Modine Manufacturing BTS Service Manual

6-561.11
5H0801060000
September, 2018
INSTALLATION AND SERVICE MANUAL
separated combustion gas-fired unit heaters
model PTS and BTS
All models approved for use in California by the CEC and in Massachusetts. Unit heater is certified for non-residential applications.
FOR YOUR SAFETY
The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
W ARNING
1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death, and could cause exposure to substances which have been determined by various state agencies to cause cancer, birth defects, or other reproductive harm. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
2. Do not locate ANY gas-fired units in areas where chlorinated, halogenated, or acidic vapors are present in the atmosphere. These substances can cause premature heat exchanger failure due to corrosion, which can cause property damage, serious injury, or death.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS:
1. Open windows.
2. Do not try to light any appliance.
3. Do not touch any electrical switch; do not use any phone in your building.
4. Extinguish any open flame.
5. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you can not reach your gas supplier, call your fire department.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
IMPOR T ANT
The use of this manual is specifically intended for a qualified installation and service agency. All installation and service of these units must be performed by a qualified installation and service agency.
Inspection on Arrival
1. Inspect unit upon arrival. In case of damage, report it immediately to transportation company and your local Modine sales representative.
2.
Check rating plate on unit to verify that power supply meets
3. Inspect unit upon arrival for conformance with description of product ordered (including specifications where applicable).
Table of Contents
Inspection on Arrival ................................. 1
Special Precautions ................................. 2
SI (Metric) Conversion Factors ........................ 3
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Unit Location ...................................... 4
Combustible Material and Service Clearances .......... 4
Unit Mounting .................................... 5
Installation ........................................ 6
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Gas Connections .................................11
High-Altitude Accessory Kit ........................ 12
Electrical ...................................... 13
Installation with Ductwork.......................... 15
Requirements/Adjustments and Data for Blower Units.... 15
Start-Up Procedure/Operation ........................ 20
Unit Components .................................. 21
Performance Data - General ......................... 22
Performance Data - Downturn Hoods .................. 23
Dimensions....................................... 24
Service/Troubleshooting............................. 26
Model/Serial Number/Replacement Parts ............... 27
Commercial Warranty........................Back Cover
THIS MANUAL IS THE PROPERTY OF THE OWNER.
SPECIAL PRECAUTIONS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE, EFFICIENT AND TROUBLE-FREE OPERATION. IN ADDITION, PARTICULAR CARE MUST BE EXERCISED REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW. FAILURE TO PROPERLY ADDRESS THESE CRITICAL AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS, PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS ARE SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which, if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided,
MAY result in a potential safety concern.
DANGER
Appliances must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
W ARNING
1. Gas fired heating equipment must be vented - do not operate unvented.
2. A built-in power exhauster is provided - additional external power exhausters are not required or permitted.
3. If an existing heater is being replaced, it may be necessary to resize the venting systems. Improperly sized venting systems can result in vent gas leakage or the formation of condensate. Refer to the National Fuel Gas Code ANSI Z223.1 (NFPA 54) or CSA B149.1 - latest edition. Failure to follow these instructions can result in injury or death.
4. Under no circumstances should two sections of double wall vent pipe be joined together within one horizontal vent system due to the inability to verify complete seal of inner pipes.
5. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing.
6. Gas pressure to appliance controls must never exceed 14" W.C. (1/2 psi).
7. To reduce the opportunity for condensation, the minimum sea level input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or 5% below the minimum rated input of dual rated units.
8. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
9. All appliances must be wired strictly in accordance with
wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard
to persons and property.
10. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
11. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than the rated voltage.
W ARNING
12. When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacements parts list may be obtained by contacting the factory. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner's risk.
CAUTION
1. All literature shipped with this unit should be kept for future use for servicing or service diagnostics. Do not discard any literature shipped with this unit.
2. Consult piping, electrical, and venting instructions in this
manual before final installation.
3. Do not attach ductwork, air filters, or polytubes to any propeller unit heater.
4. Clearances to combustible materials are critical. Be sure to follow all listed requirements.
5. Heaters are designed for use in heating applications with ambient startup temperatures between -40°F and 90°F and ambient operating temperatures between 40°F and 90°F.
6. Do not install unit outdoors.
7. In garages or other sections of aircraft hangars such as offices and shops that communicate with areas used for servicing or storage, keep the bottom of the unit at least 7' above the floor unless the unit is properly guarded to provide user protection from moving parts. In parking garages, the unit must be installed in accordance with the standard for parking structures ANSI/NFPA 88A - latest edition, and in repair garages the standard for repair garages NFPA 30A - latest edition. In Canada, installation of heaters in airplane hangars must be in accordance with the requirements of the enforcing authority, and in public garages in accordance with the current CSA-B149 codes.
8. In aircraft hangars, keep the bottom of the unit at least 10' from the highest surface of the wings or engine enclosure of the highest aircraft housed in the hangars and in accordance with the requirements of the enforcing authority and/or NFPA 409 - latest edition (Formerly NFPA 88B).
9. Installation of units in high humidity or salt water atmospheres will cause accelerated corrosion, resulting in a reduction of the normal life of the units.
10. Do not install units below 7' measured from the bottom of the unit to the floor in commercial applications (unless unit is properly guarded to provide user protection from moving parts).
11. Be sure no obstructions block air intake and discharge of
unit heaters.
12. The minimum distance from combustible material is based on the combustible material surface not exceeding 160°F. Clearance from the top of the unit may be required to be greater then the minimum specified if heat damage, other than fire, may occur to materials above the unit heater at the temperature described.
13. Allow 18" of clearance at rear (or 12" beyond end of motor at rear of unit, whichever is greater) and access side to provide ample air for proper operation of fan.
14. Installation must conform with local building codes or in the absence of local codes, the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest edition. In Canada installation must be in accordance with CSA-B149.1.
15. The concentric vent adapter box must be installed inside of the structure or building. Do not install this box on the exterior of a building or structure.
2
6-561.11
SPECIAL PRECAUTIONS / SI (METRIC) CONVERSION FACTORS
BEFORE YOU BEGIN
CAUTION
16. Purging of air from gas supply line should be performed as described in the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest edition. In Canada, installation must be in accordance with CSA-B149.1.
17. When leak testing the gas supply piping system, the appliance and its combination gas control must be isolated during any pressure testing in excess of 14" W.C. (1/2 psi).
18. The unit should be isolated from the gas supply piping system by closing its field installed manual shut-off valve. This manual shut-off valve should be located within 6' of the heater.
19. Turn off all gas before installing appliance.
20. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is less than 5% below the rated voltage.
21. Check the gas inlet pressure at the unit upstream of the
combination gas control. The inlet pressure should be 6-7" W.C. on natural gas or 12-14" W.C. on propane. If inlet pressure is too high, install an additional pressure regulator upstream of the combination gas control.
22. Service or repair of this equipment must be performed by a qualified service agency.
23. Do not attempt to reuse any mechanical or electronic ignition controller which has been wet. Replace defective controller.
IMPOR T ANT
1. To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated, or acidic) are present in the atmosphere.
2. To prevent premature heat exchanger failure, the input to the appliance as indicated on the serial plate must not exceed the rated input by more then 5%.
3. To prevent premature heat exchanger failure, observe
heat exchanger tubes. If the tubes become red while blower and furnace are in operation, check to be sure the blower has been set to the proper rpm for the application. Refer to page 15 for Blower Adjustments.
4. Start-up and adjustment procedures should be performed
by a qualified service agency.
5. To check most of the Possible Remedies in the trouble- shooting guide listed in Table 26.1 refer to the applicable sections of the manual.
1. All literature shipped with this unit should be kept for future use for servicing or service diagnostics. Leave manual with the owner. Do not discard any literature shipped with this unit.
2. Consult piping, electrical, and venting instructions in this
manual before final installation.
3. Do not attach ductwork, air filters, or polytubes to any
propeller unit heater.
In the U.S., the installation of these units must comply with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest edition and other applicable local building codes. In Canada, the installation of these units must comply with local plumbing or waste water codes and other applicable codes and with the current code CSA-B149.1.
1. All installation and service of these units must be performed by a qualified installation and service agency only as defined in ANSI Z223.1 (NFPA 54) - latest edition or in Canada by a licensed gas fitter.
2. This unit is certified with the controls furnished. For replacements parts, please order according to the replacement parts list on serial plate. Always know your model and serial numbers. Modine reserves the right to substitute other authorized controls as replacements.
3. Unit is balanced for correct performance. Do not alter fan
or operate motors at speeds below what is shown in this manual.
4. Information on controls is supplied separately.
5. The same burner is used for natural and propane gas.
SI (Metric) Conversion Factors
To Convert Multiply By To Obtain
°F (°F-32) x 5/9 °C BTU 1.06 kJ Btu/ft3 37.3 kJ/m Btu/hr 0.000293 kW CFH (ft3/hr) 0.000472 m3/min CFH (ft3/hr) 0.00000787 m3/s CFM (ft3/min) 0.0283 m3/min CFM (ft3/min) 0.000472 m3/s feet 0.305 m Gal/Hr. 0.00379 m3/hr Gal/Hr. 3.79 l/hr gallons 3.79 l Horsepower 746 W inches 25.4 mm pound 0.454 kg psig 6.89 kPa psig 27.7 "W.C.
"W.C. 0.249 kPa
CAUTION
3
6-561.11
3
UNIT LOCATION
UNIT LOCATION
DANGER
Appliances must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
CAUTION
1. Clearances to combustible materials are critical. Be sure to follow all listed requirements.
2. Heaters are designed for use in heating applications with ambient startup temperatures between -40°F and 90°F, and ambient operating temperatures between 40°F and 90°F.
3. Do not install unit outdoors.
4. In garages or other sections of aircraft hangars such
as offices and shops that communicate with areas used for servicing or storage, keep the bottom of the unit at least 7' above the floor unless the unit is properly guarded. In parking garages, the unit must be installed in accordance with the standard for parking structures ANSI/NFPA 88A - latest edition, and in repair garages the standard for repair garages NFPA 30A - latest edition (Formerly NFPA 88B). In Canada, installation of heaters in airplane hangars must be in accordance with the requirements of the enforcing authority, and in public garages in accordance with the current CSA-B149 codes.
5. In aircraft hangars, keep the bottom of the unit at least
10' from the highest surface of the wings or engine enclosure of the highest aircraft housed in the hangars
and in accordance with the requirements of the enforcing authority and/or NFPA 409 - latest edition.
6. Installation of units in high humidity or salt water
atmospheres will cause accelerated corrosion resulting in a reduction of the normal life of the units.
Figure 4.1 - Combustible Material and Service Clearances
TOP
NON
ACCESS
SIDE
BOTTOM
ACCESS
SIDE
Table 4.1 - Clearances
Combustible Materials Service Clearance
Top and Bottom 6" 18" Access Side 6" 18" Non-Access Side 6" 18" Rear 18" 18" Vent Connector 6" 18"
6. Do not install units in locations where gas ignition system is exposed to water spray, rain, or dripping water.
7. Mounting height (measured from bottom of unit) at which unit heaters are installed is critical. Refer to mounting height and heat throw data on page 22 of this manual. The maximum mounting height for any unit is that height above which the unit will not deliver heated air to the floor.
Clearance To Recommended
Unit Side
IMPOR T ANT
To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acidic) are present in the atmosphere.
Location Recommendations
1. When locating the heater, consider general space and heating requirements, availability of gas and electrical supply, and proximity to vent locations.
2. When locating units, it is important to consider that the combustion air and exhaust vent piping must be connected to the outside atmosphere. Vent terminals should be located adjacent to one another. Maximum equivalent vent lengths are listed in “Section A - General Instruction - All Units” of the Venting instructions.
3. Be sure the structural support at the unit location site is adequate to support the unit's weight. Refer to pages 24-25 for unit weights. For proper operation the unit must be installed in a level horizontal position.
4. Do not install units in locations where the flue products can be drawn into the adjacent building openings such as windows, fresh air intakes, etc.
5. Be sure that the minimum clearances to combustible materials and recommended service clearances are maintained. Units are designed for installation with the minimum clearances as shown in Figure 4.1 and Table 4.1.
4
Sound and Vibration Levels
All standard mechanical equipment generates some sound and vibration that may require attenuation. Libraries, private offices and hospital facilities will require more attenuation, and in such cases, an acoustical consultant may be retained to assist in the application. Locating the equipment away from the critical area is desirable within ducting limitations. Generally, a unit should be located within 15' of a primary support beam. Smaller deflections typically result in reduced vibration and noise transmission.
6-561.11
UNIT MOUNTING
1. Be sure the means of suspension is adequate to support the weight of the unit (see pages 24-25 for unit weights).
2. For proper operation, the unit must be installed in a level horizontal position.
3. Clearances to combustibles as specified in Table 4.1 must be strictly maintained.
4. All standard units are shipped fully boxed. Larger units are also supplied with skid supports on the bottom of the box. The larger units may be lifted from the bottom by means of a fork lift or other lifting device only if the shipping support skids are left in place and the forks support the whole depth of the unit. If the unit must be lifted from the bottom for final installation without the carton in place, be sure to properly support the unit over its entire length and width to prevent damage. When lifting units, make sure the load is balanced.
5. Propeller models have four mounting holes and blower models have 6 mounting holes. The units can be mounted with 3/8"-16 threaded rod as follows:
 •Oneachpieceofthreadedrodused,screwanutadistance
of about 1" onto the end of the threaded rods that will be screwed into the unit heater.
 •Placeawasherovertheendofthethreadedrodandscrew
the threaded rod into the unit heater weld nuts on the top of the heater at least 5 turns, and no more than 10 turns. Tighten the nut first installed onto the threaded rod to prevent the rod from turning.
 •Drillholesintoasteelchannelorangleironatthesame
center-line dimensions as the heater that is being installed. The steel channels or angle iron pieces need to span and be fastened to appropriate structural members.
 •Cutthethreadedrodstothepreferredlength,placethem
through the holes in the steel channel or angle iron and secure with washers and lock nuts or lock washers and nuts. A double nut arrangement can be used here instead of at the unit heater (a double nut can be used both places but is not necessary).
 •Donotinstallstandardunitheatersabovethemaximum
mounting height shown in Tables 22.1 or 22.2.
NOTE: A pipe hanger adapter kit, as shown in Figure 5.1, is
available as an accessory. One kit consists of two drilled 3/4" IPS pipe caps and two 3/8" - 16 x 1-3/4" capscrews to facilitate threaded pipe suspension. Two kits would be required for PTS units and 3 kits for BTS units.
Figure 5.1 - Unit Heater Suspension Methods
(Threaded Rod) (Pipe Adapter Kit)
CAUTION
1. Do not install units below 7' measured from the bottom of the unit to the floor in commercial applications (unless unit is properly guarded to provide user protection from moving parts).
2. Be sure no obstructions block air intake and discharge
of unit heaters.
3. The minimum distance from combustible material is
based on the combustible material surface not exceeding 160°F. Clearance from the top of the unit may be required to be greater than the minimum specified if heat damage, other than fire, may occur to materials above the unit heater at the temperature described.
4. Allow 18" clearance at rear (or 12" beyond end of motor
at rear of unit, whichever is greater) and access side to provide ample air for proper operation of fan.
6-561.11
5
INSTALLATION - VENTING
W ARNING
1. Gas fired heating equipment must be vented - do not operate unvented.
2. A built-in power exhauster is provided - additional external power exhausters are not required or permitted.
3. If an existing heater is being replaced, it may be necessary to resize the venting systems. Improperly sized venting systems can result in vent gas leakage or the formation of condensate. Refer to the National Fuel Gas Code ANSI Z223.1 (NFPA 54) or CSA B149.1 - latest edition. Failure to follow these instructions can result in serious injury or death.
4. Under no circumstances should two sections of double wall vent pipe be joined together within one horizontal vent system due to the inability to verify complete seal of inner pipes.
CAUTION
Installation must conform with local building codes or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest edition. In Canada installation must be in accordance with CSA B149.1.
Model PTS/BTS unit heaters must be vented with the proper passageway as described in these instructions to convey flue gases from the unit or the vent connector to the outside atmosphere. The heaters must also have a separate combustion air intake pipe to bring in fresh air for combustion from the outside atmosphere.
The venting instructions are organized in sections, based on installation type. The sections are identified as follows:
Applicable Installation Instructions
Instructions by Vent System Type
A General Instructions for ALL installations
B VERTICAL 2-PIPE vent systems C HORIZONTAL 2-PIPE vent systems
vent systems
The differences between vertical and horizontal vent systems in 2-Pipe or
HORIZONTAL AND VERTICAL CONCENTRIC
D
concentricventcongurationswillbeidentiedin“SectionA-General
Instructions – All Units”.
A3. All heaters come with factory installed vent and combustion
air adapters for attaching the vent pipe to the heater:
Table 6.1 - Vent Pipe Diameters, Transitions, and Total Equivalent Vent Pipe Lengths For Horizontal and Vertical Venting Systems
Equivalent Vent Length
Minimum Maximum
Model
Size
150
175-200 250-400
Vent Pipe Diameter
4" 5' 25' 4" 5' 50'
6" 5' 50'
Attach the vent pipe to the adapter with 3 corrosion-
resistant screws (Drill pilot holes through the vent pipe and adapter prior to screwing in place). Vent pipe must not be smaller than the connector size.
A4. Refer to Table 6.1 for total equivalent vent pipe lengths,
making the vent system as straight as possible. The equivalent length of a 4" elbow is 5' and for a 6" elbow is 7'.
A5. Horizontal sections of vent pipe are to be installed with a
minimum downward slope from the appliance of 1/4 inch per foot and suspended securely from overhead structures at points not greater than 3' apart.
A6. Fasten individual lengths of vent together with at least three
corrosion resistant sheet metal screws.
A7. Keep single wall vent pipe at least 6" from combustible
materials. For double wall vent pipe, follow the vent pipe manufacturer’s clearances to combustibles. The minimum distance from combustible materials is based on the combustible material surface not exceeding 160°F. Clearance from the vent pipe (or the top of the unit) may be required to be greater than 6" if heat damage other than fire could result (such as material distortion or discoloration).
A8. Avoid venting through unheated space when possible.
When venting does pass through an unheated space or if the unit is installed in an environment that promotes condensation, insulate runs greater than 5' to minimize condensation. Inspect for leakage prior to insulating and use
insulation that is noncombustible with a rating of not
Figure 6.1 - Venting Through Combustible Roof or Wall
Single Wall Vent Pipe
Flashing
Double Wall Vent Pipe
Specified Terminal
Specified Terminal
Flashing
Section A - General Instructions - All Units
A1. If the unit heater being installed is replacing existing
equipment and using the existing vent system from that equipment, inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) or CSA B149.1 Installation Code ­latest edition and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
A2. The vent pipe should be galvanized steel or other suitable
corrosion resistant material. Follow the National Fuel Gas Code for minimum thickness of vent material. The minimum thickness for connectors varies depending on the pipe diameter. Do not vent unit with PVC or other forms of plastic venting material.
6
Listed Thimble
Single Wall
Single Wall Vent Pipe Terminating with Double wall vent pipe.
Clearance Specified by Type B Vent Mfg.
Single Wall Vent Pipe
Listed Thimble
See Instruction A12 for attaching single wall pipe to double wall pipe.
6-561.11
Clearance Specified by Type B Vent Mfg.
Double Wall
Specified
Terminal
Single Wall
Specified
Terminal
INSTALLATION - VENTING
less than 400°F. Install a tee fitting at the low point of the
vent system and provide a drip leg with a clean out cap as shown in Figure 8.1.
A9. When the vent passes through a combustible INTERIOR
wall or floor, a metal thimble 4" greater than the vent diameter is necessary. If there is 6' or more of vent pipe in the open space between the appliance and where the vent pipe passes through the wall or floor, the thimble need only be 2" greater than the diameter of the vent pipe. If a thimble is not used, all combustible material must be cut away to provide 6" of clearance. Where authorities have jurisdiction, Type B vent may be used for the last section of vent pipe to maintain clearance to combustibles while passing through wall or floor (see Figure 6.1). Any material used to close the opening must be noncombustible.
A10. Seal all seams and joints of un-gasketed single wall pipe
with metal tape or Silastic suitable for temperatures up to 400°F. Wrap the tape 2 full turns around the vent pipe. One continuous section of double wall vent pipe may be used within the vent system to pass through the wall to the listed vent cap. Refer to instruction A12 in “Section A – General Instructions – All Units” for attaching double wall pipe to single wall pipe.
A11. The following are General Instructions for Double Wall
(Type B) Terminal Pipe Installation:
How to attach a single wall vent terminal to double wall
(Type B) vent pipe:
1. Look for the “flow” arrow on the vent pipe.
2. Slide the vent terminal inside the exhaust end of the double wall vent pipe.
3. Drill 3 holes through the pipe and the vent terminal. Using 3/4" long sheet metal screws, attach the cap to the pipe. Do not over tighten.
How to connect a single wall vent system to a double wall
(Type B) vent pipe:
1. Slide the single wall pipe inside the inner wall of the double wall pipe.
2. Drill 3 holes through both walls of the single and double wall vent pipes. Using 3/4" sheet metal screws, attach the 2 pieces of pipe. Do not overtighten.
3. The gap between the single and double wall pipe must be sealed but it is not necessary to fill the full volume of the annular area. To seal, run a large bead of 400°F silastic around the gap.
Table 7.1 - Vent Termination Clearances
Minimum Clearances for Structure Vent Terminal Location
Forced air inlet within 10 feet 3 feet above Combustion air inlet of another
appliance Door, window, gravity air inlet, 4 feet horizontal and below
or any building opening 1 foot above Electric meter, gas meter, gas 4 feet horizontal (U.S.)
regulator, and relief equipment  6 feet horizontal (Canada)
Gas regulator 6 feet horizontal (Canada)
Adjoining building or parapet wall 6 feet all directions Adjacent public walkways 7 feet all directions
Grade (ground level) 3 feet above
Do not terminate the vent directly above a gas meter or regulator.
3 feet horizontal (U.S.)
6 feet all directions
A12. Vent termination clearances must be maintained: A13. Do NOT vent this appliance into a masonry chimney. A14. Do NOT use dampers or other devices in the vent or
combustion air pipes.
A15. The venting system must be exclusive to a single
appliance and no other appliance is allowed to be vented into it.
A16. Precautions must be taken to prevent degradation of
building materials by flue products.
A17. Single wall vent pipe must not pass through any
unoccupied attic, inside wall, concealed space, or floor.
A18. Uninsulated single wall vent pipe must not be used
outdoors for venting appliances in regions where the 99% winter design temperature is below 32°F.
A19. Long runs of horizontal or vertical combustion air pipes
may require insulation in very cold climates to prevent the buildup of condensation on the outside of the pipe where the pipe passes through conditioned spaces.
A20. Vertical combustion air pipes should be fitted with a tee
with a drip leg and a clean out cap to prevent against the possibility of any moisture in the combustion air pipe from entering the unit. The drip leg should be inspected and cleaned out periodically during the heating season.
A21. The vent terminal must be:
Table 7.2 - Vent Terminals
Model Size Modine PN Other Listed Terminals
150-200 5H0722850001 Gary Steel 1092
250-400 5H0722850002 Gary Steel 1092
A22. In addition to following these general instructions, specific
instructions for vertical and horizontal vent systems in 2-Pipe or concentric vent configurations must also be followed. The following outlines the differences:
Vertical Category III Vent System Determination
  • Verticalventsystemsterminatevertically(up)
(an example is shown in Figure 8.1).
  • Determinetheventingconfigurationasfollows:
> For two building penetrations through the wall or roof
(one for the combustion air inlet pipe and one for the vent pipe), proceed to “Section B - Vertical 2-Pipe Venting".
> For a single larger building penetration through the
wall or roof, through which both the combustion air inlet and vent pipes will pass, proceed to “Section D ­Horizontal and Vertical Concentric Venting".
> For all other cases, proceed to the next section for
Horizontal Vent System Determination.
Horizontal Category III Vent System Determination
  • Horizontalventsystemsterminatehorizontally
(sideways) (an example is shown in Figure 8.2).
  • Determinetheventingconfigurationasfollows:
> For 2 building penetrations through the wall or roof
(1 for the combustion air inlet pipe and 1 for the vent pipe), proceed to “Section C - Horizontal 2-Pipe Venting".
> For a single larger building penetration through the
wall or roof, through which both the combustion air inlet and vent pipes will pass, proceed to “Section D ­Horizontal and Vertical Concentric Venting".
6-561.11
7
INSTALLATION - VENTING
Section B - Vertical 2-Pipe Vent System Installation
B1. This section applies to vertically vented 2-pipe
(1 combustion air inlet pipe and 1 vent pipe) vent systems and is in addition to “Section A - General Instructions -
All Units”. B2. Vertical vent systems terminate vertically (up). B3. It is recommended to install a tee with drip leg and clean
out cap as shown in Figure 8.1. B4. The combustion air and vent pipes must be terminated with
2 listed vent caps. B5. Vertical vents must terminate a minimum horizontal and
vertical distance from roof lines and adjacent walls or
obstructions. These minimum distances are outlined in
Figure 8.1 and Table 8.1. B6. The vent must terminate at least 1' above and 6"
horizontally from the combustion air inlet. B7. Once venting is complete, proceed to section titled
“Installation - Gas Connections".
Figure 8.1 - Vertical 2-Pipe Vent System
LISTED TERMINAL
4" MIN
EXHAUST
COMBUSTION AIR
12" MIN
6" MIN
"H" MIN*
"H" MIN*
(SEE TABLE 8.1)
TEE WITH DRIP LEG AND CLEANOUT CAP
(SLOPE 1/4" PER FOOT DOWNWARD TOWARD DRIP LEG)
TERMINAL
ROOF FLASHING
* SIZE ACCORNING TO EXPECTED SNOW DEPTH.
ROOF FLASHING
X
ROOF PITCH IS:
X / 12
USE LISTED THIMBLE THROUGH ROOF AND CEILING
BACK VIEW
TO WALL OR ADJOINING BUILDING
2' MIN
TERMINAL
USE THIMBLE THROUGH
CELLING
12
RECOMMENDED
12" MIN
12" MIN*
4" MIN
EXHAUST
Table 8.1 - Minimum Height from Roof to Lowest Discharge Opening
Rise X (in) Roof Pitch Min Height H (ft) 0-6 Flat to 6/12 1.00
6-7 6/12 to 7/12 1.25 7-8 7/12 to 8/12 1.50 8-9 8/12 to 9/12 2.00 9-10 9/12 to 10/12 2.50 10-11 10/12 to 11/12 3.25 11-12 11/12 to 12/12 4.00 12-14 12/12 to 14/12 5.00 14-16 14/12 to 16/12 6.00 16-18 16/12 to 18/12 7.00 18-20 18/12 to 20/12 7.50 20-21 20/12 to 21/12 8.00
Size according to expected snow depth.
Section C - Horizontal 2-Pipe Vent System Installation
C1. This section applies to horizontally vented 2-pipe vent
systems (1 combustion air inlet pipe and 1 vent pipe) and is in addition to “Section A - General Instructions - All Units”. Category III vent systems listed by a nationally recognized agency and matching the diameters specified may be used. Different brands of vent pipe materials may not be intermixed. Under no circumstances should two sections of double wall vent pipe be joined together within one horizontal vent system due to the inability to verify complete seal of
inner pipes. C2. Horizontal vent systems terminate horizontally (sideways). C3. All horizontal vents must be terminated with a listed vent
cap. The cap must terminate a minimum distance from the
external wall, as summarized in Figure 8.2. C4. The termination of horizontally vented system must extend
16" beyond the exterior surface of an exterior wall. C5. The combustion air pipe must be a minimum of 12" below
the vent pipe, and 6" from the exterior wall. C6. Construct the vent system as shown in Figure 8.2.
Figure 8.2 - Horizontal Venting with Downward Pitch
ADJACENT BUILDING
2' MIN
6" MIN
LISTED TERMINAL
SUPPORT BRACKET
12"
4" MIN
EXHAUST
COMBUSTION AIR
TEE WITH DRIP LEG AND CLEANOUT CAP AT LOW POINT OF VENT SYSTEM
SLOPE 1/4" PER FOOT DOWNWARD FROM UNIT
COMBUSTION AIR
12" MIN
RECOMMENDED
TEE WITH DRIP LEG AND CLEANOUT CAP
(SLOPE 1/4" PER FOOT DOWNWARD TOWARD DRIP LEG)
8
6-561.11
INSTALLATION - VENTING
C7. When horizontal vents pass through a combustible wall
(up to 22" thick), the vent passage must be constructed and insulated as shown in Figure 9.1.
C8. The vent must be supported as shown in Figure 9.1.
Figure 9.1 - Exhaust Vent Construction Through Combustible Walls and Support Bracket
METAL FACE
PLATE
45
1"
FIBER GLASS
INSULATION
MIN. 2"
1"
9"
9"
VENT TERMINATION SUPPORT BRACKET
(where required)
(Make from 1" x 1" steel angle)
METAL
SLEEVE
2" MIN.
VENT PIPE
DIAMETER
METAL
SLEEVE
2" MIN.
C9. When condensation may be a problem, the vent system
shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard, or could be detrimental to the operation of regulators, relief openings, or other equipment.
C10. Maintain a 1/4" per foot downward slope away from the
heater and place a drip leg with clean out near the exit of the vent as shown in Figure 8.2, or allow the condensate to drip out the end.
C11. For a vent termination located under an eave, the
distance of the overhang must not exceed 24". The clearance to combustibles above the exterior vent must be maintained at a minimum of 12". Consult the National Fuel Gas Code for additional requirements for eaves that have ventilation openings.
C12. Once venting is complete, proceed to section titled
“Installation - Gas Connections”.
Figure 9.2 - Vertical Concentric Vent Kit Components
Outlet Vent
Combustion Air Inlet Terminal
Concentric Vent Adapter Box
Combustion Air Exhaust
6" Min.
12" Min.*
Termination Cap
* Size according
to expected snow depth.
Building Roof / Ceiling
Figure 9.3 - Horizontal Concentric Vent Kit Components
CAUTION
The concentric vent adapter box must be installed inside of the structure or building. Do not install this box on the exterior of a building or structure.
Section D - Concentric Vent System Installation
D1. This section applies to both horizontally and vertically
vented concentric vent systems as defined in “Section A – General Instructions – All Units”, and is in addition to the instructions in that section.
D2. When utilizing the concentric vent option, it should have
been predetermined whether the appliance will be horizontally or vertically vented. Before proceeding, verify that the concentric vent kit received contains the correct components for the installation:
For Vertically Vented Units (Refer to Figure 9.2):
Concentric adapter assembly (same for horizontal and
vertical kits) Standard listed vent cap Specially designed inlet terminal (part #5H0751540001)
For Horizontally Vented Units (Refer to Figure 9.3):
Concentric adapter assembly (same for horizontal and
vertical kits) Special vent termination cap (part #5H0751500001)
Special inlet air guard
D3. Once the kit contents have been verified as correct for the
direction of venting, the concentric vent adapter box is to be installed. Determine the location of the box. Be sure to maintain all clearances as listed in these instructions.
D4. The adapter box is to be mounted on the interior side of
the building. It must not be mounted outside the building. The adapter box has integral mounting holes for ease of installation.
D5. The adapter box can be mounted flush to the wall (for
horizontal kits) or to the ceiling (for vertical kits). The box can also be offset from the wall or ceiling by using field supplied brackets. When mounting the box, consider serviceability and access to the vent and combustion air pipes. If the box is to be mounted using field supplied brackets, these brackets must be strong enough to rigidly secure the box to the wall or ceiling, and should be made from corrosion resistant material.
D6. Determine the length of the vent pipe and combustion air
inlet pipe for the selected location. THE VENT PIPE WILL PASS THROUGH THE CONCENTRIC VENT BOX. THE LAST SECTION OF VENT PIPE IS A CONTINUOUS LENGTH OF DOUBLE WALL “B” VENT. See section A12 for attaching and terminating double wall pipe. Begin with pipe lengths on the concentric pipe side of the adapter box, referring to Figure 10.1. These pipes will extend through the building wall or roof as well as any added length for the thickness of the wall and the offset from any field installed brackets.
6-561.11
9
INSTALLATION - VENTING
For Vertical Concentric Vent Kits
(Refer to Figure 9.2):
•Thebottomofthecombustionairintakepipemust
terminate above the snow line, or at least 12" above the roof, whichever distance is greater.
•Thebottomoftheventcapmustterminateatleast6"
above the top of the combustion air intake cap.
For Horizontal Concentric Vent Kits
(Refer to Figure 9.3):
•Thecombustionairintakepipemustterminateatleast
1" from the wall to prevent water from running down the wall and into the pipe.
•Thebackoftheventcapmustterminateatleast
14" from the combustion air intake pipe.
D7. Cut the concentric side vent and combustion air pipes to
the proper length as determined in the previous step. See Table 10.1 for combustion air and vent pipe sizes. The pipes must be single wall galvanized or stainless steel material, except for the last section of vent pipe, which must be one continuous length of double wall B-vent extended through the concentric vent box and combustion air inlet pipe on the concentric side of the box.
NOTE - No clearance to combustible material is required for the building penetration, which should be sized according to the external combustion air Inlet pipe diameter.
D8. Allow the concentric side vent pipe to pass through the
concentric vent adapter box, as shown in Figure 10.1. Attach the double wall vent pipe to the single wall vent pipe that goes to the unit. Be sure to seal the joint and the open area around the double wall vent. Seal all joints and seams using sealant suitable for temperatures up to 400°F.
D9 Slide the combustion air pipe over the vent pipe and
attach to the air inlet of the concentric adapter box, as shown in Figure 10.1, using at least 3 corrosion-resistant sheet metal screws. Seal the joint and seam using sealant suitable for temperatures up to 400°F.
D10. Place this assembly (the adapter box, vent pipe and
combustion air pipe) through the wall or roof and verify that the distance requirements as defined in Step D7 are met. Securely attach the assembly to the building.
D11. From outside the building, caulk the gap between the
combustion air intake pipe and the building penetration.
D12. Attach the combustion air intake and vent pipe
terminations as follows:
For Vertical Concentric Vent Kits
(Refer to Figure 9.2):
•Slidethecombustionaircapdownovertheventpipe
and fasten it to the combustion air pipe with at least 3 corrosion-resistant sheet metal screws.
•Attachtheventcaptotheventpipeusingatleast
3 corrosion-resistant sheet metal screws. Refer to instruction A11 for connecting terminal to double wall pipe.
•Caulkthegapbetweenthecombustionaircapandthe
vent pipe with silicone sealant, or other appropriate sealants suitable for metal to metal contact and for temperatures up to 400° F.
For Horizontal Concentric Vent Kits
(Refer to Figure 9.3):
•Attachthecombustionairintakeguardusingcorrosion-
resistant screws at the end of the combustion air intake pipe to prevent animals and debris from entering.
•Attachtheventcaptotheventpipeusingatleast
3 corrosion-resistant sheet metal screws.
D13. Install vent pipe and combustion air pipe between unit
heater and concentric vent adapter box as outlined in “Section A – General Instructions – All Units”.
D14. Once venting is complete, proceed to the section titled
“Installation - Gas Connections”.
Table 10.1 - Concentric Vent Pipe Sizes
Single Wall Pipe
Model Size
150-200
250-400
B-Vent must have 1/4" air gap (OD is 1/2" larger than ID).
Combustion Air (To
Unit)
4" 6" 4"
6" 8" 6"
Combustion Air
(External)
Type B Vent Pipe
Vent
(Pass-Through)
Figure 10.2 - Adapter Box Exploded Assembly
Figure 10.1 - Adapter Box with Combustion Air Intake Pipe Attached
Outlet Vent Pipe Extended Through Box
A
10
Combustion Air Pipe Attached
B
Model Sizes A B
150-200 13.33" 18.84" 250-400 17.00" 15.27"
4.57"
6-561.11
INSTALLATION - GAS CONNECTIONS
GAS CONNECTIONS
W ARNING
1. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing.
2. Gas pressure to appliance controls must never exceed 14" W.C. (1/2 psi).
3. To reduce the opportunity for condensation, the minimum sea level input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or 5% below the minimum rated input of dual rated units.
CAUTION
1. Purging of air from gas lines should be performed as described in the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest edition or in Canada CSA-B149 codes.
2. When leak testing the gas supply piping system, the appliance and its combination gas control must be isolated during any pressure testing in excess of 14" W.C. (1/2 psi).
3. The unit should be isolated from the gas supply piping
system by closing its field installed manual shut-off valve. This manual shut-off valve should be located within 6' of the heater.
4. Turn off all gas before installing appliance.
IMPOR T ANT
To prevent premature heat exchanger failure, the input to the appliance, as indicated on the serial plate, must not exceed the rated input by more than 5%.
1. Installation of piping must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest Edition. In Canada, installation must be in accordance with CSA-B149.1.
2. Piping to units should conform with local and national requirements for type and volume of gas handled, and pressure drop allowed in the line. Refer to Table 11.1 to determine the cubic feet per hour (CFH) for the type of gas and size of unit to be installed. Using this CFH value and the length of pipe necessary, determine the pipe diameter from Table 11.2. Where several units are served by the same main, the total capacity, CFH and length of main must be considered. Avoid pipe sizes smaller than 1/2". Table 11.2 allows for a 0.3" W.C. pressure drop in the supply pressure from the building main to the unit. The inlet pressure to the unit must be 6-7" W.C. for natural gas and 11-14" W.C. for propane gas. When sizing the inlet gas pipe diameter, make sure that the unit supply pressure can be met after the
0.3" W.C. has been subtracted. If the 0.3" W.C. pressure drop is too high, refer to the Gas Engineer’s Handbook for other gas pipe capacities.
3. Install a ground joint union with brass seat and a manual shut-off valve adjacent to the unit for emergency shut-off and easy servicing of controls, including a 1/8" NPT plugged tapping accessible for test gauge connection (see Figure 11.1).
4. Use 2 wrenches when connecting field piping to units.
5. Provide a sediment trap before each unit in the line where low spots cannot be avoided (see Figure 11.1).
6. When pressure/leak testing, pressures above 14" W.C. (1/2 psi), close the field installed shut-off valve, disconnect the appliance and its combination gas control from the gas supply line, and plug the supply line before testing. When testing pressures 14" W.C. (1/2 psi) or below, close the manual shut-off valve on the appliance before testing.
Figure 11.1 - Recommended Sediment Trap/Manual Shut-off Valve Installation - Side or Bottom Gas Connection
Manual shut-off valve is in the
“OFF” position when handle is perpendicular to pipe.
Table 11.1 - Sea Level Manifold Pressure & Gas Consumption
Natural Propane
Model
Manifold Pressure
Size
150
175
200
250
300
350
400
("W.C.):
CFH 142.9 60.0
OriceDrillSize 42 53
CFH 166.7 70.0
OriceDrillSize 42 53
CFH 190.5 80.0
OriceDrillSize 38 52
CFH 238.1 100.0
OriceDrillSize 39 1.55 mm
CFH 285.7 120.0
Gal/Hr.Propane n/a 3.3
OriceDrillSize 36 51
CFH 333.3 140.0
OriceDrillSize 38 52
CFH 381.0 160.0
Gal/Hr.Propane n/a 4.4
OriceDrillSize 36 51
3.5 10
# of
Orifices
6Gal/Hr.Propane n/a 1.6
7Gal/Hr.Propane n/a 1.9
7Gal/Hr.Propane n/a 2.2
9Gal/Hr.Propane n/a 2.7
9
12Gal/Hr.Propane n/a 3.8
12
Table 11.2 - Gas Pipe Capacities - Natural Gas
Pipe Length
(ft)
10 132 278 520 1050 1600 3050 20 92 190 350 730 1100 2100 30 73 152 285 590 890 1650 40 63 130 245 500 760 1450 50 56 115 215 440 670 1270 60 50 105 195 400 610 1150 70 46 96 180 370 560 1050
80 43 90 170 350 530 930 100 38 79 150 305 460 870 125 34 72 130 275 410 780 150 31 64 120 250 380 710
Capacities in cubic feet per hour through schedule 40 pipe with maximum
0.3" W.C. pressure drop with up to 14" W.C. gas pressure. Specific gravity is 0.60 for natural gas and 1.50 for propane gas.
For pipe capacity with propane gas, divide natural gas capacity by 1.6. Example:
What is the propane gas pipe capacity for 60 feet of 1-1/4" pipe? The natural gas capacity is 400 CFH. Divide by 1.6 to get 250 CFH for propane gas.
1/2" 3/4" 1" 1-1/4" 1-1/2" 2"
Natural Gas
6-561.11
11
INSTALLATION - HIGH ALTITUDE ACCESSORY KIT
HIGH ALTITUDE ACCESSORY KIT
Modine’s gas-fired equipment standard input ratings are certified by ETL. For elevations above 2,000', ANSI Z223.1 requires ratings be reduced 4 percent for each 1000' above sea level. For units in Canada, CSA requires that ratings be reduced 10 percent at elevations above 2,000'. The high altitude adjustment instructions and pressure switch kits listed in this manual are for use with units that will be installed over 2,000'. These methods and kits comply with both ANSI Z223.1 and CSA requirements.
If a unit is to be installed at higher elevations AND converted from natural gas to propane gas operation, a propane conversion kit
Manifold Pressure Adjustment
The inlet pressure to the unit must be confirmed to be within acceptable limits (6-7" W.C. for natural gas and 11-14" W.C. for propane gas) before opening the shutoff valve or the combination gas valve may be damaged.
Heaters for use with natural gas have gas valves factory set at
3.5" W.C. manifold pressure at 7.0" W.C. inlet pressure. Units for use with propane gas are set for 10.0" W.C. manifold
pressure at 14.0" W.C. inlet pressure. Installation above 2,000' elevation requires adjustment of the
manifold pressure as described.
must be used in conjunction with the pressure adjustment methods and pressure switch kits listed herein. For the selection and installation instructions for propane conversion kits, please see the latest revision of Modine Manual 75-515.
Derated BTU Content Gas and Manifold Pressure Calculation
Some utility companies may derate the BTU content (heating value) of the gas provided at altitude to a value other than 1,050 BTU/ft3 for natural gas or 2,500 BTU/ft3 for propane gas
Selection of the Proper Pressure and Kit
To determine the proper manifold pressure at altitude and if required, the proper combustion air pressure switch kit, the full model number of the heater, the fuel to be used, and the altitude the unit will be installed at must be known. Refer to the unit serial plate or carton label to obtain the necessary information about the unit.
After obtaining this information, refer to the gas pressure and selection charts shown in Tables 12.1 through 12.3. The pressure charts are differentiated by elevation, fuel type, and country the product is being installed in. The selection charts are differentiated by product type, altitude and fuel type. If
converting from natural gas to propane gas and operation at high altitude, both a propane conversion kit and a pressure switch kit must
to allow certain heating appliances to be used with no manifold pressure adjustments. For this reason it is necessary that the supplying utility be contacted for detailed information about the gas type and BTU content (heating value) before operating any heater. Tables 12.1 and 12.2 show the standard derated heating values (4% per 1,000' of elevation in the USA and 10% between 2,001' and 4,500' elevation in Canada) of natural and propane gases at various altitudes. If the utility is supplying gas with heating values as shown in Tables 12.1 and 12.2, the manifold pressure should be set to 3.5" W.C for natural gas and
10.0" W.C. for propane gas.
NOTE: Only the high fire gas pressure need be adjusted, low fire gas pressure should remain the same.
be used (if applicable). Selection charts include the proper kit suffix, when required.
Table 12.1 - Natural Gas Heating Values at
Table 12.2 - Propane Gas Heating Values at Altitude ➁ ➂ ➃
Altitude ➀ ➂ ➃
Altitude (ft)
0-2,000
2,001-3,000
3,001-4,000
4,001-4,500
4,501-5,000
5,001-6,000
6,001-7,000
7,001-8,000
8,001-9,000
9,001-10,000
Values shown are for 3.5" W.C. manifold pressure, for other BTU content values (available from local utility) use Equation 12.1 to calculate manifold pressure. Values shown are for 10.0" W.C. manifold pressure, for other BTU content values (available from local utility) use Equation 12.1 to calculate manifold pressure. When installed at altitudes above 2,000', a pressure switch may need to be changed. Refer to Table 12.3 to determine if a switch change is required. Gas heating values are derated 4% per 1,000' of elevation in the USA and 10% between 2,000' and 4,500' elevation in Canada in accordance with ANSI Z223.1
and CSA-B149, respectively.
Gas Heating Values at Altitude (BTU/ft3)
USA Canada
1,050 1,050
929 892 874 856 856 822 822 789 789 757 757 727 727 698 698
945
Altitude (ft)
0-2,000
2,001-3,000
3,001-4,000
4,001-4,500
4,501-5,000
5,001-6,000
6,001-7,000
7,001-8,000
8,001-9,000
9,001-10,000
Gas Heating Values at Altitude (BTU/ft3)
USA Canada
2,500 2,500 2,212 2,123 2,080 2,038 2,038 1,957 1,957 1,879 1,879 1,803 1,803 1,731 1,731 1,662 1,662
2,250
Table 12.3 - High Altitude Kits for PTS/BTS
Model Size Details
150-250
300
350
400
Kit Suffix
Item Code
Kit Suffix
Item Code 68412 68412
Kit Suffix
Item Code
Kit Suffix
Item Code 68413 68413 68413 68413
12
0-2,000 ft. 2,001-4,500 ft. 4,501-5,500 ft. 5,501-6,500 ft. 6,501-7,500 ft.
Not Required Label Only Label Only Label Only Label Only
Not Required Label Only Label Only
Not Required Label Only Label Only Label Only Label Only
Not Required
U.S.A. and Canada
0008 0008
0009 0009 0009 0009
6-561.11
For Label Only kits, Modine
part number 5H0807146005
isrequiredtobelledoutand
attached to the unit by the installer. Please contact the local Modine representative at 1.866.828.4328 (HEAT).
INSTALLATION - HIGH ALTITUDE ACCESSORY KIT
If the heating value of the gas being supplied is different than the values shown in Tables 12.1 and 12.2, use the following equation to determine the appropriate manifold pressure for the altitude and gas heating value being supplied.
Equation 13.1 - Manifold Pressure for Derated Gas
WHERE:
MP
= Manifold Pressure (in. W.C.) at Altitude –
ACT
BTU
TBL
BTU
ACT
MPSL = Manifold Pressure (in. W.C.), at Sea Level –
NOTE: Only the primary manifold pressure should be adjusted
on units equipped with two-stage or modulating gas controls. No adjustments to the lowf fire manifold pressure are necessary on these units.
Manifold pressure setting for the heater being installed
= BTU/ft3 Content of Gas –
Obtained from Tables 12.1 or 12.2 (whichever is applicable)
= BTU/ft3 Content of Gas –
Obtained from the local utility company
Use 3.5" W.C. for natural gas and 10.0" W.C. for propane gas
6-561.11
13
INSTALLATION - ELECTRICAL CONNECTIONS
ELECTRICAL CONNECTIONS
W ARNING
1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with
wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
3. Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% greater than rated voltage.
5. When the unit on/off toggle switch is in the “OFF” position,
supply power remains energized at the rear of the switch. When a factory or field installed motor starting device such as a relay or contactor are present, supply power terminals of these components may remain energized even in the “OFF” position. When providing service on or near these terminals, de-energize building supply power to the unit.
CAUTION
Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage.
1. Installation of wiring must conform with local building codes, or in the absence of local codes, with the National Electric Code ANSI/ NFPA 70 - Latest Edition. Unit must be electri cally grounded in conformance to this code. In Canada, wiring must comply with CSA C22.1, Part 1, Electrical Code.
2. Two copies of the unit wiring diagram are provided with each unit. One is located in the side access control compartment and the other is supplied in the literature packet. Refer to this diagram for all wiring connections.
3. Make sure all multi-voltage components (motors, transform ers, etc.) are wired in accordance with the power supply voltage.
4. The power supply to the unit must be protected with a fused or circuit breaker switch.
5. The power supply must be within 5 percent of the voltage rating and each phase must be balanced within 2 percent of each other. If not, advise the utility company.
6. External electrical service connections that must be installed include:
a. Supply power connection (115, 208, 230, 460, or 575 volts). b. Connection of thermostats, or any other accessory control
devices that may be supplied (24 volts). NOTE: All units with supply voltage 208V and greater must use a field installed step-down transformer, available as a separate accessory. Refer to Tables 14.1 through 14.4 for additional information on the required transformer.
7. Refer to Figure 21.1 for the side access control compartment
location.
8. All supply power electrical connections are made in the side access
control compartment of the unit. The low voltage (thermostat and accessory control devices) can be wired to the terminals in the side access control compartment. Refer to the wiring diagram for the terminal location of all low voltage wiring.
9. Separated combustion models include a factory installed on/off
toggle switch. The function of this switch is to disconnect power to the unit for maintenance or to shut the unit off in warm weather. Toggle switch is rated at 15amps at 125 volts or up to 3/4 HP at 125 volts.
14
6-561.11
INSTALLATION WITH DUCTWORK
A
BAFFLE
B
30,5 CM
MIN.
A
B
CLOISON
AILETTE S
ROTATIVES
12" MIN.
B
3" MAX .
TUR NING
VANES 3" MIN.
A
A
3" MIN.
12"
MIN.
3" MAX.
TUR NING
VANES
12"
B
BAFFLE
A
B
12"
MIN.
BAFFLE
TURNING
VANES
30,5 CM
MIN.
AILE TTE S
ROTATIVES
Figure 15.1- Typical Duct & Airflow Installation
Recommended Installations
SIDE VIEW SIDE VIEW
SIDE VIEW SIDE VIEW TOP VIEW
IMPOR T ANT
Do not attempt to attach ductwork of any kind to propeller models.
When installing the heater, always follow good duct design practices for even distribution of the air across the heat exchanger. Recommended layouts are shown in Figure 15.1. When installing blower units with ductwork the following must be done.
1. Provide uniform air distribution over the heat exchanger. Use turning vanes where required (see Figure 15.1).
2. Provide removable access panels in the ductwork on the downstream side of the unit heater. These openings should be large enough to view smoke or reflect light inside the casing to indicate leaks in the heat exchanger and to check for hot spots on exchanger due to poor air distribution or lack of sufficient air.
3. If ductwork is connected to the rear of the unit use Modine blower enclosure kit or if using field designed enclosure maintain dimensions of blower enclosure as shown on page 23.
Additional Requirements for Installation of Blower Models (model BTS)
Determining Blower Speed
The drive assembly and motor on gas-fired blower unit heaters with motors 2HP and below are factory assembled. 3HP and larger motors are shipped loose to prevent shipping damage.
The adjustable motor sheave has been pre-set to permit operation of this unit under average conditions of air flow and without any external static pressure. The motor sheave should be adjusted as required when the unit is to be operated at other than average air flows and/or with external static pressures. Adjustment must always be within the performance range shown on page 22 and the temperature rise range shown on the unit’s rating plate.
Dimension “B” Should Never Be Less than 1/2 of “A”
CBA
TOP VIEW
FED
To determine the proper blower speed and motor sheave turns open, the conditions under which the unit is to operate must be known. If the blower unit is to be used without duct work or filters, the only criteria for determining the motor sheave turns open and blower speed is the amount of air to be delivered. The performance tables for blower models are shown on pages 18 and 19. As an example, a model BTS 350 unit, operating with no external static pressure, that is, no duct work, filters, etc., and is to deliver an air volume of 6481 cfm (cfm = cubic feet of air per minute) requires that the unit be supplied with a 5 hp motor, a -207 drive, and the drive sheave must be set at
2.5 turns open to achieve a blower speed of 960 rpm (see performance table for units with or without blower enclosure, page 19). See “Blower Adjustments” on page 16 for setting of drive pulley turns open.
If a blower unit is to be used with ductwork or filters, etc., the total external static pressure under which the unit is to operate, and the required air flow must be known before the unit can be properly adjusted.
If Modine filters are used, the expected pressure loss through the filters is included in the performance data on page 17. If filters or ductwork are to be used with the unit, and they are not supplied by Modine, the design engineer or installing contractor must determine the pressure loss for the externally added devices or ductwork to arrive at the total external static pressure under which the unit is to operate.
Once the total static pressure and the required air flow are known, the operating speed of the blower can be determined and the correct motor sheave adjustments made. As an example, a model BTS 350 is to be used with a Modine supplied blower enclosure and Modine supplied filters attached to ductwork. The unit is to move 6481 cfm of air flow against an external static pressure of 0.2" W.C. Also, 0.2" W.C. must be added for the filter pressure drop for a total of 0.4" W.C. total pressure drop. Entering the performance table on page 18 for a BTS 350, at 6481 cfm and 0.4" W.C. static pressure, it is seen that the unit will require a 5 hp motor using a -207 drive, and the motor sheave should be set at .5 turns open to achieve a blower speed of 1050 rpm. You can see this example differs from similar conditions in paragraph 2 by the number of turns open and a higher rpm, which is needed to overcome the added external static pressure from the filters.
6-561.11
15
TOWARD MOTOR
SET SC REW
AD JUSTABLE HALF
OF SHEAVE
3/4" DEFLECTION
WITH 5 LBS. FORC
INSTALLATION
To Install
1. Remove and discard the motor tie down strap and the shipping block beneath the motor adjustment screw (not used on all models.)
2. For 3 and 5 HP motors, affix sheave to the motor shaft and install motor on the motor mounting bracket. Install belt on blower and motor sheaves.
Figure 16.1 - Blower Model
MOUNTING BRACKETS ON BLOWER
BLOWER
SHEAVE
ASSEMBLY
BLOWER
HOUSING
ADJUSTMENT
3. Adjust motor adjusting screw for a belt deflection of
approximately 3/4" with 5 pounds of force applied midway between the sheaves (refer to Figure 16.3). Since the belt tension will decrease dramatically after an initial run-in period, it is necessary to periodically re-check the tension. Excessive tension will cause bearing wear and noise.
4. The blower bearings are lubricated for life; however, before
initial unit operation the blower shaft should be lubricated at the bearings with SAE 20 oil. This will reduce initial friction and start the plastic lubricant flowing.
5. Make electrical connections according to the wiring diagram.
6. Check rotation of the blower. Motor should be in clockwise
rotation when facing motor pulley. If rotation is incorrect, correction should be made by interchanging wiring within the motor. See wiring diagram on the motor.
7. The actual current draw of the motor should be determined.
Under no condition should the current draw exceed that shown on the motor rating plate.
8. It is the installer’s responsibility to adjust the motor sheave to
provide the specified blower performance as listed on pages 18 & 19 for blower settings different from the factory set performance. The drive number on the unit may be identified by referring to the Power Code number on the serial plate of the unit (see page 27 for model number nomenclature) and matching that number with those shown on page 17. From the listing, the drive number can be determined.
MOTOR MOUNTING
MOTOR
SCREW
BRACKET
ADJUSTABLE
MOTOR SHEAVE
Blower Adjustments
Following electrical connections, check blower rotation to assure blow-through heating. If necessary interchange wiring to reverse blower rotation. Start fan motor and check blower sheave RPM with a hand-held or strobe-type tachometer. RPM should check out with the speeds listed in performance data shown on pages 18 and 19. A single-speed motor with an adjustable motor sheave is supplied with these units. If blower fan speed changes are required, adjust motor sheave as follows:
NOTE: Do not fire unit until blower adjustment has been made or unit may cycle on limit (overheat) control.
1. Shut-off power before making blower speed adjustments. Refer to “Determining Blower Speed” on
page 15 and to “Performance Data” on pages 18 and 19 to determine proper blower RPM.
2. Loosen belt and take belt off of motor sheave.
3. Loosen set screw on outer side of adjustable motor sheave (see Figure 16.2).
4. To reduce the speed of the blower, turn outer side of motor sheave counterclockwise.
5. To increase the speed of the blower, turn outer side of motor sheave clockwise.
6. Retighten motor sheave set screw, replace belt and retighten motor base. Adjust motor adjusting screw such that there is 3/4" belt deflection when pressed with 5 pounds of force midway between the blower and motor sheaves (see Figure 16.3). Since the belt tension will decrease dramatically after an initial run-in period, it is necessary to periodically re-check the tension to assure continual proper belt adjustment.
7. Check to make certain motor sheave and blower sheave are aligned. Re-align if necessary.
8. Re-check blower speed after adjustment.
9. Check motor amps. Do not exceed amps shown on motor nameplate. Slow blower if necessary.
10. Check air temperature rise across unit. Check temperature rise against values shown in performance tables on pages 18 and 19 to assure actual desired air flow is being achieved.
11. If adjustments are required, recheck motor amps after final blower speed adjustment.
Figure 16.2 - Motor Sheave Adjustment
Figure 16.3 - Belt Tension Adjustment
16
6-561.11
BLOWER PERFORMANCE DATA - MODEL BTS
Table 17.1 - Power Code Description - Blower Model BTS -
Power
Code
01
02
08
11
13
19
22
24
30
33
35
41
44
52
55
63
66
74
77
For selection of correct power code, refer to the tables on pages 18-19.
Voltage Phase
115 1 1/4 230 - - - - - - - - - - - -
115/230 1 1/3 230 1/3 238 1/2 233 1/2 204 1 240 1 1/2 250 1 1/2 247
208-230/460 3 1/3 230 1/3 238 1/2 233 1/2 204 1 257 1 1/2 251 1 1/2 248
575 3 1/3 231 1/3 239 1/2 233 1/2 204 1 257 1 1/2 251 1 1/2 248
115/230 1 1/3 232 1/2 229 1 229 1 241 1 241 1 1/2 247 - -
208-230/460 3 1/3 232 1/2 229 1 259 1 258 1 258 1 1/2 248 2 177
575 3 1/3 233 1/2 229 1 259 1 258 1 258 1 1/2 248 2 177
115/230 1 1/2 229 1 175 1 175 1.5 23 1 1/2 243 1 1/2 252 - -
208-230/460 3 1/2 229 1 253 1 253 1.5 177 1 1/2 244 1 1/2 180 3 246
575 3 1/2 229 1 253 1 253 1.5 177 1 1/2 244 1 1/2 180 3 246
115/230 1 1 175 1 1/2 237 1 1/2 235 - - 1 1/2 23 - - - -
208-230/460 3 1 253 1 1/2 234 1 1/2 236 2 180 1 1/2 177 2 177 5 245
575 3 1 253 1 1/2 234 1 1/2 236 2 180 1 1/2 177 2 177 5 245
208-230/460 3 - - - - - - - - 2 177 2 180 - -
575 3 - - - - - - - - 2 177 2 180 - -
208-230/460 3 - - - - - - - - 3 11 2 3 246 - -
575 3 - - - - - - - - 3 112 3 246 - -
208-230/460 3 - - - - - - - - - - 5 245 - -
575 3 - - - - - - - - - - 5 245 - -
BTS150 BTS175 BTS200 BTS250 BTS300 BTS350 BTS400
HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive
Table 17.2 - Filter Static Pressure Drop
BTS150 BTS175 BTS200 BTS250 BTS300 BTS350 BTS400
Filter Static ("W.C.) 0.1 0.2 0.1 0.2 0.2 0.2 0.2
Forblowerunitswithenclosureandlter,addthefollowingstaticpressurestothestaticpressuredeterminedbythesystemdesignerfortotal
external static pressure.
6-561.11
17
Loading...
+ 39 hidden pages