Type: EASY512−DA−RC
Article No.: 274106
Ordering information
Relay outputs Quantity 4
Power supply V DC 12 V DC
Description
8 digital inputs (2 inputs available as analog inputs)•
4 relay outputs•
LCD display•
Operating buttons•
Screw terminals•
Timer•
Notes concerning the product group
Backup of real−time clock (only for appropriate devices)
Backup time (hours)
1
Operating time (years)
General
EN 55011, EN 55022,
Standards
IEC/EN 61000−4, IEC
60068−2−6, IEC
60068−2−27
Dimensions (W × H × D) mm 71.5 × 90 × 58 (4 PE)
Weight kg 0,2
Top−hat rail IEC/EN 60715,
Mounting
35 mm or screw fixing using
fixing brackets
ZB4−101−GF1 (accessories)
Terminal capacities
Solid mm20.24 (AWG 22 – 12)
Flexible with ferrule mm20.22.5 (AWG 22 – 12)
Standard screwdriver mm 3.5 × 0.8
Max. tightening torque Nm 0,6
Climatic environmental conditions
−25 to 55, cold as per IEC
Operating ambient temperature °C
60068−2−1, heat as per IEC
60068−2−2
Condensation
Take appropriate measures
to prevent condensation
LCD display (clearly legible) °C 055
Storage °C −40/+70
Relative humidity, non−condensing
(IEC/EN 60068−2−30)
% 5 – 95
Air pressure (operation) hPa 795 – 1080
Corrosion resistance
IEC/EN 60068−2−42 4 days SO2cm3/m310
IEC/EN 60068−2−43 4 days H2S cm3/m31
Ambient conditions, mechanical
Pollution degree 2
Degree of protection (IEC/EN
60529)
IP 20
Vibrations (IEC/EN 60068−2−6)
Constant amplitude 0.15 mm Hz 10 – 57
Constant acceleration 2 g Hz 57 – 150
Mechanical shock resistance
(IEC/EN 60068−2−27)
Impacts 18
semi−sinusoidal 15 g/11 ms
2
Drop to IEC/EN 60068−2−31 Drop height mm 50
Free fall, packaged (IEC/EN
60068−2−32)
m 1
Mounting position horizontal/vertical
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN
61000−4−2, Level 3, ESD)
Air discharge kV 8
Contact discharge kV 6
Electromagnetic fields (IEC/EN
61000−4−3, RFI)
Radio interference suppression (EN
55011)
V/m 10
EN 55011 Class B, EN
55022 Class B
Burst pulses (IEC/EN 61000−4−4,
level 3)
Supply cables kV 2
Signal lines kV 2
High−energy pulses (surge) (IEC/EN
61000−4−5)
kV
2 (supply cables,
symmetrical, EASY...AC)
High−energy pulses (surge) (IEC/EN
61000−4−5, level 2)
Immunity to line−conducted
interference to (IEC/EN 61000−4−6)
kV
0.5 (supply cables,
symmetrical, EASY...DC)
V 10
Insulation resistance
Clearance in air and creepage
distances
EN 50178, UL 508, CSA
C22.2, no. 142
Insulation resistance EN 50178
Backup/accuracy of the real−time clock
Accuracy of the real−time clock typ. ± 5 (± 0.5 hannually)
Repetition accuracy of timing relays
Accuracy of timing relays (of values) % ± 1
Resolution
Range “S” ms 10
Range “M:S” s 1
Range “H:M” min 1
Retentive memory
Write cycles of the retentive memory 1000000 (106)
Power supply
Rated operational voltage U
e
V 12 DC (−15/+30%)
Admissible range V DC 10,2 – 15,6
Residual ripple % 5
3