Moeller easy500, easy700 User Manual

Page 1
Building Automation SystemsIndustrial Automation
User Manual
05/04 AWB2528-1508GB
easy500, easy700 Control Relay
Page 2
All brand and product names are trademarks or registered trademarks of the owner concerned.
Rückenbreite festlegen! (1 Blatt = 0,106 mm)
Page 3
I
Before commencing the installation
• Disconnect the power supply of the device.
• Ensure that devices cannot be accidentally restarted.
• Verify isolation from the supply.
• Earth and short circuit.
• Cover or enclose neighbouring units that are live.
• Follow the engineering instructions (AWA) of the device concerned.
• Only suitably qualified personnel in accordance with EN 50110-1/-2 (VDE 0105 Part 100) may work on this device/system.
• Before installation and before touching the device ensure that you are free of electrostatic charge.
• The functional earth (FE) must be connected to the protective earth (PE) or to the potential equalisation. The system installer is responsible for implementing this connection.
• Connecting cables and signal lines should be installed so that inductive or capacitive interference does not impair the automation functions.
• Install automation devices and related operating elements in such a way that they are well protected against unintentional operation.
• Suitable safety hardware and software measures should be implemented for the I/O interface so that a line or wire breakage on the signal side does not result in undefined states in the automation devices.
• Ensure a reliable electrical isolation of the low voltage for the 24 volt supply. Only use power supply units complying with IEC 60364-4-41 (VDE 0100 Part 410) or HD 384.4.41 S2.
• Deviations of the mains voltage from the rated value must not exceed the tolerance limits given in the specifications, otherwise this may cause malfunction and dangerous operation.
•Emergency stop devices complying with IEC/EN 60204-1 must be effective in all operating modes of the automation devices. Unlatching the emergency-stop devices must not cause restart.
• Devices that are designed for mounting in housings or control cabinets must only be operated and controlled after they have been installed with the housing closed. Desktop or portable units must only be operated and controlled in enclosed housings.
Moeller GmbH
Safety instructions
Warning! Dangerous electrical voltage!
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 4
II
• Measures should be taken to ensure the proper restart of programs interrupted after a voltage dip or failure. This should not cause dangerous operating states even for a short time. If necessary, emergency­stop devices should be implemented.
• Wherever faults in the automation system may cause damage to persons or property, external measures must be implemented to ensure a safe operating state in the event of a fault or malfunction (for example, by means of separate limit switches, mechanical interlocks etc.).
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 5
1
05/04 AWB2528-1508GB
About This Manual 9 Device designation 9 Writing conventions 10
1 easy 11
Target readership 11 Proper use 11 – Improper use 11 Overview 12 Versions 15 – Type reference 17 easy operation 19 –Buttons 19 – Moving through menus and choosing values 19 – Selecting main and system menu 20 – easy Status display 21 – Status display for local expansion 21 – Advanced Status display 22 – easy LED display 22 –Menu structure 23 – Selecting or toggling between menu items 28 – Cursor display 28 – Setting values 29
Content
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 6
Content
2
05/04 AWB2528-1508GB
2 Installation 31
Mounting 31 Connecting the expansion device 34 Terminals 35 –Tools 35 – Cable cross-sections 35 Connecting the power supply 35 – Cable protection 35 – Supplying AC units 36 – Supplying DC units 37 Connecting the inputs 39 – Connecting easy AC digital inputs 39 – Connecting easy DC digital inputs 44 – Connecting easy DC analog inputs 46 – Connecting high-speed counters and
frequency generators 51 Connecting the outputs 53 – Connecting relay outputs 54 – Connecting transistor outputs 56 Expanding inputs/outputs 59 – Local expansion 59 – Remote expansion 60 Connecting bus systems 62
3 Commissioning 63
Switching on 63 Setting the menu language 64 easy operating modes 65 Creating your first circuit diagram 66 – Circuit diagram display 68 – From the first contact to the output coil 69 – Wiring 70 – Testing the circuit diagram 71 – Deleting the circuit diagram 73 – Fast circuit diagram entry 73
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 7
Content
3
05/04 AWB2528-1508GB
4 Wiring with easy 75
Operation of easy 75 – Buttons for editing circuit diagrams and
function relays 75 – Operation 76 – Relay, function relays 79 – Saving and loading circuit diagrams 82 Working with contacts and relays 83 – Input and output contacts 83 – Creating and modifying connections 86 – Inserting and deleting a rung 88 – Switching with the cursor buttons 89 – Checking the circuit diagram 90 – Coil functions 91 Function relays 97 – Example with function relay timer and
counter relay 98 Analog value comparator/threshold value switch 104 – Circuit diagram display with analog value
comparator 105 – Compatibility between easy400 and easy500,
easy600 and easy700 107 – Parameter display in RUN mode 108 – Resolution of the analog inputs 108 – Function of the analog value comparator 109 Counters 117 – Function of the counter function relay 121 High-speed counters, easy-DA, easy-DC 125 – Frequency counters 125 – High-speed counter 131 Text display 137 – Wiring a text display 138 – Retention 138 – Scaling 139 – Function 139 – Text entry 140 – Character set 140 – Entering a setpoint in a display 141
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 8
Content
4
05/04 AWB2528-1508GB
7-day time switch 143 – Parameter display and parameter set for
7-day time switch: 144 – Changing time switch channel 145 – Function of the 7-day time switch 146 Operating hours counter 149 – Value range of the operating hours counter 150 – Accuracy of the operating hours counter 150 – Function of the operating hours counter
function block 150 Timing relays 154 – Parameter display and parameter set for a
timing relay: 155 – Retention 156 – Timing relay modes 157 – Time range 157 – Function of the timing relay function block 160 – Timing relay examples 168 Jumps 171 – Function 171 – Power flow display 172 Year time switch 174 – Wiring of a year time switch 174 – Parameter display and parameter set for the
year time switch: 175 – Changing time switch channel 176 – Entry rules 176 – Function of the year time switch 178 Master reset 181 – Operating modes 182 – Function of the master reset function relay 182
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 9
Content
5
05/04 AWB2528-1508GB
Basic circuits 183 – Negation (contact) 183 – Negation (coil) 184 – Maintained contact 184 – Series circuit 184 – Parallel circuit 185 – Parallel circuit operating like a series
connection of make contacts 186
– Parallel circuit operating like a series
connection of break contacts 187 – Two-way circuit 187 – Self-latching 188 – Impulse relay 189 – Cycle pulse on rising edge 190 – Cycle pulse on falling edge 190 Example circuits 191 – Star-delta starting 191 – 4x shift register 193 – Running light 197 – Stairwell lighting 199
5easy Settings 203
Password protection 203 – Password setup 204 – Selecting the scope of the password 205 – Activating the password 206 – Unlocking easy 207 Changing the menu language 209 Changing parameters 210 – Adjustable parameters for function relays 211 Setting date, time and daylight saving time 213 – Setting the time 213 – Setting summer time start and end 214 – Setting summer time start and end 215 – Summer time start and end, setting the rule 215 Activating debounce (input delay) 222 – Activating debounce (input delay) 223 – Deactivating debounce (input delay) 223
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 10
Content
6
05/04 AWB2528-1508GB
Activating and deactivating the P buttons 224 – Activating the P buttons 224 – Function of the P buttons 224 – Deactivating the P buttons 225 Startup behaviour 225 – Setting the startup behaviour 225 – Behaviour when the circuit diagram is deleted 226 – Behaviour during upload/download to
card or PC 227 – Possible faults 227 – Card mode behaviour 227 Setting the cycle time 229 Retention (non-volatile data storage) 230 – Permissible markers and function relays 230 – Setting retentive behaviour 230 – Deleting retentive actual values 232 – Transferring retentive behaviour 232 – Changing the operating mode or
the circuit diagram 233 – Changing the startup behaviour in
the SYSTEM menu 233 Displaying device information 234
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 11
Content
7
05/04 AWB2528-1508GB
6Inside easy 235
easy circuit diagram cycle 235 – easy operation and effects on
circuit diagram creation 236 Delay times for inputs and outputs 238 – Delay times with easy-DA and
easy-DC basic units 238 – Delay time with easy-easy-AB,
easy-AC basic units 240 – Delay times for the analog inputs of easy-AB,
easy-DA and easy-DC 241 Monitoring of short-circuit/overload with EASY..-D.-T.. 242 Expanding easy700 243 – How is an expansion unit recognised? 244 – Transfer behaviour 244 – Function monitoring of expansion units 245 Saving and loading circuit diagrams 246 – EASY…-..-..X 246 – Interface 246 Memory card 248 – Compatibility with EASY-M-8K, EASY-M-16K
memory cards 248 – Loading or saving circuit diagrams 249 EASY-SOFT-BASIC 252 Overview with stand-alone display/operating unit 253 Device version 254
7 What Happens If ...? 255
Messages from the easy system 255 Possible situations when creating circuit diagrams 256 Event 258
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 12
Content
8
05/04 AWB2528-1508GB
Appendix 259 Dimensions 259 Technical Data 262 – General 262 – Special approvals 264 – Power supply 265 – Inputs 266 – Relay outputs 272 – Transistor outputs 274 List of the function relays 277 – Usable contacts 277 – Available function relays 278 – Names of relays 279 – Names of function relay 279 – Name of function block inputs (constants,
operands) 280 Compatibility of function relay parameters 281 – Parameter display of analog value comparator 281 – Parameter display of counters 281 – Parameter display of 7-day time switch 282 – Parameter display of timing relay 282
Glossary 283
Index 287
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 13
9
05/04 AWB2528-1508GB
About This Manual
This manual describes the installation, commissioning and programming (circuit diagram generation) of the easy500 and easy700 control relay.
Specialist electrical training is needed for commissioning and creating circuit diagrams. When active components such as motors or pressure cylinders are controlled, parts of the system can be damaged and persons put at risk if the device is connected or programmed incorrectly.
Device designation This manual uses the following abbreviated designations for
different easy models:
easy412 for all EASY412-..-... devices
EASY512-..-..., EASY7..-..-... Type designation of the control relay, the dots represent placeholders for all characters used.
easy500 for EASY512-AB..., EASY512-AC..., EASY512-DA... and EASY512-DC...
easy600 for all EASY61.-AC-RC(X), EASY62.-DC-TC(X)
easy700 for EASY719-AB..., EASY719-AC..., EASY719-DA..., EASY719­DC... and EASY721-DC...
easy-AB for EASY512-AB... EASY719-AB...
easy-AC for EASY512-AC... EASY618-AC-RE and EASY719-AC...
easy-DA for EASY512-DA... EASY719-DA...
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 14
About This Manual
10
05/04 AWB2528-1508GB
easy-DC for EASY512-DC... EASY6..-DC..., EASY719-DC... and EASY721-DC...
easy-E for EASY2.., EASY618-AC-RE, EASY618-DC-RE and EASY620­DC-TE
Writing conventions Symbols used in this manual have the following meanings:
X indicates actions to be taken.
For greater clarity, the name of the current chapter is shown in the header of the left-hand page and the name of the current section in the header of the right-hand page. Pages at the start of a chapter and empty pages at the end of a chapter are exceptions.
h
Attention!
Warns of a hazardous situation that could result in damage to the product or components.
i
Caution!
Warns of the possibility of serious damage and slight injury.
j
Warning!
Warns of the possibility of a hazardous situation that could result in major damage and serious or fatal injury or even death.
h
Indicates interesting tips and additional information
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 15
11
05/04 AWB2528-1508GB
1easy
Target readership easy must only be installed and connected up by trained
electricians or other persons who are familiar with the installation of electrical equipment.
Specialist electrical training is needed for commissioning and creating circuit diagrams. When active components such as motors or pressure cylinders are controlled, parts of the system can be damaged and persons put at risk if easy is connected or programmed incorrectly.
Proper use easy is a programmable switching and control device and is
used as a replacement for relay and contactor control circuits. easy may only be operated when it has been correctly and properly installed.
• easy is designed to be installed in an enclosure, switch cabinet or service distribution board. Both the power feed and the signal terminals must be laid and covered so as to prevent accidental contact.
• The installation must comply with regulations for electromagnetic compatibility (EMC).
• The starting up of easy should not cause any hazards arising from controlled devices, such as unexpected motor startups or power ups.
Improper use
easy should not be used as a substitute for safety-related controls such as burner or crane controls, emergency-stop or two-hand safety controls.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 16
easy
12
05/04 AWB2528-1508GB
Overview
Figure 1: easy basic units and expansion devices
ERR
P
O
W
B
U
S
1
2
5
10
P
O
W
E
R
C
O
M
-E
R
R
A
D
R
MS
NS
3
4
6
7
8
9
2
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 17
Overview
13
05/04 AWB2528-1508GB
Legend for figure 1:
a easy500 basic unit b easy600 I/O expansion c EASY202-RE output expansion d EASY200-EASY coupling device e EASY-LINK-DS data connector f EASY204-DP PROFIBUS-DP slave gateway g EASY205-ASI AS-Interface slave gateway h EASY221-CO CANopen gateway i EASY222-DN DeviceNet gateway j easy700 basic unit
easy is an electronic control relay with logic functions, timer, counter and time switch functions. It is also a control and input device in one that can perform many different tasks in domestic applications as well as in machine building and plant construction.
Circuit diagrams are connected up using ladder diagrams, and each element is entered directly via the easy display. For example, you can:
• Connect make and break contacts in series and in parallel
• Connect output relays and markers,
• Use outputs as relays, impulse relays or latching relays
• Use multi-function timing relays with different functions
• Use up and down counters,
• Count high-speed counter pulses
• Measure frequencies
• Process analog inputs, easy-AB, easy-DA, easy-DC, (EASY512..: two analog inputs, easy700: four analog inputs)
• Display any texts with variables, enter setpoints
• Use year time switches, 7-day time switches, EASY…-..-.C(X),
• Count operating hours (four retentive operating hours counters integrated)
• Track the flow of current in the circuit diagram
• Load, save and password-protect circuit diagrams
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 18
easy
14
05/04 AWB2528-1508GB
If you prefer to wire up easy from a PC, then use EASY-SOFT­BASIC. EASY-SOFT-BASIC allows you to create and test your circuit diagram on the PC. EASY-SOFT-BASIC is also used to print out your circuit diagram in DIN, ANSI or easy format.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 19
Overview
15
05/04 AWB2528-1508GB
Versions easy basic units at a glance
Figure 2: Versions
a Power supply b Inputs c Status LED d Buttons e Interface socket for memory card or PC connection f Outputs g LCD display
DEL
ALT
ESC
OK
ESC
OK
DEL
ALT
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 20
easy
16
05/04 AWB2528-1508GB
easy basic units with stand-alone MFD-80.., MFD-CP4-500 HMI unit
Figure 3: Overview with stand-alone HMI unit
a easy500 basic units b easy700 basic units c MFD device d Power supply/communication module with MFD-CP4-500
interface cable
1
3
3
2
4
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 21
Overview
17
05/04 AWB2528-1508GB
Type reference
Table 1: Overview of comparable easy400 types with easy500
and easy600 with easy700
EASY-x x x -x x-x x x
LCD display: X = No display Time switch: C = Available; E = Expansion
Output type: R = Relay (max. 8 A) T = Transistor (0.5 A, parallel connection possible up to 2 A)
Supply voltage, device and inputs AB = 24 V AC (2, (4) inputs, also usable as 0 to 10 V analog inputs)
AC = 100, 120, 230, 240 V AC DC = 24 V DC (2 (4) inputs, also usable as 0 to 10 V analog inputs) DA = 12 V DC (2 (4) inputs, also usable as 0 to 10 V analog inputs)
Number of inputs/outputs (+ expansion) 12 = 8 I/4 O 18 = 12 I/6 O 19 = 12 I/6 O + expansion 20 = 12 I/8 O 21 = 12 I/8 O + expansion
Rating class (RC) and space unit (SU) 2 = 35.5 mm (SU) 4, 5 = 71.5 mm (4 SU), RC = 4 or 5 6, 7= 107.5 mm (6SU), RC = 6 or 7
easy control relay
easy400, easy600 easy500, easy700
EASY512-AB-RC
EASY512-AB-RCX
EASY412-AC-R
EASY512-AC-R
EASY412-AC-RC
EASY512-AC-RC
EASY412-AC-RCX
EASY512-AC-RCX
EASY412-DA-RC
EASY512-DA-RC
EASY412-DA-RCX
EASY512-DA-RCX
EASY412-DC-R
EASY512-DC-R
EASY412-DC-RC
EASY512-DC-RC
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 22
easy
18
05/04 AWB2528-1508GB
EASY412-DC-RCX
EASY512-DC-RCX
EASY412-DC-TC
EASY512-DC-TC
EASY412-DC-TCX
EASY512-DC-TCX
EASY719-AB-RC
EASY719-AB-RCX
EASY619-AC-RC
EASY719-AC-RC
EASY619-AC-RCX
EASY719-AC-RCX
EASY719-DA-RC
EASY719-DA-RCX
EASY619-DC-RC
EASY719-DC-RC
EASY619-DC-RCX
EASY719-DC-RCX
EASY621-DC-TC
EASY721-DC-TC
EASY621-DC-TCX
EASY721-DC-TCX
easy400, easy600
easy500, easy700
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 23
Overview
19
05/04 AWB2528-1508GB
easy operation Buttons
Moving through menus and choosing values
DEL: Delete object in circuit diagram ALT: Special functions in circuit diagram, Status display Cursor buttons
úíÍÚ:
Move cursor Select menu items Set contact numbers, contacts and values
OK: Next menu level, Save your entry ESC: Previous menu level, Cancel
ALT
DELDELDELDELDELDELDELDELDELDEL
ESC
OK
and
Show System menu
Go to next menu level Select menu item Store your entry
Return to last menu level Cancel your entry since the last OK
ÍÚ
úí
Change menu item Change value Change position
P button function (if enabled):
ú í
Input P1 Input P3
Í Ú
Input P2 Input P4
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 24
easy
20
05/04 AWB2528-1508GB
Selecting main and system menu
Status display
1.2 RS MO .2 6..
I .2..5.....
P­MO 02:00 ..34 . RUN
and
No password
PROGRAM...
STOPå RUN PARAMETER INFO... SET CLOCK
SECURITY...
SYSTEM... LANGUAGE...
easy500: 8 inputs, 4 outputs
Current selection flashes in
the easy menu
Clock menu on
devices with clock
1st menu level
Main menu
1st menu level
easy500 or easy700 System menu
SECURITY... SYSTEM... LANGUAGE... CONFIGURATOR
The CONFIGURATOR menu appears if a configurable expansion module is connected such as EASY204-DP (Profibus-DP bus gateway)
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 25
Overview
21
05/04 AWB2528-1508GB
Toggling between weekday, time display and date display
(only on devices with clock)
easy Status display
Status display for local expansion
.2..5.......
P-
MO 11:50
..34 RUN
.2..5.......
P-
01.04.2004
..34 RUN
.2..5.......
P-
MO 11:50
Q ..34..STOP
.2..5......
P-
01.04.2002
Q ..34..STOP
easy500: input 1 to 8, easy700: input 1 to 12
Inputs
Weekday/Time or Weekday/Date
Outputs RUN/STOP mode
easy500: output 1 to 4, easy700: output 1 to 6 or 8
On: 1, 2, 3, 4 /Off:…
1.......9...
RS AC P­MO 10:42
1.....7. RUN
Inputs
Expansion
Weekday/Time or Weekday/Date
Outputs
On: 1, 2, 3, 4/Off:… RS = Expansion functioning correctly
1.......9...
RS AC P­MO 10:42
1.....7. RUN
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 26
easy
22
05/04 AWB2528-1508GB
Advanced Status display
easy LED display
easy512-..-..X, easy700 and easy-E feature an LED on the front indicating the status of the power supply as well as whether RUN or STOP mode is active (a figure 2, page 15).
Retention/Debounce AC expansion ok/P buttons
Startup behaviour
RE
: Retention switched on
I
: Debounce switched on
AC
: AC expansion functioning correctly
DC
: DC expansion functioning correctly
GW
: Bus coupling module detected
GW flashes: Only easy200-easy detected. I/O expansion not detected.
17.03.04 Display of actual device date
ST
: When the power supply is switched on, easy switches to STOP mode
12...6.89... RE I ACP-
17.03.04 ST
123.5.78 RUN
LED OFF No power supply
LED continuously lit
Power supply present, STOP mode
LED flashing
Power supply present, RUN mode
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 27
Overview
23
05/04 AWB2528-1508GB
Menu structure
Main menu without password protection
X You access the main menu by pressing OK.
PROGRAM....Æ
STOP å RUN PARAMETER INFO... æ SET CLOCK..
PROGRAM...
DELETE PROG CARD
SAVE
CANCEL
Main menu
STOP: Circuit diagram display
Parameters
Circuit diagram
Parameter display
DELETE ?
PROGRAM...
DELETE PROG
CARD...
DEVICE-CARD
CARD-DEVICE DELETE CARD
REPLACE ?
PROGRAM... DELETE PROG
CARD...
DEVICE-CARD
CARD-DEVICE
DELETE CARD
DELETE ?
DEVICE-CARDE CARD-DEVICE
DELETE CARD
REPLACE ?
The arrows indicate that there are more than four menus.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 28
easy
24
05/04 AWB2528-1508GB
PROGRAM....Æ
STOP RUN å
PARAMETER INFO... æ SET CLOCK..
Mai
n menu
Parameter display
SET CLOCK..
SUMMER TIME..
PROGRAM....Æ
STOP RUN å
PARAMETER...
INFO... æ SET CLOCK..
PROGRAM... STOP RUN Æ PARAMETER INFO...
SET CLOCK.æ
Display for date and time setting
HH:MM --:-- DD.MM --.-- YEAR ____
HH:MM 14:23 DD.MM 17.03 YEAR 2004
T1 X S + T2 Ü M:S + C1 N + O1 +
T1 X S + S1 10.000 S2 +0
T:
Information display of the device
PROGRAM....Æ
STOP RUN å PARAMETER...
INFO... æ
SET CLOCK..
DC TC LCD OS: 1.00.027 CRC: 02752
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 29
Overview
25
05/04 AWB2528-1508GB
AM --Æ WD: --
-­DD.MM:00.00æ HH:MM:00:00 DIFF: 0:00
NONE Æ
RULE... å
EU GB æ US
NONE Æ
RULE...
EU GB æ US
AM --Æ WD: --
-­DD.MM:00.00æ HH:MM:00:00 DIFF: 0:00
Mai
n menu
PROGRAM... STOP RUN Æ PARAMETER... INFO...
SET CLOCK.æ
SET CLOCK..
SUMMER TIME.
Only one selection is possible.
NONE åÆ
RULE... EU GB æ US
SUMMER START SUMMER END
SUMMER START
SUMMER END
SET CLOCK..
SUMMER TIME.
NONE Æ
RULE... å
EU GB æ US
SUMMER START SUMMER END
SET CLOCK..
SUMMER TIME.
SET CLOCK..
SUMMER TIME.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 30
easy
26
05/04 AWB2528-1508GB
Main menu with password protection
easy System menu
The System menu is accessed by simultaneously pressing DEL and ALT.
PASSWORD.. Æ
STOP RUN å PARAMETER... INFO... æ SET CLOCK..
Password
Password entryUnlocking
easy
Main menu
PASSWORD...
STOP RUN å
DELETE ALL
Correct entry
Status display
Four wrong entries (if enabled)
Example: Password only on program
PROGRAM å Æ
PARAMETER å TIME å MODE æ INTERFACE å DEL PROG å
PROGRAM å Æ
PARAMETER TIME MODE æ INTERFACE DEL PROG
ENTER PASSW:
XXXX
System menu
ACTIVATE PW
CHANGE PW
Password entry
Change/ delete password
SECURITY...
SYSTEM... LANGUAGE... CONFIGURATOR
Password setup
PASSWORD...
RANGE...
ENTER PASSW:
XXXX
CHANGE PW
ACTIVATE PW
CHANGE PW
ACTIVATE PW
PASSWORD...
RANGE...
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 31
Overview
27
05/04 AWB2528-1508GB
DEBOUNCE å P-BUTTONS RUN MODE å CARD MODE
ENGLISH Æ DEUTSCH å FRANCAIS ESPANOL æ ITALIANO PORTUGUES NEDERLANDS SVENSKA POLSKI TURKCE CESKY MAGYAR
System menu
SECURITY... SYSTEM...
LANGUAGE...
CONFIGURATOR
SECURITY... SYSTEM... LANGUAGE...
CONFIGURATOR
The further menus depend on the connected expansion device
Only one selection is possible.
SECURITY...
SYSTEM...
LANGUAGE... CONFIGURATOR
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 32
easy
28
05/04 AWB2528-1508GB
Selecting or toggling between menu items
Cursor display
Cursor
Í Ú
Select or toggle
PROGRAM... STOP
PARAMETER
INFO
The cursor flashes.
Full cursor
Ê/:
• Move cursor with
úí,
• in circuit diagram also with
Í Ú
Value M/M
• Change position with úí
• Change values with Í Ú
Flashing values/menus are shown in grey in this manual.
HH:MM '4:23 DD.MM 17.03 YEAR 2004
HH:MM 14:23 DD.MM 17.03 YEAR 2004
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 33
Overview
29
05/04 AWB2528-1508GB
Setting values
Select value
Í Ú
Select digit úí Change value at digit ÍÚ
Store entries
Retain previous value
Current value at the
position (can be
changed, Cursor = 3)
HH:MM 14:23 DD.MM 17.03 YEAR 2004
Values
Digits
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 34
30
05/04 AWB2528-1508GB
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 35
31
05/04 AWB2528-1508GB
2 Installation
easy must only be installed and wired up by trained electricians or other persons familiar with the installation of electrical equipment.
easy is installed in the following order:
• If necessary connect devices together
• Mounting
• Wiring up the inputs
• Wiring up the outputs
• Connecting the power supply
Mounting Install easy in a control cabinet, service distribution board or
in an enclosure so that the power feed and terminal connections cannot be touched accidentally during operation.
Clip easy onto a DIN EN 50022 top-hat rail or fix easy in place using fixing brackets. easy can be mounted vertically or horizontally.
j
Danger of electric shock
Never carry out electrical work on the device while the power supply is switched on.
Always follow the safety rules:
• Switch off and isolate
• Secure against reclosing
• Ensure that the device is no longer live
• Cover adjacent live parts
h
When using easy with expansion units, connect the expansion concerned before mounting (a page 34).
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 36
Installation
32
05/04 AWB2528-1508GB
For ease of wiring, leave a gap of at least 30 cm between easy terminals and the wall or adjacent devices.
Figure 4: Clearances to easy
Mounting on top-hat rail
X Hook easy to the top edge of the top-hat rail and hinge
into place while pressing down slightly. Press the device lightly downwards and against the top-hat rail until it snaps over the lower edge of the top-hat rail.
easy will clip into place and will be secured by the built-in spring mechanism.
X Check that the device is seated firmly.
easy is mounted vertically on a top-hat rail in the same way.
30
30
30
30
1
2
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 37
Mounting
33
05/04 AWB2528-1508GB
Using a mounting plate
Mounting on a mounting plate requires the use of fixing brackets which are fixed to the back of easy. The fixing brackets are available as an accessory.
easy600 and easy700: Fasten each device with at least three fixing brackets.
Figure 5: Using a mounting plate
EASY200-EASY: easy500: easy600, easy700:
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 38
Installation
34
05/04 AWB2528-1508GB
Connecting the expansion device
Figure 6: Connecting expansion units
1
3
4
2
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 39
Terminals
35
05/04 AWB2528-1508GB
X Open the easy-LINK connections on the side of both easy
devices.
X Fit the easy-LINK data connector EASY-LINK-DS in the
opening provided on the expansion device.
X Plug the devices together. X Proceed in the reverse order to dismantle the device.
Terminals Tools
Slot-head screwdriver, width 3.5 mm, tightening torque
0.6 Nm.
Cable cross-sections
• Solid: 0.2 to 4 mm
2
• Flexible with ferrule: 0.2 to 2.5 mm
2
Connecting the power supply
Cable protection
Connect on easy cable protection (F1) rated for at least 1 A (slow).
h
The required connection data for device types , easy-AB with 24 V AC, easy-AC with standard voltages of 100 V
AC, easy-DA with 12 V DC and easy-DC with 24 V DC are provided in the section “Technical Data”, page 262.
The easy500 and easy700 basic units run a system test for two seconds after the power supply has been switched on. Either RUN or STOP mode will be activated after these two seconds, depending on the default setting.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 40
Installation
36
05/04 AWB2528-1508GB
Supplying AC units
Supplying AC basic units
EASY…-AB-RC(RCX), EASY…-AC-R(RC, RCX)
Figure 7: Power supply on the AC basic units
Supplying AC expansion units
EASY…-AC-.E
Figure 8: Power supply on the AC expansion units
NNL
N
F1
L
NNL
N
F1
L
E+
E-
R1
...
R12
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 41
Connecting the power supply
37
05/04 AWB2528-1508GB
Supplying DC units
Supplying DC basic units
EASY…-DA-RC(X), EASY…-DC-R(RC,RCX)
Figure 9: Power supply on the DC basic units
j
Applies to easy-AC devices with a power supply greater than 24 V AC:
• The voltage terminals for phase L and neutral conductor N have been reversed.
• This enables the easy interface (for memory card or PC connection) to have the full connection voltage of the phase conductor (100 to 240 V AC).
• There is a danger of electric shock if the connection at the easy interface is not properly connected or if conductive objects are inserted into the socket.
h
Attention!
A short current surge will be produced when switching on for the first time. Do not switch on easy by means of reed contacts since these may burn or melt.
+...V
0 V0 V
L01
F1
L01
DC : +24 V
DA : +12 V
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 42
Installation
38
05/04 AWB2528-1508GB
Supplying DC expansion units EASY…-DC-.E
Figure 10: Power supply on the DC expansion units
Cable protection
Connect on easy a cable protection (F1) rated for at least 1 A (slow).
0V0V24V
L01-
F1
L01+
24 V
E+
E-
R1
...
R12
h
easy-DC and easy-DA are protected against reverse polarity. To ensure that easy works correctly, ensure that the polarity of each terminal is correct.
h
When easy is switched on for the first time, its power supply circuit behaves like a capacitor. Use an appropriate device for switching on the power supply and do not use any reed relay contacts or proximity switches.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 43
Connecting the inputs
39
05/04 AWB2528-1508GB
Connecting the inputs easy inputs switch electronically. Once you have connected
a contact via an input terminal, you can reuse it as a contact in your easy circuit diagram as often as you like.
Figure 11: Connecting the inputs
Connect to the easy input terminals contacts such as pushbuttons, switches, relay or contactor contacts, proximity switches (three-wire).
Connecting easy AC digital inputs
+24 V
S1
0 V
I1
I1 i1
L
N
i
Caution!
Connect the inputs for AC devices in compliance with the safety regulations of the VDE, IEC, UL and CSA. Use the same phase conductor for the input power feed, otherwise easy will not detect the switching level and may be damaged or destroyed by overvoltage.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 44
Installation
40
05/04 AWB2528-1508GB
Connecting easy AC digital inputs on the basic unit
Figure 12: Connecting easy-AC and easy-AB digital inputs
Connecting AC digital inputs on the expansion device
Figure 13: Connecting EASY...-AC-E digital inputs
l1 I2 I7
L N
LNN
F1
L
N
R10R9R8R7R6R5R4R3R2R1E+ E-
R11
R12 NNL
F1
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 45
Connecting the inputs
41
05/04 AWB2528-1508GB
Table 2: easy-AB input signal values
Table 3: easy-AC input signals
Cable lengths
Severe interference can cause a “1” signal on the inputs without a proper signal being applied. Observe therefore the following maximum cable lengths:
Input signal voltage range Input current
OFF signal ON signal
easy500/ easy700
I1 to I6 0 to 6 V AC 14 to 26.4 V AC 4 mA at 24 V AC
I7, I8
greater than 7 V AC or greater than
9.5 V DC
2 mA with 24 V AC and 24 V DC
easy700 I9, I10
14 to 26.4 V AC 4 mA at 24 V AC
I11, I12
greater than 7 V AC or greater than
9.5 V DC
2 mA with 24 V AC and 24 V DC
Input signal voltage range Input current
OFF signal ON signal
easy500/ easy700
I1 to I6 0 to 40 V 79 to 264 V 0.5 mA at 230 V AC/
0.25 mA at 115 V AC
I7, I8
6 mA at 230 V AC/4 mA at 115 V
easy700 I9 to I12
0.5 mA at 230 V AC/
0.25 mA at 115 V AC
easy600 R1 to
R12
I1 to I6 40 m without additional circuit
I7, I8 100 m without additional circuit
I9 to I12 40 m without additional circuit
R1 to R12
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 46
Installation
42
05/04 AWB2528-1508GB
For longer lengths connect in series a diode (e.g. 1N4007) for 1 A, min. 1000 V reverse voltage, to the easy input. Ensure that the diode is pointing towards the input as shown in the circuit diagram, otherwise easy will not detect the 1 state.
Figure 14: AC input with suppression diode for easy-AC and
easy-AB
easy-AC: Inputs I7 and I8 have a higher input current on the easy-AC. Neon bulbs with a maximum residual current of 2 mA/1 mA at 230 V/115 V can be connected to I7 and I8.
Two-wire proximity switches have a residual current with the “0” state. If this residual current is too high, the easy input may only detect a “1” signal.
Therefore, use inputs I7 and I8. An additional input circuit is required if more inputs are used.
L
N
LNN
I1
F1
h
Always use neon bulbs that are operated with a separate N connection.
i
Caution!
Do not use reed relay contacts at I7, I8. These may burn or melt due to the high inrush current of I7, I8.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 47
Connecting the inputs
43
05/04 AWB2528-1508GB
Increasing the input current
The following input circuit can be used in order to prevent interference and also when using two-wire proximity switches:
Figure 15: Increasing the input current
A resistor can be connected in series with the circuit shown in order to restrict the inrush current.
Figure 16: Limitation of the input current with a resistor
L
N
LNN
I1
100 nF/275 V h
F1
h
When using a 100 nF capacitor the drop-off time of the input increases by 80 (66.6) ms at 50 (60) Hz.
L
N
LNN
I1
100 nF/275 V h
1 kO
F1
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 48
Installation
44
05/04 AWB2528-1508GB
Complete devices for increasing the input current are available under the type reference EASY256-HCI.
Figure 17: easy with EASY256-HCI
Connecting easy DC digital inputs
Use input terminals I1 to I12, R1 to R12 to connect pushbutton actuators, switches or 3 or 4-wire proximity switches. Given the high residual current, do not use 2-wire proximity switches.
L
F1
N
LNN
I1
1N
h
The increased capacitance increases the drop-off time by approx. 40 ms.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 49
Connecting the inputs
45
05/04 AWB2528-1508GB
Connecting DC digital inputs on the basic unit
Figure 18: Connecting easy-DC, easy-DA digital inputs
Connecting DC digital inputs on the expansion device
EASY…-DC-.D
Figure 19: Connecting EASY...-DC-E digital inputs
L01
L01
0 V l1 I2 I7
+...V
DC : +24 V DA : +12 V
F1
+24 V
0V
R10R9R8R7R6R5R4R3R2R1E+ E-
R11
R12 0V0V+24V
Input 24 V 24 V
F1
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 50
Installation
46
05/04 AWB2528-1508GB
Table 4: easy-DC input signals
Table 5: easy-DA input signals
Connecting easy DC analog inputs
The easy-AB, easy-DA and easy-DC basic units are provided with analog inputs. Inputs I7 and I8, and if present I11 and I12, can be used to connect analog voltages ranging from 0 V to 10 V. A simple additional circuit also allows the analog evaluation of currents from 0 to 20 mA. The analog input signals are converted to 10-bit digital signals.
The following applies:
• 0 V DC corresponds to a digital 0.
• 5 V DC corresponds to a digital value of 512.
• 10 V DC corresponds to a digital value of 1023.
Input signal voltage range Input current
OFF signal ON signal
easy500/ easy700
I1 to I6 0 to 5 V 15 to 28.8 V 3.3 mA at 24 V DC
I7, I8
greater than 8 V DC 2.2 mA at 24 V
easy700 I9, I10
15 to 28.8 V 3.3 mA at 24 V DC
I11, I12
greater than 8 V DC 2.2 mA at 24 V
easy600 R1 to
R12
15 to 28.8 V 3.3 mA at 24 V DC
Input signal voltage range Input current
OFF signal ON signal
easy500/ easy700
I1 to I6 0 to 4 V DC 8 to 15.6 V DC 3.3 mA at 12 V
I7, I8
1.1 mA at 12 V
easy700 I9, I10
3.3 mA at 12 V
I11, I12
1.1 mA at 12 V
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 51
Connecting the inputs
47
05/04 AWB2528-1508GB
Safety measures with analog signals
X Use shielded twisted pair cables to prevent interference
with the analog signals.
X For short cable lengths, ground the shield at both ends
using a large contact area. If the cable length exceeds 30 m or so, grounding at both ends can result in equalisation currents between the two grounding points and thus in the interference of analog signals. In this case, only ground the cable at one end.
X Do not lay signal lines parallel to power cables. X Connect inductive loads to be switched via the easy
outputs to a separate power feed, or use a suppressor circuit for motors and valves. If loads such as motors, solenoid valves or contactors are operated with easy via the same power feed, switching may result in interference on the analog input signals.
The following four circuits contain examples of applications for analog value processing.
i
Caution!
Analog signals are more sensitive to interference than digital signals. Consequently, greater care must be taken when laying and connecting the signal lines.
Incorrect switching states may occur if they are not connected correctly.
i
Caution!
Ensure that the reference potential is connected. Connect the 0 V of the power supply unit for the different setpoint potentiometers and sensors shown in the examples to the 0 V and neutral conductor terminal (easy-AB) of the easy power feed. Otherwise incorrect switching states may occur if they are not connected correctly.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 52
Installation
48
05/04 AWB2528-1508GB
Power supply of easy-AB devices and analog inputs
With easy-AB devices that process analog signals, the device must be fed via a transformer so that the device is isolated from the mains supply. The neutral conductor and the reference potential of the DC power feed of analog sensors must be electrically connected.
Figure 20: easy-AB analog input, connection of reference
potentials
h
Ensure that the common reference potential is grounded or monitored by a ground fault monitoring device. Observe the requirements of the relevant regulations.
I7L
NI1N
L1
N
~
0 V
+12 V
L01h
N01 h
I8
F1
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 53
Connecting the inputs
49
05/04 AWB2528-1508GB
Analog setpoint potentiometer, easy-AB, easy-DA, easy-DC
Figure 21: Analog setpoint potentiometer with own power feed
Use a potentiometer with a resistance of  1k, e.g. 1 k,
0.25 W.
easy-DC analog setpoint potentiometer
Figure 22: Analog setpoint potentiometer with 24 V DC power feed
~
0 V
+12 V
I7+...V
L
0 V N
0 V N
F1
L01
L01
1.3 kO/0.25 W
1 kO/0.25 W
0 V 0 V I7
+...V
DC : +24 V DA : +12 V
F1
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 54
Installation
50
05/04 AWB2528-1508GB
Brightness sensor, easy-AB, easy-DA, easy-DC
Figure 23: Connection of a brightness sensor, analog input
Temperature sensor, easy-DA, easy-DC
Figure 24: Connection of the temperature sensor, analog input
0 V
0...10 V
12 V
~
0 V
+12 V
I7+...V
L
0 V N
0 V N
F1
+24 V
–0 V
Out
0...10 V
–35...55 ˚C
I7+...V
L
0 V N
0 V N
F1
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 55
Connecting the inputs
51
05/04 AWB2528-1508GB
20 mA sensor
4 to 20 mA (0 to 20 mA) sensors can be connected easily without any problem using an external 500 resistor.
Figure 25: Connection 0 (4) to 20 mA sensor output, analog input
Analog sensor
The following values apply:
4 mA = 1.9 V
• 10 mA = 4.8 V
• 20 mA = 9.5 V
(Based on U = R I = 478   10 mA 4.8 V).
Connecting high-speed counters and frequency generators
High-speed counter signals and frequencies on the easy-DA and easy-DA can be counted accurately on inputs I1 to I4 independently of the cycle time. These inputs are permanently assigned to counters.
The following applies:
• I1 = C13 high-speed up/down counter
• I2 = C14 high-speed up/down counter
L01
F1
L01
500
4...20 mA
I7+...V
0 V0 V
DC : +24 V DA : +12 V
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 56
Installation
52
05/04 AWB2528-1508GB
• I3 = C15 frequency counter
• I4 = C16 frequency counter
Pulse shape of count signals: easy processes square wave signals.
Mark-to-space ratio of count signals: We recommend a mark-to-space ratio of 1:1.
If this is not the case: The minimum pulse or pause duration is 0.5 ms.
t
min
= 0.5 x (1/f
max
)
t
min
= minimum time of the pulse or pause duration
f
max
= maximum count frequency (1 kHz)
Figure 26: Connecting high-speed counters and frequency
generators
0 V
0 V
...V
L01 –
F1
L01 +
I1
I2 I3
I4 I5
I6
L02 +
24 V H
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 57
Connecting the outputs
53
05/04 AWB2528-1508GB
Connecting the outputs The Q outputs function inside easy as isolated contacts.
Figure 27: Output Q
The associated relay coils are controlled in the easy circuit diagram via the following outputs.
• Q1 to Q4 and Q1 to Q8 (Q6), basic units
• S1 to S8 (S6), expansion devices
You can use the signal states of the outputs as make or break contacts in the easy circuit diagram to provide additional switching conditions.
The relay or transistor outputs are used to switch loads such as fluorescent tubes, filament bulbs, contactors, relays or motors. Check the technical thresholds and data of the outputs before installation (a section “Technical Data”, page 262).
h
Inputs that are used as high-speed counter inputs should not be used in the circuit diagram as contacts. If the counter frequency is high:
Not all the signals of the high-speed counter can be monitored for processing in the circuit diagram. easy will only process a randomly logged state.
Q1
12
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 58
Installation
54
05/04 AWB2528-1508GB
Connecting relay outputs
EASY512-..-R..
Figure 28: EASY512-..-R.. relay outputs
Figure 29: EASY7..-..-R.. relay outputs and EASY202-RE
0 V H, N
F 8 A/B 16
L1, L2, L3 (115/230 V h) + 24 V H
25 000
R
L
24 V H 8 A 115 V h 8 A 230 V h 8 A
2 A 2 A 2 A
1000 W
10 x 58 W
1
2
1
2
1
2
1
2
10 000 000
Q1
Q2
Q3 Q4
EASY7..-..-R.. and EASY202-RE
+ 24 V H
0 V H, N
F
8 A/B 16
L1, L2, L3 (115/230 V h)
12 2 2 2 2 2
1
1
1
1
1
10 000 000
Q6Q5Q4Q3
Q2
Q1
F 8 A/B 16
+ 24 V H
0 V H, N
L1, L2, L3 (115/230 V
h
)
12 2
1
10 000 000
S2
S1
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 59
Connecting the outputs
55
05/04 AWB2528-1508GB
EASY618-..-RE
Figure 30: EASY618-..-RE.. relay outputs
Unlike the inputs, the outputs can be connected to different phases.
0 V H, N
F
8 A/B 16
L1, L2, L3 (115/230 V h) + 24 V H
25 000
R
24 V H
8A 115 V h 8A 230 V h 8 A
2A 2A 2A
1000 W
10 x 58 W
12 2 2 2 2 2
1
1
1
1
1
10 000 000
S6S5S4S3
S2
S1
j
Warning!
Do not exceed the maximum voltage of 250 V AC on a relay contact.
If the voltage exceeds this threshold, flashover may occur at the contact, resulting in damage to the device or a connected load.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 60
Installation
56
05/04 AWB2528-1508GB
Connecting transistor outputs
EASY512-..-T..
Figure 31: EASY512-..-T.. transistor outputs
EASY7..-..-T..
Figure 32: EASY7..-..-T.. transistor outputs
0 V H
R
L
24 V
0.5 A
+24 V
0 V Q1 Q2 Q3 Q4
F10 A
0.5 A
5 W/24 V
f 2.5 A + 24 V H
20.4 – 28.8 V H
Q
Q
(20.4 – 28.8 V H)
+ 24 V H
R
5 W/24 V
0.5 A
0 V H
+24 V 0 V Q1 Q2 Q3
Q4
Q5
Q6
Q7
f 2.5 A
F10 A
24 V H
0.5 A
Q8
Q
Q
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 61
Connecting the outputs
57
05/04 AWB2528-1508GB
EASY620-..-TE
Figure 33: EASY620-..-TE transistor outputs
Parallel connection: Up to four outputs can be connected in parallel in order to increase the power. The output current will increase in this case to a maximum of 2 A.
0 V H
S1 S2 S3 S4 S5 S6 S7 S8 +24 V
f 2.5 A
F10 A
0V
+ 24 V H
R
5 W/24 V
0.5 A
(20.4 – 28.8 V H)
24 V H
0.5 A
Q
Q
i
Caution!
Outputs may only be connected in parallel within a group (Q1 to Q4 or Q5 to Q8, S1 to S4 or S5 to S8), such as Q1 and Q3 or Q5, Q7 and Q8. Outputs connected in parallel must be switched at the same time.
i
Caution!
Please note the following when switching off inductive loads.
Suppressed inductive loads cause less interference in the entire electrical system. For optimum suppression the suppressor circuits are best connected directly to the inductive load.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 62
Installation
58
05/04 AWB2528-1508GB
If inductive loads are not suppressed, the following applies: Several inductive loads should not be switched off simultaneously to avoid overheating the driver blocks in the worst possible case. If in the event of an emergency stop the +24 V DC power supply is to be switched off by means of a contact, and if this would mean switching off more than one controlled output with an inductive load, then you must provide suppressor circuits for these loads (see the following diagrams).
Figure 34: Inductive load with suppressor circuit
Behaviour with short-circuit/overload
Should a short circuit or overload occur on a transistor output, this output will switch off. The output will switch on up to maximum temperature after the cooling time has elapsed. This time depends on the ambient temperature and the current involved. If the fault condition persists, the output will keep switching off and on until the fault is corrected or until the power supply is switched off (a section “Monitoring of short-circuit/overload with EASY..-D.-T..”, page 242).
U
emax
< Uz < 33 V
0 V H
Q..
+ 24 V H
0 V H
Q..
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 63
Expanding inputs/outputs
59
05/04 AWB2528-1508GB
Expanding inputs/outputs You can add expansion units to the following easy models in
order to increase the number of inputs and outputs:
Local expansion
Local expansion units are connected directly next to the basic unit.
X Connect the easy expansion unit via the EASY-LINK
connection.
Figure 35: Connecting local expansion with easy
Expandable easy basic units
Expansion units
EASY7..-..-R.. EASY7..-..-T..
EASY618-..-RE 115/230 V AC power supply
• 12 AC inputs,
• 6 relay outputs
24 V DC power supply
• 12 DC inputs,
• 6 relay outputs
EASY620-..-TE • 12 DC inputs,
• 8 transistor outputs
EASY202-RE 2 relay outputs
Special expansion units see current catalogue
EASY719-… EASY721-…
EASY6…-TE EASY6…-RE EASY200-EASY
EASY-LINK
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 64
Installation
60
05/04 AWB2528-1508GB
Remote expansion
Remote expansion units can be installed and run up to 30 m away from the basic unit.
j
Warning!
The following electrical isolation is implemented between the EASY7..-..-.C. basic unit and the expansion device (isolation always in local connection of expansion unit)
• Basic isolation 400 V AC (+10 %)
• Safe isolation 240 V AC (+10 %)
Units may be destroyed if the value 400 V AC +10 % is exceeded, and may cause the malfunction of the entire system or machine!
h
Basic unit and expansion unit can be provided with different DC power supplies.
j
Warning!
The two-wire or multi-core cable between units must have the necessary insulation voltage required for the installation environment concerned. In the event of a fault (ground leakage, short-circuit) serious damage or injury to persons may otherwise occur.
A cable such as NYM-0 with a rated operational voltage of U
e
= 300/500 V AC is normally sufficient.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 65
Expanding inputs/outputs
61
05/04 AWB2528-1508GB
Figure 36: Connecting remote expansion units to easy
E+ E–
E+ E–
EASY719-… EASY721-…
EASY200­EASY
EASY6…-RE EASY6…-TE
U
e
= 300/500 V
EASY…-AC-…E
h
Terminals E+ and E- of the EASY200-EASY are protected against short-circuits and polarity reversal. Functionality is only ensured if “E+” is connected with “E+” and “E-” with “E-”.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 66
Installation
62
05/04 AWB2528-1508GB
Connecting bus systems The EASY-LINK connection is designed to allow bus
connections, apart from I/O expansions. Special bus connection devices are available for the bus systems in use.
At present, easy700 can communicate with the following bus systems or networks:
• AS-Interface (Actuator-Sensor Interface)
•Profibus-DP
•CANopen
• DeviceNET
The different bus systems offer different functions.
The following applies:
• As a minimum data exchange, the input data R1 to R16 and output data S1 to S8 can be exchanged, provided that the bus system supports this.
• If the bus system or bus gateway is capable of this, function block, date, time parameters can be read and written via the bus. The states of inputs, outputs, markers can be read.
h
Only one device (expansion device or bus connection) can be connected to the EASY-LINK connection.
h
The range and the functions of the bus gateways are being continually further developed.
The current Moeller product line catalogue and the Internet online catalogue contain those bus gateways that are currently available.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 67
63
05/04 AWB2528-1508GB
3 Commissioning
Switching on Before switching on easy, check that you have connected the
power supply terminals and inputs correctly:
• 24 V AC version easy-AB – Terminal L: Phase conductor L – Terminal N: Neutral conductor N – Terminals I1 to I12:
Actuation via same phase conductor L
• 230 V AC version easy-AC – Terminal L: Phase conductor L – Terminal N: Neutral conductor N – Terminals I1 to I12, R1 to R12:
Actuation via phase conductor L
• 12 V DC version: –Terminal +12V: Voltage +12V – Terminal 0 V: 0 V voltage – Terminals I1 to I12:
Actuation via same +12V
•24V DC version: – Terminal +24 V: +24 V voltage – Terminal 0 V: 0 V voltage – Terminals I1 to I12, R1 to R12:
Actuation via the same +24 V
If you have already integrated easy into a system, secure any parts of the system connected to the working area to prevent access and ensure that no-one can be injured if, for example, motors start up unexpectedly.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 68
Commissioning
64
05/04 AWB2528-1508GB
Setting the menu language
When you switch on easy for the first time, you will be asked to select the menu language.
X Use the cursor buttons Í or Ú to select the language
required. –English –German –French –Spanish – Italian –Portuguese –Dutch –Swedish – Polish –Turkish –Czech – Hungarian
X Press OK to confirm your choice and press ESC to exit the
menu.
easy will then switch to the Status display.
ENGLISH å
DEUTSCH FRANCAIS ESPANOL
h
You can change the language setting at a later time (a section “Changing the menu language”, page 209).
If you do not set the language, easy will display this menu and wait for you to select a language every time you switch on.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 69
Setting the menu language
65
05/04 AWB2528-1508GB
easy operating modes easy has two operating modes - RUN and STOP.
In RUN mode easy continuously processes a stored circuit diagram until you select STOP or disconnect the power. The circuit diagram, parameters and the easy settings are retained in the event of a power failure. All you will have to do is reset the real-time clock after the back-up time has elapsed. Circuit diagram entry is only possible in STOP mode.
When a memory card with a circuit diagram is fitted in an easy model with an LCD display, this circuit diagram will not start automatically if there is circuit diagram in the device. The circuit diagram must first be transferred from the memory card to the easy unit.
In RUN mode easy-X models load the circuit diagram on the memory card automatically and run it immediately.
i
Caution!
In RUN mode easy will immediately run the saved circuit diagram in the unit when the power supply is switched on. This will happen unless STOP mode was set as startup mode. In RUN mode outputs are activated according to the switch logic of the circuit diagram.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 70
Commissioning
66
05/04 AWB2528-1508GB
Creating your first circuit diagram
The following small circuit diagram takes you step by step through wiring up your first easy circuit diagram. In this way you will learn all the rules, quickly enabling you to use easy for your own projects.
As with conventional wiring, you use contacts and relays in the easy circuit diagram. With easy, however, you no longer have to connect up components individually. At the push of a few buttons, the easy circuit diagram produces all the wiring. All you have to do is then connect any switches, sensors, lamps or contactors you wish to use.
Figure 37: Lamp controller with relays
In the following example, easy carries out all the wiring and performs the tasks of the circuit diagram shown below.
H1
L01-
S1
S2
L01+
F1
K1
K1
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 71
Setting the menu language
67
05/04 AWB2528-1508GB
Figure 38: Lamp controller with easy
Starting point: the Status display
When you switch on easy, it opens the Status display immediately to show the switching state of the inputs and outputs. It also indicates whether easy is already running a circuit diagram.
1
2
Q1
H1
L01-
S1 S2
L01+ L01-
F1
+24V
0V
I1
I2
...........
I MO 02:00
.......STOP
h
The examples were written without the use of expansion units. If an expansion unit is connected, the Status display will first show the status of the basic unit and then the status of the expansion unit before showing the first selection menu.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 72
Commissioning
68
05/04 AWB2528-1508GB
X Press OK to switch to the main menu.
Press OK to switch to the next menu level, and press ESC to move one level back.
In this case easy must be in STOP mode.
X Press OK 2 to enter the circuit diagram display via
menu items PROGRAM… r PROGRAM. This is where you will create the circuit diagram.
Circuit diagram display
The circuit diagram display is currently empty. The cursor flashes at the top left, which is where you will start to wire your circuit diagram. easy will automatically propose the first contact
I1.
Use the ÍÚ
úí cursor buttons to move the cursor over the
invisible circuit diagram grid.
The first three double columns are the contact fields and the right-hand columns form the coil field. Each line is a rung. easy automatically energizes the first contact to voltage.
X Now try to wire up the following easy circuit diagram.
Switches S1 and S2 are at the input.
I1 and I2 are the
contacts for the input terminals. Relay K1 is represented by the relay coil
ÄQ1. The symbol Ä identifies the coil's
function, in this case a relay coil acting as a contactor.
Q1 is
one of up to eight easy output relays in the basic unit.
PROGRAM...
STOP å RUN PARAMETER INFO
h
OK has two other functions:
• Press OK to save modified settings.
• In the circuit diagram, you can also press OK to insert and modify contacts and relay coils.
Â
êê êê êê êêê êê êê êê êêê êê êê êê êêê êê êê êê êêê
M
l
L
m
I1-I2----ÄQ1
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 73
Setting the menu language
69
05/04 AWB2528-1508GB
From the first contact to the output coil
With easy, you work from the input to the output. The first input contact is
I1.
X Press OK.
easy inserts the first contact
I1 at the cursor position.
X The I flashes and can be changed, for example, to a P for
a button input by using the cursor buttons Í or Ú.
However, nothing needs to be changed at this point.
X Press OK 2 , to move the cursor across the 1 to the
second contact field.
You could also move the cursor to the next contact field using the cursor button
í.
X Press OK.
Again, easy creates a contact
I1 at the cursor position.
Change the contact number to
I2 so that break contact S2
can be connected to input terminal I2.
X Press OK so that the cursor jumps to the next position and
use cursor buttons Í or Ú to change the number to
2.
X Press OK to move the cursor to the third contact field.
You do not need a third switch contact, so you can now wire the contacts directly to the coil field.
I1 êê êê êêê
I1 I1 êê êêê
h
Press DEL to delete a contact at the cursor position.
I1-I2 Â
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 74
Commissioning
70
05/04 AWB2528-1508GB
Wiring
easy displays a small arrow in the circuit diagram for creating the wiring.
Press ALT to activate the arrow and press the cursor buttons
ÍÚ
úí to move it.
The wiring arrow works between contacts and relays. When you move the arrow onto a contact or relay coil, it changes back to the cursor and can be reactivated if required.
X Press ALT to wire the cursor from I2 through to the coil
field.
The cursor changes into a flashing wiring arrow and automatically jumps to the next logical wiring position.
X Press the cursor button í. Contact I2 will be connected up
to the coil field.
X Press the cursor button í once more.
The cursor will move to the coil field.
h
ALT also has two other functions depending on the cursor position:
• From the left contact field, press ALT to insert a new, empty rung.
• The contact under the cursor can be changed between a make and break contact by pressing the ALT button.
êê êê êêê
êê êêê
M
l
L
m
l
h
easy automatically wires adjacent contacts in a rung up to the coil.
I1-I2l êê êê êê êêê êê êê êê êêê êê êê êê êêê
h
You can use the DEL button to erase a connection at the cursor or arrow position. Where connections intersect, the vertical connections are deleted first, then, if you press DEL again, the horizontal connections are deleted.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 75
Setting the menu language
71
05/04 AWB2528-1508GB
X Press OK.
easy will insert relay coil
Q1. The specified coil function Ä
and the output relay
Q1 are correct and do not have to be
changed.
Your first working easy circuit diagram now looks like this:
Press ESC to leave the circuit diagram display.
The menu shown appears.
X Press OK.
The circuit diagram is now automatically saved. CANCEL exits the circuit diagram. Changes that have been made to the circuit diagram are not saved.
Once you have connected buttons S1 and S2, you can test your circuit diagram straight away.
Testing the circuit diagram
X Switch with ESC to the main menu and select the STOP
å RUN
menu option.
With
STOP RUN å and STOP å RUN you switch
to the RUN or STOP operating modes.
easy is in RUN mode if the tick is present at the corresponding menu item. i.e.
STOP RUN å.
I1-I2----ÄQ1
I1-I2----ÄQ1
SAVE
CANCEL
h
easy saves all the necessary circuit diagram and program data retentively in the internal data memory.
PROGRAM....Æ
STOP å RUN
PARAMETER.. INFO... æ
h
The tick next to a menu item indicates which operating mode or function is currently active.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 76
Commissioning
72
05/04 AWB2528-1508GB
X Press OK.
The tick changes to STOP RUN
å
The Status display shows the current mode and the switching states of the inputs and outputs.
X Change to the Status display by pressing ESC and press
pushbutton actuator S1.
The contacts for inputs I1 and I2 are activated and relay Q1 picks up.
Power flow display
easy allows you to check rungs in RUN mode. This means that you can check your circuit diagram via the built-in power flow display while it is being processed by easy.
X Switch to the circuit diagram display (confirm PROGRAM
menu with OK) and actuate pushbutton S1.
The relay picks up and easy displays the power flow.
X Press pushbutton actuator S2, that has been connected as
a break contact.
The rung is interrupted and relay Q1 drops out.
Press ESC to return to the Status display.
PROGRAM....Æ
STOP RUN å
PARAMETER.. INFO... æ
12..........
I MO 02:00
1....... RUN
I1-I2----ÄQ1
I1-I2----ÄQ1
h
A circuit diagram does not have to be completed before you can test parts of it with easy.
easy simply ignores any incomplete wiring that is not yet working and only uses the finished wiring.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 77
Setting the menu language
73
05/04 AWB2528-1508GB
Deleting the circuit diagram
X Switch easy to STOP mode.
The display shows
STOP å RUN.
X Use PROGRAM... to switch from the main menu to the
next menu level.
X Select DELETE PROGRAM
easy will display the prompt DELETE?
X Press OK to delete the program or ESC to cancel.
Press ESC to return to the Status display.
Fast circuit diagram entry
You can create a circuit diagram in several ways. The first option is to enter the elements in the circuit and then to wire all the elements together. The other option is to use the enhanced operator guidance of easy and create the circuit diagram in one go, from the first contact through to the last coil.
If you use the first option, you will have to select some of the elements in order to create and connect up your circuit diagram.
The second, faster option is what you learned in the example. In this case you create the entire rung from left to right.
h
easy must be in STOP mode in order to extend, delete or modify the circuit diagram.
PROGRAM
DELETE PROG
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 78
74
05/04 AWB2528-1508GB
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 79
75
05/04 AWB2528-1508GB
4 Wiring with easy
By working through the example in chapter 3 you should now have gained an initial impression of just how simple it is to create a circuit diagram in easy. This chapter describes the full range of easy functions and provides further examples of how to use easy.
Operation of easy Buttons for editing circuit diagrams and function
relays
Delete rung, contact, relay or empty rung in the circuit diagram
Toggle between break and make contact Connect contacts, relays and rungs Add rungs
ÍÚ úí
Change value Move cursor up and down Change position Move cursor to left and right
Cursor buttons set as P buttons:
ú í
Input P1, Input P3,
Í Ú
Input P2 Input P4
Undo setting since previous OK Exit current display or menu
Change, add contact/relay Save setting
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 80
Wiring with easy
76
05/04 AWB2528-1508GB
Operation
The cursor buttons in the easy circuit diagram perform three functions. The current mode is indicated by the appearance of the flashing cursor.
•Move
•Enter
• Connect
In Move mode you can use
ÍÚ úí to move the cursor
around the circuit diagram in order to select a rung, contact or relay coil.
Use OK to switch to Entry mode so that you can enter or change a value at the current cursor position. If you press ESC in Entry mode, easy will undo the most recent changes.
Press ALT to switch to Connect mode for wiring contacts and relays. Press ALT again to return to Move.
Press ESC to leave the circuit diagram and parameter display.
Opening the parameter display for function relays with contacts or coils
If you specify the contact or coil of a function relay in Entry mode, easy automatically switches from the contact number to the function relay parameter display when you press OK.
Press
í to switch to the next contact or coil field without
entering any parameters.
Program
A program is a sequence of commands which easy executes cyclically in RUN mode. An easy program consists of the necessary settings for the device, password, system settings, a circuit diagram and/or function relays.
â
I 1
l
h
easy performs many of these cursor movements automatically. For example, easy switches the cursor to Move mode if no further entries or connections are possible at the selected cursor position.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 81
Operation of easy
77
05/04 AWB2528-1508GB
Circuit diagram
The circuit diagram is that part of the program where the contacts are connected together. In RUN mode a coil is switched on and off in accordance with the current flow and the coil function specified.
Function relays
Function relays are program elements with special functions. Example: timing relays, time switches, counters. Function relays are elements provided with or without contacts and coils as required. In RUN mode the function relays are processed according to the circuit diagram and the results are updated accordingly.
Examples: Timing relay = function relay with contacts and coils Time switch = function relay with contacts
Relay
Relays are switching devices which are electronically simulated in easy. They actuate their contacts according to their designated function. A relay consists of at least a coil and a contact.
Contacts
You modify the current flow with the contacts in the easy circuit diagram. Contacts such as make contacts carry a 1 signal when closed and 0 when open. Every contact in the easy circuit diagram can be defined as either a make contact or a break contact.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 82
Wiring with easy
78
05/04 AWB2528-1508GB
Coils
Coils are the actuating mechanisms of relays. In RUN mode, the results of the wiring are sent to the coils, which switch on or off accordingly. Coils can have seven different coil functions.
Table 6: Usable contacts
easy works with different contacts, which can be used in any order in the contact fields of the circuit diagram.
Table 7: Contacts
Contact
easy representation
Make contact Open in the rest state
I, Q, M, N, A, Ö, Y, C, T, O, P, :, D, S, R, Z
Break contact Closed in the rest state
i, q, m, , a, ö, , c, t, , p, ,
, ,
N Y O D
S R Z
h
To ensure compatibility with easy400 and easy600 devices, each easy500 and easy700 is provided logically with all possible contacts. If contacts are not supported by the device, i.e. devices without a clock, their switching state is always zero. The contacts (make contact) of the time switches are always set to logic 0.
The advantage of this process is that you can use the same circuit diagram on all easy500, easy700, easy-AB, easy­AC, easy-DA and easy-DC devices.
Contact type Make
contact
Break contact
easy500 easy700 Page
Analog value comparator function relay
A a A1…A16 A1…A16 104
Counter function relay
C c C1…C16 C1…C16 117
Text marker function relay
D D1D16 D1D16 137
7-day time switch function relay
Ö ö Ö1…Ö8 Ö1…Ö8 143
D
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 83
Operation of easy
79
05/04 AWB2528-1508GB
Relay, function relays
easy has nine different types of relay for wiring in a circuit diagram.
easy input terminal I i I1…I8 I1…I12 83
0 signal
I13 I13
Expansion status
I14 245
Short-circuit/overload
I16 I15…I16 245
Marker (auxiliary relay)
M m M1…M16 M1…M16 91
Marker (auxiliary relay)
N N1…N16 N1…N16 91
Operating hours counter
O O1…O4 O1…O4 149
Cursor button
P p P1…P4 P1…P4 89
easy output
Q q Q1…Q4 Q1…Q8 83
Expansion input terminal
R R1…R12 83
Short-circuit/overload with expansion
R R15…R16 245
easy output (expansion or S auxiliary marker)
S S1S8
(as marker)
S1S8 91
Timing function relay
T t T1…T16 T1…T16 154
Jump label
: :1…:8 :1…:8 171
Year time switch
Y Y1…Y8 Y1…Y8 174
Master reset, (central reset)
Z Z1…Z3 Z1…Z3 181
Contact type
Make contact
Break contact
easy500 easy700 Page
N O
R R
S
Y Z
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 84
Wiring with easy
80
05/04 AWB2528-1508GB
You can set the switching behaviour of these relays by means of the coil functions and parameters selected.
The options for setting output and marker relays are listed with the description of each coil function.
h
To ensure compatibility with easy400 and easy600 devices, each easy500 and easy700 is provided logically with all relay types. If a relay type is not supported by the device, i.e. devices without a clock, their switching state is always zero. The contacts (make contact) of the time switches are always set to logic 0.
The advantage of this process is that you can use the same circuit diagram on all easy500, easy700, easy-AB, easy­AC, easy-DA and easy-DC devices. Furthermore, you can use outputs that are not physically present as markers.
Relays easy
display
easy500 easy700 Coil
function
Parame ters
Analog value comparator function relays
A A1…A16 A1…A16 j
Counter function relays
C C1…C16 C1…C16 j j
Text marker function relays
D D1…D16 D1…D16 j j
7-day time switch function relays
Ö Ö1…Ö4 Ö1…Ö4 j
Markers (auxiliary relay)
M M1…M16 M1…M16 j
Markers (auxiliary relay)
N N1…N16 N1…N16 j
Operating hours counters
O O1…O4 O1…O4 j j
easy output relays
Q Q1…Q8 Q1…Q8 j
easy output relay expansion, auxiliary markers
S S1S8
(as marker)
S1S8 j
Timer function relays
T T1…T16 T1…T16 j j
Conditional jump
: :1…:8 :1…:8 j
Year time switch
Y Y1…Y8 Y1…Y8 j
Master reset, (central reset)
Z Z1…Z3 Z1…Z3 j
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 85
Operation of easy
81
05/04 AWB2528-1508GB
The coil functions and parameters are listed with the description of each function relay.
Circuit diagram display
In the easy circuit diagram, contacts and coils are connected up from left to right - from the contact to the coil. The circuit diagram is created on a hidden wiring grid containing contact fields, coil fields and rungs. It is then wired up with connections.
• You can add switch contacts in the three contact fields. Easy adds the first energized contact field automatically.
• You add the relay coil to be controlled together with its function and designation in the coil field.
• Every line in the circuit diagram forms a rung. Up to 128 rungs can be wired in a circuit diagram.
Connections are used to produce the electrical contact between switch contacts and the coils. They can be created across several rungs. Each point of intersection is a connection.
Contact fields Coil field
Rungs/
Current paths
I1-I2uT1-ÄQ1 Q1-Ö1kêê êêê êê êê êê êêê êê êê êê êêê
Rungs
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 86
Wiring with easy
82
05/04 AWB2528-1508GB
Saving and loading circuit diagrams
There are two ways of saving circuit diagrams in easy externally:
• By saving to a memory card
• By saving to a PC running EASY-SOFT-BASIC.
Once they have been saved, programs can be reloaded into easy, edited and run.
All circuit diagram data is saved in easy. In the event of a power failure the data will be retained until the next time it is overwritten or deleted.
Memory card
Each EASY-M-32K memory card contains a circuit diagram which is inserted into the easy interface. The program is stored retentively on the memory card.
The way the memory card works and a description of how to transfer a program to the card is given in section “Memory card” on page 248.
EASY-SOFT-BASIC
EASY-SOFT-BASIC is a PC program with which you can create, store, test (simulate) and manage easy circuit diagrams.
h
The circuit diagram display performs two functions:
• In STOP mode it is used to edit the circuit diagram.
• In RUN mode it is used to check the circuit diagram using the Power flow display.
h
EASY-M-8K memory cards of easy400 devices can be read in easy500. EASY-M-8K memory cards of easy400 devices and easy600 EASY-M16K memory cards can be read in easy700.
Write operations from easy500 and easy700 are only possible to the EASY-M32K memory card.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 87
Working with contacts and relays
83
05/04 AWB2528-1508GB
Completed circuit diagrams are transferred between your PC and easy via the connecting cable. Once you have transferred a circuit diagram, simply run easy straight from your PC.
Details on the program and transferring circuit diagrams are given in section “EASY-SOFT-BASIC” from page 252.
Working with contacts and relays
In easy circuit diagrams, the switches, buttons and relays of conventional circuit diagrams are connected up using input contacts and relay coils.
Input and output contacts
First specify which input and output terminals you wish to use in your circuit.
Depending on the type and configuration, easy has 8, 12 or 24 input terminals and 4, 6, 8, 10 or 16 outputs. The signal states on the input terminals are detected in the circuit diagram with the input contacts I1 to I12. R1 to R12 are the
Conventional circuit easy circuit diagram
easy terminal
Connect make contact S1 to input terminal I2 Connect make contact S2 to easy input terminal I3 Connect load H1 to easy output Q4 S1 or S2 switches on H1.
easy circuit diagram
H1
S1
K1
K1
S2
I2u------ÄQ4 I3k
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 88
Wiring with easy
84
05/04 AWB2528-1508GB
input contacts of the expansion. In the circuit diagram the outputs are controlled via the corresponding output relay coils Q1 to Q8 or S1 to S8 (expansion).
Entering and changing contacts and relay coils
A switch contact is selected in easy via the contact name and contact number.
A relay coil is defined by its coil function, name and number.
Values for contacts and coil fields are changed in Entry mode. The value to be changed flashes.
X Move the cursor using the buttons úíÍÚ to a contact
or coil field.
X Press OK to switch to Entry mode.
X Use úí to select the position you wish to change, or press
OK to jump to the next position.
X Use ÍÚ to modify the value of the position.
I2
Contact name
Contact number
ÄQ4
Coil function
Relay name Relay number
h
A full list of all the contacts and relays is given in the overview starting on page 78.
I1
h
If the field is empty, easy will enter contact I1 or the coil
ÄQ1.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 89
Working with contacts and relays
85
05/04 AWB2528-1508GB
easy will leave Entry mode when you press úí or OK to leave
a contact field or coil field.
Deleting contacts and relay coils
X Move the cursor using the buttons úíÍÚ to a contact
or coil field.
X Press DEL.
The contact or the relay coil will be deleted, together with any connections.
Changing make contacts to break contacts
Every switch contact in the easy circuit diagram can be defined as either a make contact or a break contact.
Change
I1 to I2 in the
contact field
Change ÄQ1 to ÄQ8 in the coil field
I1 I1 IQQQ1 ÄQ8
Q
í or
OK
2 Í Å ú M
í or
OK
2 Ú
M3 è
N3
N4 È
C4
A5 ä
T5
Ö. S
O.
Y.
R
:. C. D. T. S. OZ1
P
1 2
2
: D S
í or
OK
í or
OK
R Z
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 90
Wiring with easy
86
05/04 AWB2528-1508GB
X Switch to Entry mode and move the cursor over the
contact name.
X Press ALT. The make contact will change to a break
contact.
X Press OK 2 to confirm the change.
Figure 39: Changing contact I3 from make to break
Creating and modifying connections
Switch contacts and relay coils are connected with the wiring arrow in Connect mode. easy displays the cursor in this mode as an arrow.
X Use úíÍÚ to move the cursor onto the contact field or
coil field from which you wish to create a connection.
X Press ALT to switch to Connect mode.
X Use úí to move the diagonal arrow between the contact
fields and coil fields and ÍÚ to move between rungs.
X Press ALT to leave Connect mode.
easy will leave the mode automatically when you move the diagonal arrow onto a contact field or coil field which has already been assigned.
2
I2u------ÄQ4 I3k
I2u------ÄQ4 i3k
I2u------ÄQ4 i3kê
l
h
Do not position the cursor on the first contact field. At this position the ALT button has a different function (Insert rung).
h
In a rung, easy automatically connects switch contacts and the connection to the relay coil if there are no empty fields in-between.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 91
Working with contacts and relays
87
05/04 AWB2528-1508GB
Never work backwards. You will learn why wiring backwards does not work in section “Example: Do not wire backwards” from page 237.
When wiring more than three contacts in series, use an M or N marker.
Deleting connections
X Move the cursor onto the contact field or coil field to the
right of the connection that you want to delete. Press ALT to switch to Connect mode.
X Press DEL.
easy will delete a connection. Closed adjacent connections will be retained.
If several rungs are connected to one another, easy first deletes the vertical connection. If you press DEL again, it will delete the horizontal connection as well.
Close the delete operation with ALT or by moving the cursor to a contact or coil field.
I1-Q4-i3o z-----k hI2-I4-ÄQ2
I1-Q4-i3-ÄM1 I2-I4-M1-ÄQ2
h
You cannot delete connections that easy has created automatically.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 92
Wiring with easy
88
05/04 AWB2528-1508GB
Inserting and deleting a rung
The easy circuit diagram shows four of the 128 rungs in the display at the same time. If you move the cursor past the top or bottom of the display, easy automatically scrolls up or down the display to show hidden rungs – even empty ones.
A new rung is added below the last connection or inserted above the cursor position:
X Position the cursor on the first contact field of an empty
rung.
X Press ALT.
The existing rung with all its additional connections is “shifted” downwards. The cursor is then positioned directly in the new rung.
Deleting a rung
easy will only remove empty rungs, i.e. those without contacts or coils.
X Delete all the contacts and relay coils from the rung. X Position the cursor on the first contact field of the empty
rung.
X Press DEL.
The subsequent rung(s) will be “pulled up” and any existing links between rungs will be retained.
I2u------ÄQ4 I3k
I2u------ÄQ4
 n
I3k
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 93
Working with contacts and relays
89
05/04 AWB2528-1508GB
Switching with the cursor buttons
With easy, you can also use the four cursor buttons as hard­wired inputs in the circuit diagram.
The buttons are wired in the circuit diagram as contacts P1 to P4. The P buttons can be activated and deactivated in the System menu.
The P buttons can also be used for testing circuits or manual operation. These button functions are also useful for servicing and commissioning purposes.
Example 1:
A lamp at output relay Q1 is switched on and off via inputs I1 and I2 or using cursor buttons
Í Ú.
Example 2
Terminal I1 is used to control output relay Q1. Terminal I5 switches to Cursor button mode and deactivates rung I1 via
M
1.
The Status menu display shows whether the P buttons are used in the circuit diagram.
• P: button function wired and active.
• P2: button function wired, active and P2 button Í
pressed.
• P-: button function wired and not active.
• Empty field: P buttons not used.
P1
P2
P3
P4
I1u------SQ1 P2k I2u------RQ1 P4k
I5-------ÄM1 I1-m1u---ÄQ1 P1-M1k
h
The P buttons are only detected as switches in the Status menu. The cursor buttons are used for other functions in the menus, the power flow display and in the text display.
............
IP2 FR 15:59
........STOP
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 94
Wiring with easy
90
05/04 AWB2528-1508GB
Checking the circuit diagram
easy contains a built-in measuring device enabling you to monitor the switching states of contacts and relay coils during operation.
X Complete the small parallel connection and switch easy to
RUN mode via the main menu.
X Return to the circuit diagram display.
You are now unable to edit the circuit diagram.
The circuit diagram display performs two functions depending on the mode:
• STOP: Creation of the circuit diagram
• RUN: Power flow display
X Switch on I3.
In the power flow display, energized connections are thicker than non-energized connections.
You can follow energized connections across all rungs by scrolling the display up and down.
I2---u---ÄQ4 I3---k
h
If you switch to the circuit diagram display and are unable to modify a circuit diagram, first check whether easy is in STOP mode.
I2---U---ÄQ4 I3---k
h
The power flow display will not show signal fluctuations in the millisecond range. This is due to the inherent delay factor of LCD displays.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 95
Working with contacts and relays
91
05/04 AWB2528-1508GB
Coil functions
You can set the coil function to determine the switching behaviour of relay coils. The following coil functions are available for relays Q, M, S, D, “:”:
Table 8: Coil function
Marker relays M and N are used as a flag. The S relay can be used as the output of an expansion unit or as a marker if no expansion unit is connected. The only difference between them and the output relay Q is that they have no output terminals.
Circuit diagram symbol
easy display
Coil function Example
Ä Contactor
function
ÄQ1, ÄD2, ÄS4, Ä:1, ÄM7
Å Contactor
function with negated result
ÅQ1, ÅD2, ÅS4
è Cycle pulse with
falling edge
èQ3, èM4, èD8, èS7
È Cycle pulse with
rising edge
ÈQ4, ÈM5, ÈD7, ÈS3
ä Impulse relay
function
äQ3, äM4, äD8, äS7
S Set (latching) SQ8, SM2, SD3,
SS4
R Reset
(unlatching)
RQ4, RM5, RD7, RS3
h
The coil functions of the function relays are described in the descriptions for the appropriate relays.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 96
Wiring with easy
92
05/04 AWB2528-1508GB
Rules for wiring relay coils
To ensure a clear overview of all relay states only assign the same coil function once to a relay (
ä, S, R). However,
retentive coil functions such as
ä, S, R can be used several
times if required by the circuit diagram logic.
Exception: When using jumps to structure a circuit diagram, this coil function can also be used effectively several times.
Relay with contactor function
Ä
The output signal follows immediately after the input signal and the relay acts as a contactor.
Figure 40: Signal diagram of contactor function
Representation in easy:
• Output relays Q:
ÄQ1 to ÄQ8 (depending on type)
•Markers M, N:
ÄM1 to ÄM16, ÄN1 to ÄN16
• Function relays (Text) D: ÄD1 to ÄD16
• Output relays S: ÄS1 to ÄS8
•Jumps: Ä:1 to Ä:8
h
The coil functions Ä, Å, è, È, (contactor, contactor
negated, cycle pulse negative, rising edge) must only be used once for each relay coil. The last coil in the circuit diagram determines the status of the relay.
When controlling a contactor or relay, the control coil is only present once. If you are creating parallel circuits, use Set, Reset as a coil function.
on
on
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 97
Working with contacts and relays
93
05/04 AWB2528-1508GB
Contactor function with negated result (inverse contactor function)
Å
The output signal is simply an inversion of the input signal; the relay operates like a contactor with contacts that have been negated. If the coil is triggered with the 1 state, the coil switches its make contacts to the 0 state.
Figure 41: Signal diagram of inverse contactor function
Representation in easy
• Output relays Q:
ÅQ1 to ÅQ8 (depending on type)
•Markers M, N:
ÅM1 to ÅM16, ÅN1 to ÅN16
• Function relays (Text) D: ÅD1 to ÅD16
• Output relays S: ÅS1 to ÅS8
•Jumps: Å:1 to Å:8
Falling edge evaluation (cycle pulse) è
This function is used if the coil is only meant to switch on a falling edge. With a change in the coil state from 1 to 0, the coil switches its make contacts to the 1 state for one cycle.
Figure 42: Signal diagram of cycle pulse with falling edge
on
on
on
on
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 98
Wiring with easy
94
05/04 AWB2528-1508GB
Representation in easy:
•Markers M, N:
èM1 to èM16, èN1 to èN16
•Jumps: è:1 to è:8
Rising edge evaluation (cycle pulse) È
This function is used if the coil is only meant to switch on a rising edge. With a change in the coil state from 0 to 1, the coil switches its make contacts to the 1 state for one cycle.
Figure 43: Signal diagram of cycle pulse with rising edge
Representation in easy:
•Markers M, N:
ÈM1 to ÈM16, ÈN1 to ÈN16
•Jumps: È:1 to È:8
h
Physical outputs should not be used as a cycle pulse is generated.
on
on
h
Physical outputs should not be used as a cycle pulse is generated.
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 99
Working with contacts and relays
95
05/04 AWB2528-1508GB
Impulse relay ä
The relay coil switches whenever the input signal changes from 0 to 1. The relay behaves like an impulse relay.
Figure 44: Signal diagram of impulse relay
Representation in easy:
• Output relays Q:
äQ1 to äQ8 (depending on type)
•Markers M:
äM1 to äM16
• Function relays (Text) D: äD1 to äD8
• Relays S: äS1 to äS8
on
on
h
A coil is automatically switched off if the power fails and if STOP mode is active. Exception: Retentive coils retain signal 1 (a section “Retention (non-volatile data storage)” from page 230).
For Immediate Delivery call KMParts.com at (866) 595-9616
Page 100
Wiring with easy
96
05/04 AWB2528-1508GB
Latching relay
The “latch” and “unlatch” relay functions are used in pairs. The relay picks up when latched and remains in this state until it is reset by the “unlatch” function.
:
Figure 45: Latching relay signal diagram
• Range A: The Set coil and the Reset coil are triggered at different times
• Range B: Reset coil is triggered at the same time as the Set coil
• Range C: Power supply switched off
Representation in easy:
• Q output relays:
SQ1 to SQ8, RQ1 to RQ8 (depending on
type)
• M markers:
SM1 to SM16, RM1 to RM16
• (Text) D function relays: SD1 to SD8, RD1 to RD8
•S relays:SS1 to SS8, RS1 to RS8
Use each of the two relay functions S and R once only per
relay.
If both coils are triggered at the same time, priority is given to the coil further down in the circuit diagram. This is shown in the above signal diagram in section B.
on
on
S
R
on
AB C
I1-I2----SQ1
I2-------RQ1
For Immediate Delivery call KMParts.com at (866) 595-9616