If not, then the thermostat is faulty - replace.
6.1.6 NO HUMIDITY
Thermostat faulty
With cold prover, set humidity to ‘HI’. Check
power to terminal 1 of bottom thermostat. If
there is no power then check wiring.
Check power at terminal 2. If there is no
power then the thermostat is faulty - replace.
Element blown
With humidity thermostat on and heating
check voltage across wet element terminals.
If there is no voltage check wiring. If voltage
is correct, element is faulty - replace.
6.1.7 NO HUMIDITY CONTROL
Humidity thermostat faulty
Switch the prover on and set the humidity to
‘LO’. Check that the humidity thermostat
cycles on/off, and using a suitable probe
measure the temperature of the water in the
trough. The water temperature should be 50°
C/120°F ± 10%. If the temperature continues
to rise above this then the humidity thermostat
is faulty - replace.
6.1.8 NO HEATING / HUMIDITY
INDICATOR
Indicator faulty
Check voltage across indicator terminals with
controls on and appropriate thermostat turned
on fully. If the voltage is correct, and the
indicator is not illuminating then the indicator
is faulty - replace. If there is no voltage then
check wiring.
6.1.9 CONDENSATION ON TOP OF FRAME
Hotwire faulty
Check voltage across hotwire. If there is no
voltage then the hotwire is faulty - replace.
Revision 2/F3520
-15-
Page 14
6.2 ACCESS
6.3 REPLACEMENT
6.2.1 CONTROL PANEL
1) Undo the one screw on top of control
panel.
One Screw
Figure 6.2.1
2) Panel is now free to hinge at bottom.
When closing the panel ensure wires and
capillary tube are clear of metal or other
terminals.
6.2.2 CONTROL PANEL—REAR
Power Switch
6.3.1 LIGHT BULB / GLASS
1) Open the prover door.
2) Pull off lamp cover.
Lamp Covers
Figure 6.3.1
3) Unscrew bulb out of fitting.
4) Screw in replacement bulb.
5) Refit lamp cover.
6.3.2 INDICATOR LIGHT
1) With control panel open (refer 6.2.1)
remove the wires from the back of the
neon.
Dry Heating Indicator
Dry Thermostat
Wet Heating Indicator
Wet Thermostat
Neon Wires
Figure 6.3.2
2) From back push neon through front of
panel rotating clockwise.
3) Push new neon in from front of panel, and
reconnect wires.
6.3.3 POWER SWITCH
1) With control panel open (refer 6.2.1)
remove the wires from the back of the
switch, noting their positions.
Power Switch
Wires
Revision 2/F3520
Figure 6.2.2
Figure 6.3.3
-16-
Page 15
2) From back push switch through front of
panel.
3) Push new switch in from front of panel, and
reconnect wires.
6.3.4 THERMOSTAT
1) Pull knob off front of thermostat
2) Open control panel (refer 6.2.1) and undo
2 screws securing thermostat.
Two Screws
Figure 6.3.4
3) Transfer wires to new thermostat.
4) With door open, remove right hand side
rack. Undo thermostat support bracket
screw and remove bracket.
6.3.5 HUMIDITY THERMOSTAT
1) Pull knob off front of thermostat
2) Open control panel (refer 6.2.1.) and undo
2 screws securing thermostat.
Two Screws
Figure 6.3.7
3) Transfer wires to new thermostat.
4) With door open, remove right hand side
rack and water trough. Undo thermostat
support bracket screw and remove
bracket. Remove clips holding capillary to
element.
Support
Bracket
Screw
Support
Bracket Screw
Figure 6.3.5
5) Withdraw old thermostat phial through
side of prover.
6) Remove plastic sleeving from old
thermostat and fit to replacement
thermostat.
Thermostat Phial
Plastic Sleeving
Figure 6.3.6
7) Insert new thermostat.
8) Re-assemble in reverse order.
Capillary
Clips
Figure 6.3.8
5) Remove rubber bush in side wall, withdraw
old thermostat phial through side of prover.
6) Remove fibreglass sleeving from old
thermostat and fit to replacement
thermostat
Fibreglass Sleeve
Thermostat Phial
Figure 6.3.9
7) Insert new thermostat.
8) Re-assemble in reverse order.
Revision 2/F3520
-17-
Page 16
6.3.6 DRY ELEMENT
1) Open control panel (refer 6.2.1), remove
wires from element terminals noting
position.
Element
Terminals
Figure 6.3.10
2) With door open, remove right hand side
rack
3) Unscrew the element from inside control
housing. Pull element carefully to remove
from inside of prover.
4) Open control panel (refer 6.2.1) and
remove wires from element terminals,
noting their positions.
5) Unscrew the element from inside control
housing.
Element
Screws
Figure 6.3.13
6) Pull element carefully from the inside of
prover to remove .
7) Replace and re-assemble in reverse
order.
Wet Element Ratings
110 - 120 Volt 20.1 ohms
220 - 240 Volt 71.5 ohms
Element
Screws
Figure 6.3.11
4) Replace and re-assemble in reverse
order.
Dry Element Ratings
110 - 120 Volt 20.5 ohms
220 - 240 Volt 70.5 ohms.
6.3.7 WET ELEMENT
1) With door open, remove right hand side
rack and water trough.
2) Undo thermostat support bracket screw
and remove bracket.
3) Remove clips holding capillary to element.
Support
Bracket
Screw
6.3.8 FAN MOTOR
1) Open control panel (refer 6.2.1), and
remove wires from fan motor terminals,
noting positions.
Fan Motor
Terminals
Figure 6.3.14
2) Loosen retaining bracket screw. Slide
bracket down to bottom position.
Retaining
Bracket Screw
Capillary
Clips
Revision 2/F3520
Figure 6.3.12
Figure 6.3.15
3) Slide out motor.
4) Replace and re-assemble in reverse
order, ensuring bracket is secured in
highest position.
-18-
Page 17
6.3.9 DOOR
6.3.11 MAGNETIC CATCH
1) Open prover door.
2) Lift door vertically off hinges.
3) Remove door handle and door catch plate
(two bolts).
Two Bolts
Figure 6.3.16
4) Drill out rivets securing hinges to old door
frame (two per hinge).
Rivets
Figure 6.3.17
5) Secure door handle and catch plate to
new door.
6) Rivet hinges to new door frame.
7) Re-hang door on E87 prover.
6.3.10 DOOR HINGES
1) Open prover door.
2) Open control panel.
3) Unscrew two screws securing magnetic
door catch to prover.
Two Screws
Figure 6.3.19
NOTE: A spanner may be required to hold
the nuts located inside the control panel,
behind the magnetic catch.
4) Replace magnetic catch and re-assemble
in reverse order.
6.3.12 HOTWIRE
1) Open control panel (refer 6.2.1) and
prover door.
2) Remove silicone extrusion seal strips from
prover door frame.
Silicone
Extrusion
Strips (3)
1) Open prover door.
2) Lift door vertically off hinges.
3) Drill out rivets securing hinges to door and
E87 prover (two rivets per hinge), and remove hinges.
Door
Hinges
Hinge
Rivets
Figure 6.3.18
4) Rivet new hinges to door and E87 prover.
5) Re-hang door on prover.
Revision 2/F3520
Figure 6.3.20
3) Remove hotwire retaining sleeves (9) from
prover frame.
Retaining
Sleeves (9)
Figure 6.3.21
4) Remove hotwire from prover, noting
wiring positions.
MOTOR & ELEMENTS
013998 Motor and Fan (220-240V)
013999 Motor and Fan (110V)
014001 Dry Element (220-240V)
015759 Dry Element (110V)
015224 Wet Element (220-240V)
015230 Wet Element (110V)
DOOR
021461 Door Assembly
021468 Handle
017575 Hinge
018947 Magnetic catch
RACKS
015477 Side Rack
STACKING KIT
21547 Double Stacking Kit
Revision 2/F3520
-22-
Page 21
10. ACCESSORIES
DOUBLE STACKING KIT (PART NO
021547) - For use with E32 / G32 con-vection ovens
6” LEG OPTION (PART NO 15274)
DRIP TROUGH (PART NO 15295)
STANDOFF KIT (PART NO 21336) -
Enables prover to take 16” wide trays
Revision 2/F3520
-23-
Page 22
11.1 MAIN ASSEMBLY
11. PARTS DIAGRAMS
Revision 2/F3520
-24-
Page 23
Pos Part No. Description
1 015236 WRAPPER
2 015253 SUPPORT DISC
3 ---------- INSULATION
4 015483 LINER
5 018738 LINER SUPPORT
6 015244 RACK MOUNTING PLATE
7 015278 FAN LOCATING BRACKET
8 013998 FAN/MOTOR ASSEMBLY - 240V
013999 FAN/MOTOR ASSEMBLY - 110V
9 015243 FAN CLAMP BRACKET
10 015242 FAN COVER
11 015241 DUCTING
12 018947 MAGNETIC CATCH
13 015249 CAPILLARY BRACKET
14 021342 LAMP HOLDER ASSEMBLY
014218 BULB (15w, 240V)
014219 BULB (15w, 110V)
15 015248 DUCTING HEAT SHIELD
16 014001 DRY ELEMENT (600w, 240V)
015759 DRY ELEMENT (600w, 110V)
17 015224 WET ELEMENT (800w, 240V)
015230 WET ELEMENT (800w, 110V)
18 012272 CLAMP TOP
19 012271 CLAMP BOTTOM
20 014725 HANGER STUD
21 015474 WATER TROUGH
22 002138 CABLE CLAMP
23 002441 INSULATOR
24 018737 BASE STIFFENER
25 015237 SPACER TUBE
26 015235 BACK PANEL
27 015234 BASE PANEL
28 017858 CABLE CLAMP
29 013885 CASTOR - 5" RIGID
30 013890 CASTOR - 5" SWIVEL
31 015240 CONTROL HOUSING
32 013586 MAINS TERMINAL BLOCK
33 015477 SIDE RACK
34 015481 HANGER SPACER
35 016650 FRAME
36 015539 HEATING WIRE (100w, 240V)
015538 HEATING WIRE (100w, 110V)
37 015238 STRIP INSERT - SHORT
38 015239 STRIP INSERT - LONG
39 021464 CATCH PLATE
40 021461 DOOR ASSEMBLY
41 021468 DOOR HANDLE
42 ---------- CONTROL PANEL ASSEMBLY (REFER TO SECTION 11.2)
43 015295 DRIP TROUGH (OPTIONAL EXTRA)
44 017575 DOOR HINGE
Revision 2/F3520
-25-
Page 24
11.2 CONTROL PANEL ASSEMBLY
Pos Part No. Description
1 004726 CONTROL PANEL BAKBAR ºC
004805 CONTROL PANEL BLUE SEAL °C
004724 CONTROL PANEL MOFFAT ºF
2 021473 POWER SWITCH (240V)
021514 POWER SWITCH (110V)
3 020849 PILOT LIGHT (240V)
023857 PILOT LIGHT (110V)
4 021472 KNOB - HUMIDITY
5 020823 KNOB - THERMOSTAT
6 015485 THERMOSTAT 50-80ºC (120-175°F)
7 014233 THERMOSTAT 0-40ºC (32 - 105°F)
Revision 2/F3520
-26-
Page 25
11. SERVICE CONTACTS
AUSTRALIA
VICTORIA - MOFFAT PTY
HEAD OFFICE AND MAIN WAREHOUSE
740 Springvale Road Tel (03) 9518 3888
Mulgrave VIC 3170 Fax (03) 9518 3838
Spare Parts Department Free Call 1800 337 963
Fax (03) 9518 3895
NEW SOUTH WALES - MOFFAT PTY
Unit 8/142 James Ruse Drive
Rosehill NSW 2142
Spare Parts Free Call 1800 337 963
Fax (03) 9518 3895
QUEENSLAND - MOFFAT PTY
30 Prosperity Place
Geebung QLD 4034
Spare Parts Free Call 1800 337 963
Fax (03) 9518 3895
SOUTH AUSTRALIA - MOFFAT PTY
Suite 8/71 Fullarton Rd Tel (08) 8431 0522
Kent Town SA 5067
Spare Parts Free Call 1800 337 963
WESTERN AUSTRALIA - MOFFAT PTY
PO Box 689 Tel (08) 9305 8855
Joondalup Business Centre WA 6027
Spare Parts Free Call 1800 337 963
NATIONAL COVERAGE FOR 24 HOUR SERVICE OR MAINTENANCE DIAL
FREE CALL 1800 622 216 (AUSTRALIA ONLY)
CANADA
Lessard Agencies Limited Tel (416) 766 2764
PO Box 97 Fax (416) 760 0394
Stn “D” Free Call 1 888 537 7273
Toronto, ONT M6P 3J5
NEW ZEALAND
CHRISTCHURCH - MOFFAT LTD
16 Osborne St Free Call 0800 Moffat
PO Box 10-001 (0800 663 328)
Christchurch
Spare Parts Tel (03) 389 1007
Fax (03) 389 1276