Input current
at 115/120 V AC 60 HzmANormally 70
at 230/240 V AC 50 HzmANormally 35
Voltage dips (IEC/EN 61131−2)ms20
Power loss
at 115/120 V ACVANormally10
at 115/230 V ACVANormally10
Digital inputs 115/230 V AC
Number12
Status indicationLCD−display (if present)
Potential isolation
From power supplyNo
Between digital inputsNo
From the outputsYes
Rated voltage L (sinusoidal)
On 0 signalV AC0 – 40
On 1 signalV AC79 – 264
Rated frequencyHz50 – 60
Delay time
Delay time (0 – 1/1 – 0) I1 to I6, I9
to I12, R1 to R12
Debounce ON 50/60 Hzms8066
Debounce OFF 50/60 Hzms2016
Delay time I7, I8 (1 – 0)
Debounce ON 50/60 Hzms8066
Debounce OFF 50/60 Hzms2016
Delay time I7, I8 (0 – 1)
Debounce ON 50/60 Hzms8066
Debounce OFF 50/60 Hzms2016
Max. admissible cable length (per
input)
I1 to I6m40
I7, I8mNormally100
I9 to I12mNormally40
Relay outputs
Number6
Outputs in groups of1
Parallel switching of outputs for
increased output
4
Not permissible
Protection of an output relay
Miniature circuit−breaker B16
or fuse 8 A (slow)
Potential isolation
From power supplyYes
From the inputsYes
From the PC interface, memory
card NET network, EASY−Link
No
Safe isolationV AC300
Basic insulationV AC600
Lifespan, mechanicalOperations× 10610
Contacts
Conventional thermal current (10 A
UL)
Recommended for load: 12 V
AC/DC
Short−circuit−proof cos = 1,
characteristic B16 at 600 A
Short−circuit−proof cos = 0.5 to
0.7, characteristic B16 at 900 A
Rated impulse withstand voltage
U
of contact coil
imp
Rated operational voltageU
Rated insulation voltageU
Safe isolation to EN 50178
between coil and contact
e
i
A8
mA> 500
A16
A16
kV6
V AC250
V AC250
V AC300
Safe isolation to EN 50178
between 2 contacts
V AC300
Making capacity
AC−15, 250 V AC, 3 A (600
Ops./h)
DC−13 L/R 150 ms 24 V DC, 1 A
(500 Ops./h)
Operations300000
Operations200000
Breaking capacity
AC−15, 250 V AC, 3 A (600
Ops./h)
DC−13 L/R 150 ms 24 V DC, 1 A
(500 Ops./h)
Operations300000
Operations200000
Filament bulb load
1000 W at 230/240 V ACOperations25000
500 W at 115/120 V ACOperations25000
Fluorescent lamp load
5
Fluorescent lamp load 10 × 58 W
at 230/240 V AC
With upstream electrical deviceOperations25000
UncompensatedOperations25000
Fluorescent lamp load 1 × 58 W at
230/240 V AC, conventional,
Operations25000
compensated
Switching frequency
Mechanical operations× 10610
Switching frequencyHz10
Resistive load/lamp loadHz2
Inductive loadHz0,5
UL/CSA
Uninterrupted current at 240 V ACA10
Uninterrupted current at 24 V DCA8
AC
Control Circuit Rating Codes
(utilization category)
B 300 Light Pilot Duty
Max. rated operational voltageV AC300
Max. thermal uninterrupted current
= 1 at B 300
Max. make/break capacity 1 at B
300
A5
VA3600360
DC
Control Circuit Rating Codes
(utilization category)
R 300 Light Pilot Duty
Max. rated operational voltageV DC300
Max. thermal uninterrupted current
at R 300
A1
Max. make/break capacity at R 300VA2828
Notes
Dimensions
Notes
For additional Technical Data EASY5... and EASY7... AWB2528−1508GB,