Modine HDS, HDC User Manual

INSTALLATION AND SERVICE MANUAL
separated combustion gas-fired unit heaters
WARNING
1. Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death, and could cause exposure to substances which have been determined by various state agencies to cause cancer, birth defects or other reproductive harm. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
2. Do not locate ANY gas-fired units in areas where chlorinated, halogenated, or acidic vapors are present in the atmosphere. These substances can cause premature heat exchanger failure due to corrosion, which can cause property damage, serious injury, or death.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS:
1. Open windows.
2. Do not try to light any appliance.
3. Do not touch any electrical switch; do not use any phone in your building.
4. Immediately call your gas supplier
 fromaneighbor’sphone.Followthegas  supplier’sinstructions.Ifyoucannotreach
your gas supplier, call your fire department.
6-584.8
5H0800020000
September, 2015
model HDS and HDC
All models approved for use in California by the CEC and in Massachusetts. Unit heater is certified for residential and commercial applications.
FOR YOUR SAFETY
The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
IMPORTANT
The use of this manual is specifically intended for a qualified installation and service agency. All installation and service of these units must be performed by a qualified installation and service agency.
Inspection on Arrival
1. Inspect unit upon arrival. In case of damage, report it immediately to transportation company and your local Modine sales representative.
2.
Check rating plate on unit to verify that power supply meets available electric power at the point of installation.
3. Inspect unit upon arrival for conformance with description of product ordered (including specifications where applicable).
Table of Contents
Inspection on Arrival ................................. 1
Special Precautions ................................. 2
SI (Metric) Conversion Factors......................... 3
Before you Begin ................................... 3
Unit Location....................................... 4
Combustible Material and Service Clearances ......... 4
Unit Mounting .................................. 5
Venting ....................................... 6
Gas Connections............................... 12
High Altitude Accessory Kit . . . . . . . . . . . . . . . . . . . . . . . 13
Electrical ..................................... 15
Operation..................................... 16
Unit Components .................................. 17
Dimensions....................................... 18
Service/Troubleshooting............................. 19
Unit Wiring Diagram ................................ 20
Serial/Model Number/Replacement Parts ............... 21
Commercial Warranty........................Back Cover
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
THIS MANUAL IS THE PROPERTY OF THE OWNER.
SPECIAL PRECAUTIONS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE, EFFICIENT AND TROUBLE-FREE OPERATION. IN ADDITION, PARTICULAR CARE MUST BE EXERCISED REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW. FAILURE TO PROPERLY ADDRESS THESE CRITICAL AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS, PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which, if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which,
if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided, MAY result in a potential safety concern.
DANGER
Appliances must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
WARNING
1. Gas fired heating equipment must be vented - do not operate unvented.
2. A built-in power exhauster is provided - additional external power exhausters are not required or permitted.
3. If an existing heater is being replaced, it may be necessary to resize the venting systems. Improperly sized venting systems can result in vent gas leakage or the formation of condensate. Refer to the National Fuel Gas Code ANSI Z223.1 (NFPA 54) or CSA B149.1 latest edition. Failure to follow these instructions can result in injury or death.
4. Under no circumstances should two sections of double wall vent pipe be joined together within one horizontal vent system due to the inability to verify complete seal of inner pipes.
5. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing.
6. Gas pressure to appliance controls must never exceed 14" W.C. (1/2 psi).
7. To reduce the opportunity for condensation, the minimum sea level input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or 5% below the minimum rated input of dual rated units.
8. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
9. All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
10. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
11. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than the rated voltage.
12. When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacements parts list may be obtained by contacting the factory. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner's risk.
CAUTION
1. All literature shipped with this unit should be kept for future use for servicing or service diagnostics. Do not discard any literature shipped with this unit.
2. Consult piping, electrical, and venting instructions in this manual before final installation.
3. Do not attach ductwork, air filters, or polytubes to any propeller unit heater.
4. Clearances to combustible materials are critical. Be sure to follow all listed requirements.
5. Low profile heaters are designed for use in heating applica­ tions with ambient startup temperatures between -40°F and
90°F, and ambient operating temperatures between 40°F and 90°F.
6. Do not install unit outdoors.
7. In garages or other sections of aircraft hangars such as offices and shops that communicate with areas used for servicing or storage, keep the bottom of the unit at least 7' above the floor unless the unit is properly guarded to provide user protection from moving parts. In parking garages, the unit must be installed in accordance with the standard for parking structures ANSI/NFPA 88A latest edition, and in repair garages the standard for repair garages
NFPA 30A - latest edition (Formerly NFPA 88B). In Canada, installation of heaters in airplane hangars must be in accordance with the requirements of the enforcing authority, and in public garages in accordance with the current CSA­B149 codes.
8. In aircraft hangars, keep the bottom of the unit at least 10' from the highest surface of the wings or engine enclosure of the highest aircraft housed in the hangars and in accordance with the requirements of the enforcing authority and/or NFPA 409-latest edition.
9. Installation of units in high humidity or salt water atmospheres will cause accelerated corrosion resulting in a reduction of the normal life of the units.
10. Do not install units below 7' measured from the bottom of the unit to the floor in commercial applications (unless unit is properly guarded to provide user protection from moving parts) and 5' measured from the bottom of the unit to the floor in residential applications.
11. Be sure no obstructions block air intake and discharge of unit heaters.
12. The minimum distance from combustible material is based on the combustible material surface not exceeding 160°F. Clearance from the top of the unit may be required to be greater then the minimum specified if heat damage, other than fire, may occur to materials above the unit heater at the temperature described.
13. Allow 18" of clearance at rear (or 6" beyond end of motor at rear of unit, whichever is greater) and access side to provide ample air for proper operation of fan.
14. Installation must conform with local building codes or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest edition. In Canada installation must be in accordance with CSA-B149.1.
15. The concentric vent adapter box must be installed inside of the structure or building. Do not install this box on the exterior of a building or structure.
16. Purging of air from gas supply line should be performed as described in the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest edition, or, or in Canada in CSA-B149 codes.
17. When leak testing the gas supply piping system, the
appliance and its combination gas control must be isolated during any pressure testing in excess of 14" W.C. (1/2 psi).
2
6-584.8
SPECIAL PRECAUTIONS / SI (METRIC) CONVERSION FACTORS
BEFORE YOU BEGIN
CAUTION
18. The unit should be isolated from the gas supply piping system by closing its field installed manual shut-off valve. This manual shut-off valve should be located within 6' of the heater.
19. Turn off all gas before installing appliance.
20. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage.
21. Check the gas inlet pressure at the unit upstream of the combination gas control. The inlet pressure should be 6-7" W.C. on natural gas or 12-14" W.C. on propane. If inlet pressure is too high, install an additional pressure regulator upstream of the combination gas control.
22. Service or repair of this equipment must be performed by a qualified service agency.
23. Do not attempt to reuse any mechanical or electronic ignition controllers which has been wet. Replace defective controller.
IMPORTANT
1. To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acid) are present in the atmosphere.
2. To prevent premature heat exchanger failure, the input to the appliance as indicated on the serial plate, must not exceed the rated input by more then 5%.
3. To prevent premature heat exchanger failure, observe heat exchanger tubes. If the tubes become red while blower and furnace are in operation, check to be sure the blower has been set to the proper rpm for the application. Refer to page 15 for blower adjustments.
4. Start-up and adjustment procedures must be performed by a qualified service agency.
CAUTION
1. All literature shipped with this unit should be kept for future use for servicing or service diagnostics. Leave manual with the owner. Do not discard any literature shipped with this unit.
2. Consult piping, electrical, and venting instructions in this manual before final installation.
3. Do not attach ductwork, air filters, or polytubes to any propeller unit heater.
In the U.S., the installation of these units must comply with the National Fuel Gas Code, ANSI Z223.1 - latest edition (NFPA
54) and other applicable local building codes. In Canada, the installation of these units must comply with local plumbing or waste water codes and other applicable codes and with the current code CSA-B149.1.
1. All installation and service of these units must be performed by a qualified installation and service agency only as defined in ANSI Z223.1, latest edition or in Canada by a licensed gas fitter.
2. This unit is certified with the controls furnished. For
replacements parts, please order according to the replacement parts list on serial plate. Always know your model and serial numbers. The right is reserved to substitute other authorized controls as replacements.
3. Unit is balanced for correct performance. Do not alter fan
or operate motors at speeds below what is shown in this manual.
4. Information on controls is supplied separately.
5. The same burner is used for natural and propane gas.
To check most of the possible remedies in the troubleshooting guide listed in Table 19.1, refer to the applicable sections of the manual.
SI (METRIC) CONVERSION FACTORS
To Convert Multiply By To Obtain
"W.C. 0.249 kPa °F (°F-32) x 5/9 °C Btu 1.06 kJ Btu/ft Btu/hr 0.000293 kW CFH (ft CFH (ft CFM (ft CFM (ft
3
37.3 kJ/m
3
/hr) 0.000472 m3/min
3
/hr) 0.00000787 m3/s
3
/min) 0.0283 m3/min
3
/min) 0.000472 m3/s
To Convert Multiply By To Obtain
feet 0.305 m Gal/Hr. 0.00379 m Gal/Hr. 3.79 l/hr
3
gallons 3.79 l Horsepower 746 W inches 25.4 mm pound 0.454 kg psig 6.89 kPa psig 27.7 "W.C.
3
/hr
6-584.8
3
UNIT LOCATION
UNIT LOCATION
DANGER
Appliances must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
CAUTION
1. Clearances to combustible materials are critical. Be sure to follow all listed requirements.
2. Low profile heaters are designed for use in heating applications with ambient startup temperatures between
-40°F and 90°F, and ambient operating temperatures between 40°F and 90°F.
3. Do not install unit outdoors.
4. In garages or other sections of aircraft hangars such as offices and shops that communicate with areas used for servicing or storage, keep the bottom of the unit at least 7' above the floor unless the unit is properly guarded. In parking garages, the unit must be installed in accordance with the standard for parking structures ANSI/NFPA 88A-latest edition, and in repair garages the standard for repair garages NFPA 30A - latest edition (Formerly NFPA 88B). In Canada, installation of heaters in airplane hangars must be in accordance with the requirements of the enforcing authority, and in public garages in accordance with the current CSA-B149 codes.
5. In aircraft hangars, keep the bottom of the unit at least 10'
from the highest surface of the wings or engine enclosure of the highest aircraft housed in the hangars and in accordance with the requirements of the enforcing authority and/or NFPA 409-latest edition.
6. Installation of units in high humidity or salt water atmospheres will cause accelerated corrosion, resulting in a reduction of the normal life of the units.
Table 4.1 - Clearances
Unit Side
Combustible Materials Service Clearance
Top and Bottom 1" 1" Access Side 1" 18" Non-Access Side 1" 1" Rear 18" 18" Vent Connector 4" 4"
6. Do not install units in locations where gas ignition system is exposed to water spray, rain, or dripping water.
7. Mounting height (measured from bottom of unit) at which unit heaters are installed is critical. Refer to mounting height and heat throw data on page 16 of this manual. The maximum mounting height for any unit is that height above which the unit will not deliver heated air to the floor.
Clearance To Recommended
Turning The Unit 180° (Model sizes 30-75 only)
All units are produced at the factory with left-side controls (when looking at the unit). If the installation requires the controls to be on the right side, all HDS/HDC heaters - with the exception of the 100 and 125 - can be turned-over by following the instructions below.
• By turning the unit 180° from the way it was received from the factory, the sides become opposite but the front and back remain in the same relative position. The bottom panel now becomes the top panel and vice-versa.
• Remove the access panel, turn it 180°, and re-attach it to the unit so that all the information labels can be read.
• Remove the spring-loaded deflector blades, turn them over, replace, and adjust so they are open and in a position to direct the heated air down to the floor.
IMPORTANT
To prevent premature heat exchanger failure, do not locate ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acid) are present in the atmosphere.
Location Recommendations
1. When locating the heater, consider general space and heating requirements, availability of gas and electrical supply, and proximity to vent locations.
2. When locating units, it is important to consider that the combustion air and exhaust vent piping must be connected to the outside atmosphere. Vent terminals should be located adjacent to one another. Maximum equivalent vent lengths are listed in “Section A - General Instruction - All Units” of the venting instructions.
3. Be sure the structural support at the unit location site is adequate to support the unit's weight. For proper operation the unit must be installed in a level horizontal position.
4. Do not install units in locations where the flue products can be drawn into the adjacent building openings such as windows, fresh air intakes, etc.
5. Be sure that the minimum clearances to combustible materials and recommended service clearances are maintained. Units are designed for installation with the minimum clearances as shown in Table 4.1.
4
6-584.8
UNIT MOUNTING
CAUTION
1.
Do not install units below 7' measured from the bottom of the unit to the floor in commercial applications (unless unit is properly guarded to provide user protection from moving parts) and 5' measured from the bottom of the unit to the floor in residential applications.
2. Be sure no obstructions block air intake and discharge of unit heaters.
3. The minimum distance from combustible material is based on the combustible material surface not exceeding 160°F. Clearance from the top of the unit may be required to be greater than the minimum specified if heat damage, other than fire, may occur to materials above the unit heater at the temperature described.
4. Allow 18" clearance at rear (or 6" beyond end of motor at rear of unit, whichever is greater) and access side to provide ample air for proper operation of fan.
Figure 5.2 - Unit Heater Turned 180° (30-75 units only) (Access panel and heated air outlet change sides)
1. Be sure the means of suspension is adequate to support the weight of the unit (see page 18 for unit weights).
2. For proper operation, the unit must be installed in a level horizontal position.
3. Clearances to combustibles as previously specified must be strictly maintained.
4. For model sizes 30-75, before lifting the heater for suspension, the mounting brackets must be installed as follows (for bracket accessory installation on model sizes 100-125, see the latest revision of literature 6-594):
• For standard (left side) control access, remove the 3
screws and mounting bracket along the top edge of both the front and back of the unit. Install the front bracket as shown in Figure 5.1 by aligning the screw holes on the bracket with the screw holes on the top edge of the unit. Repeat for the bracket on the back of the unit.
• For right side control access, remove the 3 screws and
mounting bracket along the top edge of both the front and back of the unit. Turn the unit over and install the front bracket as shown in Figure 5.2 by aligning the screw holes on the bracket with the screw holes on the top edge of the unit (originally the bottom edge). Repeat for the bracket on the back of the unit.
5a. Suspension by screws/lag bolts: Secure the mounting
brackets to the ceiling joists or truss, using 1/4" screws with 1/2" washers. These unit mounting brackets are slotted to accommodate joists on 16" or 24" centerlines. See page 18 for mounting bracket dimensions.
Figure 5.1 - Unit Heater in Standard Mounting Configuration (30-75 units only)
5b. Suspension by threaded rod: The unit can also be hung
with threaded rod utilizing the same mounting brackets. Attach the threaded rod to the unit mounting brackets, securing with a top and bottom nut. For model sizes 100-125, the units are designed to be suspended by threaded rod without the use of brackets. On each piece of 3/8" threaded rod used, screw a nut a distance of about 1" onto the end of the threaded rods that will be screwed into the unit heater. Place a washer over the end of the threaded rod and screw the threaded rod into the unit heater weld nuts on the top of the heater at least 5 turns, and no more than 10 turns. Tighten the nut first installed onto the threaded rod to prevent the rod from turning.
Next, drill holes into a steel channel or angle iron at the
same centerline dimensions as those chosen for the heater being installed. The steel channels or angle iron pieces need to span and be fastened to appropriate structural members. Cut the threaded rods to the preferred length, push them through the holes in the steel channel or angle iron and secure with washers and lock nuts, lock washers and nuts, or a washer with double nut arrangement. NOTE: A pipe hanger adapter kit, shown in Figure 5.3, is available as an accessory. One kit consists of two drilled 3/4" IPS pipe caps and two 3/8" - 16 x 1-3/4" capscrews to facilitate threaded pipe suspension. Two kits would be required.
5c. Shelf mounted units: The unit heater can also be installed
on a shelf. The mounting brackets will need to be attached to the heater the same manner as explained in note #4, however, to mount on a shelf the brackets must go on the bottom of the heater. The brackets must be affixed to the shelf using similar screws (1/4" screw with 1/2" washer) as overhead joist or truss mounting. Be sure all clearance to combustible requirements are met.
Figure 5.3 - Unit Heater Suspension Methods
(Threaded Rod) (Pipe Adaptor Kit)
6-584.8
5
INSTALLATION - VENTING
WARNING
1. Gas fired heating equipment must be vented - do not operate unvented.
2. A built-in power exhauster is provided - additional external
power exhausters are not required or permitted.
3. If an existing heater is being replaced, it may be necessary to resize the venting systems. Improperly sized venting systems can result in vent gas leakage or the formation of condensate. Refer to the National Fuel Gas Code ANSI Z223.1 (NFPA 54) or CSA-B149.1 Installation Code - latest edition. Failure to follow these instructions can result in serious injury or death.
4. Under no circumstances should 2 sections of double wall
vent pipe be joined together within 1 horizontal vent system due to the inability to verify complete seal of inner pipes.
CAUTION
Installation must conform with local building codes or in the absence of local codes, with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest edition. In Canada installation must be in accordance with CSA B149.1.
Model HDS/HDC unit heaters must be vented with the proper passageway as described in these instructions to convey flue gases from the unit or the vent connector to the outside atmosphere. The heaters must also have a separate combustion air intake pipe to bring in fresh air for combustion from the outside atmosphere.
The venting instructions are organized in sections, based on installation type. The sections are identified as follows:
Instructions Applicable Installation Instructions Section by Vent System Type
A General instructions for ALL installations B VERTICAL 2-PIPE vent systems C HORIZONTAL 2-PIPE vent systems D HORIZONTAL AND VERTICAL
CONCENTRIC vent systems ➀
The differences between vertical and horizontal vent systems in 2-Pipe or
concentric vent configurations will be identified in “Section A - General Instructions – All Units”.
A4. Refer to Table 6.1 for total equivalent vent pipe lengths,
making the vent system as straight as possible. Refer to Table 6.1 for total equivalent vent pipe lengths, making the vent system as straight as possible.
Table 6.1 - Vent Pipe Diameters, Transitions, and Total Equivalent Vent Pipe Lengths For Horizontal and Vertical Venting Systems
Model
Size
30-45 3" 3' 25'
60-125 4" 3' 25'
A5. A minimum of 12" straight pipe is recommended from the
flue outlet before turns in the vent pipe.
A6. Horizontal sections of vent pipe are to be installed with a
minimum downward slope from the appliance of 1/4" per foot and suspended securely from overhead structures at points not greater than 3' apart.
A7. Fasten individual lengths of vent together with at least 3
corrosion-resistant sheet metal screws.
A8. Keep single wall vent pipe at least 6" from combustible
materials. For double wall vent pipe, follow the vent
pipe manufacturer’s clearances to combustibles. The
minimum distance from combustible materials is based on the combustible material surface not exceeding 160°F. Clearance from the vent pipe (or the top of the unit) may be required to be greater than 6" if heat damage other than fire could result (such as material distortion or discoloration).
A9. Avoid venting through unheated space when possible.
When venting does pass through an unheated space or if the unit is installed in an environment that promotes condensation, insulate runs greater than 5' to minimize condensation. Inspect for leakage prior to insulating and use insulation that is noncombustible with a rating of not less than 400°F. Install a tee fitting at the low point of the vent system and provide a drip leg with a clean out cap as shown in Figure 8.1.
Vent Pipe
Sizes
Minimum
Eqv. Length
Maximum
Eqv. Length
Figure 6.1 - Venting Through Combustible Roof or Wall
Single Wall Vent Pipe
Flashing
Listed Terminal
Double Wall Vent Pipe
Flashing
Listed Terminal
Section A – General Instructions – All Units
A1. If the unit heater being installed is replacing existing
equipment and using the existing vent system from that equipment, inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code ANSI Z223.1 or CSA B149.1 Installation Code-latest edition and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
A2. The combustion air pipe and vent pipe should be galvanized
steel or other suitable corrosion resistant material. Follow the National Fuel Gas Code for minimum thickness of vent material. The minimum thickness for connectors varies depending on the pipe diameter. Do not vent unit with PVC or other forms of plastic venting material.
A3. All heaters come with factory installed vent and combustion
air adapters for attaching the vent pipe to the heater. Attach the vent pipe to the adapter with 3 corrosion resistant screws. (Drill pilot holes through the vent pipe and adapter prior to screwing in place). Vent pipe must not be smaller than the connector size.
6
Listed Thimble
Single Wall
Single Wall Vent Pipe Terminating with Double wall vent pipe.
Clearance Specified by Type B Vent Mfg.
Single Wall Vent Pipe
Listed Thimble
See Instruction A12 for attaching single wall pipe to double wall pipe.
6-584.8
Clearance Specified by Type B Vent Mfg.
Double Wall
Listed Terminal
Single Wall
Listed Terminal
INSTALLATION - VENTING
A10. When the vent passes through a combustible INTERIOR
wall or floor, a metal thimble 4" greater than the vent diameter is necessary. If there is 6' or more of vent pipe in the open space between the appliance and where the vent pipe passes through the wall or floor, the thimble need only be 2" greater than the diameter of the vent pipe. If a thimble is not used, all combustible material must be cut away to provide 6" of clearance. Where authorities have jurisdiction type B vent may be used for the last section of vent pipe to maintain clearance to combustibles while passing through wall or floor (see Figure 6.1). Any material used to close the opening must be noncombustible.
A11. All seams and joints of the single wall pipe must be sealed
with metallic tape or silastic suitable for temperatures up to 400°F. Wrap the tape 2 full turns around the vent pipe. One continuous section of double wall vent pipe may be used within the vent system to pass through the wall to a listed vent cap. Refer to instruction A12 in “Section A – General Instructions – All Units” for attaching double wall pipe to single wall pipe.
A12. The following are general instructions for double wall (type
B) terminal pipe installation:
How to attach a single wall vent terminal to double wall (type B) vent pipe:
1. Look for the “flow” arrow on the vent pipe.
2. Slide the vent terminal inside the exhaust end of the double wall vent pipe.
3. Drill 3 holes through the pipe and the vent terminal. Using 3/4" long sheet metal screws, attach the cap to the pipe. Do not overtighten.
How to connect a single wall vent system to a double wall (type B) vent pipe:
1. Slide the single wall pipe inside the inner wall of the double wall pipe.
2. Drill 3 holes through both walls of the single and double wall vent pipes. Using 3/4" sheet metal screws, attach the 2 pieces of pipe. Do not overtighten.
3. The gap between the single and double wall pipe must be sealed but it is not necessary to fill the full volume of the annular area. To seal, run a large bead of 400°F silastic around the gap.
A13. Vent termination clearances must be maintained:
Table 7.1 - Vent Termination Clearances
Minimum Clearances for Structure Vent Terminal Location
Forced air inlet within 10 feet 3 feet above Combustion air inlet of another
appliance 6 feet all directions Door, window, gravity air inlet, 4 feet horizontal and below
or any building opening 1 foot above Electric meter, gas meter, gas 4 feet horizontal (U.S.)
regulator, and relief equipment 6 feet horizontal (Canada) Gas regulator 3 feet horizontal (U.S.)
6 feet horizontal (Canada) Adjoining building or parapet wall 6 feet all directions Adjacent public walkways 7 feet all directions Grade (ground level) 3 feet above
Do not terminate the vent directly above a gas meter or regulator.
A14. Do NOT vent this appliance into a masonry chimney. A15. Do NOT use dampers or other devices in the vent or
combustion air pipes.
A16.
The venting system must be exclusive to a single appliance, and no other appliance is allowed to be vented into it.
A17. Precautions must be taken to prevent degradation of
building materials by flue products.
A18. Single wall vent pipe must not pass through any
unoccupied attic, inside wall, concealed space, or floor.
A19. Uninsulated single wall vent pipe must not be used
outdoors for venting appliances in regions where the 99% winter design temperature is below 32°F.A19. Long runs of horizontal or vertical combustion air pipes may require insulation in very cold climates to prevent the buildup of condensation on the outside of the pipe where the pipe passes through conditioned spaces.
A20. Vertical combustion air pipes should be fitted with a tee
with a drip leg and a clean out cap to prevent against the possibility of any moisture in the combustion air pipe from entering the unit. The drip leg should be inspected and cleaned out periodically during the heating season.
A21. The vent terminal must be:
Table 7.2 - Vent Terminals (two pipe)
Model Size Modine PN Other Listed Terminals
30-45 5H0722850005 Gary Steel 1092
60-75 5H0722850001 Gary Steel 1092
100-125 5H0722850001 Gary Steel 1092
A22. In addition to following these general instructions, specific
instructions for vertical and horizontal vent systems in 2-Pipe or concentric vent configurations must also be followed. The following outlines the differences:
Vertical Category III Vent System Determination
• Vertical vent systems terminate vertically (up) (an example is shown in Figure 8.1).
• Determine the venting configuration as follows:
> For two building penetrations through the wall or roof (one
for the combustion air inlet pipe and one for the vent pipe), proceed to “Section B - Vertical 2-Pipe Venting”.
> For a single larger building penetration through the wall or
roof, through which both the combustion air inlet and vent pipes will pass, proceed to “Section D - Horizontal and Vertical Concentric Venting”.
> For all other cases, proceed to the next section for
Horizontal Vent System Determination.
Horizontal Category III Vent System Determination
• Horizontal vent systems terminate horizontally (sideways) (an example is shown in Figure 9.1).
Determine the venting configuration as follows:
> For two building penetrations through the wall or roof (one
for the combustion air inlet pipe and one for the vent pipe), proceed to “Section C - Horizontal 2-Pipe Venting”.
> For a single larger building penetration through the wall or
roof, through which both the combustion air inlet and vent pipes will pass, proceed to “Section D - Horizontal and Vertical Concentric Venting”.
6-584.8
7
INSTALLATION - VENTING
Section B – Vertical 2-Pipe Vent System Installation
B1. This section applies to vertically vented 2-pipe (one
combustion air inlet pipe and one vent pipe) vent systems and is in addition to “Section A – General Instructions – All
Units”. B2. Vertical vent systems terminate vertically (up). B3. It is recommended to install a tee with drip leg and clean out
cap as shown in Figure 8.1. B4. The combustion air and vent pipes must be terminated with
2 listed vent caps. B5. Vertical vents must terminate a minimum horizontal and
vertical distance from roof lines and adjacent walls or
obstructions. These minimum distances are outlined in
Figure 8.1 and Table 8.1. B6. The vent must terminate at least 1' above and 6" horizontally
from the combustion air inlet.
Figure 8.1 - Vertical 2-Pipe Vent System - Sloped Roof
Table 8.1 - Minimum Height from Roof to Lowest Discharge Opening
Rise X (in) Roof Pitch Min Height H (ft) 0-6 Flat to 6/12 1.00 6-7 6/12 to 7/12 1.25 7-8 7/12 to 8/12 1.50 8-9 8/12 to 9/12 2.00 9-10 9/12 to 10/12 2.50 10-11 10/12 to 11/12 3.25 11-12 11/12 to 12/12 4.00 12-14 12/12 to 14/12 5.00 14-16 14/12 to 16/12 6.00 16-18 16/12 to 18/12 7.00 18-20 18/12 to 20/12 7.50 20-21 20/12 to 21/12 8.00
Size according to expected snow depth.
Figure 8.2 - Vertical 2-Pipe Vent System - Flat Roof
TO WALL OR ADJOINING BUILDING
MINIMUM DISTANCE TO ADJOINING WALL OR BUILDING IS 2 FEET.
REFER TO TABLE 8.1 FOR "H" DIMENSION.
ROOF FLASHING
"H" MIN*
(SEE TABLE 8.1)
USE LISTED THIMBLES THROUGH CEILING AND ROOF
X
ROOF PITCH IS:
X / 12
12
USE LISTED THIMBLE THROUGH ROOF AND CEILING
"H" MIN*
(SEE TABLE 8.1)
EXHAUST
COMBUSTION AIR
"H" MIN*
LISTED TERMINAL
TEE WITH DRIP LEG AND CLEANOUT CAP
(SEE TABLE 8.1)
LISTED TERMINAL
"H" MIN*
ROOF FLASHING
2' MIN
LISTED TERMINAL
6" MIN
LISTED TERMINAL
12" MIN
USE THIMBLE THROUGH CELLING
12" MIN*
Exhaust
ROOF FLASHING
* SIZE ACCORNING TO EXPECTED
Combustion Air
SNOW DEPTH.
TEE WITH DRIP LEG AND CLEANOUT CAP
B9. Once venting is complete, proceed section titled “Installation
– Gas Connections”.
BACK VIEW
4" MIN
EXHAUST
COMBUSTION AIR
12" MIN
RECOMMENDED
8
TEE WITH DRIP LEG AND CLEANOUT CAP
(SLOPE 1/4" PER FOOT DOWNWARD TOWARD DRIP LEG)
6-584.8
Loading...
+ 16 hidden pages