Modine Manufacturing 3H038824 Service Manual

GEO16-506.0
5H0833050000
January, 2016
INSTALLATION AND SERVICE MANUAL
cased and uncased coils for ground source heat pump split unit
model 3H038824
NOTE: Energy Star only applies to certain configurations.
NOTE: Modine Cased and Uncased Coils are Energy Star Rated only when matched with the appropriate Modine GS Split Units. Model EA Air Handlers are not Energy Star Rated.
WARNING
This unit contains R-410A high pressure refrigerant. Hazards exist that could result in personal injury or death. Installation, maintenance, and service must only be performed by an HVAC technician qualified in R-410A refrigerant and using proper tools and equipment. Due to much higher pressure of R-410A refrigerant, DO NOT USE service equipment or tools designed for refrigerants other than R-410A.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death, and could cause exposure to substances which have been determined by various state agencies to cause cancer, birth defects or other reproductive harm. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
IMPORTANT
1. The use of this manual is specifically intended for a qualified installation and service agency. A qualified installation and service agency must perform all installation and service of these appliances.
2. Cased and Uncased Coils contain the refrigerant R-410A Material Safety Data Sheet (MSDS) for hazards and first aid measures.
3. This unit contains copper and / or brass components and is not suitable for use with ammonia (R717).
4. Refrigerant charging should only be carried out by an EPA-certified air conditioning contractor.
Inspection On Arrival
1. Inspect unit upon arrival. In case of damage, report it immediately to transportation company and your local factory sales representative.
2. Check rating plate on unit to verify that the coil and split
unit being installed have matching capacities and can be installed together.
3. Inspect unit received for conformance with description of product ordered (including specifications where applicable).
4. These coils are not for use with potable water.
SPECIAL PRECAUTIONS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE, EFFICIENT, AND TROUBLE-FREE OPERATION. IN ADDITION, PARTICULAR CARE MUST BE EXERCISED REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW. FAILURE TO PROPERLY ADDRESS THESE CRITICAL AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS, PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS ARE SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation
which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which,
if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which,
if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided, MAY
result in a potential safety concern.
DANGER
Appliances must not be installed where they may be exposed to potentially explosive or flammable atmosphere.
CAUTION
1. Do not use these units to heat or cool the building during construction. Mechanical components can quickly become clogged with debris. System damage may result.
2. Do not overcharge the refrigeration system. This can lead to elevated compressor discharge pressure and possibly flooding the compressor with liquid.
3. Do not attempt to reuse any mechanical or electrical component which has been wet. Such component must be replaced.
4. For horizontal applications, the horizontal drain pan must be installed. Failure to do so will result in property damage.
5. Coils must be installed on the supply airflow side of furnace.
IMPORTANT
1. Start-up and adjustment procedures must be performed by a qualified service agency.
2. All refrigeration checks must be made by a qualified R-410A refrigeration technician.
3. Do not release refrigerant to the atmosphere. When adding or removing refrigerant, all national, state/province, and local laws must be followed.
WARNING
1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with the wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
3. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
4. This unit contains R-410A high pressure refrigerant. Hazards exist that could result in personal injury or death. Installation, maintenance, and service must only be performed by an HVAC technician qualified in R-410A refrigerant and using proper tools and equipment. Due to much higher pressure of R-410A refrigerant, DO NOT USE service equipment or tools designed for refrigerants other than R-410A.
5. When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine Manufacturing Company. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner’s risk.
Table of Contents
General Information ................................. 1
Inspection on Arrival ................................. 1
Special Precautions ................................. 2
Model/Serial Number Designations ..................... 3
Unit Dimensions .................................... 3
Unit Location....................................... 5
Installation ........................................ 5
SI (Metric) Conversion Factors ...................... 5
Ducting ......................................... 6
Wiring.......................................... 8
Start-Up Procedure.................................. 9
Physical Data ..................................... 10
Maintenance.................................... 10
Replacement Parts................................11
Serial Plate – Example.............................11
Troubleshooting ....................................11
Warranty...................................Back Page
2
GEO16-506
MODEL NOMENCLATURE
Table 3.1 - Model Number Designations
Matching Split Model Size
Coil Type 024 036 048 060
Uncased 0024 0036 0048 0060
Cased 1024 1036 1048 1060
Figure 3.1 - Uncased Coil Dimensions
Table 3.2 - Dimensions (inches)
Models 0024 0036 0048 0060
Overall Coil
Suction Line Connection (in.) - Sweat 5/8 3/4 3/4 7/8
Liquid Line Connection (in.) - Sweat 3/8 3/8 3/8 1/2
Condensate Drain Connection (in. NPT), SS 3/4 3/4 3/4 3/4
Approx. Operating Weight (lbs.) 44 46 50 56
Approx. Shipping Weight (lbs.) 94 96 100 106
A 27.61 27.61 30.37 33.66
B 20.13 20.13 20.13 20.13
C 24.50 24.50 24.50 24.50
GEO16-506
3
UNIT DIMENSIONS
Figure 4.1 - Cased Coil Dimensions
Table 4.1 - Dimensions (inches)
Models 1024 1036 1048 1060
Overall Cabinet
Condensate Drain
Suction Line Connection (in.) - Sweat
Liquid Line Connection (in.) - Sweat
Condensate Drain Connection (in. NPT), SS
Approx. Operating Weight (lbs.)
Approx. Shipping Weight (lbs.)
A 27.77 27.77 31.63 35.78
B 20.88 20.88 20.88 20.88
C 24.62 24.62 24.62 24.62
I 19.60 19.60 23.60 27.60
5/8 3/4 3/4 7/8
3/8 3/8 3/8 1/2
3/4 3/4 3/4 3/4
83 85 94 105
133 135 144 155
4
GEO16-506
UNIT LOCATION / INSTALLATION
Table 5.1 - SI (Metric) Conversion Factors
To Convert Multiply By To Obtain
"W.C. 0.24 kPa psig 6.893 kPa °F inches 25.4 mm feet 0.305 meters CFM 0.028 m3/min
(°F-32) x 0.555
°C
To Convert Multiply By To Obtain
CFH 1.699 m3/min Btu/ft3 0.0374 mJ/m pound 0.453 kg Btu/hr 0.000293 kW/hr gallons 3.785 liters psig 27.7 "W.C.
3
UNIT LOCATION
DANGER
Appliances must not be installed where they may be exposed to potentially explosive or flammable atmosphere.
Handling
Each unit will be shipped to the site on a wood skid. Whenever possible, all lifting and handling of the unit should be done with
the packing and skid in position.
When slinging or using a forklift to lift the unit, the support points should be sufficiently apart to give stability when lifting. Unless otherwise noted, the lifting points should be equidistant from the
centerline. Extreme care should be taken not to drop the unit
Considerable damage can occur to the unit during positioning, in particular, to the paneling and exterior paint. Use an adequate number of personnel and the correct tools when moving the unit. The unit is designed to remain upright so care should be taken
when lifting the unit up steps.
The use of torque screwdrivers on panel, cover or component mounting screws is not recommended. Hand-start all screws.
If electric drills are used – set at the lowest possible torque.
Storage
Equipment should be stored in clean, dry area and in its original packaging.
Do not store or install units in corrosive environments or in locations subject to temperature or humidity extremes. Performance, reliability, and service life can be significantly
reduced. Transport and store units in an upright position.
Unit Protection
To prevent damage, keep the unit in its original packaging or cover with an equivalent protective covering while on the job site. Cover open connections to prevent debris from entering the system. Take extra precautions to protect the unit from damage or contamination when in an area where spraying, plastering and / or painting has not been completed. Physical damage or contamination from foreign debris may prevent proper start-up and costly equipment clean-up. Examine all fittings, valves, or pipes and remove all dirt or debris before installing unit.
Electrical
Electrical wiring should be done in accordance with all applicable national and local codes. It is the responsibility of the electrical contractor to adhere to such codes. The warranty will be voided if wiring is not in accordance with the specifications of
the unit. Modine recommends using copper conductors only. All power supply wiring must be capable of carrying the
maximum current load under no fault conditions at the stipulated voltages. Care should be taken to avoid significant voltage drops. A knockout for power connection is provided on the access side
of the unit. See unit dimensions in Figures 3.1 and 4.1.
INSTALLATION
A conventional fossil fuel forced air furnace may also be used for an air handler, as well as a alternative heat source, provided a dual-fuel capable thermostat is used. The furnace must provide airflow within +/- 5% of the airflows shown in Table 10.1. The furnace must be disabled until auxiliary heating is called for, then the heat pump must be disabled when the furnace takes over the heat load. Refer to the furnace manufacturer’s installation instructions for directions on installation of the furnace, coil, and wiring. A Dual Fuel Thermostat is required to prevent damage to
the Split Unit.
Installation of these units is to be INDOORS only. The instructions detailed below are for the Installation of a “Standard” unit. Accommodations and adjustments will be required for the usage of additional unit accessories. Should assistance be required for the installation of these additional items, consult Modine at the phone
number listed on the back cover of this manual.
Modine Cased Coils are designed for upflow, downflow, and horizontal (left and right) applications. Modifications are not required for Cased Coils applied in the upflow and downflow applications; however, the addition of a horizontal drain pan is required for horizontal applications. The horizontal conversion kit part numbers can be found in Table 6.1. Refer to GEO 16-
522 for conversion instructions.
The coils are shipped with a dry nitrogen holding charge and come standard with ODF braze refrigerant connections to ensure easy installation. The factory installed thermal expansion valves are pre-set for optimal performance with a matched
Modine Split Condensing Unit.
CAUTION
1. For horizontal applications, the horizontal drain pan must be installed. Failure to do so will result in property damage.
2. Coils must be installed on the supply airflow side of furnace.
Figure 5.1 - Cased Coil
Preparation
1. If the installation has multiple units, check that unit identifications correspond with the network diagrams. Advise Modine immediately if discrepancies are noted.
2. Remove any Accessory Kits and shipping support material from the mechanical compartment.
3. Check refrigerant piping for dents or kinks.
4. Ensure that aluminum distributor tubes and thermal expansion valve capillary tubing has not come into contact with any sheet metal brackets, or coil flanges. Do not re-bend distributor leads. Aluminum should not be re-bent.
GEO16-506
5
INSTALLATION
Location and Installation Considerations
1. It is highly recommended that the unit is located in a conditioned space that is not subject to freezing and where humidity levels are controlled so as not to could cause cabinet condensation.
2. Provide adequate clearance for front access panels. A minimum of 30” of clearance on the front side of the coil should be provided.
3. The unit can be serviced entirely from the front. Be sure to route primary and second condensate drain lines so as not to interfere with access and maintenance.
4. The air delivery of the furnace must deliver the airflow and static as specified in Table 10.1.
5. Coils must be installed on the supply airflow side of the furnace.
6. Horizontal applications require the addition of a horizontal drain pan conversion kit. Refer to Table 6.1 for part numbers and GEO-16-522 for conversion instructions.
7. Use screws with a maximum length of 3/8" to connect ducting or duct collars to the unit.
8. Use of flexible duct collars and use of acoustical duct liners are good installation practices that ensure quiet operation.
9. Provide adequate room to make refrigerant, electrical and duct connections.
10. It may be necessary to fabricate a special plate to adapt the coil casing to the furnace air discharge opening.
11. A tapered transition, with a 6" minimum length, is required to
evenly distribute airflow where the furnace cross flow area is significantly different from that of the coil casing.
12. Provide a clear physical path to the unit. Adequate space should be provided to allow removal of the unit, if necessary.
13. Allow adequate room below a horizontal unit for a
condensate drain trap.
14. Should the coil section be installed in a non-conditioned space such as an attic, garage or crawl space, a full size secondary drain pan must be provided to prevent damage from condensate run-off. In this application, it is recommended that the unit exterior be completely insulated with a minimum of 1" thick fiberglass insulation with a vapor barrier on the outside.
All ductwork must be designed and installed in accordance with local codes.
Note: The coils are equipped with a supply air duct flange to facilitate installation. The size of the supply duct must be designed to transport the rated unit airflow. Proper transition to the coil duct flange must be utilized.
Furnace Transition and Duct Mounting
1. Ensure evenly distributed airflow between the furnace and the coil. If the cased coil footprint is substantially different than that of a matched furnace, it may be necessary to fabricate either an adapter plate or a tapered transition. The tapered section should have a minimum transition length of 6".
2. Depending on the configuration, the brackets shown in Figure
6.1 may be utilized to attach the furnace supply, duct system or transition to the top side of the cased coil.
3. If screws are used to connect the furnace supply, duct system or transition to the bottom of the cased coil, keep the screws within the bottom 1" of the casing and only use on the two sides and back of the casing. Do not use screws on the front access cover. In addition, screws should have a maximum length of 3/8". Figures 3.1, 4.1 and 6.2 show the casing mounting area and dimensions, respectively.
4. If the duct construction around an uncased coil will be fastened to the uncased coil, screws may only be used in the bottom 1" of the lower base frame and the sides of the front connection mounting plate, as shown in Figure 6.2. Do not install screws into the drain pan or any part of the coil.
5. Ensure that duct joints are sealed airtight, per local codes.
6. Check that the unit is level from side-to-side and front­to-back. the drain pan is pitched to facilitate condensate removal.
7. All field wiring entry points must be sealed airtight.
Figure 6.1 - Duct Mounting Flanges - Top
Table 6.1 - Horizontal Conversion Kits
Models Part Number
024 3H0388220005
036 3H0388220006
048 3H0388220007
060 3H0388220008
Duct System
The duct system must be designed to transport the rated unit ariflow quietly and efficiently. For maximum blower sound attenuation, it is recommended that the first few feet of the supply and return plenums include an internal fiberglass duct liner or be constructed of ductboard. On metal duct systems, canvas connectors should be incorporated between the unit and ductwork. Installing the coil section to uninsulated metal ductwork in an unconditioned space will result in poor system performance and lead to condensation formation on the duct and possible structural damage.
If existing ductwork is utilized, verify that duct system can accommodate the rated airflow. If the ductwork is undersized, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired as required.
6
GEO16-506
Figure 6.2 - Duct Mounting - Bottom
INSTALLATION
Horizontal Installation
1. Refer to Horizontal Conversion Kit instructions if field conversion is required.
2. The coil may be installed on any level surface strong enough to support the weight and isolated to prevent sound transmission. Vibration isolators (by others) are recommended.
3. When installed in an attic or above a drop ceiling, the installation must conform to all local codes.
4. If the unit is suspended, typically 3/8"-16 threaded rods with a unistrut or other suitable framing systems are employed. The entire length of the unit must be supported.
5. If the coil is installed on the attic floor, the unit should be set in a full size secondary drain pan. The secondary drain pan should be set on top of a vibration absorbing mesh, on a plywood base. A secondary drain pan should be used when installed over a finished living area to provide protection from water damage in case the primary drain line becomes plugged. The secondary drain line should terminate somewhere that is easily visible by the homeowner. Be certain to show the homeowner the termination location of the secondary drain line and to explain its purpose. If the coil is installed in a crawl space, the bottom of the coil must be at least 4” above grade to prevent flooding during heavy rains.
6. Check that the unit is level from side-to-side and front–to-back. The drain pan is pitched to facilitate condensate removal.
7. All field wiring entry points must be sealed airtight.
Condensate Piping
The coil drain pan has two 3/4" NPT stainless steel drain fittings. When the coil is configured for horizontal airflow, four fittings are present. The two “upper” or “vertical” drain fittings must be plugged.
1. The drain pan has a primary and auxiliary drain connection.
It is recommended that both the primary and auxiliary drains are utilized. The installer must always follow local codes when running condensate drain piping.
2. As the coil sections are not internally trapped, a trap must
be installed in the drain line below the bottom of the drain pan to ensure free condensate flow (see Figure 8.1). Install drain lines so that they do not block service access to the front of the unit or furnace.
3. The coil drain connections must be connected to a drain line
and pitched away from the unit a minimum of 1/8” per foot to allow the condensate to flow away from the coil.
4. The primary condensate drain must be terminated to an
open drain or sump. Do not connect the condensate drain to a closed waste system.
5. An open vertical air vent should be installed to overcome
line length, friction and static pressure.
6. Make provisions for disconnecting and cleaning of the
primary drain line should it become necessary.
7. It is recommended that the auxiliary drain be connected to a
drain line for all units.
8. The auxiliary drain should be run to an area where the
homeowner will notice it draining.
9. The drain line should not be smaller than the drain
connection at the condensate pan.
10. The drain line contains cold water and should be insulated
in unconditioned spaces to avoid drain line condensation from dripping on ceiling, etc.
11. If the coil section is located in an unconditioned space, water in
the trap may freeze. It is recommended that the trap material be of a type that will allow for expansion of water when it freezes.
12. Test condensate drain pan and drain line after installation is complete. Pour enough water into drain pan to fill drain trap and line. Check to make sure drain pan is draining completely, no leaks are found in drain line fittings, and water is draining from the termination of the primary drain line.
13. It is always recommended that a secondary drain be installed under a horizontal coil.
14. Drain lines must be in conformance with local codes
Figure 8.1 - Condensate Trap Example
Secondary Drain Pan Overflow Switch
It is highly recommended a normally closed, condensate overflow switch be installed in the secondary drain pan and wired to the split system terminal strip. When installed, the controller will shut down the unit in the event of a plugged condensate drain line. Failure to wire the switch to unit may result in damage to the furnace or property.
Wire terminals are provided in the control panel for easy connection of overflow switch. Remove the BLUE jumper between the terminals and tie in the secondary drain pan overflow switch leads.
Refrigerant Line Sets
Refer to the Split Unit installation manual (GEO16-501) for for line sizing and line set guidelines.
Thermal Expansion Valve
The coil section is equipped with a TXV that is pre-set from the factory for optimized cooling. No adjustment is necessary unless service has been done on the TXV. Table 10.2 shows the coil TXV initial factory settings. Note that the matched Split system has two TXV’s, each with independent factory settings. One TXV is include with the coil and one is installed in the Split unit. Refer to the Split Ground Source Unit I&S manual for the TXV settings at the Split unit.
Air Coil
To ensure maximum performance, it is recommended that the air coil be cleaned before startup. A solution of 10% dishwasher detergent and water is recommended. Spray both sides of the coil followed by a thorough clean water rinse.
Leak Testing, Evacuating and Charging the System
Refer to the Split Unit installation manual for instructions.
GEO16-506
7
INSTALLATION
Wiring
WARNING
1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with the wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
3. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
Installation of wiring must conform with local building codes, or in the absence of local codes, with the National Electric Code ANSI/NFPA 70 - latest edition. Unit must be electrically grounded in conformance to this code. In Canada, wiring must comply with CSA C22.1, Part 1, Electrical Code.
Any damage to or failure of units caused by incorrect wiring of the units is not covered by warranty.
Dual Fuel Setup / Thermostat Wiring
When wiring to a gas furnace, a dual fuel thermostat is required to prevent the furnace from engaging when the heat pump is operating. The heat pump is the first and second stage of heating and the furnace is the backup heat. Refer to Split Unit I&S manual.
Condensate Overflow Alarm
Modine Cased and Uncased Coils are supplied with a condensate pan overflow switch kit (PN 3H038786). It is highly recommended that the switch be installed in the drain pan and wired to the split system terminal strip. The condensate alarm is a 24V, normally closed, dry contact. When installed, the controller will shut down the split system in the event of a plugged condensate drain line. Failure to wire the switch to the split system may result in damage to the furnace or property.
Installation of Condensate Pan Switch
The condensate switch is supplied with a float switch, 75' of lead wire and fastener. The drain pan features a mounting tab on the front right edge of the pan. Position the float switch mounting tab on top of the drain pan tab, as shown in Figure 8.1. Locate the center mounting hole of the float switch with the hole in the mounting tab. Insert the fastener provided through the holes and push the pin down to secure the switch in place. The installer may route the leads back to the split unit or run two wires. Refer to the Split Unit installation manual for wiring instructions.
Figure 8.1 - Float Switch Installation
8
GEO16-506
START-UP PROCEDURE
START-UP PROCEDURE
IMPORTANT
Start-up and adjustment procedures must be performed by a qualified service agency.
The unit has been factory tested and set for proper operation, but a full unit start-up is recommended.
NOTE: If any abnormal operation occurs during the startup procedure, refer to the Troubleshooting section.
NOTE: Always start the system in heating mode.
Pre-Start Checks
Before applying power to system, use the following checklist to ensure a complete and proper installation.
• Trace circuits to insure that the unit has been wired according
to the wiring diagram.
• Check that the unit has no visible damage and that all the
components are secure.
• Check that all field electrical and mechanical work has been
performed according to all applicable Federal, State, and Local codes.
• Low voltage wiring for thermostat, control wiring and the heat
pump controller setup completed.
• Condensate line is open, condensate drain line is correctly
pitched.
• Check air coil for cleanliness.
• Filter is clean and in position.
• Clean all debris from the ducting system.
• Service/access panels are in place.
Unit Startup Procedure
Refer to the Split Unit installation manual, GEO16-501, for details instructions on system startup.
GEO16-506
9
PHYSICAL DATA / MAINTENANCE
Table 10.1 - Physical Data
AIR COIL
Total Air Coil Face Area, ft² 4.5 5.0 6.0 7.0
Number of Rows 3 3 3 3
Tube Outside Diameter, in. 3/8 3/8 3/8 3/8
Fins per Inch 13 13 13 13
Suction Line Connection, in. - Sweat 5/8 3/4 3/4 7/8
Liquid Line Connection, in. - Sweat 3/8 3/8 3/8 1/2
Model Size
024 036 048 060
Condensate Drain Connection, in. - NPT
AIRFLOW
Stage 1 Heat/Cool Required Airflow, CFM / Wet Coil Static Pressure
Drop, in-wc
Stage 2 Heat/Cool Required Airflow, CFM / Wet Coil Static Pressure
Drop, in-wc
1. Furnace or air handler must be able to provide specified airflows, +/- 5%
1
3/4 3/4 3/4 3/4
560 / 0.06 900 / 0.13 1140 / 0.15 1410 / 0.18
730 / 0.09 1140 / 0.18 1490 / 0.22 1880 / 0.29
Table 10.2 - Coil Factory TXV Settings
Models
024 036 048 060
TXV Turns Closed 3-3/4 1-3/4 6-1/2 3-1/4
MAINTENANCE
Air Filters
WARNING
When servicing or repairing this equipment, use only factory­approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine Manufacturing Company. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner’s risk.
CAUTION
1. Do not attempt to reuse any mechanical or electrical component which has been wet. Such component must be replaced.
2. Air coil fin edges are sharp, take necessary precautions.
The routine care and maintenance of this unit will increase longevity, provide for the proper operational performance, and reduce the probability of failure.
Once the unit is operational, it will be necessary to perform certain routine maintenance/service checks. Following is a Maintenance Schedule with the recommended checks. If your unit is equipped with special features, there may be additional checks that are required. Consult Modine for assistance.
The use of torque screwdrivers on panel, cover or component mounting screws is not recommended. Hand-start all screws.
If electric drills are used – set at the lowest possible torque.
Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating conditions and be replaced when necessary. Units should never be operated without a filter.
Condensate Drain
In areas where airborne bacteria produce slime in the drain pan, it may be necessary to treat chemically with an algaecide approximately every three months to minimize the problem. It may be necessary to clean the condensate pan periodically to insure indoor air quality. The condensate drain can pick up lint and dirt, especially with dirty filters. Inspect twice a year to avoid the possibility of overflow.
Air Coil
The air coil should be cleaned annually to retain maximum performance. Inspect once a year under normal operating conditions. If the air coil shows dirt or debris, use a vacuum with a gentle end or a rag to clean the debris from the air coil. The fins are easily damaged, so take care when cleaning.
Cabinet
If a flood occurs, try to expel water as soon as possible. Water contact for any duration will help corrosion on the cabinet finish. If the cabinet is dirty, do not spray with water, use a damp rag with mild detergent, and wipe the system clean.
10
GEO16-506
REPLACEMENT PARTS / TROUBLESHOOTING
REPLACEMENT PARTS
For ease of identification when ordering replacement parts or contacting the factory about this unit, please provide the complete model number and unit serial number. This information can be found on the serial plate attached to the unit (see Figure
11.1). When a component part fails, a replacement part should be obtained by contacting the local distributor or Modine Sales Representative. The sales representative can assist with Return Material Authorizations (RMAs) and potential warranty claims. The following details are required to process parts orders and warranty claims:
1. Full description of part required, including unit’s model number.
2. The complete unit’s serial number.
3. Completed Return Material Authorization (RMA)
4. An appropriate purchase order number.
For further information email modinegeothermal@ccsportal.
com or call 1-877-679-4436 (4GEO).
Table 11.1 - Common Replacement Parts
Model
Air Coil Assembly TXV
Size
024 3H0387980001 5H0834700002 3H0396720000
036 3H0387980002 5H0834700003 3H0396720000
048 3H0387980003 5H0834700004 3H0396720000
060 3H0387980004 5H0834700005 3H0396720000
Condensate
Overflow Switch
TROUBLESHOOTING
Refer to Split Unit manual, GEO16-501, for Troubleshooting guidance.
Figure 11.1 - Serial Plate EXAMPLE
GEO16-506
11
COMMERCIAL WARRANTY (For Residential Warranty, see GEO16-510)
Seller warrants its products to be free from defects in material and workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use of materials substituted under emergency conditions for materials normally employed. This warranty covers replacement of any parts furnished from the factory of Seller, but does not cover labor of any kind and materials not furnished by Seller, or any charges for any such labor or materials, whether such labor, materials or charges thereon are due to replacement of parts, adjustments, repairs, or any other work done. This warranty does not apply to any equipment which shall have been repaired or altered outside the factory of Seller in any way so as, in the judgment of Seller, to affect its stability, nor which has been subjected to misuse, negligence, or operating conditions in excess of those for which such equipment was designed. This warranty does not cover the effects of physical or chemical properties of water or steam or other liquids or gases used in the equipment.
BUYER AGREES THAT SELLER’S WARRANTY OF ITS PRODUCTS TO BE FREE FROM DEFECT IN MATERIAL AND WORKMANSHIP, AS LIMITED HEREIN, SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER WARRANTIES, EITHER EXPRESS OR IMPLIED, WHETHER ARISING FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE,
THERE ARE NO OTHER WARRANTIES, INCLUDING WARRANTY OF MERCHANTABILITY OR FITNESS FOR PURPOSE, WHICH EXTEND BEYOND THE PRODUCT DESCRIPTION CONFIRMED BY BUYER AND SELLER AS OF THE DATE OF FINAL AGREEMENT.
This warranty is void if the input to the product exceeds the rated input as indicated on the product serial plate by more than 5% on gas-fired and oil-fired units, or if the product in the judgment of SELLER has been installed in a corrosive atmosphere, or subjected to corrosive fluids or gases, been subjected to misuse, negligence, accident, excessive thermal shock, excessive humidity, physical damage, impact, abrasion, unauthorized alterations, or operation contrary to SELLER’S printed instructions, or if the serial number has been altered, defaced or removed.
BUYER AGREES THAT IN NO EVENT WILL SELLER BE LIABLE FOR COSTS OF PROCESSING, LOST PROFITS, INJURY TO GOODWILL, OR ANY OTHER CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY KIND RESULTING FROM THE ORDER OR USE OF ITS PRODUCT, WHETHER ARISING FROM BREACH OF WARRANTY, NONCONFORMITY TO ORDERED SPECIFICATIONS, DELAY IN DELIVERY, OR ANY LOSS SUSTAINED BY THE BUYER.
BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR REPLACEMENT AT THE FACTORY OF SELLER, ANY COMPONENT WHICH SHALL, WITHIN THE APPLICABLE WARRANTY PERIOD DEFINED HEREIN AND UPON PRIOR WRITTEN APPROVAL, BE RETURNED TO SELLER WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE; EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER, BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. FOR GAS-FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS, BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO TEN YEARS FROM DATE OF SHIPMENT FROM SELLER.
These warranties are issued only to the original owner-user and cannot be transferred or assigned. No provision is made in these warranties for any labor allowance or field labor participation. Seller will not honor any expenses incurred in its behalf with regard to repairs to any of Seller’s products. No credit shall be issued for any defective part returned without proper written authorization (including, but not limited to, model number, serial number, date of failure, etc.) and freight prepaid.
OPTIONAL SUPPLEMENTAL WARRANTY Provided a supplemental warranty has been purchased, Seller extends the
warranty herein for an additional four (4) years on certain compressors. Provided a supplemental warranty has been purchased, Seller extends the warranty herein for an additional four (4) years or nine (9) years on certain heat exchangers.
EXCLUSION OF CONSUMABLES & CONDITIONS BEYOND SELLER’S CONTROL
This warranty shall not be applicable to any of the following items: refrigerant gas, belts, filters, fuses and other items consumed or worn out by normal wear and tear or conditions beyond Seller’s control, including (without limitation as to generality) polluted or contaminated or foreign matter contained in the air or water utilized for heat exchanger (condenser) cooling or if the failure of the part is caused by improper air or water supply, or improper or incorrect sizing of power supply.
Component
Applicable Models
Heat Exchangers
Gas-Fired Units
Heat Exchangers
Low Intensity Infrared Units
Compressors
Condensing Units for Cassettes
Burners
Low Intensity Infrared Units
Other
Components excluding Heat Exchangers, Coils, Condensers, Burners, Sheet Metal
Heat Exchangers/Coils
Indoor and Outdoor Duct Furnaces and System Units, Steam/Hot Water Units, Oil-Fired Units, Electric Units, Cassettes, Vertical Unit Ventilators, Geothermal Units
Compressors
Vertical Unit Ventilators, Geothermal Units
Burners
High Intensity Infrared Units
Sheet Metal Parts
All Products
TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE HUNDRED TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN SIXTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN EIGHTEEN MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
“APPLICABLE WARRANTY PERIOD”
As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.
© Modine Manufacturing Company 2016
Modine Manufacturing Company
1500 DeKoven Avenue Racine, WI 53403 Phone: 1.877.679.4436 (4GEO) www.modinehvac.com
Loading...