2
SPECIAL PRECAUTIONS / TABLE OF CONTENTS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN
THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE,
EFFICIENT AND TROUBLE-FREE OPERATION. IN
ADDITION, PARTICULAR CARE MUST BE EXERCISED
REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW.
FAILURE TO PROPERLY ADDRESS THESE CRITICAL
AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS,
PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS
ARE SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR
NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation
which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation
which, if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation
which, if not avoided, MAY result in minor or moderate
injury.
4. IMPORTANT: Indicates a situation which, if not avoided,
MAY result in a potential safety concern.
DANGER
Appliances must not be installed where they may be exposed
to a potentially explosive or flammable atmosphere.
WARNING
1. Disconnect power supply before making wiring connections to
prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with wiring
diagram furnished with the appliance. Any wiring different
from the wiring diagram could result in a hazard to persons
and property.
3. Any original factory wiring that requires replacement must
be replaced with wiring material having a temperature
rating of at least 105°C.
4. When servicing or repairing this equipment, use only
factory-approved service replacement parts. A complete
replacement parts list may be obtained by contacting
Modine Manufacturing Company. Refer to the rating plate
on the appliance for complete appliance model number,
serial number, and company address. Any substitution of
parts or controls not approved by the factory will be at the
owner’s risk.
CAUTION
1. Do not locate units in tightly sealed rooms or small
compartments (commonly referred to as confined spaces)
without provisions for adequate combustion air and
venting. Combustion air must have access to the confined
space through a minimum of two permanent openings in
the enclosure, at least one near the bottom. They should
provide a free area of not less than one square inch per
1,000 BTU/Hr input rating of all units in the enclosure with
a minimum of 100 square inches for each opening,
whichever is greater.
2. When oil-fired unit heaters are to be installed in areas
having negative pressure (for example - a space with
exhaust fan(s)) a power venter is recommended.
3. Do not install units below 7 feet, measured from the
bottom of the unit to the floor, unless properly guarded to
provide protection from moving parts.
IMPORTANT
1. To prevent premature heat exchanger failure, do not locate
ANY gas-fired appliances in areas where corrosive vapors (i.e.
chlorinated, halogenated or acid) are present in the
atmosphere.
2. To check most of the Possible Remedies in the troubleshooting
guide listed in Table 18.1, refer to the applicable sections of the
manual.
Table of Contents
Inspection on Arrival . . . . . . . . . . . . . . . . . . . . . . . . 1
Special Precautions . . . . . . . . . . . . . . . . . . . . . . . . . 2
SI (Metric) Conversion Factors . . . . . . . . . . . . . . . . 3
Unit Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Service Instructions . . . . . . . . . . . . . . . . . . . . . . . . . 14
Dimensional/Performance Data . . . . . . . . . . . . . . . . 17
Service & Troubleshooting . . . . . . . . . . . . . . . . . . . . 18
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Back Page
CAUTION
4. Do not install unit heater or vent pipe closer than 18
inches to combustible materials in any direction, except
the front of the unit heater, which must be unobstructed.
5. A barometric draft control must be installed on each unit
heater, in the same space as the unit heater and as close
to the unit as possible. See Figure 5.1.
6. Remove bypass plug from fuel unit when unit is connected
to one pipe oil system. Failure to do so will permanently
damage fuel unit and void warranty.
7. Do not mount the OSV more than three feet above the
burner inlet or above the lowest point in fuel line pipings
between burner and OSV. In-line mounting is recommended.
8. Start-up and adjustment procedures should be performed
by a qualified oil serviceman.
9. Do not reset primary control if heat exchanger is hot. If
unit fails to operate properly after resetting twice, consult
qualified oil serviceman.
10. Never use a nozzle size or type other than specified in
Service Instructions.
11. Do not attempt to start the burner when excess oil has
accumulated in the combustion chamber, when the heat
exchanger is full of oil vapor or very hot.
12. Burner adjustments should only be performed by qualified
oil serviceman.
13. Do not reset primary control if heat exchanger is warm.
Wait till cool.
14. To prevent unusual thermal stress and eventual harm to
the heat exchanger, do not operate unit heater without fire pot
or with a damaged fire pot that does not enclose the flame.
15. Do not attempt to reuse any mechanical or electrical
controllers which have been wet. Replace defective controller.