Modine Manufacturing MT28, MT30, MT33, MT56, MT60 Service Manual

...
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death, and could cause exposure to substances which have been determined by various state agencies to cause cancer, birth defects or other reproductive harm. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
November, 2003
INSTALLATION AND SERVICE MANUAL
high intensity gas-fired infrared heaters
model MT
IMPORTANT
The use of this manual is specifically intended for a qualified installation and service agency. A qualified installation and service agency must perform all installation and service of these units.
THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
Inspection on Arrival
1. Inspect unit upon arrival. In case of damage, report it immediately to the transportation company and your local sales representative.
2.
Check rating plate on unit to verify that the power supply meets available electric power at the point of installation.
3. Inspect unit upon arrival for conformance with description of product ordered (including specifications where applicable).
9-500.3h
5H75283ALL
CAUTION
As with all infrared equipment, clearances to combustible material are critical.
To prevent premature heat exchanger failure do not locate ANY gas-fired units in areas where chlorinated, halogenated, or acid vapors are present in the atmosphere
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. Don’t touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
FOR YOUR SAFETY
The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
DANGER
Appliances must not be installed where they may be exposed to potentially explosive or flammable atmosphere.
Special Precautions
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE, EFFICIENT AND TROUBLE-FREE OPERATION. IN ADDITION, PARTICULAR CARE MUST BE EXERCISED REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW. FAILURE TO PROPERLY ADDRESS THESE CRITICAL AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS, PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS ARE SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES.
Hazard Intensity Levels
1. DANGER: Indicates an imminently hazardous
situation which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous
situation which, if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous
situation which, if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided,
MAY result in a potential safety concern.
Table of Contents
General Information .............................................................1
Inspection on Arrival ............................................................1
Special Precautions .............................................................2
SI (Metric) Conversion Factors............................................3
Unit Location........................................................................3
Location Recommendations .........................................3
Installation............................................................................3
Mounting .......................................................................3
Combustion/Ventilation Air Requirements.....................4
Gas Connections ..........................................................5
Electrical Connections ..................................................6
Start-Up Procedure..............................................................6
Pilot Flame Adjustment .................................................7
Main Burner Adjustment................................................7
Available Controls / Operating Sequence.....................8
Dimensions .........................................................................9
Maintenance ........................................................................9
Service & Troubleshooting.................................................10
Replacement Parts Ordering .............................................11
Model Number Designations.......................................11
Serial Number Designations .......................................11
Warranty.............................................................................12
CAUTION
1. Units are designed for indoor installation only. DO NOT LOCATE UNITS OUTDOORS.
2. Purging of air from gas lines should be performed as described in ANSI Z223.1 - latest edition “National Fuel Gas Code”, or in Canada in CAN/CGA-B149 codes.
2
IMPORTANT
1. Approval requirements for infrared heaters specify that the suspended type heaters shall be installed in accordance
with certain sections of the National Fire Codes published by the National Fire Protection Association and various ANSI standards. SOME of the requirements are listed
below. Aircraft Hangars: Approval requirements are contained in
the current edition of ANSI/NFPA 409 (or in accordance with the enforcing authority for Canada).
Public Garages: Approval requirements are contained in the current edition of NFPA 88B (CAN/CGA B149 for Canada).
Parking Structures: Approval requirements are contained in the current edition of NFPA 88A.
General: All installations must be in accordance with the current edition of ANSI Z-223.1 (NFPA 54) National Fuel Gas Code and the current edition of the National Electric Code, ANSI/NFPA 70. For Canada, installations must conform with local building codes, or in the absence of local codes, in accordance with the current edition of CAN/CGA B149 and the Canadian Electric Code, C22.1.
2. Start-up and adjustment procedures should be performed by a qualified service agency.
3. To check most of the Possible Remedies in the trouble shooting guide listed in Tables 10.1 and 11.1, refer to the applicable sections of the manual.
WARNING
1. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame; use a soap solution or equivalent for testing.
2. Gas pressure to unit controls must never exceed 14" W.C. (1/2 psi).
3. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
4. All units must be wired strictly in accordance with the wiring diagram furnished with the unit. Any wiring different from the wiring diagram could result in a hazard to persons and property.
5. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
6. When servicing or repairing this equipment, use only manufacturer-approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine Manufacturing Company. Refer to the rating plate on the unit for complete unit model number, serial number, and company address. Any substitution of non-approved parts or controls will be at the owner’s risk.
7. To prevent flame bail-out from the heater, the gas input to the appliance, as indicated on the serial plate, must not exceed the rated input by more than 5% or fall below the rated input by more than 5%.
8. To prevent gas control circuit malfunction, the supply voltage to the unit, as indicated on the serial plate must not exceed or fall below the rated input voltage by more than 5%.
IMPORTANT
Approval requirements for infrared heaters specify that the suspended type heaters shall be installed in accordance with certain sections of the National Fire Codes published by the National Fire Protection Association and various ANSI standards. SOME of the requirements are listed below.
Aircraft Hangars: Approval requirements are contained in the current edition of ANSI/NFPA 409 (or in accordance with the enforcing authority for Canada).
Public Garages: Approval requirements are contained in the current edition of NFPA 88B (CAN/CGA B149 for Canada).
Parking Structures: Approval requirements are contained in the current edition of NFPA 88A.
General: All installations must be in accordance with the current edition of ANSI Z-223.1 (NFPA 54) National Fuel Gas Code and the current edition of the National Electric Code, ANSI/NFPA 70. For Canada, installations must conform with local building codes, or in the absence of local codes, in accordance with the current edition of CAN/CGA B149 and the Canadian Electric Code, C22.1.
DANGER
Units must not be installed where they may be exposed to potentially explosive or flammable atmosphere.
CAUTION
Units are designed for indoor installation only. DO NOT LOCATE UNITS OUTDOORS.
To Convert Multiply By To Obtain
" W.C.
(inches water column)
0.24 kPa
psig 6.893 kPa
°F
subtract 32 and then
°C
multiply by 0.555
inches 25.4 mm
feet 0.305 meters
cfm (ft3/min) 0.028 m3/min
cfh (ft3/hr) 1.699 m3/min
Btu/ft
3
0.0374 mJ/m
3
pound 0.453 kg
Btu/hr 0.000293 kW/hr
gallons 3.785 liters
Table 3.1 SI (METRIC) CONVERSION FACTORS
UNIT LOCATION
SI (METRIC) CONVERSION FACTORS / UNIT LOCATION / INSTALLATION
Location Recommendations
1. When locating the heater, consider the general space and heating requirements and availability of gas and electrical supply.
2. Be sure the structural support and chain at the unit location is adequate to support the weight of the unit.
3
Table 3.2 Combustible Material Clearances
Minimum Clearances to Combustible Materials
(inches)
Top Sides Rear Bottom
MT28/30/33 30 30 24 72
MT56/60/66 36 36 33 88
MT84/90/99 48 42 39 104
MT112/120/132 54 48 45 120
MT160 60 54 51 136
Model
No.
3. Be sure that the minimum clearances to combustible materials and for serving are maintained. The minimum clearances to combustibles are shown in Table 3.2.
4. Mounting height (measured from the bottom of unit) at which heaters are installed is critical. Please refer to mounting height information in Table 4.1.
5. Do not locate units in areas where chlorinated, halogenated, or acid vapors are present in the atmosphere.
INSTALLATION
Mounting
Figures 4.2 and 4.3 illustrate typical rigid and chain mounting arrangements, respectively, for a model MT infrared heater. Check local codes for mounting requirements and use of flexible gas connectors. Local codes may require rigid mounting. Heaters must be mounted at angles from 10°to 35°from horizontal. The gas manifold must be located on the low end of the heater, in a horizontal position (parallel to the floor).
Where permissible, chain mounting is recommended. 5' chain mounting sets are available as an accessory, allowing for 10° to 35° mounting angles. In the absence of this chain set, Number 1/0 Tenso chain (200 lb. working load) is recommended. “S” hooks should be a minimum
1
/4" in diameter and the ends must be closed after installation. Heaters located in aircraft hangers or near overhead doors must be rigidly mounted to prevent swinging. Under no circumstances should the gas supply line or the electrical supply line to the heater be used to provide any assistance in the suspension of the heater. Do not locate any gas or electric service lines directly above or below the heater.
Insure that:
1. Clearances to combustibles (as shown on the rating plate
and in Table 3.2) are maintained.
2. For proper operation, the unit must be mounted on an angle
ten to thirty-five degrees (10°to 35°) from the horizontal with the gas manifold located at the low end of the heater. See Figure 4.1.
3. In locations used for storage of combustible materials,
signs shall be posted to specify the maximum permissible stacking height to maintain required clearances from the heater to the combustibles. See Figure 4.4.
4. Either gas piping or suspension mounting is flexible to
prevent fatigue failure from vibration or thermal expansion.
5. Adequate clearances to sprinkler heads are maintained.
See figure 4.1 on page 4.
Figure 4.2 Typical Rigid Mounting Configuration
Figure 4.3 Typical Chain Mounting Configuration
Figure 4.4 Stacking Height
Table 4.1 Typical Mounting Height for Full Building Heating
INSTALLATION
Typical Mounting Height at Min/Max
Model No.
Mounting Angles (feet)
10° 35°
MT28, 30, 33 8-14 7-12 MT56, 60, 66 14-20 12-16 MT84, 90, 99 20-26 16-24
MT112, 120, 132 26-32 20-30
MT160 26-40 22-38
Mounting height values are recommendations only and may need to be adjusted to meet requirements of actual installation.
4
e
OVERHEAD STRUCTURE AND FIELD CONNECTIONS MUST
N G l t
d)
N G
l t
OVERHEAD STRUCTURE AND FIELD CONNECTIONS MUST
Figure 4.1 Combustible Material Clearances
REAR
BELOW
THE GAS MANIFOLD AND CONTROLS MUST BE LOCATED AT THE LOW END OF THE HEATER
TOP
NOTE: Gas manifold MUST be located on the low side of the heater.
Combustion/Ventilation Air Requirements
Maintain positive air displacement of 4 cfm per 1000 Btu/hr for natural gas and 5 cfm per 1000 Btu/hr for propane. The fresh air supply must be located in the immediate proximity of the unit(s). Fresh air intake openings are typically located high on the building sidewalls at a comparable level to the heaters. One square inch of net free inlet area per 1000 Btu/hr is required. Multiple inlets, well distributed, should be used and should direct air upward to prevent drafts at floor level. Inlets are typically limited to 1 to 2 square feet in size.
It is recommended that units be interlocked with mechanical exhaust fans for unvented applications. Mechanical exhaust fans are typically located at high points of the building. For flat roof areas, a series of small exhausters should be distributed over the roof areas and interlocked with various heating zones.
BE ADEQUATE TO SUPPORT WEIGHT OF THE HEATER.
OTE:
as main and electrical ines must not cross over op of heater.
35˚ MAX.
10˚ MIN.
3/8" All thread rigid mount (Used in aircraft hangers or where draft conditions may b expected.)
Minimum Clearance to
Combustible Materials
Mounting
Height
Stacking
Height
NOTE: Gas manifold MUST be located on the low side of the heater.
BE ADEQUATE TO SUPPORT WEIGHT OF THE HEATER.
OTE:
as main and electrical ines must not cross over op of heater.
5' Chain Mounting Set
Minimum
10˚
Horizontal Plane
'S' Hooks: 1/4" Dia. wire (Crimp all 'S' hooks close
35˚ Maximum
Minimum
10˚
Horizontal Plane
35˚
Maximum
Loading...
+ 8 hidden pages