Modine Manufacturing PD/BD, PDP/BDP, PSH/BSH Installation Instructions Manual

75-535.11
5H605846A Rev. Ul
December, 2008
SELECTION AND INSTALLATION INSTRUCTIONS
high altitude orifice kit
models PD/BD, PDP/BDP, PSH/BSH
and model series “D”, “H”, “I”, “O” duct furnace/make up air units
(not including separated combustion)
1. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing.
2. Gas supply shall be shut-off and the electrical power disconnected before proceeding with the conversion. Failure to do so could result in fi re, explosion or electrical shock.
WARNING
IMPORTANT
1. The use of this manual is specifically intended for a qualified installation and service agency. All installation and service of these kits must be performed by a qualified installation and service agency.
2. These instructions must also be used in conjunction with the Installation and Service manual originally shipped with the appliance being converted, in addition to any other accompanying component supplier literature.
Figure 1.1 - Gas Designation Disc
EQUIPPED
FOR USE
WITH
PROPANE
GAS
NRTL
NTRL
5H604841A
HIGH ALTITUDE CONVERSION For Existing Natural or Propane Gas Units
Gas-fired equipment ratings are certified by C.S.A. For elevations above 2000 ft., ANSI Z223.1 requires ratings be reduced 4 percent for each 1000 ft. above sea level. C.G.A. requires that ratings be reduced 10% at elevations above 2000 ft. To accommodate higher altitude operation, equipment
must be converted by changing orifices as explained in this instruction sheet. Tables 2.1 thru 5.2 list orifice kits which
comply with both ANSI Z223.1 recommendations and C.S.A. requirements.
As Modine Manufacturing Company has a continuous
product improvement program, it reserves the right to change design and specifications without notice.
Table of Contents Pages
High altitude conversion ......................................................... 1
High altitude propane gas
conversion from natural gas ............................................. 1
Selection of the proper kit ....................................................... 1
Installation of kits .................................................................... 6
Cross reference ...................................................................... 8
For Units being Converted from Natural Gas to Propane Gas Concurrently
IMPORTANT
Conversion from natural gas to propane gas is allowed for PD/BD, PDP/BDP, and PSH/BSH models with 11,12, 30, or 31 control codes, built in January, 1987 or later. For this
conversion, both a propane conversion kit and a propane high altitude kit must be used.
Follow carefully the propane conversion instructions, found in Bulletin 75-511, using the proper high altitude main burner orifices called out in this literature (75-535) instead of the orifices in propane conversion kit.
SELECTION OF THE PROPER KIT
To select the proper high altitude kit you need to know the specifics of the heater you will be converting, and the altitude it will be going into. If the high altitude kits are ordered at the same time as the unit heater, all pertinent information relative to the heater can be obtained from the catalog. If the high altitude kit is needed after the unit heater is in the field, you need to refer to the carton label or unit heater serial plate to obtain the necessary information. Figure 8.2 shows a portion of the unit heater serial plate where this information may be obtained. Referring to this figure, the prefix letters and successive numbers which are needed for kit selection are BV 100. The letters identify the model and the numbers the size of the unit. To determine the type of gas the unit is designed for, see the gas designation disc (Figure 1.1) and the type of gas, located on the serial plate.
After obtaining this information, refer to the proper selection chart. The selection charts are differentiated by product type, altitude and fuel type. Remember, if you are converting from
natural gas to propane gas and want to operate at high altitude, both a propane conversion kit and a propane high altitude kit must be used. Selection charts include the proper kit suffix, the
orifice drill size, and the number of orifices required for the unit being converted. Drill sizes are also stamped on each orifice.
PLEASE BE SURE TO LEAVE IT WITH HIM WHEN YOU LEAVE THE JOB.
THIS MANUAL IS THE PROPERTY OF THE OWNER.
HIGH ALTITUDE ORIFICE KIT SELECTION GUIDE
Table 2.1 - Natural Gas - 2001 to 4500 ft. Elevations - PD/BD, PDP/BDP, PSH/BSH, model series “D”, “H”,“I”, & ,“O” ➀ ➁
Model Model Size
Type 30 50 75 100 125 130 150 170 175 200 225 250 280 300 340 350 400 PD/BD, PDP/BDP 30 50 75 100 125 - 150 - 175 200 - 250 - 300 - 350 400
Kit Suffix -30 -121 -120 -22 -23 - -90 - -15 -26 - -125 - -92 - -88 -126 Drill Size 41 31 24 31 29 - 24 - 30 28 - 21 - 24 - 26 28 Orifices in Kit 1 1 1 2 2 - 2 - 3 3 - 3 - 4 - 5 6
PSH/BSH - - - - - 130 150 170 - - 225 - 280 - 340 - -
Kit Suffix - - - - - 14 94 15 - - 50 - 44 - 129 - ­ Drill Size - - - - - 28 31 30 - - 24 - 26 - 27 - ­ Orifices in Kit - - - - - 2 3 3 - - 3 - 4 - 5 - -
Pressure Switch in Kit - - - - - NO NO NO - - NO - NO - NO - -
- - 75 100 125 - 150 - 175 200 225 250 300 350 400 Kit Suffix - - -3 -22 -14 - -94 - -7 -8 -9 -10 - -11 - -85 -13
Drill Size - - 23 31 28 - 31 - 29 26 23 28 - 23 - 29 26 Orifices in Kit - - 1 2 2 - 3 - 3 3 3 4 - 4 - 6 6
Table 2.2 - Natural Gas - 4501 to 5500 ft. Elevations - PD/BD, PDP/BDP, PSH/BSH, model series “D”, “H”,“I”, & ,“O” ➀ ➁
Model Model Size
Type 30 50 75 100 125 130 150 170 175 200 225 250 280 300 340 350 400 PD/BD, PDP/BDP 30 50 75 100 125 - 150 - 175 200 - 250 - 300 - 350 400 Kit Suffix -33 -121 -127 -22 -23 - -128 - -15 -26 - -112 - -87 - -129 -126 Drill Size 42 31 25 31 29 - 25 - 30 28 - 22 - 25 - 27 28 Orifices in Kit 1 1 1 2 2 - 2 - 3 3 - 3 - 4 - 5 6
PSH/BSH - - - - - 130 150 170 - - 225 - 280 - 340 - -
Kit Suffix - - - - - 504 508 15 - - 513 - 95 - 522 - ­ Drill Size - - - - - 29 31 30 - - 25 - 27 - 28 - ­ Orifices in Kit - - - - - 2 3 3 - - 3 - 4 - 5 - -
Pressure Switch in Kit - - - - - YES YES NO - - YES - NO - YES - -
- - 75 100 125 - 150 - 175 200 225 250 - 300 - 350 400
Kit Suffix - - -120 -22 -14 - -94 - -15 -122 -50 -10 - -92 - -97 -93 Drill Size - - 24 31 28 - 31 - 30 27 24 28 - 24 - 30 27 Orifices in Kit - - 1 2 2 - 3 - 3 3 3 4 - 4 - 6 6
All conversion kits have the same base part number 3H33231, only the suffix of the part number changes by model size. Does not include DFS, DBS, DCS, IFS, IBS, ICS.
Indoor Duct Furnaces Weatherproof Duct Furnaces DFG, DBG, DCG, IFG, IBG, ICG HFG, HBG, HCG, HDG, HPG, OFG, OBG, OCG, ODG, OPG DFP, DBP, DCP, IFP, IBP, ICP HFP, HBP, HCP, HDP, HPP, OFP, OBP, OCP, ODP, OPP
2
75-535.11
HIGH ALTITUDE ORIFICE KIT SELECTION GUIDE
Table 3.1 - Natural Gas - 5501 to 6500 ft. Elevations - PD/BD, PDP/BDP, PSH/BSH, model series “D”, “H”,“I”, & ,“O” ➀ ➁
Model Model Size
Type 30 50 75 100 125 130 150 170 175 200 225 250 280 300 340 350 400 PD/BD 30 50 75 100 125 - 150 - 175 200 - 250 - 300 - 350 400
Kit Suffix -78 -121 -24 -22 -4 - -102 - -15 -7 - -9 - -44 - -96 -85 Drill Size 43 31 26 31 30 - 26 - 30 29 - 23 - 26 - 28 29 Orifices in Kit 1 1 1 2 2 - 2 - 3 3 - 3 - 4 - 5 6
PDP/BDP 30 50 75 100 125 - 150 - 175 200 - 250 - 300 - 350 400 Kit Suffix -78 -121 -501 -22 -4 - -102 - -15 -7 - -9 - -44 - -96 -85 Drill Size 43 31 26 31 30 - 26 - 30 29 - 23 - 26 - 28 29 Orifices in Kit 1 1 1 2 2 - 2 - 3 3 - 3 - 4 - 5 6 Pressure
Switch in Kit NO NO YES NO NO - NO - NO NO - NO - NO - NO NO
PSH/BSH - - - - - 130 150 170 - - 225 - 280 - 340 - - Kit Suffix - - - - - 504 508 94 - - 514 - 518 - 522 - ­ Drill Size - - - - - 29 31 31 - - 26 - 28 - 28 - ­ Orifices in Kit - - - - - 2 3 3 - - 3 - 4 - 5 - -
Pressure Switch in Kit - - - - - YES YES NO - - YES - YES - YES - -
- - 75 100 125 - 150 - 175 200 225 250 - 300 - 350 400
Kit Suffix - - -127 -22 -23 - -94 - -15 -26 -56 -115 - -87 - -97 -126 Drill Size - - 25 31 29 - 31 - 30 28 25 29 - 25 - 30 28 Orifices in Kit - - 1 2 2 - 3 - 3 3 3 4 - 4 - 6 6
- - 75 100 125 - 150 - 175 200 225 250 - 300 - 350 400
Kit Suffix - - -127 -22 -23 - -94 - -15 -26 -56 -115 - -87 - -97 -526 Drill Size - - 25 31 29 - 31 - 30 28 25 29 - 25 - 30 28 Orifices in Kit - - 1 2 2 - 3 - 3 3 3 4 - 4 - 6 6
Table 3.2 - Natural Gas - 6501 to 7500 ft. Elevations - PD/BD, PDP/BDP, PSH/BSH, model series “D”, “H”,“I”, & ,“O” ➀ ➁
Model Model Size
Type 30 50 75 100 125 130 150 170 175 200 225 250 280 300 340 350 400 PD/BD 30 50 75 100 125 - 150 - 175 200 - 250 - 300 - 350 400
Kit Suffix -78 -101 -83 -28 -4 - -5 - -94 -7 - -50 - -95 - -100 -85 Drill Size 43 32 27 32 30 - 27 - 31 29 - 24 - 27 - 29 29 Orifices in Kit 1 1 1 2 2 - 2 - 3 3 - 3 - 4 - 5 6
PDP/BDP 30 50 75 100 125 - 150 - 175 200 - 250 - 300 - 350 400 Kit Suffix -78 -101 -502 -28 -4 - -5 - -94 -7 - -50 - -95 - -100 -85 Drill Size 43 32 27 32 30 - 27 - 31 29 - 24 - 27 - 29 29 Orifices in Kit 1 1 1 2 2 - 2 - 3 3 - 3 - 4 - 5 6 Pressure
Switch in Kit NO NO YES NO NO - NO - NO NO - NO - NO - NO NO
PSH/BSH - - - - - 130 150 170 - - 225 - 280 - 340 - - Kit Suffix - - - - - 505 509 508 - - 515 - 519 - 523 - ­ Drill Size - - - - - 30 32 31 - - 27 - 29 - 29 - ­ Orifices in Kit - - - - - 2 3 3 - - 3 - 4 - 5 - -
Pressure Switch in Kit - - - - - YES YES YES - - YES - YES - YES - -
- - 75 100 125 - 150 - 175 200 225 250 - 300 - 350 400 Kit Suffix - - -24 -22 -4 - -94 -15 -7 -8 -91 -44 -97 -85
Drill Size - - 26 31 30 - 31 30 29 26 30 26 30 29 Orifices in Kit - - 1 2 2 - 3 3 3 3 4 4 6 6
- - 75 100 125 - 150 - 175 200 225 250 - 300 - 350 400 Kit Suffix - - -24 -22 -4 - -94 -15 -7 -8 -91 -44 -97 -527
Drill Size - - 26 31 30 - 31 30 29 26 30 26 30 29 Orifices in Kit - - 1 2 2 - 3 3 3 3 4 4 6 6
All conversion kits have the same base part number 3H33231, only the suffix of the part number changes by model size. Does not include DFS, DBS, DCS, IFS, IBS, ICS.
Indoor Gravity Vented Duct Furnaces Weatherproof Duct Furnaces DFG, DBG, DCG, IFG, IBG, ICG HFG, HBG, HCG, HDG, HPG, OFG, OBG, OCG, ODG, OPG,HFP, HBP, HCP, HDP, HPP, OFP, OBP, OCP, ODP, OPP
Indoor Power Vented Duct Furnaces DFP, DBP, DCP, IFP, IBP, ICP
Kit for DFP, DBP, DCP, IFP, IBP, ICP, 400 size only, also includes
a pressure switch.
75-535.11
3