Improper installation, adjustment, alteration,
service or maintenance can cause property
damage, injury or death, and could cause
exposure to substances which have been
determined by various state agencies to cause
cancer, birth defects or other reproductive
harm. Read the installation, operating and
maintenance instructions thoroughly before
installing or servicing this equipment.
IMPORTANT
The use of this manual is specifically intended
for a qualified installation and service agency.
A qualified installation and service agency
must perform all installation and service of
these appliances.
FOR YOUR SAFETY
The use and storage of gasoline or other
flammable vapors and liquids in open containers
in the vicinity of this appliance is hazardous.
Inspection On Arrival
1. Inspect unit upon arrival. In case of damage, report
immediately to transportation company and your local
Modine sales representative.
2. Check rating plate on unit and motor to verify that power
supply and motor specification requirements meet available
electric power at the point of installation.
3. Inspect unit received for conformance with description of
product ordered (including specifications where applicable).
General Information
Installation and wiring of these electric unit heaters must conform
to all applicable local codes and the National Electric Code.
Wiring of these electric unit heaters should only be performed by
a qualified electrician.
These electric unit heaters are Listed by Underwriters
Laboratories, Inc. Representative samples of this product
have been evaluated by UL and meet the applicable U.S. and
Canadian safety standards with components as furnished.
All replacement parts and controls are proprietary in that they
have all been designed, tested, and approved for the particular
application to insure both physical fit and electrical performance.
Any substitution of parts or controls not approved by Modine will
be at installer’s risk. For replacement parts, submit the unit
heater model number, power code, control code and serial
number shown on the rating plate attached to the unit.
Do not remove outlet fan guard from vertical electric unit heaters
except to service the unit.
Contents
General Information ................................1
Installation
Special Precautions / Important Instructions..........2
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
SPECIAL PRECAUTIONS / IMPORTANT INSTRUCTIONS
SPECIAL PRECAUTIONS / IMPORTANT
INSTRUCTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN THIS
MANUAL MUST BE FOLLOWED TO PROVIDE SAFE, EFFICIENT AND
TROUBLE-FREE OPERATION. IN ADDITION, PARTICULAR CARE
MUST BE EXERCISED REGARDING THE SPECIAL PRECAUTIONS
LISTED BELOW. FAILURE TO PROPERLY ADDRESS THESE
CRITICAL AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS,
PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS SUBJECT
TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation
which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which,
if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which,
if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided,
MAY result in a potential safety concern.
DANGER
Appliances must not be installed where they may be
exposed to a potentially explosive or flammable atmosphere.
1. All literature shipped with this unit should be kept for future
use for servicing or service diagnostics. Do not discard any
literature shipped with this unit.
2. Be sure no obstructions block air intake or discharge of
the appliance.
3. Do not install appliance outdoors.
4.
Do not install VE type unit heaters closer than 18 inches from
ceiling and 24 inches horizontally from combustible materials in
any direction. PTE units must be at least 24 inches from ceiling
and 18 inches horizontally from nearest enclosure. The bottom
of the unit must be at least 8 feet above the floor.
5. The bottom of the appliance must be at least 8 feet above
the floor.
6. Do not attach duct work, air filters, or polytubes to any
appliance.
7. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% less than the rated
voltage.
8. Do not reuse any electrical component which has been
wet. Such component must be replaced.
9.
SAVE THESE INSTRUCTIONS
CAUTION
WARNING
1. Disconnect power supply before making wiring connections
to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with
wiring diagram furnished with the appliance. Any wiring
different from the wiring diagram could result in a hazard
to persons and property.
3. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% greater than the
rated voltage.
4. When servicing or repairing this equipment, use only
factory-approved service replacement parts. A complete
replacement parts list may be obtained by contacting
Modine Manufacturing Company. Refer to the rating plate
on the appliance for complete appliance model number,
serial number, and company address. Any substitution of
parts or controls not approved by the factory will be at
the owner's risk.
5. Do not operate any heater if it malfunctions. Disconnect
power at service panel and have heater inspected by a
qualified installation and service agency.
IMPORTANT
To check most of the Possible Remedies in the troubleshooting
guide listed in Table 9.1, refer to the applicable sections of
the manual.
feet 0.305 m
Gal/Hr. 0.00379 m3/hr
Gal/Hr. 3.79 l/hr
3
gallons 3.79 l
Horsepower 746 W
inches 25.4 mm
pound 0.454 kg
psig 6.89 kPa
psig 27.7 "W.C.
2
2-506.15
INSTALLATION
Locating Unit Heaters
In locating heaters, consider general space-heating requirements
of the area. Unit heaters should be located so that exposed walls
are blanketed with warm air. In multiple unit installations, arrange
units so that the air discharge pattern of one unit overlaps the next
unit thus encompassing the area (See Fig. 3.1 & 3.2). Interference
of air streams by columns, beams, partitions or other obstructions
should be avoided as much as possible.
Figure 3.1 - Typical Unit Locations for Horizontal
Air Delivery
If necessary, select the correct deflector assembly to
accommodate the area being covered. Note the louver deflector
data in the table is listed with louvers fully open and with
adjusting vanes set at a 45-degree angle. For these deflectors,
vane adjustment provides a greater spread but requires a lower
mounting height. As indicated, truncone deflectors allow the
lowest mounting height and provide the widest heat spread.
Figure 3.3 - Vertical Delivery Heat Spread/Throw
H
S
S
WITH CONE-JETWITHOUT DEFLECTOR
H
H
H
S
H
H
Figure 3.2 - Typical Unit Locations for Vertical Delivery
Unit Mounting
CAUTION
1.
Do not install VE type unit heaters closer than 18 inches from
ceiling and 24 inches horizontally from combustible materials in
any direction. PTE units must be at least 24 inches from ceiling
and 18 inches horizontally from nearest enclosure. The bottom
of the unit must be at least 8 feet above the floor.
2. The bottom of the appliance must be at least 8 feet above
the floor.
3. Do not attach duct work, air filters, or polytubes to any
appliance.
Height at which unit heaters are installed is critical. Maximum
mounting heights for vertical units are listed in Table 3.1.
Maximum mounting heights for PTE units are listed in
Figure 4.2. The maximum mounting height for any unit is that
height above which the unit will not deliver heated air to the floor.
The maximum mounting heights must not be exceeded in order
to assure maximum comfort.
T
WITH LOUVERS
Table 3.1 - Maximum Mounting Heights/Spreads (feet)
Vertical Delivery
No Deflector Truncone Cone Jet Louvers
Model Blades Open Blades Open Blades 45°
H S H S H S H S H S
VE50 13 20 9 24 18 23 15 13 8 23
➀ The maximum mounting heights consider air delivery to be from the bottom of
the unit to the floor based on conditions in Table 6.2. Refer to Figure 3.3.
T
S
WITH TRUNCONE
➀
It is recommended that adequate service access in excess of
18 inches be provided for the motor and fan.
Figure 3.4 - Vertical Deflector Dimensions
TRUNCONECONE-JETLOUVERS
M
X
T
L
Z
P
If an optional air deflector has been furnished for vertical units it is
always shipped separately and may be attached to the unit before
suspension. Louvers on horizontal units may also be added
and positioned before installation. Refer to the latest revision of
75-550 for installation instructions for the optional air deflector
assemblies.
There are four tapped holes (1/2''-13) in the top of the unit for
unit suspension. Unit suspension can be made with threaded
rods, pipes, or ceiling hanger brackets furnished by others.
See Figure 4.3.
Figure 4.3 - Unit Suspension Method of Vertical
Delivery Units
Be sure the means of suspension is adequate to support
the weight of the unit. For proper operation, the unit must
be installed in a level horizontal position. Clearances to
combustibles as specified above must be strictly maintained.
Do not install unit heater above the maximum mounting height
shown in Table 3.1 for VE models or Figure 3.4 for PTE models
or below eight feet.
NOTE: A pipe hanger adapter kit is available as an accessory
from Modine. The kit consists of two drilled 3/4'' I.P.S. pipe caps
and two 1/2''-13 x 1 3/4'' capscrews to facilitate threaded-pipe
suspension. Two kits are required to pipe-mount a vertical unit.
Kit is not available on 480-volt models, VE50 thru VE250 with
transformer junction box.
Model PTE Unit Suspension
Model PTE electric heaters are provided with four hanger
brackets for installation with four ceiling suspension rods (5/8inch diameter), furnished by others. Refer to Figures 4.4 and 5.1.
Figure 4.4 - Ceiling-mounted Model PTE
4
2-506.15
Figure 5.1 - Rear view of Model PTE
For easier installation of PTE model electric unit heaters, where
ceiling suspension is not feasible, a wall-mounting bracket kit
is available. The bracket saves installation time, has a built-in
wall clearance, and provides an inexpensive and convenient
wall-mounting method. The one-point suspension, shown above,
permits swiveling the unit 180 degrees horizontally for most
effective air direction. Refer to separate bulletin included in the
kit for bracket assembly and installation. Refer to Figure 4.2
for maximum mounting heights. Minimum mounting height is
eight feet.
➀ With 70°F ambient air and heating at full capacity
➁ See Figure 4.2 for PTE mounting height and heat
throw
6
2-506.15
INSTALLATION - ELECTRICAL CONNECTIONS
Wiring
WARNING
1. Disconnect power supply before making wiring
connections to prevent electrical shock and equipment
damage.
2. All appliances must be wired strictly in accordance with
wiring diagram furnished with the appliance. Any wiring
different from the wiring diagram could result in a hazard
to persons and property.
3. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% greater than rated
voltage.
CAUTION
1. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% less than the rated
voltage.
All wiring must be done in accordance with the National Electric
Code, latest edition, (NFPA No. 70). Canadian electrical code
C22.1 applies in Canada. All internal wiring has been completed
at the factory. Provide electric service from a fused disconnect
switch to the power terminal block in the power junction box
on the unit heater. Wiring must be Type TW insulation for 60°C
(140°F) or better for Models VE50 thru VE250. Use type THW
insulation for 75°C (167°F) for Models VE and PTE 300, 400
500. Appliance wiring diagrams are located inside the power
junction box cover.
Make connections strictly in accordance with wiring
diagram furnished with unit. Any wiring differing from this
diagram may be hazardous to persons and property.
Any damage to, or failure of Modine units caused by
incorrect wiring of the units is not covered by Modine’s
standard warranty.
The location of a remote thermostat should be determined
by the heating requirements and mounted on an inside wall
approximately 5 feet above the floor. It must not be located
where it would be affected by direct heat from the unit or other
sources, or drafts from frequently opened doors or windows.
See instructions packed with thermostat. The unit may also be
controlled by a remote, manual on-off switch.
Control wiring should be No. 14 AWG (American Wire Gauge.)
All 480 volt, three-phase units have built-in transformers and
fuses to stepdown voltage and protect motor and control circuit.
Fuse blocks with fuses are factory-installed on all 480 volt,
3-phase units to protect motor control and motor transformer.
All contactor coils are rated at 208-240 volts.
Models VE and PTE 300,400, 500 with 480 volt, 3-phase power
supply are wired for two-stage control as standard equipment
and have two contactors.
Figure 7.1 - Power junction box, Models VE50 thru VE250
CONTACTOR
POWER
TERMINAL
BLOCK
GROUND
LUG
CONTROL
TERMINAL BLOCK
Figure 7.2 - Transformer and Fuse Box
TRANSFORMER
FUSE
BLOCK
W/FUSES
2-506.15
7
INSTALLATION
Model No.Power CodePower Supply
12240/1
VE50
VE75
VE100
VE150
VE200
VE25033480/3
PTE/VE30033480/3
PTE/VE40033480/3
PTE/VE50033480/3
31208/3
32240/3
33480/3
12240/1
31208/3
32240/3
33480/3
12240/1
31208/3
32240/3
33480/3
31208/3
32240/3
33480/3
32240/3
33480/3
Table 8.2 - Power Junction Box Useful VolumesTable 8.1 - Wiring Data, Vertical Units
Model Volume
VE50 thru 100 3,029 cm
VE150 thru 250 2,883 cm
VE/PTE300 thru 500 9,570 cm
3
3
3
Figure 8.3 - Side terminal Box, Models VE50 thru VE250
THERMOSTAT
WIRING OPENING
OVERHEAT
CONTROL
JUNCTION BOX
POWER SUPPLY
OPENING
ELEMENT
CONNECTION
Summer/Winter Switch
To allow a choice of fan operation of the electric unit heater
for heating and/or ventilation, a summer/winter toggle switch
kit is available for field installation. In the winter position
the thermostat will cycle the fan on and off with the heating
elements. In the summer position the fan runs continuously
for ventilation while the heating elements are controlled by the
thermostat. This position can also be used in winter to reduce
ceiling air stratification and reduce ceiling heat loss. Refer to
separate bulletin included in the kit for installation and wiring.
Low-Voltage Control
Low-voltage control is available for field installation on vertical
electric unit heaters. The control permits use of a low-voltage
thermostat that can also provide closer temperature control.
Models VE and PTE 300, 400, 500 cannot operate in two stages
with this control and a low-voltage thermostat, but will respond
with full operation of all elements.
8
2-506.15
OPERATION
Figure 9.1 - Cutaway of Electric Unit Heater
2
1. Side terminal box
2. Power junction box
3
4
5
3. Heating elements
4. Motor heat shield
5. Element support
6. Protective screen
6
7. Overheat control
8. Fan and motor
9. Outlet fan guard
1
7
8
Operating Sequence
The operation of Modine electric unit heaters is governed by
an electrical contactor which is controlled by a thermostat. The
contactor completes the electric circuit to the heating elements
when the thermostat “calls” for heat. The fan motor is also
activated when the thermostat “calls” for heat.
When the thermostat is satisfied, the fan motor stops and the
contactor opens the circuit to the heating elements.
Prior to Operation
Although this unit has been inspected and tested at the factory,
the following procedures should be performed to assure proper
on-site operation.
1. Check fan clearance. Fan should not contact casing or fan
guard when spun by hand.
2. Check all electrical connections to be sure they are secure,
and in accordance with the wiring diagram.
3. Check firmness of unit suspension. Tighten all fasteners, if
necessary.
4. Make sure fuses are installed in units that require them.
9
The motor for the circulating air fan has internal thermal
overload protection. If for any reason, the motor overheats,
the thermal protector will shut it off. The motor will re-start
automatically when it has cooled.
3. Adjust the air deflector (if provided) for desired heat
distribution.
4. Run the unit through several cycles by raising and lowering
the thermostat setting to assure proper sequence of
operation. For Models VE and PTE300, 400, 500 with
two-stage thermostats, check operation on both states.
Three elements should heat up during first stage operation
when temperature falls. As additional heat is required
the remaining three elements will be energized until the
thermostat high-stage setting is satisfied. The unit will
automatically shut off when the low-stage thermostat setting
is satisfied.
Safety Devices
The overheat control, (See Figure 9.1), will interrupt power to
the unit contactor in the event of overheating. It is a single-pole
single-throw switch, with an automatic reset. The switch will
permit the motor to continue operation and cool the heater while
power to the elements is interrupted. This overheat control
should operate only when something is seriously wrong
with the unit. When this control operates, correct the
difficulty immediately or serious and permanent damage
may result.
2-506.15
9
GENERAL MAINTENANCE
WARNING
1. When servicing or repairing this equipment, use only
factory approved service replacement parts. A complete
replacement parts list may be obtained by contacting
Modine Manufacturing Company. Refer to the rating
plate on the unit for complete unit substitution of parts
or controls not approved by the factory will be at the
owner’s risk.
2. Do not operate any heater if it malfunctions. Disconnect
power at service panel and have heater inspected by a
qualified installation and service agency.
General Maintenance
Unit heaters, like other electrical and mechanical equipment,
will give lasting trouble-free service if properly cared for.
Observance of a few simple periodic procedures will insure their
satisfactory operation.
Under average conditions, it is recommended that unit heaters
be inspected before every heating season
locations where air is contaminated with corrosive fumes, dust,
soot, or oil spray. To perform routine maintenance:
1. Disconnect power supply to the unit.
2. Open junction box doors at top of unit and inspect unit
contactors, fuses, transformer, and tighten connections if
necessary.
3. Open side terminal box by removing panel at side of unit and
check element connections and the over-heat control switch.
4. Check motor mounting from bottom of unit. Check fan for
proper clearance, free rotation, and firm connection to motor
shaft. Remove air deflectors (if provided) for acces
..
more often in
CAUTION
Do not reuse any electrical component which has been wet.
Such component must be replaced.
NOTE: To check most of the Possible Remedies in the
trouble-shooting guide listed in Table 11.1, refer to the
applicable sections of the manual.
5. Lubricate motor according to manufacturer’s instructions
on motor. When no instructions are on motor, oil every
two thousand hours of operation with SAE20 oil for
normal applications. Adjust oiling according to usage and
atmosphere. Some motors do not have oil fitting. These are
lubricated for long life and do not require further lubrication.
6. Routine cleaning of the outer unit casing and protective
screen is recommended to remove dirt, grease, or corrosive
material that may damage finish. Rusted or corroded spots
on top or bottom casing should be sanded and repainted.
7. Clean fan blades, elements, and inside casing with either
a detergent solution or compressed air. Do not scrape
elements.
8. For better element access or for more extensive cleaning of
the elements and screen, the screen can be easily removed.
Detach side terminal box cover and casing bottom before
removing protective screen.
10
2-506.15
TROUBLESHOOTING
Table 11.1 – Troubleshooting
Problem Possible cause(s) Remedy
Unit does not operate 1. Electric circuit in open position 1. a. Turn on switch or move thermostat
to higher setting.
b. Replace fuse or reset disconnect switch
2. Blown fuses in control 2. Replace fuses
compartment.
3. Defective or incorrect wiring 3. Check wiring and connections. Refer to
diagram inside junction box
4. Defective thermostat or switch 4. Check continuity with volt-ohmeter.
Replace defective part if necessary
5. Defective or burned out control 5. Check secondary voltage with
transformer voltmeter. Replace if necessary
Fan operates but 1. Power interrupted by overheat 1. a. Not enough air volume over elements.
element does not heat control Louvers must be opened at least 45°.
Clean element screen and spiral fins.
b. Check motor rpm against nameplate
rating. Replace motor if speed too slow.
c. Defective limit control. Check wiring
and connections. check continuity
through control. Replace if necessary.
2. Summer-winter switch in 2. Change switch position
summer position
3. Defective or incorrect wiring 3. Check all wiring and connections. See
diagram inside junction box.
4. Blown element fuses 4. Replace element fuses
Elements heat but fan 1. Fan motor failure 1. a. Check for loose electrical connections.
does not operate Check wiring with diagram in control
compartment
b. Repair or replace defective motor.
c. Voltage too high or too low.
Check voltage with volt-meter.
2. Summer-winter switch defective 2. Check for continuity with volt-ohmeter.
or improperly wired Replace if necessary.
3. Defective or incorrect wiring 3. Check all wiring and connections. See
diagram inside junction box
Insufficient heat 1. Too few units for heat loss 1. Add more units or increase size of units
2. Unit mounted too high 2. Lower mounting height
3. Fan operates backwards 3. Repair or replace motor or reverse fan
rotation
4. Burned out (elements) 4. Disconnect internal wiring and check
element resistance with ohmeter
2-506.15
11
COMMERCIAL WARRANTY
Seller warrants its products to be free from defects in material and
workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use
of materials substituted under emergency conditions for materials normally
employed. This warranty covers replacement of any parts furnished from the
factory of Seller, but does not cover labor of any kind and materials not
furnished by Seller, or any charges for any such labor or materials, whether
such labor, materials or charges thereon are due to replacement of parts,
adjustments, repairs, or any other work done. This warranty does not apply to
any equipment which shall have been repaired or altered outside the factory of
Seller in any way so as, in the judgment of Seller, to affect its stability, nor which
has been subjected to misuse, negligence, or operating conditions in excess of
those for which such equipment was designed. This warranty does not cover
the effects of physical or chemical properties of water or steam or other liquids
or gases used in the equipment.
BUYER AGREES THAT SELLER’S WARRANTY OF ITS PRODUCTS TO
BE FREE FROM DEFECT IN MATERIAL AND WORKMANSHIP, AS LIMITED
HEREIN, SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER
WARRANTIES, EITHER EXPRESS OR IMPLIED, WHETHER ARISING
FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE,
THERE ARE NO OTHER WARRANTIES, INCLUDING WARRANTY OF
MERCHANTABILITY OR FITNESS FOR PURPOSE, WHICH EXTEND
BEYOND THE PRODUCT DESCRIPTION CONFIRMED BY BUYER AND
SELLER AS OF THE DATE OF FINAL AGREEMENT.
This warranty is void if the input to the product exceeds the rated input as
indicated on the product serial plate by more than 5% on gas-fired and oil-fired
units, or if the product in the judgment of SELLER has been installed in a
corrosive atmosphere, or subjected to corrosive fluids or gases, been subjected
to misuse, negligence, accident, excessive thermal shock, excessive humidity,
physical damage, impact, abrasion, unauthorized alterations, or operation
contrary to SELLER’S printed instructions, or if the serial number has been
altered, defaced or removed.
BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL
OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR
REPLACEMENT AT THE FACTORY OF SELLER, ANY COMPONENT WHICH
SHALL, WITHIN THE APPLICABLE WARRANTY PERIOD DEFINED HEREIN
AND UPON PRIOR WRITTEN APPROVAL, BE RETURNED TO SELLER WITH
TRANSPORTATION CHARGES PREPAID AND WHICH THE EXAMINATION
OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE; EXCEPT THAT
WHEN THE PRODUCT IS TO BE USED BY BUYER AS A COMPONENT PART
OF EQUIPMENT MANUFACTURED BY BUYER, BUYER’S REMEDY FOR
BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO ONE YEAR FROM
DATE OF SHIPMENT FROM SELLER. FOR GAS-FIRED PRODUCTS
INSTALLED IN HIGH HUMIDITY APPLICATIONS AND UTILIZING STAINLESS
STEEL HEAT EXCHANGERS, BUYER’S REMEDY FOR BREACH, AS
LIMITED HEREIN, SHALL BE LIMITED TO TEN YEARS FROM DATE OF
SHIPMENT FROM SELLER.
These warranties are issued only to the original owner-user and cannot be
transferred or assigned. No provision is made in these warranties for any
labor allowance or field labor participation. Seller will not honor any expenses
incurred in its behalf with regard to repairs to any of Seller’s products. No
credit shall be issued for any defective part returned without proper written
authorization (including, but not limited to, model number, serial number, date
of failure, etc.) and freight prepaid.
OPTIONAL SUPPLEMENTAL WARRANTY
Provided a supplemental warranty has been purchased, Seller extends the
warranty herein for an additional four (4) years on certain compressors.
Provided a supplemental warranty has been purchased, Seller extends the
warranty herein for an additional four (4) years or nine (9) years on certain
heat exchangers.
EXCLUSION OF CONSUMABLES & CONDITIONS BEYOND
SELLER’S CONTROL
The above referenced warranty shall not be applicable to any of the following
items: refrigerant gas, belts, filters, fuses and other items consumed or worn out
by normal wear and tear or conditions beyond Seller’s control, including (without
limitation as to generality) polluted or contaminated or foreign matter contained
in the air or water utilized for heat exchanger (condenser) cooling or if the failure
of the part is caused by improper air or water supply, or improper or incorrect
sizing of power supply.
Component
Applicable Models
Heat Exchangers
Gas-Fired Units except PSH/BSH
Heat Exchangers
Low Intensity Infrared Units
Compressors
Condensing Units for Cassettes
Burners
Low Intensity Infrared Units
Other
Components excluding Heat Exchangers,
Coils, Condensers, Burners, Sheet Metal
Heat Exchangers/Coils
Indoor and Outdoor Duct Furnaces and
System Units, PSH/BSH, Steam/Hot Water Units,
Oil-Fired Units, Electric Units, Cassettes,
Vertical Unit Ventilators
Compressors
Vertical Unit Ventilators
Burners
High Intensity Infrared Units
Sheet Metal Parts
All Products
“APPLICABLE WARRANTY PERIOD”
TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE
HUNDRED TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER
OCCURS FIRST
FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN SIXTY-SIX
MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
EIGHTEEN MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
Modine Manufacturing Company has a continuous product improvement program; it reserves the right to change design and specifications without notice.
Modine Manufacturing Company
1500 DeKoven Avenue
Racine, WI 53403
Phone: 1.800.828.4328 (HEAT)