Modine Manufacturing HD, HD30, HD45, HD60, HD75 Service Manual

INSTALLATION AND SERVICE MANUAL
WARNING
1. Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death, and could cause exposure to substances which have been determined by various state agencies to cause cancer, birth defects or other reproductive harm. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
2. Do not locate ANY gas-fired units in areas where chlorinated, halogenated, or acid vapors are present in the atmosphere. These substances can cause premature heat exchanger failure due to corrosion, which can cause property damage, serious injury, or death.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS:
1. Open windows.
2. Do not try to light any appliance.
3. Do not touch any electrical switch; do not use any phone in your building.
4. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you can not reach your gas supplier, call your fire department.
6-576.5
5H74925 Rev. E
October, 2005
gas-fired unit heaters
model HD
All models approved for use in California by the CEC, in New York city by the MEA division, and in Massachusetts. Unit heater is certified for residential and commercial applications.
FOR YOUR SAFETY
The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
IMPORTANT
The use of this manual is specifically intended for a qualified installation and service agency. All installation and service of these units must be performed by a qualified installation and service agency.
Inspection on Arrival
1. Inspect unit upon arrival. In case of damage, report it immediately to transportation company and your local Modine sales representative.
2.
Check rating plate on unit to verify that power supply meets available electric power at the point of installation.
3. Inspect unit upon arrival for conformance with description of product ordered (including specifications where applicable).
Table of Contents
Inspection on Arrival. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Special Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SI (Metric) Conversion Factors . . . . . . . . . . . . . . . . . . . . . . . . . 3
Unit Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Combustible Material and Service Clearances . . . . . . . . . 4
Unit Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Gas Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Service/Trouble Shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
THIS MANUAL IS THE PROPERTY OF THE OWNER.
SPECIAL PRECAUTIONS/TABLE OF CONTENTS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE, EFFICIENT AND TROUBLE-FREE OPERATION. IN ADDITION, PARTICULAR CARE MUST BE EXERCISED REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW. FAILURE TO PROPERLY ADDRESS THESE CRITICAL AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS, PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which, if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided, MAY result in a potential safety concern.
DANGER
Appliances must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
WARNING
1. Gas fired heating equipment must be vented - do not operate unvented.
2. A built-in power exhauster is provided - additional external power exhausters are not required or permitted.
3. If you are replacing an existing heater, it may be necessary to resize the venting systems. Improperly sized venting systems can result in vent gas leakage or the formation of condensate. Refer to the National Fuel Gas Code ANSI Z223.1 or CSA B149.1 latest edition. Failure to follow these instructions can result in injury or death.
4. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing.
5. Gas pressure to appliance controls must never exceed 14" W.C. (1/2 psi).
6. To reduce the opportunity for condensation, the minimum sea level input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input.
7. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
8. All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
9. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
10. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than the rated voltage.
11. When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacements parts list may be obtained by contacting the factory. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owners risk.
CAUTION
1. All literature shipped with this unit should be kept for future use for servicing or service diagnostics. Do not discard any literature shipped with this unit.
2. Consult piping, electrical, and venting instructions in this manual before final installation.
3. Do not attach ductwork, air filters, or polytubes to any propeller unit heater.
4. Clearances to combustible materials are critical. Be sure to follow all listed requirements.
5. Do not locate units in tightly sealed rooms or small compartments (commonly referred to as confined spaces) without provisions for adequate combustion air and venting. Combustion air must have access to the confined space through a minimum of two permanent openings in the enclosure, at least one near the bottom. They should provide a free area of one square inch per 1,000 BTU/Hr input rating of the unit with a minimum of 100 square inches for each opening, whichever is greater.
6. Low profile heaters are designed for use in heating. applica­ tions with ambient temperatures between -40°F and 90°F.
7. Do not install unit outdoors.
8. In garages or other sections of aircraft hangars such as offices and shops that communicate with areas used for servicing or storage, keep the bottom of the unit at least 7' above the floor unless the unit is properly guarded to provide user protection from moving parts. In parking garages, the unit must be installed in accordance with the standard for parking structures ANSI/NFPA 88A, and in repair garages the standard for repair garages NFPA #88B. In Canada, installation of heaters in airplane hangars must be in accordance with the requirements of the enforcing authority, and in public garages in accordance with the current CSA-B149 codes.
9. In aircraft hangars, keep the bottom of the unit at least 10' from the highest surface of the wings or engine enclosure of the highest aircraft housed in the hangars and in accordance with the requirements of the enforcing authority and/or NFPA 409-latest edition.
10. Installation of units in high humidity or salt water atmospheres will cause accelerated corrosion resulting in a reduction of the normal life of the units.
11. Do not install units below 7' measured from the bottom of the unit to the floor in commercial applications (unless unit is properly guarded to provide user protection from moving parts)and 5' measured from the bottom of the unit to the floor in residential applications.
12. Be sure no obstructions block air intake and discharge of unit heaters.
13. The minimum distance from combustible material is based on the combustible material surface not exceeding 160°F. Clearance from the top of the unit may be required to be greater then the minimum specified if heat damage, other than fire, may occur to materials above the unit heater at the temperature described.
14. Allow 18" of clearance at rear (or 6" beyond end of motor at rear of unit, whichever is greater) and access side to provide ample air for combustion and proper operation of fan.
15. Installation must conform with local building codes or in the absence of local codes, with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest edition. In Canada installation must be in accordance with CSA-B149.1.
16. Purging of air from gas supply line should be performed as described in ANSI Z223.1 - latest edition “National Fuel Gas Code”, or in Canada in CSA-B149 codes.
2
6-576.5
SPECIAL PRECAUTIONS / SI (METRIC) CONVERSION FACTORS / UNIT LOCATION
CAUTION
17. When leak testing the gas supply piping system, the appliance and its combination gas control must be isolated during any pressure testing in excess of 14" W.C. (1/2 psi).
18. The unit should be isolated from the gas supply piping system by closing its field installed manual shut-off valve. This manual shut-off valve should be located within 6' of the heater.
19. Turn off all gas before installing appliance.
20. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage.
21. Check the gas inlet pressure at the unit upstream of the combination gas control. The inlet pressure should be 6-7" W.C. on natural gas or 12-14" W.C. on propane. If inlet pressure is too high, install an additional pressure regulator upstream of the combination gas control.
22. Servicing or repairing of this equipment must be performed by a qualified service agency.
23. Do not attempt to reuse any mechanical or electronic igni­ tion controllers which has been wet. Replace defective controller.
IMPORTANT
1. To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acid) are present in the atmosphere.
2. To prevent premature heat exchanger failure, the input to the appliance as indicated on the serial plate, must not exceed the rated input by more then 5%.
3. To check most of the Possible Remedies in the trouble- shooting guide listed in Tables 17.1 and 18.1, refer to the applicable sections of the manual.
SI (METRIC) CONVERSION FACTORS
Table 3.1
To Convert Multiply By To Obtain
"W.C. 0.249 kPa °F (°F-32) x 5/9 °C Btu 1.06 kJ Btu/ft3 37.3 kJ/m Btu/hr 0.000293 kW CFH (ft3/hr) 0.000472 m3/min CFH (ft3/hr) 0.00000787 m3/s CFM (ft3/min) 0.0283 m3/min CFM (ft3/min) 0.000472 m3/s
To Convert Multiply By To Obtain
feet 0.305 m Gal/Hr. 0.00379 m3/hr Gal/Hr. 3.79 l/hr
3
gallons 3.79 l Horsepower 746 W inches 25.4 mm pound 0.454 kg psig 6.89 kPa psig 27.7 "W.C.
CAUTION
1. All literature shipped with this unit should be kept for future use for servicing or service diagnostics. Leave manual with the owner. Do not discard any literature shipped with this unit.
2. Consult piping, electrical, and venting instructions in this manual before final installation.
3. Do not attach ductwork, air filters, or polytubes to any propeller unit heater.
In the U.S., the installation of these units must comply with the “National Fuel Gas Code,” ANSI Z223.1, latest edition (also known as NFPA 54) and other applicable local building codes. In Canada, the installation of these units must comply with local plumbing or waste water codes and other applicable codes and with the current code CSA-B149.1.
1. All installation and service of these units must be performed by a qualified installation and service agency
only as defined in ANSI Z223.1, latest edition or in Canada by a licensed gas fitter.
2. This unit is certified with the controls furnished. For replacements parts, please order according to the replacement parts list on serial plate. Always know your model and serial numbers. The right is reserved to substitute other authorized controls as replacements.
3. Unit is balanced for correct performance. Do not alter fan or operate motors at reduced speed.
4. Information on controls is supplied separately.
5. The same burner is used for natural and propane gas.
UNIT LOCATION
DANGER
Appliances must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
CAUTION
1. Clearances to combustible materials are critical. Be sure to follow all listed requirements.
2. Do not locate units in tightly sealed rooms or small compartments (commonly referred to as confined spaces) without provisions for adequate combustion air and venting. Combustion air must have access to the confined space through a minimum of two permanent openings in the enclosure, at least one near the bottom. They should provide a free area of one square inch per 1,000 BTU/Hr input rating of the unit with a minimum of 100 square inches for each opening, whichever is greater.
3. Low profile heaters are designed for use in heating applica­ tions with ambient temperatures between -40°F and 90°F.
4. Do not install unit outdoors.
5. In garages or other sections of aircraft hangars such as offices and shops that communicate with areas used for servicing or storage, keep the bottom of the unit at least 7' above the floor unless the unit is properly guarded. In parking garages, the unit must be installed in accordance with the standard for parking structures ANSI/NFPA 88A, and in repair garages the standard for repair garages NFPA #88B. In Canada, installation of heaters in airplane hangars must be in accordance with the requirements of the enforcing authority, and in public garages in accordance with the current CSA-B149 codes.
6. In aircraft hangars, keep the bottom of the unit at least 10' from the highest surface of the wings or engine enclosure of the highest aircraft housed in the hangars and in accor- dance with the requirements of the enforcing authority and/or NFPA 409-latest edition.
7. Installation of units in high humidity or salt water atmospheres will cause accelerated corrosion resulting in a reduction of the normal life of the units.
IMPORTANT
To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acid) are present in the atmosphere.
Location Recommendations
1. When locating the heater, consider general space and heating requirements, availability of gas and electrical supply, and proximity to vent locations.
2. When locating units, it is important to consider that the exhaust
6-576.5
vent piping must be connected to the outside atmosphere.
33
UNIT LOCATION
3. Be sure the structural support at the unit location site is adequate to support the weight of the unit. For proper operation the unit must be installed in a level horizontal position.
4. Do not install units in locations where the flue products can be drawn into the adjacent building openings such as windows, fresh air intakes, etc.
5. Be sure that the minimum clearances to combustible materials and recommended service clearances are maintained. Units are designed for installation with the minimum clearances as shown in table 4.1.
Table 4.1 Clearances
Unit Side Clearance To Recommended Combustilble Materials Service Clearance
Top and Bottom 1" 1" Access Side 18" 18" Non-Access Side 1" 1" Rear 18" 18" Vent Connector 4" 4"
6. Do not install units in locations where gas ignition system is exposed to water spray, rain, or dripping water.
7. Mounting Height (measured from bottom of unit) at which unit heaters are installed is critical. Refer to mounting height information and heat throw data on page 16 of this manual. The maximum mounting height for any unit is that height above which the unit will not deliver heated air to the floor.
Combustion Air Requirements
The National Fuel Gas Code defines an “unconfined space” as a space whose volume is greater than 50 cubic feet per 1,000 Btu/Hr input of the installed appliance(s). A confined space is 50 cubic feet or less per 1,000 Btu/Hr input of the installed appliance(s).
It is not recommended to install these unit heaters into residential confined spaces. This recommendation is due to the concern that at some point in time, the combustion air openings provided by the installer may become blocked or eliminated by the owner, either intentionally or unintentionally. Despite this commendation, if these units are installed into a residential confined space, see National Fuel Gas Code ANSI Z223.1 or CSA B149.1 Installation Code, latest edition, for detailed combustion air provisions. These requirements must be adheard to.
Units installed into confined spaces in industrial/commercial installations, must be provided with two permanent openings, one near the top of the confined space and one near the bottom of the confined space. Each opening should have a free area of not less than one square inch per 1,000 Btu/Hr of the total input rating of all units in the confined space, freely communicating with interior areas having, in turn, adequate infiltration from the outside.
For further details on supplying combustion or to a confined (tightly sealed) space or unconfined space, see the National Fuel Gas Code ANSI Z223.1 or CSA B149.1 Installation Code, latest edition.
Turning The Unit 180°
All units are produced at the factory with left-side controls, when looking at the unit. If the installation requires that the controls be on the right side, the unit heater can be “turned over”. In addition, the following instructions must be followed:
• By turning the unit 180° from the way it was received from the factory, the sides become opposite but the front and back remain in the same relative position. The bottom panel now becomes the top panel and vice-versa.
• Remove the access panel, turn it 180°, and re-attach it to the unit. This is important so that all the information labels can be read.
• Remove the spring loaded deflector blades, turn them over, replace, and adjust so they are open and in a position to direct the heated air down to the floor.
4
Unit Mounting
CAUTION
1.
Do not install units below 7' measured from the bottom of the unit to the floor in commercial applications (unless unit is properly guarded to provide user protection from moving parts) and 5' measured from the bottom of the unit to the floor in residential applications.
2. Be sure no obstructions block air intake and discharge of unit heaters.
3. The minimum distance from combustible material is based on the combustible material surface not exceeding 160°F. Clearance from the top of the unit may be requited to be greater than the minimum specified if heat damage, other than fire, may occur to materials above the unit heater at the temperature described.
4. Allow 18" clearance at rear (or 6" beyond end of motor at rear of unit, whichever is greater) and access side to provide ample air for combustion and proper operation of fan.
1. Be sure the means of suspension is adequate to support the weight of the unit (see page 16 for unit weights).
2. For proper operation, the unit must be installed in a level horizontal position.
3. Clearances to combustibles as previously specified must be strictly maintained.
4. Mounting bracket installation: Before lifting the heater for suspension, the mounting brackets must be installed. Decide if the unit will be installed as standard; that is with left-side controls when looking at the front of the unit or with right-side controls.
For standard (left side)remove brackets from shipping
position and remove the (3) screws along the top edge of both the front and back of unit. Align screw holes on mounting bracket with holes along front and back top edges. Secure (1) mounting bracket to front of unit with retained screws. Secure the other mounting bracket to back of unit in a similar way.
For right-hand, the mounting brackets are attached in a
similar manner after the unit is turned over.
5a. Suspension by screws/lag bolts:
Secure the mounting brackets to the ceiling joists or truss, using 1/4" screws with 1/2" washers. These 1" - angle, mounting brackets are slotted to accommodate joists on 16" or 24" centerlines.
5b. Suspension by threaded rod: This heater can also be hung utilizing the same mounting brackets and threaded rod. Attach the threaded rod to the unit mounting brackets, securing with a top and bottom nut.
Next, drill holes into a steel channel or angle iron at the same centerline dimensions as those chosen for the heater that is being installed. The steel channels or angle iron pieces need to span and be fastened to appropriate structural members. Cut the threaded rods to the preferred length, push them through the holes in the steel channel or angle iron and secure with washers and lock nuts, lock washers and nuts, or a double nut arrangement like used on the unit heater mounting brackets.
5c. Shelf mounted units: The unit heater can also be installed on a shelf, if so desired. The mounting brackets will need to be attached to the heater the same manner as explained earlier, however, to mount on a shelf the brackets must go on the bottom of the heater. The brackets must be affixed to the shelf using similar screws (1/4" screw with 1/2" washer) as overhead joist or truss mounting. Be sure all clearance to combustible requirements are met.
6-576.5
INSTALLATION
Venting
WARNING
1. Gas fired heating equipment must be vented - do not operate unvented.
2. A built-in power exhauster is provided - additional external power exhausters are not required or permitted.
3. If you are replacing an existing heater, it may be necessary to resize the venting systems. Improperly sized venting systems can result in vent gas leakage or the formation of condensate. Refer to the National Fuel Gas Code ANSI Z223.1 or CSA B149.1 latest edition. Failure to follow these instructions can result in serious injury or death.
4. Under no circumstances should two sections of double wall vent pipe be joined together within one horizontal vent system due to the inability to verify complete seal of inner pipes.
CAUTION
Installation must conform with local building codes or in the absence of local codes, with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest edition. In Canada installation must be in accordance with CSA B149.1.
Before you start use the following steps to verify that the venting system is adequately sized:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code ANSI Z223.1 or CSA B149.1 Installation Code-latest edition and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
3. In so far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any exhaust fans such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so that the appliance will operate continuously.
5. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use.
6. If improper venting is observed during any of the above tests, the venting system must be corrected.
Table 5.1 ANSI Unit Heater Venting Requirements
Venting Category Description Requirements
I Negative vent pressure Follow standard
Non-condensing venting requirements. II Negative vent pressure Condensate must Condensing be drained. III Positive vent pressure Vent must be gas tight. Non-condensing IV Positive vent pressure Vent must be liquid and Condensing gastight. Condensate must be drained.
Note: A vent is the vertical passageway used to convey flue gases from the unit or the vent connector to the outside atmosphere. A vent connector is the pipe which connects the unit to a vent or chimney. Vent connectors serving Category I appliances shall not be connected into any portion of mechanical draft systems operating under positive pressure.
Venting Instructions
1. All vertically vented heaters are category I venting. All horizontally vented heaters are category I or III depending on venting. The pipe should be galvanized steel or other suitable corrosion resistant material (except for category III horizontal, refer to Additional Requirements for Horizontal Category III Venting section). Follow the National Fuel Gas Code for minimum thickness of vent material. The minimum thickness for connectors varies depending on the pipe diameter. Do not vent unit with PVC or other forms of plastic venting material.
2. Vertically vented (horizontal run does not exceed 75% of vertical rise and vent terminates no less than 5’ above the vent connector) units may be vented with single or double wall vent pipe. Horizontally vented units must use single wall vent pipe (category III residential may vary) although one continuous section of double wall vent pipe may be used with the vent system.
3. Using Table 5.1, determine the venting requirements for the category determined above. A category III heater must conform to the venting requirements called out in Table
5.1, which are detailed in the following sections, as well as additional requirements also detailed in following sections.
4. A minimum of 12" straight pipe is recommended from the flue outlet before turns in the vent pipe. For vertical venting, it is recommended to install a tee with drip leg and clean out cap to the flue outlet followed by a 90° elbow.
5. All heaters come with a factory installed 3” vent adapter for attaching the vent pipe to the heater. Attach the vent pipe to the adapter with 3 non-corrosive screws. (Drill pilot holes through the vent pipe and adapter prior to screwing in place)
6. Install the vent pipes with a minimum downward slope from the appliance of 1/4 inch per foot and suspend securely from overhead structures at no points greater than 3' apart. Fasten individual lengths of vent together with at least three corrosion resistant sheet metal screws.
7. Keep single wall vent pipe at least 6" from combustible materials. Follow the double wall manufacturer’s clearances to combustibles. The minimum distance from combustible materials is based on the combustible material surface not exceeding 160°F. Clearance from the vent pipe (or the top of the unit) may be required to be greater than 6" if heat damage other than fire (such as material distortion or discoloration) could result.
8. Avoid venting through unheated space when possible. When venting does pass through an unheated space or if the unit is installed in an environment that promotes condensation, insulate runs greater than 5' to minimize condensation. Inspect for leakage prior to insulating and use insulation that is noncombustible with a rating of not less than 350°F. Install a tee fitting at the low point of the vent system and provide a drip leg with a clean out cap as shown in Figures 6.2 and
6.3.
9. When the vent passes through a combustible INTERIOR wall or floor, a metal thimble 4" greater than the vent diameter is necessary. If there is 6' or more of vent pipe in the open space between the appliance and where the vent pipe passes through the wall or floor, the thimble need only be 2" greater than the diameter of the vent pipe. If a thimble is not used, all combustible material must be cut away to provide 6" of clearance. Where authorities have jurisdiction type B vent may be used for the last section of vent pipe to maintain clearance to combustibles while passing through wall or floor. See Figure 6.1. Any material used to close the opening must be noncombustible.
6-576.5
55
INSTALLATION
10. Do NOT use dampers or other devices in the vent or combustion air pipes.
11. Precautions must be taken to prevent degradation of building materials by flue products.
12. Single wall vent pipe must not pass through any unoccupied attic, inside wall, concealed space, or floor.
13. All vertically vented heaters that are category I must be connected to a factory built chimney or vent complying with a recognized standard, or a masonry (or concrete) lined chimney with a material acceptable to the authority having jurisdiction. Venting into an unlined masonry chimney is not permitted. Refer to the National Fuel Gas Code for common venting.
14. The outlet of the vent should extend as shown in Figure
6.3 and Table 6.1 if the following conditions are met: Vent diameter is less than 12", vent is of double wall construction and is a listed product, and the vent does not terminate within 8’ of a vertical wall or similar obstruction. For vents that have a diameter of 12" or larger, constructed of single wall, or terminate within 8' of a vertical wall or similar obstruction, the vent pipe shall extend at least 2' higher than any portion of a building within a horizontal distance of 10’ (refer to Figure
6.2).
15. The vent system exhaust shall terminate at least 3’ above any forced air inlet located within 10’, and at least 4’ below, 4’ horizontally from, or 1’ above any door, window, or gravity air inlet into any building and 2’ from wall or adjoining building. The bottom of the vent terminal shall be located above the snow line or at least 1’ above grade; whichever is greater. When located adjacent to public walkways the vent system shall terminate not less than 7’ above grade.
16. A minimum of 4’ horizontal terminal clearance (6’ for Canada) from gas and electric meters, regulators, and relief equipment is required. The vent terminal shall not terminate closer than 2’ to adjacent buildings.
17. Use an approved vent terminal to reduce down drafts and moisture in the vent.
Figure 6.1 Venting Through Combustible Wall or Roof
Single Wall Vent Pipe
Listed Terminal
Double Wall Vent Pipe
Listed Terminal
Table 6.1 Minimum Height from Roof to Lowest Discharge Opening
Rise Roof Pitch Min Height X (in) H (ft) 0-6 Flat to 6/12 1.00 6-7 6/12 to 7/12 1.25 7-8 7/12 to 8/12 1.50 8-9 8/12 to 9/12 2.00 9-10 9/12 to 10/12 2.50 10-11 10/12 to 11/12 3.25 11-12 11/12 to 12/12 4.00 12-14 12/12 to 14/12 5.00 14-16 14/12 to 16/12 6.00 16-18 16/12 to 18/12 7.00 18-20 18/12 to 20/12 7.50 20-21 20/12 to 21/12 8.00
Size according to expected snow depth.
Figure 6.2 Vertical Venting Through Flat Roof
8' Min
Listed Terminal
2' Min
5' Min
4" Min
Downward
Drip Leg
Slope 1/4" towards drip leg.
12" Min
Figure 6.3 Vertical Venting Through Sloped Roof
Flashing
Clearance Specified by Type B Vent Mfg.
Double Wall
Single Wall
Listed Thimble
Single Wall
Single Wall Vent Pipe Terminating with Double wall vent pipe.
Clearance Specified by Type B Vent Mfg.
Single Wall Vent Pipe
Listed Thimble
Flashing
See Instructions for attaching single wall pipe to double wall pipe (page 6)
6
Specified
Terminal
Specified
Terminal
Drip Leg
6-576.5
Listed Terminal
Downward Slope 1/4" towards drip leg.
4" Min
12" Min
X
H
12
Roof Pitch is
x/12
INSTALLATION
General Instructions For Double Wall (Type B) Terminal Pipe Installation:
1. How to attach a single wall vent terminal to double wall (type B) vent pipe:
A. Look for the “flow” arrow on the vent pipe. Attach the vent terminal to the exhaust end of the double wall vent pipe.
B. Slide the vent terminal inside the pipe. C. Drill a hole through the pipe and the vent terminal.
Using 3/4" long sheet metal screws, attach the cap to the pipe.
2. How to connect a single wall vent system to a double wall (type B) vent pipe:
Figure 7.1 Horizontal Category III Venting with Upward Pitch
Specified Terminal
11"
6" Above snow grade
Listed Thimble
1
/4" Slope up towards termination
Clean out / drip leg
Figure 7.2 Horizontal Category III Venting with Downward Pitch (with drip leg)
Specified Terminal
11"
Listed Thimble
1
/4" Slope down towards termination
3' Min
Figure 7.3 Horizontal Category III Venting with Downward Pitch (Condensate Drips Out End)
Specified Terminal
11"
Listed Thimble
1
/
4
" Slope down towards termination
3' Min
A. Slide the single wall pipe inside the inner wall of the double wall pipe.
B. Drill a hole through both walls of the double wall pipe and through the single wall pipe. Using 3/4" sheet metal screws, attach the two pieces of pipe. Do not over tighten.
C. Repeat Step B drilling and inserting (2) additional screws, attach the two pieces of pipe. Do not over tighten.
D. To seal the annular opening, run a large bead of 350°F silastic. The “GAP” between the single and double wall pipe must be sealed but it is not
necessary to fill the full volume of the annular area.
Additional Requirements For Horizontal Category III Venting:
1. All heaters that are horizontally vented with 3" vent pipe, perform as category III appliance. Category III venting has special venting requirements as follows:
A. All residential, horizontally vented category III heaters
must be vented with an agency certified category III venting system. Agency certified category III venting systems are available from your local vent pipe distributor. Follow the agency certified category III vent manufacturers instructions for installations.
B. For commercial and industrial horizontally vented
heaters you may use either agency certified category III venting systems or single wall galvanized or stainless steel vent pipe. If uncertified single wall vent pipe is used, all seams and joints must be sealed with metallic tape or silastic suitable for temperatures up to 400°F. Wrap the tape two full turns around the vent pipe.
2. Limit the total equivalent vent pipe length to a minimum of 3' and a maximum of 30', making the vent system as straight as possible. see Figure 7.1-7.3. (The equivalent length of a 3" elbow is 1').
3. All horizontal category III vents must be terminated with a Gary Steel 1092 or Breidert Type L style vent cap. The vent cap must be 11" from side of wall. Refer to Figures 7.1-7.3.
4. When condensation may be a problem, the vent system shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief openings, or other equipment.
5. The venting system must be exclusive to a single unit, and no other unit is allowed to be vented into it.
6. When vented horizontally, maintain a 1/4" per foot rise away from the heater. Place a drain tee and clean out near the unit. See Figure 7.1. Where local authorities have jurisdiction, a 1/4" per foot downward slope is acceptable. Use a drain tee with a clean out near the exit of the vent, see Figure 7.2, or allow the condensate to drip out the end. See Figure 7.3.
7. For a vent termination located under an eave, the distance of the overhang must not exceed 24". The clearance to combustibles of the exterior vent must be maintained at a minimum of 11". Consult the National Fuel Gas Code for additional requirements for eaves that have ventilation openings.
Additional Requirements For Horizontal Category I Venting (Residential Only).
1. All heaters installed with category I horizontal vents
must be equipped with a vent transition (3" to 4" or 5" depending on vent size selected) attached to the power exhaust adapter located on the unit. All other portions of the vent system shall consist of 4 or 5-inch diameter single wall vent pipe and fittings depending on vent size selected. All seams and joints of the venting system
6-576.5
77
INSTALLATION
Vent transition
Clean out/Drip leg
Listed thimble
Ve
nt tee
1/4" Slope up towards termination
Exterior wall
12" Min
Maximum vent length (B)
must be sealed with metallic tape or silastic suitable for temperatures up to 400°F. Wrap tape two full turns around the vent pipe joint. One continuous section of double wall vent pipe may be used with the vent system.
2. The maximum length of the horizontal run of the vent shall be limited to the length listed in Table 8.1. The vent terminal for a horizontal category I vent may be either a standard vent TEE, a Gary Steel 1092 or a Breidert Type L style cap. The maximum number of elbows, slope of the horizontal section, and minimum vertical rise from horizontal vent pipe for each configuration is listed in Table 8.1.
A. When using a standard vent TEE, the preferred
orientation of the TEE is for the open ends of the TEE to be oriented horizontally. In this orientation, the minimum clearance to combustibles is 6" above the TEE to the eave. If the TEE is oriented vertically, the minimum clearance to combustibles is 27" above the TEE to the eave. Refer to Figure 9.1. The vent TEE should incorporate a bird screen made from corrosion resistant material. The individual strands of mesh in the bird screen must be located at least 1/4" apart.
B. When using a vent cap, the minimum clearance to
combustibles is 6" above the cap to the eave. Refer to Figure 9.1.
4. When vented horizontally, maintain a 1/4" per foot rise away from the heater. Place a drain tee and clean out near the vent connector. See Figures 8.1 and 9.3. Where local authorities have jurisdiction, a 1/4" per foot downward slope is acceptable. The Condensate is allowed to drip out of the end when using a TEE terminal. See Figure 9.2. When using a vent cap with an extension, a 3/8" diameter hole is drilled in the low point of the vent by the installer exterior to the space to allow condensation drainage. See Figure 9.4.
Figure 8.1 Horizontal Category I Venting -TEE With Upward Pitch
Table 8.1 Allowable Vent Configurations for Category I Horizontal Venting
Model Vent Maximum No. Minimum Vertical Maximum Vent Size Terminal Elbows Rise From Horizontal Vent Diameter (in) Horizontal (in) Length (ft) (A) (B)
30 Vent TEE 1 0 10 5
Vent Cap 2 4 10 5
Vent TEE 1 0 5 4
Vent Cap 2 12 5 4
Vent Cap 2 18 10 4
45 Vent TEE 1 0 10 5
Vent Cap 2 12 10 5
Vent Cap 2 18 5 4
60 Vent TEE 1 0 10 5
Vent Cap 2 15 10 5
75 Vent TEE 1 0 5 5
Vent Cap 2 18 5 5
One of the two allowed elbows is required to create the vent extension shown in figures 9.3 and 9.4.
The vertical rise gained from an elbow is 4
pipe needed in the vent extension. If the minimum vertical rise required is 4" you do not need to add a section of vertical pipe to the vent extension.
"
. Therefore, 4" may be subtracted from the length of vertical
8
6-576.5
3/8" Condensate
drain hole
Listed thimble
Listed thimble
Listed thimble
Minimum vertical rise from horizontal vent
(A)
6" Min
24" Max
12" Min
24" Max
27" Min
12" Min
12" Min
6" Min
24" Max
Vent extension configuration
Ve
rtical vent tee configuration
Horizontal vent tee configuration
Vent Tee
Vent Tee
Specified Terminal (See No. 3 page 8)
Vent transition
Exterior wall
1/4" Slope down towards termination
Listed thimble
Vent tee
Maximum vent length (B)
12" Min
Vent transition
Clean out/Drip leg
Listed thimble
1/4" Slope up towards termination
Exterior wall
12" Min
Maximum vent length (B)
Minimum vertical rise from horizontal vent
(A)
Specified Terminal
(see No. 3 page 8)
Vent transition
Listed thimble
1/4" Slope down
towards termination
Exterior wall
3/8" Condensate drain hole
Minimum vertical rise from horizontal vent
(A)
12" Min
Maximum vent length (B)
Specified Terminal
(see N. 3 page 8)
INSTALLATION
Figure 9.1 Horizontal Category I Venting - Clearance to Eave
Figure 9.2 Horizontal Category I Venting ­TEE With Downward Pitch
Figure 9.3 Horizontal Category I Venting ­Vent Extension With Upward Pitch
Figure 9.4 Horizontal Category I Venting ­Vent Extension With Downward Pitch
6-576.5
99
UNIT LOCATION
Additional Requirements for Common Venting:
1. The common vent system and all attached appliances must be category I.
2. The vent connector should be routed in the most direct route from the units to the common vent.
3. Where two or more vent connectors enter a common gas vent or chimney flue, the smaller connector shall enter at the highest level consistent with the available head room or clearance to combustible material.
Table 10.1 - Maximum Vent Connector Horizontal Run (ft) Type B Vent connector and Type B Common Vent
Model
HD30
HD45
HD60
HD75
Based on NFPA Tables 13.6, 13.1 & section 13.2.3
Connector
Dia.
3 6 8 10 10 11 12 4 4 4 4 5 5 6 5 NA NA NA NA NA NA 3 NA NA NA 4.5 9 13.5 4 6 8 10 10 14 15 5 NA NA NA NA NA NA 3 NA NA NA NA NA 4.5 4 6 8 10 15 20 23 5 6 8 10 14 15 17 4 NA NA 10 15 20 30 5 6 8 10 15 20 24
6 ft. 8 ft. 10 ft. 15 ft. 20 ft. 30 ft.
Vent Height
4. Restrictions within the common vent such as elbows should be minimized. Each elbow installed within the common portion of the venting system reduces maximum common vent capacity by 10% (refer to tables 10.2 and 10.4 for capacity)
5. The vent connector capacities included in these tables allow for the use of two 90 degree elbows (or turns). For each additional elbow, the vent connector capacity shall be reduced by 10%. Refer to NFPA54/ IFEC tables for capacity ratings.
6. The common vent cross sectional area must be equal to or greater than the largest vent connector cross-sectional area.
7. If all appliances are located on one level of the building, the vent height shall be measured from the highest draft hood or vent connector to be installed within the common vent system (Refer to figures 11.1 and 11.2).
8. All units must be vented in strict accordance of the common venting tables 10.1, 10.2, 10.3, and 10.4.
9. All masonry chimneys must comply with all applicable local and national codes.
10. When combining multiple vent connectors into a manifold prior to the vertical portion of the common vent, the size of the common vent manifold and the common vent shall be determined by applying a 10% reduction (.90 x maximum vent capacity from table 10.2 or 10.4) to the common vent capacity part of the common vent tables (refer to figure
11.3). The length of the common vent manifold (Lm) may not exceed 18 inches per inch of manifold diameter.
11. Refer to the national fuel gas code for instructions on multi­level common venting and exterior masonry chimneys as well as additional installation of the listed applications.
Table 10.2 - Maximum total appliance input Capacities (MBh) Type B Vent connector and Type B Common Vent
Vent
Height
6 92 81 140 116 204 161 309 248 8 101 90 155 129 224 178 339 275 10 110 97 169 141 243 194 367 299 15 125 112 195 164 283 228 427 352 20 136 123 215 183 314 255 475 394 30 152 138 244 210 361 297 547 459
Based on NFPA Table 13.6.
4 in2 5 in2 6 in2 7 in
(ft)
Fan+ Fan Fan+ Nat Fan+ Fan Fan+ Nat Fan+ Fan Fan+ Nat Fan+ Fan Fan+ Nat
Table 10.3 - Maximum Connector Horizontal Run (ft) Type B Vent connector with common vent into Masonry Chimney
Model
HD30
HD45
HD60
HD75
Based on NFPA table 13.8 & 13.2.2 “Vent Connector Maximum Length” in section 13.2
Connector
Dia. (in)
3 4.5 4.5 4.5 4.5 4.5 4.5 4 NA NA NA NA NA NA 5 NA NA NA NA NA NA 3 4.5 4.5 4.5 4.5 4.5 4.5 4 6 6 6 6 6 6 5 NA NA NA NA NA NA 3 NA NA NA NA NA NA 4 6 6 6 6 6 6 5 7.5 7.5 7.5 7.5 7.5 7.5 4 NA 6 6 6 6 6
5 7.5 7.5 7.5 7.5 7.5 7.5
6 ft. 8 ft. 10 ft. 15 ft. 20 ft. 30 ft.
Vent Height
Area of Common Vent
Table 10.4 - Maximum total appliance input Capacities (MBh) Type B Vent connector with common vent into Masonry Chimney
Vent
Height
6 NA 74 NA 119 NA 178 NA 257 8 NA 80 NA 130 NA 193 NA 279 10 NA 84 NA 138 NA 207 NA 299 15 NA NA NA 152 NA 233 NA 334 20 NA NA NA NA NA 250 NA 368 30 NA NA NA NA NA 270 NA 404
Based on NFPA Table 13.8
12 in
(ft.)
Fan+
Fan
2
Fan+
Nat
2
Area of Common Vent
2
19 in
Fan+
Nat
Fan+
Fan
Fan+
Fan
28 in
2
Fan+
Nat
38 in
Fan+
Fan
2
Fan+
Nat
10
6-576.5
Figure 11.1
USE THIMBLE THROUGH CELLING
TEE WITH DRIP LEG AND CLEANOUT CAP RECOMENDED
LISTED TERMINAL
DOWNWARD SLOPE VENT 1/4" TOWARDS DRIP LEG.
USE LISTED THIMBLE
FLASHING
CATEGORY I APPLIANCE
TYPE B DOUBLE WALL VENT CONNECTOR
TYPE B DOUBLE WALL COMMON VENT
12" MIN. REC.
3' MAX
VENT HEIGHT
DOWNWARD SLOPE VENT 1/4" TOWARDS CHIMNEY
FLASHING
CATEGORY I APPLIANCE
TYPE B DOUBLE WALL VENT CONNECTOR
MASONRY CHIMNEY (COMMON VENT)
3' MAX
USE THIMBLE THROUGH CELLING
TEE WITH DRIP LEG AND CLEANOUT CAP RECOMENDED
DOWNWARD SLOPE VENT 1/4" TOWARDS DRIP LEG.
HOT DAWG UNIT HEATER
HIDDEN VENT
CATEGORY I
APPLIANCE
CATEGORY I APPLIANCE
Lm
Common venting into double wall B vent
Figure 11.2 Common venting into masonry chimney
Figure 11.3 Common venting into manifold
6-576.5
11
GAS
SUPPLY LINE
GAS
SUPPLY LINE
GROUND
JOINT
UNION
MANUAL
SHUT-OFF
VALVE
3"
MIN.
SEDIMENT
TRAP
PLUGGED
1/8" NPT TEST
GAGE CONNECTION
TO
CONTROLS
INSTALLATION
Gas Connections
WARNING
1. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equilavent for testing.
2. Gas pressure to appliance controls must never exceed 14" W.C. (1/2 psi).
3. To reduce the opportunity for condensation, the minimum sea level input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or 5% below the minimum rated input of duel rated units.
CAUTION
1. Purging of air from gas lines should be performed as described in ANSI Z223.1 - latest edition “National Fuel Gas Code”, or in Canada CSA-B149 codes.
2. When leak testing the gas supply piping system, the appliance and its combination gas control must be isolated during any pressure testing in excess of 14" W.C. (1/2 psi).
3. The unit should be isolated from the gas supply piping system by closing its field installed manual shut-off valve.This manual shut-off valve should be located within 6' of the heater.
4. Turn off all gas before installing appliance.
and size of unit to be installed. Using this CFH value and the length of pipe necessary, determine the pipe diameter from Table 12.1. Where several units are served by the same main, the total capacity, CFH and length of main must be considered. Avoid pipe sizes smaller than 1/2". Table
12.1 allows for a 0.3" W.C. pressure drop in the supply
pressure from the building main to the unit. The inlet pressure to the unit must be 6-7" W.C. for natural gas and 11-14" W.C. for propane gas. When sizing the inlet gas pipe diameter, make sure that the unit supply pressure can be met after the 0.3" W.C. has been subtracted. If the 0.3" W.C. pressure drop is too high, refer to the Gas Engineer’s Handbook for other gas pipe capacities.
3. Install a ground joint union with brass seat and a manual
shut-off valve adjacent to the unit for emergency shut-off and easy servicing of controls, including a 1/8" NPT plugged tapping accessible for test gauge connection (See Figure 12.1).
4. Provide a sediment trap before each unit in the line where
low spots cannot be avoided. (See Figure 12.1).
5. When Pressure/Leak testing, pressures above 14" W.C.
(1/2 psi), close the field installed shut-off valve, disconnect the appliance and its combination gas control from the gas supply line, and plug the supply line before testing. When testing pressures 14" W.C. (1/2 psi) or below, close the manual shut-off valve on the appliance before testing.
Figure 12.1 Recommended Sediment Trap/Manual Shut-off Valve Installation - Side or Bottom Gas Connection
IMPORTANT
To prevent premature heat exchanger failure, the input to the appliance, as indicated on the serial plate, must not exceed the rated input by more than 5%.
1. Installation of piping must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest Edition. In Canada, installation must be in accordance with CSA-B149.1.
2. Piping to units should conform with local and national requirements for type and volume of gas handled, and pressure drop allowed in the line.Refer to Table 13.1 to determine the cubic feet per hour (CFH) for the type of gas
Table 12.1 Gas Pipe Capacities
Gas Pipe Capacities (Up to 14" W.C. Gas Pressure through Schedule 40 Pipe)
Cubic Feet per Hour with Pressure Drop of 0.3" W.C.
Natural Gas - Specific Gravity - 0.60
Propane Gas - Specific Gravity - 1.50
Length
of Pipe
(feet) Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane
10 132 83 278 175 520 328 1050 662 1600 1008 3050 1922
20 92 58 190 120 350 221 730 460 1100 693 2100 1323
30 73 46 152 96 285 180 590 372 890 561 1650 1040
40 63 40 130 82 245 154 500 315 760 479 1450 914
50 56 35 115 82 215 135 440 277 670 422 1270 800
60 50 32 105 66 195 123 400 252 610 384 1150 725
70 46 29 96 60 180 113 370 233 560 353 1050 662
80 43 27 90 57 170 107 350 221 530 334 930 586
100 38 24 79 50 150 95 305 192 460 290 870 548
125 34 21 72 45 130 82 275 173 410 258 780 491
150 31 20 64 40 120 76 250 158 380 239 710 447
12
1/2" 3/4" 1" 1-1/4" 1-1/2" 2"
Manual shut-off valve is in the “OFF” position when handle is perpendicular to pipe.
Pipe Diameter
6-576.5
INSTALLATION
Table 13.1 Manifold Pressure & Gas Consumption
Natural Propane
Model BTU/Cu. Ft. 1050 2500 No. of Size Specific Gravity 0.60 1.53 Orifices
Manifold Pressure In. W.C. 3.5 10.0
CFH 28.6 12.0 2 Gal/Hr. Propane .33
30
Sec/cu. ft. 126 300 Orifice Drill Size 49 56
CFH 42.9 18.0 3 Gal/Hr. Propane .50
45
Sec/cu. ft. 84 200 Orifice Drill Size 49 56
CFH 57.1 24.0 4 Gal/Hr. Propane .66
60
Sec/cu. ft. 63 150 Orifice Drill Size 49 56
CFH 71.4 30.0 5 Gal/Hr. Propane .83
75
Sec/cu. ft. 50 180 Orifice Drill Size 49 56
Wiring
WARNING
1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
3. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than rated voltage.
OPERATION
CAUTION
Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage.
All field installed wiring must be done in accordance with the National Electrical Code ANSI/NFPA 70 – latest edition or Canadian Electrical Code CSA C22.1 Part 1 or local codes. Unit must be electrically grounded according to these codes. If any of the original wire supplied with the heater must be replaced, replace it with wiring material having a temperature rating of at least 105°C.
The power to these unit heaters should be protected with a circuit breaker.
Location of thermostat should be determined by heating requirements and be mounted on an inside wall about 5' above floor level where it will not be affected by heat from the unit or other sources, or drafts from frequently opened doors. See instructions packed with thermostat.
Prior to Operation
Although this unit has been assembled and fire-tested at the factory, the following pre-operational procedures should be performed to assure proper on-site operation.
1. Turn off power.
2. Check fan clearance. Fan should not contact casing when spun by hand.
3. Check all electrical connections to be sure they are secure.
4. If you are not familiar with the unit’s controls (i.e. combination gas control), refer to the control manufacturer’s literature supplied with the unit.
5. Check that all horizontal deflector blades are open a minimum of 30° as measured from vertical.
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: If you do not follow these instructions exactly, a fire
or explosion may result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is equipped with an
ignition device which automatically lights the burner. Do not try to light the burner by hand.
B. BEFORE OPERATING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbors phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to move the gas control switch. Never
use tools. If the switch will not move by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the appliance and to replace any part to the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.
5. Remove the access panel.
6. Move the gas control switch to the “OFF” position.
7. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! follow “B” in the safety information above. If you don’t smell gas, go to the next step.
8. Move the gas control switch to the “ON” position.
9. Replace control access panel.
10. Turn on all electric power to the appliance.
11. Set the thermostat to the desired setting.
12. If the appliance will not operate, follow the instructions “To Turn Off Gas to Appliance” and call your service technician or gas supplier.
6-576.5
13
UNIT COMPONENTS
TO TURN OFF GAS TO APPLIANCE
1. Set thermostat to lowest setting.
2 Turn manual shut-off valve located outside of the unit to the
closed position.
3. Turn off all electric power to the appliance if service is to be performed.
4. Remove access panel.
5. Turn the gas valve switch to the “OFF” position.
6. Replace the access panel.
Figure 14.1 Major Gas, Electrical Service, Safety and Other Components
14
15
13
12
11
1. Wiring Diagram
2. Power Exhauster
3. LED Dignostic Codes
4. Pressure Switch
5. Terminal Board
For Hot Surface Ignition
Upon a call for heat from the thermostat, power is supplied to the power exhauster motor. The unit will go through a purge period and then the hot surface igniter will be energized. After the igniter has warmed up, the main valve in the combination control valve will open to allow gas to flow to the burners. If the
6. Control Transformer
7. Serial Plate (hidden)
8. Flame Sensor (hidden)
9. Flame Rollout Switch
10. Limit Control (hidden)
fan motor has not already started it will start shortly. If a flame is not sensed for any reason the main valve will close and there will be a short purge period before ignition is tried again. If the flame is not sensed after four tries there will be at least a one hour wait before ignition is tried again.
11. Hot Surface Igniter (hidden)
12. Gas Orifices
13. Mounting Brackets
14. Combination Gas Control
15. Common Replacement Parts (hidden)
14
6-576.5
UNIT COMPONENTS
Figure 15.1 Unit Heater Rear View
Fingerproof Fanguard
Fan Motor
Mounting Brackets
Electrical Access
Holes
Vent Pipe Connection
Gas Pipe Hole
(Gas Pipe Field Supplied)
Access Panel with
Lighting
Figure 15.2 Unit Heater in Standard Mounting Configuration (from factory this orientation - brackets not attached)
Figure 15.3 Unit Heater Turned 180° (Access Panel and Heated Air Outlet Change Sides)
/ Operating
Instructions
6-576.5
1515
DIMENSIONS / GENERAL PERFORMANCE DATA
(FPM)
16
6-576.5
SERVICE / MAINTENANCE / TROUBLESHOOTING
WARNING
When servicing or repairing of this equipment, use only factory-approved service replacement parts. A complete replacement parts list may be obtained by contacting the factory. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner’s risk.
CAUTION
1. Servicing or repairing of this equipment must be performed by a qualified service agency.
2. Do not attempt to reuse any mechanical or electrical controllers which have been wet. Replace defective controller.
IMPORTANT
To check most of the Possible Remedies in the troubleshooting guide listed in Tables 17.1 and 18.1, refer to the applicable sections of the manual.
General Maintenance
The unit and venting system must be checked once a year by a qualified service technician.
Only people trained and familiar with the operation of unit heaters and their controls should service this equipment. Before any service, BE SURE TO TURN OFF GAS AT THE MANUAL SHUT-OFF VALVE AHEAD OF THE COMBINATION GAS CONTROL AND TURN OFF ALL ELECTRIC POWER TO THE HEATER.
Table 17.1 Troubleshooting
TROUBLE POSSIBLE CAUSE POSSIBLE REMEDY
Unit does nothing. 1. Power supply is off 1. Turn on main power.
2. No 24V power to thermostat 2 a. Check control transformer b. If failed transformer - check thermostat wire gage and length
3. Thermostat malfunction 3 a. Verify wire connections to R&W terminals only b. Check / replace thermostat
4. LED flashes bright / dim 4. Check LED code at gas valve thermostat and connection
5. Defective control 5. Replace control
LED light off or flashing. 1. Light off - no power 1. Check main power
2. Two flashes - pressure switch closed. 2 a. Check for blocked or improper venting. b. Check vent motor hose / connection replace or reconnect c. Check pressure switch. d. Check power exhauster motor.
3. Three flashes - pressure switch open. 3 a. Check to insure control switch in "ON" position b. Check for incorrect or blocked venting c. Check pressure switch
4. Four flashes - limit or flame rollout switch 4 a. Check limit and flame controls and connections b. If flame rollout switch OK, but tripped:
1. Main gas pressure too high
2. Manifold orifice incorrect - too large
3. Incorrect unit clearance to surrounding wall/ceiling
4. Check for negative pressure in building
5. Incorrect or blocked venting
6. Access panel vent louvers wrong direction - reverse panel.
7. Area around main gas orifices blocked with debris
8. Unit louvers closed.
9. Heat exchanger tube(s) blocked with debris
5. Five flashes - Flame signal sensed 5. Flame at main burners out of sequence.
6. Six flashes - System lockout 6 a. Gas supply off or too low. b. Damaged or broken Ignitor. c. No line voltage. d. Unit not properly grounded. e. Check flame sense rod.
1. Service air moving components annually. a. Check fan for fit on motor shaft and for damage to blades.
2. Keep unit free from dust, dirt, grease, and foreign matter, paying particular attention to:
a. Combustion air inlets. b. Burners and burner orifices. Turn off gas ahead of the
combination gas control and shut off electric power to the heater. Remove the access panel, open the union on the gas line, and disconnect the igniter and sensor wires. Remove the screws that attach the burner tray to the header plate and remove the burner tray and manifold assembly from the heater. Carefully clean the burners
with a wire brush or other suitable means. Replace any damaged or deteriorating burners or orifices. Install the burner assembly back on to the header making certain that all screws, pipes and electrical connections are tight.
CAUTION: Be careful when handling the igniter.
1. Inspect the flame sensor and igniter for deterioration and/or cracks.
2. Verify that the burners are touching each other at the carryover points. This will ensure flame carryover from burner to burner.
c. Clean exterior of heat exchanger tubes. d. Fan blade.
3. Check wiring for possible loose connections.
4. Controls – The gas valves and piping should be checked annually for general cleanlimess and tightness. The gas controls should be checked to insure that the unit is operating properly. See control instruction sheets furnished separately with the unit heater.
5. Power exhaust assembly/motors – The power exhaust motor bearings have been lubricated for long life and do not require additional lubrication. In dirty atmosphere, it may be desirable to clean the motors and blower housing and blow out the cooling air passages of the motor with compressed air.
6. Perform periodic cleaning of inlet and vent terminal screens.
6-576.5
17
17
UNIT WIRING
C2-4 C1-2 C1-3C1-3 C1-1 C1-5
C2-1
C3-2 C3-1 C3-4
C2-3
C3-3
4
3
2
1
123 4
1
2
3
4
5
6
7
8
1 2 3
4 5 6
P5-4
P5-1
C1-5
C1-6
C1-4
C1-7
P5-6
P5-2
P5-3
P5-5
C1-8
TD1
Relay
24 VAC
TR2
TR1
BK
G
COM
G2
XFMR L2
XFMR L1
W
BK
BK
Terminal Block (HDS ONLY)
O
BL
R
R
Y
BK
W
BK
W
BK
W
BK
BK
BK
W
W
BK
R
BK
BK
W
RR
R
R
YYP
G
GND
GND
GND
GND
24V
120V
COM
C3
C2
ON
OFF
W
R
W
R
P5
C1
5H79409B1 REV B
from Lockout, Single-Phase.
Single-Stage, Hot Surface Ignition, 100% Shut-Off, Multiple Retry with Auto Reset
unit polarity.
Verify the power source and the
Use 105°C wire for replacements.
For deviations contact the factory.
in injury to the installer or user.
Combination Gas Control
Hot Surface
Igniter
Power
Exhaust
Motor
Flame
Sensor
Pressure
Switch
COM
R
HH
L2
L1
R
GR(G)
Y
Y
Y
R
BK BK
W
W
BK
XFMR
Press Switch
Fan Motor
Flame Rollout Switch
Limit Control
Flame Sensor
BL
W
BK
W
BK
P
Plug
BK
Hot Surface Igniter
O
R
R
W
Plug
Power Exhaust Motor
W
BK
Honeywell Combination Gas Control
R
R
24V
115V
Xfmr
L2
L1
Low Volt Therm (By Others)
Wiring Legend
Line 24V
Factory
Field Wire Nut
Caution Failure to wire this unit according to this wiring diagram may result
Note to installer: All wiring must comply with national electric code and all local codes.
All components must agree with their respective power source.
Combination Gas Control
Circuit Breaker (By Others)
Therm
TD1 Relay
Fan Motor
Contact
Flame Rollout Switch
Indicates Terminal Board Connection
Limit Control
24VAC
W
115V/60Hz/1Ø Power Shown
115V/60Hz/1Ø Power Circuit Breaker (By Others)
L1(BK)
L2(W)
R
Flame Rollout Switch
RR
G
TR1
TR2
Indicates Gas Valve Connection
L1
G2
Internal Component Wiring
Terminal Board
Flame Rollout Switch
Table 18.1 Troubleshooting (continued)
TROUBLE POSSIBLE CAUSE POSSIBLE REMEDY
Unit starts but does 1. Main gas is off. 1. Open manual gas valve . not ignite. 2. Air in gas line. 2. Purge gas line.
3. Main or manifold gas pressure 3. Set gas pressures per manual instructions
4. Check gas valve switch. 4. Set gas valve switch to "ON" position
Unit goes through cycle 1. Reversed main power polarity 1. Black wire - HOT, White wire - NEUTRAL, Green wire - Ground but the burners go out in 2. Unit not grounded 2. Ground unit and verify quality of ground connection. less then 10 seconds 3. Flame not sensed 3. Check flame sense probe and connection
Air circulating fan 1. Loose connections 1. Check all connections inoperable 2. Defective Fan time delay relay 2. Check fan time delay relay
3. Defective fan motor 3. Check fan motor
Wiring Diagram Selection
Since internal or factory wiring may vary depending on controls manufacturer, the wiring diagrams must be selected with the series identity number when installing, servicing, or troubleshooting a unit heater control system. Wiring diagrams that follow are for units with the corresponding series identity number that may be found in the 5th through the 7th digits of
Figure 18.1 Unit Heater Wiring Diagram (Series 103)
the serial number. For example, a unit with the serial number "30011033605-0981" has the 5th through the 7th digits as 103 as shown underlined above. To use the following diagram the unit series ID must be 103.
18
6-576.5
SERVICE / MAINTENANCE / TROUBLESHOOTING
Serial Number Designations (Remove access cover to locate)
01 01 101 01 97 1 000
MOTOR SUPPLIER CODE
01- Century 05- Universal etc.
FAN SUPPLIER CODE
01- Revcor 08- Brookside etc.
SERIES IDENTITY NUMBER
Identifies which series of controls were furnished on the unit.
WEEK OF MANUFACTURE
01- 1st week of year 26- 26th week of year.
SEQUENCE NUMBER
YEAR OF MANUFACTURE
97- 1997 98- 1998 etc.
Model Number Designations (Remove access cover to locate)
H D 4 5 A H 0 1 3 4
HD - Low Profile
Power Exhausted
MBH INPUT
30 - 30,000 Btu/hr input 45 - 45,000 Btu/hr input 60 - 60,000 Btu/hr input 75 - 75,000 Btu/hr input
HEAT EXCHANGER TYPE
A - Aluminized
H - Hot surface ignition
CONTROL CODE TYPE
34 - 115V/25V single
stage hot surface ignition, 100% shut-off with lockout - natural gas.
74 - 115V/25V single stage hot surface ignition, 100% shut-off with lockout - propane gas.
POWER CODE
01 - 115 volt, 60 hertz, single phase
Replacement Parts
When requesting parts please contact your local representative. Please have full model and serial number available. If you require assistance in locating your representative, please call the number located on the back page.
Figure 15.1 Common Replacement Parts
Model
Size
Heat
Exch. Kit
Power
Exhauster
Limit
Control
Switch
Flame
Roll-out
Switch
Transformer
Pressure
Switch
Control
Board
Igniter
30 3H36919 5H75038 5H75001 5H75002-2 5H75029 5H75030-3 5H78126-1 5H75032 5H76382 5H76383 45 3H36920 5H75038 5H75001 5H75002-2 5H75029 5H75030-3 5H78126-1 5H75032 5H76382 5H76383 60 3H36921 5H75038 5H75769 5H75002-2 5H75029 5H75030-3 5H78126-1 5H75032 5H76382 5H76383 75 3H36922 5H75038 5H75769 5H75002-2 5H75029 5H75030-4 5H78126-1 5H75032 5H76382 5H76383
The above list is subject to change. Please refer to unit mounted parts list for most up-to-date list.
Combination Gas
Control
Code 34
Code 74
Control
MODINE MANUFACTURING COMPANY
LIMITED WARRANTY
(Residential Use Only)
WHAT THIS WARRANTY COVERS
This warranty covers all defects in material and workmanship in your Modine unit heater, when used for your home or garage.
WHAT THIS WARRANTY DOES NOT COVER
Unit heater, or any of its parts:
1. which have been improperly installed or removed.
2. which have been damaged other than by normal use.
3. which have not been properly maintained.
4. which have been exposed to gas input more than 5% higher than specified on the serial plate of the unit heater, resulting in over-firing of the heater.
5. which have been exposed to possibly corrosive chemicals or chemical vapors (such as found in swimming pools), or potentially explosive or flammable atmospheres laden with grain dust, sawdust, or similar air­borne materials.
6. where any defect has been caused by abuse, misuse, neglect, carelessness, or accident.
7. where the serial number of the unit heater has been altered, defaced, or removed.
8. which are used in a confined space without adequate combustion air, such as can be found in more air-tight construction.
WHO THIS WARRANTY COVERS
This warranty covers the purchaser of the unit heater or anyone else who owns it during the warranty period.
HOW LONG THE WARRANTY LASTS
1. The warranty for the heat exchanger of the unit heater remains in force for ten years from the date you purchased the unit heater.
2. The warranty on all other parts of the heater remains in force for two years from the date you purchased the unit heater.
WHAT MODINE WILL DO TO CORRECT ANY WARRANTY DEFECTS, AND HOW YOU CAN GET WARRANTY SERVICE
In the event of warranty failure, Modine will provide replacement parts at Modine's cost. To obtain warranty repairs or replacement of defective parts, you must, within the period of warranty coverage, contact the agency from whom you purchased the unit heater. That seller, or the service agency performing service for the seller, will determine whether or not the unit heater, or any of its parts, is in fact defective, and will then either repair or obtain and install the necessary replacement parts for you. If it is determined that the unit heater or parts were not defective, you may be charged for any replacement parts.
CAUTION - Do not attempt to repair the unit heater yourself, nor remove it or any of its parts. This must be done by a qualified service agency.
If you have any questions about this warranty, call the person from whom you purchased the unit heater; or a Modine Heating Products Representative at 1-800-828-4328.
WHAT MODINE WILL NOT DO
Modine will not reimburse you for any labor costs or service charges related to warranty repairs or replacements.
INCIDENTAL AND CONSEQUENTIAL DAMAGES DISCLAIMED
This warranty does not cover incidental damages, such as use of substitute heating equipment, or other costs arising from the loss of use of the unit heater. This warranty also does not cover consequential damages, such as the cost of repairing or replacing other property which is damaged when this unit heater does not work properly.
HOW STATE LAW RELATES TO THIS WARRANTY
Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitations or exclusions may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
6-576.5
19
COMMERCIAL WARRANTY
Seller warrants its products to be free from defects in material and workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use of materials substituted under emergency conditions for materials normally employed. This warranty covers replacement of any parts furnished from the factory of Seller, but does not cover labor of any kind and materials not furnished by Seller, or any charges for any such labor or materials, whether such labor, materials or charges thereon are due to replacement of parts, adjustments, repairs, or any other work done. This warranty does not apply to any equipment which shall have been repaired or altered outside the factory of Seller in any way so as, in the judgment of Seller, to affect its stability, nor which has been subjected to misuse, negligence, or operating conditions in excess of those for which such equipment was designed. This warranty does not cover the effects of physical or chemical properties of water or steam or other liquids or gases used in the equipment. BUYER AGREES THAT SELLER’S WARRANTY OF ITS PRODUCTS TO BE FREE FROM DEFECT IN MATERIAL AND WORKMANSHIP, AS LIMITED HEREIN, SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER WARRANTIES, EITHER EXPRESS OR IMPLIED, WHETHER ARISING FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE, THERE ARE NO OTHER
WARRANTIES, INCLUDING WARRANTY OF MERCHANTABILITY OR FITNESS FOR PURPOSE, WHICH EXTEND BEYOND THE PRODUCT DESCRIPTION CONFIRMED BY BUYER AND SELLER AS OF THE DATE OF FINAL AGREEMENT.
This warranty is void if the input to the product exceeds the rated input as indicated on the product serial plate by more than 5% on gas-fired and oil-fired units, or if the product in the judgment of SELLER has been installed in a corrosive atmosphere, or subjected to corrosive fluids or gases, been subjected to misuse, negligence, accident, excessive thermal shock, excessive humidity, physical damage, impact, abrasion, unauthorized alterations, or operation contrary to SELLER’S printed instructions, or if the serial number has been altered, defaced or removed.
Heat Exchangers
For Seller’s non-separated combustion Gas-Fired Unit Heaters BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR REPLACEMENT AT THE FACTORY OF SELLER, ANY HEAT EXCHANGER WHICH SHALL, WITHIN TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE HUNDRED TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST, BE RETURNED TO SELLER WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE; EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER, BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. FOR GAS­FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS, BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO TEN YEARS FROM DATE OF SHIPMENT FROM SELLER. For Seller's Low Intensity Gas-Fired Infrared Heaters BUYER'S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR REPLACEMENT AT THE FACTORY OF SELLER, ANY HEAT EXCHANGER WHICH SHALL, WITHIN FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN 66 MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST, BE RETURNED TO SELLER WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE; EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER, BUYER'S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER.
Heat Exchanger (Condensers) for all Seller’s products except non­separated combustion Gas-Fired Unit Heaters and Infrared Heaters, all Burners except Infrared Heaters, and Sheet Metal for all Seller's products
BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR REPLACEMENT AT THE FACTORY OF SELLER, ANY HEAT EXCHANGER (CONDENSER) OR BURNER WHICH SHALL, WITHIN ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY
UNCHANGED CONDITION, OR WITHIN EIGHTEEN MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST, BE RETURNED TO SELLER WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE; EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER, BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER.
Burners
For Seller's Low Intensity Gas-Fired Infrared Heaters BUYER'S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR REPLACEMENT AT THE FACTORY OF SELLER, ANY BURNER WHICH SHALL, WITHIN TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN 30 MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST, BE RETURNED TO SELLER WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE; EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER, BUYER'S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. For Seller's High Intensity Gas-Fired Infrared Heaters BUYER'S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR REPLACEMENT AT THE FACTORY OF SELLER, ANY BURNER WHICH SHALL, WITHIN TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN 126 MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST, BE RETURNED TO SELLER WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE; EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER, BUYER'S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER.
All Other Components Excluding Heat Exchanger (Condenser), Burner, and Sheet Metal
For all Seller's products except Direct-Fired Heaters and High Intensity Gas-Fired Infrared Heaters BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR REPLACEMENT AT THE FACTORY OF SELLER, ANY PART OR PARTS WHICH SHALL, WITHIN TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST, BE RETURNED TO SELLER WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE; EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER, BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. For Seller's Direct-Fired Heaters and High Intensity Gas-Fired Infrared Heaters BUYER’S REMEDY FOR BREACH OF WARRANTY EXCLUSIVE OF ALL OTHER REMEDIES PROVIDED BY LAW IS LIMITED TO REPAIR OR REPLACEMENT AT THE SELLER’S OPTION ANY PART OR PARTS WHICH SHALL WITHIN A PERIOD OF ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN 18 MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST, BE RETURNED TO SELLER WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE EXAMINATION
OF THE SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE. BUYER AGREES THAT IN NO EVENT WILL SELLER BE LIABLE FOR COSTS OF PROCESSING, LOST PROFITS, INJURY TO GOODWILL, OR ANY OTHER CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY KIND RESULTING FROM THE ORDER OR USE OF ITS PRODUCT, WHETHER ARISING FROM BREACH OF WARRANTY, NONCONFORMITY TO ORDERED SPECIFICATIONS, DELAY IN DELIVERY, OR ANY LOSS SUSTAINED BY THE BUYER.
Modine Manufacturing Company has a continuous product improvement program;
it reserves the right to change design and specifications without notice.
• FOR RESIDENTIAL USE SEE LIMITED CONSUMER WARRANTY ON PREVIOUS PAGE.
Commercial HVAC&R Division
Modine Manufacturing Company 1221 Magnolia Avenue Buena Vista, Virginia 24416 Phone: 1.800.828.4328 (HEAT)
© Modine Manufacturing Company 2005
www.modine.com
11/05 - 3.5M Litho in USA