NOTE:
Energy Star only
applies to certain
configurations.
WArNING
This unit contains R-410A high pressure refrigerant.
Hazards exist that could result in personal injury
or death. Installation, maintenance, and service
must only be performed by an HVAC technician
quali ed in R-410A refrigerant and using proper
tools and equipment. Due to much higher pressure
of R-410A refrigerant, DO NOT USE service
equipment or tools designed for refrigerants other
than R-410A.
WArNING
Improper installation, adjustment, alteration,
service or maintenance can cause property
damage, injury or death, and could cause
exposure to substances which have been
determined by various state agencies to cause
cancer, birth defects or other reproductive harm.
Read the installation, operating and maintenance
instructions thoroughly before installing or
servicing this equipment.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
ImpOrTANT
1. The use of this manual is speci cally intended
for a quali ed installation and service agency.
A quali ed installation and service agency must
perform all installation and service of these
appliances.
2. GH/EH units contain the refrigerant R-410A.
Review the R-410A Material Safety Data Sheet
(MSDS) for hazards and rst aid measures.
3. Refrigerant charging should only be carried out
by an EPA-certi ed air conditioning contractor.
Inspection On Arrival
1. Inspect unit upon arrival. In case of damage, report it
immediately to transportation company and your local factory
sales representative.
2. Check rating plate on unit to verify that power supply meets
available electric power at point of installation.
3. Inspect unit received for conformance with description of
product ordered (including speci cations where applicable).
THIS MANUAL IS THE PROPERTY OF THE OWNER.
SPECIAL PRECAUTIONS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS
IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE
SAFE, EFFICIENT, AND TROUBLE-FREE OPERATION. IN
ADDITION, PARTICULAR CARE MUST BE EXERCISED
REGARDING THE SPECIAL PRECAUTIONS LISTED
BELOW. FAILURE TO PROPERLY ADDRESS THESE
CRITICAL AREAS COULD RESULT IN PROPERTY
DAMAGE OR LOSS, PERSONAL INJURY, OR DEATH.
THESE INSTRUCTIONS ARE SUBJECT TO ANY MORE
RESTRICTIVE LOCAL OR NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation
which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which,
if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which,
if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided, MAY
result in a potential safety concern.
DANGEr
1. Appliances must not be installed where they may be exposed
to potentially explosive or ammable atmosphere.
2. Water temperatures over 125°F can cause severe burns
instantly resulting in severe injury or death. Feel water before
showering or bathing. Ensure that the primary water heating
source setpoints are higher than the heat pump water
discharge temperature of 120°F.
WArNING
1. Disconnect power supply before making wiring
connections to prevent electrical shock and equipment
damage.
2. All appliances must be wired strictly in accordance with
the wiring diagram furnished with the appliance. Any
wiring different from the wiring diagram could result in a
hazard to persons and property.
3. Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature
rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% greater than rated
voltage.
5. This unit contains R-410A high pressure refrigerant.
Hazards exist that could result in personal injury or
death. Installation, maintenance, and service must only
be performed by an HVAC technician qualied in R-410A
refrigerant and using proper tools and equipment. Due
to much higher pressure of R-410A refrigerant, DO NOT
USE service equipment or tools designed for refrigerants
other than R-410A.
6. When servicing or repairing this equipment, use only
factory-approved service replacement parts. A complete
replacement parts list may be obtained by contacting
Modine Manufacturing Company. Refer to the rating plate
on the appliance for complete appliance model number,
serial number, and company address. Any substitution of
parts or controls not approved by the factory will be at the
owner’s risk.
CAUTION
1. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% less than the rated
voltage.
2. Do not overcharge the refrigeration system. This can lead
to elevated compressor discharge pressure and possibly
ooding the compressor with liquid.
3. Do not attempt to reuse any mechanical or electrical
component which has been wet. Such component must
be replaced.
ImpOrTANT
1. Start-up and adjustment procedures must be performed
by a qualied service agency.
2. All refrigeration checks must be made by a qualied
R-410A refrigeration technician.
3. Do not release refrigerant to the atmosphere. When
adding or removing refrigerant, all national, state/province,
and local laws must be followed.
4. The ground heat exchanger (open or closed loop or water
source to be connected to the unit must be designed,
constructed, and prepared in accordance with industry
guidelines (IGSHPA, ASHRAE, NGWA, etc.) and best
practices, and any more restrictive local codes and
regulations by a qualied service agency. Failure to
properly, size, install, or prepare the source could result
in reduced performance, a reduction in the normal life of
the units, and a hazard to persons and property.
5. Units selected for open loop ground source applications
should have a cupronickel source coaxial heat exchanger
to reduce mineral buildup and scaling. Open loop systems
should have the source coaxial coil ushed periodically to
maintain peak performance.
6. All piping and connections must be made in accordance
with local plumbing codes.
7. To check most of the Possible Remedies in the
troubleshooting guide listed in Tables 20.1-22.1, refer to
the applicable sections of the manual.
Table of Contents
General Information ..................................1
Inspection on Arrival ..................................1
Special Precautions ..................................2
Model/Serial Number Designations ......................3
Unit Dimensions .....................................4
SI (Metric) Conversion Factors..........................6
Unit Location........................................6
"W.C. 0.24 kPa
psig 6.893 kPa
°F
inches 25.4 mm
feet 0.305 meters
CFM 0.028 m
(°F-32) x 0.555
°C
To Convert Multiply By To Obtain
CFH 1.699 m3/min
3
0.0374 mJ/m
Btu/ft
pound 0.453 kg
Btu/hr 0.000293 kW/hr
gallons 3.785 liters
3
/min
psig 27.7 "W.C.
3
UNIT LOCATION
DANGEr
Appliances must not be installed where they may be exposed to
potentially explosive or ammable atmosphere.
Handling
Each unit will be shipped to the site on a wood skid. Whenever
possible, all lifting and handling of the unit should be done with
the packing and skid in position.
When slinging or using a forklift to lift the unit, the support points
should be sufciently apart to give stability when lifting. Unless
otherwise noted, the lifting points should be equidistant from the
centerline. Extreme care should be taken not to drop the unit.
Considerable damage can occur to the unit during positioning,
in particular, to the paneling and exterior paint. Use an adequate
number of personnel and the correct tools when moving the unit.
The unit is designed to remain upright so care should be taken
when lifting the unit up steps.
The use of torque screwdrivers on panel, cover or component
mounting screws is not recommended. Hand-start all screws.
If electric drills are used – set at the lowest possible torque.
Preparation
1. Before installation, ensure that the correct electrical power
supplies are available for the unit.
2. Each unit requires an independently fused and isolated power
supply.
3. Check to make sure that the units will have adequate
installation clearance for easy access to remove all panels
and access all internal components. Provide ample area
to access external components in and around the unit and
system including water valves, ttings, and all electrical
connections.
4. Remove any accessory kits and shipping support material
from the mechanical compartment.
5. Check refrigerant piping for dents or kinks.
6. Inspect all electrical connections. Connections must be clean
and tight at the terminal.
Electrical
Electrical wiring should be done in accordance with all
applicable national and local codes. It is the responsibility of the
electrical contractor to adhere to such codes. The warranty will
be voided if wiring is not in accordance with the specications of
the unit. Modine recommends using copper conductors only.
All power supply wiring must be capable of carrying the
maximum current load under no fault conditions at the stipulated
voltages. Care should be taken to avoid signicant voltage drops.
A knockout for power connection is provided on the access side
of the unit. See unit dimensions.
INSTALLATION
ImpOrTANT
Storage
Equipment should be stored in clean, dry area and in its original
packaging.
Do not store or install units in corrosive environments or
in locations subject to temperature or humidity extremes.
Performance, reliability, and service life can be signicantly
reduced. Transport and store units in an upright position. Tilting
units greater than 60° beyond horizontal may result in damage
to the compressor. If the unit is tilted past 60°, do not energize
the compressor until the unit has been upright for a minimum of
6 hours to prevent compressor damage.
Unit Protection
To prevent damage, keep the unit in its original packaging or
cover with an equivalent protective covering while on the job
site. Cover open water connections to prevent debris from
entering the system. Take extra precautions to protect the unit
from damage or contamination when in an area where spraying,
plastering and / or painting has not been completed. Physical
damage or contamination from foreign debris may prevent
proper start-up and costly equipment clean-up. Examine all
ttings, valves, or pipes and remove all dirt or debris before
installing unit.
1. The ground heat exchanger (open or closed loop)
or water source to be connected to the unit must be
designed, constructed, and prepared in accordance with
industry guidelines (IGSHPA, ASHRAE, NGWA, etc.)
and best practices, and any more restrictive local codes
and regulations by a qualied service agency. Failure to
properly, size, install, or prepare the source could result in
reduced performance, a reduction in the normal life of the
units, and a hazard to persons and property.
2. Units selected for open loop ground source applications
should have a cupronickel source coaxial heat exchanger
to reduce mineral buildup and scaling. Open loop systems
should have the source coaxial coil ushed periodically to
maintain peak performance.
Installation of these units is to be INDOORS only. The
instructions detailed below are for the Installation of a
“Standard” unit. Accommodations and adjustments will be
required for the usage of additional unit accessories. Should
assistance be required for the installation of these additional
items, consult Modine at the phone number listed on the back
cover of this manual.
6
GEO16-504.2
INSTALLATION
Unit Installation
1. Units should be mounted on a vibration-absorbing pad slightly
larger than the base of the unit. See Table 7.1 below for
Modine vibration pad part numbers. If the unit isn’t mounted
on a vibration-absorbing pad, it must be raised off the oor
to prevent damage due to accidental ooding. It is not
necessary to anchor the unit to the oor.
Table 7.1 - Vibration Absorbing Pads -
High Density Plastic
Pad SizePart NumberModels
32" X 32"5H0835220000036
36" X 36"5H0835230000048-132
2. Check to ensure that the unit is level in both directions and
also plumb. If adjustment is necessary, Modine recommends
the placement of metal shims in the outermost corners of the
base.
3. Provide adequate clearance for all access panels.
4. Provide easy access for servicing water valves, ttings and
compressor.
5. Provide access to the controller and all electrical connections.
6. Provide a clear physical path to the unit. Adequate space
should be provided to allow removal of the unit, if necessary.
Figure 7.1 - Water Connection Breakdown
Water Connections
1. All units utilize swivel pipe ttings for water connections that
are rated for 150 psi.
2. The connections have a rubber gasket seal similar to a garden
hose gasket, which, when mated to the ush end of most 1"
threaded male pipe ttings (MPT), provides a leak-free seal
without the need for thread sealing tape or joint compound.
3. The water piping system should include pressure/temperature
taps for serviceability.
4. Install the brass spacer and rubber gasket in swivel connector
prior to attempting any connection, as shown in Figure 7.1
(rubber gasket and brass spacer kits are shipped with unit). To
make the connection, mate the eld supplied male pipe thread
tting against the rubber gasket in the swivel connector and
thread the female locking ring onto the pipe threads, while
maintaining the brass elbow in the desired direction. Tighten
the connectors by hand, and then gently snug the tting with
pliers to provide a leak-proof joint.
5. DO NOT OVERTIGHTEN, as leaks may occur.
6. NOTE: Never use exible hose smaller than 1" inside
diameter on the unit. Limit the length to 10' per connection in
one direction. Check carefully for leaks.
Factory installed
Snap ring in
this groove
Swivel adaptor
hand tighten
Brass snap ring
Brass spacer
Rubber gasket
Swivel adaptor
hand tighten
P/T Port - access
for temperature
and pressure
GEO16-504.2
7
INSTALLATION
Hot Water Generator (Desuperheater)
Installation (If Equipped)
DANGEr
Water temperatures over 125°F can cause severe burns
instantly resulting in severe injury or death. Feel water before
showering or bathing. Ensure that the primary water heating
source setpoints are higher than the heat pump water discharge
temperature of 120°F.
ImpOrTANT
All piping and connections must be made in accordance with
local plumbing codes.
A minimum 50 gallon water heater is recommended with the
Desuperheater (DHW) option. Higher demand applications may
use either one 80 gallon water heater or two 50 gallon water
heaters piped in series. The hot water tank should be allowed
to stratify by lowering the bottom element setpoint to 100°F and
setting the top element setpoint to 125°F. Operation of the DHW
is controlled by a sensor located on the domestic water in line,
which must not be removed. Hot water will only be produced
when the unit is running a conditioning cycle.
The desuperheater pump is disabled on delivery from the
factory. It must be enabled by wiring the pump in the unit control
panel after the DHW piping has been completed and purged.
This is to prevent the domestic hot water pump from running
before the DHW tank is piped to the heat pump. DHW option
must not be enabled until all piping is complete and the DHW
loop has been purged and bled or damage can occur.
Poor domestic water quality may result in debris buildup
in the system. A water softener is recommended with hard
water (greater than 10 grains or 170 total hardness). Extreme
hard water will require additional maintenance and should be
considered with the DHW option, as maintenance costs may
outweigh potential savings.
Make sure all local electrical and plumbing codes are met for
installing a hot water generator. The installing contractor is
responsible for performing the installation accordingly.
Water piping lengths must be kept at a minimum. DO NOT use
a one way length greater than 50'.
Coaxial drain tees that provide an inlet and outlet to the heat
pump from the drain connection are not recommended. The
decreased diameter of the inlet and outlet pipes to the heat
pump make it possible for debris build up and completely stop
the ow of water to and from the desuperheater.
All components should be located in a conditioned space that is
maintained above 50°F at all times.
1. Turn off power or fuel supply to the water heater.
2. Close cold water supply valve to heater.
3. Drain and ush the tank, then remove the drain valve.
4. Inspect the water heater cold water inlet pipe for a check
valve and remove if present. Failure to do so will result in
damage to the unit.
5. Use a tee to connect the cold water supply pipe to the DHW
in connection on the unit. Be sure to install a check valve
rated for at least 1/2" PSI and a shutoff valve on the cold
water inlet pipe. Also install a shutoff valve on the supply line
to the unit, as well as an air vent at the highest point of the
system.
6. Run DHW piping using a minimum of 1/2" OD copper tubing.
See Table 8.1 for recommended line sizes.
7. Use a tee to connect the unit DHW out connection to the
water heater drain connection. Be sure to install a shutoff
valve on the pipe as near to the water heater as possible.
8. Reinstall the drain valve on one side of the tee.
Figure 8.1 - Typical DHW Piping Diagram
COLD
HOT
WATER
IN
OUT
AIR VENT
DHW IN
DHW OUT
DRAIN CONNECTION
WATER
DRAIN VALVE
Figure 8.2 - Typical DHW Piping Diagram with Two
Tanks
AIR VENT
DHW IN
DHW OUT
DRAIN CONNECTION
COLD
WATER
IN
TANK 1
HEATING
SOURCE
DISABLED
DRAIN VALVE
HOT
WATER
OUT
COLD
WATER
HOT
WATER
OUT
IN
Table 8.1 - DHW Pipe Sizes ➀
Maximum pipe length (one way) to achieve optimum ow
ModelsDHW Flow (gpm)1/2" Copper3/4" Copper
0361.250-
048 & 096
060 & 120
066 & 132
096, 120, and 132 are stacked units, data is for individual unit.
9. Open all valves, except the system drain valve, and ll the
system with water. Bleed all air and check for leaks.
10. Insulate all piping with 3/8" closed cell insulation.
11. Refer to “Start Up Procedure” for DHW setup and start up.
1.64550
2.02550
2.41050
8
GEO16-504.2
INSTALLATION
Wiring
WArNING
1. Disconnect power supply before making wiring
connections to prevent electrical shock and equipment
damage.
2. All appliances must be wired strictly in accordance with
the wiring diagram furnished with the appliance. Any
wiring different from the wiring diagram could result in a
hazard to persons and property.
3. Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature
rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% greater than rated
voltage.
CAUTION
Ensure that the supply voltage to the appliance, as indicated
on the serial plate, is not 5% less than the rated voltage.
Installation of wiring must conform with local building codes,
or in the absence of local codes, with the National Electric
Code ANSI/NFPA 70 - Latest Edition. Unit must be electrically
grounded in conformance to this code. In Canada, wiring must
comply with CSA C22.1, Part 1, Electrical Code.
Electric wiring must be sized to carry the full load amp draw of
the motor, starter and any controls that are used with the unit.
See Table 11.1 for electrical data.
Any damage to or failure of units caused by incorrect wiring of
the units is not covered by warranty.
Terminal Strip Connections
The terminal strip connections are designed to clamp down on
the wires. To properly connect the wires to the terminal strip:
1. Push a small at-head screwdriver into the square hole on the
terminal. Press rmly until the screwdriver hits the back stop
and opens the terminal (see Figure 9.1).
2. Remove approximately 3/8" of insulation from the end of
the wire and push the stripped wire into the oval hole in the
terminal.
3. Remove the screwdriver. Pull on the wire to make sure that it
is securely clamped in the terminal.
4. Make sure that the terminal clamp is in contact with bare wire
(insulation removed).
Figure 9.1 - Terminal Strip
Unit Power Connection
Refer to the unit serial plate for unit voltage and phase.
Available power must be the same as indicated on serial plate.
Remove access panel and electrical box cover. Using unit
power knockout, route power lines through unit and into main
electrical panel. Connect line voltage wires to the L1 and L2
(& L3, if three phase voltage) lugs of the contactor. Consult the
unit electrical data on the serial plate for correct overcurrent
protection sizing. Connect ground wire to ground lug in electrical
panel. Replace electrical box cover and access panel prior to
unit startup.
Hot Water Generator Pump Wiring
The domestic hot water pump is not wired in the factory to
prevent pump burnout in case the unit is powered before the
domestic hot water tank is plumbed or full of water. Refer to the
control manual for instructions on enabling the pump.
Transformer Wiring
The system supplies the power to the controller via a 24V
transformer. On 208V systems, the transformer is factory
wired and is ready for operation. On 208-230V systems, the
transformer comes factory wired for 230V operation. If the unit
is to be powered with 208V, the transformer must be wired for
208V. A terminal strip with a jumper is provided for easy eld
conguration (see Figure 10.1). Refer to the wiring diagram
provided with the unit for details.
GEO16-504.2
9
INSTALLATION
Figure 10.1 - 208-230V Transformer Wiring
Hydronic Pump Wiring
The hydronic pump must be connected to the terminal blocks
in the electrical box. The pumps will automatically be cycled as
required by the unit. Be sure to wire the pump prior to turning
the system on.
Aquastat Wiring
The aquastat wires are connected directly to the terminal blocks
in the electrical box.
Open Loop Control Valve Wiring
Always maintain water pressure in the heat exchanger by
placing water control valves at the outlet of the unit to prevent
mineral precipitation during the off cycle. Pilot operated slow
closing valves are recommended to reduce water hammer. If
water hammer persists, an expansion tank can be mounted
on the piping to help absorb the excess hammer shock. Slow
closing valve must have an end switch that enables/disables the
compressor. See Figure 10.2 for proper wiring.
Figure 10.2 - Optional Open Loop Valve Wiring
Flow Center Wiring
The ow center must be connected to the terminal blocks in
the electrical box. The pumps will automatically be cycled as
required by the unit. Be sure to wire the ow center prior to
turning the system on.
Sensor Wiring
All sensors are factory wired and installed.
10
GEO16-504.2
ELECTRICAL SPECIFICATIONS
Table 11.1 - Electrical Ratings
Models
036
048
060
066
096
120
132
Stacked unit, electrical data is for individual unit.
Start-up and adjustment procedures must be performed by a
qualied service agency.
The unit has been factory tested and set for proper operation,
but a full unit start-up is recommended.
NOTE: If any abnormal operation occurs during the startup
procedure, refer to the troubleshooting section.
NOTE: Always start the system in heating mode.
Pre-Start Checks
Before applying power to heat pump, use the following checklist
to ensure a complete and proper installation.
• Check that the supply voltage matches the unit supply voltage
listed on the unit serial plate.
• Verify that all wiring is secure and properly protected.
• All high voltage wiring is correct including, fuses, breakers and
wire sizes.
• Trace circuits to insure that the unit has been wired according
to the wiring diagram.
• Check that the unit has no visible damage and that all the
components are secure.
• Check that all eld electrical and mechanical work has been
performed according to all applicable Federal, State, and Local
codes.
• Check the supply voltage to the unit is within +/- 5% of the
voltage on the unit serial plate.
• Low voltage wiring for aquastat, control wiring and the freeze
protection setpoint completed.
• Transformer wiring is correct.
• Water supply to and load piping from heat pump is completed.
• Piping completed, water system cleaned and ushed of debris.
• Air and debris are purged from ground and load loops.
• Antifreeze added to ground and load loops, as required.
• Isolation valves are open, water control valves or loop pumps
wired.
• DHW piping is complete, all air purged from system and
charged with water.
• IMPORTANT: Ensure all valves in the DHW circuit are fully
open and pump is wired correctly.
• Service/access panels are in place.
• Entering water temperatures are within operating limits in
Table 14.1.
Verify that ALL water control valves are open and allow
water ow prior to engaging the compressor. Freezing of the
coax or water lines can permanently damage the heat pump.
CAUTION
To avoid equipment damage, DO NOT leave system lled in
a building without heat during the winter unless antifreeze
is added to the water loop. Heat exchangers never fully
drain by themselves and will freeze unless winterized with
antifreeze.
Controller Setup
GH/EH systems are pre-programmed from the factory for easy
installation, no installer setup is required for the unit to function.
The DHW pump is not wired from the factory on all units. This
is done to protect the pump during installation and startup. If a
DHW pump is in the system, it must be wired.
ImpOrTANT
Ensure that the freeze protection setpoint is properly set
(approximately 10°F above the uid freeze point) for the type
and percentage of uid used in the ground loop.
Table 12.1 - Freeze Point of Pure Antifreeze
Solutions, °F ➀
% Vol.MethanolEthanol
5.026.229.529.3
7.523.028.127.7
10.019.726.426.1
12.516.224.624.4
15.012.622.622.5
17.58.820.420.5
20.04.918.118.4
22.5—15.616.1
25.0—12.913.8
27.5—10.011.3
30.0—7.08.8
➀
All values are typical, refer to antifreeze manufacturer data sheets for actual values.
Propylene
Glycol
12
GEO16-504.2
START-UP PROCEDURE
Unit Startup Procedure
The Startup / Troubleshooting form found on page 23 of this
manual may be used to assist during unit startup.
1. Put aquastat in standby or off mode.
2. Turn on line power to heat pump.
3. Slowly raise the aquastat set-point until a heating call is
generated and the compressor energizes.
4. After a few minutes, check the load out temperature and
verify warm water delivery.
5. Verify water ow by comparing pressure drop across the
coaxial coil to values in Table 13.1.
6. Monitor ground water supply (GWI) and return (GWO)
temperatures. If temperature drop is within expected
operating range as shown in Table 14.1, continue with
testing.
7. If temperature drop is outside of expected operating range,
check refrigerant pressures and compare to values in
Table 14.1.
8. Check for vibration, noise and leaks.
9. Lower aquastat set point below tank temperature and verify
that compressor and ow center deactivate.
10. Initiate a control signal to place the unit in the cooling mode.
Cooling set point must be set below room temperature.
11. Cooling will energize after a time delay.
12. Be sure that the compressor and ow center are activated.
13. Monitor ground water supply (GWI) and return (GWO)
temperatures. If temperature rise is within expected
operating range in Table 14.1, continue with testing.
14. If temperature drop is outside of expected operating range,
check refrigerant pressures and compare to Table 14.1.
15. Check for vibration, noise and leaks.
16. Adjust the cooling set point above the tank temperature and
verify that the compressor and ow center deactivate.
17. If unit fails to operate as described, see troubleshooting
section. If the unit still does not operate properly, contact
Modine at the number listed on the back of this manual.
18. When testing is complete, set system to normal operating
mode.
DHW Startup Procedure
1. If the DHW was wired, the DHW pump will run whenever
the heat pump is running and the DHW Supply temperature
is below 120°F and the discharge temperature is above
100°F.
2. To verify operation of the DHW pump, ensure that the heat
pump is running and the DHW temperature is below 120°F
and the discharge temperature is above 100°F.
3. The temperature rise across the desuperheater should be
5-10°F.
Sequence of Operation
The unit’s controller will monitor calls for heat or cooling by
aquastat.
Cool: When the temperature increases above the cooling
aquastat's set point and the dead band, the compressor and
reversing valve will be energized. The compressor will be limited
by a timer that will provide anti-cycle protection.
Heat: When the temperature falls below the heating aquastat's
set point and the dead band, the compressor will be energized
and the reversing valve de-energized. The compressor will be
limited by a timer that will provide short-cycle protection.
Open Loop Systems: An optional valve can be tted to stop
water ow when the compressor is not energized. This allows
the variable pumping system to work more efciently.
Table 13.1 - Water Pressure Drop, psi
(Based on Entering Water Temperature)
ModelsGPM30°F40°F60°F90°F110°F
036
048
060
066
096
120
132
Pressure drop is for individual unit.
Table 13.2 - Antifreeze Pressure Drop Corrections
Antifreeze Type
Ethylene Glycol
Propylene Glycol
Equation 13.1 - Coaxial Coil Pressure Drop
Antifreeze Correction
To nd actual pressure drop through either coaxial coil
when the unit is operated with an antifreeze solution, rather
than water:
Where:
WPD
WPD
ACF = Antifreeze Correction Factor from Table 18.2
NOTE: Limits are acceptable for start-up conditions only.
Min / max limits are intended for bringing the space up / down
to normal temperatures. Units are not designed to operate at
the min / max conditions on a continual or regular basis. The
operating limits are dependent upon three primary factors:
and 3) ow rate (gpm). When any of the factors are at the
minimum or maximum levels, the other two factors must be at
the normal level for proper and reliable unit operation.
14
GEO16-504.2
START-UP PROCEDURE / PHYSICAL DATA
Table 15.1 - Refrigerant Circuit Malfunctions and Probable Causes ➀
The following chart will assist in troubleshooting and diagnosing causes of a problematic unit. The chart provides general guidance
for system measurements relative to typical operating conditions.
➀ Restricted filter / drier will have symptoms similar to restricted TXV. Check temperature drop across filter driver to verify a restriction.
➀
Head Press.
HighLowLow / NormalHighHighLowLow
Suct.
Press.
Comp Amp
Draw
SuperheatSubcool
Load
Temp Diff.
Water (Source)
Temp Diff
PHYSICAL DATA
Table 15.2 - Physical Data
Models036048060066096120132
Reversible (H),
Non-Reversible (W)
Factory Charge, R-410A,
oz (per Unit)
Factory Charge, R-410A,
oz (per Unit) - w/HWG
Unit StyleSingle UnitStacked Unit
CompressorCopeland Scroll
HWHWHWHWHWHWHW
53517067101100112112706710110011211 2
5655747110410411511 5747110410411 511 5
GEO16-504.2
15
MAINTENANCE
MAINTENANCE
WArNING
When servicing or repairing this equipment, use only factoryapproved service replacement parts. A complete replacement
parts list may be obtained by contacting Modine Manufacturing
Company. Refer to the rating plate on the appliance for
complete appliance model number, serial number, and
company address. Any substitution of parts or controls not
approved by the factory will be at the owner’s risk.
CAUTION
Do not attempt to reuse any mechanical or electrical
component which has been wet. Such component must be
replaced.
ImpOrTANT
To check most of the possible remedies in the troubleshooting
guide listed in Tables 20.1-22.1, refer to the applicable
sections of the manual.
The routine care and maintenance of this unit will increase
longevity, provide for the proper operational performance, and
reduce the probability of failure.
Once the unit is operational, it will be necessary to perform
certain routine maintenance/service checks. Following is a
maintenance schedule with the recommended checks. If your
unit is equipped with special features, there may be additional
checks that are required. Consult Modine for assistance.
The use of torque screwdrivers on panel, cover or component
mounting screws is not recommended. Hand-start all screws.
If electric drills are used – set at the lowest possible torque.
Generally coaxial coil maintenance is not needed for closed
loop systems. However, if the piping is known to have high
dirt or debris content, best practice is to establish a periodic
maintenance schedule with the owner so the coil can be
checked on a regular basis. Dirty installations are typically the
result of deterioration of iron or galvanized piping or components
in the system.
Open cooling towers requiring heavy chemical treatment and
mineral buildup through water use can also contribute to higher
maintenance. Should periodic coil cleaning be necessary, use
standard coil cleaning procedures that are compatible with the
heat exchanger material and copper water lines.
Generally, with greater water ow rates, the likelihood of scaling
reduces. However, ow rates over 3 gpm per ton can produce
water (or debris) velocities that can erode the heat exchanger
wall and ultimately produce leaks.
Desuperheater Coils
If potable water is hard or not chemically softened, the high
temperature of the desuperheater can lead to scaling. This
results in more scheduled maintenance. A buffer tank may be
installed to help prevent scaling. Extreme hard water conditions
should not use the desuperheater option. Should periodic coil
cleaning be necessary, use coil cleaning procedures that are
compatible with the heat exchanger material and copper water
lines.
Compressor
Conduct annual amperage checks to insure that amp draw is no
more than 10% greater than indicated on the operating data.
Coaxial Coil Maintenance - Ground Water
Applications
If the system is installed in an area with a known high mineral
content (125 P.P.M. or greater), best practice is to establish a
periodic maintenance schedule with the owner so the coil can
be checked on a regular basis. Should periodic coil cleaning
be necessary, use coil cleaning procedures that are compatible
with the heat exchanger material and copper water lines.
Generally, with greater water ow rates, the likelihood of scaling
reduces. Therefore, the recommended minimum water ow is
1.5 gpm per ton. Recommended minimum ow rate for entering
water temperatures below 50°F is 2.0 gpm per ton.
Keep all air out of the water. An open loop system should be
checked to ensure that the well head is not allowing air to
inltrate the water line. Lines should always be airtight. Keep
the system under pressure at all times. It is recommended in
open loop systems that the water control valve be placed in
the discharge line to prevent loss of pressure during off cycles.
Closed loop systems must have positive static pressure.
16
GEO16-504.2
MAINTENANCE
Cabinet
If a ood occurs, try to expel water as soon as possible. Water
contact for any duration will cause corrosion on the cabinet
nish. All units mounted on the ground should be installed on
an absorption pad. This also helps prevent water from entering
the cabinet. If the cabinet is dirty, do not spray with water, use a
damp rag with mild detergent, and wipe the system clean.
Refrigerant System
The refrigerant circuit is sealed; service gauges should
not be used unless the system is not operating correctly.
The operational charts show correct pressures, ow and
temperature. Before servicing the refrigerant circuit, ensure that
the water ows are correct.
Replacement Parts
For ease of identication when ordering replacement parts
or contacting the factory about your unit, please provide the
complete model number and unit serial number. This information
can be found on the serial plate attached to your unit (see
Figure 17.1).
When a component part fails, a replacement part should be
obtained by contacting your local distributor or Modine Sales
Representative. Your sales representative can assist with
Return Material Authorizations (RMAs) and potential warranty
claims. The following details are required to process parts
orders and warranty claims:
1. Full description of part required, including unit’s model
When encountering a unit with operational faults, complete
these preliminary system checks before utilizing the
troubleshooting charts.
In order to maintain system integrity, performance and
efciency, do not install service gauges unless unit operation
appears abnormal and all other diagnostic checks are normal.
Verify water source and load side temperatures changes against
typical operating data. If the performance is within the ranges in
the table and the water ows have been veried, then gauges
may be installed in order to check subcooling and superheat.
1. Verify that the unit and ow center power supplies are on.
2. Verify that all fuses or disconnects switches are intact.
3. Inspect unit for obvious defects (e.g., leaking connections,
loose or damaged wiring, etc.).
4. Verify eld inputs and outputs (refer to wiring diagram).
a. Aquastat inputs – Aquastat inputs are 24VAC signals and
can be veried using a volt meter.
b. Outputs – Compressor and reversing valve output relays
are 24VAC and can be veried using a voltmeter. The ow
center and DHW pump are powered through 240V relays.
Operation can be veried using a voltmeter or clamp-on
ammeter.
5. After completing these checks, refer to the troubleshooting
tables on the next pages.
GEO16-504.2
19
TROUBLESHOOTING
Mode
Cause
Htg
Clg
Locked out on
safety controls
Table 20.1 - Troubleshooting
Fault
No power
to unit
XXPower FailureNo voltage at line side of compressor contactor.Check disconnect switch and power distribution panel.
XX
XX
Possible
Open disconnect
switch
Blown fuse /
circuit breaker
tripped
VerifyAction
At heat pump disconnect, voltmeter shows voltage on the
line side but not on the load side.
Check fuses and circuit breaker.
Determine why the disconnect switch was opened.
Close disconnect if safe to do so.
Reset circuit breaker or replace fuses with proper size and
type. Verify total load on system and proper fuse / circuit
breaker sizing.
Compressor
not
operating
XX
XXAquastat wiring Verify wiring at unit and signals at unit.Repair wiring, if needed.
XXTransformer
XX
XX
XX
XX
XX
XX
Low supply
voltage
Power wiring
defect
Defective
compressor
overload
Compressor
motor burn out
or open windings
Defective
compressor
contactor
Loss of
compressor run
signal
Voltmeter shows abnormally low voltage at heat pump
disconnect switch (below 95% of serial plate voltage).
Check primary and secondary transformer voltages.
Check transformer secondary voltage circuit breaker.Reset breaker if tripped.
Check for loose or broken wires at compressor, contactor
and capacitor.
Check for fault.Address lockout and cycle power to unit to reset controller.
Ensure that compressor is cool and overload has had
sufcient time to reset. Ohmmeter shows a resistance
across R & S terminals and OPEN or innite resistance
between C & R or C & S terminals.
Ohmmeter shows no resistance or OPEN between
common and run terminals.
*NOTE: Make sure the compressor is rested.
Voltage on line side and contactor pulled in, but no voltage
on one or both terminals on the load side.
Voltage on line side, 24VAC across contactor coil and no
voltage on load side.
Voltage on line side of contactor veried and contactor
won’t pull in. No 24VAC on compressor contactor coil when
24VAC is present at controller and controller fuse is intact.
Call power company.
If no primary, verify wiring.
If no, or low secondary, check transformer wiring.
If wiring ok, replace transformer.
Repair wiring, if needed.
If windings are open or overload is faulty, replace
compressor.
Troubleshoot cause and replace motor.
Points damaged. Replace contactor.
Bad coil, replace contactor.
Replace controller.
Unit
“short cycles”
XX
XXUnit is oversized Verify load calculations and unit selection.
XX
XX
Defective run
capacitor
Defective
compressor
overloads
Wiring and
controls
Measure resistance across capacitor terminals. If shorts
exist, capacitor is defective.
Ensure that compressor is cool and overload has had
sufcient time to reset. Ohmmeter shows a resistance
across R & S terminals and OPEN or innite resistance
between C & R or C & S terminals.
Examine all wiring points.Tighten all wiring points.
Replace, if faulty.
If windings are open or overload is faulty, replace
compressor.
20
GEO16-504.2
TROUBLESHOOTING
Table 21.1 - Troubleshooting
Fault
Low
pressure
cutout
Mode
Htg Clg
X
X
X
Possible
Cause
Reduced water
Scaled or plugged
coaxial coil
Water supply
too cold
Entering water
X
X
too cold
Reduced water
ow
ow
VerifyAction
Check ow center operation.Troubleshoot ow center.
Manually open water valve and measure water ow.Adjust to proper ow rate.
Plugged water strainer or lter.Replace or clean, if dirty.
Check temperature drop across coaxial coil.Clean, if necessary.
Verify GEO IN with temperature probe.
Measure return water temperature, should be above 50ºF. Bring return water temperature within design parameters.
Verify hydronic pump operation.Troubleshoot pump.
Manually open water valve and measure water ow.Adjust to proper ow rate.
Plugged water strainer or lter.Replace or clean, if dirty.
Verify loop sizing; verify that all air has been purged from
ground heat exchanger; bring water temperature within
design parameters.
High
pressure
cutout
XX
X
XXRestricted TXVVerify superheat and subcooling values.Replace, if necessary.
XX
X
X
XX
XX
XXRestricted TXVVerify superheat and subcooling values.Replace, if necessary.
XX
Low refrigerant
charge
Plugged bi-ow
lter / drier
Defective low
pressure switch
Reduced water
X
X
X
ow
Water supply
too hot
Scaled or plugged
coaxial coil
Reduced water
Water
temperature out
of range
Defective high
pressure switch
Overcharged with
refrigerant
Non-condensables
in system
low
Check for refrigerant leaks.
Verify that low pressure cut-out occurs in heating mode
and not in cooling mode.
Monitor suction pressure while operating, verify low
pressure cut-out pressure (25 +/- 5 psig).
Check ow center operation.Troubleshoot ow center.
Manually open water valve and measure water ow.Adjust to proper ow rate.
Plugged water strainer or lter.Clean or replace.
Verify GEO IN with temperature probe.
Check temperature drop across coaxial coil.Clean, if necessary.
Manually open water valve and measure water ow.Adjust to proper ow rate.
Plugged water strainer or lter.Replace or clean, if dirty.
Measure return water temperature, should be below 90ºF. Bring return water temperature within design parameters.
Monitor discharge pressure while operating, verify high
pressure cut-out pressure (600 +/- 25 psig).
Verify superheat and subcooling values.Evacuate and recharge to factory recommended charge.
Verify superheat and subcooling values.Evacuate and recharge to factory recommended charge.
If leaks found, evacuate, repair and recharge to factory
recommended charge.
Replace lter if necessary.
Replace, if defective.
Verify loop sizing; bring water temperature within design
parameters.
Replace, if defective.
GEO16-504.2
21
TROUBLESHOOTING
Table 22.1 - Troubleshooting
Fault
Mode
Htg Clg
Loss of control
X
Possible
Cause
signal
VerifyAction
In cooling mode, verify 24VAC at RV coil and at REV
terminals.
If 24VAC exists, troubleshoot RV and coil. If no control
signal, troubleshoot aquastat signals.
Unit
will not
operate
in cooling
mode
Insufcient
cooling or
heating
Noisy unit
Defective
X
reversing valve
Aquastat
X
setup / wiring
Aquastat
X
operation
No water ow,
X
high pressure
cutout
XXUnit undersized Verify load calculations and unit selection.
Defective
X
reversing valve
XX
XXAmbient losses
XX
XX
XX
X
XXRestricted TXVVerify superheat and subcooling values.Replace, if necessary.
XXCompressorTroubleshoot compressor operation.
XX
XX
XXRemove compressor mounting bolts.
XX
Reduced water
ow
Low refrigerant
charge
Scaled or plugged
coaxial coil
Reduced water
ow
Water supply
X
too hot
Water supply
too cold
Non-
condensables
in system
Compressor
Rattles and
vibrates
Verify operation of reversing valve and solenoid coil.
Verify aquastat setup and wiring.Repair wiring, if needed.
Verify proper aquastat signals to unit.Replace, if necessary.
Check ow with ow meter.Check pump operation.
Verify operation of reversing valve and solenoid coil.
Defective reversing valve creating bypass of refrigerant
from discharge to suction side of compressor.
Manually open water valve and measure water ow.Replace or clean if dirty.
Plugged water strainer or lter.Replace or clean, if dirty.
Check for losses / gains due to ambient air inltration
through doors and windows.
Check superheat and subcooling values. Check for
refrigerant leaks.
Check temperature drop across coaxial coil.Clean, if necessary.
Check ow center operation.Troubleshoot ow center.
Manually open water valve and measure water ow.Adjust to proper ow rate.
Plugged water strainer or lter.Replace or clean, if dirty.
Verify GEO IN with temperature probe.
Verify GEO IN with temperature probe.
Verify superheat and subcooling values.
Make sure the compressor is not in direct contact with the
base or sides of the cabinet. Cold surroundings can cause
liquid slugging, increase ambient temperature.
Check for loose screws, panels, or internal components.
Tighten and secure. Piping could be hitting the metal
surfaces. Add insulation between the contact.
Replace, if defective. When it is necessary to replace the
reversing valve, wrap it with a wet cloth and direct the heat
away. Excessive heat can damage the valve.
If excessive, it may possible to rectify with shading and
insulation.
Replace, if defective. When it is necessary to replace the
reversing valve, wrap it with a wet cloth and direct the heat
away. Excessive heat can damage the valve.
Address issue.
If leaks found, evacuate, repair and recharge to factory
recommended charge.
Verify loop sizing; bring water temperature within
design parameters.
Verify loop sizing; bring water temperature within
design parameters.
If discharge pressure is too low and suction pressure
too high, compressor is not pumping properly. Replace
compressor.
Evacuate and recharge to factory recommended
charge.
XXPump cavitation Purge air from closed loop system.
22
GEO16-504.2
START UP / TROUBLESHOOTING FORM
Loop Type _________________
_______________
_______
When
Technician Notes
Customer Name ______________________________________ Date ________________
Note: In orderto maintain optimalperformance,DO NOThook up pressure gauges during start up procedures.
Note: In order to maintain optimal performance, DO NOT hook up pressure gauges during start up procedures.
troubleshooting,conductwaterside analysisfirst.Ifwater-side performance is poor,use of pressure gauge and
When troubleshooting, conduct water side analysis rst. If water side performance is poor, use of pressure gauge
refrigerantside analysismaybe required.
and refrigerant side analysis may be required.
Technician Notes
GEO16-504.2
23
COMMERCIAL WARRANTY (For Residential Warranty, see GEO16-510)
Seller warrants its products to be free from defects in material and
workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use
of materials substituted under emergency conditions for materials normally
employed. This warranty covers replacement of any parts furnished from the
factory of Seller, but does not cover labor of any kind and materials not
furnished by Seller, or any charges for any such labor or materials, whether
such labor, materials or charges thereon are due to replacement of parts,
adjustments, repairs, or any other work done. This warranty does not apply to
any equipment which shall have been repaired or altered outside the factory of
Seller in any way so as, in the judgment of Seller, to affect its stability, nor
which has been subjected to misuse, negligence, or operating conditions in
excess of those for which such equipment was designed. This warranty does
not cover the effects of physical or chemical properties of water or steam or
other liquids or gases used in the equipment.
BUYER AGREES THAT SELLER’S WARRANTY OF ITS PRODUCTS TO BE
FREE FROM DEFECT IN MATERIAL AND WORKMANSHIP, AS LIMITED
HEREIN, SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER
WARRANTIES, EITHER EXPRESS OR IMPLIED, WHETHER ARISING
FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE,
THERE ARE NO OTHER WARRANTIES, INCLUDING WARRANTY OF
MERCHANTABILITY OR FITNESS FOR PURPOSE, WHICH EXTEND
BEYOND THE PRODUCT DESCRIPTION CONFIRMED BY BUYER AND
SELLER AS OF THE DATE OF FINAL AGREEMENT.
This warranty is void if the input to the product exceeds the rated input as
indicated on the product serial plate by more than 5% on gas-fired and oil-fired
units, or if the product in the judgment of SELLER has been installed in a
corrosive atmosphere, or subjected to corrosive fluids or gases, been subjected
to misuse, negligence, accident, excessive thermal shock, excessive humidity,
physical damage, impact, abrasion, unauthorized alterations, or operation
contrary to SELLER’S printed instructions, or if the serial number has been
altered, defaced or removed.
BUYER AGREES THAT IN NO EVENT WILL SELLER BE LIABLE FOR
COSTS OF PROCESSING, LOST PROFITS, INJURY TO GOODWILL, OR
ANY OTHER CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY KIND
RESULTING FROM THE ORDER OR USE OF ITS PRODUCT, WHETHER
ARISING FROM BREACH OF WARRANTY, NONCONFORMITY TO
ORDERED SPECIFICATIONS, DELAY IN DELIVERY, OR ANY LOSS
SUSTAINED BY THE BUYER.
BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL
OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR
REPLACEMENT AT THE FACTORY OF SELLER, ANY COMPONENT WHICH
SHALL, WITHIN THE APPLICABLE WARRANTY PERIOD DEFINED HEREIN
AND UPON PRIOR WRITTEN APPROVAL, BE RETURNED TO SELLER
WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE
EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE;
EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A
COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER,
BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE
LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. FOR
GAS-FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS
AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS, BUYER’S
REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO
TEN YEARS FROM DATE OF SHIPMENT FROM SELLER.
These warranties are issued only to the original owner-user and cannot be
transferred or assigned. No provision is made in these warranties for any
labor allowance or field labor participation. Seller will not honor any expenses
incurred in its behalf with regard to repairs to any of Seller’s products. No
credit shall be issued for any defective part returned without proper written
authorization (including, but not limited to, model number, serial number,
date of failure, etc.) and freight prepaid.
OPTIONAL SUPPLEMENTAL WARRANTY
Provided a supplemental warranty has been purchased, Seller extends the
warranty herein for an additional four (4) years on certain compressors.
Provided a supplemental warranty has been purchased, Seller extends the
warranty herein for an additional four (4) years or nine (9) years on certain
heat exchangers.
EXCLUSION OF CONSUMABLES & CONDITIONS BEYOND SELLER’S
CONTROL
This warranty shall not be applicable to any of the following items: refrigerant
gas, belts, filters, fuses and other items consumed or worn out by normal wear
and tear or conditions beyond Seller’s control, including (without limitation as
to generality) polluted or contaminated or foreign matter contained in the air or
water utilized for heat exchanger (condenser) cooling or if the failure of the part
is caused by improper air or water supply, or improper or incorrect sizing of
power supply.
Component
Applicable Models
Heat Exchangers
Gas-Fired Units
Heat Exchangers
Low Intensity Infrared Units
Compressors
Condensing Units for Cassettes
Burners
Low Intensity Infrared Units
Other
Components excluding Heat Exchangers,
Coils, Condensers, Burners, Sheet Metal
Heat Exchangers/Coils
Indoor and Outdoor Duct Furnaces and
System Units, Steam/Hot Water Units,
Oil-Fired Units, Electric Units, Cassettes,
Vertical Unit Ventilators, Geothermal Units
Compressors
Vertical Unit Ventilators, Geothermal Units
Burners
High Intensity Infrared Units
Sheet Metal Parts
All Products
“APPLICABLE WARRANTY PERIOD”
TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE HUNDRED
TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN SIXTY-SIX
MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
EIGHTEEN MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.
Modine Manufacturing Company
1500 DeKoven Avenue
Racine, WI 53403
Phone: 1.877.679.4436 (4GEO)