Modine 246443 User Manual

1-550.29
5H0707180000
February, 2015
INSTALLATION AND SERVICE MANUAL
steam/hot water unit heaters
Model HSB
Horizontal Delivery
Top/Bottom
Inlet/Outlet
Models V/VN
Vertical Delivery
Model HC
Horizontal Delivery
Side
Inlet/Outlet
Model PT/PTN
“Power-Throw”
IMPORTANT
The use of this manual is specifically intended for a qualified installation and service agency. A qualified installation and service agency must perform all installation and service of these appliances.
Inspection On Arrival
2. Check rating plate on unit to verify that power supply meets available electric power at point of installation.
3. Inspect unit received for conformance with description of product ordered (including specifications where applicable).
C
US
General Information
Installation and service instructions in this manual are applicable to the three types of steam/hot water unit heaters which should be installed in their proper applications for their most effective function as overhead heating units.
The copper coils are warranted for operation at steam or hot water pressures up to 150 lbs. per sq. in. gauge, and or temperatures up to 375°F, cupronickel tube units are warranted for operating pressures up to 250 PSI and operating temperatures up to 400°F. Canadian Standards Association (CSA) requriements state that explosion-proof units may not be used with a fluid temperature in excess of 329°F and still maintain their explosion-proof rating, for national electric code ignition temperature rating T3B for grain dust.
Motors are designed for continuous duty. They can operate in a maximum ambient temperature of 104°F (40°C).
The unit heaters are listed by the Canadian Standards Association as certified and Canadian Registered heat exchangers CRN OH 9234.5C. *Does not apply to V/PT 952.
CAuTION
Do not remove outlet fan guard from vertical type unit heaters.
Steam horizontal and vertical delivery unit heaters are available in both standard and low-outlet temperature models. Low outlet temperature models are recommended primarily for installation on heating systems with steam pressures of 30 to 150 PSI. When used at these steam pressures they provide lower outlet air temperatures for longer heat throw and, because of wider fin spacing, they are less susceptible to clogging in dusty atmospheres.
The model number of each unit heater indicates its rated Btu/Hr. capacity/1000 at 2 lbs. steam pressure and 60°F entering air temperature. For example an HSB 63 has an output of 63,000 Btu/Hr. at 2 lbs. steam and 60°F entering air.
THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
SPECIAL PRECAUTIONS / TABLE OF CONTENTS / SI (METRIC) CONVERSION FACTORS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE, EFFICIENT AND TROUBLE-FREE OPERATION. IN ADDITION, PARTICULAR CARE MUST BE EXERCISED REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW. FAILURE TO PROPERLY ADDRESS THESE CRITICAL AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS, PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS ARE SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation
which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation
which, if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which,
if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided,
MAY result in a potential safety concern.
dANgeR
Appliances with power codes 01, 02, 04, 05, and 10 must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
wARNINg
1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
3. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
4. Ensure that the supply voltage to the appliance as indicated on the serial plate, is not 5% greater than the rated voltage.
5. When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine Manufacturing Company. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the
owner’s risk.
1. Start-up and adjustment procedures must be performed by a qualified service agency.
2. To check most of the Possible Remedies in the troubleshooting guide listed in Table 15.1, refer to the applicable sections of the manual.
Table of Contents
General Information .............................................................. 1
Special Precautions .............................................................. 2
SI (Metric) Conversion Factors ............................................. 2
Unit Location......................................................................... 3
Unit Mounting ....................................................................3-4
Unit Suspension ................................................................... 5
Installation .........................................................................5-6
Piping ................................................................................ 5
Electrical Connections ......................................................5
Operation .............................................................................. 6
Prior to Operation.............................................................. 6
Initial Start-up .................................................................... 6
Automatic Control Operations ........................................... 6
General ............................................................................. 7
Performance Data ........................................................... 8-11
Dimensional Data .......................................................... 12-13
Motor Ampere Ratings ........................................................ 14
Service................................................................................ 14
Service / Troubleshooting ................................................... 15
Warranty ................................................................Back Page
SI (METRIC) CONVERSION FACTORS
Table 2.1
To Convert Multiply By To Obtain
"W.C. 0.249 kPa °F (°F-32) x 5/9 °C Btu 1.06 kJ Btu/ft Btu/hr 0.000293 kW CFH (ft CFH (ft
3
/min) 0.0283 m3/min
CFM (ft
3
/min) 0.000472 m3/s
CFM (ft
IMPORTANT
3
37.3 kJ/m
3
/hr) 0.000472 m3/min
3
/hr) 0.00000787 m3/s
3
To Convert Multiply By To Obtain
feet 0.305 m Gal/Hr. 0.00379 m Gal/Hr. 3.79 l/hr gallons 3.79 l Horsepower 746 W inches 25.4 mm pound 0.454 kg psig 6.89 kPa psig 27.7 "W.C.
3
/hr
CAuTION
1. Do not remove outlet fan guard from vertical type unit heaters.
2. Do not install units below 8 feet measured from the bottom of the unit to the floor.
3. Service or repair of this equipment must be performed by a qualified service agency.
4. Do not reuse any electrical component which has been wet. Replace component.
5. Ensure that the supply voltage to the appliance, as indicated on the serial plate is not 5% less than the rated voltage.
6. Heaters are designed for use in heating applications with ambient temperatures between 0°F and 100°F in hot water applications and -10°F to 100°F in steam applications.
2
1-550.29
UNIT LOCATION / UNIT MOUNTING
UNIT LOCATION
dANgeR
Appliances with power codes 01, 02, 04, 05, and 10 must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.
1. Units should not be installed in atmospheres where corrosive fumes or sprays are present.
2. Be sure no obstructions block air intake or air discharge of unit heater.
3. Locate horizontal delivery unit heaters so air streams of individual units wipe the exposed walls of the building with either parallel or angular flow without blowing directly against the walls. Heaters should be spaced so the air stream from one supports the air stream from another heater. See Figure 3.1.
4. Columns, machinery, partitions, and other obstacles should not interfere with air streams from unit heaters.
5. Unit heaters installed in a building exposed to a prevailing wind should be located to direct a major volume of heated air along the windward wall of the building.
6. Large expanses of glass, or large doors that are frequently opened, should be covered by long-throw unit heaters such as large horizontal delivery of “Power-Throw” unit heaters.
7. Vertical delivery unit heaters should generally be located in the central area of the space to be heated. Place horizontal delivery units along the walls of the same building where heat loss is usually greatest. See Figure 3.3.
8. Arrange horizontal delivery units so they do not blow directly at occupants. Air streams from this type of unit should be directed down aisles, into open spaces on the floor, or along exterior walls.
9. When only vertical delivery units are installed, they should be located so exposed walls are blanketed by their air streams. See Figure 3.2.
Figure 3.1 - Horizontal Delivery Unit Location
Figure 3.3 - Combination Horizontal and Vertical Delivery Unit Installation
UNIT MOUNTING
CAuTION
Do not install units below 8 feet measured from the bottom of the unit to the floor.
Do not install unit above recommended maximum mounting heights. Height at which unit heaters are installed is critical. Maximum mounting heights for all units are listed in Table 4.1 and the height dimensions are shown in Figures 4.3 through
4.7. Maximum mounting heights for vertical models are given for units with or without optional air deflectors. The data in Table 4.1 is based on operating conditions of 2 lbs. steam or 220°F entering water with 60°F entering air. When operating conditions are other than those above, refer to Figure 4.2 for maximum mounting height correction factor. To obtain the maximum mounting at actual operating conditions, multiply the appropriate factor from Figure 4.2 by the mounting height in Table 4.1. The maximum mounting height for all units is that height above which the unit heater will not deliver heated air to the floor at standard rating conditions.
Figure 3.2 - Unit Locations of Vertical Units In Narrow Buildings
Deflector Mounting
If an optional air deflector has been furnished for vertical units, it is always shipped separately and can be attached to the unit before suspension. Vertical louvers for horizontal units and horizontal louvers for “Power-Throw” units can also be added and positioned before installation. Cone-jet and louver-type deflectors must be attached with angle brackets and machine screws to the bottom cover of the unit. Refer to mounting instructions which are furnished with each deflector.
Depending on supply or return piping arrangement, there is a possibility of interference between certain anemostat air deflectors and piping on some vertical air delivery unit heaters. Check dimensions.
1-550.29
3
1.3
1.2
1.1
1.0 .9 .8 .7 .6 .5
Correction Factor "R"
150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 310 320 330 340 350 360 370
Steam Pressure
25 10 20 30 50 70 100
150
UNIT MOUNTING
Table 4.1 - Maximum Mounting Heights
Vertical Type with Deectors
Horizontal Type Power-Throw Type
Height (ft)
Model No.
HSB/HC 18 8 9 V/VN 42 11 13 15 17 8 9 13 15 HSB/HC 24 9 11 V/VN 59 14 16 19 22 9 11 16 18 HSB/HC 33 10 12 V/VN 78 15 19 20 26 11 14 17 22
HSB/HC 47 12 14 V/VN 95 15 19 20 26 11 14 17 22 HSB/HC 63 14 16 V/VN 139 18 23 24 31 13 17 21 26 HSB/HC 86 15 17 V/VN 161 20 26 27 35 14 18 23 30
HSB/HC 108 17 19 V/VN 193 22 27 30 36 16 19 25 31 HSB/HC 121 16 18 V/VN 212 22 27 30 36 16 19 25 31 HSB/HC 165 19 21 V/VN 247 26 32 34 42 17 21 30 37 HSB/HC 193 18 PT/PTN 279 16 V/VN 279 30 36 37 45 18 22 35 41 HSB/HC 258 19 22 PT/PTN 333 17 V/VN 333 30 36 37 45 17 20 35 41 HSB/HC 290 20 23 PT/PTN 385 17 V/VN 385 30 36 36 43 17 20 35 41 HSB/HC 340 20 23 PT/PTN 500 18 V/VN 500 37 45 44 54 19 24 42 51
PT/PTN 610 20 22 V/VN 610 36 44 43 52 19 24 41 50 — PT 952 21 V 952 37 45
With horizontal louvers opened 30° from the vertical plane. HSB units have top and bottom piping connections, HC units have side connections. All have copper tubes.V and PT models have copper tubes, VN and PTN models have cupronickel tubes. Mounting heights are maximum for heaters operating at standard conditions
(2 lbs. steam or 220°F water with 60°F entering air). Heights listed for Louver or Cone-Jet are with deflectors in fully-opened position. Refer to Figure 4.2 for correction of mounting heights under other operating conditions. Maximum mounting height will be reduced as entering air temperatures exceed 60°F.
Std. L.O.T. Std. L.O.T. Std. L.O.T. Std. L.O.T. Std. L.O.T. Std. L.O.T.
Model No.
Height (ft)
No Deector Cone-Jet Truncone Louvers
Height (ft) Height (ft) Height (ft) Height (ft)
Model No.
Figure 4.2 - Maximum Mounting Heights Correction Factors
These correction factors are to be used as multipliers to correct the maximum recommended mounting heights of unit heaters when operated with steam pressures other than 2 pounds or with water at other than average temperature of 220°F.
Figure 4.3 - Horizontal Unit Delivery
H
Figure 4.4 - Vertical One-Way & Two-Way Louvers
H
H
Figure 4.3 - Vertical Cone Jet
H
4
H
Figure 4.6 - Vertical Truncone
H
1-550.29
UNIT SUSPENSION / INSTALLATION
UNIT SUSPENSION
Horizontal delivery units, Model HSB/HC Series. All horizontal
delivery units, except Models HSB 18 and HSB 24, have two tapped holes in the top for unit suspension. HSB 18 and HSB 24 models do not require independent suspension and are installed directly on their supply piping. Models HSB 33-86 and HC 18-86 have 3/8"-16 tapped holes, model sizes 108 and larger have 1/2"-13 tapped holes. Piping support hangers or clamps are recommended and should be placed as close to the unit heater as possible. For other models, independent suspension can be made with threaded rods, pipes, or ceiling hanger brackets. See Figure 5.1.
Vertical delivery units. Vertical delivery Models V/VN 42 through V/VN 279 have four tapped holes (1/2"-13) in the top cover for unit suspension. Unit suspension for these models can be made with threaded rods, pipes or ceiling hanger brackets. Models V/VN 333 through V/VN 952 are equipped with an angle­iron mounting bracket that has eight 5/8" diameter hanger holes permitting hook-hoisting and suspension with cables, if desired. A 1/2" x 3" center U-bolt can be inserted in the two holes at each end of the bracket to accommodate suspension with four threaded rods, pipes or hanger brackets.
"Power-Throw" horizontal delivery units. “Power-Throw” units are designed for horizontal air delivery and are equipped with hanger brackets for suspension. Three hanger brackets are supplied for Model PT/PTN 279, one on the front, and two on the rear panel for three-point suspension. Only two hanger brackets are furnished on the front panel of Models PT/PTN 333 through PT/PTN 952 (for required four-point suspension use the two hanger brackets on the front panel and the two holes on the ends of the upper angle supports at the rear of the unit). Each hanger bracket has a 5/8" diameter mounting hole for hook­hoisting and suspension with threaded rods, pipes, or cables.
Note: A pipe hanger adapter kit as illustrated in Figure 5.1 is available as an accessory from Modine. The kit consists of two drilled 3/4" I.P.S. pipe caps and two capscrews to facilitate threaded-pipe suspension. One kit will mount applicable HSB or HC models, two kits are required for V/VN models.
Figure 5.1 - Unit Suspension
water systems, include a balancing valve in return line for water flow regulation. A drain valve should also be provided below each unit heater to allow removal of water from the heating coil if located in an area subject to freezing.
3. In steam or hot water systems, rapid air removal is required because entrained air is a cause of corrosion. Hot water systems should be equipped with suitable air vent valves for rapid and complete removal of air at the high points and ends of both supply and return mains. Proper air venting for steam systems can be achieved by use of a steam trap with an internal air vent.
4. Traps must be located below the outlet of the unit. Consult trap manufacturer for specific recommendations. Each steam unit heater should be provided with a trap of sufficient size and capacity to pass a minimum of two times the normal condensate released by the unit at the minimum differential pressure in the system. Trap capacity is based on the pressure differential between supply and return mains. Steam systems should be equipped with a float and thermostatic trap or an inverted bucket trap with an air bypass.
5. It is advisable to use a pipe line strainer before each steam trap draining a unit heater. This protection will reduce the maintenance of the steam trap. When strainers are used they should be installed between the unit heater and the trap and be the same size as the trap tapping. In order to catch dirt and scale, the strainer should have a screen perforation size smaller than the trap orifices.
6. On systems where the steam supply to the unit heater is modulated or controlled by a motorized valve, a vacuum breaker should be installed between unit outlet and the trap. If a vacuum breaker is used, it should be in conjunction with a float and thermostatic trap.
7. Install a scale pocket at bottom of unit heater to collect dirt and scale as shown in illustrations. Pipe diameter must be the same size as unit connections and about 6" long.
8. Provide adequate pipe hangers, supports, or anchors to secure the piping system independently of the unit heater.
Electrical Connections
Piping - See Figure 6.1
1. Branch piping to and from unit heater should include swing joints to allow for expansion and contraction of the piping without placing a strain on the unit heater element. On steam systems, the branch piping should be taken off and returned above the centerline of the supply and return lines.
2. Install pipe unions and shut-off valves in lines to and from each unit heater to allow maintenance or replacement of unit without shutting down and draining entire system. For hot
wARNINg
1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
3. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
4. Ensure that the supply voltage to the appliance as indicated on the serial plate is not 5% greater than the rated voltage.
CAuTION
1. Do not install units below 8 feet measured from the bottom of the unit to the floor.
2. Do not reuse any electrical component which has been wet. Replace component.
3. Ensure that the supply voltage to the appliance, as indicated on the serial plate is not 5% less than the rated voltage.
1. Installation of wiring must conform with local building codes, or in the absence of local codes, with the National Electric Code ANSI/NFPA 70 - Latest Edition. Unit must be electrically grounded in conformance to this code. In Canada, wiring must comply with CSA C22.1, Electrical Code.
1-550.29
5
INSTALLATION / OPERATION
Figure 6.1 - Suggested Piping Arrangements
Hot Water Systems
Horizontal Unit Heater Connected to
Overhead Hot Water Mains
Vertical Unit Heater Connected to
Lower Hot Water Mains
Steam Systems
Unit Heater Connection for High Pressure Steam
Arrangements shown are recommendations only. Where horizontal units are shown, vertical units can be substituted or vice versa. For modifications to piping
suggestions shown, refer to your local plumbing authority.
Electrical Connections (Cont.)
2. Electric wiring must be sized to carry the full load amp draw of the motor, starter, and any controls that are used with the unit heater. All units with power codes 04, 05, 09, or 10 (polyphase motors) must be provided with suitable overcurrent protection in circuit supplying heater at installation. Overcurrent protectors should be sized based on motor current rating shown on the unit serial plate, and applicable national electric code procedures.
All units are provided with an electrical junction box. Junction boxes are either integral to the motor or attached to the unit casing. Units with explosion-proof motors have an explosion-proof junction box attached to the motor.
Any damage to or failure of Modine units caused by
incorrect wiring of the units is not covered by Modine’s
standard warranty.
3. Location of room thermostat, when supplied, should be in
the natural circulating path of room air. Mount thermostat about five feet above floor level where it will not be affected by heat from the unit or other sources of drafts that would prevent it from properly controlling room temperature. See instructions packed with the thermostat.
4. Speed controllers furnished with specified unit heater fan
motors, are packed separately and must be connected according to wiring diagram with each controller.
OPERATION
Prior to Operation
1. Make sure fuses are installed in fused disconnect switches.
2. Check all electrical connections to assure they are secure.
3. Check rigidity of unit mounting. Tighten all fasteners,
4. Inspect piping, strainers, traps, fittings, etc.
Initial Start-Up
1. Set thermostat to lowest position.
2. Turn on power supply to unit.
3. Open return gate valve, and then open supply gate valve
4. Raise thermostat setting to desired position.
5. Adjust louvers (if provided) for desired heat distribution.
6. To insure proper sequence of operation, cycle unit on and off
7. Check for proper rotation of fan. All fans must rotate in a
Automatic Control Operations
Install one of the following operating systems for continuous automatic control.
Intermittent Fan Operation — Hot Coil
A room thermostat starts and stops the fan motor. An aquastat is sometimes strapped to the return piping to prevent fan operation when heat is not being supplied to the unit heater.
Unit Heater Connection for Low-Pressure Steam
Open Gravity or Vacuum Return System
if necessary.
to unit.
a few times by raising and lowering thermostat setting.
counterclockwise direction when viewed from the back (HSB/HC, PT/PTN) or top (V/VN) of the unit heater.
Continuous Fan Operation — Intermittent Hot/Cold Coil
A room thermostat controls a valve which opens to allow steam or hot water to supply the unit and closes to shut off the supply when the thermostat is satisfied.
6
1-550.29
OPERATION
Figure 7.1 - Horizontal Delivery Unit Cutaway
Connections — Female-type permits direct connection of unit heater to the
piping. HC models have copper connectors at side of the unit.
Vertical fins — Less opportunity for dust and dirt to collect. Reduces cleaning. Fins die-formed for added strength and heat transfer.
Coil — All air passes through coil. Heating is uniform. Design assures maximum control over air delivery and temperature of air leaving the heater. Aluminum fins die-formed for added strength — increased heat transfer. Fins mechanically bonded to serpentine copper tube.
Motor — All motors are totally enclosed. Single phase types include built-in thermal overload protection. All motor wiring is terminated in an electrical junction box either supplied on the unit heater or as an integral part of the motor.
Fan — Lightweight. Blades accurately balanced and pitched to move air quietly and positively — with minimum power requirement.
Safety fan guard — Standard equipment. Bolted steel rod fan guard completely surrounds the fan offering constant protection.
Deflector blades — Adjustable horizontal air-deflector blades are standard — vertical blades are optional.
Casings — Electrostatically applied, gray-green polyester powder coat paint finish is applied over rust- and corrosion-treated steel for long life.
Figure 7.2 - Typical Horizontal Unit with Standard Junction Box
Figure 7.4 - Vertical Delivery Unit Cutaway
Motor-Cooling Cone — Shields
motor from coil heat — prolongs life of insulation, windings, and lubricant. Prolongs motor life.
Coil — Aluminum fins mechanically bonded to tubes for maximum heat transfer. All steam- and water­carrying passages between heavy steel pipe connections are copper, or cupronickel.
Motor — All motors are totally enclosed. Single phase types include built-in thermal overload protection.
Figure 7.3 - Horizontal Unit with Optional Fingerproof Fan Guard
Junction Box — Easier installation
with single point electrical connection.
Motor easily removable — Modine design permits motor to be removed through opening below the unit — especially important where heaters are installed close to ceiling.
Vertical fins — Less opportunity for dust and dirt to collect. Exposed for easy cleaning with air hose and brush.
Fan — Accurately balanced to operate quietly and at lowest possible power consumption.
1-550.29
Casings — Electrostatically applied, gray-green polyester powder coat paint finish applied over rust- and corrosion­treated steel lasts longer.
7
STEAM PERFORMANCE DATA - STANDARD MODELS
Table 8.1 - Performance Data for Standard Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air High Motor Speed
Air Data Motor Data
Type Model No. Btu/hr
HSB/HC 18 18,000 75 8 17 340 625 107 19 1/60 1,550 HSB/HC 24 24,000 100 9 18 370 695 119 25 1/25 1,550 HSB/HC 33 33,000 138 10 21 630 690 108 34 1/25 1,550 HSB/HC 47 47,000 196 12 28 730 810 119 49 1/12 1,550 HSB/HC 63 63,000 263 14 29 1,120 690 111 65 1/12 1,550
Horizontal
Delivery
Power-
Throw™
Vertical
Delivery
HSB/HC 86 86,000 358 15 31 1,340 835 11 8 89 1/8 1,625 HSB/HC 108 108,000 450 17 31 2,010 790 109 11 2 1/8 1,625 HSB/HC 121 121,000 504 16 25 1,775 715 122 125 1/5 1,075 HSB/HC 165 165,000 688 19 40 3,240 880 106 171 1/3 1,075 HSB/HC 193 193,000 804 18 38 2,900 810 121 200 1/3 1,075 HSB/HC 258 258,000 1,075 19 44 4,560 750 111 267 1/2 1,075 HSB/HC 290 290,000 1,208 20 46 4,590 765 11 7 300 1/2 1,075 HSB/HC 340 340,000 1,417 20 46 5,130 735 120 352 1/2 1,075
PT/PTN 279 279,000 1,163 16 100 5,460 2,165 111 289 1/2 1,075 PT/PTN 333 333,000 1,388 17 110 5,980 2,165 11 6 345 3/4 1,140 PT/PTN 385 385,000 1,604 17 115 7,680 1,860 11 0 398 1 1,140 PT/PTN 500 500,000 2,083 18 130 10,390 2,520 108 517 1 1/2 1,140 PT/PTN 610 610,000 2,542 20 140 11,750 2,315 11 2 631 1 1/2 1,140
PT 952 952,000 3,967 21 145 12,170 2,321 139 985 2 1,140 V/VN 42 42,000 175 11 15 17 11 950 825 103 43 1/30 1,050 V/VN 59 59,000 246 14 19 21 14 1,155 1,005 111 61 1/30 1,050 V/VN 78 78,000 325 15 20 23 15 1,590 1,065 109 81 1/15 1,050 V/VN 95 95,000 396 15 20 23 15 1,665 1,120 118 98 1/15 1,050
V/VN 139 139,000 579 18 24 27 18 2,660 1,285 112 144 1/6 1,075 V/VN 161 161,000 671 20 27 30 20 2,945 1,420 115 167 1/3 1,075 V/VN 193 193,000 804 22 30 33 22 3,500 1,690 116 200 1/3 1,075 V/VN 212 212,000 883 22 30 33 22 3,610 1,740 120 219 1/3 1,075 V/VN 247 247,000 1,029 26 34 39 26 4,820 1,910 111 256 1/2 1,075 V/VN 279 279,000 1,163 30 37 45 30 5,460 2,165 111 289 1/2 1,075 V/VN 333 333,000 1,388 30 37 45 30 5,980 2,165 116 345 3/4 1,140 V/VN 385 385,000 1,604 30 36 45 30 7,680 1,860 110 398 1 V/VN 500 500,000 2,083 37 44 56 37 10,390 2,520 108 517 1 1/2 1,140 V/VN 610 610,000 2,542 36 43 54 36 11,750 2,315 112 631 1 1/2 1,140
V 952 952,000 3,967 37 56 12,170 2,321 139 985 2 1,140
Sq. Ft.
EDR
Maximum Mounting
Height (ft.)
Heat Throw
or Spread @
Max. Height
CFM
Outlet
Velocity
(Fpm)
Final Air
Temp.
(°F)
Condensate
lb/hr
lbs.
2
STEAM
60° ENT. AIR
Approx.
Hp
RPM
1,140
Table 8.2 - Performance Data for Standard Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air Reduced Motor Speed
Air Data Motor Data
Type Model No. Btu/hr
HSB/HC 18 14,000 58 8 10 220 415 11 8 14 1/60 1,000 HSB/HC 24 18,000 75 9 11 230 440 131 19 1/25 1,000
Horizontal
Delivery
Horizontal units with horizontal louvers open 30° from vertical plane. Vertical types equipped with cone jet deflector, blades fully opened are shown in bold. CFM for horizontal types is entering CFM. CFM for vertical and "Power-Throw" types is leaving CFM.
V and PT models have copper tubes, VN and PTN models have 90/10 cupro-nickel tubes. Requires Solid State Motor Speed Controller.
HSB/HC 33 25,000 104 10 13 395 440 118 26 1/25 1,000 HSB/HC 47 38,000 158 12 17 450 515 137 39 1/12 1,000 HSB/HC 63 47,000 195 14 17 685 430 122 49 1/12 1,000 HSB/HC 86 64,000 265 15 19 825 525 131 66 1/8 1,000
HSB/HC 108 81,000 340 17 19 1,255 500 11 9 84 1/8 1,000
Sq. Ft.
EDR
Maximum Mounting
Height (ft.)
8
Heat Throw
or Spread @
Max. Height
1-550.29
CFM
Outlet
Velocity
(Fpm)
Final Air
Temp.
(°F)
Condensate
lb/hr
Hp
Approx.
RPM
STEAM PERFORMANCE DATA - LOW OUTLET TEMPERATURE MODELS
2
lbs.
STEAM
60° ENT. AIR
Table 9.1 - Performance Data for Low Outlet Temperature Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air High Motor Speed
Air Data Motor Data
Type Model No. Btu/hr
HSB/HC 18L 15,900 66 9 20 364 655 100 16 1/60 1,550 HSB/HC 24L 19,300 80 11 21 435 795 100 20 1/25 1,550 HSB/HC 33L 29,500 123 12 24 695 745 99 31 1/25 1,550 HSB/HC 47L 32,000 133 14 32 855 910 94 33 1/12 1,550 HSB/HC 63L 52,500 219 16 33 1,170 710 101 54 1/12 1,550
Horizontal
Delivery
Power-
Throw™PT/PTN 610L 470,000 1,958 22 154 2,400 2,445 97 486 1-1/2 1,140
HSB/HC 86L 61,500 256 17 36 1,510 910 97 64 1/8 1,625 HSB/HC 108L 86,500 360 19 36 2,150 825 97 90 1/8 1,625 HSB/HC 121L 88,000 367 18 29 2,070 800 98 91 1/5 1,075 HSB/HC 165L 143,000 596 21 45 3,480 930 97 148 1/3 1,075 HSB/HC 258L 190,000 792 22 51 4,655 750 98 197 1/2 1,075 HSB/HC 290L 207,000 863 23 53 5,040 805 94 214 1/2 1,075 HSB/HC 340L 255,000 1,063 23 53 5,575 775 102 264 1/2 1,075
Sq. Ft.
EDR
Maximum Mounting
Height (ft.)
Heat Throw
or Spread @
Max. Height
CFM
Outlet
Velocity
(Fpm)
Final Air
Temp.
(°F)
Condensate
lb/hr
Hp
Approx.
RPM
V 42L 33,000 138 13 17 20 13 960 835 94 34 1/30 1,050 V 59L 44,000 183 16 22 24 16 1,190 1,035 96 45 1/30 1,050 V 78L 62,000 258 19 26 29 19 1,740 1,070 95 65 1/15 1,050
V 95L 71,000 296 19 26 29 19 1,760 1,180 99 73 1/15 1,050 V/VN 139L 103,000 429 23 31 35 23 2,860 1,380 95 106 1/6 1,075 V/VN 161L 127,000 529 26 35 39 26 3,400 1,640 96 132 1/3 1,075
Vertical
Delivery
V/VN 193L 149,000 621 27 36 41 27 3,710 1,790 99 154 1/3 1,075 V/VN 212L 163,000 679 27 36 41 27 3,830 1,845 102 169 1/3 1,075 V/VN 247L 190,000 792 32 42 48 32 5,110 2,030 96 197 1/2 1,075 V/VN 279L 215,000 896 36 45 54 36 5,790 2,300 96 222 1/2 1,075 V/VN 333L 256,000 1,067 36 45 54 36 6,340 2,300 100 265 3/4 1,140 V/VN 385L 296,000 1,233 36 43 54 36 8,140 1,970 95 307 1 1,140 V/VN 500L 385,000 1,604 45 54 68 45 11,000 2,670 94 400 1-1/2 1,140 V/VN 610L 470,000 1,958 44 52 66 44 12,400 2,445 97 485 1-1/2 1,140
V 952L 733,000 3,055 45 - 68 - 12,940 2,450 115 759 2 1,140
Table 9.2 - Performance Data for Low Outlet Temperature Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air Reduced Motor Speed
Air Data Motor Data
Type Model No. Btu/hr
HSB/HC 18L 12,000 51 9 12 230 425 108 12 1/60 1,000 HSB/HC 24L 14,400 60 11 13 265 490 109 15 1/25 1,000
Horizontal
Delivery
Horizontal units with horizontal louvers open 30° from vertical plane. Vertical types equipped with cone jet deflector, blades fully opened are shown in bold. CFM for horizontal types is entering CFM. CFM for vertical and "Power-Throw" types is leaving CFM.
V and PT models have copper tubes, VN and PTN models have 90/10 cupro-nickel tubes. Requires Solid State Motor Speed Controller.
HSB/HC 33L 22,000 92 12 14 430 470 107 23 1/25 1,000 HSB/HC 47L 24,300 101 14 19 540 580 101 25 1/12 1,000 HSB/HC 63L 39,500 164 16 20 725 445 109 41 1/12 1,000 HSB/HC 86L 46,000 192 17 22 925 565 105 48 1/8 1,000
HSB/HC 108L 65,000 270 19 22 1,330 520 104 67 1/8 1,000
Sq. Ft.
EDR
Maximum Mounting
Height (ft.)
Heat Throw
or Spread @
Max. Height
CFM
Outlet
Velocity
(Fpm)
Final Air
Temp.
(°F)
Condensate
lb/hr
Hp
Approx.
RPM
1-550.29
9
HOT WATER PERFORMANCE DATA - STANDARD MODELS
Table 10.1 - Performance Data for Standard Units at Standard Conditions of 200°F Entering Water and 60°F Entering Air High Motor Speed
Water Data Air Data Motor Data
Type Model No. Btu/hr
HSB/HC 18 12,600 1.3 0.5 0.3 / 5.0 9 18 340 615 93 1/60 1,550 HSB/HC 24 16,200 1.7 0.8 0.3 / 5.0 10 19 370 675 100 1/25 1,550 HSB/HC 33 21,700 2.3 0.2 0.4 / 10.0 11 23 630 675 91 1/25 1,550 HSB/HC 47 30,900 3.2 0.4 0.4 / 10.0 13 30 730 785 98 1/12 1,550 HSB/HC 63 45,600 4.7 0.6 0.5 / 20.0 15 31 1,120 680 97 1/12 1,550
Horizontal
Delivery
HSB/HC 86 60,200 6.3 1.0 0.5 / 20.0 16 33 1,340 820 101 1/8 1,625 HSB/HC 108 83,700 8.7 2.8 0.5 / 30.0 18 33 2,010 775 98 1/8 1,625 HSB/HC 121 93,000 9.7 3.3 0.7 / 30.0 17 27 1,775 700 107 1/5 1,075 HSB/HC 165 130,900 13.6 8.6 2.0 / 30.0 20 43 3,240 870 96 1/3 1,075 HSB/HC 193 143,000 14.9 1.4 2.0 / 50.0 19 41 2,900 790 105 1/3 1,075 HSB/HC 258 201,900 21.0 5.7 2.5 / 70.0 20 47 4,560 740 100 1/2 1,075 HSB/HC 290 228,600 23.8 7.1 2.5 / 70.0 22 50 4,590 750 105 1/2 1,075 HSB/HC 340 271,100 28.2 11.3 2.8 / 70.0 22 50 5,130 720 108 1/2 1,075
PT/PTN 279 192,300 20.0 0.2 4.5 / 60.0 17 108 5,460 2,165 94 1/2 1,075
Power-
Throw™
PT/PTN 333 238,500 24.8 0.4 4.5 / 100.0 18 11 7 5,980 2,165 99 3/4 1,140 PT/PTN 385 276,100 28.8 0.6 4.5 / 100.0 18 124 7,680 1,860 95 1 1,140 PT/PTN 500 358,000 37.3 0.5 6.0 / 100.0 19 138 10,390 2,520 93 1 1/2 1,140 PT/PTN 610 450,400 46.9 1.0 6.0 / 100.0 22 151 11,750 2,315 97 1 1/2 1,140
PT 952 721,600 75.2 1.1 14.0 / 200.0 23 150 12,166 2,321 120 2 1,140 V/VN 42 30,100 3.1 0.6 0.5 / 10.0 12 16 18 12 950 825 90 1/30 1,050 V/VN 59 42,600 4.4 0.5 0.8 / 15.0 15 20 22 15 1,155 1,005 96 1/30 1,050 V/VN 78 57,000 5.9 0.5 1.0 / 20.0 16 22 24 16 1,590 1,065 95 1/15 1,050 V/VN 95 69,300 7.2 0.5 1.3 / 25.0 16 22 24 16 1,665 1,120 101 1/15 1,050
V/VN 139 106,600 11.1 2.6 1.0 / 30.0 19 26 29 19 2,660 1,285 99 1/6 1,075 V/VN 161 123,200 12.8 2.2 1.3 / 40.0 21 29 32 22 2,945 1,420 101 1/3 1,075
Vertical
Delivery
V/VN 193 147,200 15.3 2.2 1.5 / 50.0 23 32 35 24 3,500 1,690 101 1/3 1,075 V/VN 212 161,700 16.8 1.5 2.0 / 60.0 23 32 35 24 3,610 1,740 104 1/3 1,075 V/VN 247 188,700 19.7 2.1 2.0 / 60.0 28 37 41 28 4,820 1,910 98 1/2 1,075 V/VN 279 212,600 22.2 2.1 2.3 / 75.0 32 V/VN 333 260,100 27.1 3.8 2.8 / 75.0 32 40 48 32 5,980 2,165 102 3/4 1,140 V/VN 385 302,100 31.5 5.0 3.3 / 75.0 32 39 48 32 7,680 1,860 98 1 1,140 V/VN 500 391,700 40.8 4.8 3.0 / 100.0 39 47 59 40 10,390 2,520 96 1 1/2 1,140 V/VN 610 450,400 46.9 1.0 6.0 / 100.0 38 46 57 39 11,750 2,315 97 1 1/2 1,140
V 952 721,600 75.2 1.1 14.0 / 200.0 39 59 12,166 2,321 120 2 1,140
GPM
Pressure
Drop
(Ft. of
Water)
Min/Max
GPM
Maximum Mounting
Height (ft.)
Heat Throw
or Spread @
Max. Height
CFM
40 48 32 5,460 2,165 98 1/2 1,075
Outlet
Velocity
(Fpm)
Final Air
Temp.
(°F)
200°F ENTERING
WATER
60°F ENTERING
AIR
20°F WATER
TEMPERATURE
DROP
Approx.
Hp
RPM
Table 10.2 - Performance Data for Standard Units at Standard Conditions of 200°F Entering Water and 60°F Entering Air Reduced Motor Speeds
Water Data Air Data Motor Data
Type Model No. Btu/hr
GPM
Pressure Drop (Ft. of Water)
Maximum Mounting
Height (ft.)
HSB/HC 18 9,900 1.3 0.5 9 11 220 400 101 1/60 1,000 HSB/HC 24 12,400 1.7 0.8 10 12 230 425 109 1/25 1,000
Horizontal
Delivery
HSB/HC 33 16,700 2.3 0.2 11 14 395 430 98 1/25 1,000 HSB/HC 47 23,600 3.2 0.4 13 18 450 490 107 1/12 1,000 HSB/HC 63 34,600 4.7 0.6 15 18 685 420 106 1/12 1,000 HSB/HC 86 45,900 6.3 1.0 16 20 825 515 11 0 1/8 1,000
HSB/HC 108 64,300 8.7 2.8 18 20 1,255 490 106 1/8 1,000
Horizontal units with horizontal louvers open 30° from vertical plane. Vertical types equipped with cone jet deflector, blades fully opened are shown in bold.
Non-bolded mounting height/spread data is for units without deflectors.
CFM for horizontal types is entering CFM. CFM for vertical and "Power-Throw" types is leaving CFM.
V and PT models have copper tubes, VN and PTN models have 90/10 cupro-nickel tubes. Requires Solid State Motor Speed Controller.
10
Heat Throw
or Spread @
Max. Height
1-550.29
CFM
Outlet
Velocity
(Fpm)
Final Air
Temp.
(°F)
Hp
Approx.
RPM
HOT WATER PERFORMANCE DATA - LOW OUTLET TEMPERATURE MODELS
200°F ENTERING
WATER
60°F ENTERING
AIR
20°F WATER
TEMPERATURE
DROP
Table 11.1 - Performance Data for Low Outlet Temperature Units at Standard Conditions of 200°F Entering Water and 60°F Entering Air – High Motor Speed
Water Data Air Data Motor Data
Type Model No. Btu/hr
GPM
Pressure
Drop
(Ft. of
Min/Max
GPM
Water)
HSB/HC 18L 11,300 1.2 0.4 0.3 / 5.0 10 21 364 650 88 1/60 1,550 HSB/HC 24L 13,700 1.4 0.6 0.3 / 5.0 12 22 435 775 88 1/25 1,550 HSB/HC 33L 19,300 2.0 0.2 0.4 / 10.0 13 26 695 730 85 1/25 1,550 HSB/HC 47L 21,100 2.2 0.2 0.4 / 10.0 15 34 855 890 82 1/12 1,550 HSB/HC 63L 37,900 4.0 0.4 0.5 / 20.0 17 35 1,170 695 89 1/12 1,550
Horizontal
Delivery
HSB/HC 86L 44,600 4.6 0.6 0.5 / 20.0 18 38 1,510 890 87 1/8 1,625 HSB/HC 108L 66,100 6.9 1.8 0.8 / 30.0 20 38 2,150 815 88 1/8 1,625 HSB/HC 121L 66,700 6.9 1.9 0.8 / 30.0 19 31 2,070 785 89 1/5 1,075 HSB/HC 165L 113,200 11.8 6.6 2.0 / 30.0 23 48 3,480 920 89 1/3 1,075 HSB/HC 258L 147,400 15.4 3.2 2.5 / 70.0 23 54 4,655 735 89 1/2 1,075 HSB/HC 290L 161,100 16.8 3.7 2.5 / 70.0 25 57 5,040 800 89 1/2 1,075 HSB/HC 340L 200,900 20.9 6.6 2.5 / 70.0 25 57 5,575 760 93 1/2 1,075
Power-
Throw™PT/PTN 610L 344,900 35.9 0.6 6.0 / 100.0 24 158 12,400 2,445 86 1-1/2 1,140
Maximum Mounting
Height (ft.)
Heat Throw
or Spread @
Max. Height
CFM
Outlet
Velocity
(Fpm)
Final Air
Temp.
(°F)
Hp
Approx.
RPM
V 42L 23,000 2.4 0.4 0.5 / 10.0 14 18 21 14 960 835 83 1/30 1,050 V 59L 32,600 3.4 0.3 0.8 / 15.0 17 23 25 17 1,190 1,035 86 1/30 1,050 V 78L 43,600 4.5 0.3 1.0 / 20.0 20 28 31 21 1,740 1,170 84 1/15 1,050
V 95L 53,100 5.5 0.3 1.3 / 25.0 20 28 31 21 1,760 1,180 89 1/15 1,050 V/VN 139L 81,200 8.5 1.6 1.0 / 30.0 24 33 37 25 2,860 1,380 87 1/6 1,075 V/VN 161L 93,900 9.8 1.3 1.3 / 40.0 28 37 41 28 3,400 1,640 86 1/3 1,075
Vertical
Delivery
V/VN 193L 112,500 11.7 1.3 1.5 / 50.0 29 38 43 29 3,710 1,790 89 1/3 1,075 V/VN 212L 123,400 12.9 0.9 2.0 / 60.0 29 38 43 29 3,830 1,845 91 1/3 1,075 V/VN 247L 143,600 15.0 1.2 2.0 / 60.0 34 45 51 35 5,110 2,030 87 1/2 1,075 V/VN 279L 162,200 16.9 1.2 2.3 / 75.0 38 48 57 39 5,790 2,300 87 1/2 1,075 V/VN 333L 198,300 20.7 2.3 2.3 / 75.0 38 48 57 39 6,340 2,300 90 3/4 1,140 V/VN 385L 229,100 23.9 3.0 2.3 / 75.0 38 46 57 49 8,140 1,970 87 1 1,140 V/VN 500L 295,000 30.7 2.8 3.0 / 100.0 48 57 72 49 11,000 2,670 85 1-1/2 1,140 V/VN 610L 344,900 35.9 0.6 6.0 / 100.0 47 55 70 48 12,400 2,445 86 1-1/2 1,140
V 952L 546,700 56.9 0.7 14.0 / 100.0 48 - 72
- 12,800 2,440 102 2 1,140
Table 11.2 - Performance Data for Low Outlet Temperature Units at Standard Conditions of 200°F Entering Water and 60°F Entering Air – Reduced Motor Speeds
Water Data Air Data Motor Data
Type Model No. Btu/hr
GPM
Pressure
Drop
(Ft. of
Water)
HSB/HC 18L 8,700 1.2 0.4 10 13 230 410 94 1/60 1,000 HSB/HC 24L 10,400 1.4 0.6 12 14 265 475 95 1/25 1,000
Horizontal
Delivery
HSB/HC 33L 14,700 2.0 0.2 13 16 430 455 91 1/25 1,000 HSB/HC 47L 16,300 2.2 0.2 15 21 540 570 87 1/12 1,000 HSB/HC 63L 29,000 4.0 0.4 17 21 725 435 96 1/12 1,000 HSB/HC 86L 33,900 4.6 0.6 18 23 925 550 93 1/8 1,000
HSB/HC 108L 50,500 6.9 1.8 20 23 1,330 510 94 1/8 1,000
Horizontal units with horizontal louvers open 30° from vertical plane. Vertical types equipped with cone jet deflector, blades fully opened are shown in bold.
Non-bolded mounting height/spread data is for units without deflectors.
CFM for horizontal types is entering CFM. CFM for vertical and "Power-Throw" types is leaving CFM.
V and PT models have copper tubes, VN and PTN models have 90/10 cupro-nickel tubes. Requires Solid State Motor Speed Controller.
Maximum Mounting
Height (ft.)
Heat Throw
or Spread @
Max. Height
CFM
Outlet
Velocity
(Fpm)
Final Air
Temp.
(°F)
Hp
Approx.
RPM
1-550.29
11
DIMENSIONAL DATA
SIZES 108-193, 1/2"-13 TAP
SIZES 108-165, 1/2"-13 TAP
F
G
H
5"
Min.
D
C
B E
A
Wall
Pipe Connections
Mounting Holes
Mounting Holes 1/2" - 13 Tap
F
G
5" Min.
D
C
B E
A
Wall
Mounting Holes 1/2" - 13 Tap
Mounting Holes
Pipe Connections
Horizontal Air Delivery Models — Two Styles
Figure 12.1 - Model Dimensions HSB 18-193
MOUNTING HOLES
SIZES 33-86, 3/8"-16 TAP
B
E
A
G (MOUNTING HOLES)
F (PIPE CONNECTIONS)
C
Figure 12.3 - Model Dimensions HC 18-165
MOUNTING HOLES
SIZES 33-86, 3/8"-16 TAP
B
E
A
G (MOUNTING HOLES)
H (PIPE CONNECTION)
Figure 12.2 - Model Dimensions HSB 258-340
5"
D
MIN
Figure 12.4 - Model Dimensions HC 193-340
C
MIN
5"
D
Vertical deflector blades shown are standard on models HC 258-340
Table 12.1 - Model HSB and HC Dimensions ➀ ➁
and optional on model HC 193.
D Female Approx. Model 115 Std. 115V Exp. Connections Fan Shipping
Number A B C Motor Motor E F G H NPT Diameter Wt. lb. HSB 18 12-3/8 13 6 5 12 - 3 - - 3/4 9 16 HSB 24 12-3/8 13 6 6-1/2 12 - 3 - - 3/4 9 20 HSB 33 16-3/8 17-1/2 8-3/4 6-1/2 12-1/4 11 3-5/8 6 - 1-1/4 12 34 HSB 47 16-3/8 17-1/2 8-3/4 8 12-1/4 11 3-5/8 6 - 1-1/4 12 36 HSB 63 20-7/16 21-1/2 8-3/4 8 12-3/4 15 3-5/8 6 - 1-1/4 14 48 HSB 86 20-7/16 21-1/2 8-3/4 9 12-3/4 15 3-5/8 6 - 1-1/4 14 52 HSB 108 24-7/16 25-1/2 9-1/2 8 11-1/2 18 3-3/4 6-3/8 - 1-1/4 18 74 HSB 121 24-7/16 25-1/2 9-1/2 7-1/2 11 18 3-3/4 6-3/8 - 1-1/4 18 76 HSB 165 30-1/2 30-1/2 9-1/4 9-1/2 14 21-1/4 3-3/4 6-3/8 - 1-1/4 22 92 HSB 193 30-1/2 30-1/2 9-1/4 9-1/2 14 21-1/4 3-3/4 6-3/8 - 1-1/4 22 98 HSB 258 38-1/2 38-1/2 12-1/2 10-1/2 14 18-1/2 3-5/8 7-7/8 - 1-1/4 22 162 HSB 290 38-1/2 38-1/2 12-1/2 10-1/2 14 18-1/2 3-5/8 7-7/8 - 1-1/4 24 168 HSB 340 38-1/2 44-1/2 12-1/2 10-1/2 14 18-1/2 3-5/8 7-7/8 - 1-1/4 24 176 HC 18 11-1/2 12-3/4 6 5 12 5-5/8 2-1/4 4-1/8 7-1/2 1/2 9 16 HC 24 11-1/2 12-3/4 6 6-1/2 12 5-5/8 2-1/4 4-1/8 7-1/2 1/2 9 20 HC 33 15 17-1/2 8-3/4 6-1/2 12-1/4 11 3-5/8 6 10 3/4 12 34 HC 47 15 17-1/2 8-3/4 8 12-1/4 11 3-5/8 6 10 3/4 12 35 HC 63 18-1/2 21-1/2 8-3/4 8 12-3/4 15 3-5/8 6 14 3/4 12 48 HC 86 18-1/2 21-1/2 8-3/4 9 12-3/4 15 3-5/8 6 14 3/4 14 52 HC 108 22-1/2 25-1/2 9-1/2 8 11-1/2 18 3-5/8 6-3/8 18 3/4 18 74 HC 121 22-1/2 25-1/2 9-1/2 7-1/2 11 18 3-5/8 6-3/8 18 3/4 18 76 HC 165 26-1/2 29-1/2 9-1/4 9-1/2 14 21-1/4 3-5/8 6-3/8 22 3/4 22 92 HC 193 30-1/2 32-1/2 9-1/4 9-1/2 14 21-1/4 3-5/8 4-3/4 26 1-1/4 22 98 HC 258 38-1/2 38-1/2 12-1/2 10-1/2 14 18-1/2 3-5/8 8 34 1-1/4 22 163 HC 290 38-1/2 38-1/2 12-1/2 10-1/2 14 18-1/2 3-5/8 8 34 1-1/4 24 168 HC 340 38-1/2 44-1/2 12-1/2 10-1/2 14 18-1/2 3-5/8 8 34 1-1/4 24 176
All dimensions in inches.
Dimensions shown are for Standard and Low Outlet Temperature Models.
12
1-550.29
DIMENSIONAL DATA
Figure 13.1 - Model Dimensions V/VN and PT/PTN
Vertical Air Delivery
“Power-Throw” Air Delivery
Air Deflectors (Optional)
Table 13.1 - Model V/VN and PT/PTN Dimensions ➀ ➁ ➂
Male Connections Approx. Model Fan NPT Shipping
Number A B C D E F G Diameter Top Bottom Wt. (lb.) V/VN 42 24-3/4 3-5/8 11-3/8 2-1/8 4-3/8 14-1/2 - 14 1-1/4 1-1/4 36 V/VN 59 24-3/4 5-1/8 11-3/8 2-1/8 4-3/8 14-1/2 - 14 1-1/4 1-1/4 42 V/VN 78 24-3/4 6-5/8 11-3/8 2-1/8 2-5/8 16-1/2 - 16 1-1/4 1-1/4 46 V/VN 95 24-3/4 8-1/8 11-3/8 2-1/8 2-5/8 16-1/2 - 16 1-1/4 1-1/4 48 V/VN 139 34-3/4 6-7/8 18-3/8 2-1/8 3 19-1/2 - 19 1-1/2 1 70 V/VN 161 34-3/4 8-3/8 18-3/8 2-1/8 3 19-1/2 - 19 1-1/2 1 80 V/VN 193 34-3/4 9-7/8 18-3/8 2-1/8 3 19-1/2 - 19 1-1/2 1 86 V/VN 212 34-3/4 12-7/8 18-3/8 2-1/2 3 19-1/2 - 19 2 1-1/4 94 V/VN 247 34-3/4 12-7/8 18-3/8 2-1/2 3 21-1/2 - 21 2 1-1/4 108 V/VN 279 34-3/4 14-3/8 18-3/8 2-1/2 3 21-1/2 - 21 2 1-1/4 112 V/VN 333 43-1/4 14-5/8 31-1/2 2-7/8 3-1/8 22-1/2 18-1/5 22 2-1/2 1-1/2 166 V/VN 385 43-1/4 14-1/2 31-1/2 2-7/8 3-1/2 27-1/2 18-1/5 27 2-1/2 1-1/2 168 V/VN 500 43-1/4 19 31-1/2 2-7/8 3-1/2 27-1/2 18-1/5 27 2-1/2 1-1/2 360 V/VN 610 51-1/2 19-1/8 31-3/8 - 3-3/4 30-1/2 31-3/8 30 2-1/2 1-1/2 450 V 952 53-3/4 21-1/8 30 - 3-1/2 31 30 30 3 3 487 PT/PTN 279 34-3/4 22-5/8 25-1/4 16-3/4 16-3/4 - - 21 2 1-1/4 122 PT/PTN 333 43-1/4 23-7/8 30 15-3/4 14-3/8 - - 22 2-1/2 1-1/2 176 PT/PTN 385 43-1/4 25-3/4 30 15-3/4 14-3/8 - - 27 2-1/2 1-1/2 184 PT/PTN 500 43-1/4 29 30 20-1/4 14-3/8 - - 27 2-1/2 1-1/2 376 PT/PTN 610 51-1/2 29-5/8 30 20-3/8 21 - - 30 2-1/2 1-1/2 472 PT 952 53-3/4 26-3/8 30 23-1/8 26-7/8 - - 30 3 3 487
All dimensions in inches.Dimensions shown are for Standard and Low Outlet Temperature Models.See Table 13.2 for optional air outlet accessory dimensions.
Table 13.2 - Vertical Air Outlet Accessories Dimensions
Model Cone-Jet Truncone Louvers
Number L T M X P Z V 42, V 59 6-1/2 18-7/8 12 22 6-1/2 16-7/8 V 78, V 95 6-1/2 18-7/8 12 22 6-1/2 16-7/8 V 139, V 212 7-1/2 24-3/4 13 27 7-1/2 19-3/4 V 247, V 279 8 26-7/8 16 34 8 22-3/4 V 333 8-1/2 28 16 34 8-1/2 22-3/4 V 385, V 500 10 22-3/4 21 41 10 27-3/4 V 610 10-1/2 36-3/4 21 41 10-1/2 30-3/4 V 952 - - - - 19-1/2 32
All dimensions in inches.
1-550.29
13
MOTOR DATA / SERVICE
Table 14.1 - Motor Amp Draw Data ➀ ➁
Amp Draw by Motor Type, Voltage and Power Code
Totally Enclosed
115/60/1 208/60/1 230/60/1 208/60/3 230/460/3 575/60/3 115/60/1 230/460/60/3 Model Number Motor HP 01 N/A 02 04 05 10 06 09 HSB/HC 18 1/60 0.8 ➃ 0.44 ➃ ➃ 4.3 - HSB/HC 24, 33 1/25 1.6 ➃ 1.0 ➃ ➃ 4.3 - HSB/HC 47, 63 1/12 3.0 ➃ 1.0 ➃ 1.4/0.7 ➃ 4.3 - HSB/HC 86, 108 1/8 2.3 ➃ 1.0 ➃ 1.4/0.7 ➃ 4.3 - HSB/HC 121 1/5 2.8 ➃ 1.5 1.9 ➄ 2.1/1.05 ➃ 4.0 1.4/0.7 HSB/HC 165, 193 1/3 5.4 ➃ 2.5 1.9 ➄ 2.1/1.05 ➃ 6.5 1.4/0.7 HSB/HC 258-340 1/2 6.7 ➃ 3.5 2.6 ➄ 3.0/1.5 ➃ 9.0 2.0/1.0 V/VN 42, 59 1/30 2.1 ➃ 0.6 1.9 ➄ 2.1/1.05 ➃ 4.0 - V/VN 78, 95 1/15 2.5 ➃ 1.3 1.9 ➄ 2.1/1.05 ➃ 4.0 - V/VN 139 1/5 2.8 ➃ 1.5 1.9 ➄ 2.1/1.05 ➃ 4.0 1.4/0.7 V/VN 161-212 1/3 5.4 ➃ 2.5 1.9 ➄ 2.1/1.05 ➃ 6.5 1.4/0.7 V/VN 247 1/2 6.7 ➃ 3.5 2.6 ➄ 3.0/1.5 ➃ 9.0 2.0/1.0 V/VN, PT/PTN 279 1/2 6.7 ➃ 3.5 2.6 ➄ 3.0/1.5 ➃ 9.0 2.0/1.0 V/VN, PT/PTN 333 3/4 8.8 ➃ 4.4 3.7 ➄ 3.4/1.7 ➃ - - V/VN, PT/PTN 385 1 - - - 4.2 4.0/2.0 1.5 - 3.5/1.75 V/VN, PT/PTN 500, 610 1-1/2 - - - 7.4 6.6/3.3 2.0 - 5.8/2.9 V, PT 952 2 - - - 7.4 6.8/3.4 - - 6.2/3.1
Ratings shown are for Standard and Low Outlet Temperature Models.All motors include thermal overload protection except for units with power code 04, 05, or 10.All HSB/HC units, V/VN 42 thru V/VN, PT/PTN 333 motor HP listed for power code 01. V/VN, PT/PTN 333 thru V/VN, PT/PTN 610 motor HP listed for power code 04
and V/PT 952 motor HP listed for power code 05.
For supply voltages of 208V/60Hz/1ph and all non-explosion proof 3 phase voltages of 208, 230, 460 and 575, Model Numbers indicated with Note , require that a
115V/60Hz/1 phase power code 01 unit heater be used with a shipped loose accessory transformer. See literature #1-556 for Transformer Sizes. See Note .
Model numbers indicated with Note , can be ordered with a power code (208V/3ph=04, 230/460V/3ph=05) that provides a motor matched to the supply voltage with
amp draw as shown. Alternately, a 115V/60Hz/1 phase power code 01 unit heater could be used with a shipped loose accessory transformer. See literature #1-556 for Transformer Sizes.
Explosion Proof
SERVICE
wARNINg
When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine Manufacturing Company. Refer to the rating plate on the unit for complete unit substitution of parts or controls not approved
by the factory will be at the owner’s risk.
CAuTION
1. Service or repair of this equipment must be performed by a qualified service agency.
2. Do not reuse any electrical component which has been wet. Replace component.
IMPORTANT
To check most of the Possible Remedies in the troubleshooting guide listed in Table 15.1, refer to the applicable sections of the manual.
Heating equipment should be serviced before each heating season to assure proper operations. The following items may be required more frequently based on the environment in which the unit is installed and frequency of equipment operation.
All installation and service of these units must be performed by a qualified installation and service agency.
Before any service, BE SURE TO TURN OFF THE STEAM OR WATER SUPPLY AT THE MANUAL SHUT-OFF VALVES AND TURN OFF ALL ELECTRIC POWER TO THE HEATER.
14
1-550.29
Motors
1. Remove grease and dirt on motor during each inspection or lubrication. Open frame motors should be blown clean every heating season, or whenever coils are cleaned, whichever is sooner.
2. Lubricate motor according to manufacturer’s instructions
located on the motor. When no motor oiling instructions are on the motor, oil the motor every two thousand hours of operation with SAE20 motor oil for units in normal applications. Adjust oiling according to usage and atmosphere.
3. Some motors do not have oil fittings. These motors are lubricated for long life and do not require further lubrication.
4. A change in line voltage higher or lower than motor nameplate rating may cause overheating and serious motor damage. Check plant voltage conditions. A separate manual starter with thermal overload protection device is recommended for those units that do not have motors with built-in overload protection.
Coils
1. Clean coil at least once a year; more often under unfavorable conditions. Unless coil is kept reasonably free of dirt, lint and grease, its original heating capacity will be reduced — possibly to a serious degree, and motor damage may result.
Two commonly used cleaning methods are:
• Loosen dirt by brushing fins on side where air enters coil
and then turn on fan to blow dirt from unit.
• Use high pressure air hose to loosen dirt by blowing from
side where air leaves coil (side adjacent to louvers on blow­through units; side adjacent to fan on draw-through units).
SERVICE / TROUBLESHOOTING
2. For thorough cleaning of coil, remove motor and fan and spray a mild alkaline cleaning solution over the coil. After a few minutes, follow by a hot water rinse. (A steam gun can be used for spraying cleaning solution and hot water.)
3. Coils subjected to corrosive fumes should be checked and cleaned frequently.
4. Provide controlled water treatment — don’t use excess of
boiler compounds. Contact your boiler compound supplier for proper usage or the services of a water treatment laboratory.
5. Periodic internal flushing of the coils is recommended in areas where water supply is suspected of causing scale. Use an alkaline-chelant solution and introduce it at the main pump of the hydronic system. Flush thoroughly.
WARNING: USING INORGANIC OR MINERAL ACIDS SUCH AS MURIATIC (HYDROCHLORIC) ACID, EVEN THOUGH INHIBITED, MAY LEAD TO SEVERE DAMAGE, INCLUDING CORROSION AND LEAKAGE.
6. De-aerate boiler feed-water (particularly if large amount of new water is used).
7. Ensure rapid continuous and adequate condensate drainage by properly sized and installed traps and piping. Check traps for sticking. Clean strainers ahead of traps. (When traps
don’t work, condensate accumulates in unit heater coil; water
hammer results.)
8. Adequately vent each unit.
9. Use low pressure steam when possible.
Casings
1. Periodic cleaning of casings is recommended to remove
dirt, grease and corrosive substances that may injure finish. Rusted or corroded spots should be cleaned and repainted.
2. Tighten fan guard and motor bracket. Check fan for proper
clearance, free rotation and firm connection to shaft.
When servicing is complete, tag unit to indicate date of
inspection, lubrication and cleaning.
Replacement Parts
When requesting parts please contact your local representative. Please have full model and serial number available. See Figure 15.1.
Figure 15.1 - Model Identification Plate
Table 15.1 - Troubleshooting
Fails to Maintain Temperature
1. Undersized unit heater, boiler, pump or piping.
2. Unit heater operating at low speed when sized for high speed.
3. Unit heater mounted too high — heated air not delivered to floor.
4. Thermostat — improper location or setting, or not functioning.
5. Dirty or clogged coil.
Unit Blows Cold Air
1. Manual shut-off valve closed.
2. Insufficient steam pressure of lack of hot water.
3. Aquastat not functioning.
4. Improper venting.
5. Steam trap not functioning.
6. Drip leg too short (steam system).
7. Return line plugged (steam system).
8. Pump undersized or not operating (hot water system).
Does Not Operate When Heat Needed
1. Defective motor or electrical connections.
2. Thermostat, aquastat or pressure limit control not functioning.
Fails to Deliver Heat to Floor
1. Units mounted too high.
2. Operating on low speed.
3. Final air temperature too high.
4. Louvers not adjusted properly.
5. Wrong type of diffuser (on verticals).
6. Undersized unit heater (insufficient air delivery).
7. Wrong type of unit (may require vertical delivery).
8. Cross ventilation or drafts.
9. Obstructions to air flow.
Noisy Unit
1. Loose bolts or screws.
2. Fan blade bent, out of balance.
3. Dirt accumulation on fan blades.
4. Fan hub or blade rivets loose.
5. Motor shaft bearing worn.
6. Motor mounting bent, fan not positioned properly in venturi.
7. Conduit too rigid, transmits vibration noise.
8. BX cable touching unit heater, chatters as casing vibrates.
Employees Complain of Hot Blast
1. Air stream aimed directly at employees.
2. Louvers not adjusted properly.
3. Wrong type of diffuser (on verticals).
4. Excessive final air temperature.
Unit Operates Too Long
1. Thermostat installed on cold wall or other improper location.
2. Aquastat or pressure limit control not functioning properly.
3. Unit is undersized.
Frequent Motor Failure
1. Voltage fluctuations too high or too low.
2. Excessive or insufficient lubrication.
3. Wiring to motor undersized.
4. Improper electrical connections.
5. Motor operating in too high air temperature.
6. Restricted air flow due to clogged coil or closed louvers.
7. Fan out of balance.
8. Unbalanced voltage on 3φ power.
Coil Failure/Unit Leaks
1. Severe internal corrosion from feedwater.
2. Type of boiler treatment.
3. Entrained air causing water hammer.
4. Continuous operation above 150 PSI (375°F)(steam systems).
5. Loose connection.
1-550.29
15
COMMERCIAL WARRANTY
Seller warrants its products to be free from defects in material and workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use of materials substituted under emergency conditions for materials normally employed. This warranty covers replacement of any parts furnished from the factory of Seller, but does not cover labor of any kind and materials not furnished by Seller, or any charges for any such labor or materials, whether such labor, materials or charges thereon are due to replacement of parts, adjustments, repairs, or any other work done. This warranty does not apply to any equipment which shall have been repaired or altered outside the factory of Seller in any way so as, in the judgment of Seller, to affect its stability, nor which has been subjected to misuse, negligence, or operating conditions in excess of those for which such equipment was designed. This warranty does not cover the effects of physical or chemical properties of water or steam or other liquids or gases used in the equipment.
BUYER AGREES THAT SELLER’S WARRANTY OF ITS PRODUCTS TO BE
FREE FROM DEFECT IN MATERIAL AND WORKMANSHIP, AS LIMITED HEREIN, SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER WARRANTIES, EITHER EXPRESS OR IMPLIED, WHETHER ARISING FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE,
THERE ARE NO OTHER WARRANTIES, INCLUDING WARRANTY OF MERCHANTABILITY OR FITNESS FOR PURPOSE, WHICH EXTEND BEYOND THE PRODUCT DESCRIPTION CONFIRMED BY BUYER AND SELLER AS OF THE DATE OF FINAL AGREEMENT.
This warranty is void if the input to the product exceeds the rated input as indicated on the product serial plate by more than 5% on gas-fired and oil-fired units, or if the product in the judgment of SELLER has been installed in a corrosive atmosphere, or subjected to corrosive fluids or gases, been subjected to misuse, negligence, accident, excessive thermal shock, excessive humidity, physical damage, impact, abrasion, unauthorized alterations, or operation
contrary to SELLER’S printed instructions, or if the serial number has been
altered, defaced or removed.
BUYER AGREES THAT IN NO EVENT WILL SELLER BE LIABLE FOR COSTS OF PROCESSING, LOST PROFITS, INJURY TO GOODWILL, OR ANY OTHER CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY KIND RESULTING FROM THE ORDER OR USE OF ITS PRODUCT, WHETHER ARISING FROM BREACH OF WARRANTY, NONCONFORMITY TO ORDERED SPECIFICATIONS, DELAY IN DELIVERY, OR ANY LOSS SUSTAINED BY THE BUYER.
BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL
OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR REPLACEMENT AT THE FACTORY OF SELLER, ANY COMPONENT WHICH SHALL, WITHIN THE APPLICABLE WARRANTY PERIOD DEFINED HEREIN AND UPON PRIOR WRITTEN APPROVAL, BE RETURNED TO SELLER WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE; EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER,
BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE
LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. FOR GAS-FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS
AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS, BUYER’S
REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO TEN YEARS FROM DATE OF SHIPMENT FROM SELLER.
These warranties are issued only to the original owner-user and cannot be transferred or assigned. No provision is made in these warranties for any labor allowance or field labor participation. Seller will not honor any expenses
incurred in its behalf with regard to repairs to any of Seller’s products. No
credit shall be issued for any defective part returned without proper written authorization (including, but not limited to, model number, serial number, date of failure, etc.) and freight prepaid.
OPTIONAL SUPPLEMENTAL WARRANTY Provided a supplemental warranty has been purchased, Seller extends the
warranty herein for an additional four (4) years on certain compressors. Provided a supplemental warranty has been purchased, Seller extends the warranty herein for an additional four (4) years or nine (9) years on certain heat exchangers.
EXCLUSION OF CONSUMABLES & CONDITIONS BEYOND SELLER’S
CONTROL This warranty shall not be applicable to any of the following items: refrigerant
gas, belts, filters, fuses and other items consumed or worn out by normal wear and tear or conditions beyond Seller’s control, including (without limitation as to generality) polluted or contaminated or foreign matter contained in the air or water utilized for heat exchanger (condenser) cooling or if the failure of the part is caused by improper air or water supply, or improper or incorrect sizing of power supply.
Component
Applicable Models
Heat Exchangers
Gas-Fired Units
Heat Exchangers
Low Intensity Infrared Units
Compressors
Condensing Units for Cassettes
Burners
Low Intensity Infrared Units
Other
Components excluding Heat Exchangers, Coils, Condensers, Burners, Sheet Metal
Heat Exchangers/Coils
Indoor and Outdoor Duct Furnaces and System Units, Steam/Hot Water Units, Oil-Fired Units, Electric Units, Cassettes, Vertical Unit Ventilators, Geothermal Units
Compressors
Vertical Unit Ventilators, Geothermal Units
Burners
High Intensity Infrared Units
Sheet Metal Parts
All Products
TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE HUNDRED TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN SIXTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN EIGHTEEN MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
“APPLICABLE WARRANTY PERIOD”
As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.
© Modine Manufacturing Company 2015
Modine Manufacturing Company
1500 DeKoven Avenue Racine, WI 53403 Phone: 1.800.828.4328 (HEAT) www.modinehvac.com
Loading...