Modine Manufacturing DFP, DFP75, DFP100, DFP125, DFP150 Service Manual

...
5-564
C
US
5H080637A
December, 2008
INSTALLATION AND SERVICE MANUAL
model DFP
All models approved for use in California by the CEC
FOR YOUR SAFETY
IF YOU SMELL GAS:
1. Open windows.
2. Don’t touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death, and could cause exposure to substances which have been determined by various state agencies to cause cancer, birth defects or other reproductive harm. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
CAUTION
To prevent premature heat exchanger failure do not locate ANY gas-fired units in areas where chlorinated, halogenated, or acid vapors are present in the atmosphere.
FOR YOUR SAFETY
The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
IMPORTANT
The use of this manual is specifically intended for a qualified installation and service agency. A qualified installation and service agency must perform all installation and service of these appliances.
Inspection on Arrival
1. Inspect unit upon arrival. In case of damage, report it immediately to transportation company and your local factory sales representative.
2.
Check rating plate on unit to verify that power supply meets available electric power at the point of installation.
3. Inspect unit upon arrival for conformance with description of product ordered (including specifications where applicable).
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
THIS MANUAL IS THE PROPERTY OF THE OWNER.
5-564
SPECIAL PRECAUTIONS / TABLE OF CONTENTS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE, EFFICIENT AND TROUBLE-FREE OPERATION. IN ADDITION, PARTICULAR CARE MUST BE EXERCISED REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW. FAILURE TO PROPERLY ADDRESS THESE CRITICAL AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS, PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS ARE SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which, if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided, MAY result in a potential safety concern.
DANGER
Appliances must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
WARNING
1. Gas fired heating equipment must be vented - do not operate unvented.
2. A built-in power exhauster is provided - additional external power exhausters are not required or permitted.
3. If you are replacing an existing heater, it may be necessary to resize the venting systems. Improperly sized venting systems can result in vent gas leakage or the formation of condensate. Refer to the National Fuel Gas Code ANSI Z223.1 or CSA B149.1 latest edition. Failure to follow these instructions can result in injury or death.
4. Under no circumstances should two sections of double wall vent pipe be joined together within one horizontal vent system due to the inability to verify complete seal of inner pipes.
5. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing.
6. Gas pressure to appliance controls must never exceed 14" W.C. (1/2 psi).
7. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
8. All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
9. To reduce the opportunity for condensation, the minimum sea level input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or 5% below the minimum rated input of duel rated units.
10. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% greater than the rated voltage.
11. Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature rating of at least 105°C.
12.
When servicing or repairing this equipment, use only factory-
approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine Manufacturing Company. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owners risk.
2
2
5-564
CAUTION
1. Purging of air from gas lines should be performed as described in ANSI Z223.1 - latest edition “National Fuel Gas Code”, or in Canada in CAN/CGA-B149 codes.
2. Do not attempt to reuse any mechanical or electrical controllers which have been wet. Replace defective controller.
3. Ensure that the supply voltage to the application, as indicated on the serial plate, is not 5% less than the rated voltage.
IMPORTANT
1. To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acid) are present in the atmosphere.
2. To prevent premature heat exchanger failure, the input to the appliance, as indicated on the serial plate, must not exceed the rated input by more than 5%.
3. To prevent premature heat exchanger failure, observe heat exchanger tubes by looking at the heat exchanger through field installed access openings in connecting ductwork. If the bottom of the tubes become red while blower and duct furnace are in operation, additional baffles must be inserted between blower and duct furnace to assure uniform air flow across the heat exchanger.
4. To prevent premature heat exchanger failure, with all control systems, a blower starting mechanism must be provided so that the blower is running or energized within 45 seconds of the gas control operation.
5. Start-up and adjustment procedures should be performed by a qualified service agency.
6. To check most of the Possible Remedies in the troubleshooting guide listed in Table 20.1, refer to the applicable sections of the manual.
Table of Contents
Inspection on Arrival ................................................................. 1
Special Precautions .................................................................. 2
SI (Metric) Conversion Factors ................................................. 3
Unit Location ............................................................................. 3
Location Recommendations .............................................. 3
Combustible Material and Service Clearances ................. 3
Combustion Air Requirements ........................................... 3
Unit Suspension ....................................................................... 4
Installation ................................................................................ 4
Direction of Airflow ............................................................. 4
Duct Installation and Airflow Distribution ........................ 4-5
Venting ........................................................................... 5-6
Gas Connections ............................................................... 7
Electrical Connections ....................................................... 8
Start-Up Procedure ................................................................... 8
Pilot Burner and Main Burner Adjustment ......................... 9
Air Shutter Adjustment ..................................................... 10
Control Operating Sequence ...................................... 11-13
Variable Air Movement Applications ................................ 13
Gas Control Options ................................................... 13-14
Dimensional Data ................................................................... 15
Performance ........................................................................... 16
Air Temperature and External Static Pressure Limits ...... 16
Pressure Drop Curves ............................................................ 17
Maintenance ........................................................................... 18
Manifold Assembly Removal ........................................... 18
Burner and Pilot Assembly Removal .......................... 18-19
Service & Troubleshooting .................................................20-21
Replacement Parts Ordering .................................................. 22
Model Identification ................................................................. 22
Commercial Warranty ................................................ Back Page
SI (METRIC) CONVERSION FACTORS / UNIT LOCATION
SI (METRIC) CONVERSION FACTORS
Table 3.1
To Convert Multiply By To Obtain
"W.C. 0.24 kPa psig 6.893 kPa °F (°F-32) x 0.555 °C inches 25.4 mm feet 0.305 meters CFM 0.028 m3/min
To Convert Multiply By To Obtain
CFH 1.699 m3/min Btu/ft3 0.0374 mJ/m pound 0.453 kg Btu/hr 0.000293 kW/hr gallons 3.785 liters psig 27.7 "W.C.
3
UNIT LOCATION
DANGER
Appliances must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
IMPORTANT
To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acid) are present in the atmosphere.
Location Recommendations
1. When locating the furnace, consider general space and heating requirements, availability of gas and electrical supply, and proximity to vent locations.
2. Unit must be installed on the positive pressure side of the circulating blower.
3. Be sure the structural support at the unit location site is adequate to support the weight of the unit. For proper operation the unit must be installed in a level horizontal position.
4. Do not install units in locations where the flue products can be drawn into the adjacent building openings such as windows, fresh air intakes, etc.
5. Be sure that the minimum clearances to combustible materials and recommended service clearances are maintained. Units are designed for installation on non­combustible surfaces with the minimum clearances shown in Figure 3.1 and Tables 3.2 and 3.3.
6. Units installed downstream of refrigeration systems, or exposed to inlet air temperatures of 40°F or less, may experience condensation, therefore, provisions should be made for disposal of condensate. Means have been provided in the bottom pan of the unit to accommodate a condensate drain line connection flange.
7. When locating units, it is important to consider that the exhaust vent piping must be connected to the outside atmosphere.
8. In garages or other sections of aircraft hangars such as offices and shops which communicate with areas used for servicing or storage, keep the bottom of the unit at least 7” above the floor. In public garages, the unit must be installed in accordance with the Standard for Parking Structures NFPA #88A and the Standard for Repair Garages NFPA #88B. In Canada, installation of unit heaters in airplane hangars must be in accordance with the requirements of the enforcing authority, and in public garages in accordance with the current CAN/CGA-B149 codes.
9. Do not install units in locations where gas ignition system is exposed to water spray, rain, or dripping water.
Figure 3.1 - Combustible Material and Service
Clearances
C
Access
Slide
B
A
D"
A 3'' minimum clearance to combustible material is required from the vent collar.
Table 3.2 - Combustible Material Clearances
Clearance to Combustible Materials Model Access Size Side Side (C) (D) (A) (B)
75 12" 1" 3" 2"
100/125 12" 1" 3" 2"
150/175 12" 1" 3" 2"
200/225 12" 2" 3" 2"
250/300 12" 2" 3" 2"
350/400 12" 2" 3" 2"
Non-Access
Top Bottom
Table 3.3 - Service Clearances
Recommended Service Clearance
Model Access Non-Access Top Bottom Size Side Side (C) (D)
(A) (B)
75 18" 6" 10" 0" 100/125 20" 6" 10" 0" 150/175 25" 6" 10" 0" 200/225 27" 6" 10" 0" 250/300 30" 6" 10" 0" 350/400 41" 6" 10" 0"
Combustion Air Requirements
Units installed in tightly sealed buildings or confined spaces must be provided with two permanent openings, one near the top of the confined space and one near the bottom. Each opening should have a free area of not less than one square inch per 1,000 BTU per hour of the total input rating off all units in the enclosure, freely communicating with interior areas having, in turn adequate infiltration from the outside. For further details on supplying combustion air to a confined (tightly sealed) space or unconfined space, see the National Fuel Gas Code ANSI Z223.1 of CAN/CGA B149.1 or .2 Installation Code, latest edition.
5-564
33
UNIT SUSPENSION / INSTALLATION
UNIT SUSPENSION
Be sure the means of suspension is adequate to support the weight of the unit (see Dimensional Data for unit weights). For proper operation, the unit must be installed in a level horizontal position. Combustible material and service clearances as specified in Figure 3.1 and Tables 3.2 and 3.3 must be strictly maintained.
1. Four 1/2" - 13NC tapped holes in top of furnace are provided to accept ceiling hangers. To assure that flames are directed into the center of the heat exchanger tubes, the furnace must be supported in a vertical position. Use a spirit level to ensure that unit is suspended correctly.
2. NOTE: A pipe hanger adapter kit, shown in Figure 4.1, is available as an accessory. One kit consists of two drilled 3/4" IPS pipe caps and two 1/2 - 13 x 1-3/4" capscrews to facilitate threaded pipe suspension. Two kits are required for mounting all duct furnace models.
Figure 4.1 - Suspension Methods
Duct Installation
1. The furnace is designed to accept straight ductwork. See Figure 4.3. Provide an airtight seal between the ductwork and the furnace. Seams with cracks in ductwork should be caulked and/or taped and be of permanent type. All duct connections MUST be airtight to prevent air leakage.
2. Provide removable access panels on both the upstream and downstream sides of the ductwork; see Figure 4.3. These openings should be large enough to view smoke or reflect light inside the casing to indicate leaks in the heat exchanger and to check for hot spots on heat exchangers due to poor air distribution or lack of sufficient air (CFM)
Figure 4.3 - Duct Connections
C
INSTALLATION
Direction of Airflow
Select proper direction of airflow. The air baffle must face the air inlet direction as shown in Figure 4.2. If it is necessary to reverse the airflow direction, remove the four screws securing the air distribution baffle, reverse the air distribution baffle to the air inlet side and replace the screws. See Airflow Reversal Note.
Figure 4.2 - Air Distribution Baffle Location
Baffle location shown on entering air side of duct furnace.
AIR
DISTRIBUTION
BAFFLE
Airflow Distribution
IMPORTANT
To prevent premature heat exchanger failure, observe heat exchanger tubes by looking at the heat exchanger through field installed access openings in connecting ductwork. If the bottom of the tubes become red while blower and duct furnace are in operation, additional baffles must be inserted between blower and duct furnace to assure uniform air flow across the heat exchanger.
1. Provide uniform air distribution over the heat exchanger. Use turning vanes where required (see Figure 5.1) to obtain uniform air distribution. Avoid installing as in “G”, “H” & “J” of Figure 5.1.
2. A bottom, horizontal discharge type blower should be installed at least 12" from the furnace (See “A”, Figure 5.1).
3. A top, horizontal discharge type blower should be installed at least 24" from the furnace (See “B”, Figure 5.1). Provide air baffle at top of duct to deflect air down to the bottom of heat exchanger.
Airflow Reversal Note: If factory installed discharge air options (thermostat, freeze protection, etc.) were provided, these options would have to be relocated to the discharge air side of the duct furnace.
4
5-564
INSTALLATION
Figure 5.1 - Typical Duct & Airflow Installation
3" Max.
Turning
Vanes
3" Min.
B
B
A
12"
Min.
A
Baffle
SIDE VIEW
12"
Min.
SIDE VIEW
Air
Baffle
24"
Min.
G
POOR
3" Max.
RECOMMENCED INSTALLATIONS
RECOMMENDED INSTALLATIONS
3" Max.
B
Turning
Vanes
Baffle
12"
Min.
A
3" Min.
B
Air
Baffle
24"
Min.
SIDE VIEW
Turning
Vanes
3" Max.
15° Max.
Turning
Vanes
B
Baffle
12"
Min.
A
SIDE VIEW
INSTALLATIONS NOT RECOMMENDED
H
POOR
3" Min.
Turning
Van es
Dimensions “B” should never be less than
CA
12"
Min.
B
A
15° Max.
TOP VIEW
FED
Turning
12"
Min.
Turning
Vanes
Van es
15° Max.
TOP VIEW
J
POOR
1
¼2 of “A”.
No Air
SIDE VIEW
No Air
SIDE VIEW
No Air
TOP VIEW
5-564
5
INSTALLATION
Venting
WARNING
1. Gas fired heating equipment must be vented - do not operate unvented.
2. A built-in power exhauster is provided - additional external power exhausters are not required or permitted.
3. If you are replacing an existing heater, it may be necessary to resize the venting systems. Improperly sized venting systems can result in vent gas leakage or the formation of condensate. Refer to the National Fuel Gas Code ANSI Z223.1 or CSA B149.1 latest edition. Failure to follow these instructions can result in injury or death.
4. Under no circumstances should two sections of double wall vent pipe be joined together within one horizontal vent system due to the inability to verify complete seal of inner pipes.
NOTE: A vent is the vertical passageway used to convey flue gases from the unit or the vent connector to the outside atmosphere. A vent connector is the pipe which connects the unit to a vent or chimney. Vent connectors serving Category I appliances shall not be connected into any portion of mechanical draft systems operating under positive pressure.
General Venting Instructions
1. Installation of venting must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - Latest Edition. In Canada, installation must be in accordance with CAN/CGA-B149.1 for natural gas units and CAN/CGA-B149.2 for propane units.
2. All vertically vented units are Category I. All horizontally vented units are Category III. The installation must conform to the requirements from Table 6.2 in addition to those listed below.
3. For units vented as Category I, refer to Table 6.1 for vent sizing. Vent sizing for units vented as Category III are covered in a later section on page 7. Do not use a vent pipe smaller than the size of the outlet or vent transition of the appliance. The pipe should be suitable corrosion resistant material. Follow the National Fuel Gas Code for minimum thickness and composition of vent material. The minimum thickness for connectors varies depending on the pipe diameter.
Table 6.1 - Vertical Category I Vent Sizing Requirements
Vent Connector
Model Size
75-125
150-175 4" 5"
200 6" 6"
225-400
Requires a 4" to 5" adapter for the larger vent pipe diameter.
4. For Category I vent systems limit length of horizontal runs to 75% of vertical height. Install with a minimum upward slope from unit of 1/4 inch per foot and suspend securely from overhead structure at points no greater than 3 feet apart. For best venting, put vertical vent as close to the unit as possible. A minimum of 12" straight pipe is recommended from the power exhauster outlet before turns in the vent system. Fasten individual lengths of vent together with at least three corrosion-resistant sheet-metal screws.
5. It is recommended that vent pipes be fitted with a tee with a drip leg and a clean out cap to prevent any moisture in the vent pipe from entering the unit. The drip leg should be inspected and cleaned out periodically during the heating season.
6. The National Fuel Gas Code requires a minimum clearance of 6 inches from combustible materials for single wall vent pipe. The minimum distance from combustible materials is based on the combustible material surface not exceeding 160°F. Clearance from the vent pipe (or the top of the unit) may be required to be greater than 6 inches if heat damage other than fire (such as material distortion or discoloration) could result.
Diameter
4" 4"
6” 6”
Minimum Vent Pipe
Diameter
7. Avoid venting through unheated space. When venting does pass through an unheated space, insulate runs greater than 5 feet to minimize condensation. Inspect for leakage prior to insulating and use insulation that is noncombustible with a rating of not less than 350°F. Install a tee fitting at the low point of the vent system and provide a drip leg with a clean out cap as shown in Figure 7.1.
Table 6.2 - ANSI Venting Requirements
Appliance Venting Category Description Requirements
I Negative vent pressure Follow standard venting Non-condensing requirements.
II Negative vent pressure Condensate must be Condensing drained.
III Positive vent pressure Vent must be gastight. Non-condensing
IV Positive vent pressure Vent must be liquid and Condensing gastight. Condensate must be drained.
8. When the vent passes through a combustible wall or floor, a metal thimble 4 inches greater than the vent diameter is necessary. If there is 6 feet or more of vent pipe in the open space between the appliance and where the vent pipe passes through the wall or floor, the thimble need only be 2 inches greater than the diameter of the vent pipe. If a thimble is not used, all combustible material must be cut away to provide 6 inches of clearance. Any material used to close the opening must be noncombustible.
9. Do NOT use dampers or other devices in the vent pipes.
10. Precautions must be taken to prevent degradation of
building materials by flue products.
11. For category I vent systems the outlet of the vent should
extend as shown in Figure 7.1 and Table 7.1 if the following conditions are met:
• Vent diameter is less than 12 inches, vent is of double wall construction and is a listed product, and the vent does not terminate within 2' of a vertical wall or similar obstruction.
• For vents that have a diameter of 12 inches or larger, constructed of single wall, or terminate within 2' of a vertical wall or similar obstruction, the vent pipe shall extend at least 2' higher than any portion of a building within a horizontal distance of 10' (refer to Figure 7.1).
12. Use a listed vent terminal to reduce downdrafts and
moisture in vent.
13. For instructions on common venting refer to the National
Fuel Gas Code.
14. The vent must terminate no less than 5' above the vent
connector for Category I vent systems.
15. A unit located within an unoccupied attic or concealed space
shall not be vented with single wall vent pipe.
16. Single wall vent pipe must not pass through any attic, inside
wall, concealed space, or floor.
17. Do NOT vent this appliance into a masonry chimney.
18. When condensation may be a problem, the venting system
shall not terminate over public walkways or over an area where condensation or vapor could create a nuisance or hazard or could be detrimental to the operation of regulator relief openings or other equipment.
19. In cold ambient conditions, such as Canada, the following
items are recommended for proper operation and equipment life:
• The vent pipe must not pass through an unheated space
or interior part of an open chimney unless the vent pipe is insulated.
• Where the vent pipe may be exposed to extreme cold, or
come into contact with snow or ice, the entire vent must be insulated or double wall (includes outdoors). It is preferred that the double wall vent is one continuous piece but a joint is allowed outside the building.
• The heater system shall be checked at least once a year
by a qualified service technician.
6
5-564
TEE WITH DRIP LEG
AND CLEANOUT CAP
AT LOW POINT OF
VENT SYSTEM
POWER EXHAUSTER OUTLET
PITCH VENT PIPE DOWNWARD
FROM UNIT 1/4" PER FOOT
12"
Min.
GARY STEEL
MODEL 1092 TERMINAL
INSTALLATION
Figure 7.1 - Vertical Category I Vent System
LISTED TERMINAL
EXHAUST
12" MIN
4" MIN
* SIZE ACCORNING TO EXPECTED SNOW DEPTH.
"H" MIN*
ROOF FLASHING
TEE WITH DRIP LEG AND CLEANOUT CAP
(SLOPE 1/4" PER FOOT DOWNWARD TOWARD DRIP LEG)
ROOF FLASHING
TEE WITH DRIP LEG AND CLEANOUT CAP
(SLOPE 1/4" PER FOOT DOWNWARD TOWARD DRIP LEG)
X
ROOF PITCH IS:
X / 12
BACK VIEW
TO WALL OR ADJOINING BUILDING
12
USE LISTED THIMBLE THROUGH ROOF AND CEILING
2' MIN
TERMINAL
USE THIMBLE THROUGH
CELLING
2' MIN*
4" MIN
EXHAUST
12" MIN
RECOMMENDED
RECOMMENDED
Table 7.1 - Minimum Height from Roof to Lowest Discharge Opening
Rise X (in) Roof Pitch Min Height H (ft)
0-6 Flat to 6/12 1.00
6-7 6/12 to 7/12 1.25
7-8 7/12 to 8/12 1.50
8-9 8/12 to 9/12 2.00
9-10 9/12 to 10/12 2.50
10-11 10/12 to 11/12 3.25
11-12 11/12 to 12/12 4.00
12-14 12/12 to 14/12 5.00
14-16 14/12 to 16/12 6.00
16-18 16/12 to 18/12 7.00
18-20 18/12 to 20/12 7.50
20-21 20/12 to 21/12 8.00
Size according to expected snow depth.
Additional Requirements for Horizontally Vented Category III Units
1. Seal the joints with a metallic tape or silastic suitable for temperatures up to 350°F. (3M tapes 433 or 363 are acceptable.) Wrap tape two full turns around the vent pipe.
2. Refer to Table 7.2 for total minimum and maximum vent lengths making the vent system as straight as possible. The equivalent length of a 90° elbow is 5 feet for 4" diameter and 7 feet for 6" diameter.
Table 7.2 - Horizontal Category III Vent Sizing Requirements
Vent Connector
Model Size
75
100-175
200
225 250-300 350-400
Unit can be vented with 5" diameter pipe if a 6" to 5" reducer is used.
Otherwise, use 6" pipe.
Diameter
4" 4" 48' 4" 4" 55' 6" 6" 6" 6" 63' 6" 6" 70'
3. The vent terminal must be a Gary Steel 1092.
4. The vent must extend a minimum of 12" beyond the exterior wall surface as shown in Figure 7.2. The vent must be supported as shown in Figure 7.3. Precautions must be taken to prevent degradation of building materials by flue products.
5. The vent system shall terminate at least 3 feet above any
forced air inlet (except direct vent units) located within 10 feet,
and at least 4 feet below, 4 feet horizontally from, or 1 foot above any door, window, or gravity air inlet into any building. The bottom of the vent terminal shall be located above the snow line or at least 1 foot above grade; whichever is greater. When located adjacent to public walkways the vent system shall terminate not less than 7 feet above grade.
6. The venting system must be exclusive to a single unit, and no other unit is allowed to be vented into it.
7. Horizontally vented units must use single wall vent pipe although one continuous section of double wall vent pipe may be used with the vent system. Under no circumstances should two sections of double wall vent pipe be joined together within one vent system due to the inability to verify complete seal of inner pipes.
Minimum Vent Pipe Diameter
5" 70'
6" 70'
Maxium Vent
Length
Figure 7.2 - Horizontal Venting
Figure 7.3 - Venting Through Combustible Walls
METAL FACE
PLATE
45
1"
FIBER GLASS
INSULATION
MIN. 2"
12" min
1"
9"
9"
VENT TERMINATION SUPPORT BRACKET
(where required)
(Make from 1" x 1" steel angle)
VENT PIPE DIAMETER
2" MIN.
2" MIN.
METAL
SLEEVE
METAL
SLEEVE
5-564
7
INSTALLATION
Gas Connections
WARNING
1. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing.
2. Gas pressure to appliance controls must never exceed 14"
W.C. (1/2 psi).
3. To reduce the opportunity for condensation, the minimum sea
level input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or 5% below the minimum rated input of duel rated units.
CAUTION
Purging of air from gas lines should be performed as described in ANSI Z223.1 - latest edition “National Fuel Gas Code”, or in Canada in CAN/CGA-B149 codes.
IMPORTANT
To prevent premature heat exchanger failure, the input to the appliance, as indicated on the serial plate, must not exceed the rated input by more than 5%.
1. Installation of piping must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - Latest Edition. In Canada, installation must be in accordance with CAN/CGA-B149.1 for natural gas units and CAN/CGA-B149.2 for propane units.
2. Piping to units should conform with local and national requirements for type and volume of gas handled, and pressure drop allowed in the line. Refer to Table 10.1 to determine the cubic feet per hour (cfh) for the type of gas and size of unit to be installed. Using this cfh value and the length of pipe necessary, determine the pipe diameter from Table 8.1. Where several units are served by the same main, the total capacity, cfh and length of main must be considered. Avoid pipe sizes smaller than 1/2". Table 8.1 allows for a 0.3"
W.C. pressure drop in the supply pressure from the building main to the unit. The inlet pressure to the unit must be 6-7" W.C. for natural gas and 11-14" W.C. for propane gas. When sizing the inlet gas pipe diameter, make sure that the unit supply pressure can be met after the 0.3" W.C. has been subtracted. If the 0.3" W.C. pressure drop is too high, refer to the Gas Engineer’s Handbook for other gas pipe capacities.
3. The gas piping to the unit can enter the unit from the side of the unit or from below. Install a ground joint union with brass seat and a manual shut-off valve external of the unit casing, and adjacent to the unit for emergency shut-off and easy servicing of controls, including a 1/8" NPT plugged tapping accessible for test gauge connection (See Figure 8.1).
4. Provide a sediment trap before each unit in the line where low spots cannot be avoided. (See Figure 8.1).
5. When Pressure/Leak testing, pressures above 14" W.C. (1/2 psi), close the field installed shut-off valve, disconnect the appliance and its combination gas control from the gas supply line, and plug the supply line before testing. When testing pressures 14" W.C. (1/2 psi) or below, close the manual shut­off valve on the appliance before testing.
Figure 8.1 - Recommended Sediment Trap/Manual Shut-off Valve Installation - Side or Bottom Gas Connection
GAS
SUPPLY LINE
MANUAL GAS
TRAP
SHUT-OFF VALVE
PLUGGED
1/8" NPT TEST
GAGE CONNECTION
GAS
SUPPLY LINE
3"
MIN.
SEDIMENT
Manual shut-off valve is in the “OFF” position when handle is perpendicular to
pipe.
GROUND
JOINT
UNION
W/ BRASS
SEAT
TO
CONTROLS
Table 8.1 - Gas Pipe Capacities
Gas Pipe Capacities (Up to 14” W.C. Gas Pressure through Schedule 40 Pipe)
Length Pipe Diameter Of Pipe 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" (feet) Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane
10 132 83 278 175 520 328 1050 662 1600 1008 3050 1922
20 92 58 190 120 350 221 730 460 1100 693 2100 1323
30 73 46 152 96 285 180 590 372 890 561 1650 1040
40 63 40 130 82 245 154 500 315 760 479 1450 914
50 56 35 115 72 215 135 440 277 670 422 1270 800
60 50 32 105 66 195 123 400 252 610 384 1150 725
70 46 29 96 60 180 113 370 233 560 353 1050 662
80 43 27 90 57 170 107 350 221 530 334 990 624
90 40 25 84 53 160 101 320 202 490 309 930 586
100 38 24 79 50 150 95 305 192 460 290 870 548
125 34 21 72 45 130 82 275 173 410 258 780 491
150 31 20 64 40 120 76 250 158 380 239 710 447
8
Cubic Feet per Hour with Pressure Drop of 0.3” W.C.
Natural Gas - Specific Gravity - 0.60
Propane Gas - Specific Gravity - 1.50
5-564
INSTALLATION / START-UP PROCEDURE
Electrical Connections
WARNING
1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
3. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than rated voltage.
CAUTION
Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than rated voltage.
1. Installation of wiring must conform with local building codes, or in the absence of local codes, with the National Electric Code ANSI/NFPA 70 - Latest Edition. Unit must be electrically grounded in conformance to this code. In Canada, wiring must comply with CSA C22.1, Part 1, Electrical Code.
2. All duct furnaces are provided with a wiring diagram located
on the inside door of the electrical junction box. Refer to this wiring diagram for all wiring connections. For factory installed options and field installed accessory wiring, refer to Set A and Set B on the provided wiring diagram.
3. The power supply to the duct furnace should be protected
with a fused disconnect switch.
4. Refer to Table 9.1 to determine the amp draw of the duct
furnace by adding the amp draw for the control transformer (includes ignition controllers, gas valves, control relays, and amplifiers) and power exhauster together, based on the voltage and model size. Size the disconnect switch to cover the amp draw of the unit.
5. Refer to the unit dimensional drawing on page 15 for the
electrical knockout locations.
Table 9.1 - Unit Amps
Digit 14
Supply Voltage
A 115/60/1 0 0.35 0.65 1.3 2.17 1.4 2.4
B 208/60/1 0 0.19 0.36 0.72 1.2 0.7 1.4
C 230/60/1 0 0.17 0.33 0.65 1.09 0.6 1.3
D 208/60/3 0 0.19 0.36 0.72 1.2 0.7 1.4
E 230/60/3 0 0.17 0.33 0.65 1.09 0.6 1.3
F 460/60/3 0 0.09 0.16 0.33 0.54
G 575/60/3 0 0.07 0.13 0.26 0.43 0.24 0.52
Unit controls amp draw is included in master unit amp draw. Requires a 250 VA transformer.Requires a 500 VA transformer.For Digits F (460V) and G (575V), amp draw shown is on primary (line) side of
required step-down transformer.
Control Step Down
Transformer Amp Draw
Digit 15 - Transformer Model Size
0 1 2 3 4 75-175 200-400
Power Exhauster
Amp Draw
0.30 0.65
START-UP PROCEDURE
IMPORTANT
Start-up and adjustment procedures should be performed by a qualified service agency.
1. Turn off power to the unit at the disconnect switch. Check that fuses or circuit breakers are in place and sized correctly. Turn all hand gas valves to the “OFF” position.
2. Check that the supply voltage matches the unit supply voltage listed on the serial plate. Verify that all wiring is secure and properly protected. Trace circuits to insure that the unit has been wired according to the wiring diagram.
3. Check to insure that the venting system is installed and free from obstructions.
4. Check to see that there are no obstructions to the intake and discharge of the duct furnace.
5. Perform a visual inspection of the unit to make sure no damage has occurred during installation.
6. Turn on power to the unit at the disconnect switch. Check to insure that the voltage between terminals 1 and 2 is 24V.
7. Check the thermostat, ignition control, gas valve, power exhauster motor, and supply fan blower motor for electrical operation. If these do not function, recheck the wiring diagram. Check to insure that none of the Gas Control Options & Accessories (see page 14) have tripped.
8. Recheck the gas supply pressure at the field installed manual-shut-off valve. The inlet pressure should be 6"-7” W.C. on natural gas and 11"-14” W.C. on propane gas. If inlet pressure is too high, install an additional pressure regulator upstream of the combination gas control.
9. Open the field installed manual gas shut-off valve.
10. Open the manual main gas valve on the combination gas control. Call for heat with the thermostat. On a call for heat, the power exhauster relay will energize the power exhauster motor. Once the power exhauster motor has reached full speed, the differential pressure switch will close. Once closed, the ignition controller will attempt to light the pilot. If the pilot does not light, purge the pilot line. If air purging is required, disconnect the pilot line at outlet of pilot valve. In no case should the line be purged into heat exchanger. Check the pilot flame length (See Pilot Burner Adjustment).
11. Once the pilot has been established, check to make sure that the main gas valve opens. Check the manifold gas pressure (See Main Burner Adjustment) and flame length (See Air Shutter Adjustment) while the circulating air blower is operating.
12. Check to insure that gas controls sequence properly (See Control Operating Sequence). Verify if the unit has any additional control devices and set according to the instructions in the Gas Controls Options.
13. Once proper operation of the duct furnace has been verified, remove any jumper wires that were required for testing.
14. Close the electrical compartment door.
5-564
9
START-UP PROCEDURE
Pilot Burner Adjustment
The pilot burner is orificed to burn properly with an inlet pressure of 6-7" W.C. on natural gas and 11-14" W.C. on propane gas, but final adjustment must be made after installation. If the pilot flame is too long or large, it is possible that it may cause soot and/or impinge on the heat exchanger causing failure. If the pilot flame is shorter than shown, it may cause poor ignition and result in the controls not opening the combination gas control. A short flame can be caused by a dirty pilot orifice. Pilot flame condition should be observed periodically to assure trouble-free operation.
To Adjust the Pilot Flame
1. Create a call for heat from the thermostat.
2. Remove the cap from the pilot adjustment screw. For location, see the combination gas control literature supplied with unit.
3. Adjust the pilot length by turning the screw in or out to achieve a soft steady flame 3/4" to 1" long and encompassing 3/8"­1/2" of the tip of the thermocouple or flame sensing rod (See Figure 10.1).
4. Replace the cap from the pilot adjustment screw.
Figure 10.1 - Correct Pilot Flame
3/4" to 1"
Main Burner Adjustment
The gas pressure regulator (integral to the combination gas control) is adjusted at the factory for average gas conditions. It is important that gas be supplied to the duct furnace in accordance with the input rating on the serial plate. Actual input should be checked and necessary adjustments made after the duct furnace is installed. Over-firing, a result of too high an input, reduces the life of the appliance and increases maintenance. Under no circumstances should the input exceed that shown on the serial plate.
Measuring the manifold pressure is done at the tee in the manifold for premium gas controls (Digit 13=0, 1, 2, or 3) or at the pressure tap on the gas valve for standard gas controls (Digit 13=4)." (See Figure 10.2).
To Adjust the Manifold Pressure
1. Move the field installed manual shut-off valve to the “OFF” position.
2. Remove the 1/8" pipe plug in the pipe tee or gas valve and attach a water manometer of “U” tube type which is at least 12" high.
3. Move the field installed manual gas shut-off valve to the “ON” position.
4. Create a high fire call for heat from the thermostat.
5. Determine the correct high fire manifold pressure. For natural gas 3.5” W.C., for propane gas 10” W.C. Adjust the main gas pressure regulator spring to achieve the proper manifold pressure (for location, see the combination gas control literature supplied with unit).
6. If the unit has Electronic Modulation gas controls (determine from the Model Identification Digit 12), the low fire gas pressure needs to be adjusted. Using Figure 10.3 for item number locations, this is accomplished as follows:
a. Disconnect power. b. Remove all wires from Maxitrol Amplifier terminal “3” or
duct furnace terminal “43” (if available). c. Turn on power at the disconnect switch. d. Remove the maximum adjustment screw (4), spring
(5), and plunger (8). A small magnet is useful for this
purpose. CAUTION - The plunger is a precision part.
Handle carefully to avoid marring or picking up grease
and dirt. Do not lubricate. e. Using minimum adjusting screw (9), adjust low fire
manifold pressure to 0.56" W.C. for natural gas and
1.6" W.C. for propane gas.
f. Replace plunger and spring retainer, spring, and
maximum adjusting screw in proper order.
g. Using maximum adjustment screw (4), adjust high fire
manifold pressure to 3.5" W.C. for natural gas and 10"
W.C. for propane gas. h. Disconnect power. i. Replace cover plate (2) and re-install all wires from
Maxitrol amplifier terminal “3” or duct furnace terminal “43”.
7. After adjustment, move the field installed manual shut-off
valve to the “OFF” position and replace the 1/8" pipe plug.
8. After the plug is in place, move the field installed manual
shut-off valve to the “ON” position and recheck pipe plugs for gas leaks with soap solution.
Figure 10.3 - Maxitrol Modulating Valve Adjustments
Figure 10.2 - Manifold Pressure Test Points
Premium Controls
Manifold Pressure Test Point
Standard Controls
10
5-564
1. TOP HOUSING
2. COVER PLATE
3. SEAL GASKET
4. MAXIMUM ADJUSTMENT SCREW
5. MAXIMUM ADJUSTMENT SPRING
6. SOLENOID
7. MINIMUM ADJUSTMENT SPRING
8. PLUNGER
9. MINIMUM ADJUSTMENT SCREW
10. MINIMUM ADJUSTMENT SCREW STOP
START-UP PROCEDURE
Air Shutter Adjustment
Proper operation provides a soft blue flame with a well-defined inner core. A lack of primary air will reveal soft yellow-tipped flames. Excess primary air produces short, well-defined flames with a tendency to lift off the burner ports. For both natural and propane gas, the air shutters can be adjusted to control the burner flame height. The air shutters can be accessed by reaching behind the gas valve in Figure may require the removal of the manifold (see Manifold Assembly Removal).
Natural Gas Flame Control
Control of burner flames on duct furnaces utilizing natural gas is achieved by resetting the primary air shutters (See Figure
19.1) to either increase or decrease primary combustion air. Prior to flame adjustment, operate duct furnace for about fifteen minutes. The main burner flame can be viewed after loosening and pushing aside the gas designation disc on the side of the burner box.
To increase primary air, loosen the air shutter set screws and move the air shutters closer to the manifold until the yellow­tipped flames disappear. (See Figure 19.1 for air shutter and heat exchanger support locations.) To decrease primary air, move the air shutters away from the manifolds until flames no longer lift from burner ports, but being careful not to cause yellow tipping. Retighten set screws after adjustment.
Propane Gas Flame Control
An optimum flame will show a slight yellow tip. Prior to flame adjustment, operate furnace for at least fifteen minutes. Loosen air shutter set screws and move the air shutters away from the manifold to reduce the primary air until the yellow flame tips appear. Then increase the primary air until yellow tips diminish and a clean blue flame with a well defined inner cone appears.
10.3. The larger models
Table 11.1 - Manifold Pressure and Gas Consumption
Model Size Type of Gas Natural Propane
Btu/Cu. Ft. 1040 2500
Specific Gravity 0.60 1.53
High Fire Manifold Pressure No. of Inches of Water Column 3.5 10 Orifices
Cfh 72.1 30.0
75
Orifice Drill Size 20 37 Cfh 96.1 40.0
100
Orifice Drill Size 30 45 Cfh 120.2 50.0
125
Orifice Drill Size 25 42 Cfh 144.2 60.0
150
Orifice Drill Size 30 45 Cfh 168.3 70.0
175
Orifice Drill Size 27 43 Cfh 192.3 80.0
200
Orifice Drill Size 23 40 Cfh 216.3 90.0
225
Orifice Drill Size 20 37 Cfh 240.4 100.0
250
Orifice Drill Size 25 42 Cfh 288.7 120.0
300
Orifice Drill Size 20 37 Cfh 336.5 140.0
350
Orifice Drill Size 27 43 Cfh 384.6 160.0
400
Orifice Drill Size 23 40
1
2
2
3
3
3
3
4
4
6
6
5-564
11
START-UP PROCEDURE
IMPORTANT
To prevent premature heat exchanger failure, with all control systems, a blower starting mechanism must be provided so that the blower is running or energized within 45 seconds of the gas control operation.
Control Operating Sequence
Indoor power vented duct furnaces are supplied with intermittent pilot systems with continuous retry as standard. On mechanical modulation systems the main burner is turned off 100% when the thermostat is satisified, but the pilot remains lit. For intermittent pilot systems, except mechanical modulation both the main burner and pilot burner are turned off 100% when the thermostat is satisfied. Intermittent pilot systems, for both natural and propane gas, the ignition controller is 100% shut-off with continuous retry. On a call for heat, the system will attempt to light the pilot for 70 seconds. If the pilot is not sensed for any reason, the ignition control will wait for approximately six minutes with the combination gas control closed and no spark. After six minutes, the cycle will begin again. After three cycles, some ignition controllers lockout for approximately one hour before the cycle begins again. This will continue indefinitely until the pilot flame is sensed or power is interrupted to the system.
NOTE: Gas Control Options (see page 14) could change the
listed sequence of operation based on their function. The descriptions given are for the basic duct furnace.
Single-Stage Gas Controls
Utilizes a single-stage combination gas, an ignition control, and a single-stage low voltage thermostat.
1. The thermostat calls for heat.
2. The power exhauster relay is energized starting the power exhauster motor. Once the motor has reached full speed, the differential pressure switch closes. The power exhauster relay pre-purge timer closes after 20 to 40 seconds energizing the gas control circuit.
3. The pilot valve opens and the spark ignitor sparks in an attempt to light the pilot. (If the unit was not provided with a time delay relay, the blower starts at this time.)
4. Once the pilot is lit, the flame sensor proves the pilot and stops the spark ignitor from sparking.
5. The main gas valve is opened and the main burner is lit to 100% full fire.
6. If the unit was provided with a time delay relay, the blower starts after 30 to 45 seconds.
7. The unit continues to operate until the thermostat is satisfied, at which time both the main and pilot valves close 100%. (If the unit was not provided with a time delay relay, the blower stops at this time).
8. If the unit was provided with a time delay relay, the blower stops after 30 to 45 seconds.
Two-Stage Gas Controls
Utilizes a two-stage combination gas control, an ignition control, and a two-stage low voltage thermostat. The unit fires at 50% fire on low stage and 100% fire on high stage.
1. The thermostat calls for low stage heat.
2. The power exhauster relay is energized starting the power exhauster motor. Once the motor has reached full speed, the differential pressure switch closes. The power exhauster relay pre-purge timer closes after 20 to 40 seconds energizing the gas control circuit.
3. The pilot valve opens and the spark ignitor sparks in an attempt to light the pilot. (If the unit was not provided with a
time delay relay, the blower starts at this time.)
4. Once the pilot is lit, the flame sensor proves the pilot and stops the spark ignitor from sparking.
5. The main gas valve is opened and the main burner is lit to 50% fire.
6. If the unit was provided with a time delay relay, the blower starts after 30 to 45 seconds.
7. If the temperature at the thermostat continues to fall, the thermostat will call for high stage heat.
8. The main gas valve is opened completely and the main burner is lit to 100% full fire.
9. The unit continues to operate until the high stage of the thermostat is satisfied, at which time the main valve closes to 50% fire.
10. The unit continues to operate until the low stage thermostat
is satisfied, at which time both the main and pilot valves close 100%. (If the unit was not provided with a time delay relay, the blower stops at this time.)
11. If the unit was provided with a time delay relay, the blower
stops after 30 to 45 seconds.
Mechanical Modulating Gas Controls (Natural Gas Only)
Dial Number
Lo 1 2 3 4 5 6 7 8 Hi
Discharge Air Temp. 58 62 65 69 72 76 79 83 86 90 (°F)
Utilizes a mechanical modulating gas control and an ignition control. The mechanical modulating gas control is designed for use in constant blower applications. The discharge air temperature is maintained by setting the control dial of the modulating gas valve in one of ten positions. A hydrostatic sensing bulb located in the discharge air stream controls the gas flow between 40% through 100% full fire. When the discharge air hydrostatic sensing bulb is satisfied, the modulating valve closes completely, but the pilot remains lit. This control cannot be used with a room override thermostat.
1. Power is supplied to the unit through either an exhaust fan
interlock contact or a start/stop switch.
2. The power exhauster relay is energized starting the power
exhauster motor. Once the motor has reached full speed, the differential pressure switch closes. The power exhauster relay pre-purge timer closes after 20 to 40 seconds energizing the gas control circuit.
3. The pilot valve opens and the spark ignitor sparks in an
attempt to light the pilot. (If the unit was not provided with a time delay relay, the blower starts at this time.)
4. Once the pilot is lit, the flame sensor proves the pilot and
stops the spark ignitor from sparking.
5. The hydrostatic sensing bulb, integral to the mechanical
modulating gas valve, calls for heat. The main gas valve is opened and the main burner is lit. The burner modulates between 40% through 100% fire based on the call for heat.
6. If the unit was provided with a time delay relay, the blower
starts after 30 to 45 seconds.
7. The unit continues to operate until the hydrostatic sensing
bulb is satisfied, at which time the main valve closes 100%, but the pilot remains lit.
8. The unit blower (and pilot) continues to operate until either an
exhaust fan interlock contact or a start/stop switch is opened. If the unit was provided with a time delay relay, the blower stops after 30 to 45 seconds.
12
5-564
START-UP PROCEDURE
Electronic Modulating Gas Controls
Single Furnace
Utilizes an electronic modulating/regulating gas control, combination gas valve, an ignition control, modulating amplifier, and either a modulating room thermostat or modulating duct thermostat with remote temperature set point adjuster. The thermostat controls can modulate the gas flow between 40% through 100% full fire. When the thermostat is satisfied, the amplifier cuts power to the combination gas valve which prevents gas flow to both the main and pilot burners. When duct sensing is utilized, a room override thermostat can be added. When calling for heat, the room override thermostat provides full fire operation until the space temperature is satisfied. Control is then returned to the duct sensing control. In this situation, either the duct sensor or the room override thermostat can call for heat.
1. The thermostat calls for heat.
2. The power exhauster relay is energized starting the power exhauster motor. Once the motor has reached full speed, the differential pressure switch closes. The power exhauster relay pre-purge timer closes after 20 to 40 seconds energizing the gas control circuit.
3. The pilot valve opens and the spark ignitor sparks in an attempt to light the pilot. (If the unit was not provided with a time delay relay, the blower starts at this time.)
4. Once the pilot is lit, the flame sensor proves the pilot and stops the spark ignitor from sparking.
5. The main gas valve is opened and the main burner is lit to 100% full fire.
6. If the unit was provided with a time delay relay, the blower starts after 30 to 45 seconds.
7. The modulating gas valve can be controlled by either an electronic modulating room or duct thermostat. The thermostat can modulate the firing rate between 40% through 100% full fire. The call for heat is created by a resistance signal (8000 to 12000 ohms) in the thermostat. The amplifier converts this resistance into a DC voltage (0 to 12 volts DC with 0 volts high fire and 12 volts low fire). The output voltage is applied to the modulating gas valve to control the gas flow to the main burner. As the temperature drops, the voltage drops causing the modulating valve to open further. If the discharge air temperature increases, the voltage increases causing the modulating valve to close allowing less gas flow to the main burner. For further information regarding the operation of the electronic modulating system, consult the literature provided with the unit.
8. The unit continues to operate in this manner until the thermostat is satisfied, at which time both the main and pilot valves close 100%. (If the unit was not provided with a time delay relay, the blower stops at this time.)
9. If the unit was provided with a time delay relay, the blower stops after 30 to 45 seconds.
Electronic Modulating Gas Controls - Master/Slave
One Master furnace is provided with up to three Slave furnaces that utilize electronic modulating/regulating gas controls, combination gas valves, ignition controls, one multiple furnace modulating amplifier, and either a modulating room thermostat or modulating duct thermostat with remote temperature adjuster. The thermostat controls can modulate the gas flow of all the furnaces between 40% through 100% full fire. The amplifier sends a signal to all of the gas valves so that they modulate at the same percentage. When the thermostat is satisfied, the amplifier cuts power to the combination gas valves which prevents gas flow to both the main and pilot burners. When duct sensing is utilized, a room override thermostat can be added. When calling for heat, the room override thermostat provides full fire operation until the space temperature is satisfied. Control is then returned to the duct sensing control. In this situation, either the duct sensor or the room override thermostat can call for heat.
5-564
The sequence of operation for Electronic Modulating Gas Controls - Master/Slave is the same as Electronic Modulating Gas Controls - Single Furnace.
Electronic Modulating Gas Controls - Building Management Control (0-10Vdc or 4-20 mA Signal)
Utilizes an electronic modulating/regulating gas control, combination gas valve, an ignition control, modulating signal conditioner, and an inverted (0 Vdc or 4 mA being high fire and 10 Vdc or 20 mA being low fire) 0-10 Vdc or 4-20 mA input signal provided by a Building Management System (BMS). The signal conditioner can modulate the gas flow between 40% through 100% full fire. When the BMS thermostat (field supplied) is satisfied, the BMS heat contact (field supplied) opens to cut power to the combination gas valve which prevents gas flow to both the main and pilot burners.
1. The BMS thermostat (field supplied) calls for heat and closes the BMS heat contact (field supplied).
2. The power exhauster relay is energized starting the power exhauster motor. Once the motor has reached full speed, the differential pressure switch closes. The power exhauster relay pre-purge timer closes after 20 to 40 seconds energizing the gas control circuit.
3. The pilot valve opens and the spark ignitor sparks in an attempt to light the pilot. (If the unit was not provided with a time delay relay, the blower starts at this time.)
4. Once the pilot is lit, the flame sensor proves the pilot and stops the spark ignitor from sparking.
5. The main gas valve is opened and the main burner is lit to 100% full fire.
6. If the unit was provided with a time delay relay, the blower starts after 30 to 45 seconds.
7. The modulating gas valve is controlled by the BMS thermostat. The thermostat can modulate the firing rate between 40% through 100% full fire by modulating the input signal between either 0-10 Vdc or 4-20 mA (The signal conditioner can accept a 0-10 Vdc signal when all the dip switches are in the “OFF” position and 4-20 mA signal when all the dip switches are in the “ON” position). The signal conditioner converts the input signal into a DC voltage (0 to 12 volts DC with 0 volts high fire and 12 volts low fire). The output voltage is applied to the modulating gas valve to control the gas flow to the main burner. As the temperature drops, the voltage drops causing the modulating valve to open further. If the discharge air temperature increases, the voltage increases causing the modulating valve to close allowing less gas flow to the main burner. For further information regarding the operation of the electronic modulating system, consult the literature provided with the unit.
8. The unit continues to operate in this manner until the thermostat is satisfied, at which time the BMS heat contact opens resulting in both the main and pilot valves closing 100%. (If the unit was not provided with a time delay relay, the blower stops at this time.)
9. If the unit was provided with a time delay relay, the blower stops after 30 to 45 seconds.
Variable Air Movement Applications
When the air mover supplied by others can provide variable air movement (i.e. 2-speed or variable frequency drive units), the allowable minimum CFM of the duct furnace can be 66% of the minimum listed CFM in Table 16.1 if the unit is applied as follows:
1. The unit is provided with 2-stage, mechanical modulation, or electronic modulating gas controls. (see Model Identification).
2. The unit is provided with a factory installed discharge air controller.
3. The system does not include a room thermostat.
The factory installed discharge air thermostat will prevent the unit from firing above the allowable 100°F rise when the unit is at or above the minimum CFM by monitoring the discharge air and going to low fire. A room thermostat, because it is located remote from the unit, could cause the unit to over-fire.
13
OPTIONS
Units with Standard
Control Panel
Units with Premium Control Box
13
48
6
46
6
8
57
9
13
49
2
3
50
5
4
1
10
9
8
12
46
47
55
51
52
12
300
FM
R
LISTED PRESSURE OPERATED SWITCH 504H
ADDISON IL. U.S.A.
MODEL RLGP-A
M1
LOW
PRESSURE
50 100 150 200
350
250
mm.
W.C.
2 4 6 8 10
14
IN.
12
300
FM
R
LISTED PRESSURE OPERATED SWITCH 504H
ADDISON IL. U.S.A.
MODEL RLGP-A
M1
LOW
PRESSURE
50 100 150 200
350
250
mm.
W.C.
2 4 6 8 10
14
IN.
12
3 456
A1010 Amplifier
89101114
GH
T
PV
MV
LED
TH
PV/MV
GND
TR
SENSE
Gas Control Options
The unit must be reviewed to determine if any of the listed gas control options were supplied.
Time Delay Relay
The Time Delay Relay is factory installed in the duct furnace electrical junction box. The standard duct furnace is provided for instantaneous fan operation. On a call for heat, the blower is energized at the same time as the gas controls. The optional time delay relay allows the gas controls to operate for approximately 30 seconds before the blower starts. This allows the heat exchanger a warm up period so that the initial delivered air coming out of the ductwork is not cool. The time delay relay also keeps the motor running for approximately 30 seconds after the call for heat has been satisfied to remove the residual heat from the heat exchanger.
Low Gas Pressure Switch
The low gas pressure switch is factory installed in the duct furnace above the gas train. The switch monitors the gas pressure upstream of all the gas controls and shuts off the electric supply to the ignition controller and combination gas valve if low gas pressure is experienced. This will shut off all gas flow to the burner. The switch has an automatic reset so that if the gas pressure is interrupted and then is returned, the switch will automatically allow the unit to operate when gas conditions are returned to the allowable range of the pressure switch. The pressure switch range is 2" to 14" W.C. and should be set to insure that the minimum inlet gas pressure is available (6" W.C. for natural gas, 11" W.C. for propane gas).
High Gas Pressure Switch
The high gas pressure switch is factory installed in the duct furnace above the gas train. The switch monitors the gas pressure downstream of all the gas controls and shuts off the electric supply to the ignition controller and combination gas valve if high gas pressure is experienced right before the manifold. This will shut off all gas flow to the burner. The switch has a manual reset so that if the gas pressure is too high, a service person must check the unit to make sure that none of the gas controls have been damaged by the high gas pressure and then reset the switch to allow the unit to operate when gas conditions are returned to the allowable range of the pressure switch. The pressure switch range is 2" to 16" W.C. and should be set to insure that the maximum manifold gas pressure is not exceeded (3.5" W.C. for natural gas, 10" W.C. for propane gas).
Air Flow Proving Switch
The air flow proving switch is factory installed in the duct furnace electrical junction box. The air flow proving switch monitors the pressure differential between the duct furnace and the atmosphere. The purpose of the air flow proving switch is to cut power to the gas controls if a positive pressure is not measured by the switch. This could be caused by a lack of air movement through the heat exchanger.
NOTE: The air flow proving switch will prevent any heat
exchanger warm-up (the unit should not be equipped with a time delay relay) because the gas controls can not be energized until air flow is proven.
Setting the Air Flow Proving Switch
The range of the air flow proving switch is adjustable between 0.17" to 5.0" W.C.
1. Set the thermostat so that there is a call for heat. This should fire the burner and the blower should start.
2. Turn the set screw of the pressure switch clockwise until it stops. This will set the pressure at 5.0" W.C.
3. Turn the screw counter-clockwise until the gas controls light and then one additional full turn (This is approximately 0.25'' W.C.). This will allow for dirty filters or any other slight static pressure increases in the system.
Manual Reset High Limit
The manual reset high limit switch is factory installed in place of the standard automatic reset high limit switch located in the duct furnace electrical junction box. In case of a failure of the blower motor, blockage of the inlet air, etc., the manual reset switch prevents the unit from cycling on the high limit. If the limit temperature is exceeded, a service person must inspect the unit for the cause of the high discharge temperature, take corrective action, and then reset the switch.
Figure 14.1 - Location of Gas Control Options
Supply Air Fire Stat
The fire stat is factory installed in the duct furnace electrical junction box with the sensor in the discharge air stream. In case of elevated temperatures in the supply air, the manual reset switch shuts down the entire unit. If the limit temperature is exceeded, a service person must inspect the unit for the cause of the high discharge temperature, take corrective action, and then reset the switch.
Timed Freeze Protection
The timed freeze protection system is factory installed in the duct furnace electrical junction box with the sensor (30°-75°F adjustable) factory installed in discharge air stream. On initial start-up, the timed delay in the system allows the unit to go through the normal ignition sequence. The timed delay is an automatic reset switch and adjustable for 1-10 minutes. In the event that the unit fails to fire after this period, the discharge air sensor will sense the cold air and will shut down the entire unit.
14
Note: Wrap around gas train on
premium and electronic modulation units only.
1. Discharge Thermostat
2. Low Gas Pressure Switch
3. High Gas Pressure Switch
4. Power Exhauster
5. Timed Freeze Protection
6. Ignition Controller
8. Control Relay
9. Time Delay Relay
10. Furnace Low Voltage Terminal Strip
12. Furnace Supply Power Terminal Strip
13. Control Step Down Transformer
46. Electronic Modulating Amplifier
47. Electronic Modulating Gas Valve
48. Air Flow Proving Switch
49. High Limit Switch
50. Supply Air Fire Stat
51. Main Gas Valve
52. Burner Box
55. Differential Pressure Switch
57. Control Terminal Board
5-564
DIMENSIONAL DATA
Figure 15.1 - Indoor Power Vented Duct Furnace Dimensions
18.39
(MOUNTING
HOLES)
J (ROUND)
H
A
F (MOUNTING HOLES)
G
E (DUCT SIZE)
8.965
1.41
P
10.50
I
22.907 C
PREMIUM CONTROL BOX
M
O
K
D (DUCT SIZE)
Table 15.1 - Indoor Power Vented Duct Furnace Dimensions
(All Dimensions in inches)
Dimensions 75 100/125 150/175 200/225 250/300 350/400
A 15.41 17.90 22.16 24.29 27.33 38.83 C (standard) 22.43 22.43 22.43 24.09 24.09 24.09
B 33.05 33.05 33.05 37.05 37.05 37.05
D 15.21 17.70 21.96 24.09 27.13 38.63 E 19.07 19.07 19.07 23.07 23.07 23.07 F 14.09 16.59 20.85 22.98 26.01 37.51 G 12.65 15.14 19.41 21.60 24.60 36.14 H 23.75 26.26 30.51 32.78 35.79 47.32 I 17.83 17.83 17.83 20.68 20.68 20.68 J 4 4 4 6 6 6 K 14.55 17.04 21.31 23.26 26.44 37.80 M 2.01 2.01 2.01 1.94 1.94 1.94 N 29.65 29.65 29.65 33.65 33.65 33.65
O (max. approx.) (standard) 5.6 5.6 5.6 6.8/6.2 6.2 8.3/8.6
P 14.03 14.03 14.03 17.40 17.40 17.40 Gas Connection Pipe Size (max. std.) 1/2 1/2 1/2 1/2 / 3/4 3/4 3/4 Gas Connection Pipe Size (max. prem.) 3/4 3/4 3/4 3/4 3/4 3/4
Approx. Unit Shipping 101# 125# 152# 187# 225# 296# Weight Unit Net 85# 107# 133# 167# 193# 263#
Model Size
N
B
5-564
15
PERFORMANCE
Table 16.1 - Air Temperature Rise - Power Vented Indoor Duct Furnaces ➀ ➁
Air Temperature Rise Through Unit (°F) Model Btu/Hr 20 Size Input Output Max Min
75 75,000 60,000 2778 1389 1111 926 855 794 741 694 654 617 585 556
100 100,000 80,000 3704 1852 1481 1235 1140 1058 988 926 871 823 780 741
125 125,000 100,000 4630 2315 1852 1543 1425 1323 1235 1157 1089 1029 975 926
150 150,000 120,000 5556 2778 2222 1852 1709 1587 1481 1389 1307 1235 1170 1111
175 175,000 140,000 6481 3241 2593 2160 1994 1852 1728 1620 1525 1440 1365 1296
200 200,000 160,000 7407 3704 2963 2469 2279 2116 1975 1852 1743 1646 1559 1481
225 225,000 180,000 8333 4167 3333 2778 2564 2381 2222 2083 1961 1852 1754 1667
250 250,000 200,000 9259 4630 3704 3086 2849 2646 2469 2315 2179 2058 1949 1852
300 300,000 240,000 11111 5556 4444 3704 3419 3175 2963 2778 2614 2469 2339 2222
350 350,000 280,000 11111 6481 5185 4321 3989 3704 3457 3241 3050 2881 2729 2593
400 400,000 320,000 11111 7407 5926 4938 4558 4233 3951 3704 3486 3292 3119 2963
Ratings are shown for elevations up to 2000 feet. For higher elevations, the input rating should be reduced at the rate of 4% per 1000 feet elevation above sea level. For Canada, in
elevations between 2000 and 4500 feet, the unit must be derated to 90% of the rating listed above.
Units approved for use in California by CEC.
Power vented indoor duct furnaces are supplied with a factory installed air baffle. For applications where an air tempature rise less than 60°F is desired, it is recomended to remove
this baffle to reduce system pressure drop.
For Variable Air Movement Applications, see page 13.
The maximum CFM for the 350 and 400 results in a 23°F and a 27°F air temperature rise (respectively) based on the maximum unit pressure drop.
40 ➂ 50 ➂ 60 65 70 75 80 85 90 95 100
CFM
Air Temperature and External Static Pressure Limits
The maximum allowable discharge air temperature is 150°F. The maximum allowable air temperature rise for all Power Vented Units is 100°F. All duct furnaces are designed for a maximum allowable static pressure of 3.0" W.C. on the heat exchanger.
Figure 16.1 - Recommended Unit Configurations
SINGLE TOP VIEW
2279 CFM 60°F ENTERING AIR TEMP.
TANDEM TOP VIEW
2279 CFM 20°F ENTERING AIR TEMP.
TEMP. RISE
160,000 BTU/HR
OUTPUT
65°F
TEMP. RISE
PREHEAT
UNIT
160,000 BTU/HR
OUTPUT
65°F
OUTPUT
TEMP. RISE
REHEAT
160,000
BTU/HR
65°F
UNIT
125°F DISCHARGE
AIR TEMP.
150°F DISCHARGE
AIR TEMP.
PARALLEL TOP VIEW
5698 CFM 20°F ENTERING AIR TEMP.
200,000 BTU/HR
OUTPUT 65°F
TEMP. RISE
SEE SERVICE CLEARANCES
200,000 BTU/HR
OUTPUT 65°F
TEMP. RISE
85°F DISCHARGE
AIR TEMP.
16
5-564
PRESSURE DROP CURVES
0
0.2
0.4
0.6
0.8
1
1.2
1.4
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
CFM
PRESSURE DROP
(Δ P " W.C.)
75
100/125
150/175
200/225
250/300
350/400
Caution: Do not exceed the CFM ranges indicated in Table 16.1
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
2.8
3.0
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
11000
12000
CFM
PRESSURE DROP
( ΔP " W.C.)
75
100/125
150/175
Caution: Do not exceed the CFM ranges indicated in Table 16.1
200/225
250/300
350/400
Figure 17.1 - Indoor Duct Furnace Without Baffle Pressure Drop vs CFM curves
Figure 17.2 - Indoor Duct Furnace With Baffle Pressure Drop vs CFM curves
5-564
17
MAINTENANCE
WARNING
When servicing or repairing this equipment, use only factory­approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine Manufacturing Company. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner’s risk.
CAUTION
Do not attempt to reuse any mechanical or electrical controllers which have been wet. Replace defective controller.
IMPORTANT
To check most of the Possible Remedies in the troubleshooting guide listed in Table 20.1, refer to the applicable sections of the manual.
All installation and service of these units must be performed by a qualified installation and service agency. All heating equipment should be serviced before each heating season to assure proper operations. The following items may be required to have more frequent service schedule based on the environment in which the unit is installed, and the frequency of the equipment operation.
Before any service, BE SURE TO TURN OFF GAS AT THE MANUAL SHUT-OFF VALVE AHEAD OF THE COMBINATION GAS CONTROL AND TURN OFF ALL ELECTRIC POWER TO THE HEATER AND AIR MOVING SYSTEM.
Duct Furnace
When providing annual maintenance for the duct furnace, keep the unit free from dust, dirt, grease and foreign matter. Pay particular attention to:
1. The exhaust vent piping and vent terminal.
2. The burner ports and pilot burner orifices (avoid the use of hard, sharp instruments capable of damaging surfaces for cleaning these ports). To check the burner port and pilot burner orifice, see Burner and Pilot Assembly Removal.
3. The air shutters and main burner orifices (avoid the use of hard, sharp instruments capable of damaging surfaces for cleaning these orifices). To check the air shutters and main burner orifices, see for Manifold Assembly Removal.
The heat exchanger should be checked annually for cracks and discoloration of the tubes. If a crack is detected, the heat exchanger should be replaced before the unit is put back into service. If the tubes are dark gray, airflow across the heat exchanger should be checked to insure that a blockage has not occurred or the blower is operating properly.
Power Exhauster Motor
The power exhaust motor bearings have been lubricated for long life and do not require additional lubrication. In dirty atmosphere, it may be desirable to clean the motors and blower housing and blow out the cooling air passages of the motor with compressed air.
Electrical Wiring
The electrical wiring should be checked annually for loose connections or deteriorated insulation.
Blower Assembly
The blower assembly includes the bearings, drive sheaves and belts.
Blower bearings should be checked and lubricated based on the blower manufacturer’s recommendations. Bearings should also be checked for any unusual wear and replaced if needed.
Drive sheaves should be checked at the same time the bearings are inspected. Check to make sure the sheaves are in alignment and are securely fastened to the blower and motor shafts.
Belt tension should be rechecked shortly after the unit has been installed to check for belt stretching. After the initial start-up, monthly checks are recommended.
Filters
If the unit is supplied with a dirty filter switch and light, clean or replace the filters any time the dirty filter light comes on.
Units which do not have a dirty filter warning light should have the filters checked monthly. Clean or replace if necessary. In dirty atmospheres, filter maintenance may be required more often.
Gas Piping & Controls
The gas valves and piping should be checked annually for general cleanliness and tightness.
The gas controls should be checked to insure that the unit is operating properly.
Manifold Assembly Removal
To remove the manifold
1. Shut off gas and electric supply.
2. Disconnect gas manifold at ground union joint.
3. Remove the two screws holding the manifold to the heat exchanger support.
4. Slide the manifold through the manifold bracket.
5. Clean the orifices and adjust the air shutters as necessary.
6. Follow steps 3-6 in reverse order to install the manifold assembly.
7. Turn on the electric and gas supply.
8. Check the ground joint union for leaks with a soap solution. Tighten if necessary.
18
5-564
MAINTENANCE
Figure 19.1 - Manifold Assembly Removal
SERIAL PLATE
BURNER SIDE
ACCESS PANEL
ELECTRICAL
JUNCTION
BOX
MANIFOLD
AIR SHUTTERS
(NOT SHOWN) ARE LOCATED
ON THE
MANIFOLD
PILOT
ASSEMBLY
IGNITION
CABLE
PILOT
SUPPLY
LINE
Burner and Pilot Assembly Removal
To remove the burner
1. Shut off gas and electric supply.
2. Disconnect the pilot supply line from the gas valve.
3. Disconnect the ignition cable from the ignition controller (located in the electrical junction box). Feed the cable through the bushing in the bottom of the electrical junction box.
4. Remove the screws holding the burner side access panel. Attached to the panel are the burner retaining pins that align the burner.
5. Slide the burner assembly out. The pilot is attached to the burner assembly.
6. Examine the burner and pilot assembly for cleanliness and/or obstructions as necessary (see Duct Furnace for cleaning instructions).
7. Replace the burner assembly in reverse order. In replacing the burner, be certain that the rear burner slots are located properly on the burner retaining pins. Do not force the burner side access panel, it will not fit if the burner is not properly aligned.
8. Reconnect the ignition cable and pilot gas supply line.
9. Turn on the electric and gas supply.
5-564
19
SERVICE & TROUBLESHOOTING
Table 20.1 - Troubleshooting
Trouble Possible Cause Possible Remedy
Power Exhauster Motor will not start 1. Power supply is off.
2. No 24V power to thermostat.
3. Thermostat malfunction.
4. Defective power exhauster relay.
5. Defective power exhauster motor.
Pilot does not light/stay lit 1. Main gas is off.
2. Power supply is off.
3. Air in gas line.
4. Dirt in pilot orifice.
5. Gas pressure out of proper range.
6. Pilot valve does not open.
a. Defective ignition controller. b. Defective gas valve.
7. No spark at ignitor. a. Loose wire connections. b. Pilot sensor is grounded. c. Defective ignition controller.
8. Safety device has cut power.
9. Excessive drafts.
10. Pilot orifice fitting leak.
1. Turn on main power.
2. Check control transformer.
3. Check/replace thermostat.
4. Replace power exhauster relay.
5. Replace power exhauster motor.
1. Open manual gas valve.
2. Turn on main power.
3. Purge gas line.
4. Check for plugged pilot orifice and clean
with compressed air if necessary.
5. Adjust to a maximum of 14" W.C. Minimum for Natural Gas - 6" W.C. Minimum for Propane Gas - 11" W.C.
6. Check wiring for 24 volts to valve. a. Replace ignition controller. b. Replace gas valve.
7. a. Check all ignition controller wiring. b. Replace sensor if cracked or worn. c. Replace ignition controller.
8. Check all safety devices (High limit, air flow proving switch, differential pressure switch, gas pressure switches, etc.) Determine and correct problem. Reset if necessary.
9. Find source and re-direct airflow away from unit.
10. Tighten pilot orifice. Flame impingment on pilot sensor may cause pilot sensor to become inoperative.
Main burners do not light (Pilot is lit)
Lifting Flames (See Figure 21.1)
Yellow Tipping
(With propane gas, some yellow tipping is always present.)
Flashback 1. Too much primary air.
Floating Flames (See Figure 21.2)
Flame Rollout (See Figure 21.3)
1. Defective valve.
2. Loose wiring.
3. Defective pilot sensor.
4. Defective ignition controller.
5. Improper thermostat wiring.
1. Too much primary air.
2. Main pressure set too high.
3. Orifice too large.
1. Insufficient primary air.
2. Dirty orifice.
3. Misaligned orifice.
2. Main pressure set too high.
3. Orifice too large.
1. Insufficient primary air.
2. Main pressure set too high.
3. Orifice too large.
4. Blocked vent.
1. Main pressure set too high.
2. Orifice too large.
3. Blocked vent.
1. Replace valve.
2. Check wiring to gas valve.
3. Replace pilot sensor.
4. Replace ignition controller.
5. Verify wiring compared to wiring diagram.
1. Reduce primary air.
2. Adjust to a maximum of 14" W.C.
3. Check orifice size with those listed on the
serial plate.
1. Increase primary air.
2. Check orifices and clean with compressed
air if necessary.
3. Check manifold, replace if necessary.
1. Reduce primary air.
2. Adjust to a maximim of 14” W.C.
3. Check orifice size with those listed on
the serial plate.
1. Increase primary air.
2. Adjust to a maximum of 14" W.C.
3. Check orifice size with those listed on
the serial plate.
4. Clean/correct venting system.
1. Adjust to a maximum of 14" W.C.
2. Check orifice size with those listed on
the serial plate.
3. Clean/correct venting system.
20
5-564
SERVICE & TROUBLESHOOTING
Trouble Possible Cause Possible Remedy
Not Enough Heat
1. Unit cycling on high limit.
a. Obstructions/leaks in duct system. b. Main pressure set too high. c. Blower motor not energized.
d. Loose belt e. Blower speed too low.
f. Blocked/damaged venting system. g. Air distribution baffle removed (high
temperature rise units only).
h. Defective high limit switch.
2. Main pressure set too low.
3. Too much outside air.
4. Thermostat malfunction.
5. Gas controls wired incorrectly.
6. Unit undersized.
1.
a. Clean/correct duct system. b. Adjust to a maximum of 14" W.C. c. Check/correct to insure blower motor
operates within 45 seconds of when
- gas controls are energized. d. Adjust belt tension. e. Check/correct blower drive settings for
proper rpm. f. Check/correct venting system. g. Replace air distribution baffle.
h. Replace high limit switch.
2. Adjust main gas pressure. Minimum for Natural Gas — 6" W.C. Minimum for Propane Gas — 11" W.C.
3. Adjust outside air damper to decrease
outside air percentage (if possible).
4. Check/replace thermostat.
5. Check unit wiring against the wiring
diagram.
6. Check design conditions. If unit is
undersized, an additional unit(s) or other
heat source must be added.
Too Much Heat
1. Thermostat malfunction.
2. Gas controls do not shut-off.
a. Gas controls wired incorrectly. b. Short circuit.
3. Main gas pressure set too high.
4. Defective gas valve.
Automatic Reset High Limit
The duct furnace comes standard with an automatic reset high limit switch that will shut-off the gas should the discharge air temperature become excessive. See Figure 14.1, indicator for the location of either the standard automatic or optional manual reset high limit switch. The switch should operate only when something is seriously wrong with the unit operation. Anytime the switch operates, correct the difficulty immediately or serious damage may result. If the switch cuts off the gas supply during normal operation, refer to the “Not Enough Heat” section of Service & Troubleshooting.
1. Check/replace thermostat.
2. a. Check unit wiring against the wiring
diagram.
b. Check for loose or worn wires.
3. Adjust to a maximum of 14" W.C.
4. Replace gas valve.
Figure 21.1 Lifting Flame Condition
Figure 21.2 Floating Flame Condition
Figure 21.3 Flame Rollout Appearance
5-564
21
REPLACEMENT PARTS ORDERING
Ordering
When servicing, repairing or replacing parts on these units, locate the serial plate of the unit and always give the complete Model Number and Serial Number from the serial plate. The serial plate is located on the door of the electrical control box or
on the side of unit. The Modine Manufacturing Company part number for some common replacement parts are listed on the sample serial plate For a complete description of the model number, see Model Identification.
MODEL IDENTIFICATION
Indoor Power Vented Duct Furnace Model Nomenclature
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
PT UC V MBH HE DS AS ATR GT GV SS SV TR
1 - Product Type (PT)
D - Indoor HVAC Unit
2 - Unit Configuration (UC)
F - Furnace
3 - Venting (V)
P - Power
4,5,6 - Furnace Input Rating (MBH) 75 - 75,000 Btu/Hr Input
100 - 100,000 Btu/Hr Input 125 - 125,000 Btu/Hr Input 150 - 150,000 Btu/Hr Input 175 - 175,000 Btu/Hr Input 200 - 200,000 Btu/Hr Input 225 - 225,000 Btu/Hr Input 250 - 250,000 Btu/Hr Input 300 - 300,000 Btu/Hr Input 350 - 350,000 Btu/Hr Input 400 - 400,000 Btu/Hr Input
7 - Heat Exchanger/Burner/Drip Pan Material (HE)
A - Aluminized Steel S - 409 Stainless Steel Heat Exchanger/Burner T - 409 Stainless Steel Heat Exchanger/Burner/Drip Pan
Figure 22.1 - Serial Number Designations
8 - Development Sequence Designation (DS)
F - Single Stage M - 2-stage or Modulating
9 - Access Side (AS)
R - Right Hand L - Left hand
10 - Air Temperature Rise (ATR)
N - Not Used
11 - Gas Type (GT)
N - Natural with ignition controller P - Propane with ignition controller
12 - Gas Valve (GV)
1 - Single Stage 5 - Electronic Modulation Master 2 - Two Stage 6 - Electronic Modulation Slave 3 - Mechanical Modulation 7 - Electronic Modulation 0-10 Vdc 4 - Electronic Modulation External Input Input 8 - Electronic Modulation 4-20mmA External Input
13 - Additional Safety Switches (SS)
4 - No Switches (Standard) 1 - Low Gas Pressure Switch 0 - No Switches (Premium) (Premium) 2 - High Gas Pressure Switch (Premium) 3 - High and Low Gas Pressure Switch (Premium)
101 26 00-1000
SERIES IDENTITY NUMBER
Identifies which series of controls were furnished on the unit.
22
SEQUENCE NUMBER
YEAR OF MANUFACTURE
00 – 2000 01– 2001 etc.
WEEK OF MANUFACTURE
01 – 1st week of year 26 – 26th week of year
14 - Supply Voltage (SV)
A - 115/60/1 E - 230/60/3 B - 208/60/1 F - 460/60/3 C - 230/60/1 G - 575/60/3 D - 200-208/60/3
15 - Transformer (TR) 1 - 40 VA 3 - 150 VA 0 - None 2 - 75 VA 4 - 250 VA
5-564
5-564
23
COMMERCIAL WARRANTY
Seller warrants its products to be free from defects in material and workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use of materials substituted under emergency conditions for materials normally employed. This warranty covers replacement of any parts furnished from the factory of Seller, but does not cover labor of any kind and materials not furnished by Seller, or any charges for any such labor or materials, whether such labor, materials or charges thereon are due to replacement of parts, adjustments, repairs, or any other work done. This warranty does not apply to any equipment which shall have been repaired or altered outside the factory of Seller in any way so as, in the judgment of Seller, to affect its stability, nor which has been subjected to misuse, negligence, or operating conditions in excess of those for which such equipment was designed. This warranty does not cover the effects of physical or chemical properties of water or steam or other liquids or gases used in the equipment.
BUYER AGREES THAT SELLER’S WARRANTY OF ITS PRODUCTS TO BE FREE FROM DEFECT IN MATERIAL AND WORKMANSHIP, AS LIMITED HEREIN, SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER WARRANTIES, EITHER EXPRESS OR IMPLIED, WHETHER ARISING FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE,
THERE ARE NO OTHER WARRANTIES, INCLUDING WARRANTY OF MERCHANTABILITY OR FITNESS FOR PURPOSE, WHICH EXTEND BEYOND THE PRODUCT DESCRIPTION CONFIRMED BY BUYER AND SELLER AS OF THE DATE OF FINAL AGREEMENT.
This warranty is void if the input to the product exceeds the rated input as indicated on the product serial plate by more than 5% on gas-fired and oil-fired units, or if the product in the judgment of SELLER has been installed in a corrosive atmosphere, or subjected to corrosive fluids or gases, been subjected to misuse, negligence, accident, excessive thermal shock, excessive humidity, physical damage, impact, abrasion, unauthorized alterations, or operation contrary to SELLER’S printed instructions, or if the serial number has been altered, defaced or removed.
BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR REPLACEMENT AT THE FACTORY OF SELLER, ANY COMPONENT WHICH
SHALL, WITHIN THE APPLICABLE WARRANTY PERIOD DEFINED HEREIN AND UPON PRIOR WRITTEN APPROVAL, BE RETURNED TO SELLER WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE; EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER, BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. FOR GAS-FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS, BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO TEN YEARS FROM DATE OF SHIPMENT FROM SELLER.
These warranties are issued only to the original owner-user and cannot be transferred or assigned. No provision is made in these warranties for any labor allowance or field labor participation. Seller will not honor any expenses incurred in its behalf with regard to repairs to any of Seller’s products. No credit shall be issued for any defective part returned without proper written authorization (including, but not limited to, model number, serial number, date of failure, etc.) and freight prepaid.
OPTIONAL SUPPLEMENTAL WARRANTY Provided a supplemental warranty has been purchased, Seller extends the warranty herein for an additional four (4) years on certain compressors. Provided a supplemental warranty has been purchased, Seller extends the warranty herein for an additional four (4) years or nine (9) years on certain heat exchangers.
EXCLUSION OF CONSUMABLES & CONDITIONS BEYOND SELLER’S CONTROL The above referenced warranty shall not be applicable to any of the following items: refrigerant gas, belts, filters, fuses and other items consumed or worn out by normal wear and tear or conditions beyond Seller’s control, including (without limitation as to generality) polluted or contaminated or foreign matter contained in the air or water utilized for heat exchanger (condenser) cooling or if the failure of the part is caused by improper air or water supply, or improper or incorrect sizing of power supply.
Component
Applicable Models
Heat Exchangers
Gas-Fired Units except PSH/BSH
Heat Exchangers
Low Intensity Infrared Units
Compressors
Condensing Units for Cassettes
Burners
Low Intensity Infrared Units
Other
Components excluding Heat Exchangers, Coils, Condensers, Burners, Sheet Metal
Heat Exchangers/Coils
Indoor and Outdoor Duct Furnaces and System Units, PSH/BSH, Steam/Hot Water Units, Oil-Fired Units, Electric Units, Cassettes,
Vertical Unit Ventilators
Compressors
Vertical Unit Ventilators
Burners
High Intensity Infrared Units
Sheet Metal Parts
All Products
TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE HUNDRED TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN SIXTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN EIGHTEEN MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
“APPLICABLE WARRANTY PERIOD”
As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.
© Modine Manufacturing Company 2008
Commercial Products Group
Modine Manufacturing Company 1500 DeKoven Avenue Racine, WI 53403 Phone: 1.800.828.4328 (HEAT) www.modine.com
Litho in USA
Loading...