Read the operating instructions prior to
commissioning
Installation instructions
Combisteamer
UnitModelType of energyDevice type
FlexiCombi Classic6.15, 6.21, 10.15, 10.21GasCountertop unit
20.15, 20.21Floor-standing unit
Translation from the original document • 10014471-0AIDE-A • 08/01/2016
10014471-0AIBE-Aen-GB
Manufacturer
MKN Maschinenfabrik Kurt Neubauer GmbH & Co. KG
Halberstädter Straße 2a
38300 Wolfenbüttel, Germany
Telephone +49 53 31 / 89-0
Fax +49 53 31 / 89-280
Copyright
All rights to text, graphics and pictures in this documentation are held by MKN Maschinenfabrik Kurt
Neubauer GmbH & Co. KG. Distribution or duplication is only permitted with the prior written consent
of MKN.
Copyright by MKN Maschinenfabrik Kurt Neubauer GmbH & Co. KG.
6.10.1Checking the exhaust gas routing for leaks .......................................... 61
6.10.2Checking the monitoring of the exhaust gas routing ............................. 61
6.10.3Checking the ignition behaviour ............................................................ 62
6.10.4Checking the flame pattern ................................................................... 62
6.10.5Checking the flame monitoring.............................................................. 63
6.10.6Checking the controls............................................................................ 64
6.10.7Checking the monitoring of the cooking zone door ............................... 64
7Putting the unit into service ............................................ 65
7.1Filling out the commissioning report ........................................... 65
10014471-0AIBE-A
4Installation instructions
1 Introduction
1.1 About this manual
Introduction
The instruction manual is part of the unit and contains information on
safe installation of the unit.
Observe and adhere to the following instructions:
•Read the instruction manual in its entirety prior to installation.
•Make the instruction manual available to the installer at the
operating site at all times.
•Preserve the installation manual throughout the service life of the
unit.
•Insert any supplements from the manufacturer.
•Pass on the installation manual to any subsequent operator of the
unit.
Target group The target group for the installation manual is trained technical
personnel that is familiar with installing and operating the unit.
Figures All figures in this manual are intended as examples. Discrepancies
between these and the actual unit can arise.
10014471-0AIBE-A
5Installation instructions
Introduction
1.1.1 Explanation of signs
DANGER
Imminent threat of danger
Failure to comply will lead to death or very severe injuries.
WARNING
Possible threat of danger
Failure to comply can lead to death or very severe injuries.
CAUTION
Dangerous situation
Failure to comply can cause minor or moderate injuries.
ATTENTION
Material damage
Failure to comply can cause material damage.
Notes for better understanding and operation of the unit.
Symbol / signMeaning
•Listing of information.
Action steps, which can be performed
in any sequence.
1.
2.
Action steps, which must be performed
in the prescribed sequence.
Result of a listed action.
6Installation instructions
10014471-0AIBE-A
1.2 Use of the unit
1.3 Warranty
Introduction
This unit is intended to be used solely for commercial purposes,
particularly in commercial kitchens.
This unit is not intended for the US and Canadian markets. It is not
permitted to be used there.
The warranty is void and safety is no longer assured in the event of:
•Modifications or technical changes to the unit,
•Improper use,
•Incorrect startup, operation or maintenance of the unit,
•Problems resulting from failure to observe these instructions.
10014471-0AIBE-A
7Installation instructions
Safety information
2 Safety information
Ensuring conformity with
standards
Improper installation Risk of property damage and personal injury from improper
Transportation and storage Risk of personal injury and property damage from improper
Observe applicable international, European and national laws,
regulations, standards and directives for the unit when transporting,
setting up and connecting it.
installation
•Install the unit only as specified in these installation instructions.
•Do not add anything to the unit or modify the unit.
•Use only original spare parts.
transportation and improper storage.
•Store the unit in a dry, frost-free environment.
•Observe the safety regulations for the lifting gear used.
•Attach the unit to the lifting gear securely during transport and
setup, and prevent it from dropping.
•Transport the unit in an upright position, do not tilt or stack.
•Pay attention to protruding parts when transporting the unit
without packaging.
Fire prevention Risk of fire from combustible surfaces
•Observe general fire prevention regulations.
•When setting up the unit in close proximity to heat-sensitive
substances or substances that pose a risk of fire, observe fire
prevention regulations.
•The room's ceiling above the unit must be non-combustible.
Risk of fire from objects
•Do not obstruct the exhaust gas duct.
Organisational measures Risk of property damage and personal injury from lack of
organizational measures
•Identify hazard areas when transporting, setting up and
connecting the unit.
•Prior to starting the installation work, notify any operators present
about the procedure.
•Prior to starting the installation work, discuss how to behave in an
emergency.
•Use equipment and protective gear suitable for the activity.
•Brace housing components to prevent them from falling over and
dropping.
8Installation instructions
10014471-0AIBE-A
Setup Risk of property damage and personal injury from improper
setup
•Ensure that the installation area has adequate load-bearing
capacity.
•Wear safety shoes and protective gloves.
Electrical connection Risk of fire from improper connection
•Observe applicable regional regulations of the electrical utility.
•Ensure that only licensed electricians connect the unit.
•Ensure that the electrical system is earthed by a protective
earthing conductor.
•Note the information on the nameplate.
Risk of electric shock from live components.
•Prior to working on the electrical system, switch off the unit,
disconnect the electrical system from the mains and prevent
power from being switched on again. Check to ensure absence of
voltage.
Safety information
•Use only insulated tools.
Gas connection Risk of explosion and fire from improper connection
•Observe applicable regional regulations of the gas utility.
•Ensure that only a licensed tradesman connects the unit to the
gas supply.
•Prior to working on the gas system, switch off the unit, close the
gas supply from the gas system and secure it against being
reopened. When bleeding air or degassing, ensure that the air and
gas are discharged to the outside in a technically correct manner
and without creating a risk.
•Observe the information on the nameplate and
Gas type
supplemental label.
•Check for leaks.
•When working on the gas system and units in buildings, ensure
that a hazardous gas-air mixture cannot form in the rooms.
Risk of poisoning from exhaust gases
•Ensure that exhaust gases are discharged properly and that the
necessary amount of combustion air is supplied.
10014471-0AIBE-A
•Ensure that a maximum CO value of < 0.1 vol. % or < 1000 ppm is
achieved in undiluted exhaust gas.
Risk of fire from combustion gases and hot surfaces
•Maintain an adequate distance from grease filters on ventilation
systems.
9Installation instructions
Safety information
Additional connection work Risk of physical damage and personal injury from improper
connection
•Prior to working on the unit, switch off the unit, disconnect the unit
from the mains and prevent power from being switched on again.
Check to ensure absence of voltage.
•Prior to working on the unit, switch off the unit, close the gas
supply and secure it against being reopened.
•Route connection lines such that they cannot be damaged from
heat.
Commissioning Risk of property damage and personal injury from improper
commissioning
•Read the operating instructions prior to commissioning. Observe
the safety instructions in this installation manual and in the "Safety
information" chapter of the operating instructions.
•Put the unit into service only after a successful function test
following assembly.
•Put the unit into service only after it has reached room
temperature.
•Observe the units during operation.
10Installation instructions
10014471-0AIBE-A
3 Description of the unit
a
b
c
d
e
f
g
h
i
j
k
l
m
n
3.1 Overview of the unit
Description of the unit
Image: Gas-FlexiCombi Classic, unit size 10
a Cooking zone doorh Wastewater connection
b Door handlei Opening for power connection
c Operating elementsj Gas connection on unit
10014471-0AIBE-A
d Hand showerk Potential equalisation connection
e Equipment leg, vertically ad-
justable
f Hard water connectionm Waste gas connection
g Soft water connectionn Air intake connection fitting
l Steam outlet connection fitting
11Installation instructions
Description of the unit
a
b
c
d
e
f
g
h
i
j
k
l
m
n
o
Image: Gas-FlexiCombi Classic, size 20
a Cooking zone doori Opening for power connection
b Door handlej Gas connection on unit
c Operating elementsk Potential equalisation connection
d Hand showerl Air intake connection fitting
e Equipment leg, vertically ad-
justable
f Hard water connectionn Steam outlet connection fitting
g Soft water connectiono Waste gas connection, upper fan-as-
h Wastewater connection
m Waste gas connection, burner 2
sisted gas burner
12Installation instructions
10014471-0AIBE-A
3.2 Planning drawing
f
ba
c
d
e
h
g
a
h
b
c
d
e
Description of the unit
Image: Unit sizes 6 and 10
10014471-0AIBE-A
Image: Unit size 20
Unit sizeabcdefgh
6.15, 6.2150102050507997908501640
10.15, 10.21501020505079910605801640
20.15, 20.215010755050813------1960
a-h= mm
13Installation instructions
Description of the unit
3.3 Equipment and connection data
Unit size
6.156.2110.1510.2120.1520.21
Dimensions
Unpacked unit
Length x width x height (cm)
Packaged unit
Length x width x height (cm)
Weight
Unpacked unit (kg)137142167187355355
Packaged unit (kg)170170195195375375
Heat output
Latent (W)2200340036005200720010400
Sensible (W)170026002700390054007800
Noise level (db(A))< 70
Ambient climate5 – 40 °C, 95 % relative humidity, non-condensing
Power connection
Type of connection1NPE 220–240V AC 50/60Hz
Protection classIPX5
Connected load (kW)0.61.0
102 x 80 x79102 x 80 x79102 x 80 x
106
96 x 108 x
102
2PE 220–240 V AC 50/60 Hz
1NPE 100 V AC 50/60 Hz
96 x 108 x
102
96 x 108 x
128
102 x 80 x
106
96 x 108 x
128
108 x 82 x
196
96 x 116 x
220
108 x 82 x
196
96 x 116 x
220
Recommended fuse (A)16
Soft water connection
Carbonate hardness CaCO
(mmol/l)
Chloride Cl (mg/l)< 50
Iron Fe (mg/l)< 0.1
Connection pressure (hPa),
(bar)
Connection (inches)R 3/4, male thread
Hard water connection
Carbonate hardness CaCO
(mmol/l)
Connection pressure (hPa),
(bar)
Connection (inches)R 3/4, male thread
Wastewater connection
Discharge temperature (°C)< 80
Connection (mm)Connection fitting, 50 mm diameter
Gas connection
3
3
< 0.9
200 – 600, 2 – 6
< 4
200 – 600, 2 – 6
14Installation instructions
10014471-0AIBE-A
Description of the unit
Unit size
6.156.2110.1510.2120.1520.21
Rated heat input (kW)111718263652
Gas typeThe gas type for which the unit is set is indicated on the gas type supplemental label.
Gas connection (inches)R 3/4, male thread EN 10226-1
Connection pressure (mbar)
20
Natural gas 2H, 2E, 2L, 2LL **
Connection pressure (mbar)
50
Liquefied gas 3B/P, 3P **
Natural gas E/H, G20 (m3/h)*1.141.761.872.703.745.40
Natural gas LL/L, G25 (m3/h)*1.332.052.173.144.356.28
Natural gas 13A, G21 (kcal/h)95001460015500224003100044700
Liquefied gas B, G30 (kg/h)0.871.341.422.052.844.10
Liquefied gas P G31 (kg/h)0.851.321.402.022.804.04
LP gas B/P G30/G31 (kg/h)0.871.341.422.052.844.10
Combustion air (m3/h)*15.022.522.532.545.065.0
Supply air and exhaust gas routing
Required delivery pressure
B
(Pa)
13BS
Exhaust gas temperature B
13BS
0 – 5
170230195240205250
(°C)
Exhaust gas mass flow rate
B
(kg/h)
13BS
3047497199142
Primary air gap (cm)3 – 5
*) Information applies at 15 °C and 1013.25 mbar
**) Information is country-specific and applies in Germany; for further information, see "Checking the connection pressure"
10014471-0AIBE-A
15Installation instructions
Description of the unit
3.3.1 Connection pressure
Gas connection pressure
Gas typeConnection pressure (mbar)Connection pressure range (mbar)
Germany:
Natural gas 2H, 2E, 2L (LL)2017 (18) – 25
Liquefied gas 3B/P, 3P5042.5 – 57.5
Europe:
Natural gas 2E, 2H, (LL)2017 (18) – 25
Natural gas 2E+, (2L)20/25 (25)17 (20) – 30
Liquefied gas 3B/P, 3P5042.5 – 57.5
Liquefied gas 3B/P (3P)29 (30)25 – 35
Liquefied gas 3+ (3P)28 – 30/37 (37)20 (25) – 45
Liquefied gas 3B2920 – 35
Asia:
Natural gas13A2010 – 25
LP gas B/P2823 – 33
3.3.2 Speed of the fan-assisted gas burner
Unit sizeGas blower speed (rpm)
High output (HI)Low output (LO)
6.155050 *4800
6.2167004800
10.1550502800
10.2167002800
20.1550502800
20.2167002800
* In deviation from the table, for unit size 6.15 the gas blower speed at the described setting and upon verification of the
rated heat input is 5500rpm.
16Installation instructions
10014471-0AIBE-A
3.3.3 Exhaust gas values
Description of the unit
Gas
type
Natural
gas
Liquefied
gas, propane
Liquefied
gas, butane
* At low output (LO) 0.5 - 1.0 lower than at high output (HI)
** Adjustment aid, offset pressure applies only at low output (LO)
** Undiluted exhaust gas
OutputUnit sizeCO2 (vol. %) *p
RangeoptimalRangeoptimalRangeoptimal
HIAll units8.6 - 9.69.2------0 - 1000<100
LO6.1, 6.20.5 - 1.00.6-0.8 - 0-0.55
LO10.1, 10.2,
20.1, 20.2
HIAll units10.0 - 10.610.3------
LO6.1, 6.20.5 - 1.01.0-0.8 - 0-0.55
LO10.1, 10.2,
20.1, 20.2
HIAll units11.5 - 12.511.8------
LO6.1, 6.20.5 - 1.01.0-0.8 - 0-0.55
LO10.1, 10.2,
20.1, 20.2
0.5 - 1.00.6-0.4 - 0-0.15
0.5 - 1.01.0-0.4 - 0-0.15
0.5 - 1.01.0-0.4 - 0-0.15
3.3.4 Gas orifice diameter
(hPa) **CO (ppm) ***
offset
Unit sizeOrifice size (1/100 mm)
Natural gas E/H
G20
6.15650720N/A*470
6.21600680N/A*460
10.15565650N/A*420
10.21565630N/A*420
20.15565650N/A*420
20.21565630N/A*420
*) For information on manually setting the rated heat input, see "Adjusting the basic gas setting".
Natural gas LL/L
G25
Natural gas13A
G21
Liquefied gas B/P
G30/G31
10014471-0AIBE-A
17Installation instructions
Description of the unit
HI
G1F1
CO2
85°C
CO2
2800
HI
G0F0
CO2
HI
G1F0
CO2
HI
G1F1
CO2
Err
CO2
71
Err
CO2
72
Err
CO2
73
3.3.5 Status messages
Burner operation
DisplayMeaning
HI = High output
CO2 = CO2 measurement
G1 = Gas supply open (gas solenoid valve open)
F1 = Flame present (burner on)
85°C = Current cooking zone temperature
CO2 = CO2 measurement
2800 = Gas blower speed (rpm)
Burner status messages
DisplayMeaning
G0 = Gas supply closed (gas solenoid valve closed)
F0 = No flame (burner off)
G1 = Gas supply open (gas solenoid valve open)
F0 = No flame (burner off)
G1 = Gas supply open (gas solenoid valve open)
F1 = Flame present (burner on)
Burner error messages
DisplayMeaningPossible causeRemedy
Err = ErrorGas valve closed.
CO2 = CO2 measurement
71 = No gas
Err = ErrorPower supply inter-
CO2 = CO2 measurement
72 = Blower not running
Err = ErrorWrong gas qualityContact customer service
CO2 = CO2 measurement
73 = General gas error
Air in the gas line.
rupted. Error in the
control electronics.
Open the gas valve and
repeat ignition.
Contact customer service
18Installation instructions
10014471-0AIBE-A
4 Transporting the unit
4.1 Transport information
Image: Crossing a grate with the tray trolley
Prior to transporting the unit to the installation site, ensure that:
•The route has adequate load-bearing capacity; place rails or metal
plates underneath if necessary.
•Wall openings are large enough. Removing the packaging
reduces the clear width required (see "Equipment and connection
data").
Transporting the unit
“
4.2 Transporting to the installation site
CAUTION
Risk of property damage and personnel injury from tipping
equipment
•Do not linger next to or behind raised equipment.
•Move raised equipment carefully.
ATTENTION
Risk of physical damage from improper transport
•Transport the unit upright.
•Do not tilt or stack the unit.
•Pay attention to protruding parts when transporting the
unpacked unit.
10014471-0AIBE-A
19Installation instructions
Transporting the unit
4.2.1 Transporting on a pallet
1. Move the pallet truck under the pallet.
2. Raise the unit on the pallet.
Image: Transporting the unit on a pallet
3. Move the unit to the installation site.
4.2.2 Transporting without a pallet
ATTENTION
Risk of physical damage from improper lifting of the unit
•Lift size 6 and size 10 units only with the aid of wooden
beams placed underneath.
Unit sizes 6 and 10
Requirement Packaging removed except for the pallet
1. Move the pallet truck under the unit from the right.
2. Place the wooden beams on the lift forks and slide under the unit.
3. Lift the unit off the pallet.
20Installation instructions
10014471-0AIBE-A
Image: Transporting unit sizes 6 and 10 without a pallet
4. Move the unit to the installation site.
Unit size 20
Transporting the unit
Requirement Packaging removed except for the pallet
1. Move the pallet truck under the guide rails of the unit from the
right.
2. Lift the unit off the pallet.
Image: Transporting unit size 20 without a pallet
10014471-0AIBE-A
3. Move the unit to the installation site.
21Installation instructions
Transporting the unit
4.2.3 Transporting by raising and lowering
DANGER
Risk of fatal injury from falling unit
•Do not linger under a suspended load.
•Cordon off hazard area in compliance with regulations.
ATTENTION
Risk of physical damage from tightened lifting straps
•Always lift the unit with lifting straps and a spreader bar.
1. Guide the lifting straps under the pallet and attach them to the
spreader bar.
2. Brace the unit to prevent tipping.
3. Carefully lift the unit onto the pallet.
4.3 Unpacking the unit
CAUTION
Risk of injury from sharp edges
•Wear protective gloves.
When unpacking the unit, inspect it for transport damage. Do
not install damaged units or put into service. Enter the
information from the nameplate into the commissioning report.
1. Remove the packaging.
2. Pull the protective film off the unit.
3. Remove the packaging material from the cooking zone
completely.
4. Lift the unit off the pallet and place in position.
5. Clean the unit (see "Cleaning and maintaining the unit").
6. Separate and dispose of the packaging material.
22Installation instructions
10014471-0AIBE-A
5 Setting up the unit
The supply air and exhaust gas openings in the unit must not be
obstructed or closed.
WARNING
Risk of burns from spraying hot fat
•Set up deep fat fryers outside the range of the hand shower.
CAUTION
Risk of crushing from improper setup
•Protect the unit and work area during setup and alignment.
CAUTION
Risk of fire from failure to observe applicable regional fire
prevention regulations
•Observe applicable regional fire prevention regulations.
Setting up the unit
ATTENTION
Risk of physical damage from overheating of the unit
•Do not set up the unit close to heat sources.
5.1 Lifting the unit off the pallet
CAUTION
Risk of property damage and personnel injury from tipping
equipment
•Do not linger next to or behind raised equipment.
•Move raised equipment carefully.
ATTENTION
Risk of physical damage from lifting the unit incorrectly
•Place the forks of the lift truck next to the waste trap.
10014471-0AIBE-A
23Installation instructions
Setting up the unit
Requirement Unit unpacked
Protective film removed
Unit cleaned
Image: Lifting the unit off the pallet
1. Slide the forks of the pallet truck under the unit and to the right of
the waste trap.
2. Lift the unit off the pallet.
5.2 Placing the unit on the equipment legs
Requirement The floor must carry the weight of the unit
1. Lift the unit with the pallet truck.
2. Move the unit to the installation site.
3. Place the unit on the floor.
4. Set up the unit in accordance with the planning drawing Planning
drawing .
24Installation instructions
10014471-0AIBE-A
5.3 Setting up the unit on a work surface
ab
d
c
e
f
Requirement The base frame must carry the weight of the unit
Base frame levelled
Base frame set up in accordance with the planning drawing Planning
drawing
1. Lift the unit.
Setting up the unit
Image: Setting up the unit on a work surface
a Lift forkd Stud bolt
b Waste trap on the unite Equipment leg
c Base framef Unit
2. Place the unit over the stud bolts on the work surface.
CAUTION
Risk of burns from missing stickers
•Attach stickers if the upper insertion rails are higher than
4. Attach the sticker to the cooking zone door at a height of 1.6 m.
5.4 Aligning the unit
5.4.1 Aligning countertop units
Requirement Base frame levelled
1. Place a spirit level on the unit.
2. Screw the equipment legs in or out to level the unit.
5.4.2 Aligning floor-standing units
The tray trolley is needed to align a floor-standing unit.
Prepare the tray trolley.
ATTENTION
Risk of water discharge from leaking cooking zone
The cooking zone will leak if the tray trolley is not aligned.
•Operate a floor-standing unit only with the tray trolley.
•Align the tray trolley carefully.
1. Screw the equipment legs in or out to align the unit.
2. Open the cooking zone door.
26Installation instructions
10014471-0AIBE-A
Setting up the unit
a
c
b
d
e
Image: Aligning the unit with the tray trolley
a Tray trolleyd Equipment leg
b Distance between roller and sup-
port rail
c Support rail
e Roller
3. Place the tray trolley against the support rails.
4. Screw the equipment legs in or out until the rollers are 1 to 5 mm
above the support rails.
5. Retract the tray trolley.
6. Level the support rails.
7. Push the tray trolley against the unit until it stops.
8. Remove the push handle.
9. Close the cooking zone door.
The unit is aligned correctly.
10014471-0AIBE-A
27Installation instructions
Setting up the unit
50
500 - 800
500
a
bc
5.5 Maintaining minimum clearances
Image: FlexiCombi minimum clearances
a Ceilingc Deep-fat fryer
b Baking oven
The following clearances from walls, ceilings or other equipment must
be provided when setting up the unit:
•Left, right and behind: at least 50 mm.
•For service work, 500 mm at left recommended.
•For parking the tray trolley, 800 mm at left.
•From heat sources (baking ovens), 500 mm at the left so that the
cooling air for the unit is not heated.
•Distance to deep-fat fryers, left and right, at least one length of the
hand shower so that no water can be sprayed into the hot deep-fat
fryer.
•To ceilings, at least 500 mm. There must be no water, gas or
electric lines in the ceiling above the unit.
28Installation instructions
10014471-0AIBE-A
6 Connecting the unit
6.1 Opening and closing the housing
DANGER
Risk of personal injury and physical damage from electric
shock
•Prior to working on the unit, ensure that the unit has been
disconnected from the mains.
•Do not operate the unit with the housing open.
CAUTION
Risk of injury from sharp edges
•Wear protective gloves.
ATTENTION
Risk of physical damage from damage to the lines
Connecting the unit
•Remove and attach housing components carefully.
6.1.1 Removing and attaching the side panel
Removing the side panel
1. Unscrew the bolts on the bottom of the side panel.
2. Pull the bottom of the side panel forward.
Image: Removing and attaching the side panel
10014471-0AIBE-A
3. Remove the side panel.
29Installation instructions
Connecting the unit
Attaching the side panel
ATTENTION
Risk of physical damage from squeezing the lines
When attaching the side panel, make sure that no lines are
squeezed.
1. Insert the top edge of the side panel.
ATTENTION
Risk of physical damage from a loose side panel
•Check seals when attaching the housing parts
•Replace damaged seals
•The side wall must be in contact with the unit on all sides.
2. Carefully push the bottom of the side panel inward.
3. Secure the bottom of the side panel with bolts.
4. Check that the side panel is in contact with the unit on all sides.
6.2 Checking the supply air and exhaust gas routing
Routing of the supply air and exhaust gas must comply with the
national and regional laws, regulations, standards and directives.
6.2.1 Description of the supply air and exhaust gas routing
WARNING
Risk of poisoning from exhaust gases
•Ensure that exhaust gases are routed to the outside.
•Install the unit below or at ventilation systems.
•For type B devices: Connect unit to ventilation system or
chimney.
•Ensure that the unit can be operated only when the
ventilation system is switched on.
WARNING
Risk of burns and fire from the high temperature of the
exhaust gas
The temperature of the exhaust gas can be up to 400 °C.
•Do not touch the exhaust gas opening or its cover.
•Do not place any objects in close proximity to the exhaust
gas opening or on the unit.
Installation room requirements
•An adequate supply air from outside joints and openings to the
outside or an HVAC system is assured.
•Routing of exhaust gas to the outside is assured.
30Installation instructions
10014471-0AIBE-A
Connecting the unit
c
b
b
d
c
e
a
f
3
13BS
B
A
a
e
b
c
d
B
13BS
•Routing of the supply air and exhaust gas must not impair proper
operation (for example by underpressure).
•A safety device must ensure that gas can be supplied only when
the ventilation system is switched on.
•How the exhaust gas is routed depends on the unit type:
–Type A unit: Indirect routing of exhaust gas via ventilation
systems such as a ventilated ceiling or ventilation hood.
–Type B units: Direct routing of exhaust gas via ventilation
system or chimney.
Image: Indirect exhaust gas routing
a Ventilation hoodd Flow control
b Steam outlet connection fittinge Exhaust gas duct
c Waste gas connectionf Ventilated ceiling
Image: Direct exhaust gas routing
a Ventilation system or chimneyd Waste gas connection
b Exhaust gas ducte Steam outlet connection
c Flow control
10014471-0AIBE-A
1. Ensure that all conditions in this section are satisfied.
31Installation instructions
Connecting the unit
2. Ensure that the supply air and exhaust gas routing is
unobstructed.
3. Ensure that supply air and exhaust gas routing functions properly.
4. Fill out the commissioning report.
6.3 Making the electrical connection
6.3.1 Notes regarding the electrical connection
Installation work Electrical installation work must be performed by a licensed
electrician. Comply with the local regulations of the electric utility.
The unit must be connected on the basis of the information on the
nameplate and this manual.
Electric power cable An electric power cable of the type HO7RN-F must be used to
connect the unit to the electric mains.
Residual-current protective
device
The unit can be connected to a residual-current protective device.
The residual-current protective device must incorporate a residualcurrent protective switch of type B (RCD Type B) in order to detect
AC fault currents, pulsating DC currents and continuous DC currents.
Image: RCD switch type B circuit symbol
The unit generates a small fault current through use of special
electronic components. To ensure that the residual current device
does not trip during normal operation, each unit must have its own
residual current device.
Equipotential bonding The unit must be incorporated into the potential equalisation circuit
through use of the specified minimum wire sizes.
Permanent connection
CAUTION
Risk of property damage and personal injury from improper
installation
•In the case of a permanent electrical connection, install an
all-phase disconnect switch before the unit.
Install an all-phase disconnect switch if the unit will be connected
permanently to the electric mains.
32Installation instructions
10014471-0AIBE-A
Plug-in connection
a
b
c
d
CAUTION
Risk of property damage and personal injury from improper
installation
•The plug-in connection must be readily accessible.
If the unit will be connected to the electric mains by a plug, use a plug
and socket that comply with IEC 60309. The socket must be readily
accessible so that the unit can be disconnected from the electric
mains at any time.
6.3.2 Connecting the electric power cable to the unit
Connecting the unit
Image: Connecting the electric power cable
a Connection terminalsc Electric power cable
b Cable tied Cable gland
Length of connection cable in the unit
10014471-0AIBE-A
ModelLength (mm)
6.15, 6.211000
10.15, 10.211200
20.15, 20.21720
33Installation instructions
Connecting the unit
PE
N
L1X1N
Requirement Electrical connection to the unit matches the information on the
Image: Gas Combisteamer terminal assignment
L1 PhasesPE Protective earth
N Neutral conductorX1 Mains connection
nameplate
Housing open
Electric power cable sufficiently long
1. Insert the electric power cable into the unit through the cable
gland.
2. Connect the electric power cable in accordance with the terminal
diagram.
3. Secure the electric power cable to the unit with cable ties.
4. Tighten the cable gland securely to provide strain relief.
6.3.3 Connecting to the potential equalisation circuit
Image: Potential equalisation connection
1. Connect the potential equalisation line to the location on the unit
identified with the corresponding symbol.
2. Fill out the commissioning report.
34Installation instructions
10014471-0AIBE-A
6.4 Making the basic control settings
START
STOP
STEP
Clean
Programs
_
+
ClimaSelect
a
b
d
c
f
e
g
h
i
j
k
l
By entering the password "2100", the basic settings for the installation
can be displayed and changed.
6.4.1 Opening the Setting menu
Connecting the unit
Image: FlexiCombi Classic control panel
a
On Off
b
Select
knobh "STEP" button
c Center displayi Left knob
d Right displayj Left display
e Right knobk Indicator light
f
Ready2cook
Requirement The unit is on
1. Turn the
The indicator light illuminates.
The left display shows "PASS".
The right display flashes "0000".
2. Use the right not to set the password.
The right display shows the set password.
3. Press the "START STOP" button.
The left display flashes "HAC".
4. Use the left knob to select OPt.
The left display flashes "OPt".
The basic settings can be changed.
buttong "START STOP" button
button
Select
knob to the
Settings
symbol.
10014471-0AIBE-A
35Installation instructions
Connecting the unit
6.4.2 Changing the basic control settings
1. Press the "START STOP" button.
The left display flashes the first number of the basic setting;
refer to the of basic settings table.
The centre display shows "OPt".
The right display shows the first set value.
2. Turn the left knob.
Set number.
3. Press the "START STOP" button.
The basic setting can be adapted.
4. Turn the right knob.
Set new value.
5. Press the "START STOP" button.
Accept changes.
6. Press and hold the "STEP" button for 3 seconds.
The changes are saved.
The left display flashes "OPt".
The centre display shows "Stor".
7. Press the "STEP" button to leave the Settings menu.
Parameter
no.
1Temperature unit
2Setup height00 = 0 - 999 m
4Ready2Cook pre-
5Exhaust hood run
33Audible signal
DescriptionStandard valueInput range
00 = °C
setting
15 %0 - 30 %
heating temperature
60 s0 - 600 s
time extension
00 = quiet
volume
1 = °F
1 = 1000 - 1999 m
2 = 2000 - 2499 m
3 = 2500 m or higher
1 = loud
37Hold time after
reaching the
Ready2Cook-temperature
6.5 Making the water connection
Installation work involving drinking water must be performed by an
authorised plumbing contractor. Observe applicable regional
regulations with regard to drinking water installations and connection
data (see "Equipment and connection data").
36Installation instructions
240 min0 - 600 min
10014471-0AIBE-A
6.5.1 Connecting hard and soft water
a
b
c
d
e
g
f
h
The unit is equipped with a connection for:
•Soft water for generating steam
•Hard water for cooling, rinsing and WaveClean
CAUTION
Hygiene risk from contaminated drinking water
•The connection to the drinking water supply must be
equipped with a backflow preventer.
Always connect both water connections to the unit.
ATTENTION
Risk of physical damage from the wrong water quality
•Ensure that the water quality complies with the equipment
and connection data.
Connecting the unit
Image: Hard and soft water connection
a Soft water tape Hard water connection
b Backflow preventer, installedf Hard water hose
c Hose, soft waterg Backflow preventer, installed
d Soft water connectionh Hard water tap
Requirement Water quality meets specifications
Backflow preventers installed
Required water pressure available
Pressure-resistant hoses suitable for drinking water available
1. Connect the hoses to the water taps.
10014471-0AIBE-A
2. Open the water taps and flush the hoses.
3. Insert a dirt filter into the hard and soft water connections.
4. Connect hoses to the unit.
5. Open the water taps and check the threaded fittings for leaks.
37Installation instructions
Connecting the unit
a
b
c
de
f
g
h
6.5.2 Connecting soft water twice
If only a soft water connection is available at the installation site, the
hard water connection and the soft water connection must be
connected by means of a T-piece.
Image: Connect saltwater connection twice
a Soft water tape Hard water connection
b Backflow preventerf Dirt filter
c Hose, soft waterg T-piece
d Soft water connectionh Seal
Requirement Hose connected to soft water tap
1. Insert a dirt filter into the hard and soft water connections.
2. Connect the T-piece with seals.
3. Connect hose with seal to the T-piece.
4. Open the soft water tap and check the threaded fittings for leaks.
6.6 Making the wastewater connection
Installation work involving wastewater must be performed by an
authorised plumbing contractor. Observe the applicable regional
regulations of the sewage utility involved.
38Installation instructions
10014471-0AIBE-A
6.6.1 Identifying the cleaning system
a
b
c
d
e
c
b
a
f
FlexiCombi Classic units can be equipped with either an automatic or
manual cleaning system. The pictogram on the control panel shows
which cleaning system is installed.
Cleaning systemSewer system connection
Connecting the unit
Permanent connection, with on-site
waste trap:
Automatic cleaning system
Pictogram on control panel
Manual cleaning system
Pictogram on control panel
Install a vacuum breaker in the
wastewater line.
Unobstructed discharge with funnel
waste trap:
With an on-site waste trap, connect
only discharge funnel.
6.6.2 Connecting the wastewater line to a permanent connection
Image: Wastewater line permanent connection
a Wastewater connectiond Wastewater system trap
b Wastewater linee Pipe clamp
c Wastewater systemf Vacuum breaker valve
If a waste trap is installed in the wastewater system, a vacuum
breaker must be installed in the wastewater line.
Requirement Polypropylene (PP) pipes and elbows
•Heat-resistant to 95 °C
•Nominal diameter 50 mm
•Maximum pipe length 1.0 m
10014471-0AIBE-A
39Installation instructions
Connecting the unit
a
d
c
b
a
b
f
e
d
1. Install wastewater line up to connection to the sewer system
2. Secure the wastewater line with clamps.
3. Fill the waste trap on the unit with drinking water.
6.6.3 Connecting the wastewater line to the discharge funnel
Image: Connecting the wastewater line to the discharge funnel
.
a Wastewater connectiond Wastewater system
b Wastewater linee Wastewater system trap
c Funnel waste trapf Discharge funnel
Connect only the discharge funnel if a wastewater trap is
installed in the wastewater system.
Requirement Polypropylene (PP) pipes, elbows, discharge funnel and waste trap
•Heat-resistant to 95 °C.
•Nominal diameter 50 mm
•Maximum pipe length 1.0 m
1. Connect the discharge funnel with waste trap to the wastewater
system.
2. Connect the wastewater line to the unit and extend it to the
discharge funnel.
3. Secure the wastewater line with clamps.
4. Place the wastewater line discharge 2 cm above the discharge
funnel.
5. Fill water into the discharge funnel.
40Installation instructions
10014471-0AIBE-A
6.7 Connecting the gas
6.7.1 Notes about the gas connection
Gas installation work on the gas system and the unit may be
performed only by a licensed tradesman approved by the gas utility.
Observe the applicable regional regulations of the gas utility.
DANGER
Risk of fatal injury from operating the unit with the wrong
gas type
•Ensure that the gas type for which the unit is set (see gas
type supplemental label) matches the gas type available at
the site.
•Ensure that the unit is suitable for the available gas type (see
nameplate).
The unit is a Category II multi-gas unit and is intended for operation
with natural gas or liquefied gas (LPG).
Connecting the unit
The unit must be connected on the basis of the information on the
nameplate, gas type supplemental label and this manual.
The gas type for which the unit is set is indicated on the gas type
supplemental label.
The connection pressure and the category are indicated on the
nameplate. The gas types for which the unit is intended can be
identified from the category.
Before the gas connection line can be connected to the unit, the
following conditions must be satisfied:
•The gas type for which the unit is set must match the gas type
available at the site. If this is not the case, the unit must be
converted to the gas type available (see "Converting the gas
type"). Based on the category, check whether the unit is intended
for the gas type available.
•All parts of the gas system must be approved for use with gas.
•The gas shut-off valve for the unit must be readily accessible.
•The diameter of the gas connection line must not be smaller than
that of the connection on the unit.
Permanent connection The unit is intended for a permanent connection. The connection line
10014471-0AIBE-A
•The gas connection and the gas connection line must be
positioned such that they cannot be damaged by heat.
must be flexible. Route the flexible gas connection line or gas hose in
accordance with the manufacturers specification without being
stressed, kinked or twisted.
41Installation instructions
Connecting the unit
a
b
c
Shut-off device The unit or the gas connection line must be equipped with a thermally
activated shut-off. In strictly commercial buildings, a thermally
activated shut-off is not necessary if the objective of providing fire and
explosion safety is achieved by other means.
6.7.2 Description of the gas connection
Image: FlexiCombi gas connection
a Gas shut-off valvec Gas connection on unit
b Gas connection line
6.7.3 Connecting the gas connection line
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
ATTENTION
Risk of physical damage from improper gas connection
•Do not mix up gas connection with water connections.
•If the gas connection was mixed up with the water
connections, contact customer service.
Requirement Notes about the gas connection observed
Gas shut-off valve closed
Unit disconnected from power
Left side wall removed
42Installation instructions
1. Connect unit to the gas connection line.
10014471-0AIBE-A
Connecting the unit
ATTENTION
Risk of physical damage from excessively high pressure
•When opening the gas shut-off valve on the unit, ensure that
the pressure in the gas connection line is <150 mbar.
•If the pressure is >150 mbar, close the gas supply, reduce
the pressure in a technically correct manner and notify the
gas utility.
2. Open the gas shut-off valve on the unit, while paying attention to
the pressure in the gas connection line.
DANGER
Risk of explosion and fire from escaping gas
•When bleeding air from or degassing the gas system and the
unit, ensure that the air and gas are discharged to the
outside in a technically correct manner and without creating
a risk.
3. Bleed air from the gas system and unit in a technically correct
manner.
4. Check for leaks outside the unit.
WARNING
Risk of poisoning from exhaust gases
•Ensure that exhaust gases are discharged properly and that
the necessary amount of combustion air is supplied.
•Ensure that a maximum CO content of < 0.1 vol. % or < 1000
ppm is achieved in undiluted exhaust gas.
5. Switch on the unit.
6. Check the connection pressure (see "Checking the connection
pressure").
7. Check for leaks inside the unit (see "Checking for leaks").
8. Check the ignition behaviour (see "Checking the ignition
behaviour").
9. Check the flame pattern (see "Checking the flame pattern").
10.Check the basic gas setting (see "Checking the basic gas
setting").
11.Switch off the unit.
12.Close the housing (see "Opening and closing the housing").
13.Fill out the commissioning report.
10014471-0AIBE-A
43Installation instructions
Connecting the unit
6.7.4 Checking for leaks
Requirement Gas connection line connected
Left side wall removed
DANGER
Risk of explosion and fire from leaking, gas-conducting
parts
•Check the gas connection line and all gas-conducting parts
for leaks at the operating pressure.
•Use only bubble-forming agents and gas leak detectors
approved for use with gas.
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
ATTENTION
Risk of physical damage from electrical short-circuits
•Do not spray bubble-forming agents onto electrical
components and wires.
Gas leak detectors respond to almost all combustible gases,
even CO.
For this reason, ensure that the zero-point calibration of the gas
leak detector was performed in fresh air, free of combustible
gases. Observe the manufacturer's information.
Checking for leaks outside the unit
1. Open the gas shut-off valve.
2. Before putting the unit into service at operating pressure, check
the gas connection line and all gas-conducting parts outside the
unit for leaks with a bubble-forming agent or gas leak detector in
accordance with the Technical Regulations for Gas Installations.
3. Fill out the commissioning report.
Checking for leaks inside the unit
1. Switch on the unit.
2. Check the connection pressure.
3. Before putting the unit into service at operating pressure, check
the gas connection line and all gas-conducting parts inside the
unit for leaks with a bubble-forming agent or gas leak detector in
accordance with the Technical Regulations for Gas Installations.
4. Switch off the unit.
44Installation instructions
10014471-0AIBE-A
5. Fill out the commissioning report.
a
6.7.5 Checking the connection pressure
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
Requirement Gas connection line connected
Check for leaks outside the unit conducted
Measuring accuracy of the pressure measuring device at least 0.1
mbar
Left side wall removed
1. Close the gas shut-off valve on the unit.
2. Unscrew the sealing plug from the connection pressure measuring
point.
3. Connect the pressure measuring device.
Connecting the unit
10014471-0AIBE-A
Image: Measuring the connection pressure
a Sealing plug in the connection
pressure measuring point
ATTENTION
Risk of physical damage from excessively high pressure
•When opening the gas shut-off valve on the unit, ensure that
the pressure in the gas connection line is <150 mbar.
•If the pressure is >150 mbar, close the gas supply, reduce
the pressure in a technically correct manner and notify the
gas utility.
4. Open the gas shut-off valve on the unit, while paying attention to
the pressure in the gas connection line.
45Installation instructions
Connecting the unit
DANGER
Risk of explosion and fire from escaping gas
•When bleeding air from or degassing the gas system and the
unit, ensure that the air and gas are discharged to the
outside in a technically correct manner and without creating
a risk.
5. Bleed air from the gas system and unit in a technically correct
manner.
6. Switch on the unit.
7. Set the unit to high output (see "Checking the basic gas setting").
The unit operates at maximum output.
8. Measure the connection pressure.
DANGER
Risk of fatal injury from operating the unit at a connection
pressure outside the specified range
•Do not put the unit into service.
•Notify the gas utility.
9. Check whether the measured connection pressure is within the
specified range (see "Connection pressure").
10.Switch off the unit.
11.Close the gas shut-off valve on the unit.
12.Disconnect the pressure measuring device.
13.Tightly screw the sealing plug into the connection pressure
measuring point.
14.Open the gas shut-off valve on the unit.
15.Check the connection pressure measuring point for leaks.
16.Fill out the commissioning report.
6.7.6 Checking the basic gas setting
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
Requirement Gas connection line connected
Check for leaks outside the unit conducted
Connection pressure checked
Check for leaks inside the unit conducted
Left side wall removed
46Installation instructions
10014471-0AIBE-A
Checking the rated heat input
a
b
WARNING
Risk of poisoning from exhaust gases
•Ensure that exhaust gases are discharged properly and that
the necessary amount of combustion air is supplied.
•Ensure that a maximum CO content of < 0.1 vol. % or < 1000
ppm is achieved in undiluted exhaust gas.
Requirement Gas shut-off valve on the unit open
Connecting the unit
Image: FlexiCombi, unit size 20
a Burner 1b Burner 2
1. Switch on the unit.
2. Turn the
Select
knob to the Settings symbol.
The indicator light illuminates.
The left display shows "PASS".
The right display flashes "----".
3. Using the right knob, set "0999".
4. Press the "START STOP" button.
The left display flashes "CO2".
Press the "START STOP" button.
5. Using the left knob, set the burner to high output ("HI").
The left display flashes "HI".
The centre display shows "CO2".
6. Using the right knob, select the first burner "-1-" (only unit size 20).
The right display flashes "-1-".
7. Press the "START STOP" button.
The indicator light in the "START STOP" button flashes; the
burner starts.
10014471-0AIBE-A
The unit operates at maximum output.
47Installation instructions
Connecting the unit
a
b
d
c
8. Press the
Ready2Cook
button.
The left display shows the current temperature in the cooking
zone.
The centre display shows the selected burner "-1-" (only unit
size 20).
The right display shows the current status of the burner
("G1F1").
9. Press the
Ready2Cook
button.
The left display shows the current temperature in the cooking
zone.
The centre display shows the selected burner "-1-" (only unit
size 20).
The right display shows the burner's gas blower speed.
10.Check whether the displayed speed matches the unit size (see
"Speed of the fan-assisted gas burner").
If the displayed speed does not match the speed specified in
the table, contact customer service.
Image: Waste gas measurement – FlexiCombi Classic
a Exhaust gas measuring devicec Waste gas connection, burner 2
b Waste gas connection, burner 1d Exhaust gas connection
11.Measure the CO2 content of the exhaust gas at the exhaust gas
connection when the temperature in the cooking zone is between
130-180 °C.
12.Check whether the measured CO2 content is within the specified
range (see "Exhaust gas values").
If the CO2 content is not within the specified range, adjust the
basic gas setting (see "Adjusting the basic gas setting").
13.Press the
Ready2Cook
The left display flashes "HI".
The centre display shows "CO2".
48Installation instructions
(only unit size 20)
button.
10014471-0AIBE-A
Connecting the unit
14.Using the left knob, set the burner to low output ("LO").
The left display flashes "LO".
The centre display shows "CO2".
15.Using the right knob, select the first burner "-1-" (only unit size 20).
The right display flashes "-1-".
16.Press the "START STOP" button.
The indicator light in the "START STOP" button flashes; the
burner starts.
The unit operates at minimum output.
17.Press the
The left display shows the current temperature in the cooking
zone.
The centre display shows the selected burner "-1-" (only unit
size 20).
The right display shows the current status of the burner
("G1F1").
18.Press the
Ready2Cook
Ready2Cook
button.
button.
The left display shows the current temperature in the cooking
zone.
The centre display shows the selected burner "-1-" (only unit
size 20).
The right display shows the burner's gas blower speed.
19.Check whether the displayed speed matches the unit size (see
"Speed of the fan-assisted gas burner").
If the displayed speed does not match the speed specified in
the table, contact customer service.
20.Measure the CO2 content of the exhaust gas at the exhaust gas
connection when the temperature in the cooking zone is between
130-180 °C.
21.Check whether the measured CO2 content is within the specified
range (see "Exhaust gas values").
If the CO2 content is not within the specified range, adjust the
basic gas setting (see "Adjusting the basic gas setting").
22.Press the
Ready2Cook
button and conduct the measurements for
the second burner in the same way (only unit size 20).
23.To end the CO2 measurement, press the "START STOP" button.
The indicator light in the "START STOP" button goes out; the
burner is switched off.
24.Switch off the unit.
10014471-0AIBE-A
49Installation instructions
Connecting the unit
A
a
b
Requirement Left side wall removed
Checking the primary air quantity
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
Image: Primary air gap – FlexiCombi
a Burnerb Suction hose
1. Check whether the suction hose is routed without kinks in the
location and form shown in the figure.
2. Check whether the suction hose is damaged.
3. Check whether the opening in the suction hose is open and
unobstructed.
4. Measure the primary air gap (A).
5. Check whether the measured primary air gap is within the
specified range (see "Equipment and connection data").
If any one of the inspection criteria is not satisfied, adjust the
primary air gap (see "Checking the basic gas setting").
6. Check the flame pattern (see "Checking the flame pattern").
If the flame pattern is not OK, adjust the primary air gap (see
"Adjusting the basic gas setting").
7. Fill out the commissioning report.
50Installation instructions
10014471-0AIBE-A
Checking the exhaust gas values
a
b
d
c
WARNING
Risk of poisoning from exhaust gases
•Ensure that exhaust gases are discharged properly and that
the necessary amount of combustion air is supplied.
•Ensure that a maximum CO content of < 0.1 vol. % or < 1000
ppm is achieved in undiluted exhaust gas.
Requirement Left side wall removed
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
Connecting the unit
1. Switch on the unit.
2. Set the unit to high output (see "Checking the basic gas setting").
The unit operates at maximum output.
Image: Waste gas measurement – FlexiCombi Classic
a Exhaust gas measuring devicec Waste gas connection, burner 2
(only unit size 20)
b Waste gas connection, burner 1d Exhaust gas connection
10014471-0AIBE-A
3. Measure the CO content of the exhaust gas at the exhaust gas
connection when the temperature in the cooking zone is between
130-180 °C.
4. Check whether the measured CO content is within the specified
range (see "Exhaust gas values").
5. If the CO content is not within the specified range, adjust the basic
gas setting (see "Adjusting the basic gas setting").
6. Press the Ready2Cook button and conduct the measurements for
the second burner in the same way (only unit size 20).
7. To end the CO measurement, press the "START STOP" button.
51Installation instructions
Connecting the unit
8. The indicator light in the "START STOP" button goes out; the
burner is switched off.
9. Switch off the unit.
10.Fill out the commissioning report.
6.7.7 Adjusting the basic gas setting
Requirement Gas connection line connected
Check for leaks outside the unit conducted
Connection pressure checked
Check for leaks inside the unit conducted
Left side wall removed
Setting the rated heat input
WARNING
Risk of poisoning from exhaust gases
•Ensure that exhaust gases are discharged properly and that
the necessary amount of combustion air is supplied.
•Ensure that a maximum CO content of < 0.1 vol. % or < 1000
ppm is achieved in undiluted exhaust gas.
Requirement Basic gas setting checked and not OK
Left side wall removed
52Installation instructions
10014471-0AIBE-A
Connecting the unit
a
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
The offset pressure can be measured as an adjustment aid at
minimum output (see " Adjusting the basic gas setting").
Image: Adjustment screws on the burner
a Adjustment screw for low output
(TX40)
1. Open the gas shut-off valve on the unit.
2. Switch on the unit.
3. Set the unit to low output (see "Checking the basic gas setting").
The unit operates at minimum output.
4. Measure the CO2 content of the exhaust gas at the exhaust gas
connection when the temperature in the cooking zone is between
130-180 °C.
5. Check whether the measured CO2 content is within the specified
range (see "Exhaust gas values").
6. Using the adjustment screw for low output, adjust the CO2 content
to the specified range for low output (setting is very sensitive).
Turning anti-clockwise: CO2 content is decreased.
Turning clockwise: CO2 content is increased.
7. Set the unit to high output (see "Checking the basic gas setting").
The unit operates at maximum output.
10014471-0AIBE-A
53Installation instructions
Connecting the unit
A
a
b
8. Check whether the measured CO2 content is within the specified
range (see "Exhaust gas values").
If necessary, repeat the adjustment procedure until the CO
value at high and at low output is within the specified range.
If the CO2 content at high output cannot be set to the minimum
level, the rated heat input must be adjusted manually (see
"Adjusting the basic gas setting").
9. Press the Ready2Cook button and conduct the measurements for
the second burner in the same way (only unit size 20).
10.Check the waste gas values (see "Checking the basic gas
setting").
11.To end the CO2 measurement, press the "START STOP" button.
12.The indicator light in the "START STOP" button goes out; the
burner is switched off.
13.Switch off the unit.
14.Fill out the commissioning report.
Adjusting the primary air quality
Requirement Primary air quantity checked and not OK
Left side wall removed
DANGER
Risk of personal injury and physical damage from electric
shock
2
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
Image: Suction hose position
a Burnerb Suction hose
1. If the suction hose is not routed without kinks in the location and
form shown in the figure, correct or replace the suction hose.
54Installation instructions
10014471-0AIBE-A
Connecting the unit
2. If the suction hose is damaged, replace it.
3. If the opening of the suction hose is blocked, clean the suction
hose.
4. Adjust the primary air gap to within the specified range (A) by
aligning the suction hose (see "Equipment and connection data").
5. Check the basic gas setting (see "Checking the basic gas
setting").
6. Fill out the commissioning report.
Manually adjusting the rated heat input
WARNING
Risk of poisoning from exhaust gases
•Ensure that exhaust gases are discharged properly and that
the necessary amount of combustion air is supplied.
•Ensure that a maximum CO content of < 0.1 vol. % or < 1000
ppm is achieved in undiluted exhaust gas.
Requirement Adjustment of basic setting not OK
Gas shut-off valve on the unit closed
Left side wall removed
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
The offset pressure can be measured as an adjustment aid at
minimum output (see " Adjusting the basic gas setting").
1. Remove the gas orifice (see "Converting the gas type").
10014471-0AIBE-A
55Installation instructions
Connecting the unit
a
b
Image: Adjustment screws on the burner
a Adjustment screw for low output
(TX40)
b Adjustment screw for high output
(4 mm hexagon socket or 1.2 x
6.5 mm screwdriver)
2. Screw in adjustment screw for high output 10 mm (basic setting).
3. Open the gas shut-off valve on the unit.
4. Switch on the unit.
5. Set the unit to low output (see "Checking the basic gas setting").
The unit operates at minimum output.
6. Measure the CO2 content of the exhaust gas at the exhaust gas
connection when the temperature in the cooking zone is between
130-180 °C.
7. Check whether the measured CO2 content is within the specified
range (see "Exhaust gas values").
8. Using the adjustment screw for low output, adjust the CO2 content
to the specified range for low output (setting is very sensitive).
Turning anti-clockwise: CO2 content is decreased.
Turning clockwise: CO2 content is increased.
9. Set the unit to high output (see "Checking the basic gas setting").
The unit operates at maximum output.
10.Check whether the measured CO2 content is within the specified
range (see "Exhaust gas values").
11.Using the adjustment screw for high output, adjust the CO
2
content to the specified range for high output (setting is very
sensitive).
Turning anti-clockwise: CO2 content is increased.
Turning clockwise: CO2 content is decreased.
If necessary, repeat the adjustment procedure until the CO
2
value at high and at low output is within the specified range.
12.Press the Ready2Cook button and conduct the measurements for
the second burner in the same way (only unit size 20).
13.Check the waste gas values (see "Checking the basic gas
setting").
56Installation instructions
14.To end the CO2 measurement, press the "START STOP" button.
10014471-0AIBE-A
15.The indicator light in the "START STOP" button goes out; the
a
b
burner is switched off.
16.Switch off the unit.
17.Fill out the commissioning report.
Measuring the offset pressure
Requirement Basic gas setting checked and not OK
Measuring accuracy of the pressure measuring device at least 0.01
hPa (0.01 mbar)
Left side wall removed
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
Connecting the unit
10014471-0AIBE-A
Image: Measuring the offset pressure
a Offset pressure measuring pointb Pressure measuring device
1. Unscrew the sealing plug from the offset pressure measuring
point.
2. Connect the pressure measuring device.
3. Open the gas shut-off valve on the unit.
4. Switch on the unit.
5. Set the unit to low output (see "Checking the basic gas setting").
The unit operates at minimum output.
6. Measure the offset pressure.
7. Check whether the measured offset pressure is within the
specified range (see "Exhaust gas values").
57Installation instructions
Connecting the unit
a
b
c
d
6.8 Converting the gas type
Requirement Notes about the gas connection observed
Unit disconnected from power
Left side wall removed
Gas shut-off valve on the unit closed
DANGER
Risk of fatal injury from operating the unit with the wrong
gas type
•Ensure that the gas type for which the unit is set (see gas
•Ensure that the unit is suitable for the available gas type (see
DANGER
Risk of explosion and fire from escaping gas
type supplemental label) matches the gas type available at
the site.
nameplate).
•When bleeding air from or degassing the gas system and the
unit, ensure that the air and gas are discharged to the
outside in a technically correct manner and without creating
a risk.
DANGER
Risk of asphyxiation and explosion from damaged seals
•Check seals for damage
•Replace damaged seals
•Use only seals that are approved for use with gas
Image: Changing the gas orifice
58Installation instructions
a Burnerc Gas solenoid valve
b Bolts (TX25)d Gas orifice with seal
10014471-0AIBE-A
Connecting the unit
1. If the unit is already filled with gas, degas the unit in a technically
correct manner.
2. Unscrew the bolts from the gas solenoid valve.
3. Remove the gas solenoid valve.
4. Remove the gas orifice with seal.
5. Select the gas orifice specified for the gas type available and
insert the seal. (See "Gas orifice diameters").
6. Replace the gas type supplemental label on the unit with the
appropriate gas type supplemental label for the gas type available.
7. Replace the gas solenoid valve and secure it with the bolts.
8. Fill out the commissioning report.
ATTENTION
Risk of physical damage from excessively high pressure
•When opening the gas shut-off valve on the unit, ensure that
the pressure in the gas connection line is <150 mbar.
•If the pressure is >150 mbar, close the gas supply, reduce
the pressure in a technically correct manner and notify the
gas utility.
9. Open the gas shut-off valve on the unit, while paying attention to
the pressure in the gas connection line.
10.Bleed air from the gas system and unit in a technically correct
manner.
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
11.Switch on the power supply.
12.Switch on the unit.
13.Check for leaks (see "Checking for leaks").
14.Check the rated heat input (see " Checking the basic gas setting").
15.Fill out the commissioning report.
10014471-0AIBE-A
59Installation instructions
Connecting the unit
6.9 Making the exhaust air connection
When setting up the unit under an exhaust hood, observe the
applicable regional regulations for ventilation systems.
ATTENTION
Risk of physical damage from fouling of the exhaust air
ducts
•Do not incorporate the exhaust air line directly into an
exhaust air system.
ATTENTION
Risk of corrosion damage from condensate
•Install the exhaust air line such that condensate cannot
collect.
Requirement Flexible aluminium hose
6.10 Checking operation
Requirement Supply air and exhaust gas routing checked and operating
•Nominal diameter 63 mm for sizes 6 and 10
•Nominal diameter 76 mm for size 20
•Maximum length of hose 2.5 m
•Temperature-resistant to 180 °C
1. Connect hose to exhaust air connection fitting.
2. Route hose to the exhaust hood with a 3° rise.
3. Secure end of hose about 50-200 mm below the exhaust hood.
Power connection cable connected
Gas connection line connected
Check for leaks outside the unit conducted
Connection pressure checked
Check for leaks inside the unit conducted
Basic gas setting checked
60Installation instructions
10014471-0AIBE-A
DANGER
Risk of personal injury and physical damage from
unsuccessful operational check
•Do not put the unit into service.
•Contact customer service.
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
6.10.1 Checking the exhaust gas routing for leaks
1. Switch on the unit.
2. Set the unit to high output (see "Checking the basic gas setting").
Connecting the unit
The unit operates at maximum output.
3. Check exhaust gas-conducting parts for leaks with a condensation
mirror or approved backflow testing device in a technically correct
manner.
4. Check for problem-free exhaust gas routing at the flow control
(only type B
13BS
unit).
5. Conduct procedure for burner 2 in the same way (only unit size
20).
6. Switch off the unit.
7. Fill out the commissioning report.
6.10.2 Checking the monitoring of the exhaust gas routing
1. Switch on the unit and start any cooking program (see operating
instructions).
The burner is operating.
2. Switch off the ventilation.
The gas supply is blocked.
The flame extinguishes.
The unit attempts to ignite.
The safety device trips after 1 second.
10014471-0AIBE-A
An error message flashes on the display.
An audible signal sounds.
The
STEP
indicator light flashes.
The monitoring of the exhaust gas routing is functioning.
3. Switch on the ventilation.
4. Press the "STEP" button.
The unit restarts.
61Installation instructions
Connecting the unit
5. The cooking program starts again.
The burner ignites within 5 seconds.
The flame burns stably.
6. Switch off the unit.
7. Fill out the commissioning report.
6.10.3 Checking the ignition behaviour
Requirement Left side wall removed
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
1. Switch on the unit and start any cooking program (see operating
instructions).
2. Observe the ignition behaviour at the inspection port until the
flame burns stably.
3. End the cooking program.
4. Repeat the procedure several times.
5. Conduct procedure for burner 2 in the same way (only unit size
20).
6. Switch off the unit.
7. Fill out the commissioning report.
6.10.4 Checking the flame pattern
Requirement Left side wall removed
DANGER
Risk of personal injury and physical damage from electric
shock
•Inspection and adjustment work that can be carried out only
with the housing open and the unit under power must be
performed only by electrically trained technical personnel.
The burner ignites.
The flame extinguishes.
The burner is off.
1. Switch on the unit.
2. Set the unit to high output (see "Checking the basic gas setting").
The unit operates at maximum output.
3. Observe the flame pattern at the inspection port.
The flame must be pointed at its core, not generate soot,
appear yellow, flash back or lift off.
62Installation instructions
10014471-0AIBE-A
4. Conduct procedure for burner 2 in the same way (only unit size
20).
5. Switch off the unit.
6. Fill out the commissioning report.
6.10.5 Checking the flame monitoring
Requirement Ignition behaviour checked
Flame pattern checked
1. Switch on the unit and start any cooking program (see operating
instructions).
The burner ignites within 5 seconds.
The burner is operating.
2. Close the gas shut-off valve on the unit.
The flame extinguishes.
The unit attempts to ignite.
The safety device trips after 1 second.
Connecting the unit
An error message flashes on the display.
An audible signal sounds.
The
STEP
indicator light flashes.
The flame monitoring is functioning.
3. Open the gas shut-off valve on the unit.
4. Press the "STEP" button.
The unit restarts.
5. The cooking program starts again.
The burner ignites within 5 seconds.
The burner is operating.
6. Conduct procedure for burner 2 in the same way (only unit size
20).
7. Switch off the unit.
8. Fill out the commissioning report.
10014471-0AIBE-A
63Installation instructions
Connecting the unit
6.10.6 Checking the controls
Requirement Ignition behaviour checked
Flame pattern checked
1. Switch on the unit and start any cooking program (see operating
instructions).
Set the cooking zone temperature to a higher temperature than
the current cooking zone temperature.
The burner is operating.
Once the set cooking zone temperature is reached, the
controls switch off the burner.
The burner is off.
The controls are functioning.
2. Conduct procedure for burner 2 in the same way (only unit size
20).
3. Switch off the unit.
4. Fill out the commissioning report.
6.10.7 Checking the monitoring of the cooking zone door
1. Switch on the unit and start any cooking program (see operating
instructions).
The burner is operating.
The fan wheel is turning.
2. Open the cooking zone door during operation.
The burner is off.
The fan wheel comes to a stop.
The monitoring of the cooking zone door is functioning.
3. Close the cooking zone door.
4. Conduct procedure for burner 2 in the same way (only unit size
20).
5. Switch off the unit.
6. Fill out the commissioning report.
64Installation instructions
10014471-0AIBE-A
7 Putting the unit into service
If the unit is not put into service immediately after being
connected, all inspections involving the gas connection must be
repeated.
Requirement Supply air and exhaust gas routing checked
Electrical connection made
Gas connection made
Operation successfully checked
Left side wall closed