IMPORTANT NOTE: The information contained in this document supersedes all previously published
information regarding this product. Product specifications are subject to change without prior notice.
®
Installation and Operation Manual
Note: This manual incorporates data for the CDM-Qx and CDM-QxL.
Part Number MN/CDMQX.IOM Revision 5
Errata A
Comtech EF Data Documentation Update
Subject:
Date:
Document:
Part Number:
Collating Instructions:
Comments:
The following changes affects the acquisition rate specified in Section A.2.
Change Specifics:
Revised Acquisition Range for Demodulator
January 23, 2007
CDM-Qx, Multi-Channel Satellite Modem, Installation and
Operation Manual, Revision 5, dated January 20, 2007
MN/CDMQx.EA5
Attach this page to page A-3
Acquisition range
±1 to ±32 kHz, Symbol rate > 64 ksps (70/140 MHz)
±1 to ± (Symbol rate/2) kHz , Symbol Rate <=64 ksps (70/140 MHz)
±1 to ±200 kHz, Symbol rate > 625 ksps (L-Band)
±1 to ± 32 kHz, 64 ksps < Symobol Rate <=625 ksps (L-Band)
±1 to ± (Symbol rate/2)kHz, Synbol Rate <=64ksps (L-Band)
January 23, 2007
CDM-Qx, Multi-Channel Satellite Modem, Installation and
Operation Manual, Revision 5, dated January 20, 2007
MN/CDMQx.EB5
Attach this page to page 5-22
Revised Sub-Menu for Vit+RS and TCM+RS to delete Viterbi and TPC.
Revise Sub-Menu for Vit+RS and TCM+RS
January 23, 2007
CDM-Qx, Multi-Channel Satellite Modem, Installation and
Operation Manual, Revision 5, dated January 20, 2007
MN/CDMQx.EC5
Attach this page to page 5-25
If Vit+RS orTCM+RS is selected, the following sub-menu will be displayed:
January 23, 2007
CDM-Qx, Multi-Channel Satellite Modem, Installation and
Operation Manual, Revision 5, dated January 20, 2007
MN/CDMQx.ED5
Attach this page to page 5-16
If Vit+RS orTCM+RS is selected, the following sub-menu will be displayed:
5.3 Right-Hand Display Area .........................................................................................................................5–6
5.4 Accessing the Display Area.......................................................................................................................5–6
This manual provides installation and operation information for the Comtech EF Data
CDM-Qx Multi-Channel Modem with DoubleTalk™ Carrier-in-Carrier®. This is a
technical document intended for earth station engineers, technicians, and operators
responsible for the operation and maintenance of the CDM-Qx.
CONVENTIONS AND REFERENCES
METRIC CONVERSION
Metric conversion information is located on the inside back cover of this manual. This
information is provided to assist the operator in cross-referencing English to Metric
conversions.
CAUTIONS AND WARNINGS
CAUTION indicates a hazardous situation that, if not avoided, may
result in minor or moderate injury. CAUTION may also be used to
CAUTION
indicate other unsafe practices or risks of property damage.
WARNING indicates a potentially hazardous situation
WARN ING
that, if not avoided, could result in death or serious
injury.
Indicates information critical for proper equipment
IMPORTANT
function.
REPORTING COMMENTS OR SUGGESTIONS CONCERNING THIS MANUAL
Comments and suggestions regarding the content and design of this manual will be
appreciated. To submit comments, please contact the Comtech EF Data Technical
Publications Department: techpub@comtechefdata.com
The CDM-Qx Multi-Channel Modem with DoubleTalk™ Carrier-in-Carrier® has been
shown to comply with the following safety standard:
• EN 60950: Safety of Information Technology Equipment, including electrical
business machines
The equipment is rated for operation over the range 100 to 240 VAC. It has a maximum
power consumption of 60 watts, and draws a maximum of 600 mA.
IMPORTANT
FUSES
The CDM-Qx is fitted with two fuses - one each for line and neutral connections. These
are contained within the body of the IEC power inlet connector, behind a small plastic
flap.
• For 115 and 230 VAC operation, use T1.25A, 20mm fuses.
FOR CONTINUED OPERATOR SAFETY, ALWAYS REPLACE THE FUSES WITH
THE CORRECT TYPE AND RATING.
ENVIRONMENTAL
The CDM-Qx must not be operated in an environment where the unit is exposed to
extremes of temperature outside the ambient range 0 to 50°C (32° to 122°F),
precipitation, condensation, or humid atmospheres above 95% RH, altitudes (unpressurized) greater than 2000 meters, excessive dust or vibration, flammable gases,
corrosive or explosive atmospheres.
Operation in vehicles or other transportable installations that are equipped to provide a
stable environment is permitted. If such vehicles do not provide a stable environment,
safety of the equipment to EN60950 may not be guaranteed.
The user should observe the following instructions:
The installation and connection to the line supply must be made in compliance to local or
national wiring codes and regulations.
The CDM-Qx is designed for connection to a power system that has separate ground, line
and neutral conductors. The equipment is not designed for connection to power system
that has no direct connection to ground.
The CDM-Qx is shipped with a line inlet cable suitable for use in the country of
operation. If it is necessary to replace this cable, ensure the replacement has an equivalent
specification. Examples of acceptable ratings for the cable include HAR, BASEC and
HOXXX-X. Examples of acceptable connector ratings include VDE, NF-USE, UL, CSA,
OVE, CEBEC, NEMKO, DEMKO, BS1636A, BSI, SETI, IMQ, KEMA-KEUR and
SEV.
The modulator and demodulator cards shall not be plugged-in when the
modem is powered on. Damage to the cards can be the result.
In accordance with the Telecommunications Terminal Equipment Directive 91/263/EEC,
this equipment should not be directly connected to the Public Telecommunications
Network.
CE MARK
Comtech EF Data declares that the CDM-Qx meets the necessary requirements for the
CE Mark.
TRADEMARKS
Carrier-in Carrier is a registered trademark of Comtech EF Data Corporation.
DoubleTalk is a trademark of Applied Signal Technology, Inc.
This Comtech EF Data product is warranted against defects in material and workmanship
for a period of two years from the date of shipment. During the warranty period, Comtech
EF Data will, at its option, repair or replace products that prove to be defective.
For equipment under warranty, the customer is responsible for freight to Comtech EF
Data and all related custom, taxes, tariffs, insurance, etc. Comtech EF Data is responsible
for the freight charges only for return of the equipment from the factory to the customer.
Comtech EF Data will return the equipment by the same method (i.e., Air, Express,
Surface) as the equipment was sent to Comtech EF Data.
LIMITATIONS OF WARRANTY
The foregoing warranty shall not apply to defects resulting from improper installation or
maintenance, abuse, unauthorized modification, or operation outside of environmental
specifications for the product, or, for damages that occur due to improper repackaging of
equipment for return to Comtech EF Data.
No other warranty is expressed or implied. Comtech EF Data specifically disclaims the
implied warranties of merchantability and fitness for particular purpose.
EXCLUSIVE REMEDIES
The remedies provided herein are the buyer's sole and exclusive remedies. Comtech EF
Data shall not be liable for any direct, indirect, special, incidental, or consequential
damages, whether based on contract, tort, or any other legal theory.
DISCLAIMER
Comtech EF Data has reviewed this manual thoroughly in order that it will be an easy-touse guide to your equipment. All statements, technical information, and
recommendations in this manual and in any guides or related documents are believed
reliable, but the accuracy and completeness thereof are not guaranteed or warranted, and
they are not intended to be, nor should they be understood to be, representations or
warranties concerning the products described. Further, Comtech EF Data reserves the
right to make changes in the specifications of the products described in this manual at any
time without notice and without obligation to notify any person of such changes.
If you have any questions regarding the equipment or the information in this manual,
contact the Comtech EF Data Customer Support Department.
The CDM-Qx, Multi-Channel Satellite Modem with DoubleTalk™ Carrier-in-Carrier® is
a 70/140 MHz (or CDM-QxL with 950MHz-1950MHz L Band operation) modular multichannel modem with redundancy contained in a single rack unit (1RU) chassis. The
Modem offers flexibility, redundancy, integration, and performance with four slots
configurable as modulators or demodulators.
The CDM-Qx/QxL supports DoubleTalk Carrier-in-Carrier® option, allowing transmit
(Tx) and receive (Rx) carriers in a full-duplex link to use the same transponder segment.
Designed for bandwidth compression, Carrier-in-Carrier is based on Applied Signal
Technology’s DoubleTalk which uses “Adaptive Cancellation,” a patented (Unites States
Patent # 6,859,641) technology that allows full duplex satellite links to transmit
concurrently in the same segment of transponder bandwidth. Available as an option to
the modem, this added dimension can result in a significant improvement in satellite
transponder utilization.
1.2.2 Software – Flash Upgrading
The internal software is both powerful and flexible, permitting storage and retrieval of up
to 10 different modem configurations. The modem uses ‘flash memory’ technology
internally, and new firmware can be uploaded to the unit from an external PC. This
simplifies software upgrading, and updates can now be sent via the Internet, e-mail, or on
disk. The upgrade can be performed without opening the unit by simply connecting the
modem to the USB port or Ethernet port of a computer.
1.2.3 Verification
The Modem includes many test modes and loopbacks for rapid verification of the correct
functioning of the unit. Of particular interest is the IF loopback, which permits the user to
perform a quick diagnostic test without having to disturb external cabling. During
loopback, all of the receive configuration parameters on the selected Demodulator are
temporarily changed to match those of the selected Modulator, and an internal RF switch
connects the modulator output to the demodulator input. When normal operation is again
selected, all of the previous values are restored.
The Modem can be ordered with a number of interfaces. Each data interface can operate
on a Modulator or Demodulator. This allows the user to exchange interface cards for
different applications. The interfaces offered include:
• EIA/TIA-530
• (EIA-422) DCE (at rates up to 12 Mbps)
• V.35 DCE (at rates up to 12 Mbps)
• G.703 Balanced T1 & E1 (DB-15) with D&I
• G.703 Unbalanced T1 & E1 (BNC)
• EIA/TIA-612/613 HSSI (50-pin SCSI connector, to 20 Mbps)
• 1 to 4 Ports of G.703 (E1 with D&I ) Quad E1 Interface Card, (DB-9F)
1.2.5 Turbo Product Coding
The Modem offers optional 2nd generation Turbo Product Codec (TPC). TPC
simultaneously offers increased coding gain, lower decoding delay, and significant
bandwidth savings. The TPC provides:
• BPSK 5/16 and 21/44
• QPSK 21/44, 3/4, 7/8 and 17/18
• 8-PSK 3/4, 7/8, and 17/18
• 16-QAM 3/4 and 7/8
1.2.6 Remote Control
The operator may configure and monitor the modem from the front panel, or through the
remote M&C port. M&C is via RS-232, RS-485 (2/4 wire) or 10/100 BaseT Ethernet.
PL/10570-1 1 PPM Reference IF Backplane 70/140 MHz IF
PL/10570-2 0.1 PPM Reference IF Backplane 70/140 MHz IF
PL/10070-1 0.1 PPM Reference IF Backplane L-Band IF
PL/10069 Digital Backplane
PL/10073 Monitor and Control Card
PL/11128 70/140 MHz IF Modulator
PL/10635 70/140 MHz IF Demodulator with Carrier in Carrier
PL/10071 L-Band IF Modulator
PL/10072
AS/11014 Turbo Codec – Simplex
PL/10678 EIA-530 Duplex Data interface
PL/10697 G.703 Balanced Duplex Data Interface
PL/10698 G.703 Unbalanced Duplex Data Interface
PL/12608-1 Quad E1 G.703 Data Interface Module
PL/10898-1 EIA-612/613 HSSI Interface
PL/10416-1 AC Chassis, 70/140 IF
PL/10416-2 DC Chassis, 70/140 IF
PL/12798-1 AC Chassis, L-Band
PL/12798-2 DC Chassis, L-Band
The Modem is extremely flexible and powerful, and incorporates a large number of
optional features. Some customers may not require all of these features, and therefore, in
order to permit a lower initial cost, the Modem may be purchased with only the desired
modules and features enabled. If, at a later date, a customer wishes to upgrade the
functionality of a modulator or demodulator, Comtech EF Data provides a system known
as FAST (Fully Accessible System Topology) which permits the purchase and
installation of options through the use of special authorization codes, entered through the
front panel, or remotely.
The base configuration of the modulators and demodulators are equipped with Viterbi
and R-S codecs. It offers modulation types, and data rates up to 5 Mbps. It is, however,
limited to Closed Network operation.
The following table shows what other options are available:
Modulator & Demodulator
Options
Low Rate Variable Data rate 32 kbps to 5 Mbps Base Unit
Mid-Rate Variable Data rate 32 kbps to 10.0 Mbps FAST
Full Rate Variable Data rate 32 kbps to 20.0 Mbps FAST
8-PSK Modulation Type FAST
16-QAM Modulation Type FAST
DoubleTalk Carrier-in-Carrier 128 ksps – 512 kbps FAST
DoubleTalk Carrier-in-Carrier 128 ksps – 1 Mbps FAST
DoubleTalk Carrier-in-Carrier 128 ksps – 2.5 Mbps FAST
DoubleTalk Carrier-in-Carrier 128 ksps – 5 Mbps FAST
DoubleTalk Carrier-in-Carrier 128 ksps – 1.0 Mbps FAST
DoubleTalk Carrier-in-Carrier 128 ksps – 20 Mbps FAST
Redundancy Capability 1:1 or 1:2 or 1:3 Redundancy FAST
Turbo Codec – high rate 20 Mbps Turbo Codec Hardware
High Stability Reference Internal 10 MHz reference – 0.1 x 10-6 Hardware*
Low Stability Reference Internal 10 MHz reference – 1 x 10-6 Hardware*
75Ω TX/RX Impedance 75Ω impedance with BNC female connectors
50Ω TX/RX Impedance 50Ω impedance with N female connectors (L-
Comtech EF Data’s FAST system allows immediate implementation of different options
through the user interface keypad. All FAST options are available through the basic
platform unit.
1.4.2 FAST System Theory
FAST is an enhancement feature available in Comtech EF Data products, enabling onlocation upgrade of the operating feature set - in the rack - without removing a modem
from the setup. When service requirements change, the operator can upgrade the topology
of the modem to meet those requirements within minutes after confirmation by Comtech
EF Data. This accelerated upgrade can be accomplished only because of FAST’s
extensive use of programmable devices incorporating Comtech EF Data-proprietary
signal processing techniques. These techniques allow the use of a unique access code to
enable configuration of the available hardware. The access code can be purchased at any
time from Comtech EF Data. Once obtained, the access code is loaded into the unit
through the front panel keyboard or the rear remote port.
With the exclusive FAST technology, operators have maximum flexibility for enabling
functions as they are required. FAST allows an operator to order a modem precisely
tailored for the initial application.
1.4.3 Implementation
FAST is factory-implemented in the modem at the time of order. Hardware options for
basic modems can be ordered and installed either at the factory or in the field. The
operator can select options that can be activated easily in the field, depending on the
current hardware configuration of the product. The Activation Procedure is described in
Appendix C.
1.4.4 Hardware Options
There are four hardware options available.
There is the Comtech EF Data Turbo Product Codec (TPC), representing a very
significant development in the area of FEC. It consists of a plug-in daughter card
(SIMM module) that is field upgradeable. The TPC option provides data rate capability
up to 20 Mbps, and code rates of:
Turbo Product Coding provides one of the best Forward Error Correction technologies
currently available, and is now offered with a sufficient range of code rates and
modulation types to optimize link performance under any conditions.
The second hardware option is the Internal Reference Stability. The high stability option
includes a 1 x 10
stability option has a 1 x 10
-7
10 MHz reference oscillator on the IF Backplane board, while the low
-6
10 MHz reference on the IF Backplane board. This option
must be configured in the factory at the time of order.
The third hardware option is the IF Impedance and Connectors. The IF may be
configured with either BNC female connectors at 75Ω impedance, BNC female
connectors at 50Ω impedance, or TNC female connectors at 50Ω impedance. This option
also must be configured in the factory at the time of order.
The fourth hardware option is the Quad E1 Data Interface Module. This gives the user
1 to 4 ports of E1, (each are D&I capable). These ports must use a synchronous E1
reference. This option also must be configured in the factory at the time of order.
1.4.5 Supporting Hardware and Software
The Modem incorporates an FSK serial link that can be activated on the RX-IF port for
purpose of communicating with an FSK capable Transceiver. In this manner, a user may
monitor, configure, and control the transceiver using the front panel display and keypad
of the modem or the modem’s remote control interface. The EDMAC channel can be
used to convey M&C interface to a transceiver at the distant end of a satellite link if it is
connected to a modem.
Fully configured, the modem will meet or exceed all of the applicable requirements in
IESS-315 and is available with a full range of industry standard digital interfaces. The
modem expands the capabilities into L-Band frequencies. Utilizing advanced technology
and proprietary digital signal processing techniques, the design eliminates analog
circuitry to perform modem signal processing, resulting in higher reliability and reduced
packaging size.
1.6 Compatibility
The Modem is backwards compatible with a number of Comtech EF Data CDM modems,
SDM modems, and
Inspect shipping containers for damage. If shipping containers are damaged, keep them
until the contents of the shipment have been carefully inspected and checked for normal
operation.
The modem and manual are packaged in pre-formed, reusable, cardboard cartons
containing foam spacing for maximum shipping protection.
Do not use any cutting tool that will extend more than 1 inch into the
container. This can cause damage to the modem.
CAUTION
Unpack the modem as follows:
1. Cut the tape at the top of the carton indicated by OPEN THIS END.
2. Remove the cardboard/foam space covering the modem.
3. Remove the modem, manual, and power cord from the carton.
4. Save the packing material for storage or reshipment purposes.
5. Inspect the equipment for any possible damage incurred during shipment.
6. Check the equipment against the packing list to ensure the shipment is correct.
7. Refer to the following sections for further installation instructions.
If the modem is to be mounted in a rack, ensure that there is adequate clearance for
ventilation, particularly at the sides. In rack systems where there is high heat dissipation,
forced air-cooling must be provided by top or bottom mounted fans or blowers. Under no
circumstance should the highest internal rack temperature be allowed to exceed 50°C
(122°F).
2.2.1 Optional Rear-Mounting Installation Bracket
Install optional installation brackets (Figure 2-1) using mounting kit KT/6228-2:
There are no internal jumpers to configure. All configuration is carried out entirely in
software. The unit should first be configured locally, using the front panel keypad and
display. The unit will ship with a default Viterbi 128 kbps, QPSK, Rate 3/4 configuration.
Refer to the ‘FRONT PANEL OPERATION’ chapter for details on how to fully
configure the unit for the desired operating parameters.
Note: The auto-sensing AC power supply does not require any adjustments. Simply plug
in the supplied line cord, and turn on the switch on the rear panel.
2.4 Select Internal IF Loop
Correct operation of the unit may be verified rapidly, without the need for externally
connected equipment, providing there are at least one modulator and one demodulator.
From the top-level menu, select CONFIG, then GROUP, then MODEM. This will
require a modulator to be above a demodulator in the chassis. Then go back to the toplevel menu; select TEST, then IF LOOP (refer to the ‘FRONT PANEL OPERATION’
chapter). The demod should synchronize, and the green RECEIVE TRAFFIC LED
should illuminate. If the unit does not pass this test, call the factory for assistance.
2.5 Connect External Cables
Having verified correct operation in IF loop, enter the desired configuration, and proceed
to connect all external cables. If difficulties occur, please call the factory for assistance.
Observe the following:
• If modulators and demodulators are to be used without grouping them as a
modem, a data interface cable is required to plug into each unit. If a modulator
and demodulator are grouped as a modem, the modulator must be located above
the demodulator and a single data interface cable is used simply by connecting it
to the demodulator.
• If a modulator, demodulator, or grouped (modem) is defined as a back up unit, a
data interface cable is not required to the unit or units.
Note: Each modulator has an output power level in the range -5 to -25 dBm (-5 to -45
dBm for L-Band). Even though there is a single IF output connector and a single IF input
connector, all four slots are hooked up by way of internal power splitters and summers.
If two modulators are turned on, the total power out will be 3 dB higher (assuming both
modulators are set to the same power level). If four modulators are turned on, the total
power out will be 6 dB higher (assuming all modulators are set to the same power level).
2–4
Chapter 3. FUNCTIONAL
DESCRIPTION
The modem has two fundamentally different types of interface: IF and Data.
• The Data interface can be a bi-directional path, which connects with the
customer’s equipment (assumed to be the DTE) and the modem (assumed to be
the DCE).
• The IF interface provides a bi-directional link with the satellite via the uplink and
downlink equipment.
Transmit data is received by the terrestrial interface where line receivers convert the
clock and data signals to CMOS levels for further processing. A small FIFO follows the
terrestrial interface to facilitate the various clocking and framing options. If framing is
enabled, the transmit clock and data output from the FIFO pass through the framer, where
the overhead EDMAC data is added to the main data. Otherwise, the clock and data are
passed directly to the Forward Error Correction encoder. In the FEC encoder, the data is
scrambled, differentially encoded, and then convolutionally encoded. Following the
encoder, the data is fed to the transmit digital filters, which perform spectral shaping on
the data signals. The resultant I and Q signals are then fed to the BPSK/QPSK/
8-PSK/16-QAM modulator. The carrier is generated by a frequency synthesizer, and the
I and Q signals directly modulate this carrier to produce an IF output signal.
The RX IF signal is translated and filtered at an intermediate frequency (IF) using the
coarse step synthesizer. This is mixed with a second synthesizer, resulting in the signal
being IF sampled with a high-speed analog to digital converter (A to D). The sampled IF
is then digitally split into an in-phase (I) and a quadrature (Q) component. An AGC
circuit keeps the desired signal level constant over a broad range of input levels. The I
and Q signals are then decimated to reduce the computation rate into the poly phase
matched filter. Carrier and clock recovery is performed on the baseband I and Q signals
after the matched filter. The resultant demodulated signal is fed, in soft decision form, to
the selected FEC decoder (which can be Viterbi, TCM, Reed-Solomon, or Turbo if
installed). After decoding, the recovered clock and data pass to the de-framer (if EDMAC
framing is enabled) where the overhead information is removed. Following this, the data
passes to the Plesiochronous/Doppler buffer, which has a programmable size, or
alternatively bypasses the buffer. From here, the receive clock and data signals are routed
to the terrestrial interface, and are passed to the externally connected DTE equipment.
Physically a modem chassis is comprised of three main card assemblies:
1. The first of these is the IF Backplane card, which includes the frequency
reference; power splitters, power summers, the FSK link and the IF Loop back
functions.
2. The second card is the Digital Back plane card. This routes all the control
signals, the data path switching, the carrier-in-carrier signals and power for all
modules.
3. The third is the M&C, which controls all functions in the unit.
Within the chassis are four slots, which allow any combination of modulators or
demodulators to be installed. If configured as a single modem, two plug-in cards
comprising a modulator and demodulator are required.
A Modulator card contains the transmit interface circuits, the framer, the encoder or
encoders and the signal processing functions of modulation.
A Demodulator card performs all of the signal processing functions of carrier search,
cancellation, demodulation, Forward Error Correction, the de-framer,
plesiochronous/Doppler buffer and the receive interface circuits.
Terrestrial data interface cards can be on the modulator cards or demodulator cards.
When a modulator and demodulator are grouped together, the data interface card can be
used for full-duplex data interface. When 1 up to 4 ports of E1 (with D&I) are needed the
Quad E1 Data Interface Module can be installed in slots 3 and 4.
Figure 3-1 shows a functional block diagram of the modem with either modulators and
demodulators in all 4 slots and the figure also shows a modulator in slot 1 and a
demodulator in slot 2 along with a Quad E1 Data Interface Module in slot 3 and 4.
The modem is constructed as a 1RU high rack-mounting chassis, which can be
freestanding, if desired. Rack handles at the front facilitate removal from and placement
into a rack. Figure 4-1 shows the front panel of the modem.
The Modem front panel features a Vacuum Fluorescent Display (VFD), a keypad, and
eight LED indicators. The user enters data via the keypad, and messages are displayed on
the VFD. The LEDs indicate, in a summary fashion, the status of the selected module.
The VFD is an active display showing 2 lines, each of 40 characters. It produces a blue
light, the brightness of which can be controlled by the user. It has greatly superior
viewing characteristics compared to a Liquid Crystal Display (LCD), and does not suffer
problems with viewing angle, contrast or temperature.
The keypad has six individual keyswitches, mounted directly behind a fully sealed
membrane overlay. They have a positive ‘click’ action, which provides the user with
tactile feedback. These six switches are identified as [↑], [↓], [→], [←] arrows, ENT and
CLR. The functions of these keys are described in the ‘FRONT PANEL
OPERATION’ section.
There are eight LEDs on the front panel. The behavior of these LEDs is described in the
‘FRONT PANEL OPERATION’ section.
IMPORTANT
A USB Slave connector is provided on the front panel. This feature
allows the user to reflash firmware.
The rear panel can be customized to meet the customer’s requirements. Figure 4-2 shows
three configurations that are available. Table 4-1 lists these connectors and Figure 4-2
shows the locations.
Figure 4-2. Rear Panel
Slot 1
Slot 2
Configuration #1 Modem 1 with G.703 T1/E1 Balanced (DB-15)
Modem 2 with EIA-422 (DB-25)
Configuration #2 Modem 1 with G.703 T1/E1 Unbalanced (BNC)
Modem 2 with EIA-422 (DB-25)
Slot 3
Slot 4
IF I/OPrime Power & Control
Configuration #3 Modem 1 with G.703 T1/E1 Balanced (DB-15) and
Quad E1 Interface Module, 1-4 Ports of E1,with D&I (2) DB-9F)
1. One interface per Modem (i.e. Modulator and Demodulator card combination) or one interface
per Modulator card and Demodulator card are required if used independently.
2. When grouping a modulator and demodulator together to use as a modem, the modulator must be
located above the demodulator.
3. For redundant operation the backup unit does not need an interface.
4. For redundant operation the backup unit needs to be located in the lower right hand slot (#4) for
single module redundancy. For modem redundancy the backup units must be located in the right
hand slots (#3 & #4).
5. In the example Configuration #1 above, because all modules have interfaces, the following
configurations are possible.
a. Two independent modulators - one with a G.703 balanced and the other with an EIA-530
interface, with two independent demodulators one with a G.703 balanced and the other
with an EIA-530 interface.
b. Two independent modems - one with a G.703 balanced and the other with an EIA-530
interface (located on the demodulators).
c. A 1:1 redundant modem, with the online unit configured with a G.703 interface. The off
line modules will provide the backup even with a different interface.
6. In the example Configuration #3 above, the Quad E1 Interface Module is used in slot 3 and 4.
The modulator in slot 1 is grouped with the demoduletor in slot 2. This unique combinations
allows the user to select the Quad E1 interface or the data interface located in the modulator or
demodulator.
Note: The European EMC Directive (EN55022, EN50082-1) requires using properly shielded cables for
DATA I/O.
4.4 Chassis Connections
4.4.1 USB Port
This port is used to reflash firmware.
For continued operator safety, always replace the fuses with the correct type and
IMPORTANT
rating.
4.4.2 M&C 10/100BaseT Connector
The M&C 10/100BaseT connector is an 8-pin RJ-45 10/100BaseT Ethernet port
providing access to the modem’s management functions.
4.4.3 485/232 Connector
The 485/232 connectors are a 9-pin 'D' type male (DB9-M). Access is provided to remote
control ports of the modem, using both RS-232 and RS-485.
Table 4-2. Remote Control Interface Connector Pin Assignments
Pin # Description Direction
1 Ground
2 RS-232 TX Data Out
3 RS-232 RX Data In
4 Reserved - do not connect to this pin
5 Ground
6 RS-485 RX Data B * In
7 RS-485 RX Data A * In
8 RS-485 TX Data B Out
9 RS-485 TX Data A Out
All modules contain an alarm connector. The Alarms connector is a 15-pin 'D' type male
(DB15 M). This provides the user with access to the Form-C relay contacts, which
indicate the fault status of the unit. These are typically connected to an external fault
monitoring system, often found in satellite earth stations.
For a Modulator, TX fault and Unit Fault are supported. The transmit I and Q modulator
samples are available on this connector. Connecting these signals to an oscilloscope in
X,Y mode will provide the modulator signal constellation diagram, which is a useful
diagnostic aid. A pin also is provided which can mute the transmit carrier. This requires
that the pin be shorted to ground, or a TTL ‘low’.
For a Demodulator, RX fault and Unit Fault are supported. If a Modulator and
Demodulator are vertically grouped together as a modem, TX fault and the External
carrier off pin will also be supported. The receive I and Q demodulator samples are
provided on this connector. Connecting these signals to an oscilloscope in X,Y mode will
provide the receive signal constellation diagram, which is a useful diagnostic aid. As an
aid to antenna pointing, or for driving step-track equipment, an analog AGC signal is
provided on Pin 2 of this connector.
The Balanced G.703 connection is a 15-pin female connector located on the rear
mounting plate of the modulator or demodulator. If a Modulator and Demodulator are
vertically grouped together as a modem, the data interface connector on the Demodulator
switches to duplex. This feature allows a single data interface connection to be used for a
modem instead of needing a “Y” cable. Otherwise, each module is a simplex data
interface. Refer to Table 4-4 for pin assignments.
1 Drop Data Input ( - ) DDI– In
9 Drop Data Input (+) DDI+ In
2 Ground GND
10 Not Used
3 Insert Data Output ( - ) IDO– Out
11 Insert Data Output (+) IDO+ Out
4 Ground GND
12 Drop Data Output ( - ) DDO– Out (D&I Only)
5 Drop Data Output (+) DDO+ Out (D&I Only)
13 Insert Data Input ( - ) IDI– In (D&I Only)
6 Insert Data Input (+) IDI+ In (D&I Only)
14 Not Used
7 Not Used
15 Not Used
8 Not Used
4.4.6 Unbalanced G.703 Tx/Rx Connectors
Two female BNC 75Ω connectors are available for unbalanced operation at the G.703
data rates of T1 (1.544 Mbps) and E1 (2.048 Mbps). If a Modulator and Demodulator are
vertically grouped together as a modem, the Tx data input interface connector on the
Demodulator becomes active, allowing duplex operation. Otherwise, the Tx data input
connector is used on the modulator and the Rx data output connector is used on the
demodulator.
The Data connector is a 25-pin ‘D’ type female (DB-25F). This connector conforms to
the RS-530 pinout, which allows for connection of different electrical standards,
including EIA-422, V.35, and EIA-232.
All data interfaces are duplex! They will only operate as duplex if a
Modulator and Demodulator are vertically grouped together as a modem. In
that case the data interface connector on the Demodulator switches to duplex.
This feature allows a single data interface connection to be used for a modem
IMPORTANT
instead of needing a “Y” cable. Otherwise, the data interface for each module
will only operate as simplex.
It is the responsibility of the user to provide the appropriate cables to connect
to this RS-530 connector.
Table 4-5. RS-530 Data Interface Connector Pin Assignments
Pin #
2 TX Data A DTE to Modem SD A SD A BA 103
14 TX Data B DTE to Modem SD B SD B - 103
24 TX Clock A DTE to Modem TT A SCTE A DA 113
11 TX Clock B DTE to Modem TT B SCTE B - 113
15 INT TX Clock A Modem to DTE ST A SCT A DB 114
12 INT TX Clock B Modem to DTE ST B SCT B - 114
3 RX Data A Modem to DTE RD A RD A BB 104
16 RX Data B Modem to DTE RD B RD B - 104
17 RX Clock A Modem to DTE RT A SCR A DD 115
9 RX Clock B Modem to DTE RT B SCR B - 115
8 Receiver Ready A Modem to DTE RR A RLSD * CF 109
10 Receiver Ready B Modem to DTE RR B - - 109
23
7 Signal Ground - SG SG AB 102
1 Shield - Shield FG AN 101
Generic Signal
Description
External Carrier Off
(RS-232 ‘1' or TTL ‘low’ )
Direction
DTE to Modem - - - -
RS-422
RS- 530
LVDS
V.35 RS-232 Circuit #
Notes:
1. Receiver Ready is an RS-232 -level control signal on a V.35 interface
2. DO NOT connect signals to pins which are not shown - these pins are reserved for use by the redundancy
system
3. ‘B’ signal lines are not used for RS-232 applications
4. For X.21 operation, use the EIA-422 pins, but ignore RX Clock if the Modem is DTE, and ignore TX clocks if
The (2) Data connectors on the Quad E1 interface card are 9-pin ‘D’ type female (DB9F). Refer to Table 4-xx for pin assignments. J1 and J2 are shown below. Also available
is an adapter y-cable to adapt the DB9 to (2) RJ45 jacks, (part number PL/xxxTBD), see
Table xx and figure xx.
Table 4-xx6. Quad E1 Data Interface J1 Connector Pin Assignments
Pin # Signal Function Name Direction
5 DDI (+) Port1_Tx+ In
9 DDI (-) Port1_Tx– In
4 IDO (+) Port1_Rx+ Out
8 IDO (-) Port1_Rx– Out
3 Ground Gnd 7 DDI (+) Port2_Tx+ In
2 DDI (-) Port2_Tx– In
6 IDO (+) Port2_Rx+ Out
1 IDO (-) Port2_Rx– Out
Table 4-xx7. Quad E1 Data Interface J2 Connector Pin Assignments
Pin # Signal Function Name Direction
5 DDI (+) Port3_Tx+ In
9 DDI (-) Port3_Tx– In
4 IDO (+) Port3_Rx+ Out
8 IDO (-) Port3_Rx– Out
3 Ground Gnd 7 DDI (+) Port4_Tx+ In
2 DDI (-) Port4_Tx– In
6 IDO (+) Port4 Rx+ Out
1 IDO (-) Port4_Rx– Out
5 E1 Ref Clock In (+) Ref_Clk_In (+) In
9 E1 Ref Clock In (-) Ref_Clk_In (+) In
4 Not used -- -8 Not used -- -3 Ground Gnd 7 Not used -- -2 Not used -- -6 E1 Ref Clock Out (+) Ref_Clk_Out (+) Out
1 E1 Ref Clock Out (-) Ref_Clk_Out (+) Out
The IF connectors will depend on the configuration ordered. The following reflects
configurations available. BNC 75Ω is standard for 70/140MHz IF, N-Type 50Ω for LBand, and BNC Ref Connector. This 50Ω BNC female connector provides an external
reference input for the Tx and Rx IF synthesizers, and for the internal transmit clock.
The load impedance is 60.4Ω, so the VSWR is less than 1.25:1 at either 50Ω or 75Ω.
Input level is 0 dBm minimum to +20 dBm maximum at either 1, 2, 5, 10, or 20 MHz.
When external reference is enabled, the internal 10 MHz reference oscillator is phase
locked to the external reference input by a 10Hz bandwidth PLL. If no activity is present
at the external reference input, the modem will revert to the internal 10 MHz reference.
4.5 AC Power Connector
A standard, detachable, non-locking, 3-prong power cord (IEC plug) supplies the
Alternating Current (AC) power to the modem. Observe the following:
AC Power Specifications
Input Power 290W maximum, 57W typical without BUC power supply.
Input Voltage 100 - 240 volts AC, +6%/-10% - autosensing
(total absolute max. range is 90 to 254 VAC)
Connector Type IEC
Fuse Protection 3.15A Slow-blow
Line and neutral fusing
20 mm type fuses
4.6 DC Power Connector
A standard, 3-screw terminal block supplies the Direct Current (DC) power to the
modem. Observe the following:
AC Power Specifications
Input Power 290W maximum, 57W typical without BUC power supply.
Input Voltage 36 to 72 VDC; 6.25 amps
Connector Type Terminal Block
Fuse Protection 3.15A Slow-blow
The user can fully control and monitor the operation of the Modem from the front panel
(Figure 5-1), using the keypad and display. Nested menus are used, which display all
available options, and prompt the user to carry out a required action.
The display has two lines of 40 characters each. The display is divided into two areas.
• The left hand area briefly describes the contents of the four plug-in slots and
indicates which slot is currently being addressed. To navigate between sides is
as simple as selecting a slot if the curser is on the left side and being in the root
menu on the left side and arrowing to the left.
• The right hand side accesses the addressed plug-in device. To group a modulator
and demodulator together requires the modulator to be located above the
demodulator, one of the two modules needs to be selected in the left side of the
screen, return to the right side of the screen go to Config, Group, Modem, and
select Group.
5–1
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
On most menu screens, the user will observe a flashing solid block cursor, which blinks
at a once-per-second rate. This indicates the currently selected item, digit, or field. Where
this solid block cursor would obscure the item being edited (for example, a numeric field)
the cursor will automatically change to an underline cursor.
If the user were to display the same screen for weeks at a time, the display could become
‘burnt’ with this image. To prevent this, the unit has a ‘screen saver’ feature that will
activate after 1 hour. The top line of the display will show the Circuit ID (which can be
entered by the user) and the bottom line will show the circuit Eb/No value (if there is a
demod and it is locked) followed by ‘Press any key....’. The message moves from right to
left across the screen, then wraps around. If there are multiple circuits, their messages and
Eb/No’s will be displayed sequentially. Pressing any key will restore the previous screen.
The behavior of the front panel LEDs is described below in Table 5-1.
Table 5-1. Front Panel LED Indicators
LED Color Condition
Unit
Status
Transmit
Traffic
Receive
Traffic
Online
Stored Event
Remote
EDMAC Mode
Test Mode
Red A Unit Fault exists (Example: PSU fault)
Green No Unit Faults
Note: Unit fault does not include Tx or Rx fault.
Green No Tx Traffic Faults
Off A Tx Traffic fault exists or the Tx Carrier is in OFF state
Note: This LED corresponds to the selected slot, example <TX>.
Green No Rx Traffic Faults (demod and Viterbi decoder are locked, everything is OK)
Off
Note: This LED corresponds to the selected slot, example <RX>.
Green The Unit is On Line, and carrying traffic
Off
Note: This LED corresponds to the selected slot, example <RX>.
Orange
Off There are no Stored Events
Orange The Unit is in Remote Mode - local monitoring is possible, but no local control
Off The Unit is in Local Mode - remote monitoring is possible, but no remote control
Flashing ODU FSK control has been enabled, and there is a communications fault.
Orange
Off
Orange
Off
An Rx Traffic fault exists (the demod may still be OK – check the fault status of the
unit from the Monitor menu).
The Unit is Off Line (standby) - forced by externally connected 1:1 or 1:N
redundancy system
There is a Stored Event in the log, which can be viewed from the front panel, or
retrieved via the remote control interface
Framing on, EDMAC on, and unit defined as Slave - local monitoring is possible,
but no local control
Either the unit is in Transparent mode (no framing), or the framing has been
selected, but in AUPC-only mode, or EDMAC Master configuration.
A Test Mode is selected (example: IF Loopback), or BERT Generator is turned on,
or BERT Monitor is turned on, or Spectrum Analyzer is turned on.
There is no Test Mode currently selected, BERT Generator is off, BERT Monitor is
off, and spectrum Analyzer is off.
In general, the Alarm relay state will reflect the state of the Front Panel LEDs. For instance, if
the Unit Status LED is red, the Unit Alarm relay will be active, etc. The one exception is the
Transmit Traffic relay. This will only be activated if a Transmit Traffic Fault exists – it does not
IMPORTANT
5–2
reflect the state of the TX carrier.
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
The keypad is shown in Figure 5-2:
Diamond Keypad (Presently used on all Units) Button Keypad (New Configuration for Units)
Figure 5-2. Keypad
The function of these keys is as follows:
IMPORTANT
ENT
(Enter)
CLR
(Clear)
←→
(Left, Right)
↑↓
(Up, Down)
This key is used to select a displayed function or to execute a
modem configuration change.
This key is used to back out of a selection or to cancel a
configuration change, which has not been executed using ENT.
Pressing CLR generally returns the display to the previous
selection.
These arrows are used to move to the next selection or to move the
cursor position. Most of the menus (space permitting) include arrow
key hints to guide the user.
These arrows are used primarily to change configuration data
(numbers), at the current cursor position. Occasionally they may be
used to scroll through a number of choices at the current cursor
position. Most of the menus (space permitting) include arrow key
hints to guide the user.
The keypad has an auto-repeat feature. If a key is held down for more than 1 second, the key
action will repeat, automatically, at the rate of 15 keystrokes per second. This is particularly
useful when editing numeric fields, with many digits, such as frequency or data rate.
5–3
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
5.2 Left-Hand Display Area
The left side of the display (or slot screen) efficiently indicates what is in the four plug-in
slots and which slot is currently being addressed.
Four ungrouped plug-ins are displayed as in this example:
TX TX | (right hand display area)
<RX> RX | (right hand display area)
This display indicates modulators in the top slots, and demodulators in the bottom. The
locations of the four indicators line up with the location of the four slots when viewed
from the back of the chassis. The left hand TX on the display corresponds with the top
left slot in the chassis when viewed from the back. An empty slot is left blank.
The left RX on the example display is highlighted. This is the selected slot. All monitor
functions (including the front panel LEDs) reflect the status of this slot. All parameters
selected from the menu tree while this slot is selected apply either to this slot or to
common functions. The menus for common functions appear redundantly in all four slots.
To change slots, move the cursor to the desired slot, and press enter.
The designator for a plug-in device with an unmasked failure has an F suffix:
TX TXF | (right hand display area)
<RX> RX | (right hand display area)
In this example, the upper right transmitter has a fault. (View the fault using Monitor,
Alarms, etc).
5.2.1 Modems
A modulator in a top slot can be grouped with a demodulator in the slot directly below it
to form a modem:
TX <MD> | (right hand display area)
RX | (right hand display area)
The example indicates a configuration in the right hand slots (when viewed from the back
of the chassis) grouped together to form a modem. Selecting the slots is the same as a
basic configuration except that the blank area below the MD are not be selectable. When
the modem is selected, the menus will display modulator and demodulator functions, and
the software will select the appropriate plug-in for the command.
5–4
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
Two modems can share a modem:
MD <MD> | (right hand display area)
| (right hand display area)
The selected modem is the modulator demodulator pair on the right side of the chassis
(when viewed from the back). When modem is in CnC™ mode, the brackets (<>) will
turn into bold characters.
5.2.2 Redundancy
Modules, (modulators and demodulators) can be upgraded to operate as redundant units.
If enabled the module can back up a like kind module located anywhere in the chassis. If
a modulator and demodulator have redundancy enabled and they are grouped as a
modem, the pair can back up a modem. Note: The interface selected for the modules
does not have to match the interface type used on the prime modules.
Three redundancy modes are possible with a modem. Back-up devices are notated with a
B suffix while the designated prime modules (non-modem grouped) are noted with P
suffix. In a non-modem configuration, the back-up device must be installed in slot #4. If a
backup device has failed, the B suffix and the F suffix will alternately display.
1:1 redundant modems look similar to the two-modem example. The modems have
independent monitor functions, but configuring the prime modem will configure the back
up modem.
MD <MDB> | (right hand display area)
| (right hand display area)
In this example, the backup modem is selected.
1:2 and 1:3 modulators or demodulators look similar to the basic display. A backup
modulator or demodulator will back up all compatible modulators or demodulators in the
chassis designated as primes.
The Online LED together with the selection bracket (<>) is used to indicate which device
is online.
5–5
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
5.2.3 Spectrum Analyzer
The built-in spectrum analyzer mode is available, accessible via remote control, front
panel or web browser. When it is active, the selected demod will not respond to specific
Rx front panel settings, nor will it carry traffic. It is marked with an S suffix. It has it’s
own front panel menu controls under “Test” menu.
TX TX | (right hand display area)
<RX> RXS | (right hand display area)
In this example, the bottom right receiver (as seen from the back of the chassis) is being
used as a spectrum analyzer. Only one Rx is allowed to enable spectrum analyzer in a
chassis. To view the spectrum, the user needs a Windows application from Comtech or a
web browser.
5.3 Right-Hand Display Area
Figure 5-3 shows the menu structure similar to the CDM-570L. The menus are shown
fully populated, but if the addressed plug-in device is a modulator or a demodulator,
much of the menu tree will be locked out. Functions that are not tied to a plug-in slot
(like the external reference) are displayed no matter which slot is addressed.
The detailed screens and menus are as follows.
5.4 Accessing the Display Area
Since the front panel display screen is split into two, the left-hand display area (also
called as the slot screen) can be accessed by using ◄ arrow key if the menu-level is
MAIN, CONFIG, MONITOR, or INFO (and there is more than one module to select
between).
To go back to the right-hand display area (also called the menu screen), just press CLR
or ENT. By pressing ENT, the user has selected the plug-in card.
5–6
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
Para Title Remarks
5.5 Opening Screen
5.6 Main Menu Select: Config; Monitor; Test; Info; Save/Load; Util; ODU
Select: View; Clear-All
Select: View; Clear-All; Config
Framing is required for AUPC Monitor
Select: ODU; LNB
Select: Base; Slot1; Slot2; Slot3; Slot4
Figure 5-3. Principle Menu Tree
5–7
CDM-Qx Satellite Modem Revision 5
-
Q
Front Panel Operation MN/CDMQx.IOM
5.5 Opening Screen
Comtech EF Data CDM
Firmware Version: 1.1.1
This screen is displayed whenever power is first applied to the unit (70/140 MHz
version). The word “CDM-Qx” will be replaced with “CDM-QxL” for L-Band units.
Pressing any key will take the user to the top-level selection screen:
5.6 TOP LEVEL SELECTION
MAIN MENU: Config Monitor
Test Info Save/Load Util ODU
The user is presented with the following choices:
Config
Monitor
Test
Info
Save/Load
Util
ODU
(70/140 MHz only)
(Configuration) This menu branch permits the user to fully configure the
unit.
This menu branch permits the user to monitor the alarm status of the unit,
to view the log of stored events, and to display the Receive Parameters
screen.
This menu branch permits the user to invoke one of several test modes
(loopbacks, for example).
(Information) This menu branch permits the user to view information on
the unit, without having to go into configuration screens.
This menu branch permits the user to save and to retrieve up to 10
different modem configurations.
(Utility) This menu branch permits the user to perform miscellaneous
functions, such as setting the Real-time clock, adjusting the display
brightness, etc. For L-Band unit, the menu “Util” will be replaced with
“Utility”.
This menu permits the user to monitor and control Comtech CSAT and
KST transceivers.
x
5–8
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
5.6.1 CONFIG
The sub-branches available are:
CONFIG: Remote Tx Rx Group
Frame Interface Ref Mask ODU
Remote
Tx
Rx
Group
Frame
Interface
Ref
Mask
ODU
(L-Band unit
only)
(Remote Control) This menu sub-branch permits the user to define whether
the unit is being controlled locally, or remotely.
NOTE: The unit may be monitored over the remote control bus at any time.
When in Local mode, however, configuration parameters may only be
changed through the front panel. Conversely, when in Remote mode, the unit
may be monitored from the front panel, but configuration parameters may
only be changed via the remote control bus.
(Transmit) This menu sub-branch permits the user to define, on a parameterby-parameter basis, the transmit configuration of the unit.
(Receive) This menu sub-branch permits the user to define, on a parameterby-parameter basis, the receive configuration of the unit.
This menu sub-branch permits the user to group a vertically aligned
modulator and demodulator into a modem, or to group any compatible plugins for redundancy.
This menu sub-branch permits the user to define if the unit should operate in
a transparent mode (no framing) or in a framed mode. In the framed mode
(EDMAC), an overhead of 5% is added to the rate transmitted over the
satellite so that M&C information may be passed to the distant end.
(Interface) This menu sub-branch permits the user to define which electrical
interface type is active at the data connectors.
(Reference) This menu sub-branch permits the user to define whether the
unit should use its own internal 10MHz reference, or phase lock to an
externally applied reference, and if so, at what frequency. If the internal
reference is selected, it can optionally drive the connector.
This menu sub-branch permits the user to mask certain traffic alarms, which
may cause problems to the user. As an example, certain multiplexers use ‘all
ones’ as an idle pattern. However, by convention, the ‘all ones’ condition is
taken to be the Alarm Indication Signal (AIS). The CDM-Qx monitors for the
AIS condition, and if desired, this alarm may be masked.
(Outdoor Unit) This menu sub-branch permits the user to configure externally
connected Low-noise Block Down Converter (LNB) and/or Block Up
Converter (BUC) for L-Band units.
5–9
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
5.6.1.1 (ConfigRemote) – REMOTE CONTROL
Select Local,Serial, or Ethernet using the
(◄ ►)arrow keys, then press ENT.
Remote Control Entry: Local
Serial Ethernet (◄ ►,ENT)
If Local is selected then remote control will be disabled. Remote monitoring is still
possible.
(ConfigRemoteSerial)
If Serial is selected:
Remote Serial Config:
Interface Baudrate (◄ ►,ENT)
(ConfigRemoteSerialInterface)
If Interface is selected:
M&C Serial Interface: RS232
RS485-2W RS485-4W (◄ ►,ENT)
Select RS232, RS485-2W (2-wire), or RS485-4W (4-wire), using the ◄ ► arrow keys,
then press ENT.
At this point the user will be further prompted to enter the bus address.
If RS232 is selected, the following menu is displayed:
In RS-232 Mode, Serial Bus
Base Address is fixed @ 0000
5–10
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
(ConfigRemoteSerialInterfaceRS485) - RS-485 Bus
Address
However, if either RS-485 mode is selected, the user will be further prompted:
Edit RS-485 Serial Bus Base
Address: 0245 (◄ ►,▲▼,ENT)
Edit the RS-485 bus address of this unit. This is accomplished by selecting the digit to be
edited, using the
dcarrow keys. The user should then press ENT. The valid range of addresses is from
1 to 9999.
efarrow keys. The value of the digit is then changed using the
(ConfigRemoteSerialBaudrate)
If the user selects Baud Rate, the user is presented with the following menu:
M&C Serial Bus Baud Rate:
19200 Baud (▲ ▼,ENT)
Edit the baud rate of the remote control bus, connected locally to the M&C computer.
The value is changed using the cdarrow keys. The user should then press ENT. Values
of 2400, 4800, 9600, 19200, 38400, and 57600 baud
are possible.
Note that the asynchronous character format is FIXED at 8 data bits, 1 stop bit, no parity
(8-N-1).
(ConfigRemoteEthernet)
If Ethernet is selected:
Ethernet Config: (◄ ►, ENT)
Gateway Address MAC SNMP
5–11
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
(ConfigRemoteEthernetGateway)
If Gateway is selected, the submenu will display:
M&C Ethernet IP Gateway:
192.128.001.001 (◄►▲▼, ENT)
Edit the IP Gateway Address for the Ethernet M&C port for this unit. This is
accomplished by selecting the digit to be edited, using the ◄ ► arrow keys. The value
of the digit is then changed using the
▲▼ arrow keys. The user should then press ENT.
(ConfigRemoteEthernetAddress)
If Address is selected, the submenu will display:
M&C Ether IP Address/Range:
192.168.001.001/24 (◄►▲▼,ENT)
Edit the IP Address and Range for the Ethernet M&C port for this unit. This is
accomplished by selecting the digit to be edited, using the ◄ ► arrow keys. The value
of the digit is then changed using the STarrow keys. The user should then press ENT.
(ConfigRemoteEthernetMAC)
If MAC is selected, the user will only be allowed to view it as displayed for example:
M&C Port MAC Address:
00-06-B0-00-00-D5
This is a read-only window, which displays the factory program MAC address for the
Ethernet management interface.
(ConfigRemoteEthernetSNMP)
If SNMP is selected, the following sub-menu is displayed:
SNMP: Communities Traps
(◄►, ENT)
5–12
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
(ConfigRemoteEthernetSNMPCommunities)
If Communities is selected:
SNMP Communities:
Read Write (◄►, ENT)
If Read is selected, the following sub-menu is displayed:
Read Community: (◄►▲ ▼,ENT)
public
If Write is selected, the following sub-menu is displayed:
Write Community: (◄►▲ ▼,ENT)
private
Edit the SNMP Read or Write Community string using the ◄ ► and ▲ ▼ arrow keys.
Only the first 20 characters on the bottom line are available. The cursor selects the
position on the bottom line (◄ ►) and the character is then edited (▲ ▼). All printable
ASCII characters are available with the exception of backslash (ASCII code 92) and ~
(ASCII code 126). When the user has composed the string, press ENT. All trailing spaces
are removed from the Community string upon entering.
(ConfigRemoteEthernetSNMPTraps)
If Traps is selected, the following sub-menu is displayed:
Traps: Community Version
IP Addr#1 IP Addr#2 (◄►, ENT)
5–13
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
If Community is selected, the following sub-menu is displayed.
Trap Community: (◄►▲ ▼,ENT)
comtech
Edit the Trap Community string using the ◄ ► and ▲ ▼ arrow keys. Only the first 20
characters on the bottom line are available. The cursor selects the position on the bottom
line (◄ ►) and the character is then edited (▲ ▼). All printable ASCII characters are
available with the exception of backslash (ASCII code 92) and ~ (ASCII code 126).
When the user has composed the string, press ENT. All trailing spaces are removed from
the Community string upon entering.
If Version is selected, the following sub-menu is displayed.
Trap Version: (◄ ►, ENT)
SNMPv1 SNMPv2
Select SNMPv1 or SNMPv2, using the ◄ ► arrow keys, then press ENT.
If IP Addr#1 is selected, the following sub-menu is displayed:
Trap IP Addr#1: (◄►▲ ▼ENT)
000.000.000.000
If IP Addr#2is selected, the following sub-menu is displayed:
Trap IP Addr#2: (◄►▲ ▼ENT)
000.000.000.000
These two IP Addresses are Trap Destination’s IP Addresses. Edit the IP Address by
using the ◄ ► and ▲ ▼ arrow keys. If both Trap IP Address are 000.000.000.000, it
means Trap is disabled.
5–14
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
5.6.1.2 (ConfigTx) - TRANSMIT
Tx: FEC Mod Code Data Freq
On/Off Pwr Scram Clk Inv Txα
Select FEC, Mod, Code, Data, Freq, On/Off, Pwr, Scram, Clk, Inv, or Tx
the ◄ ► arrow keys, then press ENT. The user will then be taken to a further submenu. Each of these choices is described briefly in the table below:
(Forward Error Correction) This sub-menu permits the user to select the method of FEC used
FEC
Mod
Code
Data
Freq
On/Off
Pwr
Scram
Clk
Inv
Txα
for transmission (Viterbi, TPC, etc). FEC type takes the highest configuration priority.
(Modulation) This sub-menu permits the user to select the modulation type used for
transmission (BPSK, QPSK, 8-PSK, etc.). The available choice of modulation will depend on the
FEC type chosen.
(FEC Code Rate) This sub-menu permits the user to select the FEC Code Rate used for
transmission (Rate 1/2, Rate 3/4, etc). The available choice of Code Rate will depend on both
the FEC type and Modulation type selected.
(Data Rate) This sub-menu permits the user to select the transmit data rate, in steps of 1 bps.
The choice of data rate will depend on the FEC type, Modulation type, and Code Rate selected.
(Frequency) This sub-menu permits the user to select the transmit frequency, from 950 MHz to
1950 MHz, in steps of 100Hz for L-Band units, or from 50 MHz to 90 MHz and from 100 MHz to
180 MHz for 70/140MHz units.
This sub-menu permits the user to control the output state of the transmit carrier.
(Output Power level) This sub-menu permits the user to control the output level of transmit
carrier, either manually, or using the AUPC (Automatic Uplink Power Control) feature.
(Scrambler) This sub-menu permits the user to select whether or not data scrambling is used.
(Clock Source) This sub-menu permits the user to select the clock source for transmission. This
can be from the internal source, from an external source, or from the distant-end of the satellite
link (loop timed).
(Inversion) This sub-menu permits the user to invert the sense of the transmitted spectrum, or to
invert the sense of the transmitted baseband data or data clock
(α-Factor) This permits the user to select the modulator’s roll-off factor either 20% or 35%.
The FEC type takes the highest configuration priority, and the selection here
depends on what, if any, optional plug-in Codecs are installed. The choice of
IMPORTANT
FEC type then determines what modulation types, code rates, and data rates
are available. The order of hierarchy is therefore:
FEC type ► Modulation type ► Code Rate ► Data Rate
(Highest) (Lowest)
α using
5–15
CDM-Qx Satellite Modem Revision 5
-
P
Front Panel Operation MN/CDMQx.IOM
If the user changes a parameter within this hierarchy, the other parameters may
become invalid. In this case, the software will change those other parameters, in
order that the configuration remains valid at all times.
Example: Suppose the user has selected Viterbi + Reed Solomon, QPSK, Rate
1/2. Now, the user changes the modulation type from QPSK to 16-QAM. In this
case, Rate 1/2 is no longer a valid code rate, and so it will be automatically
changed to the nearest valid code rate (Rate 3/4). Each of the configuration subbranches will now be described in detail.
(ConfigTxFEC) – TX FEC TYPE
Tx FEC: Vit Vit+RS TCM+RS
TPC (◄ ►, ENT)
All possible choices are presented at all times. If an option is not installed
(either Hardware, or FAST) or not valid, the ◄ ► arrow keys will force the
IMPORTANT
FEC Type RULES COMMENT
Vit (Viterbi) Always valid
Vit+R-S (Viterbi +Concatenated
Reed-Solomon)
TCM+R-S (Trellis Coded
Modulation + Concatenated ReedSolomon)
TPC (Turbo) If the TPC codec is installed
cursor to skip past the unavailable choice.
Always valid
If 8-PSK FAST is enabled Fixed at 8-PSK and
Rate 2/3
(ConfigTxMod) – MODULATION SCHEME
Modulation: BPSK QPSK 8
16-QAM (◄ ►, ENT)
All possible choices are presented at all times. If an option is not installed
(either Hardware, or FAST) or valid , the ◄ ► arrow keys will force the
IMPORTANT
CASE RULES
BPSK Valid for all FEC types except TCM+R-S
QPSK Valid for all FEC types except TCM+R-S
8-PSK Valid for TCM+R-S, TPC (Turbo) requires 8-PSK FAST option
16-QAM Valid for Viterbi + R-S, TPC (Turbo) requires 16-QAM FAST option
5–16
cursor to skip past the unavailable choice.
SK
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
All possible choices are presented at all times. If an option is not installed
(either Hardware, or FAST) or valid, the ◄ ► arrow keys will force the
IMPORTANT
CASE RULES
5/16 Valid for BPSK and Turbo
21/44 Valid for BPSK, QPSK and Turbo
1/2 Valid for BPSK, QPSK, Viterbi, Viterbi+R-S
2/3 Valid for TCM+R-S only (8-PSK)
3/4 Valid for QPSK, 8-PSK, and 16-QAM
7/8 Valid for QPSK, 8-PSK, and 16-QAM
17/18 Valid for QPSK, 8-PSK , and Turbo
cursor to skip past the unavailable choice.
(ConfigTxData) – TX DATA RATE
Tx Data Rate: 05000.000kbps
Sym:02500.000ksps
In Quad Drop&Insert (QDI) mode, these data rates are read-only! The data rate
will be the sum of the tributary rates for all ports. This also will show the
calculated symbol rate and Nx64kbps (where N=001 to 124).
The overall range of data rates is from 32 to 20000 kbps. The overall range of symbol
rates is up to 10000 ksps. The minimum data rate is set to 32 kbps only for BPSK and
IMPORTANT
QPSK, and the maximum data rates are dependent on modulation type and FEC
encoder rate. If the user changes the modulation or FEC, and the currently selected
data rate can no longer be supported, the data rate will be adjusted automatically, up or
down, keeping the symbol rate constant. The bottom line of the display shows the
symbol rate, based on FEC type, modulation, FEC Code Rate, and Data Rate. The
valid ranges of data rate are shown in the following table.
5–17
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
FEC Type
Viterbi BPSK Rate 1/2 32 kbps to 5 Mbps Yes – see note below
Viterbi QPSK Rate 1/2 32 kbps to 10 Mbps Yes – see note below
Viterbi QPSK Rate 3/4 32 kbps to 15 Mbps Yes – see note below
Viterbi QPSK Rate 7/8 32 kbps to 17.5 Mbps Yes – see note below
Viterbi + R-S BPSK Rate 1/2 32 kbps to 4.5 Mbps Yes – see note below
Viterbi + R-S QPSK Rate 1/2 32 kbps to 9.1 Mbps Yes – see note below
Viterbi + R-S QPSK Rate 3/4 32 kbps to 13.7 Mbps Yes – see note below
Viterbi + R-S QPSK Rate 7/8 32 kbps to 16 Mbps Yes – see note below
Viterbi + R-S 16-QAM Rate 3/4 349.1 kbps to 20 Mbps Yes – see note below
Viterbi + R-S 16-QAM Rate 7/8 407.3 kbps to 20 Mbps Yes – see note below
TCM + R-S 8-PSK Rate 2/3 232.7 kbps to 18.3 Mbps Yes – see note below
TPC BPSK Rate 5/16 32 kbps to 3.1 Mbps Yes – see note below
TPC BPSK Rate 21/44 32 kbps to 4.7 Mbps Yes – see note below
TPC QPSK Rate 21/44 32 kbps to 9.5 Mbps Yes – see note below
TPC QPSK Rate 3/4 32 kbps to 15 Mbps Yes – see note below
TPC QPSK Rate 7/8 32 kbps to 17.5 Mbps Yes – see note below
TPC QPSK Rate 17/18 32 kbps to 18.888 Mbps Yes – see note below
TPC 8-PSK Rate 3/4 288 kbps to 20 Mbps No
TPC 8-PSK Rate 7/8 336 kbps to 20 Mbps No
TPC 8-PSK Rate 17/18 362.7 kbps to 20 Mbps No
TPC 16-QAM Rate 3/4 384 kbps to 20 Mbps No
TPC 16-QAM Rate 7/8 448 kbps to 20 Mbps No
Important Note: Where noted in the table above, if EDMAC framing is employed, the upper data rate will be reduced
by 5% for data rates up to 2.048 Mbps, and by 1.6% for data rates above 2.048 Mbps, where EDMAC2 framing is
used, or for Rate 21/44 BPSK/QPSK Turbo, or Rate 5/16 BPSK Turbo.
Modulation Code Rate Data Rate Range EDMAC limited?
Tx IF Freq: 1156.3456 MHz
(◄ ►,▲ ▼, ENT)
(ConfigTxFreq) – TX IF FREQUENCY
Edit the Transmit IF Frequency. This is accomplished by selecting the digit to be edited,
using the WXarrow keys. The value of the digit is then changed using the STarrow
keys. The user should then press ENT. The range of frequencies depends upon the plugin module. The above example shows the L-Band version of modem.
5–18
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
If (using the ODU, BUC menus) the user has selected a BUC LO frequency (other than
zero) and defined whether the mix is high side or low side, the display will be modified
as shown below, to include the calculated Transmit RF frequency of the modem/BUC
combination:
Tx IF Freq: 1156.3456 MHz
RF=14156.3456 (◄ ►▲ ▼ ENT)
As the Tx IF frequency is edited the RF frequency will automatically be updated
(ConfigTxOn/Off) – TRANSMIT ON/OFF CONTROL
Tx Output State: On Off
RxTxInhibit Common (◄ ►, ENT)
Select either On, Off, RxTxInhibit, or Common using the WXarrow keys, then press
ENTER.
When Rx-Tx Inhibit (RTI) is selected, it will prevent the TX carrier from being
transmitted, until the demodulator is locked.
To avoid the Tx Carrier from being turned off when the demodulator loses lock for a very
short period of time, the demodulator must be unlocked continuously for a period of 10
seconds before the transmit carrier is inhibited. This time interval is fixed and the user
cannot change it.
Having this feature enabled does not affect the internal IF Loopback feature.
But, please be aware that if an external IF Loopback is attempted (connecting
IMPORTANT
When Common is selected, this sub-menu will appear:
an external cable from the Tx IF output to the Rx IF input), then this will not
work! (The Tx carrier cannot turn on until the demod is locked, and the demod
cannot lock, because the TX output is off. The net result is that the demod will
not lock, and the Tx carrier will not turn on. USE THE RTI FEATURE WITH
EXTREME CARE!
Tx Common Output State:
Off On (◄ ► ENT)
This will turn On or Off all the transmit path – master control for all modulators.
5–19
CDM-Qx Satellite Modem Revision 5
-
R
Front Panel Operation MN/CDMQx.IOM
(ConfigTxPwr) – TRANSMIT POWER LEVEL MODE
Select the output power level mode, either Manual or AUPC, then press ENT.
Output Power Level Mode:
Manual AUPC (◄ ►, ENT)
If the user selects Manual, the following menu is displayed:
(ConfigTxPwrManual) – MANUAL MODE
Tx Output Power Level:
-03.9 dBm (◄ ►, ▲ ▼, ENT)
Edit the output power level using the ◄ ► and STarrow keys, then press ENT.
If the user selects AUPC, and ‘Framed’ mode is not selected, the following menu is
displayed:
Warning! AUPC needs
Framed Mode (ENT or CLR)
Pressing either ENT or CLR returns the user to the previous menu with Manual
selected.
If the user selects AUPC, and ‘Framed’ mode is selected, the following menu is
displayed:
(ConfigTxPwrAUPC) – AUPC MODE
Target-Eb/No Max
DemodUnlock (◄ ►, ENT)
Select either Target EbNo, Max-Range, Alarm or Demod-Unlock using the W Xarrow
keys. The user should then press ENT.
Edit the target Eb/No of the remote demod, using the ◄ ►
Default value is 3.0 dB, and upper limit is 9.9 dB. The user should then press ENT.
and STarrow keys.
(ConfigTxPwrAUPC) – MAX RANGE
Maximum-permitted Power
increase: 01dB (▲ ▼, ENT)
Edit the maximum permitted increase in power level (when in AUPC mode), using the
STarrow keys. Default value is 1dB, and upper limit is 9 dB. Then press ENT.
(ConfigTxPwrAUPC) – ALARM
Action when max Tx Power
reached: None TxAlarm (◄ ►,
Select the action that will occur if the AUPC causes the maximum output power level to
be reached, either None or TxAlarm. Then press ENT.
(ConfigTxPwrAUPC) – DEMOD-UNLOCK
Action when Remote Demo
unlocks: Nom-Pwr Max-Pwr
Select the action that will occur if the remote demod is unlocked. The choices are: NomPwr (Nominal Power), where the output level will revert to the nominal power level set
under Manual, or Max-Pwr, (Maximum Power), where the output level will change to
the maximum permitted. The user should then press ENT.
5–21
CDM-Qx Satellite Modem Revision 5
-
O
Front Panel Operation MN/CDMQx.IOM
(ConfigTxPwrCombined) – COMBINED TRANSMIT POWER
Tx Combined Output Power:
-3.9 dBm (◄ ►,▲ ▼,ENT)
The combined power adjusts the level after all modulators in the chassis have been
combined. It has a range of –5 dBm to +5 dBm. This level is fixed, and is not adjusted by
AUPC.
(ConfigTxScram) – SCRAMBLER
Scrambling:Default
n
IESS-315-On Off (◄ ►,ENT)
The options are:
Default-On
IESS-315-On
Off
the appropriate scrambler type is automatically selected
this only applies when Turbo is installed and has been selected as the FEC
type
No scrambling
As before, the options are displayed all of the time, but the ◄ ► arrow keys will force
the cursor to skip past an unavailable choice.
The default scrambler types are:
IMPORTANT
Viterbi, no framing: ITU V.35 (Intelsat variant)
Viterbi, EDMAC frame: Comtech proprietary, frame synchronized
Viterbi + R-S or TCM/R-S: Per IESS-308, frame synchronized
TPC: Comtech proprietary, frame synchronized
(ConfigTxClk) – TX CLOCKING MODE
Tx Clocking Mode: Int Ext
Loop-Timed ExtLoop (◄ ►,ENT)
Select Int (Internal), Ext (External) or Loop-Timed, using the ◄ ► arrow keys, then
press ENT.
5–22
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
Internal
External
LoopTimed
ExtLoop
indicates that the CDM-QX will supply a clock to the DTE, which is derived from its
internal high-stability source.
indicates that the CDM-QX expects to receive a clock from the DTE, to which the unit
can phase-lock its internal circuits. (If G.703 is selected as the Interface type, the
software will force the clock mode to External.)
indicates that the transmit timing source should be the receive clock, from the
direction of the satellite. This is a useful mode, in that no external connection needs
to be made in this mode. If the demodulator loses lock, or if there is no receive signal
present, the internal clock is substituted. Note also that this mode will work even with
asymmetric Rx and Tx data rates.
Indicates that the CDM-Qx expects to receive a clock from the DTE, which is derived
from the received clock from the direction of the satellite. This is useful in CnC mode
with G.703 interface wherein the remote station is relying on a centralized clock from
the hub station.
(ConfigTxInv) – TX INVERSION FUNCTIONS
Tx Inversion functions:
Spectrum Data Clock (◄ ►,ENT)
Select Spectrum or Data Clock, using the ◄ ► arrow keys, then press ENT.
If Spectrum is selected, the following sub-menu will be displayed:
Tx Spectral Inversion:
Normal Inverted (◄ ►, ENT)
Select Normal or Inverted, using the ◄ ► arrow keys, then press ENT.
If Data Clock is selected, the following sub-menu will be displayed:
Tx Data Sense:
Normal Inverted (◄ ►, ENT)
Select Normal or Inverted, using the ◄ ► arrow keys, then press ENT.
If Clock is selected, the following sub-menu will be displayed:
Tx Clock Inversion:
Normal Inverted (◄ ►, ENT)
5–23
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
(ConfigTxTxα) – TX Roll-Off (α) factor
Tx Roll-off: 20% 35%
(◄ ►, ENT)
Select 20% or 35%, using the ◄ ► arrow keys, then press ENT. The default is 35%.
Select FEC, Dem, Code, Data, Frq, Acq, Descram, Buf, Inv, Misc, or CnC® using
the WXarrow keys, then press ENT. The user will then be taken to a further sub-menu.
Each of these choices is described briefly in the table below:
FEC
Demod
Code
Data
Acq
On/Off
Descram
Buf
Inv
Misc
C-in-C
(Forward Error Correction) This sub-menu permits the user to select the method of
FEC used for reception (Viterbi, TPC, etc.). FEC type takes the highest configuration
priority.
(Demodulation) This sub-menu permits the user to select the modulation type used for
reception (BPSK, QPSK, 8-PSK, etc.). The available choice of demodulation will
depend on the FEC type chosen.
(FEC Code Rate) This sub-menu permits the user to select the FEC Code Rate used
for reception (Rate 1/2, Rate 3/4, etc.). The available choice of Code Rate will depend
on both the FEC type and Demodulation selected.
(Data Rate) This sub-menu permits the user to select the receive data rate, in steps of
1 bps. The choice of data rate will depend on the FEC type, Demodulation, and Code
Rate selected.
(Acquisition) This sub-menu permits the user to determine the amount of frequency
uncertainty the demodulator will search over in order to find and lock to an incoming
carrier.
This sub-menu permits the user to control the output state of the transmit carrier.
(Descrambler) This sub-menu permits the user to select whether or not data
descrambling is used.
(Buffer) This sub-menu permits the user to select whether or not the
Plesiochronous/Doppler buffer is used, and if so, the size of that buffer.
(Inversion) This sub-menu permits the user to invert the sense of the received
spectrum, or to invert the sense of the received baseband data.
(Miscellaneous) This sub-menu will allow the user to select Eb/No Alarm Threshold
(EbNo) and Rx roll-off (alpha) factor Rxα.
(Carrier-in-Carrier®) This sub-menu allows the user to set-up the carrier-in-carrier
parameters.
5–24
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
The FEC type takes the highest configuration priority, and the selection here
depends on what, if any, optional plug-in Codecs are installed. The choice of
IMPORTANT
FEC type then determines what demodulation types, code rates, and data rates
are available. The order of hierarchy is therefore:
FEC type ► Demodulation type ► Code Rate ► Data Rate
(Highest) (Lowest)
If the user changes a parameter within this hierarchy, the other parameters may
become invalid. In this case, the software will change those other parameters, in
order that the configuration remains valid at all times.
Example: Suppose the user has selected Viterbi + Reed-Solomon, QPSK, Rate
1/2. Now, the user changes the demodulation type from QPSK to 16-QAM. In
this case, Rate 1/2 is no longer a valid code rate, and so it will be automatically
changed to the nearest valid code rate (Rate 3/4).
Each of the configuration sub-branches will now be described in detail.
(ConfigRxFEC) – RX FEC TYPE
Rx FEC: Vit Vit+RS TCM+RS
TPC (◄ ► ENT)
All possible choices are presented at all times.
If an option is not installed (either Hardware, or FAST) or valid, the
◄ ► arrow keys will force the cursor to skip past the unavailable
IMPORTANT
choice.
CASE RULES COMMENT
Vit (Viterbi) Always valid
Vit+R-S (Viterbi +Concatenated
Reed-Solomon)
TCM+R-S (Trellis Coded
Modulation + Concatenated
Reed-Solomon)
TPC (Turbo) If the TPC codec is installed
If Vit, Vit+RS, TCM+RS, or TPC is selected, the following sub-menu will be
displayed:
All possible choices are presented at all times.
If an option is not installed (either Hardware, or FAST) or valid, the
◄ ► arrow keys will force the cursor to skip past the unavailable choice.
IMPORTANT
CASE RULES
BPSK Valid for all FEC types except TCM+R-S
QPSK Valid for all FEC types except TCM+R-S
8-PSK Valid for TCM+R-S, TPC (Turbo) requires 8-PSK FAST option
16-QAM Valid for Viterbi + R-S, TPC (Turbo) requires 16-QAM FAST option
All possible choices are presented at all times. If an option is not installed
(either Hardware, or FAST) or valid, the ◄ ► arrow keys will force the cursor
IMPORTANT
CASE RULES
5/16 Valid for BPSK and Turbo
21/44 Valid for BPSK, QPSK and Turbo
1/2 Valid for BPSK, QPSK, Viterbi, Viterbi+R-S
2/3 Valid for TCM+R-S only (8-PSK)
3/4 Valid for QPSK, 8-PSK, and 16-QAM
7/8 Valid for QPSK, 8-PSK, and 16-QAM
17/18 Valid for QPSK, 8-PSK , and Turbo
to skip past the unavailable choice.
SK
5–26
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
(ConfigRxData) – RX DATA RATE
Rx Data Rate: 05000.000kbps
Sym:02500.000ksps
In QDI mode, these data rates are read-only! The data rate will be the sum of the
tributary rates for all ports. This will also show the calculated symbol rate and Nx64kbps
(where N=001 to 124).
The overall range of data rates is from 32 to 20000 kbps. The overall range of
symbol rates is up to 10000 ksps. The minimum and maximum data rates are
IMPORTANT
FEC Type
Viterbi BPSK Rate 1/2 32 kbps to 5 Mbps Yes – see note below
Viterbi QPSK Rate 1/2 32 kbps to 10 Mbps Yes – see note below
Viterbi QPSK Rate 3/4 32 kbps to 15 Mbps Yes – see note below
Viterbi QPSK Rate 7/8 32 kbps to 17.5 Mbps Yes – see note below
Viterbi + R-S BPSK Rate 1/2 32 kbps to 4.5 Mbps Yes – see note below
Viterbi + R-S QPSK Rate 1/2 32 kbps to 9.1 Mbps Yes – see note below
Viterbi + R-S QPSK Rate 3/4 32 kbps to 13.7 Mbps Yes – see note below
Viterbi + R-S QPSK Rate 7/8 32 kbps to 16 Mbps Yes – see note below
Viterbi + R-S 16-QAM Rate 3/4 349.1 kbps to 20 Mbps Yes – see note below
Viterbi + R-S 16-QAM Rate 7/8 407.3 kbps to 20 Mbps Yes – see note below
TCM + R-S 8-PSK Rate 2/3 232.7 kbps to 18.3 Mbps Yes – see note below
TPC BPSK Rate 5/16 32 kbps to 3.1 Mbps Yes – see note below
TPC BPSK Rate 21/44 32 kbps to 4.7 Mbps Yes – see note below
TPC QPSK Rate 21/44 32 kbps to 9.5 Mbps Yes – see note below
TPC QPSK Rate 3/4 32 kbps to 15 Mbps Yes – see note below
TPC QPSK Rate 7/8 32 kbps to 17.5 Mbps Yes – see note below
TPC QPSK Rate 17/18 32 kbps to 18.888 Mbps Yes – see note below
TPC 8-PSK Rate 3/4 288 kbps to 20 Mbps No
TPC 8-PSK Rate 7/8 336 kbps to 20 Mbps No
TPC 8-PSK Rate 17/18 362.7 kbps to 20 Mbps No
TPC 16-QAM Rate 3/4 384 kbps to 20 Mbps No
TPC 16-QAM Rate 7/8 448 kbps to 20 Mbps No
Important Note: Where noted in the table above, if EDMAC framing is employed, the upper data rate will be reduced
by 5% for data rates up to 2.048 Mbps, and by 1.6% for data rates above 2.048 Mbps, where EDMAC2 framing is
used, or for Rate 21/44 BPSK/QPSK Turbo, or Rate 5/16 BPSK Turbo.
dependent on modulation type and FEC encoder rate. If the user changes the
modulation or FEC, and the currently selected data rate can no longer be
supported, the data rate will be adjusted automatically, up or down, keeping
the symbol rate constant. The bottom line of the display shows the symbol rate,
based on FEC type, modulation, FEC Code Rate, and Data Rate.
Modulation Code Rate Data Rate Range EDMAC limited?
5–27
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
(ConfigRxFreq) – RX FREQUENCY
Rx IF Freq: 1156.3456 MHz
(◄ ►, ▲ ▼,ENT)
Edit the receive frequency. This is accomplished by selecting the digit to be edited, using
the WXarrow keys. The value of the digit is then changed using the STarrow keys. The
user should then press ENT. The range of frequencies depends upon the plug-in module.
The above examples shows the L-Band version of CDM-Qx.
If (using the ODU, LNB menus) the user has selected an LNB LO frequency (other than
zero) and defined whether the mix is high side or low side, the display will be modified
as shown below, to include the calculated Receive RF frequency of the modem/BUC
combination:
Rx IF Freq:1156.3456 MHz
RF=12156.3456 (◄ ► ▲ ▼ ENT)
As the Rx IF frequency is edited the RF frequency will automatically be updated
(ConfigRxAcq) – DEMOD ACQUISITION RANGE
Demod Acquisition Range:
+/- 32 kHz (▲ ▼ ENT)
Edit the acquisition search range of the demodulator (the value entered here determines
the amount of frequency uncertainty the demodulator will search over in order to find and
lock to an incoming carrier). Editing the value is accomplished by selecting the digit to be
edited, , using the W Xarrow keys. The value of the digit is then changed using the
STarrow keys. The user should then press ENT.
The range varies from ± 1 kHz to ± 32 kHz for 70/140 IF, ± 1 kHz to ±(symbol rate/2) up
to ±200 kHz for L-Band. For symbol rates < 64 ksps, it will be ± (symbol rate/2)
The value entered here determines the amount of frequency uncertainty the demodulator
will search over in order to find and lock to an incoming carrier.
5–28
CDM-Qx Satellite Modem Revision 5
-
O
-
S
Front Panel Operation MN/CDMQx.IOM
(ConfigRxDescram) - DESCRAMBLER
Descrambling: Default
n
IESS-315-On Off (◄ ► ENT)
Options are:
Default-On
IESS-315-On
Off
the appropriate descrambler type is automatically selected.
this only applies when Turbo is installed and has been selected as the FEC
type.
no descrambling.
As before, the options are displayed all of the time, but the ◄ ► arrow keys will force
the cursor to skip past an unavailable choice.
The default descrambler types are:
IMPORTANT
Viterbi, no framing: ITU V.35 (Intelsat variant)
Viterbi, EDMAC frame: Comtech proprietary, frame synchronized
Viterbi + RS or TCM/RS: Per IESS-308, frame synchronized
TPC: Comtech proprietary, frame synchronized
(ConfigRxBuf) – RX BUFFER CLOCK SOURCE
Rx Buffer: Internal Rx
Tx-Terrestrial Ins (◄ ►, ENT)
User will select which Rx buffer clock source. Note that Tx-Terrestrial will only be
selected if the cards are grouped as modem. Also, note that External will only be
selected if QDI interface type is selected. Selecting either one will allow the user to select
th e buffer size as shown below:
Rx Buffer Size:
Disabled (▲ ▼, ENT)
Edit the size, in bits, of the Plesiochronous/Doppler Buffer. The value is changed using
the S T arrow keys. The user should then press ENT. Values of Disabled, ± 512, 1024, 2048, 4096, 8192, and 16384 bits are possible.
When Disabled is selected, the Plesiochronous/Doppler buffer is disabled. The receive
clock will then be derived from the satellite signal, and will therefore be subject to clock
offsets relative to the local transmit clock, This is due in part to the originating clock
5–29
at
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
being slightly different from the local clock (a so-called plesiochronous offset), and to
the motion of the satellite (a Doppler offset). The input to the buffer will be the signal
from the satellite, with any clock offsets and jitter. The output from the buffer will be
derived from the local TRANSMIT clock. In this way, the receive data will be perfectly
synchronous with this local clock. The modem operates with independent receive and
transmit data rates. Even in this configuration, where RX data rate <> TX data rate, the
output clock for the buffer will be phase locked to the transmit clock.
While it is only possible to select the size in bits, the corresponding total buffer size is
displayed in ms (which will vary in inverse proportion to the data rate).
(ConfigRxInv) – RX INVERSION FUNCTIONS
Rx Inversion functions:
Spectrum Data Clock (◄ ►, ENT)
Select Spectrum,Data, or Clock using the ◄ ► arrow keys, then press ENT.
If Spectrum is selected, the following sub-menu will be displayed:
Select Normal or Inverted, using the ◄ ► arrow keys, then press ENT.
If Data is selected, the following sub-menu will be displayed:
Rx Data Sense:
Rx Spectral Inversion:
Normal Inverted (◄ ►, ENT)
Normal Inverted (◄►,ENT)
Select Normal or Inverted, using the ◄ ► arrow keys, then press ENT.
If Clock is selected, the following sub-menu will be displayed:
Rx Clock Inversion:
Normal Inverted (◄ ►, ENT)
Select Normal or Inverted, using the ◄ ► arrow keys, then press ENT.
(ConfigRxMisc) – Rx Miscellaneous
Rx Misc: EbNo Rxα (◄ ►, ENT)
Select EbNo or Rx
α using the WXarrow keys, then press ENT.
5–30
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
(ConfigRxMiscEbNo) - Eb/No ALARM
Eb/No Alarm Point:
02.0 dB (◄ ►,▲ ▼,ENT)
Edit the Eb/No alarm point. This is accomplished by selecting the digit to be edited, using
the ◄ ► arrow keys. The value of the digit is then changed using the STarrow keys.
The user should then press ENT.
The range of values is from 2.0 to 16.0 dB. The user may select a value here, and if the
Eb/No falls below this value, a receive traffic fault will be generated.
(ConfigRxMiscRxα) – RX Roll-Off (α) factor
Rx Roll-off: 20% 35%
(◄ ►, ENT)
Select 20% or 35%, using the ◄ ► arrow keys, then press ENT. The default is 35%.
Select Mode, FrqOffs, SrchDelay, or ReAcq using theWXarrow keys, then press
ENT. The user will then be taken to a further sub-menu.Each of these choices is
described briefly in the table below:
Mode
FrqOffs
SrchDelay
ReAcq
(Mode of Operation) This sub-menu permits the user to select the mode of
operation for the CnC™.
(Frequency Offset) This sub-menu permits the user to adjust the frequency
offset for the CnC™.
(Search Delay) This sub-menu permits the user to configure the search
delay parameters for the CnC™.
(ReAcquisition Time) This permits the user to set the re-acquisition time in
seconds when the desired carrier is lost.
5–31
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
(ConfigRxCnCMode) – CnC® MODE OF OPERATION
CnC Mode: Off On
(◄ ►, ENT)
Select Off, or On using the WXarrow keys, then press ENT. The user will then be
taken to a further sub-menu. If CnC On is selected, there will be some messages at the
front panel as shown below:
LOADING CnC SAT SEARCH...
...PLEASE WAIT!
CnC SEARCH IS PROCESSING...
...PLEASE WAIT!
If CnC is successful, it will display as follows:
CnC SEARCH SUCCESSFUL!
Delay=239ms Offset=+001.0k
If CnC is not successful, it will display this:
CnC SEARCH IS UNRESOLVED!
PLEASE CHECK TX POWER LEVEL
(ConfigRxCnCFrqOffs) – CnC FREQUENCY OFFSET
CnC Frequency Offset:
+/-015 (▲ ▼ ENT)
Edit the CnC Frequency Offset. The value of the digit is changed using the STarrow
keys. The user should then press ENT.
5–32
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
Edit the Min/Max Search Delay in milliseconds by selecting the digit to be edited, using
the WXarrow keys. The value of the digit is then changed using the STarrow keys. The
user should then press ENT.
Edit the re-acquisition time using the WXSTarrow keys. The user should then press
ENT.
5.6.1.4 (ConfigGroup) – GROUPING MOD/DEMOD CARDS
If Group is selected:
Grouping:
Modem Redundancy (◄ ►, ENT)
Enter Modem to group a vertically aligned modulator and demodulator into a modem.
The Device Selection screen should indicate either one of the devices that is to be
grouped.
Enter Redundancy to designate the backup for a redundant group. The Device Selection
screen should indicate the device to become the backup.
(ConfigGroupModem)
Modem Group:
Separate Grouped (◄ ►, ENT)
If there is a vertically aligned modulator demodulator pair with the modulator in the top
position, then the Modem selection is allowed. The selection applies to the pair of which
one is currently selected in the device select area.
Once grouped, the modulator demodulator pair can be configured as a single device.
5–33
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
(ConfigGroupRedundancy)
Redundancy: Config Mode
(◄ ►, ENT)
Selecting “Config” allows the user to set redundancy either 1:1, 1:2, 1:3, or none.
Redundancy is a FAST option and needs to be purchased to turn on this feature. Selecting
“Mode” allows the unit to do auto or manual switching between prime and back-up
device.
(ConfigGroupRedundancyConfig)
Config Redundancy:
None 1:1 1:2 1:3 (◄ ►,ENT)
If None is selected, it turns off redundancy.
(ConfigGroupRedundancyConfig 1:1)
Selecting the 1:1 entry configures 1:1 redundant modem. Modulators are required in the
top two slots, and demodulators in the bottom two. Without the proper hardware and
FAST option enabled, the WXarrow keys will force the cursor to skip past the
unavailable choice. The backup modem is installed in slot #3 and slot #4. The user can
also do 1:1 Tx or 1:1 Rx. For ungrouped scenario, the backup card is always installed in
slot #4.
(ConfigGroupRedundancyConfig 1:2)
For 1:2 case, the backup is always installed in slot #4. This is only applicable for
ungrouped scenario (no modem), that means, 1:2 Tx or 1:2 Rx.
(ConfigGroupRedundancyConfig 1:3)
For 1:3 case, the backup is always installed in slot #4. This is only applicable for
ungrouped scenario (no modem), that means, 1:3 Tx or 1:3 Rx.
5–34
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
(ConfigGroupRedundancyMode)
Redundancy Mode:
Manual Auto (◄ ►,ENT)
Default is “Manual”. If “Auto” is selected, that means the back-up will automatically
take over once the designated prime is faulted, and vice-versa. If “Manual” is selected,
when the prime is faulted, the back up will not take over. Also, the user will have the
option to do force switching.
If redundancy is configured (e.g. 1:1), force-backup menu will appear which will allow
the user to do force switching between back up and designated primary device.
Framing requires a modulator/demodulator pair grouped into a modem (see
ConfigGroup).
Select Unframed, EDMAC, EDMAC-2, or D&I++ using the ◄ ► arrow keys, then
press ENT.
The sub-branches available are:
(ConfigFrameUnframed) - UNFRAMED
No framing is selected. No overhead is added, and the unit will be compatible with other
manufacturer’s equipment, when operating in a ‘standard’ configuration.
5–35
CDM-Qx Satellite Modem Revision 5
-
O
Front Panel Operation MN/CDMQx.IOM
(ConfigFrameEDMAC, or ConfigFrameEDMAC-2) -
EDMAC or EDMAC-2
Comtech EF Data proprietary framing is included. The framing permits the bi-directional
passing of M&C and AUPC data between local and distant-end units. EDMAC is
backwards compatible with the CDM-500, CDM-550, CDM-550T, CDM-600 and
CDM-600L. EDMAC-2 is a reduced overhead version of EDMAC, and is not backwards
compatible with the modems listed above.
If either of these modes is selected, the following sub-menu will be displayed:
Framing mix: AUPC
nly
AUPC+EDMAC (◄ ►,
Select either AUPC-Only (default) or AUPC+EDMAC, using the ◄ ► arrow keys,
then press ENT.
Note that if framing is enabled (either EDMAC or EDMAC-2), then AUPC is
automatically enabled, but the specific EDMAC feature (passing M&C data from a local
to a distant-end unit) needs to enabled here.
If AUPC-Only is selected then none of the EDMAC features are available, even though
framing will still be enabled.
If AUPC+EDMAC is selected, the user is further prompted to select whether the unit is
an EDMAC master, or an EDMAC slave:
(ConfigFrameEDMACAUPC+EDMAC, or
ConfigFrameEDMAC-2AUPC+EDMAC) -
AUPC+EDMAC MODE
EDMAC Mode:
Master Slave (◄ ►, ENT)
Select either MASTER or SLAVE, using the ◄ ► arrow keys, then press ENT.
An EDMAC MASTER is a unit which is local to the M&C computer, and which passes
messages, via the overhead, to a distant-end modem.
An EDMAC SLAVE is a unit that is not local to the M&C computer, which is at the
distant-end of a satellite link. If MASTER is selected then the following sub-menu is
displayed:
5–36
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
Distant-end Base Address
0240 (◄ ►,▲ ▼, ENT)
Edit the address of the distant-end modem that this unit will pass messages to. This is
accomplished by selecting the digit to be edited, using the ◄ ► arrow keys. The value of
the digit is then changed using the STarrow keys. The user should then press ENT.
There is a restriction on values that can be entered here - they may only be in increments
of 10. This is automatically taken care of - the user may not edit the last digit of the
address. This has been implemented so that a single MASTER may pass messages for up
to 10 devices at the distant end. The valid range of addresses is from 10 to 9990.
But if SLAVE is selected, then the following sub-menu is displayed:
Address of this Slave
Unit: 0241 (◄ ►,▲ ▼,ENT)
Edit the address of this SLAVE unit. This is accomplished by selecting the digit to be
edited, using the WXarrow keys. The value of the digit is then changed using the
STarrow keys. The user should then press ENT. The valid range of addresses is from 1
to 9999, although ‘base 10' values will be automatically skipped.
Remember that this is a unit that is intended to be located at the distant-end of
a link, and will therefore be under the control of a MASTER at the other
end. This is the equivalent of putting the unit into Remote Control mode -
IMPORTANT
no local control is possible.
(ConfigFrameD&I++) – D&I++
If D&I++ is selected, the following sub-menu will be displayed:
Drop & Insert: EDMAC
Drp-CH/TS Ins-CH/TS (◄ ►, ENT)
If Drp-CH/TS is selected, the Tx Data Rata will be displayed.
If the Ins-CH/TS is selected the Rx data rate will be displayed.
5–37
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
5.6.1.6 (ConfigInterface) – DATA INTERFACE
Data interface for each card (modulator or demodulator) is auto detected. If grouped as a
modem, the operating data interface will be the one installed in the demod card (interface
on the modulator is not required). If a QDI interface is installed and a modem is grouped,
then either it or the interface installed on the Demod can be selected. The card can
support one of the following:
• RS-422 (RS-530)
• V.35
• RS-232
• G.703 (for single T1 or E1)
• HSSI
• QDI (Quad Drop & Insert)
The blinking cursor will point to the supported data interface for the card being installed,
then press ENT
Interface: RS422 V.35 RS232
HSSI ASI G.703 QDI NONE
If grouped as a modem and RS422, V.35 or RS232 are selected, the following sub menu
will be displayed:
RTS/CTS operation: (▲ ▼, ENT)
Loop,RTS Controls Tx Out
The option is changed using the STarrow keys. The user should then press ENT. The
following options are possible:
RTS/CTS Loop, No Action
Loop, RTS Controls Tx Out
Ignore RTS, Assert CTS
RTS and CTS are looped, so that CTS echoes the state of RTS,
but RTS does not control the ON/OFF state of the carrier.
RTS and CTS are looped, so that CTS echoes the state of RTS,
and RTS controls the ON/OFF state of the carrier (in other
words, the modem will not bring up its TX carrier until RTS is
asserted.
RTS is ignored, and CTS is asserted unconditionally.
5–38
CDM-Qx Satellite Modem Revision 5
-
B
d
Front Panel Operation MN/CDMQx.IOM
IfHSSI is selected, the following sub menu will be displayed:
HSSI Mode Select: (▲ ▼, ENT)
TA to CA Loop
The option is changed using the STarrow keys. The user should then press ENT. The
following options are possible:
TA to CA Loop
RR controls CA, TA controls
Tx Out
If G.703 is selected, the following sub menu will be displayed:
TA and CA are looped, but TA does not control the ON/OFF
state of the carrier.
TA controls the ON/OFF state of the carrier (in other words, the
modem will not bring up its TX carrier until TA is asserted.
G.703 Type: T1 E1
alance
E1-Unbalanced (◄ ►,
If G.703 balanced interface, the user can select either T1 or E1-Balanced. If G.703
unbalanced interface, the user can select either T1 or E1-Unbalanced. Use the ◄ ►
arrow keys to select, then press ENT.
If T1 is selected, the following sub-menu will be displayed:
T1 Configuration:
Length Line-Code (◄ ►, ENT)
Select Length or Line Code using the ◄ ► arrow keys, then press ENT.
If Line –Code is selected, the following sub-menu will be displayed:
G.703 T1 Line Code:
HDB3 AMI (◄ ►, ENT)
Select HDB3 or AMI using the ◄ ► arrow keys, then press ENT.
5–39
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
If Length is selected, the following sub-menu will be displayed:
T1 Line Length:
000-133 feet (▲ ▼,
Edit the line length using the STarrow keys, then press ENT Values will toggle
between the following values:
0-133, 133-266, 266-399, 399-533, and 533-655 feet.
If either E1-Balanced or E1-Unbalanced is selected, the following sub-menu will be
displayed:
Select HDB3 or AMI using the W Xarrow keys, then press ENT.
G.703 E1 Line Code:
HDB3 AMI (◄ ►, ENT)
If QDI is selected, the following sub-menu will be displayed:
QDI Tributary Ports:
1 2 3 4 (◄ ►, ENT)
In this sub menu, the user can select one of the four (4) ports to be configured. Choosing
either one of them will display the next sub-menu as follows:
Port#X: Drop Insert LineCode
Alarm (◄ ►, ENT)
Where X is the tributary port number. If Drop is selected, the next sub-menu will be
Port#X Tx Trib Rate:(▲▼, ENT)
01536.000kbps (24x64kbps)
This sub-menu shows the Nx64kbps data rate where N=24 in this example. Use
STarrow keys to set the data rate. After pressing ENT, a sub-menu will appear as
shown:
Px D-CH: 1 2 3 4 5 6 ►
TS: 11 02 06 04 05 03
Where x is the tributary port number. A X display means that there are more channels
beyond channel 6 as in this example. Use right arrow key X to view more. sure that ENT
key is pressed once it’s done.
5–40
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
If Insert is selected, the sub-menu will display:
IMPORTANT
Port#X Rx Trib Rate:(▲▼, ENT)
01536.000kbps (24x64kbps)
This is similar to the drop-side. Upon setting the data rate, a sub-menu will appear as
shown:
Px I-CH: 1 2 3 4 5 6 ►
TS: 11 02 06 04 05 03
This is similar to the drop-side except that this is done at the Rx side. Please make sure
that ENT key is pressed once it’s done.
If LineCode is selected, the next sub-menu will be displayed:
Port#X Line Code:
HDB3 AMI (◄ ►, ENT)
Select HDB3 or AMI using the W Xarrow keys, then press ENT.
If Alarm is selected, the sub-menu will display
Port#X Bipolar Violation:
Active Masked (◄ ►, ENT)
Default is Masked.
5–41
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
5.6.1.7 (ConfigRef) - REFERENCE OSCILLATOR
The modem can accept an externally supplied frequency reference, using the BNC
connector on the rear panel. However, rather than bypassing the internal reference, and
substituting the external signal, the internal reference is used in a low-bandwidth (~ 2Hz)
phase-locked loop (PLL), so the modem actually phase locks to the reference external
signal. There are two distinct advantages to this scheme:
a. It permits hitless switching between the operation of internal and external reference.
There are no sudden discontinuities of frequency and phase in the transmitted carrier.
b. Due to the very low bandwidth of the PLL, it permits the external reference to have
an inferior phase noise characteristic than the internal reference of the modem. The
narrow loop essentially ‘cleans up’ the external signal. This is particularly important
if the modem is being used to supply a 10MHz reference to a BUC or LNB.
Edit the configuration and value of the frequency reference. The value is changed using
the STarrow keys. The user should then press ENT. Values of Internal 10 MHz,
External 01 MHz, External 02 MHz, External 05 MHz, External 10 MHz, External
20 MHz, Out Int. 10 MHz, and Auto are possible.
The user should then press ENT. Two examples are shown below:
Frequency Reference:
Internal 10 MHz (▲ ▼, ENT)
Frequency Reference:
External 05 MHz (▲ ▼, ENT)
5.6.1.8 (ConfigMask) - MASK
Select Transmit, Receive or Reference, using the ◄ ► arrow keys, then press ENT.
If Transmit is selected the following sub-menu will be displayed:
Tx Alarm Mask: Tx
IFO
G.703-BPV Tx-AIS (◄ ► ENT)
Select Tx-FIFO, G.703-BPV, or Tx-AIS, using the ◄ ► arrow keys, then press ENT.
For each of the choices a sub-menu similar to the one shown below will be shown:
Tx-FIFO Alarm:
Active Masked (◄ ► ENT)
Select Active or Masked, using the ◄ ► arrow keys, then press ENT.
If the user selects Active, then a Transmit Traffic fault will be generated whenever the
transmitter sees that the transmit FIFO has slipped.
Similarly, the user can mask a G.703 BPV or Transmit AIS alarm.
If the user selects Masked, no alarm will be generated.
If Receive is selected the following sub-menu will be displayed:
Rx Alarm Mask: AGC Eb/No
Rx-AIS Buffer (◄ ► ENT)
Select AGC, Eb/No, Rx-AIS or Buffer, using the ◄ ► arrow keys, then press ENT. For
each of the choices a sub-menu similar to the one shown below will be shown:
AGC Alarm:
Active Masked (◄ ► ENT)
Select Active or Masked, using the ◄ ► arrow keys, then press ENT.
If the user selects Active, then a Receive Traffic fault will be generated whenever the
demodulator sees that the composite input level being applied will cause compression in
the IF stages, and hence degrade the performance of the demodulator.
Similarly, the user can mask an Eb/No, Receive AIS or Buffer alarm.
If the user selects Masked, no alarm will be generated.
5–43
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
If Reference is selected the following sub-menu will be displayed:
Reference Alarm:
Active Masked (◄ ► ENT)
Select Active or Masked, using the ◄ ► arrow keys, then press ENT.
If the user selects Active, then a unit fault will be generated whenever the unit sees:
1. External Reference is selected
2. There is no signal activity at the external reference port
If the user selects Masked, no alarm will be generated.
If BUC is selected the following sub-menu will be displayed:
BUC Alarm:
Active Masked (◄ ► ENT)
Select Active or Masked, using the ◄ ► arrow keys, then press ENT.
If LNB is selected the following sub-menu will be displayed:
LNB Alarm:
Active Masked (◄ ► ENT)
Select Active or Masked, using the ◄ ► arrow keys, then press ENT.
5–44
CDM-Qx Satellite Modem Revision 5
-
P
Front Panel Operation MN/CDMQx.IOM
5.6.1.9 (ConfigODU) – OUTDOOR UNIT (for L-Band Unit Only)
ODU (Outdoor Unit):
BUC LNB (◄ ► ENT)
The ODU (Outdoor Unit) menu permits the user to choose between controlling and
monitoring either a BUC (Block Upconverter) or an LNB (Low-noise Block
downconverter). Select BUC or LNB, using the ◄ ► arrow keys, then press ENT.
(ConfigODUBUC) – BLOCK UPCONVERTER (BUC)
If BUC is selected, the following sub-menu is displayed:
BUC:M&C-FSK DC
wr 10MHz
Alarm Delay LO Mix(◄ ► ENT)
Select M&C-FSK, DC-Pwr, 10MHz, Alarm, Delay, LO, or Mix, using the ◄ ► arrow
keys, then press ENT.
M&C-FSK
DC-Pwr (DC POWER) If a BUC supply is installed this menu permits the
10MHz
Alarm
Delay
LO
Mix
If an FSK-capable BUC is employed, this menu provides access to
a further set of menus that define the FSK setup, and use it for
control and monitor.
user to turn DC power ON or OFF.
This menu permits the user to turn the 10MHz frequency reference
for the BUC ON or OFF.
This menu permits the user to define the upper and lower limits for
a current ‘window’. If the measured BUC current falls outside this
window, an alarm is generated.
This menu permits the user to define the carrier-on delay following
a power-up sequence.
This menu permits the user to define the LO frequency used in the
BUC. This is then used in the display of RF frequency in the
ConfigTxFreq menu.
This menu permits the user to define the sense of the frequency
translation – either high-side mix or low-side mix.
5–45
CDM-Qx Satellite Modem Revision 5
Front Panel Operation MN/CDMQx.IOM
(ConfigODUBUCM&C-FSK) - M&C FSK
If M&C-FSK is selected, the following sub-menu is displayed:
BUC M&C-FSK: Comms Address
Tx-On/Off (◄ ►, ENT)
Select Comms, Address, Tx-On/Off, or Pwr-Level, using the ◄ ► arrow keys, then
press ENT.
Comms
Address
TX-On/Off
If an FSK-capable BUC is employed, this menu turns the FSK
between the modem and BUC either ON or OFF.
(Address) This menu permits the user to enter the logical
address of the BUC, from 1 to 15.
This menu permits the user to turn the RF Output of the BUC
ON or OFF.
(ConfigODUBUCM&C-FSKAddress) – FSK COMMS
If Comms is selected, the following sub-menu is displayed:
BUC M&C FSK Comms:
On Off (◄ ►, ENT)
Select On or Off, using the ◄ ► arrow keys, then press ENT.
(ConfigODUBUCM&C-FSKAddress) – FSK ADDRESS
If Addr is selected, the following sub-menu is displayed:
BUC FSK Address: 01
(▲▼, ENT)
Edit the value of the address using the ▲ ▼ arrow keys, then press ENT. The valid range
is from 01 to 15.
5–46
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.