Mod-tronic 40T Specifications

Out 1 solidly lit
Out 1 flashing
°C
°F
Loc
Pr1
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
©Copyright 2009 Dwyer Instruments, Inc. Printed in U.S.A. 12/09 FR# R5-443741-00
The Series 40T Digital Temperature Switch accepts thermocouple and RTD inputs to allow temperature measurements and set points up to 1999°F (1300°C). Observ­ing the current status of the control is made easier with the 3-1/2 digit, multi-color LED display that has alarm, defrost and output symbols. For added versatility, the temper­ature units can be field selected for °F or °C. For cooling applications, manual defrost mode can be initiated by pushing a single button. A flashing alarm informs users when the current temperature exceeds preset limits. When programming multiple units, a programming key is available to reduce set up time.
INSTALLATION Note: Unit must be mounted away from vibration, impacts, water and corrosive gases.
• Cut hole in panel 71 x 29 mm (2.80 x 1.14 in)
• Apply silicone around the perimeter of the hole to prevent leakage
• Insert unit into hole from the front side of the panel
• Slide the mounting bracket securely against the panel from the rear of the unit
• Wiring diagram is displayed on top of the control
WIRING
Avoid installing the temperature probe cables in close proximity of any power cables. If the length of the probe cables is longer than 100 meters, a recalibration adjustment may be made using the CA1 parameter.
Series 40T Digital Thermocouple/RTD Temperature Switch
Specifications - Installation and Operating Instructions
Bulletin T-40T
SPECIFICATIONS Probe Range: K T/C: -140 to 1999°F (-100 to 1300°C);
J T/C: -140 to 1450°F (-100 to 800°C); RTD: -320 to 1200°F (-200 to 650°C).
Input: Pt100 RTD and J/K type thermocouple. Output: 16A @ 250 VAC SPDT relay (max current allowed is 10A). Control Type: On/off. Power Requirements: 12 to 24 VAC/VDC, 115 VAC or 230 VAC (depending on
model).
Accuracy: ±1% F.S. Display: 3-1/2 digit red display. Resolution: 0.1°C. Memory Backup: Non-volatile memory. Temperature Limits: 32 to 131°F (0 to 55°C). Weight: 2.3 oz (65 g). Front Panel Rating: IP 65. Agency Approvals: UL, CE.
DISPLAYING ROOM TEMPERATURE
If the P5 parameter is set to display the temperature set point, the probe temperature can be displayed by pressing the DOWN ARROW key for two seconds until Pb1 is dis­played. Next, hit the SET key. To return to the normal display, press SET key.
MANUAL DEFROST ACTIVATION/DEACTIVATION
To manually activate the defrost cycle, press the UP ARROW key for four seconds. This feature is disabled during heating operation.
PARAMETER LOCK OUT ACTIVATION/DEACTIVATION
The key pad lock out can be activated/deactivated by pressing the SET and DOWN ARROW keys simultaneously for two seconds. The display will flash Loc or UnL to sig­nify the change in states.
ALARM BUZZER RESET
The audible alarm can be silenced by pressing any key.
RESTORING FACTORY DEFAULT SETTINGS
Factory settings can be restored by following the below procedure:
• Pressing the UP ARROW and DOWN ARROW keys for four seconds until PA is displayed
• Press the SET key
• Press the UP ARROW or DOWN ARROW to adjust the value to 743
• Press SET key
• Pressing the UP ARROW and DOWN ARROW keys for four seconds until dEF is displayed
• Press SET key
• Press the UP ARROW or DOWN ARROW to adjust the value to 149
• Press SET key
• Cycle the power after the flashing dEF goes away
Output 1 is active
Either modification of set point or call for load during
load protection (C1 or C2)
Defrost cycle is active
Alarm condition is present
Temperature is measured in °C
Temperature is measured in °F
Key pad is locked
Probe 1 error
DISPLAY MESSAGES
ADJUSTING PARAMETER VALUES
In order to change the parameter values, follow the procedure below:
• Press UP ARROW and DOWN ARROW simultaneously for four seconds until PA is displayed
• Press SET
• Use UP ARROW or DOWN ARROW to adjust value to -19
• Press SET
• Press UP ARROW and DOWN ARROW simultaneously for four seconds until SP is displayed
• Use UP ARROW or DOWN ARROW to cycle through parameters
• Press SET to view value of parameter
• Use UP ARROW or DOWN ARROW to adjust value of parameter
• Press SET to store value
• Press UP ARROW and DOWN ARROW simultaneously for four seconds to exit menu
MAINTENANCE, CLEANING AND REPAIR
After final installation of the unit no routine maintenance is required. Clean the surface of the display controller with a soft and damp cloth. Never use abrasive detergents, petrol, alcohol or solvents. A periodic check of the system calibration is recommended. The Series 40T is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief de­scription of the problem plus any relevant application notes. Contact customer serv­ice to receive a return goods authorization number before shipping.
1 2 3 4 5 6 7
POWER SUPPLY
POWER SUPPLY
LOAD1
Tc
J/K
+
TO 40X-K TO SUP. (OPT.)
9 10 11 12
9 10 11 12
16A 250V~
MAX
10A
Pt100
2-31/64 [63.22]
1-3/32 [27.94]
3
[76.20]
1-11/32 [33.99]
2-3/8
[60.33]
3-3/16 [80.92]
2-3/16 [55.52]
7/16
[10.92]
Note: Terminals 4 and 5 are only on 115 VAC and 230 VAC. Models 12 to 24 VAC only have terminals 6 and 7.
T-40T:Layout 1 12/4/09 11:27 AM Page 1
Parameter
SP CA1 P0 P1 P2 P5 r0 r1 r2 r3 r5 C1 C2 C3 C4 C5 d0 d3 d4 d5 d6 A1 A2 A3 A4 A5 A6 A7 E9
Description
Set point Ambient probe adjustment Type of input probe Decimal point position Display units Value displayed during normal operation Set point differential Minimum set point value Maximum set point value Set point locked Cooling or heating Minimum time between compressor starts Minimum compressor stoppage time Minimum on time of compressor Off time of fault cycle On time of fault cycle Interval between defrost Duration of defrost cycle Defrost on power up Defrost delay upon power up Display during defrost cycle Alarm set point 1 Alarm delay for A1 Alarm 1 type Alarm delay upon set point modification Alarm set point 2 Alarm delay for A2 Alarm 2 type Reserved for future use
Units
Degrees Degrees Option Option Option Option Degrees Degrees Degrees Option Option Minutes Minutes Seconds Minutes Minutes Hours Minutes Option Minutes Option Degrees Minutes Option Minutes Degrees Minutes Option None
Range
r1 to r2
-25 to 25 0 to 3 0 or 1 0 or 1 0 or 1
0.1 to 99.0
-199.0 to r2 r1 to 1999 0 or 1 0 or 1 0 to 240 0 to 240 0 to 240 0 to 240 0 to 240 0 to 99 0 to 99 0 or 1 0 to 99 0 or 1
-199 to 1999 0 to 240 0 to 4 0 to 240
-199 to 1999 0 to 240 0 to 4 None
Factory Setting
0.0
0.0 0 1 0 0
2.0
0.0
350.0 0 1 0 0 0 10 10 8 0 1 0 1
0.0 0 0 0
0.0 0 0 None
PARAMETER LIST
PARAMETER DESCRIPTION
SP Sets ambient temperature set point between r1 and r2 CA1 Ambient probe calibration adjustment P0 Type of input probe
0 = J type thermocouple 1 = K type thermocouple 2 = 3 wire Pt100 RTD
3 = 2 wire Pt100 RTD P1 Position of decimal place P2 Display engineering units
0 = °C
1 = °F
2 = No units P5 Value shown during normal operation
0 = Probe temperature
1 = Set point r0 Set point differential or hysteresis r1 Minimum value for set point r2 Maximum value for set point r3 Set point lock out
0 = Unlocked
1 = Locked r5 Selection of heating/cooling operation
0 = Cooling
1 = Heating C1 Minimum time between compressor starts C2 Minimum time compressor must remain off before being restarted C3 Minimum time compressor must remain on after being started C4 During probe error, time compressor is off C5 During probe error, time compressor is on d0 Interval of time between defrost cycles
(if 0, defrost will never be activated) d3 Duration of defrost cycle d4 Start defrost cycle upon power up
0 = No
1 = Yes d5 Defrost delay time upon power up (d4 must be 1) d6 Temperature shown during defrost
0 = Display probe temperature
1 = Display probe temperature up to (set point + r0)
if probe temperature is below (set point + r0) at activation of
defrost cycle. Display probe temperature if the probe
temperature is above (set point + r0) at activation of defrost cycle. A1 Alarm 1 temperature set point A2 Alarm 1 not activated unless temperature remains in alarm state
for this time A3 Alarm 1 type
0 = Alarm disabled
1 = Absolute low alarm (A1)
2 = Absolute high alarm (A1)
3 = Deviation low alarm (SP - A1)
4 = Deviation high alarm (SP + A1) A4 Temperature alarms not activated for this time after modifications
to set point A5 Alarm 2 temperature set point A6 Alarm 2 not activated unless temperature remains in alarm state
for this time A7 Alarm 2 type
0 = Alarm disabled
1 = Absolute low alarm (A1)
2 = Absolute high alarm (A1)
3 = Deviation low alarm (SP - A1)
4 = Deviation high alarm (SP + A1) E9 Reserved
RESISTANCE VS TEMPERATURE TABLE
°C
-55
-50
-45
-40
-35
-30
-25
-20
-15
-10
-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150
°F
-67.0
-58.0
-49.0
-40.0
-31.0
-22.0
-13.0
-4.0
5.0
14.0
23.0
32.0
41.0
50.0
59.0
68.0
77.0
86.0
95.0
104.0
113.0
122.0
131.0
140.0
149.0
158.0
167.0
176.0
185.0
194.0
203.0
212.0
221.0
230.0
239.0
248.0
257.0
266.0
275.0
284.0
293.0
302.0
Temperature
A
607800.00
441200.00
323600.00
239700.00
179200.00
135200.00
102900.00
78910.00
61020.00
47540.00
37310.00
29490.00
23460.00
18780.00
15130.00
12260.00
10000.00
8194.00
6752.00
5592.00
4655.00
3893.00
3271.00
2760.00
2339.00
1990.00
1700.00
1458.00
1255.00
1084.00
939.30
816.80
712.60
623.60
547.30
481.80
425.30
376.40
334.00
297.20
265.10
237.00
B
963849.00
670166.00
471985.00
336479.00
242681.00
176974.00
130421.00
97081.00
72957.00
55329.00
42327.00
32650.00
25392.00
19901.00
15712.00
12493.00
10000.00
8057.00
6531.00
5326.00
4368.00
3602.00
2986.00
2488.00
2083.00
1752.00
1480.00
1255.00
1070.00
915.50
786.60
678.60
587.60
510.60
445.30
389.60
341.90
301.00
265.80
235.30
208.90
186.10
C
289154.70
201049.80
141595.50
100943.70
72804.30
53092.20
39126.30
29.124.30
21887.10
16598.70
12698.10
9795.00
7617.60
5970.30
4713.60
3747.90
3000.00
2417.10
1959.30
1597.80
1310.40
1080.60
895.80
746.40
624.90
525.60
444.00
376.50
321.00
274.65
235.98
203.58
176.28
153.18
133.59
116.88
102.57
90.30
79.74
70.59
62.67
55.83
D
78.32
80.31
82.29
84.27
86.25
88.22
90.19
92.16
94.12
96.09
98.04
100.00
101.95
103.90
105.85
107.79
109.74
111.67
113.61
115.54
117.47
119.40
121.32
123.24
125.16
127.08
128.99
130.90
132.80
134.71
136.61
138.51
140.40
142.29
144.18
146.07
147.95
149.83
151.71
153.58
155.46
157.33
E
783.2
803.1
822.9
842.7
862.5
882.2
901.9
921.6
941.2
960.9
980.4
1000.0
1019.5
1039.0
1058.5
1077.9
1097.4
1116.7
1136.1
1155.4
1174.7
1194.0
1213.2
1232.4
1251.6
1270.8
1289.9
1309.0
1328.0
1347.1
1366.1
1385.1
1404.0
1422.9
1441.8
1460.7
1479.5
1498.3
1517.1
1535.8
1554.6
1573.3
F
2394000.00
1646200.00
1145800.00
806800.00
574400.00
413400.00
300400.00
220600.00
163.500.00
122280.00
92240.00
70160.00
53780.00
41560.00
32340.00
25360.00
20000.00
15892.00
12704.00
10216.00
8264.00
6722.00
5498.00
4520.00
3734.00
3100.00
2586.00
2166.00
1822.60
1540.00
1306.40
1112.60
951.00
815.80
702.20
606.40
525.60 N/A N/A N/A N/A N/A
Resistance Curves (in Ohms)
T-40T:Layout 1 12/4/09 11:27 AM Page 2
Loading...