Modine Manufacturing MPR Installation And Service Manual

MCP15-500.7
5H0816400000
March, 2018
INSTALLATION AND SERVICE MANUAL
commercial packaged ventilation system units
model MPR
Model MPR Commercial Packaged Ventilation System Unit (C-Cabinet size shown)
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death, and could cause exposure to substances which have been determined by various state agencies to cause cancer, birth defects or other reproductive harm. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
This unit contains R-410A high pressure refrigerant. Hazards exist that could result in personal injury or death. Installation, maintenance, and service must only be performed by an HVAC technician qualified in R-410A refrigerant and using proper tools and equipment. Due to much higher pressure of R-410A refrigerant, DO NOT USE service equipment or tools designed for refrigerants other than R410A.
WARNING
WARNING
(for units with 24 digit model numbers)
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death or property damage.
Be sure to read and understand the installation, operation and service instructions in this manual.
Improper installation, adjustment, alteration, service or maintenance can cause serious injury, death or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch, do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a phone remote from the building. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
1. Inspect unit upon arrival. In case of damage, report it immediately to transportation company and your local factory sales representative.
2.
Check rating plate on unit to verify that power supply meets
available electric power at the point of installation.
3. Inspect unit upon arrival for conformance with description of product ordered (including specifications where applicable).
WARNING
THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
1MCP15-500.7
SPECIAL PRECAUTIONS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE, EFFICIENT AND TROUBLE-FREE OPERATION. IN ADDITION, PARTICULAR CARE MUST BE EXERCISED REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW. FAILURE TO PROPERLY ADDRESS THESE CRITICAL AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS, PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS ARE SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which, if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided, MAY result in a potential safety concern.
dANGeR
Appliances must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
WARNING
de-energized.
11. This unit contains R-410A high pressure refrigerant. Hazards exist that could result in personal injury or death. Installation, maintenance, and service must only be performed by an HVAC technician qualified in R-410A refrigerant and using proper tools and equipment. Due to much higher pressure of R-410A refrigerant, DO NOT USE service equipment or tools designed for refrigerants other than R410A.
12. The power supply wiring for the Energy Recovery Section comes from a single point power connection on the unit. Disconnect power supply at model MPR before making wiring connections to prevent electrical shock and equipment damage.
13. When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine Manufacturing Company. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner's risk.
WARNING
1. Failure to follow proper lifting instructions could result in property damage, serious injury, or death. Lifting should only be done by a qualified rigging company. Use ALL lifting points. Test lift to ensure proper balance and rigging. Never lift in high winds.
2. Disconnect power supply before making wiring connections or working on this equipment. Follow all applicable safety procedures to prevent accidental power up. Failure to do so can result in injury or death from electrical shock or moving parts and may cause equipment damage.
3. For units equipped for dual power supply sources, both sources of power must be disconnected to prevent electrical shock and equipment damage.
4. All appliances must be wired strictly in accordance with the wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
5. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
6. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than the rated voltage.
7. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing.
8. Gas pressure to appliance controls must never exceed 14" W.C. (1/2 psi).
9. To reduce the opportunity for condensation, the minimum sea level gas input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or 5% below the minimum rated input of dual rated units.
10. When the dead front disconnect switch(es) (for main unit and/or powered convenience outlet option) is in the “OFF” position, supply power remains energized at the line (supply) side of the dead front disconnect switch(es). The switch body is located inside of another junction box to protect against contact with the live wiring. The junction box must not be disassembled unless the main power supply from the building to the unit is
CAUtIoN
1. Appliances are designed for outdoor installation only. DO NOT LOCATE APPLIANCES INDOORS.
2. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage.
3. Purging of air from gas lines should be performed as described in ANSI Z223.1 - latest edition “National Fuel Gas Code”, or in Canada in CAN/CGA-B149 codes.
4. Units not approved for use in potable water systems.
5. Do not operate the unit with steam. The coil is not designed for steam condensate removal which can damage the unit.
6. Hot water supplied to the hot water heating option must not exceed 180°F temperature or 75 PSIG pressure.
7. When servicing the unit, some components may be hot enough to cause pain or injury. Allow time for cooling of hot components before servicing.
8. Do not overcharge the refrigeration system. This can lead to elevated compressor discharge pressure and possibly flooding the compressor with liquid. This may result in compressor failure not covered under warranty.
9. Do not reuse any mechanical or electrical component which has been wet. Such components must be replaced.
IMPoRtANt
1. To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acid) are present in the atmosphere.
2. A properly designed drain with trap must be installed immediately after the unit evaporator coil condensate drain pan connection. Failure to do so will result in condensate that cannot properly drain from the unit,
2 MCP15-500.7
TABLE OF CONTENTS / SI (METRIC) CONVERSION FACTORS / UNIT LOCATION
TABLE OF CONTENTS
IMPoRtANt
eventually causing the drain pan to fill. To prevent damage to the building or unit, a drain pan float switch is included as standard and will disable the unit if the maximum condensate level is reached.
3. To prevent premature heat exchanger failure, the input to the appliance, as indicated on the serial plate, must not exceed the rated input by more than 5%.
4. To prevent premature heat exchanger failure, check to be sure the blower has been set to deliver the proper airflow for the application. Refer to page 17 for Blower Adjustments.
5. Start-up and adjustment procedures must be performed by a qualified service agency.
6. All scroll compressors requires the correct supply power phase rotation. Phase reversal may result in compressor failure not covered under warranty. Refer to the Start-Up Procedure section.
7. All refrigeration checks must be made by a qualified R-410A refrigeration technician.
8. Do not release refrigerant to the atmosphere. When adding or removing refrigerant, all national, state/ province, and local laws must be followed.
9. On units with the electric preheat option, to prevent premature heat exchanger failure, check to be sure the blower has been set to deliver the proper airflow for the application. Refer to page 17 for Blower Adjustments.
10. The exhaust fan is not designed for high temperature or smoke control exhaust applications. Exhaust air temperature must not exceed 104°F. Operating the exhaust fan above 104°F will result in failure of the exhaust fan.
SI (METRIC) CONVERSION FACTORS
To Convert Multiply By To Obtain
"W.C. 0.24 kPa psig 6.893 kPa °F (°F-32) x 0.555 °C inches 25.4 mm feet 0.305 meters CFM 0.028 m
3
Special Design Requests
Modine Manufacturing Company will sometimes build units with special features as requested by the customer. This manual only covers standard features and does not include any changes made for special feature requests by the customer. Units built with special features are noted with an SPO (Special Product Order) Number on the Serial Plate
To Convert Multiply By To Obtain
CFH 1.699 m
3
0.0374 mJ/m
Btu/ft pound 0.453 kg Btu/hr 0.000293 kW gallons 3.785 liters psig 27.7 "W.C.
/min
3
/min
3
Inspection on Arrival ............................................................ 1
Special Precautions ............................................................. 2
SI (Metric) Conversion Factors ........................................... 3
Special Design Requests .................................................... 3
Storage Prior to Installation ................................................. 3
Unit Location ....................................................................... 4
Installation ......................................................................4-15
Combustible Material and Service Clearances .........4-5
Roof Curb Installation ................................................... 4
General Rigging Instructions/Unit Installation ...........6-7
Duct & Condensate Drain Installation .......................... 8
Electrical Connections .................................................. 9
Gas Connections ........................................................ 10
Vent Terminals and Combustion Air Hoods ................ 11
Gas Heating Option Condensate Drains & Traps ......14
Hot Water Piping Connections ...................................15
Start-Up Procedure ......................................................16-29
General. ...................................................................... 16
Blower Adjustments .................................................... 17
Airflow Proving Switch and Dirty Filter Switch............ 19
Variable Air Movement Applications ........................... 19
Checking Refrigerant Charge ..................................... 20
Gas Heating Option .................................................... 21
Energy Recovery Option (B-Cabinet units only) ........ 28
Unit Features/Options Location Drawings .................... 30-35
Dimensions/Weights .................................................... 36-44
B-Cabinet Size Unit without Energy Recovery. .......... 36
B-Cabinet Size Unit with Energy Recovery. ............... 38
C-Cabinet Size Unit .................................................... 40
D-Cabinet Size Unit .................................................... 42
Base Model Weights ...................................................44
Option and Accessory Pressure Drop Tables ..............45-47
Maintenance .................................................................48-50
Service & Troubleshooting ...........................................51-55
Serial Plates ...................................................................... 56
Model Nomenclature ....................................................57-59
Commercial Warranty ...........................................Back Page
Storage Prior to Installation
If the unit is stored outside prior to installation, the unit should be covered.
3MCP15-500.7
*Available as a factory supplied, field installed accessory.
Curb Gasketing*
2 x 4 Wooden Nailing Strip*
Curb*
2” Acoustic
Fiberglass
(By Others)
Roof Deck
6” Inverted Channel
(Both Sides)
(By Others)
Roof
Trusses
Cant Strip
(By Others)
Roof Insulation
(By Others)
Counterflashing
(By Others)
Roofing Material
(By Others)
Insulation
(By Others)
UNIT LOCATION
dANGeR
Appliances must not be installed where they may be exposed to potentially explosive or flammable atmosphere.
CAUtIoN
Appliances are designed for outdoor installation only. DO NOT LOCATE APPLIANCES INDOORS.
IMPoRtANt
To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acid) are present in the atmosphere.
Location Recommendations
1. When locating the packaged rooftop unit, Model MPR, consider general space and cooling/heating requirements and availability of gas and electrical supply.
2. Be sure the structural support at the unit location site is adequate to support the weight of the unit and any other required support structure. For proper operation the unit must be installed in a level horizontal position.
3. All mechanical equipment generates some sound and vibration that may require attenuation. Locating the equipment away from the critical area is desirable within ducting limitations. Frequently, units can be located above utility areas, corridors, restrooms, and other non-critical areas. Generally, a unit should be located within 15 feet of a primary support beam. Smaller deflections mean lesser vibration and noise transmission. For critical applications, please consult with an acoustical attenuation expert.
4. Do not install units in locations where the flue products (if equipped with a gas fired heating option) can be drawn into the adjacent building openings such as windows, fresh air intakes, etc.
5. Be sure that the minimum clearances to combustible materials and recommended service clearances are maintained. For units with the gas heating option, be sure clearances are maintained to the combustion air inlet louvers and power exhauster discharge cover. Units are designed for installation on non-combustible surfaces with the minimum clearances shown in Figure 5.1.
6. On units that have fresh air openings, a method must be provided to prevent water and debris from entering the unit such as a rainhood, which is available as an accessory from Modine. Where possible, install the unit so that the inlet is not facing into the prevailing wind to prevent water entrainment.
7. The exhaust fan is not designed for high temperature or smoke control exhaust applications. Exhaust air temperature must not exceed 104°F. Operating the exhaust fan above 104°F will result in failure of the exhaust fan.
Roof Curb Installation
An optional roof curb is available to simplify site preparation and raise the unit above roof water and snow level for drainage. It can be installed in advance of the unit. The curb is shipped knocked down with separate instructions (Literature #MCP15-590) for its assembly, flashing, and sealing with the roof. The following are some general guidelines for roof curb installed units:
1. The roof structure must be adequately designed to support the live weight load of the unit and any other required support structure. The roof curb should be supported at points no greater than five feet apart. Additional truss reinforcement should be provided, if necessary.
2. Roof curbs supplied by Modine are fabricated from 10 gauge galvanized steel and supplied knocked down for assembly on the job site. The curb consists of two side pieces, two end pieces, gasketing, four joiner angles, four 2x4 inch wood nailing strips, nuts, bolts, and washers.
3. Outside dimensions must be held when installing curb. Top surface must be level and straight to ensure weather­tightness. If roof is pitched it will be necessary to construct a sub-base on which to install the curb. All corners must be square.
4. All dimensions are +1/8 inch.
5. When a roof curb is used in conjunction with factory supplied discharge and/or return air connectors, the ductwork can be fastened to the connectors prior to the unit installation. The connectors will accept 90° flanged ductwork (see Figure 7.1).
6. Final electric and gas connections must be made after unit is installed to allow for tolerance in setting of unit on curb. For electrical power supply allow approximately eight feet of wire, plus provisions for weathertight flexible conduit for connection to unit, as required by local codes.
7. Maintain a 12-inch minimum height from top of roof deck to top of curb.
8. Caulk butt joints after curb is assembled and installed on roof structural members and roof flashing is added.
9. For improved sound attentuation, line the roof deck within the curb area with 2" acoustic fiberglass.
Figure 4.1 - Typical Curb Details
4 MCP15-500.7
CLEARANCES / ROOF CURB INSTALLATION
Figure 5.1 - Combustible Material & Service Clearances
B- AND C-CABINET UNITSWITHOUT ENERGY RECOVERY D-CABINET UNITSWITHOUT ENERGY RECOVERY
FIELD INSTALLED
SEE NOTE 2
36.0
SEE NOTE 2
36.0
ACCESSORY
RAINHOOD
48.0
SEE NOTE 3
36.0
SEE NOTE 4
FOR UNITS WITH GAS HEAT,
MAINTAIN 48" MINIMUM
FROM VENT TERMINATIONS
48.0
SEE NOTE 1
B- AND C-CABINET UNITSWITH ENERGY RECOVERY
FIELD INSTALLED
36.00
36.0
SEE NOTE 4
FOR UNITS WITH GAS HEAT,
MAINTAIN 48" MINIMUM
FROM VENT TERMINATIONS
48.0
SEE NOTE 1
ACCESSORY
RAINHOOD
48.0
SEE NOTE 3
SEE NOTE 4
48.00
SEE NOTE 3
48.00
SEE NOTE 1
FOR UNITS WITH GAS HEAT,
MAINTAIN 48" MINIMUM
FROM VENT TERMINATIONS
j The minimum recommended clearance for service is 48". For service
clearances less than shown, applicable local code requirements must be followed. If the ability for future condenser coil replacement is desired, the minimum clearance must be:
• 102" for B-Cabinet sized units
• 112" for C-Cabinet sized units
• 100” for D-Cabinet sized units
See Note k for alternate coil replacement direction.
k The minimum recommended clearance for service is 36". For service
clearances less than shown, applicable local code requirements must be followed. If the ability for future condenser coil replacement is desired, the minimum clearance must be (from the end panel of the condenser, not the end of the inlet hood):
• 102” for B-Cabinet sized units
• 112” for C-Cabinet sized units
• 100” for D-Cabinet sized units
See Note j for alternate coil replacement direction.
l The minimum recommended clearance for service is 48". For service
clearances less than shown, applicable local code requirements must be followed. If the ability for future evaporator coil, hot gas reheat coil, and/or energy wheel replacement is desired, the minimum clearance must be:
• 55" for B-Cabinet sized units
• 64" for C-Cabinet sized units
• 100” for D-Cabint sized units
m Additional Required Clearances:
-Clearance above unit must be unobstructed.
-Clearance to combustibles below the unit is 6" minimum.
48.00
SEE NOTE 3
5MCP15-500.7
GENERAL RIGGING INSTRUCTIONS / UNIT INSTALLATION
SPREADER BAR
AND LIFTING
CHAINS/STRAPS
BY INSTALLER
ADJUST CHAIN/STRAP
LENGTH SO UNIT IS
LEVEL WHEN LIFTED
RAINHOOD
ACCESSORY
(FIELD INSTALL)
(4) 1.50" LIFTING EYE BOLTS
(EACH CORNER OF UNIT)
SPREADER BAR
AND LIFTING
CHAINS/STRAPS
BY INSTALLER
ENSURE THE LIFTING
CHAINS/STRAPS CLEAR
THE CASING ON EACH SIDE
(6) 1.0" LIFTING LUGS
MIN. 65
v
SPREADER BAR AND LIFTING CHAINS/STRAPS BY INSTALLER
ADJUST CHAIN/STRAP
LENGTH SO UNIT IS
LEVEL WHEN LIFTED
RAINHOOD ACCESSORY (FIELD INSTALL)
ENSURE THE LIFTING CHAINS/STRAPS CLEAR THE CASING ON EACH SIDE
(4) 1.0" LIFTING LUGS
LIFTING LUG KIT IS SHIPPED LOOSE IN SUPPLY FAN SECTION. INSTALL (4) LIFTING LUGS PER MCP15-505 USING (4) GRADE 5 BOLTS PER LUG, TORQUED TO 75 ft-lb.
B-CABINET UNIT - NO ENERGY RECOVERY C-CABINET UNIT - ALL
D-CABINET UNIT - ALL
B-CABINET UNIT - WITH ENERGY RECOVERY
General Rigging Instructions
WARNING
Failure to follow proper lifting instructions could result in property damage, serious injury, or death. Lifting should only be done by a qualified rigging company. Use ALL lifting points. Test lift to ensure proper balance and rigging. Never lift in high winds.
Lifting Lug Installation
Before attaching lifting equipment, verify location of lifting lugs or eyes. B- and C-Cabinet sized units have the lifting lugs or eyes factory installed as follows:
• B-Cabinet sized units without Energy Recovery include (4) eye bolts at each corner on the top of the unit.
• B-Cabinet sized units with Energy Recovery include (6) lifting lugs on the base, one at each corner and one on each length-wise side of the unit between the corners.
• C-Cabinet sized units include (4) eye bolts at each corner on the top of the unit. For units that include the shipped separate Energy Recovery Module (model ERM) option, refer to the latest revision of the Installation and Service Manual, #MCP15-520, that shipped with the ERM for separate rigging instructions.
• D-Cabinet sized units must have the lifting lugs installed in the unit base assembly prior to rigging as follows:
1. Locate the lifting lug kit box, kit # 66802, located in
the supply fan compartment.
2. Install the kit per the “Installation Instructions, Lifting
Lugs D-Cabinet”, #MCP15-505, included with the kit.
3. After installing the kit, verify that all (4) lugs are
installed following the instructions in Step 2. Verify that each lug is secured using (4) Grade 5 bolts provided with the kit. Each bolt must be torqued to 75 ft-lb.
Unit Rigging and Lifting
Rigging and lifting of the units should only be done by a qualified rigging company. With the lifting lugs or eyes identified and installed, the units can be lifted by crane or helicopter.
1. Follow site preparation instructions for the roof curb or equipment stand before installation.
2. Check the Serial Plate(s) of unit with plans to be sure unit is properly located. Although units may look outwardly similar, their function, capacities, options, and accessories will often vary.
3. Check unit dimensions of both the unit base and the curb or stand on which the unit will be installed.
4. If the unit will be installed on a roof curb:
a. Thoroughly clean and dry the top of the curb surface.
b. Lay a bead of weather resistant caulking on top
perimeter of roof curb as illustrated in Figure 7.1. Note: If roof curb is supplied by Modine, full perimeter gasket material is supplied and caulking is not necessary.
5. When lifting the equipment, connect sturdy steel cables, chains, or straps with eye loops as illustrated in Figure 6.1. For stability in lifting and lowering and to prevent damage to the unit, include a spreader bar as illustrated in Figure
6.1. Avoid twisting or uneven lifting of the unit. The cable length from the lifting point on the unit to the spreader bar should always be longer than the distance between the outer lifting points.
6. Test lift the unit to check for proper rigging balance before hoisting to the desired installation location.
7. Once lifted to the installation location, orient the hoisted unit to match the ductwork locations and set evenly on the curb or stand.
8. Following the instructions in this manual, make final unit connections to the electric power supply and remote control circuits. Connect the gas lines to the unit heating compartment. Seal all utility line clearance holes on the unit after connections are completed so they are watertight.
Figure 6.1 - Typical Rigging for Model MPR
6 MCP15-500.7
DUCT INSTALLATION AND UTILITY CONNECTIONS
RETURN AIR CONNECTOR
DISCHARGE AIR CONNECTOR
90° FLANGED DUCTWORK
(By Installer)
UNIT BASE (Shown without unit for clarity)
ROOF CURB
BEFORE UNIT INSTALLATION CAULK ALL MATING SURFACES (Caulk by installer)
If roof curb is supplied by Modine, full perimeter gasket material is supplied and caulking is not necessary.
Duct Installation
1. The unit is designed to accept 90° flanged ductwork on both the supply and return air openings. Refer to the roof curb or the unit base dimensional drawings to determine the location of the openings.
2. Acoustic duct liners are recommended on all internal supply and return air ducts.
3. When ductwork is installed prior to unit arrival, flexible connections should be included to make connections easier and to simplify possible future service.
4. When a roof curb is used in conjunction with factory supplied discharge and/or return air connectors, the ductwork can be fastened to the connectors prior to the unit installation. The connectors will accept 90° flanged ductwork (see Figure 7.1).
Figure 7.1 - Discharge and/or Return Air Connectors
5. To assure proper air flow from the unit, follow these duct design recommendations:
a. Be sure ducts are properly sized and installed. b. As a general rule, all discharge ducts should have a
A = Cross Sectional Area of Rectangular Duct P = Perimeter of Rectangular Duct D = Diameter of Round Cut
c. Wherever turns in the duct work are made, include
d. Supply air ducts in a “T” configuration should be
avoided to prevent air temperature stratification. If this configuration must be used, provide appropriate mixing devices and/or the necessary straight duct length before the “T” to provide uniformly mixed air temperature delivery to both supply air duct trunks.
Utility Connections
Utility and control connections can be made to the unit from the bottom or through the fixed side panels. Holes can be field drilled in fixed side panels to accommodate utility connections as shown on the unit dimensional drawings and the utility entrance location area label located on the unit. All gas and electrical connections to the unit must be weatherized so they are watertight.
straight run of at least three (3) hydraulic duct diameters before making turns in the ductwork.
Hydraulic Duct Diameter for Rectangular Ducts = 4A/P Hydraulic Duct Diameter for Circular Ducts = D where:
turning vanes.
7MCP15-500.7
CONDENSATE DRAIN INSTALLATION
Evap Condensate Drain Trap Installation
IMPoRtANt
A properly designed drain with trap must be installed immediately after the unit evaporator coil condensate drain pan connection. Failure to do so will result in condensate that cannot properly drain from the unit, eventually causing the drain pan to fill. To prevent damage to the building or unit, a drain pan float switch is included as standard and will disable the unit if the maximum condensate level is reached.
All units require a drain system with a condensate trap to be
connected to the condensate drain pan connection which is accessible from the exterior of the unit casing. Failure to install a condensate drain trap may result in condensate overflowing from the drain pan, causing damage to the unit and building. See Figure 30.1 or 31.1 for location. The drain system is to be installed as follows:
1. The condensate drain pan includes a 1-1/4" female NPT stainless steel connection accessible from the exterior of the unit casing. Do not reduce the drain diameter. A drain pan connection kit is shipped loose for field installation to allow connection exterior to the casing. Refer to Figure 8.1 for assembly details.
Figure 8.1 - Condensate Drain Pan Connection Kit
Threaded Connection on Evap Coil Drain Pan
Threaded Nipple
Note: All kit components shown are factory supplied for field installation.
Rubber Washer
Corrosion Resistant Steel Washer
Corrosion Resistant Steel Locknut
Figure 8.2 - Condensate Drain Trap Installation
Note: All piping components shown are supplied by others.
 •Thetrapdepthmustbe½xthetrapheight.Forexample,if
the trap height is the minimum 6”, the trap depth must be 3” (see Figure 8.2).
 •Formaintenance,itisrecommendedtohaveacapped
cleanout at the top of the trap as shown in Figure 8.2.
5. After the exit from the trap, the drain must be pitched down from the unit connection at least 1” for every 10 feet of horizontal run to promote proper drainage. If the local installation code allows, the drain can be run to a waste water system.
6. If the trap may experience below freezing temperatures during non-cooling periods, heating wraps must be used to avoid water from freezing in and damaging the trap and drain system.
7. The trap must be primed before the unit is put into operation and properly maintained on a regular schedule. Refer to the Start-Up Procedure section and the Maintenance section for additional guidance.
TRAP HEIGHT
(6" MINIMUM)
CAPPED CLEANOUT
1/2 x TRAP
HEIGHT
2. The drain line should include provisions for disconnecting the line at or near the unit for maintenance/servicing of the unit. The drain line must not interfere with access panels, which are removable for maintenance/service.
3. The drain line must include a trap immediately after the unit, as shown in Figure 8.2. Failure to do so will result in condensate that cannot properly drain from the unit, eventually causing the drain pan to fill and overflow. If the drain pan overflows, significant damage can occur to the unit and/or building on which the unit is installed. A drain pan float switch is included as standard and will disable the unit if the maximum condensate level is reached.
4. The design of the trap is critical to ensure proper drainage. If the trap is not constructed properly with the dimensions as outlined in the following instructions, air could be drawn through the drain pipe and into the system or could back up into the drain pan.
 •Thedrainislocatedonthesuctionsideofthemain
supply air fan, resulting in a negative pressure relative to outside the unit cabinet. The trap height must be at least 6” to account for maximum negative pressure, including allowance for dirty filters. Note that the trap height is the difference in height from the drain connection of the unit to the leaving side of the trap. Refer to Figure 8.2.
8 MCP15-500.7
ELECTRICAL CONNECTIONS
Electrical Connections
WARNING
1. Disconnect power supply before making wiring connections or working on this equipment. Follow all applicable safety procedures to prevent accidental power up. Failure to do so can result in injury or death from electrical shock or moving parts and may cause equipment damage.
2. For units equipped for dual power supply sources, both sources of power must be disconnected to prevent electrical shock and equipment damage.
3. All appliances must be wired strictly in accordance with the wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
4. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
5. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than rated voltage.
roltage.
CAUtIoN
Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage.
1. Installation of wiring must conform with local building codes, or in the absence of local codes, with the National Electric Code ANSI/NFPA 70 - Latest Edition. Unit must be electrically grounded in conformance to this code. In Canada, wiring must comply with CSA C22.1, Part 1, Electrical Code.
2. Two copies of the job specific wiring diagram are provided with each unit, one permanently affixed to the inside of the door of the controls compartment and the other as a loose copy with the literature packet that ships with the unit. Refer to this diagram for all wiring connections.
3. Control wiring consists of both 24V analog control wiring and low current digital control signal wiring. To avoid signal interference, the two types should be run in separate conduits. If run in the same conduit, the digital signal wiring should be shielded at one end of the wiring run. Wiring should be twisted, stranded, and shielded communication wire.
4. The wire gauge must be sized according to the National Electric Code or CSA code based on amp draw and length of run. Refer to Table 9.1 for maximum wire lengths and the number of wires that can be wired to each low voltage terminal block based on the wire gauge being used.
Table 9.1 - 24V and Digital Control Wire Lengths
Minimum
Recommended
Wire Gauge
22 n/a 120
20 n/a 200
18 75 300
16 125 500
14 175 n/a
24V Control Wiring Digital Control Wiring
Maximum Distance from
Control Device to Unit
5. For field wiring to the factory terminal strip, the terminal strip connections are designed to clamp down on the wires. To properly connect the wires to the terminal strip:
• Push a small flat-head screwdriver into the square hole on the terminal. Press firmly until the screwdriver hits the back stop and opens the terminal (see Figure 9.1).
• Remove approximately 3/8” of insulation from the end of the wire and push the stripped wire into the oval hole in the terminal.
• Remove the screwdriver. Pull on the wire to make sure that it is securely clamped in the terminal.
• Make sure that the terminal clamp is in contact with bare wire (insulation removed).
Figure 9.1 - Terminal Strip Wiring
Oval Holes
for Wiring
(two rows each)
Square Holes
for Wire Release
(two rows each)
Terminal
Numbers
Test Probe
Points
6. Depending on the configuration of the unit controls, there may be sensors that are field installed. Review the unit ordered to verify that the sensors supplied match the configuration of the unit. The following are sensors that may be included for field installation:
Supply Air Temperature Sensor
This sensor is required on all units and should be mounted in the supply air ductwork downstream of the unit. The sensor should be located at least 5 feet, but not more than 20 feet downstream from the unit discharge.
Space Temperature/Humidity Sensor
This sensor is required on all units that have space temperature/humidity reset control. The sensor is to be wall-mounted in the space at a height of approximately 5 feet from the floor.
Building Pressure Sensor This sensor is required on all units that have space pressure control, either through modulating dampers or variable frequency drive control on the supply air blower. The sensor is to be mounted inside a control panel in the space and includes two pressure taps. One pressure tap is for outside atmospheric pressure reference, the other is for sampling the space pressure.
Duct Pressure Sensor
This sensor is required on all units that have duct pressure control through variable frequency drive control on the supply air blower. The sensor is to be mounted with the sensing probe inserted into the supply duct. The atmospheric pressure sampling tap is left open.
9MCP15-500.7
ELECTRICAL CONNECTIONS / GAS CONNECTIONS
Space CO2 Sensor
This sensor is required on all units that have demand based ventilation control. The sensor is to be mounted in the space at a height of approximately 5 feet from the floor.
Duct Mounted Smoke Detector
When ordered as a field installed accessory, the detector
should be mounted in the supply air or return air ductwork.
For further instructions on the above sensor(s), refer to the installation instructions that shipped with the sensor(s).
7. If the unit is a C-Cabinet sized unit with a Modine supplied Energy Recovery Module, Model ERM, the wiring connection between the MPR unit and the ERM unit must be made by extending the loose end of the wire drop located in the MPR unit outside air damper section, through the transition duct between units, and connected to the ERM control panel. Refer to the Installation & Service Manual that shipped with the ERM (Literature #MCP15-
520) for additional instructions. If the unit is a B-Cabinet sized unit with integral Energy Recovery, the unit is already factory wired to the Energy Recovery section.
8. The power supply to the unit must be protected with a fused or circuit breaker disconnect switch. Refer to the Figures on pages 32 through 35 for the location of the factory installed dead front disconnect option, if provided. Field installed disconnect switches should be mounted where required by the National Electric Code. Refer to the Model Serial plate for MCA and MOP values for the unit.
9. The power supply must be within +/-5% percent of the voltage rating and each phase must be balanced within 2 percent of each other. If not, advise the utility company.
10. External electrical service connections that must be installed include:
a. Supply power (120, 208, 240, 480, or 600 volts). b. Thermostats, building pressure sensors, or any other
accessory control devices that may be supplied (24 volts).
11. All outdoor electrical connections must be weatherized to prevent moisture from entering the electrical compartment.
12. Electrical connections are made in the controls cabinet and can be run through the bottom or side of the unit. Refer to the unit and base dimensional drawings for locations of wiring entrance. Refer to the wiring diagram for the terminal location of all low voltage wiring.
REVIEW BEFORE PROCEEDING
THIS SECTION APPLIES TO UNITS WITH
(MODEL DIGIT 17=2 OR 3).
IF THE UNIT DOES NOT HAVE GAS HEAT,
Gas Connections
WARNING
1. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing.
2. Gas pressure to appliance controls must never exceed 14" W.C. (1/2 psi).
3. To reduce the opportunity for condensation, the minimum sea level gas input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or 5% below the minimum rated input of dual rated units.
CAUtIoN
Purging of air from gas supply line should be performed as described in ANSI Z223.1 - latest edition “National Fuel Gas Code”, or in Canada in CAN/CGA-B149 codes.
IMPoRtANt
To prevent premature heat exchanger failure, the input to the appliance, as indicated on the serial plate, must not exceed the rated input by more than 5%.
1. Installation of piping must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - Latest Edition. In Canada, installation must be in accordance with CAN/CGA-B149.1 for natural gas units and CAN/CGA-B149.2 for propane units.
2. Piping to units should conform with local and national requirements for type and volume of gas handled, and pressure drop allowed in the line. Refer to Table 11.1 to determine the cubic feet per hour (cfh) for the size of unit to be installed. Using this cfh value and the length of pipe necessary, determine the pipe diameter from Table 11.2. Where several units are served by the same main, the total capacity, cfh and length of main must be considered. While the gas connection(s) on the unit may be smaller than 1", do not use pipe sizes smaller than 1" leading up to the unit. At the unit, reduce the pipe size down to the appropriate size (refer to Table 11.1 for connection sizes). Table 11.2 allows for a 0.3" W.C. pressure drop in the supply pressure from the building main to the unit. The inlet pressure to the unit must be 6-7" W.C. for natural gas and should not drop below 6.0" W.C. when the unit is operating. When sizing the inlet gas pipe diameter, make sure that the unit supply pressure can be met after the 0.3" W.C. has been subtracted. If the 0.3" W.C. pressure drop is too high, refer to the Gas Engineer’s Handbook for other gas pipe capacities.
OPTIONAL GAS HEAT
SKIP TO PAGE 15.
roltage.
10 MCP15-500.7
GAS
GAS CONNECTIONS
Furnace Size
(Btu/hr)
Gas Consumption
(CFH)
Gas
Connection
Table 11.1 - Natural Gas Heating Gas Consumption
Digit 6 Digit 18
F 150,000 143 1/2"
G 200,000 190 3/4"
H 250,000 238 3/4"
B
J 300,000 286 3/4"
K 400,000 381 3/4"
R 175,000 167 1/2"
S 225,000 214 3/4"
T 310,000 295 3/4"
J 300,000 286 3/4"
K 400,000 381 1"
C
L 500,000 476 1"
L 600,000 571 1"
U 350,000 333 1"
V 450,000 429 1"
K 400,000 381 1.5" x 2
L 500,000 476 1.5" x 2
M 600,000 571 1.5" x 2
Q 800,000 762 1.5" x 2
D
1 900,000 857 1.5" x 2
2 1,000,000 952 1.5" x 2
3 1,200,000 1143 1.5" x 2
4 1,400,000 1333 1.5" x 2
5 1,600,000 1524 1.5" x 2
j Natural gas consumption based on a heating value of 1050 Btu/cu. ft. k C-Cabinet units consist of two furnaces that together total the value shown in
Table 11.1.
l D-Cabinet units consist of two furnaces that together total the value shown
in Table 11.1 for sizes up to 800,000 Btu/hr. For sizes over 800,000 Btu/hr, the unit consists of four furnaces that together total the value shown in Table
11.1.
3. The gas piping to the unit can enter the unit from the side of the unit (refer to the unit dimensions) or from below (refer to the base dimensions). A drill locator sticker and dimple is located on the side of the unit to indicate the safe area for drilling the hole for side gas pipe entry on B- and C-Cabinet sized units. D-Cabinet sized units include a holes with grommets for side pipe entry. Install a ground joint union with brass seat and a manual shut-off valve external of the unit casing, and adjacent to the unit for emergency shut-off and easy servicing of controls, including a 1/8" NPT plugged tapping accessible for test gauge connection (see Figure
11.1). Verify the manual shut-off valve is gas tight on an annual basis.
NOTE: For bottom piped units, some local codes may require
a manual shutoff valve external to the unit casing. In this case, the gas piping must exit the unit through the side, followed by the manual shut-off valve, piped back into the unit side, and lead to an additional union and manual shut-off valve.
4. Provide a sediment trap before each unit in the line where low spots cannot be avoided (see Figure 11.1).
5. When Pressure/Leak testing pressures above 14" W.C. (1/2 psi), close the field installed shut-off valve, disconnect the appliance and its combination gas control from the gas supply line, and plug the supply line before testing. When testing pressures 14" W.C. (1/2 psi) or below, close the manual shut-off valve on the appliance before testing.
Figure 11.1 - Recommended Sediment Trap/Manual
Shut-off Valve Installation
GAS
SUPPLY LINE
SUPPLY LINE
MANUAL GAS
SHUT-OFF VALVE
GROUND JOINT
UNION WITH BRASS SEAT
Table 11.2 - Gas Pipe Capacities (Cu. Ft. per Hour) m
Pipe
Length
(feet)
1" 1-1/4" 1-1/2" 2"
10 520 1050 1600 3050 20 350 730 1100 2100 30 285 590 890 1650
40 245 500 760 1450 50 215 440 670 1270 60 195 400 610 1150 70 180 370 560 1050 80 170 350 530 990
90 160 320 490 930 100 150 305 460 870 125 130 275 410 780 150 120 250 380 710
m Gas pipe capacities based on gas pressure up to 14" W.C. through Schedule
40 pipe with a pressure drop of 0.3" W.C. for Natural gas with a specific gravity of 0.60.
Gas Pipe Diameter
TO GAS
CONTROLS
MIN.
3"
PLUGGED
1/8" NPT TEST
GAUGE CONNECTION
Side Gas Connection
SEDIMENT
TRAP
CONTROLS
PLUGGED 1/8"
NPT TEST GAUGE
CONNECTION
Through hole
in bottom of unit.
(caulk hole to prevent
GROUND
JOINT UNION
W/ BRASS
SEAT
water leakage.)
MANUAL GAS
SEDIMENT
TRAP
SHUT-OFF VALVE
GAS
SUPPLY LINE
Bottom Gas Connection
j Valve is in the “OFF” position when handle is perpendicular to pipe.
MIN.
3"
j
TO
11MCP15-500.7
GAS HEATING OPTION VENT TERMINALS AND COMBUSTION AIR HOODS
Vent
Terminals
Combustion
Air Hoods
6
Type
Field Installe d Qty
(Btu/hr)
18
Vent Terminals and Combustion Air Hoods
1. Do not operate the units without the factory supplied (shipped loose) power exhauster vent system/vent termination(s) or combustion air hoods if applicable. Refer to Table 12.1 to determine how many terminals and hoods are required based on the model MPR nomenclature.
2. Do not modify or obstruct the combustion air inlet louvers or the power exhauster discharge cover terminations.
3. Do not add any vents other than those supplied by the manufacturer. For units that require vent extension kits, refer to Literature #MCP15-574, “Installation Instructions, Extended Vent Kit, Model MPR Gas Heat”.
Table 12.1 - Power Exhauster Vent Terminal and
Combustion Air Hood Quantity
Digit
B
C
D
Furnace Size
Digit
F 150,000
G 200,000
H 250,000
J 300,000
K 400,000
R 175,000
S 225,000
T 310,000
J 300,000
K 400,000
L 500,000
L 600,000
U 350,000
V 450,000
K 400,000
L 500,000
M 600,000
Q 800,000
1 900,000
2 1,000,000
3 1,200,000
4 1,400,000
5 1,600,000
Furnace
Non-
Condensing
Condensing
Non-
Condensing
Condensing
Non-
Condensing
Non-
Condensing
1
1 n/a
2
2
2 2
4 2
n/a
n/a
n/a
Non-Condensing Furnaces (B, C, or D-Cabinet)
For Non-Condensing furnace types, as determined from Table
12.1, refer to Figure 12.1 for vent termination installation details, otherwise skip to the section titled Condensing Furnaces. For units that require vent extension kits, refer to Literature #MCP15-574, “Installation Instructions, Extended Vent Kit, Model MPR Gas Heat”.
Figure 12.1 - Power Exhauster Vent Terminal for
Non-Condensing Gas Furnace Option
Note: Caulk mating surfaces before
2
Gas Furnace
Vent Outlet
k C-Cabinet sized unit shown with two vent terminals. B-Cabinet sized units
have only one and D-Cabinet with have either one on each side of the cabinet (two total) or two on each side of the cabinet (four total).
attaching to the unit
(6) Screws for Fastening Gas Furnace Vent Outlet Cover (supplied with kit)
For D-Cabinet units, the furnace doors must have the combustion air hoods field installed as shown in Figure 12.2,
using the screws included with the kit. Once complete, proceed to the “Start-Up” section.
Figure 12.2 - Combustion Air Hood Installation
(D-Cabinet only)
For specific instructions on each configuration in Table 12.1, refer to the appropriate section from the following sections titled:
• Non-Condensing Furnaces (B, C, or D-Cabinet), or
• Condensing Furnace (B-Cabinet), or
• Condensing Furnace (C-Cabinet)
12 MCP15-500.7
Note: Caulk mating surfaces before attaching to the unit.
Also shown are the vent terminals for reference.
(refer to
Instructions
Step 1)
(refer to Instructions Step 3)(refer to Instructions Step 2)
(refer to Instructions Step 1) (refer to Instructions Step 2)
GAS HEATING OPTION VENT TERMINALS AND COMBUSTION AIR HOODS
Condensing Furnaces (B-Cabinet)
For B-Cabinet units with Condensing furnace types, as determined from Table 12.1 on page 12, refer to Figures 13.1 and 13.2 for vent termination installation details. The installation steps are as follows:
Step 1: Insert short vent pipe length into the vent pipe
reducer. Insert that assembly into the rubber coupling on the power exhauster outlet. Tighten the clamp on the flexible coupling to secure the vent pipe.
Step 2: Insert the outer vent pipe with termination elbow
through the enclosure wall grommet and into the vent pipe section installed in Step 1.
Once complete, proceed to the “Condensate Drain and Trap Installation” section.
Condensing Furnaces (C-Cabinet)
Figure 13.1 - Power Exhauster Vent Terminal for
Condensing Gas Furnace Option
For C-Cabinet units with Condensing furnace types, as determined from Table 12.1 on page 12, refer to Figures 13.3 and 13.4 for vent termination installation details. The installation steps are as follows:
Step 1: Insert small diameter outside vent pipe termination
through enclosure wall grommet and into the flexible rubber coupling on the right side power exhaust outlet. Tighten the clamp on the flexible coupling to secure the vent pipe.
Step 2: Insert large diameter inner vent pipe assembly into
the flexible rubber coupling on the left side power exhaust outlet. Tighten the clamp on the flexible coupling to secure the vent pipe.
Step 3: Insert large diameter outside vent pipe termination
through enclosure wall grommet and into the interlocking joint of the inner vent pipe assembly from Step 2.
Step 4: Verify that the bird screens are inserted in the outlet
elbow.
Once complete, proceed to the “Condensate Drain and Trap Installation” section.
Figure 13.3 - Power Exhauster Vent Terminal for
Condensing Gas Furnace Option
Figure 13.2 - Orientation of Installed Vent Terminal for Condensing Gas Furnace Option (B-Cabinet)
Discharge Elbow must be
oriented to exhaust
straight down.
Figure 13.4 - Orientation of Installed Vent Terminal for Condensing Gas Furnace Option (C-Cabinet)
Discharge Elbows must
be oriented to exhaust
straight down.
13MCP15-500.7
3/4" Threaded Elbow on Heat Exchanger Drain Assembly (included with kit)
3/4" Male Threaded PVC Adapter (included with kit)
3/4" PVC Pipe (by others) with Sufficient Length to Reach the Heat Exchanger Drain Assembly from the Inside of the Building
3/4" Unions (by others) Recommended for Ease of Future Service
PVC "EZ-Trap" (included with kit) for Proper Drain Trapping (a 3/4" to 1" bushing by others may be required)
Note: The trap must be located in a heated space or protected to avoid freezing.
Vacuum Breaker and Drain Piping Components (by others)
To Building Drain System
From Heat
GAS HEATING OPTION CONDENSATE DRAIN AND TRAP INSTALLATION
Condensate Drain and Trap Installation (Condensing Furnace Type Only)
For Condensing furnace types, as determined from Table 12.1 on page 12, during heating operation, condensate is produced in the furnace sections. The installation requires condensate drain systems from each furnace section, as shown in Figures
14.1 and 14.2 and described below. Condensate trap kits are
provided with the unit.
1. For proper heating system performance, the condensate
drain system must include a trap for each furnace. B-Cabinet units have one furnace while C-Cabinet units have two furnaces.
2. All joints must be watertight to prevent leakage of
condensate. The drains must be extended down through the base of the unit and into the heated space below.
3. Each heat exchanger drain assembly includes a threaded
elbow that is oriented down. Once the male threaded PVC adapters, included with the kit, are glued to the PVC drain pipe (by others) that extends into the space, they are to be routed up through the holes in the unit base pan and screwed into the elbow connections. The threads must be sealed to prevent leaks.
4. Unions are recommended to permit maintenance of the
drains and to facilitate service of the heater. A union is shown on both sides of each trap.
5. A vacuum breaker is required after each trap. The vacuum
breaker should be constructed so that dirt and debris do not enter and clog the drain system.
6. Local code permitting, the condensate drain systems may
be joined after the traps and connected to a sanitary drain within the building. Because the condensate produced is acidic, some municipalities may require that the condensate be neutralized before being discharged into the sanitary sewer. A condensate neutralizer tube kit is available from Modine to reduce the pH of the condensate. A single tube can be used for drains that are joined after the traps providing the tube is installed after the junction. Refer to the instructions that come with the kit.
7. For proper operation, the traps must be primed with water.
The traps must be installed with the higher side connected to the heater and the lower side connected to the drain.
8. If there is an opportunity that the temperature in the space
will fall below freezing during non-operating periods, the condensate drain systems and secondary heat exchanger must be completely drained to prevent freeze damage. Alternately, heat tape can be applied to the drain pipe system in accordance with the heat tape manufacturers instructions.
Figure 14.1 - Furnace Condensate Drain/Trap
System j
j C-Cabinet sized unit shown with two condensate drain systems. B-Cabinet
sized units require only one drain system.
Figure 14.2 - Drain System Trap/Vacuum Breaker
Exchanger Drain Assembly on Unit
Note: Drain pipe from unit
Vacuum Breaker
To Building Drain System
Note: Refer to figure above for determination of parts supplied by others.
must enter the high side of the drain trap.
14 MCP15-500.7
HOT WATER PIPING CONNECTIONS
REVIEW BEFORE PROCEEDING
THIS SECTION APPLIES TO UNITS WITH
OPTIONAL HOT WATER HEAT
(MODEL DIGIT 17=4).
IF THE UNIT DOES NOT HAVE HOT WATER
HEAT, SKIP TO PAGE 16.
CAUtIoN
1. Units not approved for use in potable water systems.
2. Do not operate the unit with steam. The coil is not designed for steam condensate removal which can damage the unit.
3. Hot water supplied to the hot water heating option must not exceed 180°F temperature or 75 PSIG pressure.
1. Models with a factory installed hot water heating coil (for use with water or propylene glycol fluids) are supplied with 1-1/2" sweat connections (1.625").
Figure 15.1 - Hot Water Coil Connections
 •On3-wayvalvecontrolconfigurations,includeabalancing
valve between the supply line and control valve to balance the system.
 •Includeahosebibdrainvalveonthebottomofthesupply
manifold to allow for periodic flushing of the system to remove sediments from the coil.
 •Includeapipelinestraineronthesupplylinetoprevent
sediment from reaching the coil.
 •Includeanairventatthetopofthereturnmanifoldtobleed
off accumulated air in the system. Air in the system will generate noise and may cause water hammer that can damage the joints of the piping and coil.
 •Includeeithera2-wayor3-waymodulatingcontrolvalve
designed for a 0-10VDC control signal. The valves will be automatically modulated by the unit’s Carel controller to maintain the supply air temperature setpoint. Note that the control valve must be a normally open, spring return type valve. This is to allow hot water to flow through the coil for freeze protection when the unit is shut down. Refer to the Freeze Stat Option section for additional detail.
 •Hotwaterpipesshouldbeinsulatedtoreduceheatlossand
to prevent overheating of the end compartment.
9. Leak test the coil and connections as outlined in the Start-Up section.
Figure 15.2 - Typical 2-Way Piping Installation (piping and components by others)
Supply Connection Return Connection
2. The entering water temperature (EWT) supplied to the heating coil must not exceed 180°F.
3. The fluid flow rate must not exceed 50 gallons/minute (GPM) and fluid pressure must not exceed 75 psi.
4. It is recommended to use an inhibited glycol solution that is designed for HVAC applications for corrosion protection and freeeze protection for the lowest possible outside air temperatures for the installed location. Failure to protect against freezing can result in damage to the coil and property.
5. Provide adequate pipe hangers, supports, or anchors to secure the piping system independently of the coil to prevent excess vibration and stress that can damage the piping and joints.
6. All field brazing and welding should be performed using high quality materials and an inert gas purge (such as nitrogen) to reduce oxidation of the internal surface of the coil.
7. System piping should be flexible enough to allow for thermal expansion and contraction of the coil and piping components.
8. Refer to Figures 15.2 and 15.3 for typical piping system design and the following recommended items:
 •Installshut-offvalvesinlinestoandfromtheunittoallow
for maintenance or replacement of the coil without shutting down and draining the entire system.
 •Installunionsforeaseofpipingcomponent/coilremoval.  •Includeacircuitsetterinthereturnlinetoregulateflow.
HOSE BIB DRAIN
SHUT-OFF
VALV E
SHUT-OFF
VALV E
SUPPLY
RETURN
HOT WATER
COIL
AIR VENT
UNION
UNION
2-WAY CONTROL
VALV E
STRAINER
UNION
CIRCUIT SETTER
Figure 15.3 - Typical 3-Way Piping Installation
(piping and components by others)
HOSE BIB DRAIN
SHUT-OFF
VALV E
SHUT-OFF
VALV E
SUPPLY
RETURN
HOT WATER
COIL
AIR VENT
UNION
UNION
BALANCING
VALV E
3-WAY CONTROL
VALV E
UNION
STRAINER
UNION
CIRCUIT SETTER
Optional Factory Installed Freeze Stat
When equipped with the optional Coil Freeze Stat, an auto­resetting capillary type freeze stat (see Figure 50.1) is factory installed immediately below and across the face of the hot water coil. The stat is set to trip at 40°F (adjustable) and will automatically reset when the coil temperature rises 5°F above the setpoint. If the stat has tripped, the unit controls would respond by closing the outdoor air damper, opening the return air damper (if applicable), de-energize the supply air fan, open the hot water coil valve 100%, and log the alarm on the controller. The freeze stat can be removed from the unit for servicing as discussed in the Maintenance section.
15MCP15-500.7
START-UP PROCEDURE
General
1. When the dead front disconnect switch(es) (for main unit and/or powered convenience outlet option) is in the “OFF” position, supply power remains energized at the line (supply) side of the dead front disconnect switch(es). The switch body is located inside of another junction box to protect against contact with the live wiring. The junction box must not be disassembled unless the main power supply from the building to the unit is de-energized.
2. For units equipped for dual power supply sources, both sources of power must be disconnected to prevent electrical shock and equipment damage.
WARNING
WARNING
CAUtIoN
When servicing the unit, some components may be hot enough to cause pain or injury. Allow time for cooling of hot components before servicing.
IMPoRtANt
1. To prevent premature heat exchanger failure, check to be sure the blower has been set to deliver the proper airflow for the application. Refer to page 17 for Blower Adjustments.
2. Start-up and adjustment procedures must be performed by a qualified service agency.
3. All scroll compressors requires the correct supply power phase rotation. Phase reversal may result in compressor failure not covered under warranty. Refer to the Start-Up Procedure section.
4. The exhaust fan is not designed for high temperature or smoke control exhaust applications. Exhaust air temperature must not exceed 104°F. Operating the exhaust fan above 104°F will result in failure of the exhaust fan.
1. Turn off power to the unit at the disconnect switch. If equipped with gas heating option, turn all hand gas valves to the “OFF” position.
Note: The dead front disconnect switch, if included, is factory installed in the controls/compressor compartment section (refer to the figures on pages 32 through 35). The disconnect switch is designed so that it must be turned “OFF” before entry to the compartment can be obtained. When in the “OFF” position, power is disconnected to all unit wiring electrically following the switch (see WARNING).
2. For units equipped for dual power supply sources, both sources of power must be disconnected to prevent electrical shock and equipment damage.
3. Open the power compartment, controls compartment, and blower access doors.
4. Check that the supply voltage matches the unit supply voltage listed on the Unit Serial Plate. For units equipped for dual power supply sources, the voltage on both the main feed and the auxiliary feed must match the unit supply voltage listed on the Unit Serial Plate.
5. Check that fuses or circuit breakers are in place and sized correctly.
6. Verify that all wiring is secure and properly protected. Trace circuits to ensure that the unit has been wired according to the wiring diagram.
7. Check that all electrical and gas connections are weatherized.
8. For C-Cabinet sized units, if the unit is installed with a Modine supplied Energy Recovery Module, Model ERM, verify that the wiring connection between the MPR unit and the ERM unit has been properly installed. If the unit is a B-Cabinet sized unit with integral Energy Recovery, the unit is already factory wired to the Energy Recovery section.
9. For units with gas heating, check to ensure that the combustion air inlet louvers and the power exhauster discharge cover (Non-Condensing as determined from Table 12.1 on page 12) or the vent elbow terminations (Condensing as determined from Table 12.1 on page 12) are free from obstructions.
10. For units with condensing gas heating, check that the condensate drain system is properly installed and the trap has has been primed with water.
11. For units with Hot Water Heat (Digit 17=4), check the following:
• Open air vents so that air is eliminated from within the coil circuitry and headers. Verify that vents and drains are not obstructed and do discharge a stream of water.
• Open all required valves to fill the coil. Once the coil is full, close all air vents.
• Perform an initial hydrostatic leak test of all brazed, threaded or flanged joints, valves and interconnecting piping, and the hot water coil. Recheck the coil level and correct if necessary.
• When the setup is found to be leak free, flush the coil through the drain valve to eliminate grease, oil, flux and sealing compounds present from the installation.
• Recheck the coil and all connections for water leaks.
• Check water flow rates and pressure drops and compare
to design.
• Check that the hot water supplied to the coil does not exceed 180°F temperature or 75 PSIG pressure. Verify that the appropriate glycol mixture is used for freeze protection.
12. Check to see that there are no obstructions to the intake and discharge of the unit.
13. Verify that the belts are aligned in the sheave grooves properly and are not angled from sheave to sheave.
14. On belt driven blowers, blower bearings are permanently lubricated unless they are pillow block bearings or if they have grease fittings. For motors or blower bearings that are not permanently lubricated, lubricate according to the manufacturer’s instructions. Refer to the Maintenance section on page 48.
15. Check to make sure that all filters are in place and that they are installed properly according to direction of air flow. Pleat direction must be vertical to ensure optimum performance.
16. Perform a visual inspection of the unit to make sure no damage has occurred during installation.
16 MCP15-500.7
START-UP PROCEDURE - CONTINUED
17. Check that the evaporator drain pan drain trap has been primed with water.
18. Turn on power to the unit at the disconnect switch. Note: Units include one blower door switch per access door (one on B- and C-Cabinet, two on D-Cabinet) that are factory installed inside the blower access section door(s). When a blower section door is opened, the switch is opened and interrupts power to the low voltage circuit and de-energizes the blower motor controller. D-Cabinet units also have the same switches on the evaporator/hot gas reheat coil access sections.
19. Check the Carel microprocessor controller and supply fan blower motor for electrical operation. If the unit is equipped with the optional building power exhauster module (with or without energy recovery), check the blower motor for electrical operation. If these do not function, recheck the wiring diagram. Check to ensure that none of the Control Options (for example, smoke detector, etc.) have tripped.
20. Check to make sure that the damper(s) operate properly without binding.
21. Check that the supply power wiring is wired with the correct phase rotation. For units equipped for dual power supply sources, correct phase rotation must be verified on both the main feed and the auxiliary feed. Incorrect phase rotation can damage the equipment. Check the phase rotation as follows:
• For units equipped with single speed motor starters on the supply fan: Check the blower wheel
for proper direction of rotation when compared to the air flow direction arrow on the blower housing. Blower wheel rotation, not air movement, must be checked as insufficient air will be delivered if the blower wheel is running backwards. If the blower wheel is rotating in the opposite direction, the phase reversal must be corrected by changing the incoming power feed legs at the supply to the unit, NOT the individual components on the unit. Recheck for proper rotation.
• For units equipped with a variable frequency drive on the supply fan: The VFD will correct the phase
rotation for the supply fan, but will not correct the phase rotation for the rest of the unit, therefore observing the supply blower wheel rotation direction is not an accurate indicator of correct phase rotation. Scroll compressors will only compress in one rotational direction. Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation will result in no pressure differential as compared to normal values. There is no negative impact on durability caused by operating the compressors in the reversed direction for a short period of time (under one hour) but should not be allowed to operate longer than the time it takes to verify rotation. If the compressor is rotating in the opposite direction, the phase reversal must be corrected by changing the incoming power feed legs at the supply to the unit, NOT at the compressor. Recheck for proper rotation.
22. Check the blower speed (rpm). Refer to Blower Adjustments for modification.
23. Check the motor speed (rpm).
24. Check the motor voltage. On three phase systems, check to make sure all legs are in balance.
25. Check the motor amp draw to make sure it does not exceed the motor nameplate rating. Check all legs to ensure system is balanced.
26. For units equipped for dual power supply sources, the unit should be started separately on the main power feed and again on the auxiliary power feed to verify proper unit and control operation.
Note: Units equipped for dual power supply sources have the unit power wiring separated into two circuits as follows:
Circuit #1
• Compressors
• Condenser fans
• Electric heating section (if applicable).
• Energy recovery wheel (if applicable)
Circuit #2
• Main unit controller
• Supply fan
• Dampers
• Gas heating section (if applicable)
• Exhaust fan (if applicable)
• Energy recovery wheel bypass damper (if applicable)
When operating in a full power state with the main power feed, both Circuit #1 and Circuit #2 should be powered. When operating in a low power state with the auxiliary power feed, only Circuit #2 should be powered.
Blower Adjustments
The units are designed for ease of airflow adjustments, within a range, for field balancing against actual external static pressure conditions. If the static pressure external to the unit is above or below the original design point for the unit, the blower will deliver an airflow volume that is lower or higher than required. When equipped with the building exhaust option (with or without energy recovery), the air balancing must be performed for both the main unit supply fan, as well as the exhaust fan.
The blower speed (supply and/or exhaust blowers) may be adjusted to achieve the desired air volume, provided:
• The allowable temperature rise range and the maximum supply air temperature for heating is not exceeded as shown in Table 18.1, and
• The airflow is within the allowable limits shown on the serial plate for both heating and cooling, and
• The total static pressure does not exceed the limit shown on the unit serial plate, and
• It is within the range of adjustability for the unit, and
• The motor amp draw must not exceed the motor
nameplate rating.
The blower speed adjustment method is dependant on the following configurations:
Direct Drive where the blower is driven directly by the motor as seen in Figure 18.1. This is the current standard supply fan configuration for all units.
Belt Drive where the blower is driven by the motor with a belt and sheaves as seen in Figure 18.2. This is the current standard exhaust fan configuration (if equipped) for all units. It was also used on supply fans for units shipped before 2018.
Once the blower/motor configuration of the unit is determined, follow the appropriate instructions in the sections on the following pages.
17MCP15-500.7
START-UP PROCEDURE - CONTINUED
Figure 18.1 - Direct Drive Blower Example
Direct Driven Blower
(dual blower shown)
Figure 18.2 - Belt Drive Blower Example
Motor Sheave (adjustable)
Blower Sheave (non-adjustable)
Automatic Belt Tensioner
Blower Adjustments – Direct Drive Fans
All direct drive supply fan speed adjustments can be performed with the Modine Control System programmable microprocessor controller. There are two ways to access the menus:
1. Using the user interface on the main unit controller.
2. Using the pGD1 Digital Display/Interface Module.
For guidance on either method above, refer to the latest revision of the following documents for additional warnings, cautions, controller location, instructions, and menu navigation:
• ControlsManual,MCP15-525.
• pGD1DigitalDisplay/InterfaceModuleInstallation
Instructions, MCP15-543.
The blower adjustments are made as follows:
1. Ensure unit is running at the maximum airflow setting for the control type selected. For example, if the unit has Multi-Speed or Variable Speed fan control, ensure the unit is operating at the highest speed setting.
2. On the keypad navigate to menu “G. Service -> f. SERVICE SETTINGS”. At this menu, you will be prompted to enter the Service password of 1500.
3. Navigate to “c. Control Settings” and scroll to the “Supply Fan Control (CS6)” screen. See Figure 18.3.
Table 18.1 - Allowable Temperature Rise Range and
Maximum Supply Air Temperature
Casing
Size
B
C
D
Heat Type Rating
(for formula)
1 A, B, C, D 1.00 N 1 - 100°F 100°F
F, G, H, J, K 0.81
2 or 3
2 or 3
2 or 3
R, S, T 0.94 N 30 - 100°F 100°F
1 A, B, C, D, E 1.00 N 1 - 100°F 100°F
J 0.81 N 30 - 75°F
K, L, M 0.81
U, V 0.81
1 A, B, C, D, E 1.00 N 1 - 100°F 100°F
K 0.81 L 30 - 75°F
L, M, Q 0.81
1, 4
2, 3, 5 H 60 - 120°F
Eff
0.81
Temp Rise
Allowable
Temp Rise
Range
L 30 - <70°F H 70 - 100°F
L 30 - <70°F H 70 - 100°F L 30 - <70°F H 70 - 100°F
L 30 - <70°F H 70 - 100°F H 70 - 120°F
Max Supply
Air TempDigit 6 Digit 17 Digit 18 Digit 19
130°F
130°F
100°F
130°F
Figure 18.3 - Control Settings Screen CS6
4. Adjust the Air Balance Adj parameter up or down to obtain the design airflow given the actual static pressure.
5. In the event you are unable to increase or decrease the motor speed to the desired air balance please consult your factory representative.
6. Check the motor amps to ensure the maximum motor amp rating is not exceeded. For units equipped with a VFD, measure the amps at the incoming lines to the motor. If the unit has dual supply fans, measure each motor individually. Verify airflow volume and repeat steps above for further adjustment.
7. If equipped with gas heat, turn on the gas and initiate burner operation. For guidance, refer to the Controls Manual.
8. Verify the temperature rise and supply air temperature of the heating section do not fall outside the range or exceed the maximums shown in Table 18.1. Airflow can be approximated with the following formula:
CFM = (Input Btu/hr x Eff) / (1.08 x Temp Rise) where Eff (Efficiency) is determined from Table 18.1
18 MCP15-500.7
Loading...
+ 42 hidden pages