MOELLER MFD CP8 ME Technical data

Type: MFD−CP8−ME Article No.: 267164
IP20, cage clamp terminals
Ordering information
Cage clamp terminals
Description
Serial interface Suitable for connection of Easy expansions
Power supply V DC 24 V DC
Notes concerning the product group
Backup of real−time clock (only for appropriate devices)
Backup time (hours)
Operating time (years)
General
1
Standards
EN 61000−6−1/−2/−3/−4, IEC 60068−2−6, IEC 60068−2−27
Weight kg 0,145
Fitted onto the fixing shaft of the display or onto top−hat rail to IEC/EN 60715 , 35 mm depth (without display)
Mounting
(mounting plate thinckness: 1 – 4 mm) or by instrument feet (without display). When using top−hat rail MFD−TS−144, the mounting plate thickness is 1 – 6 mm.
Terminal capacities
Solid mm20.24 (AWG 24 – 12)
Flexible with ferrule mm20.22.5 (AWG 24 – 12)
Standard screwdriver mm 3.5 × 0.6
Climatic environmental conditions
−25 to 55, cold as per IEC
Operating ambient temperature °C
60068−2−1, heat as per IEC 60068−2−2
Condensation
Take appropriate measures to prevent condensation
Storage °C −40/+70
Relative humidity, non−condensing (IEC/EN 60068−2−30)
% 5 – 95
Air pressure (operation) hPa 795 – 1080
Ambient conditions, mechanical
Pollution degree 2
Degree of protection (IEC/EN 60529) IP 20
Vibrations (IEC/EN 60068−2−6)
Constant amplitude 0.15 mm Hz 10 – 57
Constant acceleration 2 g Hz 57 – 150
Mechanical shock resistance (IEC/EN 60068−2−27) semi−sinusoidal 15 g/11
Impacts 18
ms
Drop to IEC/EN 60068−2−31
Free fall, packaged (IEC/EN 60068−2−32)
Drop
height
mm 50
m 1
Mounting position horizontal, vertical
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN
2
61000−4−2, Level 3, ESD)
Air discharge kV 8
Contact discharge kV 6
Electromagnetic fields (IEC/EN 61000−4−3, RFI)
Radio interference suppression (EN
55011)
V/m 10
EN 55011 Class B, EN 55022 Class B
Burst pulses (IEC/EN 61000−4−4, level 3)
Supply cables kV 2
Signal lines kV 2
High−energy pulses (surge) (IEC/EN 61000−4−5)
High−energy pulses (surge) (IEC/EN 61000−4−5, level 2)
Immunity to line−conducted interference to (IEC/EN 61000−4−6)
kV 2 (supply cables, symmetrical)
kV
0.5 (supply cables, symmetrical)
V 10
Insulation resistance
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, no. 142
Insulation resistance EN 50178
Backup/accuracy of the real−time clock
Accuracy of the real−time clock Normally ±5 s/day (±0.5 hyear)
Repetition accuracy of timing relays
Accuracy of timing relays (of values) % ± 0,02
Resolution
Range “S” ms 5
Range “M:S” s 1
Range “H:M” min 1
Retentive memory
Write cycles of the retentive memory 1010 (read/write cycles)
Power supply
Rated operational voltage U
e
V 24 DC (−15+20 %)
Admissible range V DC 20,4 – 28,8
Residual ripple % 5
Input current
at 24 V DC mA Normally 200
Voltage dips (IEC/EN 61131−2) ms 10
Power loss
Heat dissipation at 24 V DC W 3.4
3
Dimensions
Dimensions
Moeller GmbH, Hein−Moeller−Str. 7−11, D−53115 Bonn E−Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net Copyright 2006 by Moeller GmbH. Subject to modifications. HPL−C2006GB−INT V2.3