NOTE:
Energy Star only
applies to certain
configurations.
NOTE: GS Split Units are Energy Star Rated only when
matched with the appropriate Modine GA Air Handler or Modine
A-Coil. Model ES Split Units are not Energy Star Rated.
WARNING
This unit contains R-410A high pressure refrigerant.
Hazards exist that could result in personal injury
or death. Installation, maintenance, and service
must only be performed by an HVAC technician
qualied in R-410A refrigerant and using proper
tools and equipment. Due to much higher pressure
of R-410A refrigerant, DO NOT USE service
equipment or tools designed for refrigerants other
than R-410A.
WARNING
Improper installation, adjustment, alteration,
service or maintenance can cause property
damage, injury or death, and could cause
exposure to substances which have been
determined by various state agencies to cause
cancer, birth defects or other reproductive harm.
Read the installation, operating and maintenance
instructions thoroughly before installing or
servicing this equipment.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
IMPORTANT
1. The use of this manual is specically intended
for a qualied installation and service agency.
A qualied installation and service agency must
perform all installation and service of these
appliances.
2. GS/ES Split Units contain the refrigerant
R-410A. Review the R-410A Material Safety
Data Sheet (MSDS) for hazards and rst aid
measures.
3. Refrigerant charging should only be carried out
by an EPA-certied air conditioning contractor.
Inspection On Arrival
1. Inspect unit upon arrival. In case of damage, report it
immediately to transportation company and your local factory
sales representative.
2. Check rating plate on unit to verify that power supply meets
available electric power at point of installation.
3. Inspect unit received for conformance with description of
product ordered (including specications where applicable).
THIS MANUAL IS THE PROPERTY OF THE OWNER.
SPECIAL PRECAUTIONS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS
IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE
SAFE, EFFICIENT, AND TROUBLE-FREE OPERATION. IN
ADDITION, PARTICULAR CARE MUST BE EXERCISED
REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW.
FAILURE TO PROPERLY ADDRESS THESE CRITICAL
AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS,
PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS
ARE SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR
NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation
which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which,
if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which,
if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided, MAY
result in a potential safety concern.
DANGER
1. Appliances must not be installed where they may be exposed
to potentially explosive or ammable atmosphere.
2. Water temperatures over 125°F can cause severe burns
instantly resulting in severe injury or death. Feel water before
showering or bathing. Ensure that the primary water heating
source setpoints are higher than the heat pump water
discharge temperature of 120°F.
WARNING
1. Disconnect power supply before making wiring
connections to prevent electrical shock and equipment
damage.
2. All appliances must be wired strictly in accordance with
the wiring diagram furnished with the appliance. Any
wiring different from the wiring diagram could result in a
hazard to persons and property.
3. Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature
rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% greater than rated
voltage.
5. This unit contains R-410A high pressure refrigerant.
Hazards exist that could result in personal injury or
death. Installation, maintenance, and service must only
be performed by an HVAC technician qualied in R-410A
refrigerant and using proper tools and equipment. Due
to much higher pressure of R-410A refrigerant, DO NOT
USE service equipment or tools designed for refrigerants
other than R-410A.
6. When servicing or repairing this equipment, use only
factory-approved service replacement parts. A complete
replacement parts list may be obtained by contacting
Modine Manufacturing Company. Refer to the rating plate
on the appliance for complete appliance model number,
serial number, and company address. Any substitution of
parts or controls not approved by the factory will be at the
owner’s risk.
CAUTION
1. Ensure that the supply voltage to the appliance, as indicated
on the serial plate, is not 5% less than the rated voltage.
2. Do not use these units to heat or cool the building
during construction. Mechanical components can quickly
become clogged with debris. System damage may result.
3. Do not overcharge the refrigeration system. This can lead
to elevated compressor discharge pressure and possibly
ooding the compressor with liquid.
4. Do not attempt to reuse any mechanical or electrical
component which has been wet. Such component must
be replaced.
IMPORTANT
1. Start-up and adjustment procedures must be performed
by a qualied service agency.
2. All refrigeration checks must be made by a qualied
R-410A refrigeration technician.
3. Do not release refrigerant to the atmosphere. When
adding or removing refrigerant, all national, state/
province, and local laws must be followed.
4. The ground heat exchanger (open or closed loop or water
source to be connected to the unit must be designed,
constructed, and prepared in accordance with industry
guidelines (IGSHPA, ASHRAE, NGWA, etc.) and best
practices, and any more restrictive local codes and
regulations by a qualied service agency. Failure to
properly, size, install, or prepare the source could result in
reduced performance, a reduction in the normal life of the
units, and a hazard to persons and property.
5. Units selected for open loop ground source applications
should have a cupronickel source coaxial heat exchanger
to reduce mineral buildup and scaling. Open loop systems
should have the source coaxial coil ushed periodically to
maintain peak performance.
6. All piping and connections must be made in accordance
with local plumbing codes.
7. To check most of the Possible Remedies in the
troubleshooting guide listed in Tables 22.1-24.1, refer to
the applicable sections of the manual.
Table of Contents
General Information ..................................1
Inspection on Arrival ..................................1
Special Precautions ..................................2
Model/Serial Number Designations ......................3
Unit Dimensions .....................................4
Unit Location........................................5
Appliances must not be installed where they may be exposed to
potentially explosive or ammable atmosphere.
Handling
Each unit will be shipped to the site on a wood skid. Whenever
possible, all lifting and handling of the unit should be done with
the packing and skid in position.
When slinging or using a forklift to lift the unit, the support points
should be sufciently apart to give stability when lifting. Unless
otherwise noted, the lifting points should be equidistant from the
centerline. Extreme care should be taken not to drop the unit
Considerable damage can occur to the unit during positioning,
in particular, to the paneling and exterior paint. Use an adequate
number of personnel and the correct tools when moving the unit.
The unit is designed to remain upright so care should be taken
when lifting the unit up steps.
The use of torque screwdrivers on panel, cover or component
mounting screws is not recommended. Hand-start all screws.
If electric drills are used – set at the lowest possible torque.
Storage
Equipment should be stored in clean, dry area and in its original
packaging.
CAUTION
Do store or install units in corrosive environments or in locations
subject to temperature or humidity extremes (e.g., attics,
garages, rooftops, etc.). Performance, reliability, and service
life can be signicantly reduced. Transport and store units in an
upright position. Tilting units greater than 60° beyond horizontal
may result in damage to the compressor. If the unit is tilted
past 60°, do not energize the compressor until the unit has
been upright for a minimum of 6 hours to prevent compressor
damage.
Unit Protection
To prevent damage, keep the unit in its original packaging or
cover with an equivalent protective covering while on the job
site. Cover open water connections to prevent debris from
entering the system. Take extra precautions to protect the unit
from damage or contamination when in an area where spraying,
plastering and / or painting has not been completed. Physical
damage or contamination from foreign debris may prevent
proper start-up and costly equipment clean-up. Examine all
ttings, valves, or pipes and remove all dirt or debris before
installing unit.
Preparation
1. Before installation, ensure that the correct electrical power
supplies are available for the unit.
2. Each unit requires an independently fused and isolated power
supply.
3. Check to make sure that the units will have adequate
installation clearance for easy access to remove all panels
and access all internal components. Provide ample area
to access external components in and around the unit and
system including water valves, ttings, and all electrical
connections.
4. Remove any Accessory Kits and shipping support material
from the mechanical compartment.
5. Check Refrigerant Piping for dents or kinks.
6. Inspect all electrical connections. Connections must be clean
and tight at the terminal.
Electrical
Electrical wiring should be done in accordance with all
applicable national and local codes. It is the responsibility of the
electrical contractor to adhere to such codes. The warranty will
be voided if wiring is not in accordance with the specications of
the unit. Modine recommends using copper conductors only.
All power supply wiring must be capable of carrying the
maximum current load under no fault conditions at the stipulated
voltages. Care should be taken to avoid signicant voltage drops.
A knockout for power connection is provided on the access side
of the unit. See unit dimensions in Figure 4.1.
INSTALLATION
IMPORTANT
1. The ground heat exchanger (open or closed loop)
or water source to be connected to the unit must be
designed, constructed, and prepared in accordance with
industry guidelines (IGSHPA, ASHRAE, NGWA, etc.)
and best practices, and any more restrictive local codes
and regulations by a qualied service agency. Failure to
properly, size, install, or prepare the source could result in
reduced performance, a reduction in the normal life of the
units, and a hazard to persons and property.
2. Units selected for open loop ground source applications
should have a cupronickel source coaxial heat exchanger
to reduce mineral buildup and scaling. Open loop systems
should have the source coaxial coil ushed periodically to
maintain peak performance.
Installation of these units is to be INDOORS only. The
instructions detailed below are for the Installation of a
“Standard” unit. Accommodations and adjustments will be
required for the usage of additional unit accessories. Should
assistance be required for the installation of these additional
items, consult Modine at the phone number listed on the back
cover of this manual.
The unit must be located in a conditioned space that will remain
above freezing and where humidity levels could cause cabinet
condensation.
GEO16-501.4
5
INSTALLATION
Unit Installation
1. Units should be mounted on a vibration-absorbing pad slightly
larger than the base of the unit. See Table 6.1 below for
Modine vibration pad part numbers. If the unit isn’t mounted
on a vibration-absorbing pad, it must be raised off the oor
to prevent damage due to accidental ooding. It is not
necessary to anchor the unit to the oor.
Table 6.1 - Vibration Absorbing Pads -
High Density Plastic
Pad SizePart NumberModels
32" X 32"5H0835220000024-036
36" X 36"5H0835230000048-072
2. Check to ensure that the unit is level in both directions and
also plumb. If adjustment is necessary, Modine recommends
the placement of metal shims in the outermost corners of the
base.
3. Provide adequate clearance for all access panels.
4. Provide easy access for servicing water valves, ttings and
compressor.
5. Provide access to the controller and all electrical connections.
6. Provide a clear physical path to the unit. Adequate space
should be provided to allow removal of the unit, if necessary.
Water Connections
1. All units utilize swivel pipe ttings for water connections that
are rated for 150 psi.
2. The connections have a rubber gasket seal similar to a garden
hose gasket, which, when mated to the ush end of most 1"
Figure 6.1 - Water Connection Breakdown
threaded male pipe ttings (MPT), provides a leak-free seal
without the need for thread sealing tape or joint compound.
3. The water piping system should include pressure/temperature
taps for serviceability.
4. Refer to Figure 6.1. Install the brass spacer and rubber gasket in
swivel connector prior to attempting any connection (rubber
gasket and brass spacer kits are shipped with unit). To make
the connection, mate the eld supplied male pipe thread tting
against the rubber gasket in the swivel connector and thread
the female locking ring onto the pipe threads, while
maintaining the brass elbow in the desired direction. Tighten
the connectors by hand, and then gently snug the tting with
pliers to provide a leak-proof joint.
5. DO NOT OVERTIGHTEN, as leaks may occur.
6. NOTE: Never use exible hose smaller than 1" inside
diameter on the unit. Limit the length to 10' per connection in
one direction. Check carefully for leaks.
Installation with Existing Air Handler or
Refrigerant Coil
Modine recommends installing Split units with a new matching
Modine Air Handling or A-coil unit, but the Split unit may be
matched with an existing air handler or coil if the following
conditions are met:
1. Coil must be R-410A rated and use a heat pump thermal
expansion valve with internal check valve.
2. The air coil and line set have been ushed with a compound
that vaporizes in accordance with the instructions provided
with the ushing agent.
Follow the air handler manufacturer’s installation instructions to
install the air handler. Note that such installations do not qualify
for Energy Star.
Factory installed
Snap ring in
this groove
Swivel adaptor
hand tighten
Brass snap ring
Brass spacer
Rubber gasket
Swivel adaptor
hand tighten
P/T Port - access
for temperature
and pressure
6
GEO16-501.4
INSTALLATION
Dual Fuel Setup
A conventional fossil fuel forced air furnace may also be used
for an air handler, as well as a supplemental heat source. The
furnace must provide at least 400 CFM/Ton of nominal unit
cooling capacity. Refer to the Cased / Uncased Coil I&S manual
for exact airow requirement for the rated matched systems.
The furnace should be disabled until auxiliary heating is called
for, then the heat pump should be disabled when the furnace
takes over the heat load. Refer to the furnace manufacturer’s
installation instructions for directions on installation of the
furnace, coil, and wiring. A Dual Fuel Thermostat is required to
prevent damage to the split unit (see Figure 12.1).
Refrigerant Line Sets
Only ACR grade copper tubing should be used. Recommended
line sets are shown in Table 9.2. Refer to the table for proper
line sizing, as well as maximum allowable lengths of the line set.
The table is based on equivalent line length. Equivalent Line
Length is the combination of the actual lengths of all straight
runs and the equivalent length of all bends valves and ttings in
a particular line. Refer to the ASHRAE Fundamentals Handbook
for determining the equivalent lengths of bends, valves and
ttings. If calculated equivalent line length is between two
lengths in Table 9.2, use the size for the next longer length.
Line sets over 60 feet are not recommended and can lead to oil
return problems, which can dramatically reduce the life of the
compressor, and excessive pressure drop, which can reduce
capacity and efciency of the system.
Vertical lines should be kept to a minimum. Large vertical lifts
will increase pressure drop in the liquid line. Whenever possible,
the air handler or cased / uncased A-coil should be installed
above the unit to aid in oil return. Horizontal suction lines
should be pitched slightly toward the unit to aid in oil return. Do
not exceed the largest suction line size in the table for each
given unit size. Bends and turns should be avoided if possible
and all wall penetrations should be sealed. Line sets must be
suspended properly and should not contact anything except
the hangers and insulation. Ends of copper lines should be
kept sealed until joints are brazed. All lines should be insulated
with 3/8" thick insulation at minimum. The lter drier should be
replaced whenever the lines are broken into for service.
All brazing should be done with nitrogen owing through the
inside of the tubing at 2-3 psi to prevent oxidation. A low silver
phos-copper braze alloy is recommended. When brazing to the
Split Unit service valves, wrap the valves in a wet rag to prevent
damage to the valves. NOTE: The Split Unit is shipped with a
factory refrigerant charge. The service valves should not be
opened until the entire line set has been leak tested, purged and
evacuated.
Existing Line Sets
New line sets are recommended, but required if the following
conditions exist:
• A compressor burnout occurred in the previous system
• Oil traps were installed in the existing line sets
• The existing line set sizes are not equal the recommended line
sets
• The existing line set shows signs of damage, corrosion,
abrasion or fatigue
Thermal Expansion Valve
The Split Ground Source Unit is equipped with a thermal
expansion valve (TXV) that is pre-set from the factory for
performance. No adjustment is necessary unless service has
been done on the TXV. Table 9.1 shows the Split Unit TXV
initial factory settings. Note that the matched Split System has
two TXV’s, each with independent factory settings. One TXV is
included with the A-coil or Air Handler, and one is installed in
the Split unit. Refer to the Cased / Uncased or Air Handler I&S
manual for the initial factory TXV settings at the A-coil.
WARNING
R-22 RETROFITS
It is highly recommended that a new line set be installed for
any R-22 system retrot. If it is impossible to replace the
line set, the line set must be ushed prior to the installation
of the R-410A split system. It is also critical that the installer
clear traps of all residual mineral oils.
GEO16-501.4
7
INSTALLATION
DANGER
Water temperatures over 125°F can cause severe burns
instantly resulting in severe injury or death. Feel water before
showering or bathing. Ensure that the primary water heating
source setpoints are higher than the heat pump water discharge
temperature of 120°F.
8. Reinstall the drain valve on one side of the tee.
9. Open all valves, except the system drain valve, and ll the
system with water. Bleed all air and check for leaks.
10. Insulate all piping with 3/8” closed cell insulation.
11. Refer to Start Up Procedure for DHW setup and start up.
Figure 8.1 - Typical DHW Piping Diagram
COLD
WATER
HOT
WATER
IN
OUT
IMPORTANT
All piping and connections must be made in accordance with
local plumbing codes. All components should be located in a
conditioned space that is maintained above 50°F at all times.
Hot Water Generator (Desuperheater)
Installation (If Equipped)
A minimum 50 gallon water heater is recommended with the
Desuperheater (DHW) option. Higher demand applications may
use either one 80 gallon water heater or two 50 gallon water
heaters piped in series. The hot water tank should be allowed
to stratify by lowering the bottom element setpoint to 100°F and
setting the top element setpoint to 125°F. Control of the DHW
pump is via electro-mechanical temperature switches. The
pump is energized whenever the unit is running a conditioning
cycle, the DWH supply temperature (water leaving the
desuperheater coil) is < = 120°F and the compressor discharge
temperature is > = 100°F.
The desuperheater pump is disabled on delivery from the
factory. It must be enabled by wiring the pump in the unit control
panel after the DHW piping has been completed and purged.
This is to prevent the domestic hot water pump from running
before the DHW tank is piped to the heat pump. DHW option
must not be enabled until all piping is complete and the DHW
loop has been purged and bled or damage can occur.
Poor domestic water quality may result in debris buildup
in the system. A water softener is recommended with hard
water (greater than 10 grains or 170 total hardness). Extreme
hard water will require additional maintenance and should be
considered with the DHW option, as maintenance costs may
outweigh potential savings.
Make sure all local electrical and plumbing codes are met for
installing a hot water generator. The installing contractor is
responsible for performing the installation accordingly.
Water piping lengths must be kept at a minimum. DO NOT use
a one way length greater than 50 feet.
Coaxial drain tees that provide an inlet and outlet to the heat
pump from the drain connection are not recommended. The
decreased diameter of the inlet and outlet pipes to the heat
pump make it possible for debris build up and completely stop
the ow of water to and from the desuperheater.
1. Turn off power or fuel supply to the water heater.
2. Close cold water supply valve to heater.
3. Drain and ush the tank, then remove the drain valve.
4. Inspect the water heater cold water inlet pipe for a check
valve and remove if present. Failure to do so will result in
damage to the unit.
5. Use a tee to connect the cold water supply pipe to the DHW
In connection on the unit. Be sure to install a shutoff valve
on the Cold Water Inlet pipe. Also install a shutoff valve
on the supply line to the unit, as well as an air vent at the
highest point of the system.
6. Run DHW piping using a minimum of 1/2" OD copper
tubing. See Table 8.1 for recommended line sizes.
7. Use a tee to connect the unit DHW Out Connection to the
water heater drain connection. Be sure to install a shutoff
valve on the pipe as near to the water heater as possible.
8
Figure 8.2 - Typical DHW Piping Diagram with Two Tanks
Table 8.1 - DHW Pipe Sizes
GEO16-501.4
AIR VENT
DHW IN
DHW OUT
DRAIN CONNECTION
AIR VENT
DHW IN
DHW OUT
DRAIN CONNECTION
Maximum pipe length (one way) to achieve optimum flow
Models
0240.850-
0361.250-
0481.64550
0602.02550
0722.41050
DHW Flow
(gpm)
COLD
WATER
IN
TANK 1
HEATING
SOURCE
DISABLED
DRAIN VALVE
Copper
DRAIN VALVE
HOT
WATER
OUT
1/2"
COLD
WATER
3/4" Copper
HOT
WATER
OUT
IN
INSTALLATION
Leak Testing and Evacuating the
Refrigeration System
Pressurize the line set and air coil with 150 psi dry nitrogen
and thoroughly check for leaks. Once a leak free system is
veried, purge the system and evacuate the line set and air
coil to at least 500 microns. Use both service ports to prevent
false readings. A quality vacuum pump capable of accurately
measuring vacuum depth is required to ensure system is ready
for charging. System must hold vacuum for a minimum for 30
minutes.
Charging the System
Do not overcharge the system. Charge all systems by weight
as determined from Table 9.2 and the supplied factory charge.
Factory charge includes, split unit charge, A-coil charge and
a 25' line set. If the line set varies from 25', then a charge
adjustment must be calculated.
Table 9.1 - Initial Split Unit TXV Superheat Settings
Models
024036048060072
TXV Turns
Closed
Verify final settings after initial adjustments.
3-1/44-3/45-1/46-1/45-1/4
Table 9.2 - Line Sizing and Initial Refrigerant Charges
Equivalent Line Length
Air Handler
Size
024024024
036036036
048048048
060060060
072N/A072
Initial system charge includes Split unit charge, 25' line charge, and Air Coil charge. Adjust charge via actual system subcooling and superheat measurements.
Additional charge for R-410A is 1.0 oz/ft for 1/2" line and 0.5 oz/ft for 3/8" line
A-Coil Size
Split Unit
Size
20 Feet40 Feet60 Feet
SuctionLiquidSuctionLiquidSuctionLiquid
5/8"3/8"5/8"3/8"3/4"3/8"9396
3/4"3/8"3/4"3/8"3/4"1/2"99103
3/4"3/8"7/8"3/8"7/8"1/2"125128
7/8"1/2"7/8"1/2"1-1/8"1/2"171175
7/8"1/2"7/8"1/2"1-1/8"1/2"171175
Split Unit
Factory
Charge (oz)
- No HWG
Split Unit
Factory
Charge (oz)
- w/HWG
GEO16-501.4
9
INSTALLATION
Wiring
WARNING
1. Disconnect power supply before making wiring
connections to prevent electrical shock and equipment
damage.
2. All appliances must be wired strictly in accordance with
the wiring diagram furnished with the appliance. Any
wiring different from the wiring diagram could result in a
hazard to persons and property.
3. Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature
rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% greater than rated
voltage.
CAUTION
Ensure that the supply voltage to the appliance, as indicated
on the serial plate, is not 5% less than the rated voltage.
Installation of wiring must conform with local building codes,
or in the absence of local codes, with the National Electric
Code ANSI/NFPA 70 - Latest Edition. Unit must be electrically
grounded in conformance to this code. In Canada, wiring must
comply with CSA C22.1, Part 1, Electrical Code.
Electric wiring must be sized to carry the full load amp draw of
the motor, starter and any controls that are used with the unit.
See Table 13.1 for electrical data.
Any damage to or failure of units caused by incorrect wiring of
the units is not covered by warranty.
Terminal Strip Connections
The terminal strip connections are designed to clamp down on
the wires. To properly connect the wires to the terminal strip:
1. Push a small at-head screwdriver into the square hole on the
terminal. Press rmly until the screwdriver hits the back stop
and opens the terminal (see Figure 10.1).
2. Remove approximately 3/8" of insulation from the end of
the wire and push the stripped wire into the oval hole in the
terminal.
3. Remove the screwdriver. Pull on the wire to make sure that it
is securely clamped in the terminal.
4. Make sure that the terminal clamp is in contact with bare wire
(insulation removed).
Figure 10.1 - Terminal Strip
Unit Power Connection
Refer to the unit serial plate for unit voltage and phase.
Available power must be the same as indicated on serial plate
Remove access panel and electrical box cover. Using Unit
Power knockout, route power lines through unit and into main
electrical panel. Connect line voltage wires to the L1 and L2 lugs
of the contactor. Consult the unit electrical data on the serial
plate for correct overcurrent protection sizing. Connect ground
wire to ground lug in electrical panel. Replace electrical box
cover and access panel prior to unit startup.
Hot Water Generator Pump Wiring
The domestic hot water pump is not wired in the factory to
prevent pump burnout in case the unit is powered before the
domestic hot water tank is plumbed or full of water. Refer to the
control manual and wiring diagram for instructions on enabling
the pump.
Transformer Wiring
The system supplies the power to the controller via a 24V
transformer. On 208-230V systems, the transformer comes
factory wired for 230V operation. If the unit is to be powered
with 208V, the transformer must be wired for 208V. A terminal
strip with a jumper is provided for easy eld conguration (see
Figure 11.1). Refer to the wiring diagram provided with the unit
for for details.
10
GEO16-501.4
INSTALLATION
Figure 11.1 - 208-230V Transformer Wiring
Flow Center Wiring
The ow center must be connected to the terminal blocks in
the electrical box. The pumps will automatically be cycled as
required by the unit. Be sure to wire the ow center prior to
turning the system on.
Thermostat Wiring
The thermostat wires are connected directly to the appropriate
terminal blocks in the electrical box. Refer to the unit wiring
diagram or control manual for details.
Thermostat Installation and Wiring
The thermostat should be located on an interior wall in a larger
room approximately 54" off the oor and away from supply
duct drafts. DO NOT locate the thermostat in areas subject to
sunlight, drafts or on external walls.
GEO16-501.4
11
INSTALLATION
Dual Fuel Setup / Thermostat Wiring
When matched with an A-coil and a furnace for the air handler,
a dual fuel thermostat is required to prevent furnace from
engaging when heat pump is operating. The heat pump is the
rst and second stage of heating and the furnace is the auxiliary
heat.
Figure 12.1 - Field Wiring to Fossil Fuel Furnace
500
〈〈
02
5
〈〈
20
5
〈〈
21
5
〈〈
22
5
〈〈
Control Panel Terminals
91
5
〈〈
92
5
〈〈
C24VAC Common
R24VAC Hot
GFan
Y1Compressor Stage 1
Y2Compressor Stage 2
W1Aux Ht Stg 1
W2Aux Ht Stg 2
Condensate Overflow Alarm
Modine Air Handlers and Cased / Uncased A-coils are supplied
with a condensate pan overow switch which should be wired
back to the Split System with two wires. Terminals are provided
in control panel for eld wiring of condensate overow switch.
Remove the blue jumper wire and wire COS to terminals 533 &
534. Refer to wiring diagram and Figure 12.2.
If the Modine Split unit is matched with an existing air handler or
air coil, it is highly recommended a normally closed, condensate
overow switch is installed in the air coil drain pan and wired to
the unit control board. When installed, the controller will shut
down the unit in the event of a plugged condensate drain line.
Failure to wire the switch to unit may result in damage to the
furnace or property.
The condensate switch accessory assembly, 3H0387860001, is
available for eld installation. It is supplied with 75’ of lead wire.
The condensate alarm is a 24V, normally closed, dry contact.
The installer may route the leads back to the unit or run two
wires.
Figure 12.2 - Condensate Overflow Switch Wiring
Open Loop Control Valve Wiring
Always maintain water pressure in the heat exchanger by placing
water control valves at the outlet of the unit to prevent mineral
precipitation during the off cycle. Pilot operated slow closing valves
are recommended to reduce water hammer. If water hammer
persists, an expansion tank can be mounted on the piping to help
absorb the excess hammer shock. Slow closing valve must have
an end switch that enables/disables the compressor. See valve
manufacturer's instructions for proper wiring.
Furnace Terminals
12
GEO16-501.4
ELECTRICAL DATA
ELECTRICAL DATA
Table 13.1 - Electrical Data
Models
024036048060
Supply Voltage208-230/60/1
Min / Max
Voltage
FLA15.719.728.134.737.6
MCA18.523.533.541.845.4
MOP30.040.050.070.070.0
197 / 253
072
GEO16-501.4
13
START-UP PROCEDURE
START-UP PROCEDURE
CAUTION
IMPORTANT
Start-up and adjustment procedures must be performed by a
qualied service agency.
The unit has been factory tested and set for proper operation,
but a full unit start-up is recommended.
NOTE: If any abnormal operation occurs during the startup
procedure, refer to the Troubleshooting section.
NOTE: Always start the system in heating mode.
Pre-Start Checks
Before applying power to heat pump, use the following checklist
to ensure a complete and proper installation.
• Check that the supply voltage matches the unit supply voltage
listed on the Unit Serial Plate.
• Verify that all wiring is secure and properly protected.
• All high voltage wiring is correct including, fuses, breakers and
wire sizes.
• Trace circuits to insure that the unit has been wired according
to the wiring diagram.
• Check that the unit has no visible damage and that all the
components are secure.
• Check that all eld electrical and mechanical work has been
performed according to all applicable Federal, State, and Local
codes.
• Check the supply voltage to the unit is within +/- 5% of the
voltage on the unit serial plate.
• Low voltage wiring for thermostat, control wiring and the freeze
protection setpoint completed.
• Transformer wiring is correct.
• Water supply to heat pump is completed.
• Piping completed, water system cleaned and ushed of debris.
• Air and debris are purged from the ground loop.
• Antifreeze added to ground loop, as required
• Isolation valves are open, water control valves or loop pumps
wired.
• DHW piping is complete, all air purged from system and
charged with water.
• IMPORTANT: Ensure all valves in the DHW circuit are fully
open.
• Condensate line is open, condensate drain line is correctly
pitched.
• Blower rotates freely.
• Check air coil for cleanliness.
• Filter is clean and in position.
• Clean all debris from the ducting system.
• Service/access panels are in place.
• Entering air and water temperatures are within operating limits
in Table 16.2.
CAUTION
Verify that ALL water control valves are open and allow
water ow prior to engaging the compressor. Freezing of the
coax or water lines can permanently damage the heat pump.
To avoid equipment damage, DO NOT leave system lled in
a building without heat during the winter unless antifreeze
is added to the water loop. Heat exchangers never fully
drain by themselves and will freeze unless winterized with
antifreeze.
Controller Setup
GS/ES systems are pre-programed from the factory for easy
installation, no installer setup is required for the unit to function.
The DHW pump is not wired from the factory on all units. This
is done to protect the pump during installation and startup. If a
DHW pump is in the system, it must be wired.
IMPORTANT
Ensure that the freeze protection setpoint is properly set
(approximately 10°F above the uid freeze point) for the type
and percentage of uid used in the ground loop.
Table 14.1 - Freeze Point of Pure Antifreeze
Solutions, °F ➀
% Vol.MethanolEthanol
5.026.229.529.3
7.523.028.127.7
10.019.726.426.1
12.516.224.624.4
15.012.622.622.5
17.58.820.420.5
20.04.918.118.4
22.5—15.616.1
25.0—12.913.8
27.5—10.011.3
30.0—7.08.8
➀
All values are typical, refer to antifreeze manufacturer data sheets for actual values.
Unit Startup Procedure
The Startup/Troubleshooting form found on page 25 of this
manual may be used to assist during unit startup.
1. Put thermostat in standby or off mode.
2. Turn on line power to heat pump.
3. Turn thermostat fan position to “ON” and verify blower
operation.
4. Put thermostat in heating mode.
5. Slowly raise the thermostat set-point until a heating call is
generated and the compressor energizes.
6. After a few minutes, check the supply air and verify warm air
delivery.
7. Verify water ow by comparing pressure drop across the
coaxial coil to values in Table 15.1.
8. Monitor ground water supply (GWI) and return (GWO)
temperatures. If temperature drop is within expected
operating range as shown in Table 16.1, continue with testing.
Propylene
Glycol
14
GEO16-501.4
START-UP PROCEDURE
9. If temperature drop is outside of expected operating range,
check refrigerant pressures and compare to those shown in
Table 16.1.
10. Check air temperature rise across the coil. Air temperature
rise should be between 20°F and 30°F.
11. Check for vibration, noise and leaks.
12. Lower thermostat set point below room temperature and
verify that compressor and ow center deactivate.
13. Initiate a control signal to place the unit in the cooling mode.
Cooling set point must be set below room temperature.
14. Cooling will energize after a time delay.
15. Be sure that the compressor and ow center are activated.
16. Monitor ground water supply (GWI) and return (GWO)
temperatures. If temperature rise is within expected
operating range as shown in Table 16.1, continue with
testing.
17. If temperature drop is outside of expected operating range,
check refrigerant pressures and compare to those shown in
Table 16.1.
18. Check for an air temperature drop of 15°F to 25°F across
the air coil.
19. Check for vibration, noise and leaks.
20. Adjust the cooling set point above the room temperature and
verify that the compressor and ow center deactivate.
21. If unit fails to operate as described, see troubleshooting
section. If the unit still does not operate properly, contact
Modine at the number listed on the back of this manual.
22. When testing is complete, set system to normal operating
mode.
DHW Startup Procedure
1. If the DHW was wired, the DHW pump will run whenever the
heat pump is running and the DHW Supply temperature is
below 120°F and the discharge temperature is above 100°F.
2. To verify operation of the DHW pump, ensure that the heat
pump is running and the DHW temperature is below 120°F
and the discharge temperature is above 100°F.
3. The temperature rise across the desuperheater should be
5-10°F.
Sequence of Operation
The unit’s controller will monitor calls for heat or cooling by
thermostat(s).
Blower: The blower will cycle with a call for cooling or heating.
Cool: Upon receiving a a G, Y1, and O signal from the
thermostat, the blower, compressor and reversing valve will be
energized. On two stage units with ECM, the rst stage of the
compressor will be energized and the blower will provide the
rst stage airow. The compressor will be limited by a timer
that will provide anti-cycle protection. When a subsequent Y2
signal is received, the second stage of the compressor will be
energized and the blower will provide second stage airow (two
stage units with ECM only).
Heat: Upon receiving a G and Y1 and signal from the
thermostat, the blower and compressor will be energized. On
two stage units with ECM, the rst stage of the compressor will
be energized and the blower will provide the rst stage airow.
The compressor will be limited by a timer that will provide anticycle protection. When a subsequent Y2 signal is received,
the second stage of the compressor will be energized and the
blower will provide second stage airow (two stage units with
ECM only).
Open Loop Systems: An optional valve can be tted to stop
water ow when the compressor is not energized. This allows
the pumping system to work more efciently.
Supplemental Electric Heat (Field Installed Accessory):
Upon receiving a W1 signal from the thermostat, heat is
energized. Upon receiving a W2/E signal from the thermostat,
electric heat is energized.
Table 15.1 - Water Pressure Drop, psi
(Based on Entering Water Temperature)
Equation 15.1 - Coaxial Coil Pressure Drop
Antifreeze Correction
To nd actual pressure drop through either coaxial coil
when the unit is operated with an antifreeze solution, rather
than water:
WPDA = WPDS x ACF
Where:
WPDA = Water Pressure Drop at Actual Conditions
WPDS = Water Pressure Drop at Standard Conditions
(water) from Table 18.1
ACF = Antifreeze Correction Factor from Table 18.2
GEO16-501.4
15
START-UP PROCEDURE
Table 16.1 - Typical Operating Conditions
Entering Water
Temperature
(°F)
30
50
70
Entering Water
Temperature
(°F)
50
70
90
Water Flow
(gpm/ton)
1.568-76285-3108-123-95-715-21
3.072-80290-3158-123-93-517-23
1.5100-110315-3459-135-117-922-28
3.0104-114320-3509-135-115-724-30
1.5134-144355-39510-146-129-1130-36
3.0138-148360-39010-146-127-932-38
Water Flow
(gpm/ton)
1.5122-130220-23513-1910-1619-2321-25
3.0120-128190-21013-1910-169-1221-25
1.5127-136210-28011-158-1419-2320-24
3.0125-134250-27011-158-149-1220-24
1.5132-144360-38010-148-1418-2218-22
3.0130-142330-35010-148-149-1218-22
Table 16.2 - Operating Limits
Operating LimitsCooling, °FHeating, °F
Min. Ambient4545
Rated Ambient80.668
Max Ambient10085
Min. Entering Air5040
Rated Entering Air, db/wb80.6/66.268/59
Suction
Pressure
(psig)
Suction
Pressure
(psig)
Heating - No Desuperheater
Discharge
Pressure
(psig)
Superheat
(°F)
Cooling - No Desuperheater
Discharge
Pressure
(psig)
Superheat
(°F)
NOTE: Limits are acceptable for start-up conditions only.
Min / max limits are intended for bringing the space up/down
to normal temperatures. Units are not designed to operate
at the min/max conditions on a continual or regular basis.
The operating limits are dependant upon three primary factors:
1) water temperature, 2) return air temperature, and 3) ambient
temperature. When any of the factors are at the minimum or
maximum levels, the other two factors must be at the normal
level for proper and reliable unit operation.
Subcool
(°F)
Subcool
(°F)
Water
Temperature
Drop (°F)
Water
Temperature
Rise (°F)
Air
Temperature
Rise (°F)
Air
Temperature
Drop (°F)
Max. Entering Air, db/wb110/8380
Min. Entering Water3020
Normal Entering Water50-9030-60
Max. Entering Water12090
16
GEO16-501.4
START-UP PROCEDURE
Table 17.1 - Compressor Winding Resistance (Ohms)
CompressorC to SC to RS to R
ZPS20K5E-PFV1.641.302.94
ZPS26K5E -PFV1.911.022.93
ZPS30K5E -PFV1.520.892.40
ZPS35K5E -PFV1.550.622.17
ZPS40K5E-PFV1.870.522.38
ZPS49K5E-PFV1.670.422.09
ZPS51K5E-PFV1.670.422.09
ZPS60K5E-PFV1.910.362.27
Table 17.2 - Refrigerant Circuit Malfunctions and Probable Causes ➀
The following chart will assist in troubleshooting and diagnosing causes of a problematic unit. The chart provides general guidance
for system measurements relative to typical operating conditions.
➀ Cooling capacity based on 350 CFM , 75/63°F Dry Bulb/Wet Bulb Return Air
18
GEO16-501.4
MAINTENANCE
MAINTENANCE
WARNING
When servicing or repairing this equipment, use only factoryapproved service replacement parts. A complete replacement
parts list may be obtained by contacting Modine Manufacturing
Company. Refer to the rating plate on the appliance for
complete appliance model number, serial number, and
company address. Any substitution of parts or controls not
approved by the factory will be at the owner’s risk.
CAUTION
Do not attempt to reuse any mechanical or electrical
component which has been wet. Such component must be
replaced.
IMPORTANT
To check most of the Possible Remedies in the troubleshooting
guide listed in Tables 22.1 - 24.1, refer to the applicable
sections of the manual.
The routine care and maintenance of this unit will increase
longevity, provide for the proper operational performance, and
reduce the probability of failure.
Once the unit is operational, it will be necessary to perform
certain routine maintenance/service checks. Following is a
Maintenance Schedule with the recommended checks. If your
unit is equipped with special features, there may be additional
checks that are required. Consult Modine for assistance.
The use of torque screwdrivers on panel, cover or component
mounting screws is not recommended. Hand-start all screws.
If electric drills are used – set at the lowest possible torque.
Coaxial Coil Maintenance – Ground Water
Applications
If the system is installed in an area with a known high mineral
content (125 P.P.M. or greater), best practice is to establish a
periodic maintenance schedule with the owner so the coil can
be checked on a regular basis. Should periodic coil cleaning
be necessary, use coil cleaning procedures that are compatible
with the heat exchanger material and copper water lines.
Generally, with greater water ow rates, the likelihood of scaling
reduces. Therefore, the recommended minimum water ow is
1.5 gpm per ton. Recommended minimum ow rate for entering
water temperatures below 50°F is 2.0 gpm per ton.
Keep all air out of the water. An open loop system should be
checked to ensure that the well head is not allowing air to
inltrate the water line. Lines should always be airtight. Keep
the system under pressure at all times. It is recommended in
open loop systems that the water control valve be placed in
the discharge line to prevent loss of pressure during off cycles.
Closed loop systems must have positive static pressure.
Generally water coil maintenance is not needed for closed
loop systems. However, if the piping is known to have high
dirt or debris content, best practice is to establish a periodic
maintenance schedule with the owner so the coil can be
checked on a regular basis. Dirty installations are typically the
result of deterioration of iron or galvanized piping or components
in the system.
Open cooling towers requiring heavy chemical treatment and
mineral buildup through water use can also contribute to higher
maintenance. Should periodic coil cleaning be necessary, use
standard coil cleaning procedures that are compatible with the
heat exchanger material and copper water lines.
Generally, with greater water ow rates, the likelihood of scaling
reduces. However, ow rates over 3 gpm per ton can produce
water (or debris) velocities that can erode the heat exchanger
wall and ultimately produce leaks.
Desuperheater Coils
If potable water is hard or not chemically softened, the high
temperature of the desuperheater can lead to scaling. This
results in more scheduled maintenance. A buffer tank may be
installed to help prevent scaling. Extreme hard water conditions
should not use the desuperheater option. Should periodic coil
cleaning be necessary, use coil cleaning procedures that are
compatible with the heat exchanger material and copper water
lines.
Air Filters
Filters must be clean to obtain maximum performance. They
should be inspected monthly under normal operating conditions
and be replaced when necessary. Units should never be
operated without a lter.
Condensate Drain
In areas where airborne bacteria produce slime in the drain
pan, it may be necessary to treat chemically with an algaecide
approximately every three months to minimize the problem. It
may be necessary to clean the condensate pan periodically to
insure indoor air quality. The condensate drain can pick up lint
and dirt, especially with dirty lters. Inspect twice a year to avoid
the possibility of overow.
Compressor
Conduct annual amperage checks to insure that amp draw is no
more than 10% greater than indicated on the operating data.
Blower Motors
All units have lubricated fan motors. Do not lubricate unless
obvious, dry operation is inspected. Periodic oiling is not
required (may lead to excessive dirt buildup & motor failure).
Check the operation amperage annually to ensure the amp draw
is not greater than 10% of data indicated on the name plate.
ECM fan motors need NO oiling.
GEO16-501.4
19
MAINTENANCE / REPLACEMENT PARTS
Cabinet
If a ood occurs, try to expel water as soon as possible. Water
contact for any duration will cause corrosion on the cabinet
nish. All units mounted on the ground should be installed on
an absorption pad. This also helps prevent water from entering
the cabinet. If the cabinet is dirty, do not spray with water, use a
damp rag with mild detergent, and wipe the system clean.
Refrigerant System
The refrigerant circuit is sealed, service gauges should
not be used unless the system is not operating correctly.
The operational charts show correct pressures, ow and
temperature. Before servicing the refrigerant circuit, ensure that
the water and air ow are correct.
REPLACEMENT PARTS
For ease of identication when ordering replacement parts
or contacting the factory about this unit, please provide the
complete model number and unit serial number. This information
can be found on the serial plate attached to the unit (see Figure
20.1). When a component part fails, a replacement part should
be obtained by contacting the local distributor or Modine Sales
Representative. The sales representative can assist with Return
Material Authorizations (RMAs) and potential warranty claims.
The following details are required to process parts orders and
warranty claims:
1. Full description of part required, including unit’s model
number.
2. The complete unit’s serial number.
3. Completed Return Material Authorization (RMA)
4. An appropriate purchase order number.
For further information email modinegeothermal@ccsportal.
When encountering a unit with operational faults, complete
these preliminary system checks before utilizing the
troubleshooting charts.
In order to maintain system integrity, performance and
efciency, do not install service gauges unless unit operation
appears abnormal and all other diagnostic checks are normal..
Verify water and air side temperatures changes against Typical
Operating Data. If the performance is within the ranges in the
table and the air and water ows have been veried, then
gauges may be installed in order to check subcooling and
superheat.
1. Verify that the unit and ow center power supplies are on
2. Verify that all fuses or disconnects switches are intact
3. Inspect unit for obvious defects (e.g., leaking connections,
loose or damaged wiring, etc.)
4. Verify eld inputs and outputs (refer to wiring diagram)
a. Thermostat inputs – Thermostat inputs are 24VAC
signals and can be veried using a volt meter between C
and Y, G, O, W.
b. Outputs – Compressor and reversing valve output relays
are 24VAC and can be veried using a voltmeter. The fan,
ow center and DHW pump are powered through 240V
relays. Operation can be veried using a voltmeter or
clamp-on ammeter.
5. After completing these checks, refer to the troubleshooting
tables on the next pages.
GEO16-501.4
21
TROUBLESHOOTING
Table 22.1 - Troubleshooting
Fault
Mode
Htg Clg
XX
Possible CauseVerifyAction
Power FailureNo voltage at line side of compressor contactor.Check disconnect switch and power distribution panel.
No power to
unit
Compressor
not operating
Blower does
not run
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XXDefective thermostat Verify operation of thermostat.Replace if defective.
XX
XX
XX
XX
XX
Open disconnect
switch
Blown fuse / circuit
breaker tripped
Low supply
voltage
Thermostat positionVerify that thermostat is in heating or cooling position.Test operation of thermostat.
Defective thermostat Verify operation of thermostat; verify thermostat
Thermostat wiringVerify thermostat wiring at unit and signals at unit.Repair wiring, if needed.
TransformerCheck primary and secondary transformer voltages.If no primary, verify wiring
Power wiring defectCheck for loose or broken wires at compressor,
Locked out on safety
controls
Defective
compressor overload
Compressor motor
burn out or open
windings
Defective
compressor
contactor
Loss of compressor
run signal
Defective run
capacitor
Thermostat wiringVerify thermostat wiring at unit.Repair wiring, if needed.
Loss of power to
motor (208/240V
units)
Defective PSC motor Check line voltage at motor with G call.If power at motor, check capacitor. Replace motor or
Defective ECM
motor
Unit is oversizedVerify load calculations and unit selection.
At heat pump disconnect, voltmeter shows voltage on
the line side but not on the load side.
Check fuses and circuit breaker.Reset circuit breaker or replace fuses with proper
Voltmeter shows abnormally low voltage at heat pump
disconnect switch (below 95% of serial plate voltage).
signals at unit.
Check transformer secondary voltage circuit breaker.Reset breaker, if tripped.
contactor and capacitor.
Check controller display for fault.Address lockout and reset controller.
Ensure that compressor is cool and overload has
had sufficient time to reset. Ohmmeter shows a
resistance across R & S terminals and OPEN or
infinite resistance between C & R or C & S terminals.
Ohmmeter shows no resistance or OPEN between
common and run terminals. *NOTE: Make sure the
compressor is rested.
Voltage on line side and contactor pulled in, but no
voltage on one or both terminals on the load side.
Voltage on line side, 24VAC across contactor coil and
no voltage on load side.
Voltage on line side of contactor verified and contactor
won’t pull in. No 24VAC on compressor contactor coil
when 24VAC is present at controller and controller
fuse is intact.
Measure resistance across capacitor terminals.
If shorts exist, capacitor is defective.
Verify voltage across 240VAC L1 IN & L2 IN.If no voltage, on L1 and L2, check wiring on board and
Verify line voltage at motor.If power at motor, verify control signals.
Determine why the disconnect switch was opened.
Close disconnect if safe to do so.
size and type. Verify total load on system and proper
fuse / circuit breaker sizing.
Call power company.
Replace, if defective.
If no, or low secondary, check transformer wiring
If wiring ok, replace transformer.
Repair wiring, if needed.
If windings are open or overload is faulty, replace
compressor.
Troubleshoot cause and replace motor
Points damaged. Replace contactor.
Bad coil, replace contactor.
Replace controller.
Replace, if faulty.
top of contactor; repair wiring as needed.
capacitor, if defective.
22
GEO16-501.4
TROUBLESHOOTING
Table 23.1 - Troubleshooting
Fault
Unit “short
cycles”
Low pressure
cutout
High pressure
cutout
Mode
Htg Clg
XX
XX
XX
XXWiring and controls Examine all wiring points.Tighten all wiring points.
X
X
X
XX
X
XX
XX
X
X
XX
XX
XX
XX
Possible CauseVerifyAction
Dirty Air FilterCheck air filterReplace, if necessary.
Thermostat location Check to see if thermostat is installed near a supply
Defective
compressor
overloads
Reduced water flow Check flow center operationTroubleshoot flow center
Scaled or plugged
coaxial coil
Water supply too
cold
Entering air too cold Measure return air, should be above 60ºF.Bring return air temperature within design parameters.
X
Reduced air flowVerify blower operation.Troubleshoot blower operation.
X
Low refrigerant
charge
Plugged bi-flow
filter / drier
Restricted TXVVerify superheat and subcooling values.Replace, if necessary.
Defective low
pressure switch
Reduced water
flow
X
Water supply too
X
hot
Scaled or plugged
X
coaxial coil
Reduced or no air
flow in heating
Air temperature out
of range
Defective high
pressure switch
Overcharged with
refrigerant
Restricted TXVVerify superheat and subcooling values.Replace, if necessary.
Non-condensables
in system
Loss of control
X
signal
air grill.
Ensure that compressor is cool and overload has
had sufficient time to reset. Ohmmeter shows a
resistance across R & S terminals and OPEN or
infinite resistance between C & R or C & S terminals.
Manually open water valve and measure water flow.Adjust to proper flow rate.
Plugged water strainer or filter.Replace or clean, if dirty.
Check temperature drop across coaxial coil.Clean, if necessary.
Verify GEO IN with temperature probe.Verify loop sizing; verify that all air has been purged
Check air filter.Replace or clean, if dirty.
Check for airflow restrictions in ducting system.Address any ductwork airflow restrictions.
Check external static.Check external static against blower table.
Check for refrigerant leaks.If leaks found, evacuate, repair and recharge to factory
Verify that low pressure cut-out occurs in heating
mode and not in cooling mode.
Check for airflow restrictions in ducting system.Address any ductwork airflow restrictions.
Check external static.Check external static against blower table.
Measure return air, should be below 95ºF.Bring return air temperature within design parameters.
Monitor discharge pressure while operating, verify high
pressure cut-out pressure (600 +/- 25 psig).
Verify superheat and subcooling values.Evacuate and recharge to factory recommended
Verify superheat and subcooling values.Evacuate and recharge to factory recommended
In cooling mode, verify 24VAC at RV coil and at REV
terminals.
Relocate, if necessary.
If windings are open or overload is faulty, replace
compressor.
from ground heat exchanger; bring water temperature
within design parameters.
recommended charge.
Replace filter, if necessary.
If defective, replace.
design parameters.
Replace, if defective.
charge.
charge.
If 24VAC exists, troubleshoot RV and coil.
If no control signal, troubleshoot thermostat signals.
GEO16-501.4
23
TROUBLESHOOTING
Table 24.1 - Troubleshooting
Fault
Unit will not
operate in
cooling mode
Insufficient
cooling or
heating
Condensate
overflow
Auxiliary
heater
is always
“ON”
Noisy unit
Mode
Htg Clg
X
X
X
X
XX
XX
XX
X
X
X
XX
XX
XX
XX
X
X
X
X
XX
XX
XX
X
X
X
X
XX
XX
XX
XX
XX
Possible CauseVerifyAction
Defective reversing
valve
Thermostat setup /
wiring
Thermostat operation Verify proper thermostat signals to unit.Replace, if necessary.
No water flow, high
pressure cutout
Dirty Air FilterCheck air filter.Replace or clean, if dirty.
Unit undersizedVerify load calculations and unit selection.If excessive, it may possible to rectify with shading and
Thermostat locationCheck to see if thermostat is installed near a supply air
Defective reversing
valve
Reduced or no air
flow in heating
Reduced air flow in
cooling
Duct lossesCheck supply and return air temperatures at heat
Ambient lossesCheck for losses / gains due to ambient air infiltration
Low refrigerant
charge
Scaled or plugged
coaxial coil
Reduced water flowCheck flow center operation.Troubleshoot flow center.
Water supply too hot Verify GEO IN with temperature probe..Verify loop sizing; bring water temperature within design
Reduced water flowCheck flow center operation.Troubleshoot flow center.
Water supply too
cold
Restricted TXVVerify superheat and subcooling values.Replace, if necessary.
CompressorTroubleshoot compressor operation.If discharge pressure is too low and suction pressure
Non-condensables in
system
Blocked drainCheck for blockage and clean drain.
Improper trapCheck trap dimensions and location.
Poor drainageCheck piping slope, away from unit and toward outlet.
Defective auxiliary
heater PCB
CompressorMake sure the compressor is not in direct contact with
Rattles and vibratesCheck for loose screws, panels, or internal components.
Air flow is noisyUndersized duct work will cause high airflow velocities
Pump cavitationPurge air from closed loop system.
Verify operation of reversing valve and solenoid coil.If defective, replace. When it is necessary to replace the
Verify thermostat setup and wiring.Repair wiring, if needed.
Check flow with flow meter.Check pump operation.
grill.
Verify operation of reversing valve and solenoid coil.
Defective reversing valve creating bypass of refrigerant
from discharge to suction side of compressor.
Check for airflow restrictions in ducting system.Address any ductwork airflow restrictions.
Check external static.Check external static against blower table.
pump and at furthest registers. If difference is significant,
duct losses are occurring.
through doors and windows.
Check superheat and subcooling values. Check for
refrigerant leaks.
Check temperature drop across coaxial coil.Replace or clean, if dirty.
Manually open water valve and measure water flow.Adjust to proper flow rate.
Plugged water strainer or filter.Clean or replace.
Manually open water valve and measure water flow.Adjust to proper flow rate.
Plugged water strainer or filter.Replace or clean, if dirty.
Verify GEO IN with temperature probe.Verify loop sizing; bring water temperature within design
Verify superheat and subcooling values.Evacuate and recharge to factory recommended charge.
Check venting.
Cycle power to system, using an amp meter verify
amperage draw.
Check 24VAC voltage signals to the auxiliary heater
printed circuit board.
the base or sides of the cabinet. Cold surroundings can
cause liquid slugging, increase ambient temperature.
Remove compressor mounting bolts.
Tighten and secure. Piping could be hitting the metal
surfaces. Add insulation between the contact.
and noisy operation.
reversing valve, wrap it with a wet cloth and direct the
heat away. Excessive heat can damage the valve.
insulation.
Relocate, if necessary.
Replace, if defective. When it is necessary to replace the
reversing valve, wrap it with a wet cloth and direct the
heat away. Excessive heat can damage the valve.
Repair duct losses.
Address issue.
If leaks found, evacuate, repair and recharge to factory
recommended charge.
parameters.
parameters.
too high, compressor is not pumping properly. Replace
compressor.
Replace printed circuit board.
Replace printed circuit board.
24
GEO16-501.4
SPLIT UNIT START UP / TROUBLESHOOTING FORM
Technician Notes
Customer Name ___________________________________________________ Date _________________________
Address _______________________________________________________________ Loop Type _________________
Model # ________________________________ Serial # ______________________________ Antifreeze ____________
Note: In order to maintain optimal performance, DO NOT hook up pressure gauges during start up procedures. When
troubleshooting, conduct water side analysis first. If water-side performance is poor, use of pressure gauge and
refrigerant side analysis may be required.
GEO16-501.4
25
THIS PAGE INTENTIONALLY LEFT BLANK
26
GEO16-501.4
THIS PAGE INTENTIONALLY LEFT BLANK
GEO16-501.4
27
COMMERCIAL WARRANTY (For Residential Warranty, see GEO16-510)
Seller warrants its products to be free from defects in material and
workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use
of materials substituted under emergency conditions for materials normally
employed. This warranty covers replacement of any parts furnished from the
factory of Seller, but does not cover labor of any kind and materials not
furnished by Seller, or any charges for any such labor or materials, whether
such labor, materials or charges thereon are due to replacement of parts,
adjustments, repairs, or any other work done. This warranty does not apply to
any equipment which shall have been repaired or altered outside the factory of
Seller in any way so as, in the judgment of Seller, to affect its stability, nor
which has been subjected to misuse, negligence, or operating conditions in
excess of those for which such equipment was designed. This warranty does
not cover the effects of physical or chemical properties of water or steam or
other liquids or gases used in the equipment.
BUYER AGREES THAT SELLER’S WARRANTY OF ITS PRODUCTS TO BE
FREE FROM DEFECT IN MATERIAL AND WORKMANSHIP, AS LIMITED
HEREIN, SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER
WARRANTIES, EITHER EXPRESS OR IMPLIED, WHETHER ARISING
FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE,
THERE ARE NO OTHER WARRANTIES, INCLUDING WARRANTY OF
MERCHANTABILITY OR FITNESS FOR PURPOSE, WHICH EXTEND
BEYOND THE PRODUCT DESCRIPTION CONFIRMED BY BUYER AND
SELLER AS OF THE DATE OF FINAL AGREEMENT.
This warranty is void if the input to the product exceeds the rated input as
indicated on the product serial plate by more than 5% on gas-fired and oil-fired
units, or if the product in the judgment of SELLER has been installed in a
corrosive atmosphere, or subjected to corrosive fluids or gases, been subjected
to misuse, negligence, accident, excessive thermal shock, excessive humidity,
physical damage, impact, abrasion, unauthorized alterations, or operation
contrary to SELLER’S printed instructions, or if the serial number has been
altered, defaced or removed.
BUYER AGREES THAT IN NO EVENT WILL SELLER BE LIABLE FOR
COSTS OF PROCESSING, LOST PROFITS, INJURY TO GOODWILL, OR
ANY OTHER CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY KIND
RESULTING FROM THE ORDER OR USE OF ITS PRODUCT, WHETHER
ARISING FROM BREACH OF WARRANTY, NONCONFORMITY TO
ORDERED SPECIFICATIONS, DELAY IN DELIVERY, OR ANY LOSS
SUSTAINED BY THE BUYER.
BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL
OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR
REPLACEMENT AT THE FACTORY OF SELLER, ANY COMPONENT WHICH
SHALL, WITHIN THE APPLICABLE WARRANTY PERIOD DEFINED HEREIN
AND UPON PRIOR WRITTEN APPROVAL, BE RETURNED TO SELLER
WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE
EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE;
EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A
COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER,
BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE
LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. FOR
GAS-FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS
AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS, BUYER’S
REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO
TEN YEARS FROM DATE OF SHIPMENT FROM SELLER.
These warranties are issued only to the original owner-user and cannot be
transferred or assigned. No provision is made in these warranties for any
labor allowance or field labor participation. Seller will not honor any expenses
incurred in its behalf with regard to repairs to any of Seller’s products. No
credit shall be issued for any defective part returned without proper written
authorization (including, but not limited to, model number, serial number,
date of failure, etc.) and freight prepaid.
OPTIONAL SUPPLEMENTAL WARRANTY
Provided a supplemental warranty has been purchased, Seller extends the
warranty herein for an additional four (4) years on certain compressors.
Provided a supplemental warranty has been purchased, Seller extends the
warranty herein for an additional four (4) years or nine (9) years on certain
heat exchangers.
EXCLUSION OF CONSUMABLES & CONDITIONS BEYOND SELLER’S
CONTROL
This warranty shall not be applicable to any of the following items: refrigerant
gas, belts, filters, fuses and other items consumed or worn out by normal wear
and tear or conditions beyond Seller’s control, including (without limitation as
to generality) polluted or contaminated or foreign matter contained in the air or
water utilized for heat exchanger (condenser) cooling or if the failure of the part
is caused by improper air or water supply, or improper or incorrect sizing of
power supply.
Component
Applicable Models
Heat Exchangers
Gas-Fired Units
Heat Exchangers
Low Intensity Infrared Units
Compressors
Condensing Units for Cassettes
Burners
Low Intensity Infrared Units
Other
Components excluding Heat Exchangers,
Coils, Condensers, Burners, Sheet Metal
Heat Exchangers/Coils
Indoor and Outdoor Duct Furnaces and
System Units, Steam/Hot Water Units,
Oil-Fired Units, Electric Units, Cassettes,
Vertical Unit Ventilators, Geothermal Units
Compressors
Vertical Unit Ventilators, Geothermal Units
Burners
High Intensity Infrared Units
Sheet Metal Parts
All Products
TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE
HUNDRED TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER
OCCURS FIRST
FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN SIXTY-SIX
MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
EIGHTEEN MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
“APPLICABLE WARRANTY PERIOD”
As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.