Model IHR, Control Codes 47, 48, 97, 98, 27, and 67
INSTRUCTIONS APPLY TO:
Installation Operation Maintenance
WARNING
Improper installation, adjustment, alteration,
service or maintenance can cause property
damage, injury or death. Read the installation,
operating, and service/maintenance instructions
thoroughly before installing or servicing this
equipment.
WARNING
Gas-Fired appliances are not designed for use in
hazardous atmospheres containing flammable
vapors or combustible dust, or atmospheres
containing chlorinated or halogenated
hydrocarbons.
FOR YOUR SAFETY
The use and storage of gasoline or other flammable
vapors and liquids in the vicinity of this appliance is
hazardous.
FOR YOUR SAFETY
If you smell gas:
1. Open Windows.
2. Do not touch electrical Switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
5. If gas supplier cannot be reached, call fire
department.
FOR INDOOR INSTALLATION ONLY.
NOT FOR RESIDENTIAL USE.
HAZARD INTENSITY LEVELS
• DANGER: Failure to comply will result in severe
personal injury or death and property damage
• WARNING : Failure to comply could result in severe
personal injury or death and/or property damage.
• CAUTION: Failure to comply could result in minor
personal injury and/or property damage.
Improper installation, adjustment, alteration, service, or maintenance can cause property
damage, serious injury, or death. Read and understand the installation, operating, and
maintenance instructions thoroughly before installing or servicing this equipment. Only
trained, qualified gas installation and service personnel may install or service this
equipment.
Safety Symbols
Safety is the most important consideration during installation, operation, and maintenance of the infrared
heater. You will see the following symbols and signal words when there is a hazard related to safety or
property damage.
Warning indicates a potentially hazardous situation
WARNING
which, if not avoided, could result in death or injury.
Caution indicates a potentially hazardous situation
CAUTION
NOTICE
which, if not avoided, could result in minor or
moderate injury.
Notice indicates a potentially hazardous situation
which, if not avoided, could result in property
damage.
Applications
This is not an explosion proof heater. Consult your local fire marshal, insurance carrier, and other authorities
for approval of the proposed installation.
Commercial / Industrial (Indoor Use Only)
Infrared heaters are designed and certified for use in industrial and commercial buildings such as warehouses,
manufacturing plants, aircraft hangars, and vehicle maintenance shops. For maximum safety, the building
must be evaluated for potential hazards before installing the heater system. A critical safety factor to consider
before installation is the clearance to combustibles.
Residential
This heater is NOT approved for use in any residential application. This includes, but not limited to, attached
garages, living quarters, solariums, etc. Consult the local fire marshal and/or insurance provider if unsure
of your application.
Not For Residential Use.
Installation of an infrared heater system in residential indoor spaces, RV’s,
mobile homes, etc. may result in property damage, asphyxiation, fire, serious
injury, or death.
WARNING
!
1.0 Safety • Clearance to Combustibles
!
IHR Series Manual
Clearance to Combustibles
WARNING
Placement of explosive objects, flammable objects, liquids,
and vapors close to the heater may result in explosion, fire,
property damage, serious injury, or death. Do not store, or use,
explosive objects, liquids, and vapor in the vicinity of the
heater.
Failure to comply with the published clearances to combustibles could result in personal injury, death,
and/or property damage.
CAUTION
Signs shall be posted specifying the maximum permissible stacking height in order to
maintain clearances to combustibles.
Hazards Include:
For maximum safety the building must be evaluated for hazards before installing the heater system.
Examples include, but are not limited to:
• Gas and electrical lines
• Combustible and explosive materials
• Chemical storage areas
• Areas of high chemical fume concentrations
• Provisions for accessibility to the heater
• Adequate clearances around air openings
• Combustion and ventilating air supply
A critical safety factor to consider before installation is the clearances to combustibles. Clearance to
combustibles is defined as the minimum distance you must have between the infrared surface, or reflector,
and the combustible item. Considerations must also be made for moving objects around the infrared heater.
The following is a partial list of items to maintain clearances from:
The stated clearance to combustibles represents a surface temperature of 90°F (50°C) above room
temperature. Building materials with a low heat tolerance (such as plastic, vinyl siding, canvas, tri-ply, etc.)
may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adjacent
materials are protected from degradation.
When installing the infrared heater system, the minimum clearances to combustibles must be maintained.
These distances are shown in Chart 1.1 and on the heater. If you are unsure of the potential hazards, consult
your local fire marshal, fire insurance carrier, or other qualified authorities on the installation of gas fired
infrared heaters for approval of the proposed installation.
4
IHR Series Manual
1.0 Safety • Clearance to Combustibles
Chart 1.1 • Clearance to Combustibles in Inches (see Figure 1.1)
Model No.SidesBackTopBelow/ Front
IHR 3030182872
IHR 60321840 72*
IHR 9048304298
IHR 130483052120
IHR 160503260132
* This clearance is 80 in. when the heater is fitted with a parabolic reflector.
NOTE: If the heater is mounted beneath a non-combustible surface, a 24 in. minimum top clearance must
be maintained from the top of the heater to prevent overheating the controls.
Figure 1.1 • Clearance to Combustibles
Top
SideSide
Front
20° - 35°
Mount Heater Level
- Side to Side -
FRONT VIEWSIDE VIEW
Back
Manifold or
Control End
Below
1.0 Safety • Gas Connection • Standards, Certifications and Government Regulations
!
IHR Series Manual
Gas Connection
WARNING
An approved connector, suitable for the environment of equipment usage, is required.
Visible or excessive swaying, flexing, and vibration of the gas connections must be avoided
to prevent failure. Neither the gas pipe nor the connector shall be placed in the ‘flue
discharge area’. In no case shall the gas supply support the weight of the heater.
To ensure your safety, and comply with the terms of the warranty, all units must be installed in accordance
with these instructions.
Standards, Certifications and Government Regulations
Installation of this infrared heater must comply with all applicable local, state, and national specifications,
regulations and building codes. Contact the local building inspector and/or fire marshal for guidance.
In the absence of local codes, the installation must conform to the latest edition of:
United States: National Fuel Gas Code, ANSI Z223.1 (NFPA 54).Canada: CAN/CGA B149.1 and .2, Canadian Electrical Code C22.1
Copies of these standards can be viewed or purchased at www.nfpa.org or www.scc.ca.
Chart 1.2 • Standards and Code Installation Guidelines • Building Aspect
Building
Aspect
Electrical
Venting
The heater must be electrically grounded in accordance with the following codes:
United States: Refer to National Electrical Code
Wiring must conform to the latest edition of National Electrical Code
ordinances, and any special diagrams furnished.
Canada: Refer to Canadian Electrical Code CSA C22.1 Part 1 (latest edition).
Venting must comply with the requirements within this manual and the following
codes:
United States: Refer to NFPA54/ANSI Z223.1 (latest edition), the National Fuel
Gas Code.
Canada: Refer to CAN/CGA B149.1 Installation Codes for Gas Burning Appliances.
Codes and Guidelines
®
, ANSI/NFPA 70 (latest edition).
®
, local
6
IHR Series Manual
1.0 Safety • Standards, Certifications and Government Regulations
Chart 1.3 • Standards and Code Installation Guidelines • Building Type
Building
Aspect
Public
Garages
Aircraft
Hangars
Codes and Guidelines
Installation of this infrared heater in public garages must conform to the following
codes:
United States:
Standard for Parking Structures NFPA 88A (latest edition) or the
Code for Motor Fuel Dispensing Facilities and Repair Garages NFPA 30A (latest
edition).
Canada: Refer to CAN/CGA B149.1 and B149.2: Installation Codes for Gas
Burning Appliances.
Guidelines:
• Heaters must not be installed less than 8 ft. (2.4 m) above the floor. Minimum
clearances to combustibles must be maintained from vehicles parked below the
heater.
• When installed over hoists, minimum clearances to combustibles must be
maintained from the upper most point of objects on the hoist.
Installation of this infrared heater in aircraft hangars must be in accordance with the
following codes:
United States: Refer to Standard for Aircraft Hangars, ANSI/NFPA 409 (latest
edition).
In Canada: Refer to Standard CAN/CGA B149.1 and B149.2.
Guidelines:
• In aircraft storage and servicing areas, heaters shall be installed at least 10 ft.
(3 m) from above the upper surface of wings or of the engine enclosures of the
highest aircraft that may be housed in the hangar. The measurement shall be
made from the wing or engine enclosure, whichever is higher from the floor, to
the bottom of the heater.
• In areas adjoining the aircraft storage area (e.g., shops, offices) the bottom of
heaters shall be installed no less than 8 ft. (2.4 m) above the floor.
• Suspended or elevated heaters shall be located in spaces where they shall not
be subject to damage by aircraft, cranes, movable scaffolding, or other objects.
Provisions shall be made to assure accessibility to suspended infrared heaters for
recurrent maintenance purposes.
Applicable authorities governing the manufacturing or installation of this heater include (but are
not limited to) the following organizations:
In the United States:
• NFPA 54/ANSI Z223.1 - National Fuel Gas Code.
• ANSI Z83.19/C2.35 - Gas-fired High Intensity Infrared Heaters.
• ANSI/NFPA 70 - National Electric Code.
• IRSC.
In Canada:
• CAN/CGA B149.1-10 - Natural Gas and
Propane Installation Code.
• ANSI Z83.19/C2.35 - Gas-fired High Intensity
Infrared Heaters.
• C22.1 Part 1 - Canadian Electrical Code.
SAMPLE
1.0 Safety • Safety Signs and Labels
SAMPLE
IHR Series Manual
Safety Signs and Labels
It is important to provide warnings to alert individuals to potential hazards and safety actions. ANSI Z83.19
and the National Fuel Gas Code require you to post a sign “specifying the maximum permissible stacking
height to maintain the required clearances from the heater to the combustibles” near the heater’s thermostat
or in absence of such thermostats in a conspicuous location. Signs should state the hazards for the
particular application and be legible to the building occupants. Consult the factory or a factory representative
for additional information on signage compliance.
Safety warning labels must be maintained on the
infrared heater. Illustrations of the safety labels,
and their locations, are pictured below.
Back View
Bottom View
UNVENTED GAS RADIANT HEATER
FOR INDOOR (Non-Residential) INSTALLATION ONLY.
High - Intensity Infrared Heater
MODEL NO.
IHR 60S 47
VOLTS AC:
120V - 60Hz
AMPS - STARTING:
0.1
AMPS - RUNNING:
0.1
DESIGN COMPLIES WITH:
ANSI Z83.19 (latest edition) - Gas Fired High Intensity Infra-Red Heater
MODINE MANUFACTURING COMPANY
1500 DEKOVEN AVENUE - RACINE, WI 53403
1.800.828.4328 (HEAT)
Class IIIA Permanent Label
INPUT BTU/H
60,000
HEATER TYPE:
C1
MANIFOLD PRESSURE:
10.0 INCHES W.C.
MAX. INLET PRESSURE
14.0 INCHES W.C.
www.modinehvac.com
MODEL NO.
IHR 60S 47
VOLTS AC:
120V - 60Hz
AMPS - STARTING:
0.1
AMPS - RUNNING:
0.1
DESIGN COMPLIES WITH:
ANSI Z83.19 (latest edition) - Gas Fired High Intensity Infra-Red Heater
MODINE MANUFACTURING COMPANY
1500 DEKOVEN AVENUE - RACINE, WI 53403
262-636-1200 www.modine.com
UNVENTED GAS RADIANT HEATER
FOR INDOOR (Non-Residential) INSTALLATION ONLY.
High - Intensity Infrared Heater
Class IIIA Permanent Label
INPUT BTU/H
60,000
HEATER TYPE:
C1
MANIFOLD PRESSURE:
10.0 INCHES W.C.
MAX. INLET PRESSURE
14.0 INCHES W.C.
VERSION
05/97
VERSION
05/97
FOR USE WITH
Natural Gas
MIN. INLET PRESSURE FOR
PURPOSE OF ADJUSTMENT
11.0 INCHES W.C.
MIN. MOUNTING ANGLE
20 DEGREES
MAX. MOUNTING ANGLE
35 DEGREES
Serial No. 0807MODI123456001
FOR USE WITH
Natural Gas
MIN. INLET PRESSURE FOR
PURPOSE OF ADJUSTMENT
11.0 INCHES W.C.
MIN. MOUNTING ANGLE
20 DEGREES
MAX. MOUNTING ANGLE
35 DEGREES
Serial No. 0807MODI123456001
Rating Plate
CAUTION
Avoid Equipment Failure
Consult manual for installation guidelines.
Connect proper VOLTA GE as noted on gas valve and heater’s
rating label (25VAC or 120VAC).
Proper POLARITY must be observed. Hot line of electrical
source must be connected to black wire; neutral line to white wire.
For proper operation, green line must connect to POSITIVE EARTH on all 120VAC heaters.
Observe listed inlet GAS PRESSURES.
Natural Gas: 7 Inches W.C. Min. 14 Inches W.C. Max.
L.P. Gas: 11 Inches W.C. Min. 14 Inches W.C. Max.
Observe 20°-35° MOUNTING ANGLE. DO NOT mount
horizontally. Consult installation manual.
Reference the WIRING DIAGRAM located inside this box.
F/N: LLDR002
F/N: LL01 - Clearance
Safety Tag
(Affix adjacent to
heater’s thermostat)
8
F/N: LLDCL002
Clearance to Combustibles Label
!
!
IHR Series Manual
2.0 Installation • Design
2.0 Installation
WARNING
Read and understand, the installation, operating, and maintenance instructions
thoroughly before installing or servicing this equipment.
Only trained, qualified gas installation and service personnel may install or service this
equipment.
CAUTION
This heater cannot be used in a building with an uninsulated roof or condensation problems can occur.
Design
To ensure a safe, properly designed heating system, a layout should be developed for the correct placement
of the infrared heater(s). Aside from safety factors such as clearance to combustibles (see Chart 1.1 on
page 5), you should take also into consideration the environment (e.g., cold/drafty, average, protected),
heat coverage (sq. ft.) needed, heater centers, the distance behind a person or work station(s) and exhaust
path. Also, the effective infrared surface temperature of a person or object may be diminished with wind
above 5 mph. Wind barrier(s) may be required. Most importantly, clearance to combustibles must always
be maintained! Refer to hazards on page 4.
This installation manual, along with national, state, provincial, and local codes, address these issues. It is
critical that you read, understand, and follow all guidelines and instructions. Always inspect and evaluate the
mounting conditions, space for exhaust, gas supply and wiring.
Perimeter mounting of infrared heaters provides the most effective distribution of heat. The recommended
spacing between the heaters is shown in Chart 2.1. Add additional heaters in the center of the space when
heaters are spaced farther than the recommended distance (see Figure 2.1 ).
When heated, materials high in hydrocarbons (solvents, paint thinner, mineral spirits, formaldehydes, etc.)
can evaporate. This may result in odors or fumes being emitted into the environment. To correct this problem,
clean the area and/or introduce additional ventilation. Heaters installed and serviced in accordance with the
installation manual do not emit foul odors into the environment.
IMPORTANT: Fire sprinkler heads must be located at an appropriate distance from the heater. This
distance may exceed the published clearance to combustibles. Certain applications will require the use of
high temperature sprinkler heads or relocation of the heaters.
Sprinkler systems containing propylene glycol or other flammable substances are not to be used in
conjunction with this heater without careful consideration for, and avoidance of, potential fire or explosion
hazards. For further information, consult NFPA 13. Always observe applicable state and local codes.
2.0 Installation • Heater Placement
IHR Series Manual
Chart 2.1 • Recommended Mounting Heights and Distances for “Total Area” Heating
Mounting Heights Dim. A
30° Angle
Standard
Model No.
IHR 3012-1412-158-2415- 404-8
IHR 6014-1618-2112-3615-556 -12
IHR 9016-1821-2516-4820-706-12
IHR 13021-2426-3220-6025-858-14
IHR 16024-2829-3524-6530 -1008-14
Reflector (ft.)
30° Angle
Parabolic
Reflector (ft.)
Distance
Between
Heaters
Dim. B (ft.)
Distance
Between
Heater Rows
Dim. C (ft.)
Distance
Between
Heater
and Wall (ft.)
Factory recommended mounting heights are listed as a guideline. If infrared heaters are mounted too low or
too high, they may result in discomfort or lack of heat. Modine Manufacturing Company generally recommends
observing the recommended mounting heights to optimize comfort conditions. However, certain applications
such as spot heating, freeze protection, outdoor patio heating or very high ceilings may result in the heaters
being mounted outside of the recommended mounting heights.
Figure 2.1 • Total Area Heating Sample Layout
B
Key
Infrared heater
B
C
Thermostat
Perimeter mounting
Air intake louver
Exhauster
A
A
Perimeter and center row mounting
10
IHR Series Manual
2.0 Installation • Heater Placement
Chart 2.2 • Recommended Mounting Heights and Distances for “Spot” Heating
Model
& Input
IHR 30
30,000
BTU/h
IHR 60
60,000
BTU/h
IHR 90
90,000
BTU/h
IHR 130
130,000
BTU/h
IHR 160
160,000
BTU/h
Recommended
Approx.
Type of Area
(Surroundings)
Cold/Drafty10’ x 10’1009’ to 10’4’10’
Average12’ x 12’14 410’ to 12’5’12’
Protected/Insul.14’ x 14’19612’ to 14’6’14’
Cold/Drafty16’ x 16’25612’ to 14’6’16’
Average18’ x 18 ’32414’ to 16’7’18’
Protected/Insul.20’ x 20’40016’ to 18’8’20’
Cold/Drafty20’ x 20’40016’ to 18’9’20’
Average24’ x 24’57618’ to 20’10’24’
Protected/Insul.28’ x 28’78420’ to 22’11’26’
Cold/Drafty26’ x 26’67618’ to 20’11’26’
Average30’ x 30’90018’ to 20’12’28’
Protected/Insul.35’ x 35’122520’ to 22’13’32’
Cold/Drafty28’ x 28’78420’ to 22’12’28’
Average35’ x 35’122524’ to 26’16’32’
Protected/Insul.40’ x 40’160028’ to 30’20’35’
Area
Covered
Approx.
Coverage
(sq. ft.)
Mounting Height
Stnd. Reflector
(Dim. A)
Behind
Person or
Work Station
(Dim. B)
Centers for
Full Coverage
(Spot & Area)
Htg. Only
Distance
Figure 2.2 • Spot Heater Heights
B
A
2.0 Installation • Heater Mounting
!
IHR Series Manual
Heater Mounting
WARNING
Improper suspension of the infrared heater may result in collapse and being crushed. Always
suspend from a permanent part of the building structure that can support the total force and
weight of the heater.
Failure to maintain minimum clearance to combustibles may result in fire and/or explosion,
property damage, serious injury, or death. Always maintain minimum clearances and post
signs or provided tags (F/N: LL01) where needed. Signs should state the hazards for the
particular application and be legible to the building occupants. Consult the factory or a
factory representative for additional information on signage compliance.
An approved connector, suitable for the environment of equipment usage, is required.
Visible or excessive swaying, flexing, and vibration of the gas connections must be avoided
to prevent failure. Neither the gas pipe nor the connector shall be placed in the ‘flue
discharge area’. In no case shall the gas supply support the weight of the heater.
The heater can be suspended with chains or rigid threaded rod. Local codes or conditions that would cause
the unit to move (e.g., wind drafts, blowers, crane rails, etc.) may require rigid threaded rod. Consult all
applicable codes before installation.
The heater must be level from side to side and between 20° and 35° from horizontal. The pilot burner or
ignitor, manifold, and controls must be located on the lower end. Refer to Figure 2.3.
Figure 2.3 • Heater Mounting and Orientation
Steel “C”
clamp
Rigid threaded
rod
Chain
hanging
set
Closed “S” hook
(typical)
Mount Heater Level
Side to Side
Control
20˚ - 35˚
SIDE VIEW
End Down
20˚ - 35˚
SIDE VIEW
12
Control
End Down
Pilot/spark electrode must
be in lower right corner.
(excludes IHR30S)
FRONT VIEW
IHR Series Manual
!
2.0 Installation • Ventilation
Ventilation
WARNING
Insufficient ventilation may result in health problems, carbon monoxide
poisoning, or death. Vent enclosed spaces and buildings according to
national, state, provincial, and local codes.
Improper venting may result in asphyxiation, fire, explosion, injury, or death.
It is required that the levels where heaters are mounted be properly ventilated to supply combustion air to
the heaters and to sufficiently dilute the products of combustion. It is also required that the flue discharge
area is kept clear of gas piping and electrical wiring (see Figure 2.4).
This infrared heater must be vented in accordance with national, state, provincial, and local codes and the
guidelines in this manual. In the United Sates refer to the latest edition of ANSI Z223.1 (NFPA 54) and in
Canada refer to the latest edition of the CAN/CGA B149.1 & B149.2 Standard.
Figure 2.4 • Hot Flue Discharge
Flue Discharge Area
Important! Do not
install gas piping or
electrical wiring above
the flue discharge
area!
20˚ - 35˚
SIDE VIEW
Provisions must also be made to provide sufficient fresh air intake area and exhaust air outlet area. For
proper ventilation, a positive air displacement of 4 CFM/1,000 BTU/h of gas consumed mus be provided.
Where insufficient air movement exists, induced air displacement is required. A balanced system is essential
to avoid negative building pressure which causes excessive infiltration, unfavorable drafts, and affects
combustion efficiency.
Air displacement may be accomplished by either natural or mechanical means. Mechanical exhausters are
preferred and typically mounted at high points on the roof where stagnant air accumulates inside the building.
For a flat roof, considerations of prevailing winds, high and low pressure areas, and distribution of air
movement must be taken into consideration when locating exhausters.
Manifold/Control
End Down
Best air distribution is accomplished by using a number of small exhausters versus one large exhauster.
Provide a minimum of one square inch of inlet area per 1,000 BTU/h for combustion air supply. Inlet
opening in the building should be well distributed (see Figure 2.1) high in the sidewalls and should direct
incoming air upward to dilute products of combustion while preventing drafts at lower levels. Inlets are
typically 1 to 3 sq. ft.
Local codes may require that mechanical exhaust systems be interlocked with heaters to enable both to
function simultaneously (see page 17, Figure 2.6) or allow control of exhausters with a ceiling mounted
humidistat.
2.0 Installation • Gas Supply
!
IHR Series Manual
Gas Supply
WARNING
Improperly connected gas lines may result in fire, explosion,
poisonous fumes, toxic gases, asphyxiation, or death. Connect
gas lines in accordance to national, state, provincial, and local
codes.
The gas supply to the infrared heater must be connected and tested in accordance with national, state,
provincial, and local codes along with the guidelines in the Modine Manufacturing Company IHR Series
manual. In the United States refer to the latest edition of the ANSI Z223.1 (NFPA 54) Standard and in
Canada refer to the latest edition of the CAN/CGA B149.2 Standard.
Important! Before connecting the gas supply to the infrared heater(s):
• Check that the gas piping and service has the capacity to handle the load of all heaters being installed, as well as any other gas appliances being connected to the supply line.
• Check that the main gas supply line is of proper diameter to supply the required fuel pressures.
• If utilizing used pipe, verify that its condition is clean and comparable to a new pipe. Test all gas supply lines in accordance with local codes.
• Test and confirm that inlet pressures are correct. Refer to the rating plate for required minimum and maximum pressures (see Chart 2.3). The gas supply pipe must be of sufficient size to provide the required capacity and inlet pressure to the heater (if necessary, consult the local
gas company).
Chart 2.3
Note: Check manifold pressure at the tap located either at the outlet of the gas valve or on the gas
manifold pipe. Readings will be above atmospheric pressure during operation.
Pressure Equivalents: 1 inch W.C. equals .058 oz/sq. in. equals 2.49 Mbar.
Pressure
Minimum
Inlet Pressure
Maximum
Inlet Pressure
14
IHR Series Manual
!
!
!
2.0 Installation • Gas Connection
To connect the gas:
WARNING
Failure to install, operate, or service this appliance in the approved manner may result in
property damage, injury, or death.
An approved connector, suitable for the environment of equipment usage, is required.
Visible or excessive swaying, flexing, and vibration of the gas connections must be
avoided to prevent failure. Neither the gas pipe nor the connector shall be placed in the
‘flue discharge area’. In no case shall the gas supply support the weight of the heater.
This heater must be installed and serviced by trained gas installation and service personnel only.
The installation of this heater must conform with local building codes or, in the absence of such codes, the
National Fuel Code (NFPA 54).
The gas outlet must be in the same room as the appliance and accessible. It may not be concealed within
or run through any wall, floor or partition.
The IHR Series heater is equipped to receive a gas supply line nipple of 1/2” NPT Schedule 40
1
metallic pipe. All piping must be installed in accordance with the requirements outlined in the National
Fuel Gas Code ANSI/Z223.1 (latest edition) or CSA B149.2. Support all gas supply with pipe hangers,
metal strapping, or other suitable material. Do not rely on the heater to support the gas pipe.
Form the stainless steel flexible connector (field supplied) into a smooth C-shape allowing 12 in.
2
between the flexible connector’s end nuts. Figure 2.5 on page 16. NOTE: Not for use on rigidly
mounted heaters.
Install a ground joint union with a brass seat and a manual shut off valve adjacent to the unit for
3
emergency shut off and easy servicing of controls. A 1/8” NPT plugged tap that is accessible for a test
gauge connection is also recommended.
A sediment trap must be installed in the supply line in the lowest spot prior to connecting to the heater.
4
The trap length shall be at least three inches long. Ideally, the trap would be installed as close as
possible to the shut off.
When connecting piping to the unit, the use of a thread joint compound is required. The thread
5
compound (pipe dope) shall be resistant to the action of propane gas or any other chemical
constituents of the gas to be conducted through the piping. Use of Teflon
®
tape is not permitted.
WARNING
Always use two (2) opposing wrenches to tighten mating pipe connections
to prevent excessive torque on the gas valve and manifold pipe. Excessive
torque can damage the valve and/or misalign the orifice, resulting in fire,
explosion, serious injury, or death.
2.0 Installation • Gas Connection • Leak Testing
!
!
!
Figure 2.5 • Gas Connection
NOTE: Use a
regulator when gas
supply pressure
exceeds 14” W.C. Do
not exceed 14” W.C.
to the appliance.
20˚ - 35˚
Disconnect switch
Ball Valve / Inlet Tap
IHR Series Manual
TOP VIEW
Drip Leg/
Sediment Trap
SIDE VIEW
Stainless Steel Gas Connector, formed into a smooth C-Shape
(Field Supplied). Not for use with rigidly mounted heaters.
Leak Testing
WARNING
Use a soap solution or equivalent for leak testing. Never test for leak with an open flame.
Failure to comply could result in personal injury, property damage, or death.
Always leak test final gas assembly for gas leaks according to the procedures outlined in NFPA 54 and all
local codes and/or Standards.
For leak testing on pressures below ½” PSI
Before leak testing, close the field installed manual shut off valve shown on Figure 2.5 on the supply line
to isolate the gas valve from the pressure.
NOTE: All factory installed gas connections have passed an approved leak test.
For leak testing on pressures above ½” PSI
When leak testing with pressures above ½” PSI (14 inches W.C.), the unit must be isolated from the
supply pipe. Close the field installed manual shut off valve, disconnect the supply line to the unit, and
temporarily cap the supply line for testing purposes.
Gas pressures to the appliance controls must never exceed 14 inches W.C. (1/2” PSI).
Supply pressures greater than 14” W.C. can damage the controls, resulting in personal
injury, property damage, or death.
WARNING
16
IHR Series Manual
!
!
2.0 Installation • Electrical Requirements and Wiring Diagrams
Electrical Requirements and Wiring Diagrams
WARNING
Shock hazard. Disconnect power supply before making wiring connections to prevent
electrical shock and equipment damage. Any original factory wiring that requires replacement
must be replaced with wiring material having a temperature rating of at least 105°C.
All field installed wiring to the unit heater must be must be done in accordance with the national, state,
provincial, local codes, and to the guidelines in this manual. In the United States, refer to the most current
revisions to the Electrical Code ANSI/NFPA 70 and in Canada refer to the most current revisions to the
Canadian Electrical Code CSA C22.1 Part 1. The unit must be electrically grounded according to these
codes. Line polarity must be observed when making field connections.
CAUTION
The power supply to the heater must be within +/- 5% of the voltage rating as indicated on the rating
plate of the appliance. If input power does not meet these specifications, contact your utility company.
Before proceeding with electrical connections, ensure that the supply voltage, frequency, phase and
current capacity meet the requirements specified on the rating plate. A dedicated line voltage supply with
properly sized wire should run directly from the main electrical panel to the heater. The power to the unit
must be protected with a circuit breaker appropriate for the load. The unit must be electrically grounded
in accordance with local codes, or in their absence, with the latest edition of the National Electrical Code,
ANSI / NFPA 70 and/or the Canadian Electrical Code CSA C22.1, latest edition.
Control systems are initiated by either 120 VAC, 24 VAC or millivolt energy. The 120 VAC systems can be
used directly from a 120 VAC line. On 24 VAC systems, transformers must be used to supply power of
sufficient VA rating for single or multiple connected installations.
Millivolt systems require NO external power, as energy needed to operate the valve is developed by the
power-pile generator. Do not use multiple connections, as one thermostat may only control one heater.
For wiring of controls on the unit, see the Figure 2.6 below. It is recommended that the thermostat be
installed on the hot side of a fused supply line and have sufficient ampere capacity rating for the heater(s)
it will control. The ventilation system may not be controlled separately from the heating system (consult
local codes) by the use of a humidistat that closes then the humidity rises. The humidistat control should
be installed at roof level. For summer ventilation, a simple on/off switch can be installed at the occupant
level.
Figure 2.6 • Typical Field Wiring
IHR Series
Heater
IHR Series
Heater
IHR Series
Heater
Thermostat
Transformer
(required on
24V heaters)
Hot
Neutral
Exhaust
Fan
N/PFS-2 24VAC
2.0 Installation • Wiring Diagrams
Figure 2.7 • Millivolt • 750 Schematic
• Millivolt Control
Figure 2.8 • 24V Schematic
IHR Series Manual
• Direct Spark
Ignition
ELECTRODE
• VA Draw: 12
ASSEMBLY
• Amps: .48
• Potted Circuit
Board
GAS VALVE
Figure 2.9 • 120V Schematic
• Direct Spark
Ignition
ELECTRODE
ASSEMBLY
• VA Draw: 12
BK
BL
O
W
SENSE
GROUND
G
NEUTRAL
THERMOSTAT
VALVE
24VAC DSI MODULE
O
HIGH
VOLTAGE
BK
W
GG
BK
W
W
(24VAC)
(COMMON)
L1
• Amps: .10
• Potted Circ uit
Board
GAS VALVE
BK
SENSE
NEUTRAL
THERMOSTAT
W
W
BK
NEUTRAL
VALVE
GROUND
120VAC DSI MODULE
G
G
HIGH
VOLTAGE
G
W
L2
18
IHR Series Manual
!
3.0 Operation •Lighting Instructions
3.0 Operation
WARNING
Do not attempt to ignite a direct spark ignition heater by hand. Failure to comply could
result in personal injury, property damage, explosion, fire, or death.
Upon satisfactory completion of the electrical supply and purging of the gas supply line to the heater(s),
follow the lighting instructions on the heater’s rating label to put the heater into operation.
Direct Spark Ignition
Lighting Instructions
Rotate the heater’s valve knob to the “ON” position.
1
Close electrical circuit (typically the thermostat).
2
If the heater fails to light, turn off gas, open electrical circuit and wait 5 minutes before repeating the
3
above steps.
Shutdown Instructions
Open electrical circuit.
1
Rotate the heater’s valve knob to the “OFF” position.
2
Sequence of Operation
Starting Circuit: Upon a call for heat, voltage is applied to L1 and Neutral. After a pre-purge, the spark
electrode is energized and the gas valve opens. The trial for ignition is 15 seconds. If flame is not sensed,
the heater will attempt two more times to reignite.
Running Circuit: After ignition, the sensing electrode monitors the burner flame. If sense of flame is lost,
the control immediately acts to reignite the gas-air mixture. If flame sense is not established within 15
seconds, the heater will attempt two additional ignition sequences before proceeding to hard lockout. The
control can be reset by briefly interrupting the power source.
Millivolt
Lighting Instructions
Purge main gas supply line.
1
Slightly depress and rotate the heater’s manual gas valve knob COUNTERCLOCKWISE from the
2
“OFF” position to the “PILOT” position.
Fully depress the manual gas valve knob and light the pilot burner. Continue to depress for 30
3
seconds and then release.
Rotate the heater’s valve knob to the “ON” position.
4
Close the control circuit. If the heater fails to light, turn off the gas, open control circuit and wait 5
5
minutes before repeating the above steps.
Shutdown Instructions
Open the control circuit.
1
Rotate the heater’s valve knob to the “PILOT” position, depress slightly and rotate to the “OFF” position.
2
Sequence of Operation
Starting Circuit: After manually lighting the pilot (see lighting instructions), upon a call for heat, the main
burner solenoid is energized. The gas valve opens and the pilot lights the main burner.
Running Circuit: After ignition, the powerpile monitors the pilot flame. If the pilot flame is lost, the
powerpile cools and closes the valve within 180 seconds. See lighting instructions to relight the heater.
4.0 Maintenance •Maintenance Checks
!
!
IHR Series Manual
4.0 Maintenance
It is recommended that the following become a standard yearly procedure to obtain maximum operating
efficiency and trouble free operation.
During long periods of non-usage, remove or cover heater with a polyethylene bag and shut off gas supply.
If further service to the heater is desired, contact your representative or the factory.
Main Burner
Gently use an air hose to blow any
1
accumulated dust and/or dirt off the heater.
Air hose pressure must not exceed 30 psig.
Gently pass the air hose over the entire
2
exposed area of the ceramic. A distance of
2’ to 4’ from the unit is recommended.
NOTE: Blowing out the gasket material will
permanently damage the rayhead.
WARNING
Use protective glasses when cleaning
the heater.
Disconnect power to heater before
servicing.
Gently place the air hose outlet into each
3
venturi tube and allow the air to flow for
approximately one minute.
See troubleshooting chart (page 21) if there
4
are any signs of burner malfunction. Replace
if necessary.
Pilot Burner
Remove pilot access door.
1
Use an air hose and gently blow the pilot
2
burner free of dust or debris.
Gas Supply
Periodically inspect the gas supply for signs
1
of corrosion or failure. Replace if necessary.
Do not operate unit if repairs are
necessary. Do not operate unit
showing any signs of burner
malfunction. Call a professional for
assistance.
CAUTION
Avoid Equipment Failure.
Do not blow out heating elements
with high pressure air.
20
IHR Series Manual
4.0 Maintenance •Troubleshooting
Chart 4.1 Troubleshooting Guide
SymptomCodePossible CauseCorrective Action
Burning of gas-air
mixture inside
plenum (flashback).
Delayed ignition.A
Low ceramic surface
temperature, exces
sive rollout or soot on
rods.
Control system
overheating.
Gas odor.A, BB• Loose pipe connection.
Heater cycles
repeatedly.
Pilot on, no gas to
main burner.
No spark; no ignition.A
Heater lights, and
“locks out” after
approximately 10
seconds.
Spark is present. No
main gas operation.
Unit “locks out”.
Heater will not
shut off.
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
-
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
• Heater mounted at incorrect angle.
• Excessive drafts.
• Gas leaking or blocked orifice/venturi.
• Separation of ceramic grids.
• Ceramic grids cracked.
• Electrode out of specification.
• Low gas pressure.
• Partially blocked orifice.
• Improper orifice size.
• Incorrect gas.
• Dirty or plugged rayhead ceramics.
• Partially blocked orifice.
• Low inlet gas pressure.
• Low manifold gas pressure.
• High manifold pressure.
• Foreign matter in venturi tube.
• Gas supply piping too small.
• Incorrect gas.
• Heater not mounted correctly.
• Heater mounted too close to ceiling.
• Pilot not lit.
• Heater located in drafty area.
A
• Low gas pressure.
• Thermostat located in drafty area.
• Weak pilot flame.
B
• Defective flame detector.
B• Weak pilot flame.
• No electrical power to unit.
• Pilot sensor element not located in pilot flame.
• Defective main valve solenoid.
• Defective pilot generator or thermocouple.
• Excessive thermostat wire length with millivolt
system.
• Manual valve off.
• Lack of 120V or 24V incoming voltage.
• Open high voltage wire.
A
• Improper electrode gap.
A
• Loose or open wire connection.
A
• Poor or no equipment ground.
A
• Unit in “safety lockout” mode.
A
• Defective “gas lighter” control.
A
• Poor or no equipment ground.
A
• Polarity is reversed.
A
• Low gas pressure.
A
• Electrode not sensing.
A
• Heater mounted at incorrect angle.
A
A
• Gas valve in “Off” position.
A
• Defective main valve solenoid.
A
• Defective “Gas lighter” control.
• Defective thermostat or wiring.
• Gas valve stuck open.
• High gas pressure.
• Mounting angle 20°-35° from horizontal.
• Relocate or shield from draft.
• Do not operate. Check with leak detector solution.
• Do not operate. Replace rayhead.
• Do not operate. Replace rayhead.
• See Figure 4.3.
• See Gas Supply section.
• Clean or replace.
• Consult dealer.
• Do not operate. See nameplate. Correct immediately.
• See maintenance instructions.
• Remove and clean.
• See Gas Supply section.
• Adjust main valve regulator for 6” W.C. natural
gas, 10” W.C. propane.
• Adjust main valve regulator for 6” W.C. natural
gas, 10” W.C. propane.
• See Maintenance Section.
• Increase inlet pressure or replace.
• Do not operate. See nameplate. Correct immediately.
• Mounting angle 20°-35° from horizontal.
• Observe clearance to combustibles safety chart
located on heater reflector. Do not operate.
• Check all connections with leak-detector
solution, tighten as necessary.
• Cycle thermostat or manually light.
• Relocate or shield from draft.
• See Gas Supply section for propane.
• Replace thermostat.
• Clean or adjust pilot.
• Replace.
• Clean or adjust pilot.
• Check thermostat, manual switch or circuit
breaker.
• Locate upper 3/4 of element in pilot flame.
• Isolate. Measure resistance, replace if “0”.
• Replace.
• Wire not to exceed length provided by factory.
• Turn to “ON” position.
• Proper voltage needed or repair wire.
• Isolate and measure resistance, replace if “0”.
• See Figure 4.3.
• Check all wires, tighten or replace.
• Trace ground wire for complete circuit back to
equipment ground from control.
• Interrupt power source, repeat trial for ignition.
• Verify proper voltage. Replace.
• Check all connections, provide positive earth
ground.
• 120V to black, neutral to white.
• See Gas Supply section.
• Relocate or replace if defective.
• Mounting angle 20°-35° from horizontal.
• Turn to “On” position.
• Isolate and check for resistance. Replace if “0”.
• Verify proper voltage. Replace.
• Replace or repair.
• Replace.
• See Gas Supply section.
Code: A - Direct Spark Ignition (24V/120V) B - Standing Pilot (Millivolt)
4.0 Maintenance • Heater Assembly Components
IHR Series Manual
Heater Assembly Components
NOTE: Replacement burners are called “rayheads” with rod inserts. Ceramic grids are not sold separately.
Figure 4.2 • Heater Assembly Components
(rear view of Direct Spark)
Cross-over
Bracket
High
Voltage
Wire
Low
Voltage
Wire
Circuit Board
(Housed inside
Junction Box)
Gas
Valve
Pilot or Electrode
Assembly
Figure 4.3 • Spark Electrode Side View
Side View
Side Frame
Electrode Bracket
Proper installation results
in 1/8” clearance from
face of ceramic
Ceramic
Tile
Rods
Set gap to 1/8” - 3/16”
(Direct Spark)Figure 4.4 • Pilot Assembly Side View
Electrode
Powerpile
(Millivolt)
Ceramic Tile
Pilot Burner
Pilot Orifice
Pilot Shield
22
IHR Series Manual
4.0 Maintenance • Parts Listing
Parts Listing
IMPORTANT: Contact factory for conversion assistance. Note: Gas type conversions require gas
valve and gas orifice among other changes Conversion may also require burner and crossover changes.
Chart 4.2 • Direct Spark Control Components
Part No.Description
78636Combination gas valve, natural gas25V
78637Combination gas valve, natural gas120V
78638Combination gas valve, propane gas25V
78639Combination gas valve, propane gas120V
78640Main burner electrode25V, 120V
78 64125V circuit board25V
78642Wiring harness for Mark 10DX-24 circuit board25V
78643120V circuit board120V
78644Wiring harness for Mark 10DX-117 circuit board120V
78645High voltage ignition wire25V, 120V
78646Low voltage ignition wire25V, 120V
Voltage
Chart 4.3 • Millivolt Control Components
Part No.Description
78647Combination gas valve, natural gas
78648Combination gas valve, propane gas
78649Pilot flame detector powerpile
78650Pilot burner
78651Pilot orifice, natural gas
78652Pilot orifice, propane gas
78653Pilot regulator, natural gas
78654Pilot regulator, propane gas
78655Millivolt Thermostat
7865635’ Thermostat Wire
Chart 4.4 • Miscellaneous Core Components
Part No.DescriptionPart No.Description
78657Manifold78675Electrode mounting bracket (Direct Spark)
78658Upper frame (*specify 1-5)78676Red Rubber Spark Boot (Direct Spark)
78659Heat shield (*specify 1-5)78677Low volt black wire grommet (Direct Spark)
78660Flash shield (*specify 1-5)78678High volt black wire heyco grommet (Direct Spark)
78661Reflector End (*specify 1-5)78679JB-0514 metal junction box (Direct Spark)
78662Full Reflector Assembly (*specify 1-5) 78680#8 x 1/2” common sheet metal screw
78663Side frame786811/4 - 20 x 1/2” machine screw (IHR Bolt)
78664Side frame insert786821/4 - 20 hex nut (mates to IHR bolt)
78665Embossed reflector sides786831/4 - 20 x 1/2” self-tap IHR bolt
78666Rayhead with center support786841/4 - 10 short electrode mounting screw
78667Rayhead no center support
(IHR30 LP models only)
78668Cross-over bracket78686Pilot access door with zip screw (Millivolt)
78669Long rayhead rod78687Pilot shield for F10-1 pilot burner (Millivolt)
78670Short rayhead rod78688Pilot line for IHR 30 (Millivolt)
78671Union fitting, 3-piece78689Pilot line (Millivolt)
78672Brass gas orifice (specify model #)78690Plastic junction box (Top)
786733/8” flex conduit (Direct Spark)78691Plastic Junction Box (Bottom)
786743/8” conduit attachment fitting
*Reference proper part number when ordering these parts: 1=IHR30; 2=IHR60; 3=IHR90; 4=IHR130, 5 =IHR160
(NFS-2/PFS-2)
78685#8 x 1/2” sheet metal self-tap screw
5.0 Limited Warranty
Seller warrants its products to be free from defects in material and
workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use
of materials substituted under emergency conditions for materials normally
employed. This warranty covers replacement of any parts furnished from
the factory of Seller, but does not cover labor of any kind and materials not
furnished by Seller, or any charges for any such labor or materials, whether
such labor, materials, or charges thereon are due to replacement of parts,
adjustments, repairs, or any other work done. This warranty does not
apply to any equipment which shall have been repaired or altered outside
the factory of Seller in any way so as, in the judgement of Seller, to affect its
stability, nor which has been subjected to misuse, negligence, or operating
conditions in excess of those for which such equipment was designed.
This warranty does not cover the effects of physical or chemical properties
of water or steam or other liquids or gases used in the equipment.
BUYER AGREES THAT SELLER’S WARRANTY OF ITS PRODUCTS
TO BE FREE FROM DEFECT IN MATERIAL AND WORKMANSHIP,
AS LIMITED HEREIN, SHALL BE IN LIEU OF AN EXCLUSIVE
OF ALL OTHER WARRANTIES, EITHER EXPRESS OR IMPLIED,
WHETHER ARISING FROM LAW, COURSE OF DEALING, USAGE OF
TRADE, OR OTHERWISE, THERE ARE NO OTHER WARRANTIES,
INCLUDING WARRANTY OF MERCHANTABILITY OR FITNESS FOR
PURPOSE, WHICH EXTEND BEYOND THE PRODUCT DESCRIPTION
CONFIRMED BY BUYER AND SELLER AS OF THE DATE OF FINAL
AGREEMENT.
This warranty is void if the input to the product exceeds the rated input
as indicated on the product serial plate by more than 5% on gas-fired
and oil-fired units, or if the product, in the judgement of the SELLER, has
been installed in a corrosive atmosphere, or subjected to corrosive fluids
or gases, been subjected to misuse, negligence, accident, excessive
thermal shock, excessive humidity, physical damage, impact, abrasion,
unauthorized alterations, or operation contrary to SELLER’S printed
instructions, or if the serial number has been altered, defaced, or removed.
BUYER AGREES THAT IN NO EVENT WILL SELLER BE LIABLE FOR
COSTS OF PROCESSING, LOST PROFITS, INJURY TO GOODWILL,
OR ANY OTHER CONSEQUENTIAL OR INCIDENTAL DAMAGES
OF ANY KIND RESULTING FROM THE ORDER OR USE OF ITS
PRODUCT, WHETHER ARISING FROM BREACH OF WARRANTY,
NONCONFORMITY TO ORDERED SPECIFICATIONS, DELAY IN
DELIVERY, OR ANY LOSS SUSTAINED BY THE BUYER.
BUYER’S REMEDY FOR BREATCH OR WARRANTY, EXCLUSIVE
OF ALL OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO
REPAIR OR REPLACEMENT AT THE FACTORY OF SELLER, ANY
COMPONENT WHICH SHALL, WITHIN THE APPLICABLE WARRANTY
PERIOD DEFINED HEREIN AND UPON PRIOR WRITTEN APPROVAL,
BE RETURNED TO SELLER WITH TRANSPORTATION CHARGES
PREPAID AND WHICH THE EXAMINATION OF SELLER DISCLOSE
TO HAVE BEEN DEFECTIVE; EXCEPT THAT WHEN THE PRODUCT IS
TO BE USED BY BUYER AS A COMPONENT PART OF EQUIPMENT
MANUFACTURED BY BUYER, BUYER’S REMEDY FOR BREACH, AS
LIMITED HEREIN, SHALL BE LIMITED TO ONE YEAR FROM DATE OF
SHIPMENT FROM SELLER, FOR GAS-FIRED PRODUCTS INSTALLED
IN HIGH HUMIDITY APPLICATIONS AND UTILIZING STAINLESS
STEEL HEAT EXCHANGERS, BUYER’S REMEDY FOR BREACH, AS
LIMITED HEREIN, SHALL BE LIMITED TO TEN YEARS FROM DATE OF
SHIPMENT FROM SELLER.
These warranties are issued only to the original owner-user and cannot
be transferred or assigned. No provision is made in these warranties for
any labor allowance or field labor participation. Seller will not honor any
expenses incurred in its behalf with regard to repairs to any of Seller’s
products. No credit shall be issued for any defective part returned without
proper written authorization (including, but not limited to, model number,
serial number, date of failure, etc.) and freight prepaid.
OPTIONAL SUPPLEMENTAL WARRANTY
Provided a supplemental warranty has been purchased, Seller extends
the warranty herein for an additional four (4) years on certain compressors.
Provided a supplemental warranty has been purchased, Seller extends
the warranty herein for an additional four (4) years or nine (9) years on
certain heat exchangers.
EXCLUSION OF CONSUMABLES & CONDITIONS BEYOND SELLER’S
CONTROL
This warranty shall not be applicable to any of the following items:
refrigerant, gas, belts, filters, fuses, and other items consumed or warn out
by normal wear and tear or conditions beyond Seller’s control, including
(without limitation as to generality) polluted or contaminated or foreign
matter contained in the air or water utilized for heat exchanger (condenser)
cooling or if the failure of the part is caused by improper air or water supply,
or improper or incorrect sizing of power supply.
Component
Applicable Models
Heat Exchangers
Gas-Fired Units
Heat Exchangers
Low Intensity Infrared Units
Compressors
Condensing Units for Cassettes
Burners
Low Intensity Infrared Units
Other
Components excluding Heat
Exchangers, Coils, Condensers,
Burners, Sheet Metal
Heat Exchangers/Coils
Indoor and Outdoor Duct Furnaces
and System Units, Steam/Hot
Water Units, Oil-Fired Units,
Electric Units, Cassettes, Vertical
Unit Ventilators, Geothermal Units
Compressors
Vertical Unit Ventilators,
Geothermal Units
Burners
High Intensity INfrared Units
Sheet Metal Parts
All Prodcuts
As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.
TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS FROM
DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE HUNDRED
TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST.
FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN SIXTY-SIX
MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST.
TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST.
ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN ONE
YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN EIGHTEEN
MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST.
“APPLICABLE WARRANTY PERIOD”
Modine Manufacturing Company
1500 DeKoven Avenue
Racine, WI 53403
Phone: 1.800.828.4328 (HEAT)
www.modinehvac.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.