Modine HD75AS0111 Product Troubleshooting

Troubleshooting HD Direct Spark Units
Click here enter this application
Literature:6-586.0 Original: 10/5/15
evisions: NA
R

Troubleshooting HD Direct Spark Units

Enter

HOW TO USE THIS APPLICATION

This Application Contains Embedded Links in blue text
Follow the instructions on the page
Where appropriate, select the best answer
Yes
This will bring you to the correct page
Continue until the problem is solved
Select “Start Over” to return to the Table of Contents
No
Go to Table of Contents

TABLE OF CONTENTS

Definitions and Basic Oper ation Call for heat and units does nothing - Green Light ON
Call for heat and units does nothing - Green Light OFFT roubleshooting Codes for Ignition ControlUnit starts but does flame does not igniteFlame lights and shuts down within 10 secondsMain fan / air mover does not operateReplace control board O NLY after completing these steps FOR ADDITIONAL HELP & LIVE OPERATORS

DEFINITIONS & BASIC OPERATION

Soft Lockout of Control - The control does not initiate a call for heat or call for continuous f an while in lockout. The control will respond to an open limit and undesired flame. Lockout shall automatically reset af ter 1 hour. Lockout may be manually reset by removing power from the control for more than 1 second or removing the thermostat call for heat for more than 1 and less than 20 seconds.
Hard Lockout - If the control detects a f ault on the control board, t he status LED will be de-energized and the control will lockout as long as the fault remains. A hard lockout will automatically reset if the hardware fault clears.
Flame Status LED (Yellow LED labeled “FLAME”) is
provided to indicate flame status
Call for Heating Sequence of Operation
End of Call for Heating Sequence of Operation
Back Start Over

FLAME STATUS - YELLOW LED LABELED “FLAME”

Flame Status LED is Lit - When flame is sensed, the
flame LED is lit.
Flame LED flashes slowly - Flame current is below
1.0 uA (+/-50%), the to indicate “weak” flame.
Flame LED flashes fast - Flame is present with
gas valve off. If flame is sensed l onger than 4 secs while the gas v al v e is de-energized, the control shall energize the power exhauster and indoor blower motor. When flame is no longer sensed, the power exhauster will run through post-purge and the blower motor will run through fan off delay time. The control will do a soft lockout, but will still respond to open limit and flame. The Flame LED shall flash rapidly when lockout is due to undesired flame.
Yellow Flame LED
Back Start Over

HEATING SEQUENCE OF OPERATION

Call for heat
T stat contact close T stat on terminals R & W of board
24 volts from R to W terminal on board
Power exhauster cycles on. 115 VAC at IND and Neutral on board.
Starts pre purge cy cl e
24 volts through limits and pressure switch from board
Short delay and then 24 volts to gas valve from board
Igniter sparks
Flames carries to sensing probe and proves
Yellow light turns on, burner stays lit.
50 to 60 seconds later, fan motor cycles on.
115 volts at EAC and Neutral terminals.
Back Start Over

END OF HEATING SEQUENCE OF OPERATION

Call for heat ends
Thermostat contacts open
Burner flame off
Yellow light turns off.
Post purge on power exhauster
Power exhauster cycles off.
Fan motor cycles off.
Green light on board sta ys on.
Back Start Over

CALL FOR HEAT – UNIT DOES NOTHING

Green Light on Control Boar d is ON
Verify that the thermostat is wired correctly & there
is a call for heat
Thermostat should be wired between R & WIf the thermostat is wired correctly and the unit still
does not operate. Turn power off. Remove tstat wires. Carefully install a jumper wire between terminals R & W directly on the control board. Turn power on. BE AWARE THAT THE UNIT MAY START!
Did installing the jumper wire resolve the issue?
Yes No
Back Start Over

CALL FOR HEAT – UNIT DOES NOTHING

Green Light on Control Board is ON. Unit operates correctly when a jumper wire is installed between terminals R & W on the board
Check field wiring to the thermostatPotentially a bad thermostat (verify and replace if
needed)
Back Start Over

CALL FOR HEAT – UNIT DOES NOTHING

Green Light on Control Board is ON. Unit DOES NOT operate correctly when a jumper wire is installed between terminals R & W on the board
Check for loose connections. Disconnect and
reconnect all Molex plugs.
– Check to make sure there are NO troubleshooti ng
codes
– Turn the switch to the gas valve off and on. Then
leave on
Potentially a bad control board (verify and replace if
needed)
Back Start Over

CALL FOR HEAT – UNIT DOES NOTHING

Green Light on Control Board is OFF
– There will not be a flash code – Is there 24 VAC bet ween Sec & Com
on board?
Green Light
Yes
No
Sec & Com Terminals
Back Start Over

CALL FOR HEAT – UNIT DOES NOTHING

Green Light on Control Board is OFF. 24 VAC NOT present between Sec & Com on board
Possible Causes Check for loose connections Check incoming power (115 VAC) If incoming power is correct, check for 24VAC at
the secondary of the transformer. If incoming voltage is correct and no voltage at the secondary,
replace transformer
Back Start Over

CALL FOR HEAT – UNIT DOES NOTHING

Green Light on Control Board is OFF 24 VAC IS present between Sec & Com on board
Possible Causes
-Check fuse for blown element.
Remove the fuse. Check for continuity.
Do NOT just inspect element. Check for continuity. If the fuse is bad, replace fuse.
-Check for loose connections
-If fuse is not blown, terminal board is not letting 24 VAC through the board. Replace board.
Back Start Over

TROUBLESHOOTING FLASH CODES

No Flashes See Green Light is off
One Flash Pressure swi tch does not close within
30 seconds of inducer energized.
Two Flashes Pressure switch is closed before
inducer is energized
Three Flashes Open in the safety switch circuit
(limit switch or flame roll out switch is open)
Four, Five, Six or Seven Flashes
Back Start Over
Back Start Over

TROUBLESHOOTING FLASH CODES

Four Flashes In lockout from failed ignition
or flame loss
Five Flashes Twi n communic a ti ons fault
Six Flashes Open in the safety switch circuit
5 times during heat cycle (limit switch or flame roll out switch)
Seven Flashes 5 Flame losses during one
heat cycle
Back Start Over
Back Start Over

NO FLASHES – TROUBLESHOOTING CODES

No Flashes Go To:
Call for heat – unit does nothing
Back Start Over

ONE FLASH - TROUBLESHOOTING CODES

Does the power exhauster cycle on?
Yes No
Back Start Over

ONE FLASH – NO POWER EXHAUSTER

Pressure switch does not close within 30 seconds of inducer energized
Unit sequence:
Green Light on, call for heat, 24 volts at R & W on
board. Nothing happens. Green light will give One flash. Fan motor will not cycle on.
Possible cause:
Defective exhauster mot or. Receiving 115 volts from
IND and NEUTRAL terminals on board, but will not run. Replace exhauster .
Defective board. Not sending 115 volts from IND and NEUTRAL terminals to exhauster. Replace board
Back Start Over

ONE FLASH – PRESSURE SWITCH W ON’T CLOSE

Pressure switch does not close within 30 seconds of inducer energized
Unit sequence: Green light on, call for heat, 24 VAC at
R & W , power exhauster cycles on, after approx. 30 seconds, Green Light will give One Flash
Possible cause:
Blockage in tubing to pressure or venting not allowing
for a proper vacuum to pull pressure switch contacts closed. Troubleshoot Venting.
Wire off pressure switch
24 VAC not coming from board.
Defective pressure sw i tch (verify and replace)
Back Start Over

TWO FLASHES - TROUBLESHOOTING CODES

Pressure switch is closed before inducer is energized
Unit Sequence: Green light on, call for heat, 24 volts
at R & W terminal. Nothing will happen to unit operation except Green Light will give Two Flashes.
Possible Cause:
Defective or damaged pressure switch
Showing continuity between terminals in non-heat
mode
The two yellow wires are showing continuity in non-
heat mode.
Defective board (verify and replace if bad)
Back Start Over

THREE FLASHES - TROUBLESHOOTING CODES

Open in the safety switch circuit (limit switch or flame roll out switch is open)
The limit switch is ignored unless a call for heat is present (R to W energized). If the limit switch is open and a call for heat is present, the control de-energizes the gas valve, runs the blower motor, and runs the power exhauster. The control will flash “3” on the LED until the limit switch closes. When the switch re­closes or the call for heat is lost, the control runs the power exhauster through post-purge and runs the blower through the fan off delay. The control will return to normal operation after the blower off delay is completed.
Possible Causes
Back Start Over

THREE FLASHES - TROUBLESHOOTING CODES

Open in the safety switch circuit (limit switch or flame roll out switch is open).
Unit sequence:
Green Light on, call for heat. Power exhauster cycles on.
Fan Motor Cycles on. Green light starts three flashes.
Possible cause:
Open or short in safety circuit (flame roll out s witches som e and
some limit switches are man ual reset).
Check for open contacts on switch in safety circuit. Reset flame roll
out switches and manual reset limit switches
Check wiring. Wire off limit or flam e rollout switch. Limit or flame
rollout switch shorting to unit. Defec tive limit or flame rollout switch. Verify and replace if required.
Defective board, not letting 24 VAC through limits.
Back Start Over

FOUR FLASHES - TROUBLESHOOTING CODES

In lockout fr om failed ignition or f lame loss
Does the unit ignition spa rk
Yes No
Back Start Over

FOUR FLASHES - TROUBLESHOOTING CODES

In lockout fr om failed ignition or f lame loss unit DOES SPARK
Does the flame shut down wit hin 10 Seconds
Yes No
Back Start Over

FOUR FLASHES - TROUBLESHOOTING CODES

In lockout from failed ignition or flame loss unit
SPARKS and SHUTS DOWN within 10 seconds
Unit Sequence:
Green Light on, call for heat
Power exhauster cycles on, starts pre purge
24 VAC present through pressure switch, limits, and to
gas valve
Igniter sparks, burner cycles on for 10 seconds, then cycles off, no yellow flame light on board. Fan motor never cycles on.
Possible Causes
Back Start Over

FOUR FLASHES - TROUBLESHOOTING CODES

In lockout from failed ignition or flame loss unit
SPARKS and SHUTS DOWN within 10 seconds
Possible Causes:
Reversed Polarity
Wire off sensor. Check for loose wires
Dirty or defective flame sensor, not sending micro-
amps to board. Clean sensor with emery cloth. If the problem is not resolved, verify and replace sensor.
Defective board, getting correct micro-amps from sensor, but not allowing ignition
Back Start Over

FOUR FLASHES - TROUBLESHOOTING CODES

In lockout fr om failed ignition or flame loss unit
SPARKS and SHUTS DOWN within 10 seconds
Reversed Polarity
To check for reversed polarity. (1) Shut down all power
to unit (2) Switch main incoming power lines (black and
white) to unit. (3) Carefully turn main power back on to unit.
If issue is not resolved, shut off all power and return
white and black wires to original positions.
More possible causes
Back Start Over

FOUR FLASHES - TROUBLESHOOTING CODES

In lockout fr om failed ignition or flame loss unit
SPARKS and SHUTS DOWN within 10 seconds
Have eliminated Reversed Polarity
Wire off sensor. Check for loose wires
Dirty or defective flame sensor, not sending micro-amps
to board. Clean sensor with emery cloth. If the problem is not resolved, verify and replace sensor.
If issue is not resolved, shut off all power and return
white and black wires to original positions.
Potentially defective board.
Back Start Over

FOUR FLASHES - TROUBLESHOOTING CODES

In lockout from failed ignition or flame loss unit
SPARKS but DOES NOT IGNITE
Unit Sequence:
Green light on: call for heat, 24 VAC at R & W terminals
Power exhauster cycles on, start pre purge. 24 VAC
through pressure switch and limits.
Igniter sparks, no ignition, no y ellow flame sense light. Will cycle 5 times in this manner, then Green light will flash four times. Power exhauster will cycle off. Fan motor will never cycle on.
Possible Causes
Back Start Over

FOUR FLASHES - TROUBLESHOOTING CODES

In lockout from failed ignition or flame loss unit
SPARKS but DOES NOT IGNITE
Possible Causes:
Gas valve in “off” position
No 24 VAC from board to gas valve
Loose wires: wire off gas valve
Excessive Inlet pressure
Low or No gas pressure to inlet of valve (purge lines)
Defective Gas valve. Verify and replace of required
Defective board not allowing ignition
Back Start Over

FOUR FLASHES - TROUBLESHOOTING CODES

In lockout fr om failed ignition or f lame loss
unit DOES NOT SPARK
Unit Sequence:
Green Light on, call for heat
Power exhauster cycles on, starts pre purge
24 VAC power present through pressure switch, limits, and to valve
No spark at igniter, RAW gas is going through orifices for approx. 6 seconds during this cycle, then cycles off, no yellow flame sense light
Will cycle 5 times in this manner . T hen Green light will give four flashes. Power exhauster will cycle off. Fan motor does not turn on.
Possible Causes
Back Start Over

FOUR FLASHES - TROUBLESHOOTING CODES

In lockout fr om failed ignition or flame loss
unit DOES NOT SPARK
Possible Causes:
Loose wires: Wire off Igniter
Defective or damaged igniter. Examine, verify
and replace of required.
Defective board not sending v olt age to i gnite r
Back Start Over

FIVE FLASHES - TROUBLESHO OTING CODES

Twin c ommunications fault
Occurs if the 24 VAC supply to the twins are not in phase with each other, or power is removed from one of the twins.
While a Twin Fault exists, the control does not respond to thermostat commands and f lashes " 5" on the status LED. Open limit and undesired flame response are still operational. The control continually tries to establish communication and automatically resumes normal operation when communication is re-established. If a twin f ault occurs during a heat cycle, bot h furnaces terminate t he call for heat imm ediately. The only chance for blower mis-synchronization i s if the blower off delays are set differently on the t wins. If a twin fault occurs during high speed fan or continuous fan, both controls shut blowers off immediately.
Back Start Over

SIX FLASHES - TROUBLESHOO TING CODES

Open in the safety switch circuit 5 times during heat cycle (limit switch or flame roll out switch). Control goes into a hard lockout.
Lockout may be manually reset by removing power from the control for more tha n 1 second or removing the thermostat call for heat for more than 1 and less than 20 seconds
Does the fan (main air mover) cycle on?
Yes No
Back Start Over

SIX FLASHES - TROUBLESHOO TING CODES

Open in the safety switch circuit (limit switch or flame roll out switch is open). Main air mover CYCLES ON.
Unit sequence:
Green Light on, call for heat. Power exhauster cycles on.
Fan Motor Cycles on. Green light starts six flashes.
Possible cause:
Open contacts due to over-firing of unit (flame roll out switches
some and some limit switches are m anual reset).
Check gas pressure. Check to make sure noth i ng is blocking airflow
out of unit.
Wire off limit or flame rollout switch. Limit or flame rollout switch
shorting to unit. De f e ctive limit or flame rollout switch.
Defective board, not letting 24 VAC through limits.
Back Start Over

SIX FLASHES - TROUBLESHOO TING CODES

Open in the safety switch circuit (limit switch or flame roll out
switch is open). Main air mover DOES NOT cycle on.
Unit Sequence:
Green Light on, call for heat Power exhauster cycles on, pre purge
24 volts power present through pressure switch, limits, and to valve
Igniter Sparks, burner cycles on, yellow flame light on board is on.
After 3 to 4 mi nutes , unit goes out on a limit switch, yellow light off, green light will flash six times.
Possible cause:
Check all wiring, loose wire
Defective motor, 115 VAC present at EAC & Neutral terminals on
board, but motor does not run.
Defective board, 115 VAC not present at EAC and Neutral terminals
Back Start Over

SEVEN FLASHES - TROUBLESHOOTI NG CODES

5 Flame losses during one heat cycle
Ignition Re-Cycle - The c ontr ol wil l re-cycle
up to 5 flame losses (4 re-cycles) within a single call for heat before going to lockout. The LED will flash “ 7” during this lock out.
Back Start Over

BEFORE REPLACING THE CONTROL BOARD

Remove thermostat and use a temporary jumper wire to make a call for heat
Check the supply power for correct polarity
Rech eck all wiring to the control boa r d for loose connecti ons. Disconnect and reconnect all Molex plugs
Rech eck that the wiring to the contr ol boa r d matc hes the wiring diagr a m
If the control board has a fuse, remove and test continuity of the fuse. Do not just do a visual inspection
of the fuse - check continuity
Make sure the pressure switch is not opening during the call for heat cycle
Check limits and rollout switches for an open circuit
Turn the switch on the gas valve to off and then to on several times
Make sure power inducer is running when there is a call for heat
Check for a proper micro amp signal from the flame sensor to the control board. A proper signal is 1-5
micro-amps
Check for proper supply gas pressure. Excessive gas pressure can/will lockup the main valve
Check for limit and/or flame sensor shorts (make sure they are not touching metal)
Check for any moisture on board that may have occurred if checking for gas leaks with a liquid solution.
Check in-line regulators for BTU sizing, and lock up point not above a 14” WC.
Check setting of heat anticipator of t stat if applicable, and wire size and run
Rev iew troubleshooting codes.
Check for any moisture or moisture marks on the board that may have occurred if checking for gas leaks
with liquid solution.
Check in-line regulators for BTU sizing and lock up point not above a 14" WC
Check to make sure external regulator is not right next to the unit so that the regulator "fights" the
regulator inside the combination gas valve.
Check setting of heat anticipator of T -Stat if applicable, also check wire size and run length
Back Start Over
FOR ADDITIONAL HELP
INSTALLATION & SERVICE MANUAL
LIVE OPERATORS
HD Installation and Service Manual
Other Installation & Service Manuals
Live Operators: 800-828-4328
Back Start Over
Loading...