MOELLER LSE 02 Technical data

Type: LSE−02 Article No.: 266122 Sales text CB electr.adjustable,2B
Basic unit
Visible status display, comparable with positive opening function
Conditional short−circuit, restart after reset
Ordering information
Auxiliary contacts: = safety function, by positive opening to IEC/EN 60947−5−1
N/C = Normally closed 2 N/C
Housing Insulated material
Contact sequence
Contact diagram
1
Colour of enclosure cover
Note concerning the product
LSE−11 and LSE−02: Individual operating point adjustment:
circuit example for series connection:
LSE−11 and LSE−02 can be used in safety circuits
S1 is connected to 24 V DC
S2, S3 each switch with a delay of 0.7 s
R1, R2 e.g. series element M22−XLED60 (2820 /0.5 W)
Notes concerning the table header
Contact travel
= contact closed
= contact open
2
= setting range
Notes concerning the product group
Cage Clamp is a registered trademark of Wago Kontakttechnik, 32432 Minden, Germany.
General
Standards
IEC/EN 60947 EN 61000−4
Damp heat, constant, to IEC
Climatic proofing
60068−2−78; damp heat, cyclical, to IEC 60068−2−30
Ambient temperature °C ... 25...+70
Mounting position As required
Protection type IP66, IP67
Terminal capacity of screw terminal and Cage Clamp
Solid mm21 × (0.5 – 2.5)
Flexible with ferrules to DIN 46228 mm21 × (0.5 – 1.5)
Power supply
Rated voltage U
e
V DC 12 – 30
Rated operational current 12 V I
e
A 0,015
24 V I mA 18 30 V I A 0,019
Contacts/switching capacity
Overvoltage category/pollution degree
III/3
Rated operational current
DC−13 24 V I
e
A 0,2
Repetition accuracy mm 0,02
Mechanical variables
Lifespan
Snap−action contact Operations × 1063 (electronic)
Contact temperature of roller head °C 100
Mechanical shock resistance (half−sinusoidal shock, 20 ms)
Basic unit g 30
Operating frequency Operations/h 3000
3
Switching point
0.5 – 5.5 mm, freely adjustable
Hysteresis mm 0.4
Contact sequence (contact closed open Zw = positive opening
mm 0.04
clearance)
Actuation
Mechanical
Actuating force at beginning/end of stroke
Basic units N 3.5/8.0
LS(M)−XP N 1.0/8.0
LS(M)−XL N 1.0/8.0
LS(M)−XLA N 1.0/8.0
Actuating torque of rotary drives Nm 0,2
Max. operating speed with DIN cam
Basic units for angle of actuation = 0°/30° m/s 1/0.5
LS(M)−XRL for angle of actuation = 0° m/s 1,5
LS(M)−XRLA for angle of actuation
= 30°, L =
125 mm
m/s 1,5
LS(M)−XRR for L = 130 mm m/s 1,5
LS(M)−XL for angle of actuation = 30°/45° m/s 1
LS(M)−XLA for angle of actuation = 30°/45° m/s 1
LS(M)−XP for angle of actuation = 0°/30° m/s 1/1
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61000−4−2, Level 3, ESD)
Air discharge kV 8
Contact discharge kV 4
Electromagnetic fields (IEC/EN 61000−4−3, RFI)
V/m 10
Burst pulses (IEC/EN 61000−4−4, level 3)
Supply cables kV 2
Signal lines kV 2
High−energy pulses (surge) (IEC/EN 61000−4−5)
kV 0.5
Immunity to line−conducted interference to (IEC/EN 61000−4−6)
Notes
4
V 10
Notes
The following applies for LSE−11 and LSE−02: ensure that the power supply operates correctly when setting the operating point.
Notes
Cage Clamp is a registered trademark of Wago Kontakttechnik, 32423 Minden, Germany.
Accessories for the Cage Clamp terminals from Wago:
Jumper insert, grey, Wago article no. 264−402
Tightening torque of cover screws: 0.8 Nm ±0.2 Nm only with LS (insulated version) Fixing screws 2 x M4 30 MA = 1.5 Nm
Moeller GmbH, Hein−Moeller−Str. 7−11, D−53115 Bonn E−Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net Copyright 2006 by Moeller GmbH. HPL−C2007G V2.1
5
Loading...