MOELLER MFD CP8 ME Technical data

Type: MFD−CP8−ME Article No.: 267164
IP20, cage clamp terminals
Ordering information
Cage clamp terminals
Description
Serial interface Suitable for connection of Easy expansions
Power supply V DC 24 V DC
Notes concerning the product group
Backup of real−time clock (only for appropriate devices)
Backup time (hours)
Operating time (years)
General
1
Standards
EN 61000−6−1/−2/−3/−4, IEC 60068−2−6, IEC 60068−2−27
Weight kg 0,145
Fitted onto the fixing shaft of the display or onto top−hat rail to IEC/EN 60715 , 35 mm depth (without display)
Mounting
(mounting plate thinckness: 1 – 4 mm) or by instrument feet (without display). When using top−hat rail MFD−TS−144, the mounting plate thickness is 1 – 6 mm.
Terminal capacities
Solid mm20.24 (AWG 24 – 12)
Flexible with ferrule mm20.22.5 (AWG 24 – 12)
Standard screwdriver mm 3.5 × 0.6
Climatic environmental conditions
−25 to 55, cold as per IEC
Operating ambient temperature °C
60068−2−1, heat as per IEC 60068−2−2
Condensation
Take appropriate measures to prevent condensation
Storage °C −40/+70
Relative humidity, non−condensing (IEC/EN 60068−2−30)
% 5 – 95
Air pressure (operation) hPa 795 – 1080
Ambient conditions, mechanical
Pollution degree 2
Degree of protection (IEC/EN 60529) IP 20
Vibrations (IEC/EN 60068−2−6)
Constant amplitude 0.15 mm Hz 10 – 57
Constant acceleration 2 g Hz 57 – 150
Mechanical shock resistance (IEC/EN 60068−2−27) semi−sinusoidal 15 g/11
Impacts 18
ms
Drop to IEC/EN 60068−2−31
Free fall, packaged (IEC/EN 60068−2−32)
Drop
height
mm 50
m 1
Mounting position horizontal, vertical
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN
2
Loading...