Modine Manufacturing MCP15-542.0 Service Manual

MCP15-542.0
5H081676A
IMPORTANT
1. Disconnect power supply before installing the accessory to prevent the unit from operating during installation.
2. The use of this manual is specifically intended for a qualified installation and service agency. All installation and service of these kits must be performed by a qualified installation and service agency.
3. These instructions must also be used in conjunction with the Installation and Service Manual originally shipped with the appliance, in addition to any other accompanying component supplier literature.
Power Supply Input:
24 Vac (powered from unit)
Power Consumption:
1 Watt Maximum
Operating Conditions:
32°F to 122°F 10 to 85% Relative Humidity
(non-condensing)
Index of Protection:
IP30 (NEMA Type 1)
Carel pAD Digital Wall Stat/Humidity Sensor
INSTALLATION INSTRUCTIONS
Carel pAD digital wall stat/humidity sensor
commercial packaged ventilation system units
model MPR
Application
The Carel pAD (Ambient Display) wall thermostat/humidity sensor is used in conjunction with the Carel pCO3 controller mounted on model MPR Packaged Rooftop Commercial Ventilation units.
Functions of the pAD include:
Change temperature and humidity set points  Clock display  Alarm indication  Time clock override  Display of icons (refer to page 3)
Specifications
THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
INSTALLATION – Carel pAD Digital Wall Stat/Humidity Sensor
Terminal on pAD
Terminal on Main Unit or
pCO3 Controller
G (24 Vac)
503 (on unit)
G0 (ground)
500 (on unit)
Rx/Tx+ (positive pLAN)
Rx/Tx+ (on pCO3 – J11 block)
Rx/Tx- (negative pLAN)
Rx/Tx- (on pCO3 – J11 block)
1 – Cooling Mode 2 – Heating Mode 3 – Auto 4 – Dehumidification Mode 5 – Humidification Mode 6 – Fan Speed 7 – Units of Measure
8 – Temp/Humidity Setpoint 9 – Day of the Week 10 – Time/Temp/Humidity Setpoint 11 – ON/OFF Time 12 – Occupied Override Time 13 – pAD Locked 14 – Active Alarm Indication
Installation
1. Separate the sensor from its base by pushing the white tab at the bottom of the sensor and pull the white body from the gray base by hinging it up from the bottom. Refer to Figure 2.1.
Figure 2.1 – Separating the Sensor from the Base
2. Locate and mount the sensor in the conditioned space, considering the following:
Mount in a location representative of the space
temperature. Do not locate on an outside wall or near supply grills, windows, or other devices that could cause incorrect temperature readings.
Mounting height will depend on personal
preferences and applicable codes.
If required, the sensor can be mounted in a well-
ventilated thermostat cover.
The sensor base will mount on a standard 2 x 4
electrical box mounted sideways.
3. Connect the control wiring to the base terminals, running the wiring through the hole in the center of the base. The recommended control cable is 18-22 AWG 4-Core Twisted Pairs. Refer to Figure 2.2.
Figure 2.2 – Control Wiring to pAD Sensor Base
4. Connect the control wiring to the terminals on the model MPR unit, or on the pCO3 controller mounted on the model MPR unit, using Table 2.1 to cross-reference the correct connections.
Table 2.1 – Terminal to Terminal Wiring Connection
5. Holding the sensor on the outer edge of the enclosure, reinstall the sensor on the base by hooking the top of the sensor into the base and hinge down, making sure the pins line up. DO NOT force the sensor into place or touch the components on the back of the sensor.
6. For the pAD Sensor to function correctly, the pAD setting must be enabled in the pCO3 microprocessor controller. This can be found under “Manufacturing Settings” using the keypad (See pCO3 manual).
Display Features
Figure 2.3 shows the operation icons on the display of the pAD and what they indicate. Note that not all are used with model MPR applications.
Figure 2.3 – pAD Display Features
2 MCP15-542.0
Not used with model MPR.
Loading...
+ 2 hidden pages