gas-fired indoor power vented duct furnace/make-up air units
models DBP/DCP
9900100
All models approved for use in California by the CEC
FOR YOUR SAFETY
IF YOU SMELL GAS:
1. Open windows.
2. Don’t touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
WARNING
Improper installation, adjustment, alteration,
service or maintenance can cause property
damage, injury or death, and could cause
exposure to substances which have been
determined by various state agencies to cause
cancer, birth defects or other reproductive
harm. Read the installation, operating and
maintenance instructions thoroughly before
installing or servicing this equipment.
CAUTION
To prevent premature heat exchanger failure do
not locate ANY gas-fired units in areas where
chlorinated, halogenated, or acid vapors are
present in the atmosphere.
FOR YOUR SAFETY
The use and storage of gasoline or other
flammable vapors and liquids in open containers
in the vicinity of this appliance is hazardous.
IMPORTANT
The use of this manual is specifically intended
for a qualified installation and service agency.
A qualified installation and service agency must
perform all installation and service of these
appliances.
Inspection on Arrival
1. Inspect unit upon arrival. In case of damage, report it
immediately to transportation company and your local factory
sales representative.
2.
Check rating plate on unit to verify that power supply meets
available electric power at the point of installation.
3. Inspect unit upon arrival for conformance with description of
product ordered (including specifications where applicable).
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
THIS MANUAL IS THE PROPERTY OF THE OWNER.
SPECIAL PRECAUTIONS / TABLE OF CONTENTS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS
IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE
SAFE, EFFICIENT AND TROUBLE-FREE OPERATION.
IN ADDITION, PARTICULAR CARE MUST BE EXERCISED
REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW.
FAILURE TO PROPERLY ADDRESS THESE CRITICAL
AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS,
PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS
ARE SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR
NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation
which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which,
if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which,
if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided,
MAY result in a potential safety concern.
dANGER
Appliances must not be installed where they may be exposed
to a potentially explosive or flammable atmosphere.
WARNING
1. Gas fired heating equipment must be vented - do not operate
unvented.
2. A built-in power exhauster is provided - additional external
power exhausters are not required or permitted.
3. If you are replacing an existing heater, it may be necessary to
resize the venting systems. Improperly sized venting systems
can result in vent gas leakage or the formation of condensate.
Refer to the National Fuel Gas Code ANSI Z223.1 or CSA
B149.1 latest edition. Failure to follow these instructions can
result in injury or death.
4. Under no circumstances should two sections of double wall
vent pipe be joined together within one horizontal vent system
due to the inability to verify complete seal of inner pipes.
5. All field gas piping must be pressure/leak tested prior to
operation. Never use an open flame. Use a soap solution or
equivalent for testing.
6. Gas pressure to appliance controls must never exceed 14"
W.C. (1/2 psi).
7. Disconnect power supply before making wiring connections
to prevent electrical shock and equipment damage.
8. All appliances must be wired strictly in accordance with
wiring diagram furnished with the appliance. Any wiring
different from the wiring diagram could result in a hazard to
persons and property.
9. To reduce the opportunity for condensation, the minimum
sea level input to the appliance, as indicated on the serial
plate, must not be less than 5% below the rated input, or
5% below the minimum rated input of duel rated units.
10. Ensure that the supply voltage to the appliance, as indicated
on the serial plate, is not 5% greater than the rated voltage.
11. Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature
rating of at least 105°C.
12. When servicing or repairing this equipment, use only factory-
approved service replacement parts. A complete replacement
parts list may be obtained by contacting Modine Manufacturing
Company. Refer to the rating plate on the appliance for
complete appliance model number, serial number, and
company address. Any substitution of parts or controls not
approved by the factory will be at the owners risk.
CAUTION
1. Purging of air from gas supply line should be performed
as described in ANSI Z223.1 - latest edition “National Fuel
Gas Code”, or in Canada in CAN/CGA-B149 codes.
2. Do not attempt to reuse any mechanical or electronic ignition
controllers which has been wet. Replace defective controller.
3. Ensure that the supply voltage to the appliance, as indicated
on the serial plate, is not 5% less than the rated voltage.
1. To prevent premature heat exchanger failure, do not locate
ANY gas-fired appliances in areas where corrosive vapors
(i.e. chlorinated, halogenated or acid) are present in the
atmosphere.
2. To prevent premature heat exchanger failure, the input to
the appliance, as indicated on the serial plate, must not
exceed the rated input by more than 5%.
3. To prevent premature heat exchanger failure, observe heat
exchanger tubes by looking at the heat exchanger through
the field installed access openings in connecting ductwork
in cooling package units or the unit access doors in blower
package units. If the bottom of the tubes become red
while blower and duct furnace are in operation, check to
be sure the blower has been set to the proper rpm for the
application. Refer to page 15 for Blower Adjustments.
4. Start-up and adjustment procedures should be performed
by a qualified service agency.
5. To check most of the Possible Remedies in the troubleshooting guide listed in Table 50.1, refer to the applicable
sections of the manual.
Table of Contents
Inspection on Arrival..................................1
Special Precautions ..................................2
SI (Metric) Conversion Factors..........................3
Unit Location........................................3
Combustible Material and Service Clearances ..........3
Unit Lifting and Unit Mounting ..........................4
Appliances must not be installed where they may be exposed
to a potentially explosive or flammable atmosphere.
IMPORTANT
To prevent premature heat exchanger failure, do not locate
ANY gas-fired appliances in areas where corrosive vapors (i.e.
chlorinated, halogenated or acid) are present in the atmosphere.
Location Recommendations
1. When locating the furnace, consider general space and
heating requirements, availability of gas and electrical
supply, and proximity to vent locations.
2. Unit must be installed on the positive pressure side of the
circulating blower.
3. Be sure the structural support at the unit location site is
adequate to support the weight of the unit. For proper
operation the unit must be installed in a level horizontal
position.
4. Do not install units in locations where the flue products
can be drawn into the adjacent building openings such as
windows, fresh air intakes, etc.
5. Be sure that the minimum clearances to combustible
materials and recommended service clearances are
maintained. Units are designed for installation on noncombustible surfaces with the minimum clearances shown
in Figure 3.1 and Tables 3.2 and 3.3.
6. Units installed downstream of refrigeration systems, or
exposed to inlet air temperatures of 40°F or less, may
experience condensation, therefore, provisions should
be made for disposal of condensate. Means have been
provided in the bottom pan of the unit to accommodate a
condensate drain line connection flange.
7. When locating units, it is important to consider that the
exhaust vent piping must be connected to the outside
atmosphere.
8. In garages or other sections of aircraft hangars such as
offices and shops that communicate with areas used for
servicing or storage, keep the bottom of the unit at least
7' above the floor unless the unit is properly guarded to
provide user protection from moving parts. In parking
garages, the unit must be installed in accordance with the
standard for parking structures ANSI/NFPA 88A, and in
repair garages the standard for repair garages NFPA #88B.
In Canada, installation of heaters in airplane hangars must
be in accordance with the requirements of the enforcing
authority, and in public garages in accordance with the
current CAN/CGA-B149 codes.
9. Do not install units in locations where gas ignition system is
exposed to water spray, rain, or dripping water.
Figure 3.1 - Combustible Material and Service
Clearances
3
➀A 3'' minimum clearance to combustible material is required from the vent collar.
Table 3.2 - Combustible Material Clearances
Model Access
Size Side (A) Side (B) (C) (D)
75-175 12" 1" 3" 2"
200-400 12" 2" 3" 2"
Non-Access
Top Bottom
Table 3.3 - Recommended Service Clearances
Model Access Non-Access Top Bottom
Size Side (A) Side (B) (C) (D)
Units installed in tightly sealed buildings or confined spaces
must be provided with two permanent openings, one near
the top of the confined space and one near the bottom. Each
opening should have a free area of not less than one square
inch per 1,000 BTU per hour of the total input rating off all
units in the enclosure, freely communicating with interior areas
having, in turn adequate infiltration from the outside.
For further details on supplying combustion air to a confined
(tightly sealed) space or unconfined space, see the National
Fuel Gas Code ANSI Z223.1 of CAN/CGA B149.1 or .2
Installation Code, latest edition.
Sound and Vibration Levels
All standard blower mechanical equipment generates some
sound and vibration that may require attenuation. Libraries,
private offices and hospital facilities will require more
attenuation, and in such cases, an acoustical consultant may
be retained to assist in the application. Locating the equipment
away from the critical area is desirable within ducting limitations.
Generally, a unit should be located within 15 feet of a primary
support beam. Smaller deflections mean lesser vibration and
noise transmission.
5-565.13
UNIT LOCATION/UNIT LIFTING/UNIT MOUNTING
A
5/8 Dia. (4)
C
B
BLOWER
SECTION
DOOR
ELECTRICAL
SECTION
DOOR
DUCT
FURNACE
3/4" SUSPENSION
RODS (BY OTHERS)
(2) 3/4" NUTS &
LOCKWASHER
(1) 3/4" NUT &
LOCKWASHER
UNIT LIFTING
All standard blower system units are shipped fully crated with
skid supports below the unit. The unit may be lifted from the
bottom by means of a fork lift or other lifting device only if the
shipping support skids are left in place. DO NOT attempt to lift
the unit from the bottom unless the shipping skid supports are
still in place. When lifting units, make sure the load is balanced.
All extended cabinet systems are shipped without a crate and
cannot be lifted with a fork truck. Use a crane or other overhead
lifting device in conjunction with the lifting holes (refer to page
45 for base rail lifting hole locations) for safe unit relocation. If
the unit must be lifted from the bottom for final installation of the
unit be sure to properly support the unit over its entire length to
prevent damage.
UNIT MOUNTING
Be sure the method of unit support (suspension or floor
mounting) is adequate to support the weight of the unit (see
Weights for base unit and factory installed option weights). For
proper operation, the unit must be installed in a level horizontal
position. Combustible material and service clearances as
specified in Figure 3.1 and Tables 3.2 and 3.3 must be strictly
maintained. To assure that flames are directed into the center of
the heat exchanger tubes, the unit must be level in a horizontal
position. Use a spirit level to ensure that the unit is suspended
or floor mounted correctly.
Unit Suspension
3/4" diameter suspension hanging locations are provided in
the base rail assembly of the unit. Refer to Figure 45.1 for
Suspension Hanging Locations and Figure 4.1 demonstrates
how the unit should be suspended and the suspension rods
fastened to the unit base rail. If required, vibration isolators may
be added.
Figure 4.1 - Unit Suspension Method
Floor Mounted Units
For floor installations, the floor structure must be adequately
designed to support the live weight load of the unit and any
other required support structure. Additional reinforcement should
be provided, if necessary. The floor should include threaded 5/8inch anchor bolts spaced according to Figure 4.2, for securing
the unit in place. Anchor bolts should extend at least 1-1/2"
above the surface of the floor to allow clearance for mounting
washers, nuts and bolts (mounting washers, nuts, and bolts by
others).
Figure 4.2 - Floor Mounted Units
Model Blower Type DBP Units DCP Units All Units DBP Units
Size (Digit 16) (A) (A) (B) (C)
75 All 86.27 115.48 33.85 -
100/25 All 86.37 115.48 36.36 -
150/175 All 86.37 115.48 40.61 -
200/225 All 86.37 115.48 42.71 -
250/300 E,F,G, or H 86.37 115.48 45.75 -
250/300 I,J, or K 112.12 151.34 45.75 -
350/400 E,F,G or H 86.37 115.48 57.27 -
350/400 I,J, or K 122.2 151.34 57.27 -
500/600 G or H 119.52 - 45.75 33.5
500/600 I,J, or K 155.38 - 45.75 33.5
700/800 G or H 119.52 - 57.27 33.5
700/800 I,J,K, or L 155.37 - 57.27 33.5
840/960 I,J,K, or L 184.61 - 57.27 62.73
Standard blower cabinet shown
5-565.14
DUCT INSTALLATION
*DIMENSION "B" SHOULD NEVER BE
LESS THAN 1/2 OF DIMENSION "A".
AIR
FLOW
SIDE VIEW
PROVIDE LEAK TIGHT ACCESS PANELS
IN SIDE OF DISCHARGE DUCT FOR
HEAT EXCHANGER INSPECTION
*DIMENSION "B" SHOULD NEVER BE
LESS THAN 1/2 OF DIMENSION "A".
AIR
FLOW
PROVIDE LEAK TIGHT ACCESS PANELS
IN SIDE OF DISCHARGE DUCT FOR
HEAT EXCHANGER INSPECTION
TOP VIEW
B*
12" MINIMUM
3" MINIMUM
TURNING VANES
3" MAXIMUM
A
B*
3" MINIMUM
TURNING VANES
3" MAXIMUM
A
12" MINIMUM
DUCT INSTALLATION
Furnace discharge duct connection
1. The furnace discharge is designed to accept straight
ductwork. (See Figure 5.1.) Provide an airtight seal
between the ductwork and the furnace. Seams with cracks
in the ductwork should be caulked and/or taped and be of
permanent type. All duct connections MUST be airtight to
prevent air leakage.
2. Provide removable access panels on the downstream side
of the ductwork. (See Figure 5.1.) This opening should be
large enough to view smoke or reflect light inside the casing
to indicate leaks in the heat exchanger and to check for hot
spots on heat exchangers due to poor air distribution or lack
of sufficient air (CFM).
Figure 5.1 - Furnace Discharge Duct Connection
Blower section and cooling cabinet discharge duct
connections
The blower section back and bottom and cooling cabinet
section discharge are designed to accept 90° flanged ductwork.
(See Figure 5.3.) Provide an airtight seal between the ductwork
and the unit. Seams with cracks in the ductwork should be
caulked and/or taped and be of permanent type. All duct
connections MUST be airtight to prevent air leakage.
3. Provide uniform air distribution over the heat exchanger. Use
turning vanes where required to obtain uniform air distribution.
(See Figure 5.2).
Figure 5.2 - Recommended Field Installed Discharge
Duct Configurations for Blower Package Units
5-565.15
INSTALLATION
Venting
WARNING
1. Gas fired heating equipment must be vented - do not
operate unvented.
2. A built-in power exhauster is provided - additional external
power exhausters are not required or permitted.
3. If you are replacing an existing heater, it may be necessary
to resize the venting systems. Improperly sized venting
systems can result in vent gas leakage or the formation of
condensate. Refer to the National Fuel Gas Code ANSI
Z223.1 or CSA B149.1 latest edition. Failure to follow these
instructions can result in injury or death.
4. Under no circumstances should two sections of double wall
vent pipe be joined together within one horizontal vent system
due to the inability to verify complete seal of inner pipes.
NOTE: A vent is the vertical passageway used to convey
flue gases from the unit or the vent connector to the outside
atmosphere. A vent connector is the pipe which connects the
unit to a vent or chimney. Vent connectors serving Category
I appliances shall not be connected into any portion of
mechanical draft systems operating under positive pressure.
General Venting Instructions
1. Installation of venting must conform with local building codes,
or in the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1 (NFPA 54) - Latest Edition. In Canada,
installation must be in accordance with CAN/CGA-B149.1 for
natural gas units and CAN/CGA-B149.2 for propane units.
2. All vertically vented units are Category I. All horizontally vented
units are Category III. The installation must conform to the
requirements from Table 6.2 in addition to those listed below.
3. For units vented as Category I, refer to Table 6.1 for vent
sizing. Vent sizing for units vented as Category III are covered
in a later section on page 7. Do not use a vent pipe smaller
than the size of the outlet or vent transition of the appliance.
The pipe should be suitable corrosion resistant material.
Follow the National Fuel Gas Code for minimum thickness
and composition of vent material. The minimum thickness for
connectors varies depending on the pipe diameter.
Table 6.1 - Vertical Category I Vent Sizing Requirements
Vent Connector
Model Size
75-125
150-1754"5"➀
2006"6"
225-400
➀ Requires a 4" to 5" adapter for the larger vent pipe diameter.
4. For Category I vent systems limit length of horizontal runs to
75% of vertical height. Install with a minimum upward slope
from unit of 1/4 inch per foot and suspend securely from
overhead structure at points no greater than 3 feet apart.
For best venting, put vertical vent as close to the unit as
possible. A minimum of 12" straight pipe is recommended
from the power exhauster outlet before turns in the vent
system. Fasten individual lengths of vent together with at
least three corrosion-resistant sheet-metal screws.
5. It is recommended that vent pipes be fitted with a tee with a
drip leg and a clean out cap to prevent any moisture in the
vent pipe from entering the unit. The drip leg should be inspected
and cleaned out periodically during the heating season.
6. The National Fuel Gas Code requires a minimum clearance
of 6 inches from combustible materials for single wall vent
pipe. The minimum distance from combustible materials is
based on the combustible material surface not exceeding
160°F. Clearance from the vent pipe (or the top of the unit)
may be required to be greater than 6 inches if heat damage
other than fire (such as material distortion or discoloration)
could result.
Diameter
4"4"
6”6”
Minimum Vent Pipe
Diameter
7. Avoid venting through unheated space. When venting does
pass through an unheated space, insulate runs greater than
5 feet to minimize condensation. Inspect for leakage prior to
insulating and use insulation that is noncombustible with a
rating of not less than 350°F. Install a tee fitting at the low
point of the vent system and provide a drip leg with a clean
out cap as shown in Figure 7.1.
INegative vent pressure Follow standard venting
Non-condensing requirements.
IINegative vent pressure Condensate must be
Condensing drained.
IIIPositive vent pressure Vent must be gastight.
Non-condensing
IVPositive vent pressure Vent must be liquid and
Condensing gastight. Condensate must
be drained.
8. When the vent passes through a combustible wall or floor,
a metal thimble 4 inches greater than the vent diameter is
necessary. If there is 6 feet or more of vent pipe in the
open space between the appliance and where the vent
pipe passes through the wall or floor, the thimble need only
be 2 inches greater than the diameter of the vent pipe. If a
thimble is not used, all combustible material must be cut
away to provide 6 inches of clearance. Any material used
to close the opening must be noncombustible.
9. Do NOT use dampers or other devices in the vent pipes.
10. Precautions must be taken to prevent degradation of
building materials by flue products.
11. For category I vent systems the outlet of the vent should
extend as shown in Figure 7.1 and Table 7.1 if the following
conditions are met:
• Vent diameter is less than 12 inches, vent is of double
wall construction and is a listed product, and the vent
does not terminate within 2' of a vertical wall or similar
obstruction.
• For vents that have a diameter of 12 inches or larger,
constructed of single wall, or terminate within 2' of a
vertical wall or similar obstruction, the vent pipe shall
extend at least 2' higher than any portion of a building
within a horizontal distance of 10' (refer to Figure 7.1).
12. Use a listed vent terminal to reduce downdrafts and
moisture in vent.
13. For instructions on common venting refer to the National
Fuel Gas Code.
14. The vent must terminate no less than 5' above the vent
connector for Category I vent systems.
15. A unit located within an unoccupied attic or concealed space
shall not be vented with single wall vent pipe.
16. Single wall vent pipe must not pass through any attic, inside
wall, concealed space, or floor.
17. Do NOT vent this appliance into a masonry chimney.
18. When condensation may be a problem, the venting system
shall not terminate over public walkways or over an area
where condensation or vapor could create a nuisance or
hazard or could be detrimental to the operation of regulator
relief openings or other equipment.
19. In cold ambient conditions, such as Canada, the following
items are recommended for proper operation and
equipment life:
• The vent pipe must not pass through an unheated space
or interior part of an open chimney unless the vent pipe is
insulated.
• Where the vent pipe may be exposed to extreme cold, or
come into contact with snow or ice, the entire vent must
be insulated or double wall (includes outdoors). It is
preferred that the double wall vent is one continuous
piece but a joint is allowed outside the building.
• The heater system shall be checked at least once a year
by a qualified service technician.
5-565.16
12" MIN
RECOMMENDED
4" MIN
TEE WITH DRIP LEG
AND CLEANOUT CAP
(SLOPE 1/4" PER
FOOT DOWNWARD
TOWARD DRIP LEG)
EXHAUST
"H" MIN*
12" MIN
RECOMMENDED
4" MIN
BACK VIEW
ROOF PITCH IS:
X / 12
TEE WITH DRIP LEG
AND CLEANOUT CAP
(SLOPE 1/4" PER
FOOT DOWNWARD
TOWARD DRIP LEG)
ROOF FLASHING
USE LISTED THIMBLE
THROUGH ROOF AND
CEILING
EXHAUST
12
X
LISTED TERMINAL
* SIZE ACCORNING
TO EXPECTED
SNOW DEPTH.
TO WALL OR ADJOINING BUILDING
2' MIN
2' MIN*
USE THIMBLE
THROUGH
CELLING
ROOF FLASHING
TERMINAL
METAL
SLEEVE
FIBER GLASS
INSULATION
MIN. 2"
2" MIN.
VENT TERMINATION
SUPPORT BRACKET
(where required)
(Make from 1" x 1" steel angle)
9"
9"
45
1"
METAL
SLEEVE
2" MIN.
VENT PIPE
DIAMETER
METAL FACE
PLATE
1"
12" min
TEE WITH DRIP LEG
AND CLEANOUT CAP
AT LOW POINT OF
VENT SYSTEM
POWER EXHAUSTER OUTLET
PITCH VENT PIPE DOWNWARD
FROM UNIT 1/4" PER FOOT
12"
Min.
GARY STEEL
MODEL 1092 TERMINAL
INSTALLATION
Figure 7.1 - Vertical Category I Vent System
Table 7.1 - Minimum Height from Roof to Lowest
Discharge Opening
Rise X (in) Roof Pitch Min Height H (ft) ➀
0-6 Flat to 6/12 1.00
6-7 6/12 to 7/12 1.25
7-8 7/12 to 8/12 1.50
8-9 8/12 to 9/12 2.00
9-10 9/12 to 10/12 2.50
10-11 10/12 to 11/12 3.25
11-12 11/12 to 12/12 4.00
12-14 12/12 to 14/12 5.00
14-16 14/12 to 16/12 6.00
16-18 16/12 to 18/12 7.00
18-20 18/12 to 20/12 7.50
20-21 20/12 to 21/12 8.00
➀ Size according to expected snow depth.
Additional Requirements for Horizontally Vented
Category III Units
1. Seal the joints with a metallic tape or silastic suitable for
temperatures up to 350°F. (3M tapes 433 or 363 are
acceptable.) Wrap tape two full turns around the vent pipe.
2. Refer to Table 7.2 for total minimum and maximum vent
lengths making the vent system as straight as possible.
The equivalent length of a 90° elbow is 5 feet for 4" diameter
and 7 feet for 6" diameter.
Table 7.2 - Horizontal Category III Vent Sizing
Requirements
Vent Connector
Model Size
75
100-175
200
225
250-300
350-400
➀ Unit can be vented with 5" diameter pipe if a 6" to 5" reducer is used.
Otherwise, use 6" pipe.
Diameter
4"4"48'
4"4"55'
6"
6"
6"6"63'
6"6"70'
3. The vent terminal must be a Gary Steel 1092.
4. The vent must extend a minimum of 12" beyond the exterior
wall surface as shown in Figure 7.2. The vent must be
supported as shown in Figure 7.3. Precautions must be taken
to prevent degradation of building materials by flue products.
5. The vent system shall terminate at least 3 feet above any
forced air inlet (except direct vent units) located within 10 feet,
and at least 4 feet below, 4 feet horizontally from, or 1 foot
above any door, window, or gravity air inlet into any building.
The bottom of the vent terminal shall be located above the
snow line or at least 1 foot above grade; whichever is greater.
When located adjacent to public walkways the vent system
shall terminate not less than 7 feet above grade.
6. The venting system must be exclusive to a single unit, and
no other unit is allowed to be vented into it.
7. Horizontally vented units must use single wall vent pipe
although one continuous section of double wall vent pipe
may be used with the vent system. Under no circumstances
should two sections of double wall vent pipe be joined
together within one vent system due to the inability to verify
complete seal of inner pipes.
Minimum Vent
Pipe Diameter
5" ➀70'
6"70'
Maxium Vent
Length
Figure 7.2 - Horizontal Venting
Figure 7.3 - Venting Through Combustible Walls
5-565.17
UNIT INSTALLATION
GAS
SUPPLY LINE
GAS
SUPPLY LINE
GROUND
JOINT
UNION
W/ BRASS
SEAT
MANUAL GAS
SHUT-OFF V A LV E
3"
MIN.
SEDIMENT
TRAP
PLUGGED
1/8" NPT TEST
GAGE CONNECTION
TO
CONTROLS
Gas Connections
WARNING
1. All field gas piping must be pressure/leak tested prior to
operation. Never use an open flame. Use a soap solution or
equivalent for testing.
2. Gas pressure to appliance controls must never exceed 14"
W.C. (1/2 psi).
3. To reduce the opportunity for condensation, the minimum
sea level input to the appliance, as indicated on the serial
plate, must not be less than 5% below the rated input, or 5%
below the minimum rated input of duel rated units.
CAUTION
Purging of air from gas supply line should be performed as
described in ANSI Z223.1 - latest edition “National Fuel Gas
Code”, or in Canada in CAN/CGA-B149 codes.
IMPORTANT
To prevent premature heat exchanger failure, the input to the
appliance, as indicated on the serial plate, must not exceed
the rated input by more than 5%.
1. Installation of piping must conform with local building codes,
or in the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1 (NFPA 54) - Latest Edition. In Canada,
installation must be in accordance with CAN/CGA-B149.1
for natural gas units and CAN/CGA-B149.2 for propane
units.
2. Piping to units should conform with local and national
requirements for type and volume of gas handled, and
pressure drop allowed in the line. Refer to Table 14.1
to determine the cubic feet per hour (cfh) for the type of
gas and size of unit to be installed. Using this cfh value
and the length of pipe necessary, determine the pipe
diameter from Table 8.1. Where several units are served
by the same main, the total capacity, cfh and length of
main must be considered. Avoid pipe sizes smaller than
1/2". Table 8.1 allows for a 0.3" W.C. pressure drop in the
supply pressure from the building main to the unit. The inlet
pressure to the unit must be 6-7" W.C. for natural gas and
11-14" W.C. for propane gas. When sizing the inlet gas
pipe diameter, make sure that the unit supply pressure can
be met after the 0.3" W.C. has been subtracted. If the 0.3"
W.C. pressure drop is too high, refer to the Gas Engineer’s
Handbook for other gas pipe capacities.
3. The gas piping to the unit can enter the unit from the side of
the unit or from below. Install a ground joint union with brass
seat and a manual shut-off valve external of the unit casing,
and adjacent to the unit for emergency shut-off and easy
servicing of controls, including a 1/8" NPT plugged tapping
accessible for test gauge connection
(See Figure 8.1). Verify the manual shut-off valve is gas
tight on an annual basis.
4. Provide a sediment trap before each unit in the line where
low spots cannot be avoided. (See Figure 8.1).
5. When Pressure/Leak testing, pressures above 14" W.C.
(1/2 psi), close the field installed shut-off valve, disconnect
the appliance and its combination gas control from the gas
supply line, and plug the supply line before testing. When
testing pressures 14" W.C. (1/2 psi) or below, close the
manual shut-off valve on the appliance before testing.
Figure 8.1 - Recommended Sediment Trap/Manual
Shut-off Valve Installation - Side or Bottom Gas
Connection
➀
➀ Manual shut-off valve is in the “OFF” position when handle is perpendicular
to pipe.
Table 8.1 - Gas Pipe Capacities
Gas Pipe Capacities (Up to 14” W.C. Gas Pressure through Schedule 40 Pipe)
Cubic Feet per Hour with Pressure Drop of 0.3” W.C.
Natural Gas - Specific Gravity - 0.60
Propane Gas - Specific Gravity - 1.50
5-565.18
BLOWER
SECTION
DOOR
ELECTRICAL
SECTION
DOOR
DUCT
FURNACE
ELECTRIC SUPPLY
COMPONENTS MUST BE
CLEAR OF SERVICE DOORS
DISCONNECT
SWITCH WIRING,
AND CONNECTOR
UNIT INSTALLATIONUNIT INSTALLATION
Electrical Connections
WARNING
1. Disconnect power supply before making wiring connections
to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with
wiring diagram furnished with the appliance. Any wiring
different from the wiring diagram could result in a hazard
to persons and property.
3. Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature
rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% greater than rated
voltage.
CAUTION
Ensure that the supply voltage to the appliance, as indicated
on the serial plate, is not 5% greater than rated voltage.
1. Installation of wiring must conform with local building codes,
or in the absence of local codes, with the National Electric
Code ANSI/NFPA 70 - Latest Edition. Unit must be electrically grounded in conformance to this code. In Canada,
wiring must comply with CSA C22.1, Part 1, Electrical Code.
2. Two copies of the job specific wiring diagram are provided
with each unit, one located in the duct furnace electrical
junction box and one in the electrical section of the unit.
Refer to this diagram for all wiring connections.
3. The wire gauge must be sized according to the National
Electric Code or CSA code based on the power supply
voltage, amp draw, and length of run. Refer to Table 9.1
for maximum wire lengths. Once the wire gauge has been
determined, refer to Table 9.2 for the number of wires for
which the low voltage terminal blocks in the unit are rated.
Table 9.1 - Low Voltage (24V) Maximum Wire Length
(Feet)
NEC-1996, Table 310-17, Copper wire with 90°C insulation,
conductors in free space (not in conduit), 86°F ambient. For
other wire types, refer to the NEC of CSA code.
Wire Gauge
Model No. Trans.
Digit 15 VA 18 GA 16Ga 14 Ga 12 Ga 10 Ga
1 40 162 216 315 360 495
2 75 86 115 168 192 264
3 150 43 58 84 96 132
4 250 26 35 50 58 79
Table 9.2 - Number of Wires Per Terminal
Wire Gauge Number of Wires per Terminal
#10 AWG 1
#12 AWG 1 to 2
#14 AWG 1 to 3
#16 AWG 1 to 4
#18 AWG 1 to 5
#22 AWG 2 to 5
4. Make sure all multi-voltage components (motors, transformers, etc.) are wired in accordance with the power supply
voltage.
5. The power supply to the unit must be protected with a fused
or circuit breaker disconnect switch. Refer to the Factory
Mounted Option Locations (Figure 18.1) for the factory
mounted disconnect switch location and then review the
unit to determine if a factory installed dead front disconnect
switch was provided. Accessory field installed disconnect
switches should be mounted where shown in Figure 9.1. For
fusible disconnect switches, refer to the Model Identification
plate for the fuse size and type.
6. The power supply must be within 5% of the voltage rating
and each phase must be balanced within 2 percent of each
other. If not, advise the utility company.
7. External electrical service connections that must be installed
include:
a. Supply power connection (120, 208, 240, 480, or 600
volts).
b. Connection of thermostats, remote monitoring panels,
building pressure sensors, CO detectors, time clocks, or
any other accessory control devices that may be supplied
(24 volts).
8. Refer to the unit dimensional drawings on Figures 43.1
through 44.1 for the electrical knock-out locations.
9. All supply power electrical connections are made in the
electrical section of the unit. The low voltage (thermostat
and accessory control devices) can be wired to either the
electrical section or the duct furnace electrical junction box.
Refer to the wiring diagram for the terminal location of all low
voltage wiring.
Cooling Coil Units
Models with a cooling section can be provided with either a
factory installed direct expansion (DX) evaporator, a chilled
fluid (for use with water, ethylene glycol, or propylene glycol
fluids) coil, or the coil can be field supplied and installed by
others. For units equipped with a factory installed cooling coil
(Digit 23 = 1), refer to the packing slip to determine the coil type
provided. The cooling section is located downstream of the
duct furnace heat exchanger in a blow-through configuration,
preventing condensation on the heat exchanger in the cooling
mode. Thus, a stainless steel heat exchanger is not required
when a cooling section is used. (However, a stainless steel heat
exchanger is still recommended when the combined entering/
return air to the unit is below 40°F.)
5-565.19
UNIT INSTALLATIONUNIT INSTALLATION
Suctio n Line
Expansion Valve
Remot e Sens ing Bulb
Straps
Suctio n Connection
Coil
Suctio n Header
Distributor
Equali zer Line
Nozzle
Liquid Line
(By Others)
The cooling section includes a full coverage, 3-way sloping
409 stainless steel drain pan to remove condensate from coil
headers, thermal expansion valves, and refrigerant piping.
Insulation is standard on outdoor units and optional on indoor
units and double wall construction is optional on all units. The
cabinet includes two doors, a removable upper door for service
access to the coil once the plumbing has been installed and a
lower door which includes a factory supplied 1" stubbed drain
connection to the exterior of the cabinet. Field connections for
coil inlet and outlet piping can be made through the cabinet
corner post or back of the unit. The cooling section duct
transition includes 1-1/2" flanges for fastening the sides of
the coil. The bottom duct transition is angled to remove any
condensation that may be entrained in the supply air stream.
For field supplied coils, do not exceed the maximum coil
dimensions listed in Literature 82-135. The dimensions listed
are for the maximum coil dimensions. If the coil supplied is
smaller than the listed dimensions, field supplied blank off
plates are required to prevent air bypass around the coil. The
coil is supported by two 14 gauge support rails which contain
mounting provisions for fastening 4", 5", 6", 7.5", 8.5", and
10" deep coils. When obtaining the specifications from a coil
manufacturer, it is important to obtain the pressure drop through
the coil so that the proper motor horsepower can be selected.
Figure 10.1 - Cooling Section
Optional double
wall construction
DX single circuit (shown) and
dual circuit coils available
Direct Expansion (DX) Piping
The refrigerant lines should be insulated to prevent warming
or cooling of the refrigerant. If the suction line is allowed to be
cooled, liquid will condense in the line and can severely damage
the compressor. If the liquid line is warmed, the refrigerant
can "flash" into a gas. This will cause erratic operation of
the expansion device and impair the heat transfer ability of
the cooling coil. Long runs of piping need to be periodically
supported to prevent excess vibration that can damage the
piping and joints. It is recommended to provide dampening
supports at intervals of length equivalent to 15 tube diameters.
Figure 10.2 - General DX Piping
Optional Factory
Installed
DX or Chilled
Water coil.
Fin spacings
of 6,8,10,12
or 14 fins per
inch
Adjustable
mounting bracket
for 2,3,4 and 6
row coils
Full coverage
3-way sloping
409 stainless
steel drain pan
Right or left hand coil
header access to
1” stubbed drain
connection
match gas controls
For Both Chilled Water and Direct Expansion Coils: The
condensate drain line needs to include a P-trap immediately
downstream of the connection to the unit. This trap should
extend at least two inches below the connection to prevent
air pressure from forcing air into the unit. The trap should be
primed with a water/glycol solution to prevent freezing. All points
where refrigerant, water or condensate lines enter the structure
should be sealed and vibration dampened. Include shut-off
valves to isolate the cooling coil from the system in order to
remove the coil for service or replacement without draining the
entire system. For additional guidelines, refer to the ASHRAE
Fundamentals Handbook section of piping recommendations.
1. Inspect the refrigerant distributor and verify that the nozzle
is in place.
2. All field brazing and welding should be performed using
high quality materials and an inert gas purge (such as
nitrogen) to reduce oxidation of the internal surface of the coil.
3. Connect the suction line and suction connection.
4. Install the expansion valve (By Others). Follow the
expansion valve manufacturer's recommendations for
installation to avoid damaging the valve.
5. The expansion valve's remote sensing bulb should be
securely strapped to the horizontal run of the suction line
at the 3 or 9 o'clock position and insulated.
6. Connect the liquid line to the expansion valve. Pressurize
the coil, expansion valve assembly and suction connection
to 100 psig with dry nitrogen or other suitable gas. The coil
should be left pressurized for a minimum of 10 minutes.
7. If the coil holds pressure, the hook-up can be considered
leak free. If the pressure drops by 5 psi or less,
repressurize the coil and wait another 10 minutes. If the
pressure drops again, there are more than likely one or
more small leaks, which should be located and repaired.
Pressure losses greater than 5 psi would indicate a larger
leak, which should be isolated and repaired. Be sure to
check valves and fittings as potential sites for leakage or
bleed. If the coil is found to be leaking, contact your local
factory representative.
5-565.110
UNIT INSTALLATION
Air Vent
Gate Va lve
T e e
Vent Plug
Re
t
u
r
n
A
i
r
F
l
o
w
Supply
Dirt Leg
Cap
Union
Drain Plug
Table 11.1 - Cooling Coil Performance Limits
DX - Single Circuit DX - Dual Circuit Chilled Water Max. Cooling Tons ② ③
Model
Max Coil Area Max Coil Area Max Coil Area DX Chilled
➀ Based on 550 feet per minute (FPM) coil face velocity.
➁ 1 Ton = 12,000 Btu/Hr
➂ Based on 95°F Entering Dry Bulb, 75°F Entering Wet Bulb.
➃ Model Size 75 CFM listed for Chilled Water - DX Single Circuit CFM minimum is 688 and DX Dual Circuit CFM min is 621.
➄ Model Size 100 CFM listed for Chilled Water - DX Single Circuit CFM minimum is 802 and DX Dual Circuit CFM min is 745.
8. Use a vacuum pump to evacuate the coil and any
Figure 11.1 - General Chilled Fluid Piping
interconnecting piping that has been open to atmosphere.
Measure the vacuum in the piping using a micron gauge
located as far from the pump as possible (the vacuum at
the pump will be greater than the rest of the system).
Evacuate the coil to 500 microns or less then close the
valve between the pump and the system. If the vacuum
holds to 500 microns or less for one minute, the system
is ready to be charged or refrigerant pumped down in
another portion of the system can be opened to the coil.
A steady rise in microns would indicate that moisture is still
present and that the coil should be further vacuumed until
the moisture has been removed.
9. Failure to obtain a high vacuum is indicative of a great
deal of moisture or a small leak. Break the vacuum with
a charge of dry nitrogen or other suitable gas and recheck
for leaks (soapy water works well). If no leaks are found,
continue vacuuming the coil until the desired vacuum is
reached.
10. All field piping must be self-supporting.
Chilled Fluid Piping
To prevent noise within a system, an air vent is necessary to
bleed off the accumulated air in the system. The vent should be
located on the top of the inlet manifold where the air collects.
This vent should be opened twice a year. Air in the system will
generate noise and may cause water hammer than can damage
the joints of the piping and the cooling coil.
The outlet manifold should have a drain installed on the bottom
of the manifold to allow for periodic flushing of the system to
remove sediments and corrosion products from the cooling
coil. This drain should be opened to allow some fluid to drain
twice a year. Check coloration and viscosity of the effluent for
indications of corrosion in the system. The lines between the
unit and the structure should be insulated to prevent freezing of
the water.
1. Once installed, the coil should be pressurized to 100 psig
with dry nitrogen or other suitable gas. The coil should be
left pressurized for a minimum of 10 minutes. If the coil
holds the pressure, the hook-up can be considered leak
free. If the pressure drops by 5 psig or less re-pressurize
the coil and wait another 10 minutes. If the pressure drops
again, there is more than likely one or more small leaks
which should be located and repaired. Pressure losses
greater than 5 psig would indicate a larger leak that should
be isolated and repaired. If the coil itself is found to be
leaking, contact your local factory representative.
2. All field brazing and welding should be performed using
high quality materials and an inert gas purge (such as
nitrogen) to reduce oxidation of the internal surface of
the coil.
3. All field piping must be self supporting. System piping
should be flexible enough to allow for thermal expansion
and contraction of the coil.
5-565.111
UNIT INSTALLATION / START-UP PROCEDURE
Operation
General - All coils
1. Proper air distribution is vital to coil performance. Air flow
anywhere on the coil face should not vary by more than
20%.
2. Air velocities should be maintained between 200 and 550
feet per minute.
3. For chilled fluid coils, fluid velocities should be maintained
within the recommended values of 1 to 8 fps for Water and
1 to 6 fps for Glycol solutions.
Chilled fluid coils - Initial Start-Up
1. Open all air vents so that air is eliminated from within the
coil circuitry and headers. Verify that all vents and drains
are not obstructed and do discharge a stream of water.
2. Fill the coil with water then close all vents.
3. Perform an initial hydrostatic leak test of all brazed,
threaded or flanged joints, valves and interconnecting
piping. Recheck the coil level and correct if necessary.
When the setup is found to be leak free, discharge and
discard initial water charge. It is important that all grease,
oil, flux and sealing compounds present from the
installation be removed.
Maintenance
General
1. Filters should be inspected on a regular basis and
changed as needed. Maintaining clean filters is a costeffective way to help maintain maximum coil performance
and service life.
2. Periodic inspection of the coil for signs of corrosion and for
leaks is recommended. For DX coils, Small leaks can be
detected using a Halide torch. Repair and replacement of
the coil and the connecting piping, valves, etc., should be
performed as needed by a qualified individual(s).
3. Should the coil surface need cleaning, caution should be
exercised in selecting the cleaning solution as well as the
cleaning equipment. Improper selection can result in
damage to the coil and/or health hazards. Clean the coil
from the leaving air-side so that foreign material will be
washed out of the coil rather than pushed further in. Be
sure to carefully read and follow the cleaning fluid
manufacturer's recommendations before using any
cleaning fluid.
4. For DX coils, the use of filter-dryers in the system piping is
recommended along with a sight glass that has a moisture
indicator. Replace the filter dryer(s) as needed.
5. For chilled fluid coils,
A) Maintain the circulated fluid free of sediment, corrosive
products and biological contaminants. Periodic testing
of the fluid followed by any necessary corrective
measures along with maintaining adequate fluid
velocities and proper filtering of the fluid will help to
satisfy this goal.
B) Automatic air vents must be utilized to remove
accumulated air.
C) Freeze Protection - During the winter, chilled water coils
need to be protected against freezing. The two
predominant protective measures are 1) Blowing-out
the coils with air or 2) Flushing coils with inhibited
glycol. It is recommended to use inhibited glycol
designed for HVAC applications for corrosion
protection. Select an inhibited glycol solution that will
protect the coil from the lowest possible temperatures
that can occur at the particular coil's locality.
Start-Up Procedure
IMPORTANT
1. To prevent premature heat exchanger failure, observe heat
exchanger tubes by looking at the heat exchanger through
the field installed access openings in connecting ductwork
in blower package units or the unit access doors in
cooling package units. If the bottom of the tubes become
red while blower and duct furnace are in operation, check
to be sure the blower has been set to the proper rpm for
the application. Refer to page 15 for Blower Adjustments.
2. Start-up and adjustment procedures should be performed
by a qualified service agency.
1. Turn off power to the unit at the disconnect switch. Check
that fuses or circuit breakers are in place and sized correctly. Turn all hand gas valves to the “OFF” position.
2. Remove the blower exterior panels and open the electrical
compartment door.
3. Check that the supply voltage matches the unit supply voltage listed on the Model Identification plate. Verify that
all wiring is secure and properly protected. Trace circuits to
insure that the unit has been wired according to the wiring
diagram.
4. Check to insure that the venting system is installed and
free from obstructions.
5. Check to see that there are no obstructions to the intake
and discharge of the unit.
6. Check the belt tension and sheave alignment. Refer to Blower Adjustments for proper belt tension.
7. Check bearings for proper lubrication. For units provided
with pillow block bearings (See Model Nomenclature), refer
to Lubrication Recommendations for lubrication requirements.
8. Check to make sure that all filters are in place and that they
are installed properly according to direction of air flow.
9. Perform a visual inspection of the unit to make sure no damage has occurred during installation.
10. Turn on power to the unit at the disconnect switch. Check to
insure that the voltage between duct furnace electrical box
terminals 1 and 2 is 24V.
11. Check the thermostat, ignition control, gas valve, and supply fan blower motor for electrical operation. If these do
not function, recheck the wiring diagram. Check to insure
that none of the Control Options have tripped.
12. For units with a return air damper, the return air damper
linkage needs to be adjusted. Refer to Damper Linkage
Adjustment.
13. Check to make sure that the damper opens properly without binding.
14. Check the blower wheel for proper direction of rotation when compared to the air flow direction arrow on the blower housing. Blower wheel rotation, not air movement,
must be checked as some air will be delivered through the
duct furnace with the blower wheel running backwards.
15. Check the blower speed (rpm). Refer to Blower Adjustments for modification.
16. Check the motor speed (rpm).
17. Check the motor voltage. On three phase systems, check
to make sure all legs are in balance.
18. Check the motor amp draw to make sure it does not exceed the motor nameplate rating. On three phase systems, check all legs to insure system is balanced.
5-565.112
UNIT INSTALLATION / START-UP PROCEDURE
19. Recheck the gas supply pressure at the field installed
manual shut-off valve. The minumum inlet pressure should
be 6" W.C. on natural gas and 11" W.C. on propane gas.
The maximum inlet pressure for either gas is 14" W.C. If
inlet pressure exceeds 14" W.C., a gas pressure regulator
must be added upstream of the combination gas valve.
20. Open the field installed manual gas shut-off valve.
21. Open the manual main gas valve on the combination gas
valve. Call for heat with the thermostat and allow the pilot
to light for intermitent pilot ignition. If the pilot does not light,
purge the pilot line. If air purging is required, disconnect the
pilot line at outlet of pilot valve. In no case should line be
purged into heat exchanger. Check the pilot flame length
(See Pilot Flame Adjustment).
22. Once the pilot has been established, check to make sure
that the main gas valve opens. Check the manifold gas
pressure (See Main Gas Adjustment) and flame length (See
Air Shutter Adjustment) while the supply fan blower is
operating.
23. Check to insure that gas controls sequence properly (See
Control Operating Sequence). Verify if the unit has any
additional control devices and set according to the
instructions in the Control Options.
24. Once proper operation of the unit has been verified, remove
any jumper wires that were required for testing.
25. Close the electrical compartment door.
26. Replace all exterior panels.
Refer to page 54 for the Start-up Checklist.
Pilot Burner Adjustment
The pilot burner is orificed to burn properly with an inlet pressure
of 6-7" W.C. on natural gas and 11-14" W.C. on propane gas,
but final adjustment must be made after installation. If the pilot
flame is too long or large, it is possible that it may cause soot
and/or impinge on the heat exchanger causing failure. If the
pilot flame is shorter than shown, it may cause poor ignition and
result in the controls not opening the combination gas control.
A short flame can be caused by a dirty pilot orifice. Pilot flame
condition should be observed periodically to assure trouble-free
operation.
To Adjust the Pilot Flame
1. Create a call for heat from the thermostat.
2. Remove the cap from the pilot adjustment screw. For location,
see the combination gas control literature supplied with unit.
3. Adjust the pilot length by turning the screw in or out
to achieve a soft steady flame 3/4" to 1" long and
encompassing 3/8"-1/2" of the tip of the thermocouple or
flame sensing rod (See Figure 13.1).
4. Replace the cap from the pilot adjustment screw.
Figure 13.1 - Correct Pilot Flame
3/4" to 1"
Main Burner Adjustment
The gas pressure regulator (integral to the combination gas
control) is adjusted at the factory for average gas conditions.
It is important that gas be supplied to the duct furnace in
accordance with the input rating on the serial plate. Actual
input should be checked and necessary adjustments made
after the duct furnace is installed. Over-firing, a result of too
high an input, reduces the life of the appliance and increases
maintenance. Under no circumstances should the input exceed
that shown on the serial plate.
Measuring the manifold pressure is done at the tee in the
manifold or at the pressure tap of the gas valve for standard gas
string. (See Figure 14.1).
To Adjust the Manifold Pressure
1. Move the field installed manual shut-off valve to the “OFF”
position.
2. Remove the 1/8" pipe plug in the pipe tee or gas valve and
attach a water manometer of “U” tube type which is at least
12" high.
3. Move the field installed manual gas shut-off valve to the
“ON” position.
4. Create a high fire call for heat from the thermostat.
5. Determine the correct high fire manifold pressure. For
natural gas 3.5” W.C., for propane gas 10” W.C. Adjust the
main gas pressure regulator spring to achieve the proper
manifold pressure (for location, see the combination gas
control literature supplied with unit).
6. If the unit has Electronic Modulation gas controls (determine
from the Model Identification Digit 12), the low fire gas
pressure needs to be adjusted. Using Figure 14.2 for item
number locations, this is accomplished as follows:
a. Disconnect power.
b. Remove all wires from Maxitrol Amplifier terminal “3” or
duct furnace terminal “43” (if available).
c. Turn on power at the disconnect switch.
d. Remove the maximum adjustment screw (4), spring
(5), and plunger (8). A small magnet is useful for this
purpose. CAUTION - The plunger is a precision part.
Handle carefully to avoid marring or picking up grease
and dirt. Do not lubricate.
e. Using minimum adjusting screw (9), adjust low fire
manifold pressure to 0.56" W.C. for natural gas and
1.6" W.C. for propane gas.
f. Replace plunger and spring retainer, spring, and
maximum adjusting screw in proper order.
g. Using maximum adjustment screw (4), adjust high fire
manifold pressure to 3.5" W.C. for natural gas and 10"
W.C. for propane gas.
h. Disconnect power.
i. Replace cover plate (2) and re-install all wires from
Maxitrol amplifier terminal “3” or duct furnace terminal “43”.
7. After adjustment, move the field installed manual shut-off
valve to the “OFF” position and replace the 1/8" pipe plug.
8. After the plug is in place, move the field installed manual
shut-off valve to the “ON” position and recheck pipe plugs
for gas leaks with soap solution.
5-565.113
START-UP PROCEDURE
Standard Controls
Premium Controls
Manifold Pressure Te st Point
Figure 14.1 - Checking Manifold Pressure with
“U” Tube Manometer
Proper operation provides a soft blue flame with a well-defined
inner core. A lack of primary air will reveal soft yellow-tipped
flames. Excess primary air produces short, well-defined flames
with a tendency to lift off the burner ports. For both natural
and propane gas, the air shutters can be adjusted to control
the burner flame height. The air shutters can be accessed by
reaching behind the gas valve in Figure 14.1. The larger models
may require the removal of the manifold (see Manifold Assembly
Removal).
Natural Gas Flame Control
Control of burner flames on duct furnaces utilizing natural gas
is achieved by resetting the primary air shutters (See Figure
48.4) to either increase or decrease primary combustion air.
Prior to flame adjustment, operate duct furnace for about fifteen
minutes. The main burner flame can be viewed after loosening
and pushing aside the gas designation disc on the side of the
burner box.
To increase primary air, loosen the air shutter set screws and
move the air shutters closer to the manifold until the yellowtipped flames disappear. (See Figure 48.4 for air shutter and
heat exchanger support locations.) To decrease primary air,
move the air shutters away from the manifolds until flames
no longer lift from burner ports, but being careful not to cause
yellow tipping. Retighten set screws after adjustment.
Propane Gas Flame Control
An optimum flame will show a slight yellow tip. Prior to flame
adjustment, operate furnace for at least fifteen minutes. Loosen
air shutter set screws and move the air shutters away from the
manifold to reduce the primary air until the yellow flame tips
appear. Then increase the primary air until yellow tips diminish
and a clean blue flame with a well defined inner cone appears.
Table 14.1 - Manifold Pressure and Gas Consumption
Model Size Type of Gas Natural Propane
Btu/Cu. Ft. 1040 2500
Specific Gravity 0.60 1.53
High Fire Manifold Pressure No. of
Inches of Water Column 3.5 10 Orifices
Cfh 72.1 30.0
75
Orifice Drill Size 20 37
Cfh 96.1 40.0
100
Orifice Drill Size 30 45
Cfh 120.2 50.0
125
Orifice Drill Size 25 42
Cfh 144.2 60.0
150
Orifice Drill Size 30 45
Cfh 168.3 70.0
175
Orifice Drill Size 27 43
Cfh 192.3 80.0
200
Orifice Drill Size 23 40
Cfh 216.3 90.0
225
Orifice Drill Size 20 37
Cfh 240.4 100.0
250
Orifice Drill Size 25 42
Cfh 288.7 120.0
300
Orifice Drill Size 20 37
Cfh 336.5 140.0
350
Orifice Drill Size 27 43
Cfh 384.6 160.0
400
Orifice Drill Size 23 40
Cfh 240.4 ➀100.0 ➀
500 ➀
Orifice Drill Size 25 42
Cfh 288.7 ➀ 120.0 ➀
600 ➀
Orifice Drill Size 20 37
Cfh 336.5 ➀ 140.0 ➀
700 ➀
Orifice Drill Size 27 43
Cfh 384.6 ➀ 160.0 ➀
800 ➀
Orifice Drill Size 23 40
Cfh 336.5 ➁ 140.0 ➁
840 ➁
Orifice Drill Size 27 43
Cfh 384.6 ➁ 160.0 ➁
960 ➁
Orifice Drill Size 23 40
➀ Model contains 2 furnaces. Values shown are per furnace.
➁ Model contains 3 furnaces. Values shown are per furnace.
1
2
2
3
3
3
3
4
4
6
6
➀
4
➀
4
➀
6
➀
6
➁
6
➁
6
5-565.114
START- UP PROCEDURE
To ward Motor
Set Screw
Adjustable Half
of Sheave
ROD
CONNECTING
JOINT
Blower Adjustments
If blower fan speed changes are required, adjust motor sheave
as follows:
1. Refer to page 34 to determine correct blower speed
according to job requirements, then proceed with steps 2
through 8.
2. Loosen motor base and take belt off of motor sheave.
3. Loosen set screw on outer side of adjustable motor sheave.
Figure 15.1 - Motor Sheave Adjustment
Damper Linkage Adjustment
If the unit is provided with a return air damper, to prevent
shipping damage, the return air damper linkage is disconnected
and the damper closed. Before operating the unit, the fresh and
return air dampers must be connected. This is accomplished by
the following:
1. The damper actuator should be de-energized and the fresh
air damper in a fully closed position.
2. Open the return air damper in a fully open position.
3. Slide the connecting rod into the ball joint on the blade arm
with the return air damper fully open. See Figure 15.3.
4. Tighten the 5/16" hex head screw on the ball joint.
Figure 15.3 - Damper Linkage Adjustment
4. Turn outer side of motor sheave clockwise until motor
sheave is fully closed.
5. From fully closed position, turn outer side of motor sheave
counterclockwise until the proper number of turns open are
achieved.
6. Retighten motor sheave set screw, replace belt and retighten
motor base. Motor base should be shifted for proper belt
tension which is 3/4" deflection with about 5 lbs. of force.
Figure 15.2 - Belt Tension Adjustment
3/4" deflection
with 5 lbs. of force
➪
7. Recheck blower rpm after adjustment.
NOTE: Do not fire unit until blower adjustment has been
made or unit may cycle on high limit control.
8. Check motor amps. Do not exceed nameplate amps shown
on motor nameplate.
Lubrication Recommendations
The blower can be provided with either spider or pillow block
bearings. Spider bearings are permanently lubricated and do not
require lubrication. Pillow block bearings are shipped greased
from the factory but will require lubrication. The bearings should
be checked and lubricated before each heating season but a
more frequent lubrication schedule may be required based on
the environment in which the unit is installed, and the frequency
of the equipment operation. Shell Alvania #2 lubricant is
recommended.
Control Operating Sequence
IMPORTANT
To prevent premature heat exchanger failure, with all control
systems, a blower starting mechanism must be provided so
that the blower is running or energized within 45 seconds of
the gas control operation.
Indoor power vented duct furnaces are supplied with intermittent
pilot systems with continuous retry as standard. On mechanical
modulation systems the main burner is turned off 100%
when the thermostat is satisified, but the pilot remains lit. For
intermittent pilot systems, except mechanical modulation both
the main burner and pilot burner are turned off 100% when
the thermostat is satisfied. Intermittent pilot systems, for both
natural and propane gas, the ignition controller is 100% shut-off
with continuous retry. On a call for heat, the system will attempt
to light the pilot for 70 seconds. If the pilot is not sensed for
any reason, the ignition control will wait for approximately six
minutes with the combination gas control closed and no spark.
After six minutes, the cycle will begin again. After three cycles,
some ignition controllers lockout for approximately one hour
before the cycle begins again. This will continue indefinitely until
the pilot flame is sensed or power is interrupted to the system.
NOTE: Gas Control Options (see page 16) could change the
listed sequence of operation based on their function.
The descriptions given are for the basic duct furnace.
5-565.115
START-UP PROCEDURE
Single-Stage Gas Controls (intermittent pilot)
Utilizes a single-stage combination gas control, an ignition
control, and a single-stage low voltage thermostat.
1. The thermostat calls for heat.
2. The power exhauster relay is energized starting the power
exhauster motor. Once the motor has reached full speed,
the differential pressure switch closes. The power exhauster
relay pre-purge timer closes after 20 to 40 seconds
energizing the gas control circuit.
3. The pilot valve opens and the spark ignitor sparks in an
attempt to light the pilot. (If the unit was not provided with a
time delay relay, the blower starts at this time.)
4. Once the pilot is lit, the flame sensor proves the pilot and
stops the spark ignitor from sparking.
5. The main gas valve is opened and the main burner is lit to
100% full fire.
6. If the unit was provided with a time delay relay, the blower
starts after 30 to 45 seconds.
7. The unit continues to operate until the thermostat is
satisfied, at which time both the main and pilot valves close
100%. (If the unit was not provided with a time delay relay,
the blower stops at this time).
8. If the unit was provided with a time delay relay, the blower
stops after 30 to 45 seconds.
Two-Stage Gas Controls (intermittent pilot)
Utilizes a two-stage combination gas control, an ignition control,
and a two-stage low voltage thermostat. The unit fires at 50%
fire on low stage and 100% fire on high stage.
1. The thermostat calls for low stage heat.
2. The power exhauster relay is energized starting the power
exhauster motor. Once the motor has reached full speed,
the differential pressure switch closes. The power exhauster
relay pre-purge timer closes after 20 to 40 seconds
energizing the gas control circuit.
3. The pilot valve opens and the spark ignitor sparks in an
attempt to light the pilot. (If the unit was not provided with a
time delay relay, the blower starts at this time.)
4. Once the pilot is lit, the flame sensor proves the pilot and
stops the spark ignitor from sparking.
5. The main gas valve is opened and the main burner is lit to
50% fire.
6. If the unit was provided with a time delay relay, the blower
starts after 30 to 45 seconds.
7. If the temperature at the thermostat continues to fall, the
thermostat will call for high stage heat.
8. The main gas valve is opened completely and the main
burner is lit to 100% full fire.
9. The unit continues to operate until the high stage of the
thermostat is satisfied, at which time the main valve closes
to 50% fire.
10. The unit continues to operate until the low stage thermostat
is satisfied, at which time both the main and pilot valves
close 100%. (If the unit was not provided with a time delay
relay, the blower stops at this time.)
11. If the unit was provided with a time delay relay, the blower
stops after 30 to 45 seconds.
Utilizes a mechanical modulating gas control and an ignition
control. The mechanical modulating gas control is designed
for use in constant blower applications. The discharge air
temperature is maintained by setting the control dial of the
modulating gas valve in one of ten positions. A hydrostatic
sensing bulb located in the discharge air stream controls the gas
flow between 40% through 100% full fire. When the discharge
air hydrostatic sensing bulb is satisfied, the modulating valve
closes completely, but the pilot remains lit. This control cannot
be used with a room override thermostat.
1. Power is supplied to the unit through either an exhaust fan
interlock contact or a start/stop switch.
2. The power exhauster relay is energized starting the power
exhauster motor. Once the motor has reached full speed,
the differential pressure switch closes. The power exhauster
relay pre-purge timer closes after 20 to 40 seconds
energizing the gas control circuit.
3. The pilot valve opens and the spark ignitor sparks in an
attempt to light the pilot. (If the unit was not provided with a
time delay relay, the blower starts at this time.)
4. Once the pilot is lit, the flame sensor proves the pilot and
stops the spark ignitor from sparking.
5. The hydrostatic sensing bulb, integral to the mechanical
modulating gas valve, calls for heat. The main gas valve is
opened and the main burner is lit. The burner modulates
between 40% through 100% fire based on the call for heat.
6. If the unit was provided with a time delay relay, the blower
starts after 30 to 45 seconds.
7. The unit continues to operate until the hydrostatic sensing
bulb is satisfied, at which time the main valve closes 100%,
but the pilot remains lit.
8. The unit blower (and pilot) continues to operate until either
an exhaust fan interlock contact or a start/stop switch is
opened. If the unit was provided with a time delay relay, the
blower stops after 30 to 45 seconds.
Electronic Modulating Gas Controls
Single Furnace - Model Sizes 75-400
Utilizes an electronic modulating/regulating gas control,
combination gas valve, an ignition control, modulating amplifier,
and either a modulating room thermostat or modulating duct
thermostat with remote temperature set point adjuster. The
thermostat controls can modulate the gas flow between 40%
through 100% full fire. When the thermostat is satisfied, the amplifier
cuts power to the combination gas valve which prevents gas
flow to both the main and pilot burners.
When duct sensing is utilized, a room override thermostat can
be added. When calling for heat, the room override thermostat
provides full fire operation until the space temperature is
satisfied. Control is then returned to the duct sensing control.
In this situation, either the duct sensor or the room override
thermostat can call for heat.
1. The thermostat calls for heat.
2. The power exhauster relay is energized starting the power
exhauster motor. Once the motor has reached full speed,
the differential pressure switch closes. The power exhauster
relay pre-purge timer closes after 20 to 40 seconds
energizing the gas control circuit.
3. The pilot valve opens and the spark ignitor sparks in an
attempt to light the pilot. (If the unit was not provided with a
time delay relay, the blower starts at this time.)
4. Once the pilot is lit, the flame sensor proves the pilot and
stops the spark ignitor from sparking.
5. The main gas valve is opened and the main burner is lit to
100% full fire.
6. If the unit was provided with a time delay relay, the blower
starts after 30 to 45 seconds.
7. The modulating gas valve can be controlled by either an
electronic modulating room or duct thermostat. The thermostat
can modulate the firing rate between 40% through 100% full
fire. The call for heat is created by a resistance signal (8000
to 12000 ohms) in the thermostat. The amplifier converts this
resistance into a DC voltage (0 to 12 volts DC with 0 volts
high fire and 12 volts low fire). The output voltage is applied
to the modulating gas valve to control the gas flow to the
5-565.116
START-UP PROCEDURE
main burner. As the temperature drops, the voltage drops
causing the modulating valve to open further. If the discharge
air temperature increases, the voltage increases causing the
modulating valve to close allowing less gas flow to the main
burner. For further information regarding the operation of the
electronic modulating system, consult the literature provided
with the unit.
8. The unit continues to operate in this manner until the
thermostat is satisfied, at which time both the main and pilot
valves close 100%. (If the unit was not provided with a time
delay relay, the blower stops at this time.)
9. If the unit was provided with a time delay relay, the blower
stops after 30 to 45 seconds.
Electronic Modulating Gas Controls
Two & Three Furnaces - Model Sizes 500-960
One Master furnace is provided with up to two Slave furnaces
that utilize electronic modulating/regulating gas controls,
combination gas valves, ignition controls, one multiple furnace
modulating amplifier, and either a modulating room thermostat
or modulating duct thermostat with remote temperature adjuster.
The thermostat controls can modulate the gas flow of all the
furnaces between 40% through 100% full fire. The amplifier
sends a signal to all of the gas valves so that they modulate
at the same percentage. When the thermostat is satisfied,
the amplifier cuts power to the combination gas valves which
prevents gas flow to both the main and pilot burners.
When duct sensing is utilized, a room override thermostat can
be added. When calling for heat, the room override thermostat
provides full fire operation until the space temperature is
satisfied. Control is then returned to the duct sensing control.
In this situation, either the duct sensor or the room override
thermostat can call for heat.
The sequence of operation for Electronic Modulating Gas
Controls - Two & Three Furnaces is the same as Electronic
Modulating Gas Controls - Single Furnace.
Electronic Modulating Gas Controls Building Management Control
(0-10 Vdc or 4-20 mA Signal)
Utilizes an electronic modulating/regulating gas control,
combination gas valve, an ignition control, modulating signal
conditioner, and an inverted (0 Vdc or 4 mA being high fire and
10 Vdc or 20 mA being low fire) 0-10 Vdc or 4-20 mA input
signal provided by a Building Management System (BMS).
The signal conditioner can modulate the gas flow between 40%
through 100% full fire. When the BMS thermostat (field supplied)
is satisfied, the BMS heat contact (field supplied) opens to cut
power to the combination gas valve which prevents gas flow to
both the main and pilot burners.
1. The BMS thermostat (field supplied) calls for heat and closes
the BMS heat contact (field supplied).
2. The power exhauster relay is energized starting the power
exhauster motor. Once the motor has reached full speed, the
differential pressure switch closes. The power exhauster relay
pre-purge timer closes after 20 to 40 seconds energizing the
gas control circuit.
3. The pilot valve opens and the spark ignitor sparks in an
attempt to light the pilot. (If the unit was not provided with a
time delay relay, the blower starts at this time.)
4. Once the pilot is lit, the flame sensor proves the pilot and
stops the spark ignitor from sparking.
5. The main gas valve is opened and the main burner is lit to
100% full fire.
6. If the unit was provided with a time delay relay, the blower
starts after 30 to 45 seconds.
7. The modulating gas valve is controlled by the BMS
thermostat. The thermostat can modulate the firing rate
between 40% through 100% full fire by modulating the
input signal between either 0-10 Vdc or 4-20 mA (The
signal conditioner can accept a 0-10 Vdc signal when all
the dip switches are in the “OFF” position and 4-20 mA
signal when all the dip switches are in the “ON” position).
The signal conditioner converts the input signal into a DC
voltage (0 to 12 volts DC with 0 volts high fire and 12 volts
low fire). The output voltage is applied to the modulating
gas valve to control the gas flow to the main burner. As the
temperature drops, the voltage drops causing the modulating
valve to open further. If the discharge air temperature
increases, the voltage increases causing the modulating
valve to close allowing less gas flow to the main burner. For
further information regarding the operation of the electronic
modulating system, consult the literature provided with the
unit.
8. The unit continues to operate in this manner until the
thermostat is satisfied, at which time the BMS heat contact
opens resulting in both the main and pilot valves closing
100%. (If the unit was not provided with a time delay relay,
the blower stops at this time.)
9. If the unit was provided with a time delay relay, the blower
stops after 30 to 45 seconds.
Variable Air Movement Applications
Units may be supplied with variable frequency drives for
applications where variable air volume is required. The minimum
air flow may be varied between 30 and 100% of the full speed
air flow depending on the controls selection of the unit. Due to the
extra restrictions of the controller all selections must be performed
with the AccuSpec configuration software. Within AccuSpec, three
variable frequency drive speed control changeover options are
available:
1. Two speed which may be controlled by a manual high/low
switch which may be factory mounted on the control panel or
shipped loose for field installation or by exhaust fan
interlocks.
2. Floating building pressure sensing which utilizes a photohelic
pressure controller to adjust the building pressure by
varying the amount of makeup air supplied to the the space.
3. Building management control which allows for an external
signal of 0-10VDC of 4-20mA to adjust the unit airflow.
Additionally, when the air mover supplied by others can provide
variable air movement (i.e. 2-speed or variable frequency drive
units), the allowable minimum CFM of the duct furnace can
be 66% of the minimum listed CFM in Table 26.1 if the unit is
applied as follows:
1. The unit is provided with 2-stage, mechanical modulation,
or electronic modulating gas controls. (see Model
Identification).
2. The unit is provided with a factory installed discharge air
controller.
3. The system does not include a room thermostat.
The factory installed discharge air thermostat will prevent the
unit from firing above the allowable 100°F rise when the unit is
at or above the minimum CFM by monitoring the discharge air
and going to low fire. A room thermostat, because it is located
remote from the unit, could cause the unit to over-fire.
5-565.117
OPTIONS
(Shown with cover removed)
Thermostat body
Box
Control
Electrical
Duct Furnace
RBW
WBR
Left
Right
Adjuster
Setpoint
Capillary
45
4340
38
36
34
Units with Premium Control Box
3230
946
48
12
13
10
50
49
5251 5547
4
6
5
1
2
3
8
27
25
23
21
19
17
15
16
18
2022
24
26
14
44423937353331
Options - Factory Installed
Figure 18.1 - Factory Mounted Option Locations
1. Discharge Thermostat
2. Low Gas Pressure Switch
3. High Gas Pressure Switch
4. Power Exhauster
5. Timed Freeze Protection
6. Ignition Controller
8. Control Relay
9. Differential Pressure Switch
10. Furnace Low Voltage Terminal Strip
12. Furnace Supply Power Terminal Strip
13. Control Step Down Transformer
14. Control Relay
15. Blower Low Voltage Terminal Strip
16. Dead Front Disconnect Switch
17. Step Down Transformer Fuses
18. Step Down Transformer
19. Factory Installed Minimum Positioner
20. Extended Grease Line Zerk Fittings
21. Extended Grease Lines
22. Return Air Fire Stat
23. Blower Housing
24. Pillow Block Bearings
25. Blower Motor
26. Filters
27. Fresh Air Damper
30. Direct Drive Damper Actuator
31. Enthalpy Controller
32. Damper to Damper Linkage
33. Return Air Damper
34. Proportional Temp Controller Sensor
35. Motor and Blower Vibration Isolation
36. Blower Support
All units include the standard (STD) features. The unit
must be reviewed to determine the optional (OPT)
features that may have been supplied with the unit.
(1) Discharge Thermostat – (OPT)
The discharge thermostat is factory installed in the discharge
air stream of the unit. For additional information, refer to
the thermostat vendor literature provided in the literature
packet with the unit.
NOTE: Model Sizes 500-960 contain multiple furnaces so multiple thermostats/sensors may be included. The thermostat(s) provided can be one of the following:
a) Two-stage Capillary Type Thermostat – The thermostat
includes a thermostat body that is factory installed for
cooling package units below the unit junction box. For
blower package units the thermostat is factory wired
and capilary is to be field installed in duct work. The
thermostat body contains the discharge air set point
adjuster that must be field set.
5-565.118
37. Convenience Outlet
38. Blower Door Switch
39. Dirty Filter Switch
40. Motor Starter/VFD Control
42. Proportional Temp Controller
43. Warm-Up Stat
44. Blower Supply Power Terminal Strip
45. Service Switches
46. Electronic Modulating Amplifier
47. Electronic Modulating Gas Valve
48. Air Flow Proving Switch
49. High Limit Switch
50. Supply Air Fire Stat
51. Main Gas Valve
52. Burner Box
55. Time Delay Relay
Figure 18.2 - Two-stage Capillary Type Thermostat
Duct
Furnace
Electrical
Control
Setpoint
Adjuster
Box
Thermostat body
(Shown with cover removed)
Capillary
OPTIONS
Duct Furnace
Electrical
Control
Box
Air flow
3
2
1
Mixing Tube
Discharge air
Sensor T e rminals
Gas Control Knob
Hydrostatic Sensing Bulb
HI
8
7
6
5
4
3
2
1
LO
IN
OFF
NO
Control Dial
Box
Control
Electrical
Duct Furnace
Sensor
Pressure adjustment screw
(High Pressure Switch only)
Reset Switch
C
NO
NC
Top: cover removed
b) Two-stage Electronic Type Thermostat - Includes a
factory installed discharge air sensor. The thermostat
body is field installed remotely and includes the discharge
air set point adjuster that must be field set. Refer to
Literature 5-577 latest revision.
Figure 19.1 - Two-stage Electronic Type Thermostat Sensor
Duct
Furnace
Electrical
Control
Box
Sensor
c) Mechanical Modulating Sensing Bulb - The mechanical
modulating valve includes a hydrostatic sensing bulb that
is factory installed in the discharge air stream for cooling
package units. For blower package units the sensing
bulb is temporarilly afixed to the side of unit to be field
installation in duct work. The discharge air temperature
is field set by the control dial on the modulating gas
valve. Refer to Control Operating Sequence - Mechanical
Modulating Gas Controls for set point temperatures.
Figure 19.2 - Mechanical Modulating Sensing Bulb
Hydrostatic Sensing Bulb
Gas Control Knob
Control Dial
d) Electronic Modulating Discharge Air Thermostat –
Includes a factory installed mixing tube and discharge
air sensor for cooling package units. For blower package
units, the air sensor is factory wired but field installed in
duct work. The set point adjuster is field installed remotely
and must be field set. Refer to Literature 5-578 latest
revision.
(2) Low Gas Pressure Switch – (OPT)
The low gas pressure switch is factory installed in the duct
furnace above the gas train. The switch monitors the gas
pressure upstream of all the gas controls and shuts off the
electric supply to the ignition controller and combination gas
valve if low gas pressure is experienced. This will shut off all
gas flow to the burner. The switch has an automatic reset so
that if the gas pressure is interrupted and then is returned, the
switch will automatically allow the unit to operate when gas
conditions are returned to the allowable range of the pressure
switch. The pressure switch range is 2" to 14" W.C. and should
be set to insure that the minimum inlet gas pressure is available
(6" W.C. for natural gas, 11" W.C. for propane gas).
Figure 19.4 - Low or High Gas Pressure Switch
Reset Switch
(High Pressure Switch only)
Pressure adjustment screw
Top cover removed
(3) High Gas Pressure Switch – (OPT)
The high gas pressure switch is factory installed in the duct
furnace above the gas train. The switch monitors the gas
pressure downstream of all the gas controls and shuts off
the electric supply to the ignition controller and combination
gas valve if high gas pressure is experienced right before the
manifold. This will shut off all gas flow to the burner. The switch
has amanual reset so that if the gas pressure is too high, a
service person must check the unit to make sure that none of
the gas controls have been damaged by the high gas pressure
and then reset the switch to allow the unit to operate when gas
conditions are returned to the allowable range of the pressure
switch. The pressure switch range is 2" to 16" W.C. and should
be set to insure that the maximum manifold gas pressure is not
exceeded (3.5" W.C. for natural gas, 10" W.C. for propane gas).
(5) Timed Freeze Protection – (OPT)
The timed freeze protection system is factory installed in the
duct furnace electrical junction box with the sensor (30°-75°F
adjustable) factory installed in the discharge air stream. On
initial start-up, the timed delay in the system allows the unit to
go through the normal ignition sequence. The timed delay is an
automatic reset switch and adjustable for 1-10 minutes. In the
event that the unit fails to fire after this period, the discharge air
sensor will sense the cold air and will shut down the entire unit.
Figure 19.5 - Timed Freeze Protection Module
Figure 19.3 - Electronic Modulating Discharge Air
Thermostat
5-565.119
OPTIONS
%
Belimo
60
80
100
40
20
0
instruction lable
Handle opening
Stand-off Panel
Blower Electrical Section
(See warning)
Supply Power Terminals
(with door open)
To override turn shaft 90 C.W.
(6) Ignition Controller – (OPT)
The ignition controller is factory installed in the duct furnace
electrical junction box with the spark ignitor and sensor located
on the burner.
For both natural and propane gas units, the ignition controller
is 100% shut-off with continuous retry. On a call for heat, the
system will attempt to light the pilot for 70 seconds. If the pilot
is not sensed for any reason, the ignition control will wait for
approx imately six minutes with the combination gas control
closed and no spark. After six minutes, the cycle will begin
again. After three cycles, some ignition controllers lockout for
approximately one hour before the cycle begins again. This will
continue indefinitely until the pilot flame is sensed or power is
interrupted to the system.
(8) Control Relay – (OPT)
The control relay is factory installed in the duct furnace
electrical junction box. The relay has a 24V coil with doublepole, double throw (DPDT) contacts. Refer to the unit wiring
diagram for the function of the switching operation of the relay.
The two normally open and two normally closed contacts are
rated for a maximum of 30 amps @ 115V/1Ph.
(9) Time Delay Relay – (STD)
The time delay relay is factory installed in the duct furnace
electrical junction box. The time delay relay allows the gas
controls to operate for approximately 30 seconds before the
blower starts. This allows the heat exchanger a warm up period
so that the initial delivered air coming out of the ductwork is
not cool. The time delay relay also keeps the motor running for
approximately 30 seconds after the call for heat has been satisfied to remove the residual heat from the heat exchanger. For
single phase units below 2 Hp, the time delay relay controls the
motor directly. For single phase units 2 Hp and greater and all
three phase units, the time delay relay controls the motor starter.
(10) Furnace Low Voltage Terminal Strip – (STD)
The furnace low voltage terminal strip is located in the duct
furnace electrical junction box. The terminal strip is labeled
to match the electrical wiring diagram provided with the unit.
Low voltage labeling ranges from terminal numbers 1 to 79. All
field wiring connections should be made to the top side of the
terminals to prevent miswiring by modifying the factory wiring
which is made to the bottom of the terminal strip.
(12) Furnace Supply Power Terminal Strip – (STD)
The furnace supply power terminal strip is located in the duct
furnace electrical junction box. The terminal strip is labeled
to match the electrical wiring diagram provided with the unit.
Supply power labeling ranges from terminal numbers 80 to 99.
All field wiring connections should be made to the bottom side
of the terminals to prevent miswiring by modifying the factory
wiring which is made to the top of the terminal strip.
(13) Control Step Down Transformer – (STD)
The control step down transformer is located in the duct furnace
electrical junction box. The transformer is used to step down
the supply power (115V, 208V, 230V, 460V, 575V) to 24V. This
transformer is used to control the gas controls, damper actuator,
motor starter, etc. Refer to the unit model number to determine
the volt- amp (VA) capacity of the duct furnace. The 15th digit
indicates the VA (See Model Nomenclature).
(14) Control Relay – (OPT)
The control relay is factory installed in the electrical section.
See description of Option 8 for additional details.
(15) Blower Low Voltage Terminal Strip – (STD)
The blower low voltage terminal strip is located in the
electrical section. The terminal strip is labeled to match the
electrical wiring diagram provided with the unit. Low voltage
labeling ranges from terminal numbers 1 to 79. All field wiring
connections should be made to the right side of the terminals to
prevent miswiring by modifying the factory wiring which is made
to the left side of the terminal strip.
(16) Dead Front Disconnect Switch – (OPT)
WARNING
When the dead front disconnect switch is in the “OFF”
position, supply power remains energized at the blower supply
power terminal strip and the top of the dead front disconnect
switch. When providing service on or near these terminals,
building supply power to the unit should be de-energized.
Figure 20.1 - Dead Front Disconnect Switch Assembly
Supply Power Terminals
(See Warning)
Handle opening
instruction table
Pinch handle latch
(A) & handle (B)
together when
opening and
closing door
A
B
To override turn shaft 90° C.W.
(with door open)
Blower Electrical Section
Stand-off Panel
The dead front disconnect switch is factory installed in the
electrical section. The disconnect switch is designed so that
it must be turned “OFF” before entry to the electrical control
cabinet can be obtained (See Figure 20.1). When in the “OFF”
position, power is disconnected to all unit wiring electrically
following the switch (See Warning). To open, see Figure 20.1.
For servicing the unit, the disconnect switch can be manually
overridden by using a wrench and turning the disconnect switch
shaft 90° clockwise (See Figure 20.1). Fusible and circuit breaker
switches available. For fusible switches, Class “J” time delay
fuses must be field provided matching the fuse size listed on the
Model Identification plate.
(17) Step Down Transformer Fuses – (OPT)
The transformer fuses are factory installed in the electrical section.
The fuses are included to protect the transformer. Fuses included.
(18) Step Down Transformer – (OPT)
The step down transformer is factory installed in the eletrical
section. The transformer is required for power exhausted units
with a supply voltage of 460V/3Ph and 575V/3Ph.
(19) Factory Installed Minimum Positioner – (OPT)
The factory installed minimum positioner is installed in the
electrical section and is used with a modulating damper actuator
to set the minimum percentage of outside air. The minimum
positioner dial is manually set between 0 to 100% resulting in a
2 to 10 VDC signal being sent to the damper actuator. When
used in conjunction with the Proportional Temp Controller, the
positioner sets the minimum outside air percentage and the
Proportional Temp Controller then modulates between the
minimum position and 100% outside air.
Figure 20.2 - Minimum Positioner
5-565.120
OPTIONS
set to angle of rotation
Adjustable end switch
50% rotation limit
Actuator clamp at
Lock down with screw as shown.
R
L
(20) Extended Grease Line Zerk Fittings – (OPT)
The extended grease line zerk fittings are factory installed on the
exterior corner post between the electrical and blower sections.
The zerk fittings allow pillow block bearings to be lubricated with
a grease gun. Refer to Lubrication Recommendations for
lubricant recommendations.
(21) Extended Grease Lines – (OPT)
The extended grease lines are factory installed in the blower
section from the Extended Grease Line Zerk Fittings to the Pillow
Block Bearings. The grease lines allow the pillow block bearings
to be lubricated without requiring the service personnel to
remove both blower doors to access the bearings.
(22) Return Air Fire Stat – (OPT)
The return air fire stat is factory installed in the electrical section
with the sensor in the return air stream. In case of elevated
temperatures in the return air stream, the manual reset switch
shuts down the entire unit. If the limit temperature is exceeded,
a service person must inspect the unit for the cause of the high
discharge temperature, take corrective action, and then reset the
switch.
(23) Blower Housing – (STD)
The blower housing is factory installed in the blower section.
The blower housing contains a double width, double inlet (DWDI)
blower wheel so both sides of the blower must be free from
obstructions for proper operation. For Right Hand units
(Digit 9 = R), during operation the blower wheel should rotate
in the clockwise direction when viewed from the service side of
the unit. For Left Hand units (Digit 9 = L), during operation the
blower wheel should rotate in the counterclockwise direction
when viewed from the service side of the unit. If necessary,
interchange supply power wiring to reverse blower rotation.
(24) Pillow Block Bearings – (OPT)
The blower bearings are factory installed in the blower section.
The blower can be provided with either spider or pillow block
bearings. Spider bearings are permanently lubricated and do not
require lubrication. Pillow block bearings are shipped nongreased from the factory and require lubrication before start-up.
For lubrication recommendations, see Lubrication
Recommendations.
(25) Blower Motor – (STD)
The blower motor is factory installed in the blower section. The
blower motor can be provided in a variety of supply voltages,
frame types, and motor horsepowers. Refer to the model
nomenclature to determine the type of motor provided. The
blower motor is supplied with an adjustable sheave that can be
used to increase/decrease the blower RPM. For instructions on
changing the blower RPM, refer to Blower Adjustments.
provided, is controlled by the damper linkage between the two
dampers. All damper actuators are low voltage (24V). For Right
Hand units (Digit 9 = R), during operation the actuator should
rotate in the counterclockwise direction when viewed from the
service side of the unit. For Left Hand units (Digit 9 = L), during
operation the actuator should rotate in the clockwise direction
when viewed from the service side of the unit. Three different
types of dampers actuators can be provided: Two-position,
Modulating, and Floating.
Two-position Damper Actuator: A two-position damper actuator
is provided with Air Control options DA, EA, EQ, and FA (Digits
20 & 21). The two-position damper actuator provides open/
closed operation of the fresh air damper. When the damper is
energized, the fresh air damper is opened to 100% outside air in
75 seconds (For units with a two-position damper limiter, the
outside air percentage would be the set by the damper limiter.
See Two-Position Damper Limiter below). All two-position
damper actuators are spring return, so when the damper is
de-energized, the fresh air damper will spring closed. All twoposition dampers include auxiliary switches (one normally open
and one normally closed) that reverse when the damper actuator
is at 85° rotation (adjustable).
Two-Position Damper Limiter: The two-position damper limiter is
factory set to prevent the outside air damper from opening 100%.
The outside air percentage and the actuator end switch is set
based on the unit order.
Field adjustment of the two-position damper limiter is
accom plished by the following:
1. Determine the amount of damper rotation required
(Percentage of outside air).
2. Locate the angle of rotation limiter on the actuator so that its
edge lines up with the degree graduation on the actuator face
which corresponds with the required rotation. (See Figure 21.1
which is shown at 50% rotation limit.)
3. Find the appropriate cross-hair location through the slot of the
limiter. This is the screw mounting location.
4. Pierce through the label material to allow easy fastening of
the retaining screw.
5. Position the limiter back to the desired position, making sure
the locating “teeth” on the limiter are engaged into the locating
holes on the actuator.
6. Fasten the limiter to the actuator using the self tapping screw
provided.
7. Test the damper rotation either manually with the manual
crank or apply power and if required, a control signal. Readjust if necessary.
Figure 21.1 - Two-position damper actuator and limiter
(26) Filters – (OPT)
When filters are supplied with the unit, a rack and the filters are
factory installed in the blower section. The unit can be supplied
with 1" or 2" permanent filters, 2" FARR® Aeropleat MERV 7 or
2" FARR® 30/30 MERV 8 filters. For filter replacement, refer to
Maintenance.
(27) Fresh Air Damper – (OPT)
When a fresh air damper is supplied with the unit, the damper is
factory installed in the blower section. The fresh air damper is
used as an outside air shut-off damper, so ultra low leak, Class II
leakage resistance (less than 10 CFM/ft2 at 1" W.C.) dampers
with self-compensating stainless steel side seals and santoprene
and galvanized steel blade seals are used.
(30) Direct Drive Damper Actuator – (OPT)
The direct drive damper actuator is factory installed in the blower
section on the side of the fresh air damper. The actuator controls
the position of the fresh air damper. The return air damper, if
5-565.121
OPTIONS
Modulating Damper Actuator: A modulating damper actuator is
provided with Air Control options GA, GB, GC, GD, GE, GF, GG,
GH, GJ, GK, GM, and GN (Digits 20 & 21). The modulating
damper actuator provides incremental operation of the fresh air
damper (The return air damper is controlled by the fresh air
damper position). Full 90° rotation of the modulating actuator
requires 150 seconds. All modulating damper actuators operate
using a 0-10 Vdc input signal (Air Control GB utilizes a resistor to
convert from a 4-20 mA to 0-10 Vdc) from a damper controller.
All modulating damper actuators are spring return, so when the
damper is de-energized, the fresh air damper will spring closed.
Floating Damper Actuator: A floating damper actuator is provided
with Air Control option HP (Digits 20 & 21). The floating damper
actuator provides forward and reversing damper operation in
response to contact closures from the space pressure controller.
When the space pressure is above the desired set point, a high
pressure contact on the space pressure controller energizes the
damper to drive the fresh air damper closed. When the space
pressure is below the desired set point, a low pressure contact
on the space pressure controller energizes the damper to drive
the fresh air damper open. When the space pressure is between
the high and low set points, the damper “floats” at the fresh air
percentage that satisfied the space pressure controller. Full 90°
rotation of the floating actuator requires 150 seconds. For
additional information on the space pressure controller, refer to
Literature 5-585.
The damper actuator is designed to “float” and therefore it is not
spring return. When the unit is de-energized under normal
operation, the fresh air damper is closed by a relay contact
closure which electrically drives the damper closed. If the supply
power to the unit is interrupted before the damper actuator can
drive closed, the fresh air damper will remain open. The damper
can be manually closed through the use of the manual override
switch on the floating damper actuator.
(31) Enthalpy Controller – (OPT)
An enthalpy controller is provided with Air Control option GJ
(Digits 20 & 21) and factory installed in the blower section.
The purpose of the enthalpy controller is to use outside air for
cooling, whenever possible, to reduce compressor operation of
the mechanical cooling system. The economizer functions as a
true first stage of cooling and provides maximum fuel economy
during the cooling cycle.
The enthalpy controller is used in conjunction with the Enthalpy
Sensor (not shown and field installed) and a mixed air temperature sensor (not shown). The mixed air temperature sensor is
factory installed in the blower section to sense the combined
temperature of the fresh and return air streams. The sensor is
non-adjustable and when in the free cooling mode, modulates
the dampers to maintain between 50°F and 56°F at the sensor.
The enthalpy controller contains a minimum position adjustment
and an enthalpy changeover set point that must be field set.
Figure 22.1 - Enthalpy Controller
Minimum Position Adjustment:
The minimum position adjustment keeps the outdoor air damper
from closing completely during system operation to provide
ventilation in both the heating and cooling modes.
To set the minimum position adjustment:
1. Disconnect mixed air sensor from terminals T and T1 on the
enthalpy controller.
2. Make sure the factory installed jumper is in place across
terminals P and P1.
3. Connect 24 Vac across terminals TR and TR1.
4. Adjust the minimum position adjustor with a screwdriver for
the desired minimum position.
Figure 22.2 - Enthalpy Changeover Set Point Control
Points
An enthalpy sensor is provided with Air Control option GJ and
field installed in the inlet air stream. The enthalpy sensor senses
and combines the temperature and humidity of the outdoor air to
provide the 4-20 mA input signal to the Enthalpy Controller.
HEATING and VENTILATING MODE
When the space thermostat calls for heat or it is in the fan
ON position without a call for cooling (ventilation mode), the
economizer is automatically locked out. It holds the outdoor air
damper at the minimum position setting.
COOLING MODE
When the space thermostat calls for cooling, the system
operates as follows:
Outdoor Air Enthalpy is Below Changeover Set Point
1. The outdoor air damper is proportioned open (and the return
air damper is proportioned closed) to maintain between 50°F
and 56°F at the mixed temperature air sensor.
2. During economizer operation, mechanical cooling is operated
by the second stage of the cooling on the space thermostat.
Outdoor Air Enthalpy is Above Changeover Set Point
1. The outdoor air damper is closed to its minimum position.
2. A call for cooling from the space thermostat brings on
mechanical cooling.
5-565.122
OPTIONS
NONC
COM
Operating Point
Rest position
"Cheat Interlock" Point
C
NO
Outdoor Enthalpy Changeover Set Point
The outdoor enthalpy changeover set point returns the outdoor
air damper to the minimum position when the enthalpy rises
above its set point. Enthalpy set point scale markings, located
on the enthalpy controller, are A, B, C, and D. See Figure 24.2
for the corresponding control point. The factory installed 620ohm jumper placed across terminals SR and + is required for
proper operation and should not be removed. Refer to suppliers
literature supplied with the unit for additional information.
(32) Damper to Damper Linkage – (OPT)
Units with fresh and return air dampers include a damper
actuator that controls the fresh air damper. The return air
damper position is controlled by the fresh air damper through
the connecting rod. For adjustment, refer to Damper Linkage
Adjustment.
(33) Return Air Damper – (OPT)
When a return air damper is supplied with the unit, the damper
is factory installed in the blower section. The return air damper is
used as an air balancing damper so low leak, Class III leakage
resistance (less than 40 CFM/ft2 at 1" W.C.) dampers with selfcompensating stainless steel side seals and santoprene blade
seals are used.
(34) Proportional Temperature Controller Sensor – (OPT)
A proportional temperature controller sensor is provided with Air
Control options GF, GG, GH, GK, GM, or GN (Digits 20 & 21)
and factory installed in the blower section. The sensor provides
the mixed air temperature signal to the A350P Proportional
Temperature Controller which is mounted in the electrical
section.
(35) Motor and Blower Vibration Isolation – (OPT)
The motor vibration isolation is factory installed in the blower
section below the blower support bracket. The four (4) 13/32"
neoprene vibration mount grommet provides isolation of the
blower housing and motor from the blower support channels.
The blower vibration isolation is factory installed in the
blower section between blower discharge and the blower
duct connection. The blower duct connection is not rigidly
mechanically fastened and the 1/4'' thick gasketing around the
duct transition provides vibration isolation.
(36) Blower Support – (STD)
The blower supports are factory installed in the blower section.
The blower supports are used to rigidly support the weight of the
blower and motor during operation and shipping.
(37) Convenience Outlet – (OPT)
WARNING
Do not perform service on the convenience outlet without
disconnecting its power supply. The convenience outlet
power supply is separate from main power supply to the
unit. When the main disconnect switch is de-energized,
the convenience outlet power supply remains energized.
section door on the access side of the unit. When the blower
section door is removed, the momentary switch is released and
interrupts power to the low voltage circuit. For single phase
units 1-1/2 Hp and less, the door switch de-energizes a relay
that controls blower motor operation. For three phase units
and single phase units 2 Hp and greater, the door switch deenergizes the motor starter that controls blower motor operation.
For servicing, the switch is equipped with an override position
that can be manually pulled out to override the switch. See
Figure 23.1
Figure 23.1 - Blower Door Switch with Manual Override
(39) Dirty Filter Switch – (OPT)
The dirty filter pressure switch is factory installed in the electrical
section. The dirty filter pressure switch monitors the pressure
differential between the two sides of the filters. When the filters
become dirty, the differential pressure increases and trips
the pressure switch which energizes a light on the remote
monitoring panel. The pressure differential switch must be field
set because setting the switch requires the blower to be in
operation and the ductwork to be installed.
Setting the Dirty Filter Switch
The range of the dirty filter pressure switch is adjustable
between 0.17" to 5.0" W.C.
1. Ensure that the unit filters are clean. Clean or replace if
necessary.
2. Connect the leads of a continuity tester to the NO and C
terminals of the dirty filter pressure switch. See Figure 23.2
3. Set the thermostat so that there is a call for heat. This should
fire the burner and the blower should start.
4. Turn the set screw of the pressure switch clockwise until
it stops. This will set the pressure at 5.0" W.C. and the
continuity tester should be sensing an open circuit.
5. Begin turning the screw counterclockwise until the continuity
tester senses a closed circuit. This determines the base
pressure of the system.
6. Turn the screw clockwise until the continuity tester senses an
open circuit and then one additional full turn (This is approximately 0.25" W.C.) This will allow for the increase in static
pressure due to dirty filters.
Figure 23.2 - Dirty Filter Pressure Switch and Air Flow
Proving Switch
Positive pressure connector
Negative pressure
connector
The convenience outlet is factory installed in the blower section
for providing power for 115V service equipment (trouble light,
power tools, etc.). The 115V ground fault circuit interrupter
(GFCI) is rated for 15 amps and includes test and reset
switches. A separate field supplied 115V/1Ph power supply must
be routed through the electrical section wall into the back of the
convenience outlet junction box.
(38) Blower Door Switch – (OPT)
The blower door switch is factory installed inside the blower
Pressure adjustment set screw
5-565.123
OPTIONS
DIAL
SET POINT
4 8 12 16 25
2 4 6 8 10
VOLT S
MILLIAMPS
CONTROLS
JOHNSON
A350 P
ON
RESET
WINDOW
INDICATOR
TRIP
DIAL
SET POINT
CURRENT
H
A
R
E
S
E
T
NC
NO
96959798
T36T2
4T12
A2
14NO6T34
T2T1
2
NO13L35L2
3
A2
L1
1
A1
CONTACTOR
MODULE
OVERLOAD
MODULE
(40) Motor Starter – (OPT)
The motor starter is factory installed in the electrical section.
A motor starter is required for all three phase motors and single
phase motors 2 Hp and greater. The motor starter current set
point dial is factory set to the motor full load amp draw listed on
the motor nameplate.
(40) Variable Frequency Drive – (OPT)
The VFD controller adjusts the motor rpm to vary the unit air
flow. The minimum air flow may be varied between 30 and 100%
of the full speed air flow depending on the controls selection of
the unit. The control changeover options are two speed, floating
building pressure sensing, and building management control.
The overload module of the motor starter is designed to trip to
protect the motor from exceeding the nameplate amps. If the
motor exceeds the amp draw on the current set point dial, the trip
condition is indicated by a red color in the trip indicator window.
The motor starter can be placed in the automatic or manual
reset positions. Automatic reset is accomplished by depressing
the “RESET” button and turning the button 1/4 turn. When in the
automatic reset position, if the overload module trips, the module
will reset itself once the overload relay has cooled. In the manual
reset position, if the overload module trips, the “RESET” button
must be depressed before the blower can operate.
The contractor module includes one (1) normally open auxiliary
contact. The contact rating is 10 amps.
If the factory installed motor starter option was not ordered with a
unit that has a three phase motor or single phase motor 2 Hp or
greater, a motor starter must be field supplied and installed.
Figure 24.1 - Motor Starter
Figure 24.2 - Proportional Temperature Controller
(44) Blower Supply Power Terminal Strip – (STD)
The blower supply power terminal strip is located in the electrical
section. The terminal strip is labeled to match the electrical wiring
diagram provided with the unit. Supply power labeling ranges
from terminal numbers 80 to 99. All field wiring connections
should be made to the bottom side of the terminals to prevent
miswiring by modifying the factory wiring which is made to the
top of the terminal strip.
(45) Service Switches – (OPT)
The service switches are factory installed in the electrical
section. The service switches allow for service personnel to
independently test operation of the damper, blower, and furnace
without using jumper wires. The switches override the remote
monitoring panel and/or thermostats to energize each component directly. All switches need to be reset to the “OFF” position
after testing otherwise the components will remain energized.
(42) Proportional Temperature Controller – (OPT)
A proportional temperature controller is provided with Air Control
options GF, GG, GH, GK, GM, or GN (Digits 20 & 21) and factory
installed in the electrical section. The controller compares the
mixed air temperature set point and the mixed air temperature
from the Proportional Temperature Controller Sensor. The
controller sends a 2-10 Vdc signal to the modulating damper
actuator in order to maintain the set point. The controller includes
a set point dial that must be field set to the desired mixed air
temperature (typically 55°F).
(43) Warm-Up Stat – (OPT)
A warm-up stat is provided with Air Control options GK, GM, or
GN (Digits 20 & 21) and factory installed in the electrical section
with the sensor in the return air stream. The warm-up thermostat
monitors the return air temperature to the unit and prevents
the fresh air dampers from opening until the temperature of the
return air has reached the desired set point (typically 65°F or 5°F
below the room temperature).
Figure 24.3 - Service Switches
(46) Electronic Modulation Amplifier – (OPT)
An electronic modulation amplifier is provided factory installed
in the duct furnace electrical junction box when the unit is
equip ped with Electronic Modulating Gas Controls (Digit 12 =
4 or 5). The amplifier processes the thermostat temperature
and set point signals to modulate the firing rate between 40%
to 100% full fire. For additional information, refer to Control
Operating Sequence.
5-565.124
OPTIONS
(47) Electronic Modulating Gas Valve – (OPT)
An electronic modulating gas valve is provided factory installed
in the duct furnace gas train when the unit is equipped with
Electronic Modulating Gas Controls (Digit 12 = 4, 5, 6, 7, or 8).
The gas valve modulates the firing rate between 40% to 100%
full fire based on the input signal from the Electronic Modulation
Amplifier or Signal Conditioner. For additional information, refer
to Control Operating Sequence.
(48) Air Flow Proving Switch – (OPT)
The air flow proving switch is factory installed in the duct furnace
electrical junction box. The air flow proving switch monitors
the pressure differential between the duct furnace and the
atmosphere. The purpose of the air flow proving switch is to cut
power to the gas controls if a positive pressure is not measured
by the switch. This could be caused by a lack of air movement
through the heat exchanger.
NOTE: The air flow proving switch will prevent any heat
exchanger warm-up because the gas controls can not
be energized until air flow is proven.
Setting the Air Flow Proving Switch
The range of the air flow proving switch is adjustable between 0.17"
to 5.0" W.C.
1. Set the thermostat so that there is a call for heat. This should start
the blower and then the burner ignition sequence.
2. Turn the set screw of the pressure switch clockwise until it stops.
This will set the pressure at 5.0" W.C.
3. Turn the screw counter-clockwise until the gas controls light and
then one additional full turn (This is approximately 0.25'' W.C.).
This will allow for dirty filters or any other slight static pressure
increases in the system.
(55) Differential Pressure Switch
A differential pressure switch is supplied on all power vented
duct furnaces and is designed to prevent operation of the main
burner in the event there is improper venting through the vent
system. This may occur due to a restricted vent, inadequate
vent draw, uninsulated vent pipe in cold ambient or long vent
runs, excessive vent diameter, restricitve vent terminal, negative
pressure within space, etc. See Troubleshooting section for
more information.
(Not Shown) Circuit Analyzer – (OPT)
The circuit analyzer is factory installed on the door of the
electrical section. The circuit analyzer is used to quickly assist
service personnel in troubleshooting by monitoring the unit firing
sequence and vital operating steps. Lights will come on as a
point of electrical operation is passed and proven. If any light is
not lit, that is the point where failure occurred.
Figure 25.1 - Circuit Analyzer
Circuit analyzer tagging will vary based on the unit ordered.
Circuit analyzer shown is for reference only.
(49) High Limit Switch
Automatic – (STD)
The automatic reset high limit switch is factory installed in the
duct furnace electrical junction box. If the limit temperature is
exceeded, the gas controls are de-energized until the switch
is cooled.
Manual – (OPT)
The manual reset high limit switch is factory installed in place
of the standard automatic reset high limit switch located in the
duct furnace electrical junction box. In case of a failure of the
blower motor, blockage of the inlet air, etc., the manual reset
switch prevents the unit from cycling on the high limit. If the limit
temperature is exceeded, a service person must inspect the unit
for the cause of the high discharge temperature, take corrective
action, and then reset the switch.
(50) Supply Air Fire Stat – (OPT)
The supply air fire stat is factory installed in the duct furnace
electrical junction box with the sensor in the discharge air
stream. In case of elevated temperatures in the supply air
stream, the manual reset switch shuts down the entire unit. If
the limit temperature is exceeded, a service person must inspect
the unit for the cause of the high discharge temperature, take
corrective action, and then reset the switch.
(51) Main Gas Valve – (STD)
The main gas valve is factory installed in the duct furnace gas
train. The main gas valve provides the pilot, regulator, main gas,
and manual shutoff functions. For additional information, see the
supplier literature included with the unit.
(52) Burner Box – (STD)
The burner box is located in the duct furnace section and contains
the burner and pilot assembly. The burner box includes an access
panel for removal of the burner for inspection and servicing.
5-565.125
GENERAL PERFORMANCE DATA
Table 26.1 - General Performance Data - Models With Blower
Blower Style (Digit 16 Letter) G or H I, J, or K L I, J, or K L I, J, or K L
Max. Temp. Rise (°F) 120 120 120 120 120 120 120
Min. Temp. Rise (°F) 87 46 41 60 60 68 63
Max. CFM 6850 13000 14500 13000 13000 13000 14000
Min. CFM ➁4938 4938 4938 6481 6481 7407 7407
➀ Ratings are shown for elevations up to 2000 ft. For higher elevations the input rating should be reduced at the rate of 4% for each 1000 feet above sea level.
For Canada, in elevations between 2000 and 4500 feet, the unit must be derated to 90% of the rating listed above.
➁ For Variable Air Movement Applications, see page 17.
➀ Ratings are shown for elevations up to 2000 ft. For higher elevations the input rating should be reduced at the rate of 4% for each 1000 feet above sea level. For
Canada, in elevations between 2000 and 4500 feet, the unit must be derated to 90% of the rating listed above.
➁ For Variable Air Movement Applications, see page 17.
Air Temperature Limits
The maximum allowable discharge air temperature is 150°F.
The maximum allowable air temperature rise per furnace for
Low Air Temperature Rise Units is 60°F. All system units are
designed for a maximum allowable total static pressure of
3.0" W.C.
5-565.127
UNIT SELECTION
Selection Procedure
In order to properly select an indirect-fired heating, ventilating,
cooling or make-up air unit, it is necessary to have the following
basic information.
1. Required air handling capacity (CFM).
The air capacity of the unit is usually determined by the
ventilation air requirements, exhaust load of the building,
infiltration losses, or the air turns/changes of the space.
2. Outdoor and indoor design temperature.
The outdoor design temperature is determined by using
the ASHRAE Guide design temperatures for the city where
the equipment is to be installed. For heating and ventilating
units, the desired room temperature would be used as the
indoor design temperature. In the case of 100% make-up
air units, the discharge air temperature should be at least
equal to the temperature of the air being exhausted.
3. Required heating output capacity (Btu/Hr).
The heating output capacity of the unit is determined by
using the formula:
BTU/HR = CFM x Temp. Rise (°F) x 1.08
4. External static pressure to unit.
The external static pressure (E.S.P.) is determined using
the ASHRAE Guide for duct losses, or may be provided by
the design engineer.
5. Unit configuration with options and accessories
(Filters or dampers).
The unit configuration is determined by the location
where the unit is to be installed. The critical options and
accessories are those that add internal static pressure
(I.S.P.) to the unit. Once these items are determined, the
pressure drop curves would be used to calculate the total
pressure drop (T.S.P.)
Total Static Pressure = Internal + External Static Pressure
6. Heat exchanger material.
The heat exchanger type is determined by the application.
The standard heat exchanger material is aluminized
steel. A 409 stainless steel heat exchanger and burner is
recommended when the unit is installed downstream of a
cooling coil or evaporative cooler, and when the combined
entering/return air to the unit is below 40°F.
7. Type of fuel.
Either natural or propane gas determined by the design
engineer.
8. Gas control staging method.
Either single stage, two stage, mechanical modulation, or
electronic modulation determined by the design engineer.
9. Main power supply voltage to unit.
10. Altitude at which unit is to be installed.
With this information a basic unit can be selected as shown in
the following example.
Selection Example Conditions
Select an indirect-fired, 100% make-up air unit to meet the
following conditions:
3. Heating output capacity =
5000 cfm x (70°F -10°F) x 1.08 = 324,000 Btu/Hr
4. External Static Pressure = 0.65
5. The unit with the controls on the Right Hand Side is to be
provided with the following:
2" Permanent Filters, and Fresh Air Damper.
6. Heat exchanger and burner = 409 Stainless Steel.
7. Gas Type = Natural
8. Gas Controls = Electronic Modulating with Duct Sensing.
9. Supply Voltage: 460V/60Hz/3Ph
10. Altitude: 1000 feet
With the information listed above, the basic model, using the
Model Nomenclature shown on page 55, can be selected as
shown in the following example:
1. Determine the Model Configuration and Venting:
The Model Configuration is determined by the required
sections of the unit (Blower only) and the venting style
(power vented) that are obtained from item #5. Using the
Model Nomenclature on page 55, the Model Configuration
and Venting = DBP.
2. Determine the Furnace Input Rating (MBH):
Using the Heating output capacity, the Furnace Input
Rating is determined from Table 26.1. The closest model
to 324,000 Btu/Hr output has an Btu/Hr Input rating of
400,000 Btu/Hr so the Furnace Input Rating = 400.
3. Determine the Heat Exchanger/Burner/Drip Pan
Material:
From item #2 in Selection Example Conditions, the Heat
Exchanger and Burner required are 409 Stainless Steel.
Because the Drip Pan material is not specified, the standard
Aluminized Steel drip pan will be used. Thus, the Heat
Exchanger/Burner/Drip Pan Material = S.
4. Determine the Development Sequence:
From item #8 in Selection Example Conditions, the
modulating gas controls result in the Development
Sequence = M.
5. Determine the Access Side:
From item #5 in Selection Example Conditions, the Right
Hand Gas controls result in the Access Side = R.
6. Determine the Air Temperature Rise:
From item #2 in Selection Example Conditions, the Air
Temperature Rise is 60°F (70°F - 10°F). However, using the
output capacity of the DBP400 @ 5000 cfm, the resulting
temperature rise is 59.3°F (320,000/(5000 x 1.08)). Since
the rise is less than 60°F, the air baffle must remain in place.
7. Determine the Gas Type:
From item #7 in Selection Example Conditions, the Natural
Gas results in the Gas Type = N.
8. Determine the Gas Valve:
From item #8 in Selection Example Conditions, the
Electronic Modulating with Duct Sensing results in the Gas
Valve = 4.
9. Determine the Additional Safety Switches:
Since no additional safety switches were specified, the
Additional Safety Switches = 0.
5-565.128
UNIT SELECTION
10. Determine the Supply Voltage:
From item #9 listed above, the 460V/60Hz/3Ph results in the
Supply Voltage = F.
11. Determine the Transformer:
For DBP/DCP models, a 75VA Transformer is required.
Thus, the Transformer = 2.
12. Determine the Blower Size and Bearing Type:
Using Table 26.1, the Model Size 400 has three available
blowers for which the performance tables are shown on
pages 30-33. Since all of the blower performance curves
can provide the required 5000 cfm, the total static pressure
must be determined.
A) The Pressure Drop of an option or accessory is
determined by entering the right of the table at the
desired cfm and reading up the table until the cfm
intersects the desired item. For this example, in table
30.1 the 2'' Permanent Filter line is used. At the point of
intersection, read across the table to the left and read the
pressure drop, in inches of water column for the filters.
For this example, the pressure drop is 0.06'' W.C.
As a result:
For the Model Size 400 with Digit 16 = E,F,G, or H:
The Total Static Pressure for the system is determined by
Internal Static + External Static = Total Static Pressure
For this example 0.06'' + 0.65'' = 0.71'' W.C. T.S.P.
13. Determine the Motor Horsepower:
The motor horsepower determined in step 12 was a 3 Hp.
Since the supply voltage is 460V/60Hz/3Ph, a motor starter
will need to be provided either with the unit or by others. For
purposes of this selection, a motor starter by others will be
used so the Motor Horsepower = G.
14. Determine the Motor Type:
The motor type was not specified so for purposes of this
selection the standard open drip proof motor will be used so
the Motor Type = 1.
15. Determine the Sheave Arrangement:
To establish the Sheave Arrangement, the motor frame size
must be determined. The Motor Data tables on pages 38 to
42 contain the motor frame size.
A) Using the Supply Voltage (460V/60Hz/3Ph), enter the
correct Motor Data table (Table 41.1). Using Model
Nomenclature Digits 17 and 18 (G1) determined in steps
13 and 14, find the motor frame size (182T).
B) Using the Motor Frame Size enter the Sheave Selection
table for the selected blower determined by step 13
(Table 35.2). Using the rpm calculated in step 12
(870 rpm), select the sheave range that contains the
required rpm. Find the intersection with the Motor
Frame Size to determine the Sheave Selection. For this
example with a 182T frame with 870 rpm, from Table
35.2, the Sheave Arrangement = I.
From page 30,
for the Model Size 400 with Digit 16 = I, J, or K:
2'' Permanent Filters: 0.04'' W.C.
Internal Static Pressure Drop 0.04'' W.C.
The Total Static Pressure for the system is determined by
Internal Static + External Static = Total Static Pressure
For this example 0.04'' + 0.65'' = 0.69'' W.C. T.S.P.
B) Using the total static pressure (T.S.P.) calculated in step
12a, use blower performance tables for the Model Size
400 (Table 32.1).
Using Table 32.1, enter the table at the required 5000
cfm for E, F blowers, and follow the cfm line up the
right until it intersects with the T.S.P. line of 0.75'' W.C.
which is shown at the top of the table. At the point of
intersection of these two columns, read the required
horsepower and blower rpm. Repeat this process for
1.00”T.S.P. and literate to determine the BHP and rpm for
0.89” W.C. For this example the horsepower is 5 and the
blower rpm is 1280.
Following this procedure for G,H blowers (Using 5000
cfm and 0.89'' W.C. T.S.P), the horsepower is 5 hp and
920 rpm. Following this procedure for I,J,H blowers
(Using 5000 cfm and 0.87'' W.C. T.S.P), the horsepower
is 3hp and 700 rpm. Although I,J,H blowers results in a
3 hp motor, this blower requires the use of the extended
cabinet length. As a result, for purposes of this selection
example G,H will be used.
Since the Bearing Type was not specified, the standard
spider bearings will be used. Thus, using Table 32.1 with
spider bearings, the Blower Size and Bearing Type = G.
16. Determine the Air Control:
The Air Control option is selected based on the required
damper configuration. The available damper selections are
detailed on page 21. For this selection, a 100% fresh air unit
without return air was required so the Air Control = DA.
17. Determine the Evaporative Cooler:
An evaporative cooler is not available, so for purposes of
this selection the Evaporative Cooler = 0.
18. Determine the Cooling Coil:
A cooling coil cabinet was not specified so for purposes of
this selection the Cooling Coil = 0.
Based on the previous steps, the model number for the base
unit is the following:
DBP400SMRLN40F2GG1IDA00
Once the basic model has been determined, the additional
options and accessories outlined on page 18 to 25 can be
added to the unit.
5-565.129
OPTION & ACCESSORY PRESSURE DROP DATA
Table 30.1 - Option & Accessory Pressure Drop Tables (in ''W.C.) ➀
➀ Total static pressure should include external static pressure and accessory / option static pressure from Table 30.1. Unit internal resistance has been
included in the unit performance tables.
➁ Brake Horsepower and RPM values are approximate values only. Please consult the AccuSpec selection software for values at other than listed
➀ Total static pressure should include external static pressure and accessory / option static pressure from Table 30.1. Unit internal resistance has been included in the
unit performance tables.
➁ Brake Horsepower and RPM values are approximate values only. Please consult the AccuSpec selection software for values at other than listed CFM / static
Based on the Sheave Arrangement, Tables 34.1 through 35.5
give the Sheave Assembly numbers used on units that include a
blower. The Sheave Arrangement is Digit 19 and is found on the
unit Model Identification Plate. The Sheave Assembly describes
the motor and blower sheave size and bore as well as the belt
provided.
To determine how many turns open the motor sheave should be
set for:
1. Follow the Selection Procedure found on pages 28 and 29
to determine what blower rpm is required to meet the job
specifications.
Figure 34.1 - Blower Section
EXTENDED
GREASE
LINES
EXTENDED
GREASE LINE
ZERK FITTINGS
1/4" PERIMETER
GASKETED
BLOWER
CONNECTION
2. Locate the unit Model Identification Plate and note Digit 16
and Digit 19 of the model number. Digit 16 is the Blower
Size and Type and Digit 19 is the Sheave Arrangement.
3. Once the Blower Size and Type (Digit 16) is known, enter
the proper Sheave Arrangement table.
4. Use the Sheave Arrangement (Digit 19) to determine the
Sheave Assembly provided.
5. Use Table 36.1 and the Sheave Assembly number to
determine the required turns open to achieve the
desired blower rpm.
6. Set the motor sheave as described in Blower Adjustments.
ADJUSTABLE
MOTOR
SHEAVE
5 HP
TWO-SPEED
MOTOR
FILTER
RACK
CONVENIENCE
OUTLET
BLOWER DOOR
SAFETY SWITCH
BOTTOM
SUPPORTED
BLOWER AND
MOTOR
DIRECT
DRIVE
DAMPER
ACTUATOR
Blower Sheave Assembly Numbers
Table 34.1 - Digit 16 = A or B (9-7 Blower Units)
RPM Range
Motor Frame 656-1001 978-1265 1150-1561 1526-1858 1763-2147
48 A 3H35126B1C 3H35126B356 B 3H35126B2D 3H35126B4F 3H35126B6I 3H35126B9L 3H35126B12
143 or 145 E 3H35126B5G 3H35126B7J 3H35126B10M 3H35126B13
182 or 184 H 3H35126B8 K 3H35126B11 N 3H35126B14
5-565.134
BLOWER SHEAVE ASSEMBLY DATA
Blower Sheave Assembly Numbers (Con’t)
Table 35.1 - Digit 16 = E or F (12-12 Blower Units)
RPM Range
Motor Frame 468-715 644-874 863-1078 1029-1332 1150-1438 1327-1659
48 A 3H35127B1
56 B 3H35127B2 C 3H35127B3 F 3H35127B6 Q 3H35127B17
143 to 145 D 3H35127B4 G 3H35127B7 I 3H35127B9 L 3H35127B12
182 or 184 E 3H35127B5 H 3H35127B8 J 3H35127B10 M 3H35127B13 O 3H35127B15
213 or 215 K 3H35127B11 N 3H35127B14 P 3H35127B16
Table 35.2 - Digit 16 = G or H (15-15 Blower Units)
RPM Range
Motor Frame 410-625 568-771 767-958 934-1136 1136-1380
48 A 3H35128B1
56 B 3H35128B2 D 3H35128B4 G 3H35128B7 O 3H35128B15
143 to 145 C 3H35128B3 E 3H35128B5 H 3H35128B8 J 3H35128B10
182 or 184 F 3H35128B6 I 3H35128B9 K 3H35128B11 M 3H35128B13
213 or 215 L 3H35128B12 N 3H35128B14
Table 35.3 - Digit 16 = I or J (18-18 Blower Units under 15 Hp motor)
RPM Range
Motor Frame 491-649 586-744 682-821 821-1009 995-1161 1101-1285
56 A 3H35129B1 D 3H35129B4
143 or 145 B 3H35129B2 E 3H35129B5 H 3H35129B8
182 to 184 C 3H35129B3 F 3H35129B6 I 3H35129B9 K 3H35129B11 O 3H35129B15
213 or 215 G 3H35129B7 J 3H35129B10 L 3H35129B12 P 3H35129B16 S 3H35129B19
254 M 3H35129B13 Q 3H35129B17 T 3H35129B20
256N 3H35129B14 R 3H35129B18 U 3H35129B21
Table 35.4 - Digit 16 = K (18-18 Blower Units with 15 Hp motor & up)
256 B 3H35130B2 D 3H35130B4 F 3H35130B6
284 G 3H35130B13 I 3H35130B15 K 3H35130B17 M 3H35130B19
286 H 3H35130B14 J 3H35130B16 L 3H35130B18 N 3H35130B20
Table 35.5 - Digit 16 = L (20-18 Blower Units)
RPM Range
Motor Frame 491-649 626-765 765-901 901-1059 995-1161 1101-1285
143 or 145 A 3H36622B1 C 3H36622B3
182 to 184 B 3H36622B2 D 3H36622B4 F 3H36622B6 L 3H36622B12
213 or 215 E 3H36622B5 G 3H36622B7 M 3H36622B13 R 3H36622B18
25 4 H 3H36622B8 N 3H36622B14 S 3H36622B19 W 3H36622B23
256 I 3H36622B9 O 3H36622B15 T 3H36622B20 X 3H36622B24
284 J 3H36622B10 P 3H36622B16 U 3H36622B21 Y 3H36622B25
286 K 3H36622B11 Q 3H36622B17 V 3H36622B22 Z 3H36622B26
Table 37.1 - Blower Sheave Assembly Numbers and Size
Sheave
Assembly
3H35125B12.90.550.75A30
3H35125B22.90.62550.75A31
3H35125B34.40.560.75A34
3H35125B44.40.62560.75A35
3H35125B54.40.87560.75A35
3H35125B63.80.6254.20.75A31
3H35125B73.80.8754.20.75A31
3H35125B85.60.6255.20.75A35
3H35125B95.60.8755.20.75A35
3H35125B105.60.6254.50.75A34
3H35125B115.60.8754.50.75A34
3H35126B12.90.550.75A33
3H35126B22.90.62550.75A34
3H35126B34.40.560.75A37
3H35126B44.40.62560.75A38
3H35126B54.40.87560.75A38
3H35126B63.80.6254.20.75A34
3H35126B73.80.8754.20.75A34
3H35126B83.81.1254.20.75A36
3H35126B95.60.6255.20.75A38
3H35126B105.60.8755.20.75A38
3H35126B115.61.1255.20.75A40
3H35126B125.60.6254.50.75A37
3H35126B135.60.8754.50.75A37
3H35126B145.61.1254.50.75A39
3H35127B12.90.571A42
3H35127B22.90.62571A43
3H35127B33.80.6257.51A46
3H35127B43.80.8757.51A45
3H35127B53.81.1257.51A47
3H35127B650.62581A48
3H35127B750.87581A48
3H35127B851.12581A50
3H35127B94.40.8755.71A43
3H35127B104.41.1255.71A45
3H35127B115.21.3756.71A49
3H35127B1250.87561A45
3H35127B1351.12561A47
3H35127B145.21.3756.21A49
3H35127B1551.1255.21A45
3H35127B165.61.3755.71A48
3H35127B174.40.6255.71A43
3H35128B12.90.581A47
3H35128B22.90.62581A48
3H35128B32.90.87581A48
3H35128B43.80.6258.51A50
3H35128B53.80.8758.51A50
3H35128B63.81.1258.51A52
3H35128B750.62591A53
3H35128B850.87591A52
3H35128B951.12591A54
3H35128B105.60.8758.51A53
3H35128B115.61.1258.51A54
3H35128B125.21.37581A54
3H35128B135.61.12571A52
3H35128B145.21.3756.51A52
3H35128B155.60.6258.51A53
Motor SheaveBlower Sheave
Pitch
Diameter Bore
Pitch
DiameterBore
Browning
Belt No.
Sheave
Assembly
3H35129B14.10.62510.91B71
3H35129B24.10.87510.91B71
3H35129B34.11.12510.91B70
3H35129B44.70.62510.91BX71
3H35129B54.70.87510.91BX71
3H35129B64.71.12510.91BX71
3H35129B75.51.37512.41BX71
3H35129B85.90.87512.41BX77
3H35129B95.91.12512.41BX75
3H35129B105.91.37512.41BX75
3H35129B115.31.1258.91BX68
3H35129B125.51.3759.41BX68
3H35129B135.51.6259.41BX75
3H35129B145.51.6259.41BX75
3H35129B1571.12510.41B73
3H35129B1671.37510.41B72
3H35129B1771.62510.41B78
3H35129B1871.62510.41B78
3H35129B1971.3759.41B70
3H35129B2071.6259.41B77
3H35129B2171.6259.41B77
3H35130B15.51.6259.41.44Qty (2) B74
3H35130B25.51.6259.41.44Qty (2) B74
3H35130B371.62510.41.44Qty (2) B78
3H35130B471.62510.41.44Qty (2) B78
3H35130B571.6259.41.44Qty (2) B77
3H35130B671.6259.41.44Qty (2) B77
3H35130B1371.87512.41.44Qty (2) B82
3H35130B1471.87512.41.44Qty (2) B82
3H35130B1571.87510.41.44Qty (2) B79
3H35130B1671.87510.41.44Qty (2) B79
3H35130B1771.8759.41.44Qty (2) B77
3H35130B1871.8759.41.44Qty (2) B77
3H35130B1971.8758.41.44Qty (2) B75
3H35130B2071.8758.41.44Qty (2) B75
3H36622B14.10.87510.91.44B75
3H36622B24.11.12510.91.44BX73
3H36622B34.10.8758.91.44B72
3H36622B44.11.1258.91.44B70
3H36622B55.51.37512.41.44BX78
3H36622B64.71.1258.91.44B74
3H36622B75.51.37510.41.44BX75
3H36622B861.62511.41.44Qty (2) BX82
3H36622B961.62511.41.44Qty (2) BX82
3H36622B1071.87513.41.44Qty (2) B86
3H36622B1171.87513.41.44Qty (2) B86
3H36622B125.31.1258.41.44B71
3H36622B135.91.3759.41.44BX74
3H36622B1461.6259.41.44Qty (2) BX79
3H36622B1561.6259.41.44Qty (2) BX79
3H36622B1671.87511.41.44Qty (2) B83
3H36622B1771.87511.41.44Qty (2) B83
3H36622B1871.37510.41.44B77
3H36622B1971.62510.41.44Qty (2) B82
3H36622B2071.62510.41.44Qty (2) B82
3H36622B2171.87510.41.44Qty (2) B81
3H36622B2271.87510.41.44Qty (2) B81
3H36622B2371.6259.41.44Qty (2) B80
3H36622B2471.6259.41.44Qty (2) B80
3H36622B2571.8759.41.44Qty (2) B80
3H36622B2671.8759.41.44Qty (2) B80
Motor SheaveBlower Sheave
Pitch
Diameter Bore
Pitch
Diameter Bore
Browning
Belt No.
5-565.137
ELECTRICAL DATA / MOTOR DATA
Total Unit Amp Draw
The total unit amp draw is a combination of the motor, the control step down transformer, and the power exhauster amp draw. The
control step down transformer includes damper actuators, ignition controllers, gas valves, control relays, amplifiers, and motor starters.
Unit Amp Draw (Table 38.1) =
Motor Amp Draw (Tables 38.2 to 42.1) =
➀ Unit controls amp draw is included in master unit amp draw.
➁ Requires a 250 VA transformer.
➂ Requires a 500 VA transformer.
➃ Requires a 750 VA transformer.
➄ Requires a 1000 VA transformer.
➅ For Digits F (460V) and G (575V), amp draw shown is on
primary (line) side of required step-down transformer.
Table 38.3 - Motor Data for Digit 14 = B - 208V/60Hz/1Ph
Digits Motor Motor Frame Amp. Service Thermal Weight Efficiency
17&18 Size (HP) Type ➀Size Draw Factor Overload (lbs) ➁ (%)
E2 or Q2 1 1/2 ODP 145T 4.8 1.00 35 89.5%
E3 or Q3 1 1/2 ODP 18/9 145T 5.0/2.1 1.15 29 80.0 / 65.0%
E4 or Q4 1 1/2 ODP 18/12 145T 5.0/2.9 1.15 49 80.0 / 71.0%
E5 or Q5 1 1/2 TEFC 56 4.8 1.15 33 N/A
E6 or Q6 1 1/2 TE HE 145T 4.9 1.15 62 84.0%
E7 or Q7 1 1/2 TEFC 18/9 145T 4.3/1.9 1.00 38 83.0 / 71.0%
E8 or Q8 1 1/2 TEFC 18/12 145T 5.0/2.9 1.00 38 80.0 / 72.0%
F1 or R12 ODP 145T 7.2 1.15 43 82.0%
F2 or R22 ODP 145T 5.8 1.00 74 89.5%
F3 or R32 ODP 18/9 145T 6.2/2.6 1.15 33 81.0 / 67.0%
F4 or R42 ODP 18/12 182T 6.5/3.5 1.15 78 81.0 / NA%F5 or R52 TE 145T 7.0 1.15 52 84.0%
F6 or R62 TE HE 145T 6.5 1.15 66 86.5%
F7 or R72 TEFC 18/9 145T 6.4/2.5 1.00 41 84.0 / 70.0%
F8 or R82 TE 18/12 182T 6.4/3.9 1.15 65 84.0 / 77.0%
G1 or S13 ODP 182T 10.0 1.15 78 81.5%
G2 or S23 ODP HE 182T 8.9 1.15 83 89.5%
G3 or S33 ODP 18/9 182T 10.1/4.1 1.15 66 82.0 / 72.0%
G4 or S43 ODP 18/12 184T 9.3/4.9 1.15 79 81.0 / 75.0%
G5 or S53 TE 182T 10.0 1.15 83 87.5%
G6 or S63 TE HE 182T 9.4-9.1 1.15 92 88.5%
G7 or S73 TE 18/9 182T 9.3/3.5 1.00 64 84.0 / 70.0%
G8 or S83 TE 18/12 184T 9.2/5.4 1.15 84 84.0 / 82.0%
H1 or T15 ODP 184T 16.0 1.15 76 84.0%
H2 or T25 ODP HE 182T 15.7 1.15 94 89.5%
H3 or T35 ODP 18/9 184T 16.0/6.2 1.15 81 85.0 / 77.0%
H4 or T45 ODP 18/12 215T 16.0/9.7 1.15 117 86.0 / 78.0%
H5 or T55 TE 184T 14.2 1.15 90 87.5%
H6 or T65 TE HE 184T 15.0 1.15 99 88.5%
H7 or T75 TE 18/9 184T 15.0/5.3 1.00 85 85.0 / 85.0%
H8 or T85 TE 18/12 213T 15.0/8.5 1.15 107 85.0 / 80.0%
I1 or W1 7 1/2 ODP 213T 26.9 1.15 106 81.5%
Motor
Digits Size Motor Frame Amp. Service Weight Efficiency
17&18 (HP) Type ➁ Size Draw Factor (lbs) (%)
I2 or W2 7 1/2 ODP HE 213T 22.3 1.15 141 91.7%
I3 or W3 7 1/2 ODP 18/9 213T 23.0/9.3 1.15 108 85.0 / 72.0%
I4 or W4 7 1/2 ODP 18/12 215T 22.0/12.3 1.15 167 89.0 / 85.0%
I5 or W5 7 1/2 TE 213T 24.0 1.15 126 89.5%
I6 or W6 7 1/2 TE HE 213T 22.0 1.15 158 90.2%I7 or W7 7 1/2 TE 18/9 213T 21.0/8.8 1.15 106 87.0 / 75.0%
I8 or W8 7 1/2 TE 18/12 215T 21.8/12.0 1.15 124 86.0 / 80.0%
J1 or X1 10 ODP 215T 32.6 1.15 120 84.0%
J2 or X2 10 ODP HE 215T 29.0 1.15 126 91.7%
J3 or X3 10 ODP 18/9 215T 27.7/11.2 1.15 118 88.0 / 77.0%J4 or X4 10 ODP 18/12 256T 27.0/14.5 1.15 196 88.0 / 80.0%
J5 or X5 10 TE 215T 29.0 1.15 130 87.5%
J6 or X6 10 TE HE 215T 27.6 1.15 200 90.2%
J7 or X7 10 TE 18/9 215T 29.0/11.5 1.15 118 87.0 / 77.0%
J8 or X8 10 TE 18/12 254T 30.0/17.0 1.15 212 88.0 / 80.0%
K1 or Y1 15 ODP 254T 45.6 1.15 147 87.5%K2 or Y2 15 ODP HE 254T 43.4 1.15 220 93.0%
K3 or Y3 15 ODP 18/9 256T 42.5/16.5 1.15 244 90.2 / 84.0%
K5 or Y5 15 TE 254T 42.0 1.15 250 91.0%
K6 or Y6 15 TE HE 254T 40.3 1.15 259 91.7%K7 or Y7 15 TE 18/9 256T 44.0/16.0 1.15 218 88.0 / 82.0%
K8 or Y8 15 TE 18/12 256T 42.0/23.0 1.15 219 88.0 / 84.0%
V1 or Z1 20 ODP 256T 61.6 1.15 200 87.5%
V2 or Z2 20 ODP HE 256T 57.0 1.15 250 93.6%
V3 or Z3 20 ODP 18/9 284T 56.0/21.0 1.15 221 90.2 / 82.5%V4 or Z4 20 ODP 18/12 286T 54.0/28.0 1.15 270 89.0 / 86.0%
V6 or Z6 20 TE HE 256T 54.0 1.15 290 91.7%
V7 or Z7 20 TE 18/9 284T 59.0/20.0 1.15 346 89.0 / 88.0%
① Motors have no thermal overload.
② Refer to page 42 for Motor Type abbreviations.
5-565.139
MOTOR DATA
Table 40.1 - Motor Data for Digit 14 = E - 230V/60Hz/3Ph ①
Motor
Digits Size Motor Frame Amp. Service Weight Efficiency
17&18 (HP) Type ➁ Size Draw Factor (lbs) (%)
A1 or L1 1/3 ODP 56 1.6 1.35 17 N/A
A5 or L5 1/3 TE 48 1.2 1.00 15 N/A
B1 or M1 1/2 ODP 56 2.2 1.25 18 N/A
B5 or M5 1/2 TEFC 56 2.2 1.15 18 N/A
C1 or N1 3/4 ODP 56 2.8 1.25 21 N/A
C5 or N5 3/4 TEFC 56 2.8 1.15 30 N/A
D1 or P1 1 ODP 143T 3.1 1.15 36 82.5%
D2 or P2 1 ODP HE 143T 3.2 1.15 30 84.0%
D3 or P3 1 ODP 18/9 143T 3.4/1.6 1.15 26 76.0 / 59.0%
D4 or P4 1 ODP 18/12 145T 3.4/2.2 1.15 42 74.0 / 60.0%
D5 or P5 1 TEFC 56 3.6 1.15 28 N/A
D6 or P6 1 TE HE 143T 3.0 1.15 68 85.5%
D7 or P7 1 TEFC 18/9 143T 3.4/1.6 1.00 29 76.0 / 58.0%
D8 or P8 1 TEFC 18/12 145T 3.4/2.2 1.00 31 74.0 / 60.0%
E1 or Q1 1 1/2 ODP 145T 4.4 1.15 42 84.0%
E2 or Q2 1 1/2 ODP 145T 5.6 1.00 35 89.5%
E3 or Q3 1 1/2 ODP 18/9 145T 4.8/2.7 1.15 29 80.0 / 65.0%
E4 or Q4 1 1/2 ODP 18/12 145T 4.9/2.8 1.15 49 80.0 / 71.0%
E5 or Q5 1 1/2 TEFC 56 4.8 1.15 33 N/A
E6 or Q6 1 1/2 TE HE 145T 5.0 1.15 62 86.5%
E7 or Q7 1 1/2 TEFC 18/9 145T 4.0/1.7 1.00 38 83.0 / 71.0%
E8 or Q8 1 1/2 TEFC 18/12 145T 4.9/2.8 1.00 38 80.0 / 72.0%
F1 or R1 2 ODP 145T 5.8 1.15 43 84.0%
F2 or R2 2 ODP 145T 5.8 1.00 74 89.5%
F3 or R3 2 ODP 18/9 145T 6.4/2.7 1.15 33 81.0 / 67.0%
F4 or R4 2 ODP 18/12 182T 6.3/3.5 1.15 78 81.0 / NA%
F5 or R5 2 TE 145T 5.8 1.15 52 84.0%
F6 or R6 2 TE HE 145T 6.0 1.15 64 85.5%
F7 or R7 2 TEFC 18/9 145T 6.4/2.6 1.00 41 84.0 / 70.0%
F8 or R8 2 TE 18/12 182T 6.4/4.2 1.15 65 84.0 / 77.0%
G1 or S1 3 ODP 182T 9.4 1.15 81 86.5%
G2 or S2 3 ODP HE 182T 8.6 1.15 74 89.5%
G3 or S3 3 ODP 18/9 182T 11.6/4.4 1.15 66 82.0 / 72.0%
G4 or S4 3 ODP 18/12 184T 8.5/4.6 1.15 79 81.0 / 75.0%
G5 or S5 3 TE 182T 8.2 1.15 83 87.5%
G6 or S6 3 TE HE 182T 8.0 1.15 110 89.5%
G7 or S7 3 TE 18/9 182T 10.0/3.6 1.00 64 84.0 / 70.0%
G8 or S8 3 TE 18/12 184T 8.8/5.5 1.15 84 84.0 / 82.0%
H1 or T1 5 ODP 184T 14.0 1.15 87 87.5%
H2 or T2 5 ODP HE 184T 13.6 1.15 94 89.5%
H3 or T3 5 ODP 18/9 184T 17.7/6.2 1.15 81 85.0 / 77.0%
H4 or T4 5 ODP 18/12 215T 15.5/10.2 1.15 117 86.0 / 78.0%
H5 or T5 5 TE 184T 13.0 1.15 90 87.5%
H6 or T6 5 TE HE 184T 13.0 1.15 117 90.2%
H7 or T7 5 TE 18/9 184T 16.0/5.3 1.00 85 85.0 / 85.0%
H8 or T8 5 TE 18/12 213T 14.0/8.8 1.15 107 85.0 / 80.0%
① Motors have no thermal overload.
② Refer to page 42 for Motor Type abbreviations.
Motor
Digits Size Motor Frame Amp. Service Weight Efficiency
17&18 (HP) Type ➁ Size Draw Factor (lbs) (%)
I1 or W1 7 1/2 ODP 213T 19.6 1.15 121 88.5%
I2 or W2 7 1/2 ODP HE 213T 19.4 1.15 160 91.7%
I3 or W3 7 1/2 ODP 18/9 213T 22.5/8.2 1.15 108 85.0 / 72.0%
I4 or W4 7 1/2 ODP 18/12 215T 19.5/12.3 1.15 167 89.0 / 85.0%
I5 or W5 7 1/2 TE 213T 20.0 1.15 126 89.5%
I6 or W6 7 1/2 TE HE 213T 19.2 1.15 194 91.7%
I7 or W7 7 1/2 TE 18/9 213T 21.0/8.8 1.15 106 87.0 / 75.0%
I8 or W8 7 1/2 TE 18/12 215T 20.0/12.4 1.15 124 86.0 / 80.0%
J1 or X1 10 ODP 215T 26.8 1.15 138 89.5%
J2 or X2 10 ODP HE 215T 25.2 1.15 220 91.7%
J3 or X3 10 ODP 18/9 215T 32.4/11.6 1.15 118 88.0 / 77.0%
J4 or X4 10 ODP 18/12 256T 24.0/13.0 1.15 196 88.0 / 80.0%
J5 or X5 10 TE 215T 26.0 1.00 138 89.5%
J6 or X6 10 TE HE 215T 25.0 1.15 213 90.2%
J7 or X7 10 TE 18/9 215T 29.0/11.5 1.15 118 87.0 / 77.0%
J8 or X8 10 TE 18/12 254T 28.0/17.5 1.15 212 88.0 / 80.0%
K1 or Y1 15 ODP 254T 38.6 1.15 215 91.0%
K2 or Y2 15 ODP HE 254T 37.8 1.15 217 93.0%
K3 or Y3 15 ODP 18/9 256T 40.0/17.0 1.15 244 90.2 / 84.0%
K5 or Y5 15 TE 254T 40.0 1.15 250 91.0%
K6 or Y6 15 TE HE 254T 38.0 1.15 322 92.4%
K7 or Y7 15 TE 18/9 256T 39.0/15.0 1.15 218 88.0 / 82.0%
K8 or Y8 15 TE 18/12 256T 38.0/22.0 1.15 219 88.0 / 84.0%
V1 or Z1 20 ODP 256T 50.0 1.15 233 91.0%
V2 or Z2 20 ODP HE 256T 49.0 1.15 250 93.6%
V3 or Z3 20 ODP 18/9 284T 51.0/21.5 1.15 221 90.2 / 82.5%
V4 or Z4 20 ODP 18/12 286T 48.0/26.0 1.15 270 89.0 / 86.0%
V5 or Z5 20 TEFC 256T 51.0 1.15 287 91.0%
V6 or Z6 20 TE HE 256T 48.2 1.15 368 93.0%
V7 or Z7 20 TE 18/9 284T 52.0/18.0 1.15 346 89.0 / 88.0%
5-565.140
MOTOR DATA
Table 41.1 - Motor Data for Digit 14 = F - 460V/60Hz/3Ph ➀
Motor
Digits Size Motor Frame Amp. Service Weight Efficiency
17&18 (HP) Type ➁ Size Draw Factor (lbs) (% )
A1 or L1 1/3 ODP 56 0.8 1.35 17 N/A
A3 or L3 1/3 TE 48 0.6 1.00 15 N/A B1 or M1 1/2 ODP 56 1.1 1.25 18 N/AB5 or M5 1/2 TEFC 56 1.1 1.15 18 N/AC1 or N1 3/4 ODP 56 1.4 1.25 21 N/AC5 or N5 3/4 TEFC 56 1.4 1.15 30 N/AD1 or P1 1 ODP 143T 1.6 1.15 36 82.5%
D2 or P2 1 ODP HE 143T 1.5 1.15 30 84.0%
D3 or P3 1 ODP 18/9 143T 1.8/0.8 1.15 26 76.0 / 59.0%
D4 or P4 1 ODP 18/12 145T 1.7/1.1 1.15 39 74.0 / 60.0%D5 or P5 1 TEFC 56 1.8 1.15 28 N/AD6 or P6 1 TE HE 143T 1.5 1.15 68 85.5% D7 or P71 TEFC 18/9 143T 1.8/0.8 1.00 28 73.0 / 58.0%D8 or P8 1 TEFC 18/12 145T 1.7/1.1 1.00 31 74.0 / 60.0% E1 or Q1 1 1/2 ODP 145T 2.2 1.15 42 84.0%E2 or Q2 1 1/2 ODP 145T 2.4 1.00 35 89.5% E3 or Q3 1 1/2 ODP 18/9 145T 2.3/1.0 1.15 29 80.0 / 65.0%E4 or Q4 1 1/2 ODP 18/12 145T 2.4/1.4 1.15 32 75.0 / 71.0% E5 or Q5 1 1/2 TEFC 56 2.4 1.15 33 N/AE6 or Q6 1 1/2 TE HE 145T 2.5 1.15 62 86.5% E7 or Q7 1 1/2 TEFC 18/9 145T 2.0/0.9 1.00 39 83.0 / 71.0%E8 or Q8 1 1/2 TEFC 18/12 145T 2.5/1.4 1.00 37 80.0 / 72.0%
F1 or R1 2 ODP 145T 2.9 1.15 43 84.0%
F2 or R2 2 ODP 145T 2.9 1.00 74 89.5%
F3 or R3 2 ODP 18/9 145T 3.0/1.3 1.15 33 79.0 / 62.0%
F4 or R4 2 ODP 18/12 182T 3.0/2.0 1.15 61 80.0 / 70.0%
F5 or R5 2 TE 145T 2.9 1.15 52 84.0%
F6 or R6 2 TE HE 145T 3.0 1.15 64 85.5%
F7 or R7 2 TEFC 18/9 145T 3.2/1.3 1.00 42 84.0 / 70.0%
F8 or R8 2 TE 18/12 182T 3.1/1.9 1.15 68 81.0 / 77.0%
G1 or S1 3 ODP 182T 4.5 1.15 81 86.5%G2 or S2 3 ODP HE 182T 4.3 1.15 74 89.5%G3 or S3 3 ODP 18/9 182T 4.5/1.8 1.15 60 80.0 / 66.0% G4 or S43 ODP 18/12 184T 4.6/2.7 1.15 71 82.5 / NA%G5 or S5 3 TE 182T 4.1 1.15 83 87.5%G6 or S6 3 TE HE 182T 4.0 1.15 110 89.5%G7 or S7 3 TE 18/9 182T 4.6/1.7 1.15 65 84.0 / 70.0%G8 or S8 3 TE 18/12 184T 4.3/2.6 1.15 73 82.5 / 75.5%
H1 or T1 5 ODP 184T 7.0 1.15 87 87.5%
H2 or T2 5 ODP HE 184T 6.8 1.15 94 89.5%
H3 or T3 5 ODP 18/9 184T 9.1/3.2 1.15 94 84.0 / 73.0%
H4 or T4 5 ODP 18/12 215T 7.1/4.8 1.15 117 78.0 / 71.0%
H5 or T5 5 TE 184T 6.5 1.15 90 87.5%
➀ Motors have no thermal overload.
➁Refer to page 42 for Motor Type abbreviations.
Motor
Digits Size Motor Frame Amp. Service Weight Efficiency
17&18 (HP) Type ➁ Size Draw Factor (lbs) (%)
H6 or T6 5 TE HE 184T 6.5 1.15 117 90.2%
H7 or T7 5 TE 18/9 184T 7.0/2.5 1.15 83 86.0 / 83.0%
H8 or T8 5 TE 18/12 213T 6.9/4.1 1.15 107 85.0 / 75.5%
I1 or W1 7 1/2 ODP 213T 9.8 1.15 121 88.5%
I2 or W2 7 1/2 ODP HE 213T 9.7 1.15 160 91.7%
I3 or W3 7 1/2 ODP 18/9 213T 11.8/4.2 1.15 125 85.0 / 72.0%
I4 or W4 7 1/2 ODP 18/12 215T 10.0/6.0 1.15 131 87.0 / 80.0%
I5 or W5 7 1/2 TE 213T 10.0 1.15 126 89.5%
I6 or W6 7 1/2 TE HE 213T 9.6 1.15 194 91.7%
I7 or W7 7 1/2 TE 18/9 213T 10.0/4.1 1.15 83 84.0 / 74.0%
I8 or W8 7 1/2 TE 18/12 215T 10.3/5.6 1.15 128 85.0 / 80.0%
J1 or X1 10 ODP 215T 13.4 1.15 138 89.5%
J2 or X2 10 ODP HE 215T 12.6 1.15 220 91.7%
J3 or X3 10 ODP 18/9 215T 15.0/5.3 1.15 116 83.0 / 71.0%
J4 or X4 10 ODP 18/12 256T 12.0/6.3 1.15 192 87.0 / 82.0%
J5 or X5 10 TE 215T 13.0 1.00 138 89.5%
J6 or X6 10 TE HE 215T 12.5 1.15 213 90.2%
J7 or X7 10 TE 18/9 215T 13.0/5.4 1.15 107 86.5 / 77.0%
J8 or X8 10 TE 18/12 254T 13.5/7.5 1.15 222 87.0 / 82.0%
K1 or Y1 15 ODP 254T 19.3 1.15 215 91.0%
K2 or Y2 15 ODP HE 254T 18.9 1.15 217 93.0%
K3 or Y3 15 ODP 18/9 256T 19.3/7.8 1.15 203 88.5 / 81.5%
K4 or Y4 15 ODP 18/12 256T 18.0/9.5 1.15 298 86.0 / 81.0%
K5 or Y5 15 TE 254T 20.0 1.15 250 91.0%
K6 or Y6 15 TE HE 254T 19.0 1.15 322 92.4%
K7 or Y7 15 TE 18/9 256T 19.5/7.5 1.15 218 88.0 / 82.0%
K8 or Y8 15 TE 18/12 256T 19.5/11.0 1.15 223 88.0 / 84.0%
V1 or Z1 20 ODP 256T 25.0 1.15 233 91.0%
V2 or Z2 20 ODP HE 256T 24.5 1.15 250 93.6%
V3 or Z3 20 ODP 18/9 256T 25.2/10.0 1.15 208 89.5 / 82.5%
V4 or Z4 20 ODP 18/12 286T 24.0/13.0 1.15 270 90.0 / 84.0%
V5 or Z5 20 TEFC 256T 25.5 1.15 287 91.0%
V6 or Z6 20 TE HE 256T 24.1 1.15 368 93.0%
V7 or Z7 20 TE 18/9 284T 26.0/8.7 1.15 331 89.0 / 88.0%
V8 or Z8 20 TE 18/12 284T 24.7/14.0 1.15 361 90.0 / 86.0%
5-565.141
MOTOR DATA
Table 42.1 - Motor Data for Digit 14 = G - 575V/60Hz/3Ph ➀
Digits Motor Motor Frame Amp. Service Weight Efficiency
17&18 Size (HP) Type ➁Size Draw Factor (lbs) (%)
A5 or L5 1/3 TEFC 56 0.6 1.15 16 N/A
B1 or M1 1/2 ODP 56 0.9 1.25 25 N/A
B5 or M5 1/2 TEFC 56 0.9 1.15 24 N/A
C1 or N1 3/4 ODP 56 0.9 1.25 28 N/A
C5 or N5 3/4 TEFC 56 1.1 1.15 33 N/A
D1 or P1 1 ODP 143T 1.1 1.15 41 82.5%
D5 or P5 1 TEFC 56 1.5 1.15 28 77.0%
D6 or P6 1 TE HE 143T 1.2 1.15 68 85.5%
E1 or Q1 1 1/2 ODP 145T 1.8 1.15 48 84.0%
E5 or Q5 1 1/2 TEFC 145T 2.0 1.15 72 84.0%
E6 or Q6 1/12 TE HE 145T 1.7 1.15 66 85.5%
F1 or R1 2 ODP 145T 2.3 1.15 50 84.0%
F5 or R5 2 TEFC 145T 2.3 1.15 65 84.0%
F6 or R6 2 TE HE 145T 2.4 1.15 66 86.5%
G1 or S1 3 ODP 182T 3.4 1.15 72 86.5%
G5 or S5 3 TEFC 182T 3.4 1.15 98 87.5%
G6 or S6 3 TE HE 182T 3.2 1.15 100 89.5%
H1 or T1 5 ODP 184T 5.2 1.15 91 87.5%
H5 or T5 5 TEFC 184T 5.2 1.15 89 87.5%
H6 or T6 5 TE HE 184T 5.2 1.15 117 89.5%
I1 or W1 7 1/2 ODP 213T 7.8 1.15 113 88.5%
I5 or W5 7 1/2 TEFC 213T 8.0 1.15 142 89.0%
I6 or W6 7 1/2 TE HE 213T 7.6 1.15 192 90.2%
J1 or X1 10 ODP 215T 10.3 1.15 123 89.5%
J5 or X5 10 TE 215T 10.4 1.15 154 89.5%
J6 or X6 10 TE HE 215T 9.6 1.15 200 90.2%
K1 or Y1 15 ODP 254T 15.4 1.15 184 91.0%
K5 or Y5 15 TE 254T 16.0 1.15 250 91.0%
K6 or Y6 15 TE HE 254T 15.2 1.15 326 92.4%
V1 or Z1 20 ODP 256T 20.8 1.15 255 91.0%
V5 or Z5 20 TEFC 256T 20.4 1.15 287 91.0%
V6 or Z6 20 TE HE 256T 19.5 1.15 368 93.0%
➀ Motors have no thermal overload
➁ Motor Type Abbreviations
ODP Open Drip Proof
ODP HE Open Drip Proof, High Efficiency
ODP 18/9 Open Drip Proof, 2-speed 1800/900 RPM
ODP 18/12 Open Drip Proof, 2-speed 1800/1200 RPM
TE Totally Enclosed
TEFC Totally Enclosed, Fan Cooled
TE HE Totally Enclosed, High Efficiency
TE 18/9 Totally Enclosed, 2-speed 1800/900 RPM
TE 18/12 Totally Enclosed, 2-speed 1800/1200 RPM
TENV Totally Enclosed, Non-Ventilating
5-565.142
BOTTOM ELECTRICAL CONNECTION
KNOCKOUTS, IDENTICAL SIZE AS SIDE
CONNECTIONS (ONLY ON ACCESS SIDE)
250/300 E, F, G, or H 1 3775 23.07 27.13 32.75 30.00 28.00 29.96 43.23 44.05 42.37 24.60 8/10 44.80 87.77 3/4
350/400 E, F, G, or H 1 37.75 23.07 38.63 32.75 42.00 28.00 41.90 43.23 55.57 42.37 36.14 10 44.80 87.77 3/4
500/600 G or H 2 37.75 23.07 27.13 32.75 n/a n/a 29.96 43.23 44.05 42.37 24.60 8/10 44.80 120.90 3/4
700/800 G or H 2 37.75 23.07 38.63 32.75 n/a n/a 41.90 43.23 55.57 42.37 36.14 10 44.80 120.90 3/4
➀ For Right Hand Access Units - Location of electrical connection knock-outs are identical sizes as side electrical connections.
➁For Left Hand Access Units - Location of electrical connection knock-outs are identical sizes as side electrical connections.
Dimensions
5-565.143
BOTTOM ELECTRICAL CONNECTION
KNOCKOUTS, IDENTICAL SIZE AS SIDE
CONNECTIONS (ONLY ON ACCESS SIDE)
Figure 44.1 - DBP Indoor Power Vented Blower Package Unit Dimensions with Blower Type I, J, K, or L
500 - 800 Model Shown
Figure 44.2 - DCP Indoor Power Vented Cooling Package Unit Dimensions with Blower Type I, J, K, or L
Table 44.1 - DBP/DCP Indoor Power Vented Unit Dimensions with Blower Type I, J, K, or L
(All dimensions in inches)
Model Blower Type Qty. of Gas
Size (Digit 16) Furnaces C E G J L N S U ➂ W ➂ X ➂ Conn.
250/300 I, J, or K 1 27.13 30.00 29.96 44.05 24.60 8/10 123.35 n/a n/a n/a 3/4
350/400 I, J, or K 1 38.63 42.00 41.90 55.07 36.14 10 123.35 n/a n/a n/a 3/4
500/600 I, J, K, or L 2 27.13 n/a 29.96 44.05 24.60 8/10 156.76 29.74 6.5 41.62 3/4
700/800 I, J, K, or L 2 38.63 n/a 41.90 55.57 36.14 10 156.76 29.74 6.5 41.62 3/4
840/960 I, J, K, or L 3 38.63 n/a 41.90 55.57 36.14 10 185.99 29.74 6.5 41.62 3/4
➀ For Right Hand Access Units - Location of electrical connection knock-outs are identical sizes as side electrical connections.
➁For Left Hand Access Units - Location of electrical connection knock-outs are identical sizes as side electrical connections.
➂Applies to units with Digit 16 = L only.
Dimensions
5-565.144
DIMENSIONS - BASE
0.75" Suspensio
n
Hanging Location
s
(Typical 4 Corners
)
0.63
2.
36
1.4
5
Return Air
Openin
g
4.3
5
24.00 Insid
e
M
E Insi
de
C
To end of uni
t
J
D
K
L
N
Lifting
Point
Suspension
Point
Suspension
Point
Lifting
Point
g
Figure 45.1 - Unit Base Dimensions
Table 45.1 - Indoor Power Vented Blower Package Units (All dimensions in inches)
Model Blower Type
Size (Digit 16) A B C D E N K L J M
75 All 87.77 34.85 81.30 19.52 32.00 6.23
100/125 All 87.77 37.36 81.30 19.52 34.50 7.49
150/175 All 87.77 41.61 81.30 23.49 38.75 7.63
200/225 All 87.77 43.71 81.30 23.49 40.85 8.69
250/300 E,F,G, or H 87.77 46.75 81.30 29.46 43.89 7.21
250/300 I, J, or K 123.35 46.75 117.26 29.46 43.89 7.21
350/400 E,F,G, or H 87.77 58.27 81.30 41.40 55.41 7.00
350/400 I, J, or K 123.35 58.27 117.26 41.40 55.41 7.00
500/600 G, or H 120.90 46.75 111.68 34.12 29.46 89.14 34.12 43.89 7.21
500/600 I, J, K, or L 156.76 46.75 147.53 34.12 29.46 117.82 82.27 43.89 7.21
700/800 G, or H 120.90 58.27 111.68 34.12 41.40 89.14 34.12 55.41 7.00
700/800 I, J, K, or L 156.76 58.27 147.53 34.12 41.40 117.82 82.27 55.41 7.00
840/960 I, J, K, or L 185.99 58.27 176.75 30.31 41.40 147.06 63.36 147.06 55.41 7.00
Dimensions
Table 45.2 - Indoor Power Vented Cooling Package Units (All dimensions in inches)
1. Holes visable on right side are
also on left side in the same location.
2. Holes on top are also on the back
in the same location horizontally,
1" down vertically.
Figure 47.1 - Remote Panel Dimensions
Table 47.3 - Remote Panel Dimensions
(All dimensions in inches)
Remote Panel Type A B C
Light and Switch Panels Only 7.06 - 2.81
Light and Switch Panels with Single Stage
Thermostat or Electronic Set Point Adjustor
Light and Switch Panels with
Two Stage Thermostat
Table 47.1 - Blower Package Unit Operating Weights
(All weights in pounds)
Model Blower Type Dampers Dampers Double Wall
Size (Digit 16) Unit Fresh Air F & RA (All Sections)
75All 236 6 26 46 5 38
100/125All 272 6 26 46 5 38
150/175All 308 6 29 52 5 43
200/225All 365 6 29 52 7 46
250/300 E,F,G, or H 396 8 33 60 7 46
250/300 I, J, or K 645 15 33 60 14 93
350/400 E,F,G, or H 482 12 38 70 7 53
350/400 I, J, or K 763 17 38 70 14 96
500/600G or H 577 8 33 60 7 46
500/600 I, J, K, or L 826 15 33 60 14 93
700/800G or H 733 12 38 70 7 53
700/800 I, J, K, or L 1014 17 38 70 14 96
840/960 I, J, K, or L 1265 17 38 70 14 96
Motor
Filters
See Motor Data
Insulation
10.60 3.53 4.58
13.09 6.03 5.82
Table 47.2 - Cooling Package Unit Operating Weights
(All weights in pounds)
Blower Dampers Model Type Dampers Fresh & Double Wall
Size (Digit 16) Unit Motor Filters Fresh Air Return Air Insulation (All Sections)
75 All 343 6 26 46 10 72
100/125 All 382 6 26 46 10 72
150/175 All 423 6 29 52 10 77
200/225 All 491 6 29 52 12 85
250/300 E,F,G, or H 526 8 33 60 12 87
250/300 I, J, or K 775 15 33 60 19 134
350/400 E,F,G, or H 631 12 38 70 12 101
350/400 I, J, or K 912 17 38 70 19 144
See Motor
Data
5-565.147
MAINTENANCE
WARNING
When servicing or repairing this equipment, use only factoryapproved service replacement parts. A complete replacement
parts list may be obtained by contacting Modine Manufacturing
Company. Refer to the rating plate on the appliance for
complete appliance model number, serial number, and
company address. Any substitution of parts or controls not
approved by the factory will be at the owner’s risk.
CAUTION
Do not attempt to reuse any mechanical or electrical controllers
which have been wet. Replace defective controller.
IMPORTANT
To check most of the Possible Remedies in the troubleshooting
guide listed in Table 50.1, refer to the applicable sections of the
manual.
All heating equipment should be serviced before each heating
season to assure proper operations. The following items may be
required to have more frequent service schedule based on the
environment in which the unit is installed, and the frequency of
the equipment operation.
Blower Assembly
The blower assembly includes the bearings, drive sheaves and belts.
Blower bearings should be checked and lubricated based on the
blower manufacturer’s recommendations. Bearings should also
be checked for any unusual wear and replaced if needed.
Drive sheaves should be checked at the same time the bearings
are inspected. Check to make sure the sheaves are in alignment
and are securely fastened to the blower and motor shafts.Belt
tension should be rechecked shortly after the unit has been
installed to check for belt stretching. After the initial start-up,
monthly checks are recommended.
Figure 48.2 - Filter Replacement Arrangement for
Blower Size (Digit 16) I, J, K, and L
A
D
B
A
NON-ACCESS
SIDE
D
350/400
700/800
840/960
FILTER
SPACER
B
A
C
A
NON-ACCESS
SIDE
A
C
A
A = 20'' x 25''
B = 16'' x 25''
C = 20'' x 16''
D = 15'' X 25''
FILTER
SPACER
A
A
A
A
A
C
250/300
500/600
Manifold Assembly Removal
To remove the manifold
1. Shut off gas and electric supply.
2. Disconnect gas manifold at ground union joint.
3. Remove the two screws holding the manifold to the heat
exchanger support.
4. Slide the manifold through the manifold bracket.
5. Clean the orifices and adjust the air shutters as necessary.
6. Follow steps 3-6 in reverse order to install the manifold
assembly.
7. Turn on the electric and gas supply.
8. Check the ground union joint for leaks with a soap solution.
Tighten if necessary.
Figure 48.3 - Manifold Assembly Removal
Filters
If the unit is supplied with a dirty filter switch and light, clean or
replace the filters any time the dirty filter light comes on.
Units which do not have a dirty filter warning light should have
the filters checked monthly. Clean or replace if necessary. In dirty
atmospheres, filter maintenance may be required more often.
Figure 48.1 - Filter Replacement Arrangement for
Blower Size (Digit 16) A, B, C, D, E, F, G and H
FILTER SPACER
▼
B
C
B
C
75
A
A
A = 20" X 25" FILTER
B = 16" X 25" FILTER
C = 15" X 25" FILTER
Filter Spacer to be inserted on non-access side of unit
A
A
200/225
B
B
B
100/125
A
A
250/300
500/600
B
FILTER SPACER
A
A
B
B
A
150/175
A
A
C
A
C
A
350/400
700/800
A
ELECTRICAL
JUNCTION
BOX
MANIFOLD
SERIAL PLATE
BURNER SIDE
ACCESS PANEL
5-565.148
MAINTENANCE
Burner and Pilot Assembly Removal
To remove the burner
1. Shut off gas and electric supply.
2. Disconnect the pilot supply line from the gas valve.
3. Disconnect the ignition cable from the ignition controller (located
in the electrical junction box). Feed the cable through the
bushing in the bottom of the electrical junction box.
4. Remove the screws holding the burner side access panel.
Attached to the panel are the burner retaining pins that align
the burner.
5. Slide the burner assembly out. The pilot is attached to the
burner assembly.
6. Examine the burner and pilot assembly for cleanliness and/or
obstructions as necessary (see Duct Furnace for cleaning
instructions).
7. Replace the burner assembly in reverse order. In replacing
the burner, be certain that the rear burner slots are located
properly on the burner retaining pins. Do not force the burner
side access panel, it will not fit if the burner is not properly
aligned.
8. Reconnect the ignition cable and pilot gas supply line.
9. Turn on the electric and gas supply.
Figure 49.1 - Burner and Pilot Assembly Removal
AIR SHUTTERS
(NOT SHOWN)
ARE LOCATED
ON THE
MANIFOLD
PILOT
ASSEMBLY
IGNITION
CABLE
PILOT
SUPPLY
LINE
5-565.149
SERVICE & TROUBLESHOOTING
Table 50.1 - Troubleshooting
Trouble Possible Cause Possible Remedy
Power Exhauster Motor will not start1. Power supply is off.
2. No 24V power to thermostat.
3. Thermostat malfunction.
4. Defective power exhauster relay.
5. Defective power exhauster motor.
Pilot does not light/stay lit1. Main gas is off.
2. Power supply is off.
3. Air in gas line.
4. Dirt in pilot orifice.
5. Gas pressure out of proper range.
6. Pilot valve does not open.
a. Defective ignition controller.
b. Defective gas valve.
7. No spark at ignitor.
a. Loose wire connections.
b. Pilot sensor is grounded.
c. Defective ignition controller.
8. Safety device has cut power.
9. Excessive drafts.
10. Pilot orifice fitting leak.
1. Turn on main power.
2. Check control transformer.
3. Check/replace thermostat.
4. Replace power exhauster relay.
5. Replace power exhauster motor.
1. Open manual gas valve.
2. Turn on main power.
3. Purge gas line.
4. Check for plugged pilot orifice and clean
with compressed air if necessary.
5. Adjust to a maximum of 14" W.C.
Minimum for Natural Gas - 6" W.C.
Minimum for Propane Gas - 11" W.C.
6. Check wiring for 24 volts to valve.
a. Replace ignition controller.
b. Replace gas valve.
7. a. Check all ignition controller wiring.
b. Replace sensor if cracked or worn.
c. Replace ignition controller.
8. Check all safety devices (High limit, air flow
proving switch, differential pressure switch,
gas pressure switches, etc.) Determine and
correct problem. Reset if necessary.
9. Find source and re-direct airflow away from
unit.
10. Tighten pilot orifice. Flame impingment
on pilot sensor may cause pilot sensor to
become inoperative.
Main burners do not light (Pilot is lit)
Lifting Flames (See Figure 51.1)
Yellow Tipping
(With propane gas, some yellow tipping
is always present.)
Flashback1. Too much primary air.
Floating Flames (See Figure 51.2)
Flame Rollout (See Figure 51.3)
1. Defective valve.
2. Loose wiring.
3. Defective pilot sensor.
4. Defective ignition controller.
5. Improper thermostat wiring.
1. Too much primary air.
2. Main pressure set too high.
3. Orifice too large.
1. Insufficient primary air.
2. Dirty orifice.
3. Misaligned orifice.
2. Main pressure set too high.
3. Orifice too large.
1. Insufficient primary air.
2. Main pressure set too high.
3. Orifice too large.
4. Blocked vent.
1. Main pressure set too high.
2. Orifice too large.
3. Blocked vent.
1. Replace valve.
2. Check wiring to gas valve.
3. Replace pilot sensor.
4. Replace ignition controller.
5. Verify wiring compared to wiring diagram.
1. Reduce primary air.
2. Adjust to a maximum of 14" W.C.
3. Check orifice size with those listed on the
serial plate.
1. Increase primary air.
2. Check orifices and clean with compressed
air if necessary.
3. Check manifold, replace if necessary.
1. Reduce primary air.
2. Adjust to a maximim of 14” W.C.
3. Check orifice size with those listed on
the serial plate.
1. Increase primary air.
2. Adjust to a maximum of 14" W.C.
3. Check orifice size with those listed on
the serial plate.
4. Clean/correct venting system.
1. Adjust to a maximum of 14" W.C.
2. Check orifice size with those listed on
the serial plate.
3. Clean/correct venting system.
5-565.150
SERVICE & TROUBLESHOOTING
Trouble Possible Cause Possible Remedy
Not Enough Heat
1. Unit cycling on high limit.➀
a. Obstructions/leaks in duct system.
b. Main pressure set too high.
c. Blower motor not energized.
d. Loose belt
e. Blower speed too low.
f. Blocked/damaged venting system.
g. Air distribution baffle removed (high
temperature rise units only).
h. Defective high limit switch.
2. Main pressure set too low.
3. Too much outside air.
4. Thermostat malfunction.
5. Gas controls wired incorrectly.
6. Unit undersized.
1.
a. Clean/correct duct system.
b. Adjust to a maximum of 14" W.C.
c. Check/correct to insure blower motor
operates within 45 seconds of when
- gas controls are energized.
d. Adjust belt tension.
e. Check/correct blower drive settings for
proper rpm.
f. Check/correct venting system.
g. Replace air distribution baffle.
h. Replace high limit switch.
2. Adjust main gas pressure.
Minimum for Natural Gas — 6" W.C.
Minimum for Propane Gas — 11" W.C.
3. Adjust outside air damper to decrease
outside air percentage (if possible).
4. Check/replace thermostat.
5. Check unit wiring against the wiring
diagram.
6. Check design conditions. If unit is
undersized, an additional unit(s) or other
heat source must be added.
Too Much Heat
1. Thermostat malfunction.
2. Gas controls do not shut-off.
a. Gas controls wired incorrectly.
b. Short circuit.
3. Main gas pressure set too high.
4. Defective gas valve.
➀ Automatic Reset High Limit
The duct furnace comes standard with an automatic reset high
limit switch that will shut-off the gas should the discharge air
temperature become excessive. See Figure 14.1, indicator ➆ for
the location of either the standard automatic or optional manual
reset high limit switch. The switch should operate only when
something is seriously wrong with the unit operation. Anytime
the switch operates, correct the difficulty immediately or serious
damage may result. If the switch cuts off the gas supply during
normal operation, refer to the “Not Enough Heat” section of
Service & Troubleshooting.
1. Check/replace thermostat.
2. a. Check unit wiring against the wiring
diagram.
b. Check for loose or worn wires.
3. Adjust to a maximum of 14" W.C.
4. Replace gas valve.
Figure 51.1
Lifting Flame Condition
Figure 51.2
Floating Flame Condition
Figure 51.3
Flame Rollout Appearance
5-565.151
MODEL DESIGNATIONS
Modine Manufacturing Company
1500 DeKoven Ave., Racine, WI 53403
Phone: 800.828.4328
I
C
B
A
D"
Access
Slide
Model Identification
Duct furnace/make-up air units contain an ETL/ETL Canada
certified indoor duct furnace. This duct furnace is combined with
either a blower section or a blower and cooling section to make
a complete make-up air or heating/ventilating/ cooling unit that
is ETL/ETL Canada certified. For this reason, two identification
plates are used on these models. The Serial Plate is used
to identify the duct furnace and its components. The Model Identification Plate is used to identify the complete model,
including blower and cooling sections.
Figure 52.1 - Serial Plate
Ordering
When servicing, repairing or replacing parts on these units,
locate the model identification plate of the unit and always give
the complete Model Number and Serial Number from the model
identification plate. The model identification plate is located on
the door of the electrical control box or on the side of unit. The
part number for some common replacement parts are listed on
the serial plate (See Figure 52.1) and the model identification
plate (See Figure 53.1). For a complete description of the model
number, see Model Identification.
5-565.152
MODEL DESIGNATIONS
Figure 53.1 - Model Identification Plate
DBP 75AFRHN10A1AA1AAA1A
115/208-23060
115
60
18.4710.00
Modine Manufacturing Company
1500 DeKoven Ave., Racine, WI 53403
Phone: 800.828.4328
1
01101010109-0002
6.6/3.0-3.3
9F202185H63081-205H76183-31
5H71790-5H58064-3
Figure 53.2 - Serial Number DesignationFigure 53.3 - Serial Number Designations
101 01 02 - 1000
SERIES IDENTITY
NUMBER
Identifies which series
of controls were
furnished on the unit.
SEQUENCE
NUMBER
YEAR OF
MANUFACTURE
01 – 2001
02 – 2002
etc.
WEEK OF
MANUFACTURE
01 – 1st week of year
26 – 26th week of year
01 10 201 01 02 - 1000
MOTOR
VENDOR CODE
01 – Century
15 – Marathon
etc.
FAN OR BLOWER
VENDOR CODE
10 – Lau
20 – Morrison
etc.
SERIES IDENTITY
NUMBER
Identifies which series
of controls were
furnished on the unit.
Serial Number Designations
SEQUENCE
NUMBER
YEAR OF
MANUFACTURE
01 – 2001
02 – 2002
etc.
WEEK OF
MANUFACTURE
01 – 1st week of year
26 – 26th week of year
5-565.153
START-UP CHECKLIST
INDIRECT GAS-FIRED HEATING EQUIPMENT
Job Name: Date:
Address: Model No.:
City & State: Order No.:
Start-Up Check List “ALL ITEMS MUST BE CHECKED” Serial No.:
1. All shipping straps, braces, tie downs removed? ____ Yes ___ No
2. Unit installed level and secure? ____ Yes ___ No
3. Gas burner properly located and aligned? ____ Yes ___ No
4. Blower and motor alignment okay? ____ Yes ___ No
5. Bearings aligned and tight on shaft/bearing supports? ____ Yes ___ No
6. Electrical connections checked and secure? ____ Yes ___ No
7. Gas piping checked and tightened if necessary? ____ Yes ___ No
8. Any visible damage to unit? ____ Yes ___ No
Describe: ______________________________________________
If damaged, was the damage repaired? ____ Yes ___ No
9. Air inlet and discharge checked for obstructions? ____ Yes ___ No
10. Bearings checked for proper lubrication? ____ Yes ___ No
11. Filters in place and correct to direction of air flow? ____ Yes ___ No
12. Belt tension checked? ____ Yes ___ No
13. Electric supply to unit: ______ Volts, ______ Hz, ______ Phase
14. Gas supply to unit: ______ Natural, ______ Propane
15. Gas supply pressure to unit: ______ " W.C., ______ PSIG
23. High temperature limit control continuity checked? ____ Yes ___ No
24. Burner light off
Low Fire: Does entire burner light off? ____ Yes ___ No
Hi Fire: Burner pressure reading? ______ " W.C.
Is flame clean and stable? ____ Yes ___ No
Does flame modulate in response to temperature control(s)? ____ Yes ___ No
25. Gas input checked? ____ Yes ___ No
Input at maximum firing rate: __________ Btu/Hr
Input at minimum firing rate: -__________ Btu/Hr
26. Gas piping checked for and free of leaks? ____ Yes ___ No
27. Has wiring been verified to match the unit wiring diagram? ____ Yes ___ No
28. Have all the modes of the sequence of operation been verified and tested? ____ Yes ___ No
29. What optional and/or accessory control devices have been set?
Device: _______________ Setting: ___________ (°F/psi/Inches W.C./etc.) ____ Yes ___ No
Device: _______________ Setting: ___________ (°F/psi/Inches W.C./etc.) ____ Yes ___ No
Device: _______________ Setting: ___________ (°F/psi/Inches W.C./etc.) ____ Yes ___ No
Customer/Owner instructed in operation and maintenance of unit? ____ Yes ___ No
Name of Person(s) Instructed: ______________________________________________________________
4 - No Switches (Standard) 1 - Low Gas Pressure Switch (Premium)
0 - No Switches (Premium) 2 - High Gas Pressure Switch (Premium)
3 - High and Low Gas Pressure Switch (Premium)
14 - Supply Voltage (SV)
A - 115/60/1 E - 230/60/3
B - 208/60/1 F - 460/60/3
C - 230/60/1 G - 575/60/3
D - 208/60/3
15 - Transformer (TR)
1 - 40 VA 4 - 250 VA
2 - 75 VA 0 - None
3 - 150 VA
16 - Blower Size & Bearing Type (BB)
A - 9-7 Spider Bearings G - 15-15 Spider Bearings
B - 9-7 Pillow Block Bearings H - 15-15 Pillow Block Bearings
C - 9-9 Spider Bearings I - 18-18 Spider Bearings under 15 Hp
D - 9-9 Pillow Block Bearings J E - 12-12 Spider Bearings K F - 12-12 Pillow Block Bearings L - 20-18 Pillow Block Bearings
17 - Motor Horsepower (HP)
A - 1/3 Hp L - 1/3 Hp with Motor Starter
B - 1/2 Hp M - 1/2 Hp with Motor Starter
C - 3/4 Hp N - 3/4 Hp with Motor Starter
D - 1 Hp P - 1 Hp with Motor Starter
E - 1-1/2 Hp Q - 1-1/2 Hp with Motor Starter
F - 2 Hp R - 2 Hp Hp with Motor Starter
G - 3 Hp S - 3 Hp with Motor Starter
H - 5 Hp T - 5 Hp with Motor Starter
I - 7-1/2 Hp W - 7-1/2 Hp with Motor Starter
J - 10 Hp X - 10 Hp with Motor Starter
K - 15 Hp Y - 15 Hp with Motor Starter
V - 20 Hp Z - 20 Hp with Motor Starter
18 - Motor Type (MT)
1 - ODP 5 - TE
2 - ODP - High Eff. 6 - TE - High Eff.
3 - ODP, 1800/900 RPM 7 - TE, 1800/900 RPM
4 - ODP, 1800/1200 RPM 8 - TE, 1800/1200 RPM
19 - Sheave Arrangement (SA)
A - (See Sheave Tables 34.1 to 35.5)
20,21 - Air Control (AC)
AA - RA Opening
BA - FA Opening
CA - FA & RA Openings
DA - FA Dampers w/ 2 pos motor (No RA)
EA - FA & RA Dampers w/ 2 pos motor
EQ - ASHRAE Cycle I - (“EA” with Warm-up Stat)
FA - FA Damper & RA Opening w/ 2 pos motor
GA - FA & RA Mod motor w/ 0-10 Vdc External Input
GB - FA & RA Mod motor w/ 4-20 mA External Input
GC - FA & RA Mod motor w/ Minimum Position
GD - FA & RA Mod motor w/ Remote Position (On Remote Panel)
GE - FA & RA Mod motor w/ 3 pos. damper (100% RA, Variable, 100% OA)
GF - FA & RA Mod motor w/ A350P Proportional Temp Controller
GG - FA & RA Mod motor w/ Minimum Position & Prop. Temp Controller
GH - FA & RA Mod motor w/ Remote Position & Prop. Temp Controller
GJ - FA & RA Mod motor w/ FA Enthalpy Controller
GK - ASHRAE Cycle II - (“GG” with Warm-up Stat)
GM - ASHRAE Cycle II - (“GH” with Warm-up Stat)
GN - ASHRAE Cycle III - (“GF” with Warm-up Stat)
HP - FA & RA Floating motor w/ Space Pressure Controller
JA - Manual FA & RA Dampers
KA - Manual FA Damper with Return Air Opening
22 - Evaporative Cooling (EC)
0 - None
23 - Cooling Coil (CC)
0 - None
1 - Factory Installed Coil
18-18 Pillow Block Bearings under 15 Hp
18-18 Pillow Block Bearings for 15 Hp & up
5-565.155
COMMERCIAL WARRANTY
Seller warrants its products to be free from defects in material and
workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use
of materials substituted under emergency conditions for materials normally
employed. This warranty covers replacement of any parts furnished from the
factory of Seller, but does not cover labor of any kind and materials not
furnished by Seller, or any charges for any such labor or materials, whether
such labor, materials or charges thereon are due to replacement of parts,
adjustments, repairs, or any other work done. This warranty does not apply to
any equipment which shall have been repaired or altered outside the factory of
Seller in any way so as, in the judgment of Seller, to affect its stability, nor
which has been subjected to misuse, negligence, or operating conditions in
excess of those for which such equipment was designed. This warranty does
not cover the effects of physical or chemical properties of water or steam or
other liquids or gases used in the equipment.
BUYER AGREES THAT SELLER’S WARRANTY OF ITS PRODUCTS TO
BE FREE FROM DEFECT IN MATERIAL AND WORKMANSHIP, AS LIMITED
HEREIN, SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER
WARRANTIES, EITHER EXPRESS OR IMPLIED, WHETHER ARISING
FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE,
THERE ARE NO OTHER WARRANTIES, INCLUDING WARRANTY OF
MERCHANTABILITY OR FITNESS FOR PURPOSE, WHICH EXTEND
BEYOND THE PRODUCT DESCRIPTION CONFIRMED BY BUYER AND
SELLER AS OF THE DATE OF FINAL AGREEMENT.
This warranty is void if the input to the product exceeds the rated input as
indicated on the product serial plate by more than 5% on gas-fired and oil-fired
units, or if the product in the judgment of SELLER has been installed in a
corrosive atmosphere, or subjected to corrosive fluids or gases, been
subjected to misuse, negligence, accident, excessive thermal shock, excessive
humidity, physical damage, impact, abrasion, unauthorized alterations, or
operation contrary to SELLER’S printed instructions, or if the serial number has
been altered, defaced or removed.
BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL
OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR
REPLACEMENT AT THE FACTORY OF SELLER, ANY COMPONENT WHICH
SHALL, WITHIN THE APPLICABLE WARRANTY PERIOD DEFINED HEREIN
AND UPON PRIOR WRITTEN APPROVAL, BE RETURNED TO SELLER
WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE
EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE;
EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A
COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER,
BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE
LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. FOR
GAS-FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS
AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS, BUYER’S
REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO TEN
YEARS FROM DATE OF SHIPMENT FROM SELLER.
These warranties are issued only to the original owner-user and cannot be
transferred or assigned. No provision is made in these warranties for any
labor allowance or field labor participation. Seller will not honor any expenses
incurred in its behalf with regard to repairs to any of Seller’s products. No
credit shall be issued for any defective part returned without proper written
authorization (including, but not limited to, model number, serial number, date
of failure, etc.) and freight prepaid.
OPTIONAL SUPPLEMENTAL WARRANTY
Provided a supplemental warranty has been purchased, Seller extends the
warranty herein for an additional four (4) years on certain compressors.
Provided a supplemental warranty has been purchased, Seller extends the
warranty herein for an additional four (4) years or nine (9) years on certain
heat exchangers.
EXCLUSION OF CONSUMABLES & CONDITIONS BEYOND
SELLER’S CONTROL
The above referenced warranty shall not be applicable to any of the following
items: refrigerant gas, belts, filters, fuses and other items consumed or worn
out by normal wear and tear or conditions beyond Seller’s control, including
(without limitation as to generality) polluted or contaminated or foreign matter
contained in the air or water utilized for heat exchanger (condenser) cooling or
if the failure of the part is caused by improper air or water supply, or improper
or incorrect sizing of power supply.
Component
Applicable Models
Heat Exchangers
Gas-Fired Units except PSH/BSH
Heat Exchangers
Low Intensity Infrared Units
Compressors
Condensing Units for Cassettes
Burners
Low Intensity Infrared Units
Other
Components excluding Heat Exchangers,
Coils, Condensers, Burners, Sheet Metal
Heat Exchangers/Coils
Indoor and Outdoor Duct Furnaces and
System Units, PSH/BSH, Steam/Hot Water Units,
Oil-Fired Units, Electric Units, Cassettes,
Vertical Unit Ventilators
Compressors
Vertical Unit Ventilators
Burners
High Intensity Infrared Units
Sheet Metal Parts
All Products
TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE
HUNDRED TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER
OCCURS FIRST
FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN SIXTY-SIX
MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
EIGHTEEN MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
“APPLICABLE WARRANTY PERIOD”
As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.