Warning! Dangerous electrical voltage!
Before commencing the installation
• Disconnect the power supply of the device.
• Ensure that devices cannot be accidentally restarted.
• Verify isolation from the supply.
• Earth and short circuit.
• Cover or enclose neighbouring units that are live.
• Follow the engineering instructions (AWA) of the device concerned.
• Only suitably qualified personnel in accordance with EN 50110-1/-2 (VDE 0105 Part 100) may work on this device/system.
• Before installation and before touching the device ensure that you are free of electrostatic charge.
• The functional earth (FE) must be connected to the protective earth (PE) or to the potential equalisation. The system installer is responsible for implementing this connection.
• Connecting cables and signal lines should be installed so that inductive or capacitive interference does not impair the automation functions.
• Install automation devices and related operating elements in such a way that they are well protected against unintentional operation.
• Suitable safety hardware and software measures should be implemented for the I/O interface so that a line or wire breakage on the signal side does not result in undefined states in the automation devices.
• Ensure a reliable electrical isolation of the low voltage for the 24 volt supply. Only use power supply units complying with IEC 60364-4-41 (VDE 0100 Part 410) or HD 384.4.41 S2.
• Deviations of the mains voltage from the rated value must not exceed the tolerance limits given in the specifications, otherwise this may cause malfunction and dangerous operation.
• Emergency stop devices complying with IEC/EN 60204-1 must be effective in all operating modes of the automation devices. Unlatching the emergency-stop devices must not cause restart.
• Devices that are designed for mounting in housings or control cabinets must only be operated and controlled after they have been installed with the housing closed. Desktop or portable units must only be operated and controlled in enclosed housings.
• Measures should be taken to ensure the proper restart of programs interrupted after a voltage dip or failure. This should not cause dangerous operating states even for a short time. If necessary, emergency-stop devices should be implemented.
• Wherever faults in the automation system may cause damage to persons or property, external measures must be implemented to ensure a safe operating state in the event of a fault or malfunction (for example, by means of separate limit switches, mechanical interlocks etc.).
Moeller GmbH
Safety instructions
I
II
Hardware Device Description Embedded HMI XVH-3x0
Notes
01/05 AWB2776-1559GB © by Moeller GmbH
3
Device Description Embedded HMI XVH-3x0 Hardware
Contents
Contents
1 Explanation of Symbols ..................................................................................... 5
2 Introduction......................................................................................................... 6
2.1 Benefits of the XVH-330/340-57 Systems...............................................................6
2.2 Aim and purpose of this document..........................................................................7
2.3 List of documents .................................................................................................... 7
3 Device Versions .................................................................................................. 8
3.1 Scope of delivery..................................................................................................... 8
3.2 Options.................................................................................................................... 8
4 Commissioning ................................................................................................... 9
4.1 Overview of the terminals........................................................................................ 9
4.2 General notes on cabling....................................................................................... 10
4.3 Connection to the power supply............................................................................ 10
4.4 Ethernet................................................................................................................. 11
4.5 USB device............................................................................................................ 12
4.6 Expansion module interfaces (ComModule) optional............................................ 13
4.6.1 CAN............................................................................................................................13
4.6.2 MPI.............................................................................................................................14
5 System Control Button (CTRL)........................................................................ 15
6 System settings ................................................................................................ 16
7 CompactFlash Slot ........................................................................................... 17
8 Expansion and Configuration Options ........................................................... 18
8.1 Device interventions ..............................................................................................18
9 Function and Control LEDs.............................................................................. 19
10 Mounting Instructions ...................................................................................... 21
10.1 General mounting instructions............................................................................ 21
10.2 Standard front..................................................................................................... 22
10.3 Mechanical dimensions......................................................................................23
10.4 Front panel cutout standard front....................................................................... 24
11 Notes on the Touch Screen.............................................................................. 25
11.1 Infra-Red Touch ................................................................................................. 25
11.2 Resistive Touch.................................................................................................. 26
12 Display Technology, Backlight........................................................................ 27
13 Maintenance and Repair................................................................................... 28
14 Disposal............................................................................................................. 29
15 Technical Data................................................................................................... 30
16 EU Conformity/Safety ....................................................................................... 32
16.1 EMC ................................................................................................................... 32
16.2 Explosion protection...........................................................................................32
16.2.1 Zone 22, Category 3D ............................................................................................. 32
17 Safety / North American Approvals................................................................. 33
4
01/05 AWB2776-1559GB
© by Moeller GmbH
Hardware Device Description Embedded HMI XVH-3x0
Explanation of Symbols
1 EXPLANATION OF SYMBOLS
Danger warnings
The following information is for your personal safety and the prevention of damage to the product described or connected devices.
Safety instructions and warnings for the prevention of danger to the life and health of users or service personnel, and for the prevention of damage are highlighted in this document by the following pictograms. “Warning” and “Information” pictograms are shown in this document.
Warnings indicate the following:
Death, serious injury or substantial material damage may occur if the related safety measures are not implemented.
The individual “Warning” pictograms have the following meaning:
Caution! General! Is an instruction that must be strictly observed in order to protect oneself and the device from hazards relating to the operation of the device and to ensure the proper use of the device.
Caution! Dangerous voltage! There is a danger of electric shock if a live part is touched.
Caution! Observe ESD measures! Electrostatic discharge may damage or destroy electronic components.
Information pictograms indicate the following:
Important information about the product or the relevant section of the document, requiring the particular attention of the reader.
The “Information” pictogram has the following meaning:
Indicates important and instructional information.
01/05 AWB2776-1559GB © by Moeller GmbH
5
Device Description Embedded HMI XVH-3x0 Hardware
Introduction
2 INTRODUCTION
2.1 BENEFITS OF THE XVH-330/340-57 SYSTEMS
The PANEL in conjunction with Galileo is a professional and powerful data management and visualization system for machine and system building and for building services automation.
BENEFIT The device is a genuine communication professional. The onboard Ethernet and USB
Device interfaces, as well as the expansion slot for Com modules (CAN, RS 232, etc.) can even be used as a gateway for different PLC and bus systems simultaneously.
INNOVATION State-of-the-art technologies such as FTP server, remote client/server, OPC
client/server, printing via Ethernet, UNICODE support and many additional features fulfill every possible need.
BENEFIT The operating system, the application programs and data can be exchanged easily
without any other technical resources.
The PANELs use the benefits of a seamless Ethernet and IT-based (WEB-based) automation solution and thus offer an unlimited range of possible applications.
6
01/05 AWB2776-1559GB
© by Moeller GmbH
Hardware Device Description Embedded HMI XVH-3x0
Introduction
2.2 AIM AND PURPOSE OF THIS DOCUMENT
This device description is a reference for the installation, the terminals, technical data, commissioning, operating and maintenance.
2.3 LIST OF DOCUMENTS
Subject Document Doc. No.
[1]
Installation
[2]
Networks
[3]
Windows CE
(this list of documents is not final)
Installation instructions General wiring instructions AWB2776-1569 Networks in brief AWB2776-1568 PANEL with WindowsCE AWB2776-1553
01/05 AWB2776-1559GB © by Moeller GmbH
7
Device Description Embedded HMI XVH-3x0 Hardware
Device Versions
3 DEVICE VERSIONS
The XVH-330/340-57 Systems are available in the following versions:
Type Touch Front / Type of fixing
XVH-330-57XXX-x-13-x Resistive Standard / Fixing brackets XVH-340-57XXX-x-13-x Infra-red Standard / Fixing brackets
3.1 SCOPE OF DELIVERY
Each device version is supplied with the following accessories:
Device version: XVH-330-57 XVH-340-57
-x-13-x
-x-13-x
Resistive touch Standard front IR touch Standard front
Accessories (included) 4 fixing brackets for mounting the device Sealing strip(for IP65) Power supply plug connector CompactFlash cover for the CompactFlash slot Resistive touch pen
3.2 OPTIONS
OS Flash Additional fixing brackets for IP65
8
01/05 AWB2776-1559GB
© by Moeller GmbH
Hardware Device Description Embedded HMI XVH-3x0
Commissioning
4 COMMISSIONING
4.1 OVERVIEW OF THE TERMINALS
Ethernet
ComModule plug
(e.g. CAN)
Supply
USB Device
ÎLED functions see chap. 9.
The Ethernet, ComModule (e.g. CAN) and Supply terminals are located on the right of the device when viewed from the rear. The terminal for the USB interface is located on the left of the device.
01/05 AWB2776-1559GB © by Moeller GmbH
9
Device Description Embedded HMI XVH-3x0 Hardware
Commissioning
4.2 GENERAL NOTES ON CABLING
Cabling should be carried out with special care in order to ensure interference-free operation. The EMC values stated in the technical data can only be guaranteed if the connections and cables are prepared according to the specifications stated.
The cabling must be laid separately from low-voltage cables or isolated with double or reinforced insulation.
Î Further information: Installation instructions, General wiring instructions [1]
4.3 CONNECTION TO THE POWER SUPPLY
System supply 24 VDC SELV (safety extra low voltage)
Not isolated Current consumption Î Chapter 15 Fuse / protection Internal fuse / protection against reverse polarity Housing potential Connected to 0 V terminal Terminal type Screw terminal (screwdriver No. 3), pluggable Cross section min. 0.75 mm2 / max. 2.5 mm2 (lead or wire)
min. AWG24 / max. AWG12 Stripping length 7 mm
Î Further technical data: Chapter 15
Plug connector: Phönix MSTB 2.5/3-ST-5.08 Phönix Order No. 1757022; Supplied with unit (view from the wiring side)
+24 VDC +24 VDC power supply GND Functional ground, connected with housing (connection not compulsory) 0 V 0 V power supply (connected with housing)
+24 VDC GND 0 V