MK Electric K732BSS, K2757D2WHI, K1246D1RED Installation Instructions

2 3 4
5 6 7
9 10 11
8
12
Socket Outlets
2 amp, 5amp, 13amp & 15amp
A Product Features 2
B Recommended MK Boxes 3
C Safety Instructions 4
D Installation 8
E Changing the Fuse 17
F Cleaning 20
G Disposal Instructions 20
H Guarantee 21
Please leave this leaflet with the end user for future reference
43097PL Ed.1
Refer to the product packaging for the type of socket being installed.
All sockets should be mounted on boxes with a minimum internal depth as specified in Section B.
Certain sockets have a Non-Standard Earth socket arrangement (see Section D1).
Certain sockets have a Double Earth facility (see Section D2).
Three Gang Switchsocket is supplied fitted with a 13A fuse (see Section E).
A. PRODUCT FEATURES
Logic Plus Products:-
Flush Metal Surface Metal Boxes; Surface Boxes With Without
Plastic
25mm 35mm* Knockouts Knockouts Boxes
1 Gang 861 866 K2213 K2211 K2140
K2181(PVC)
2 Gang 862 886 K2214 K2212 K2142
K2183(PVC)
3 Gang K863 – N o t A v ailable– K2153
K2185(PVC)
9mm Metal Frontplate Product Ranges:-
Flush Metal Surface Metal Boxes; Metal Boxes With Without
25mm 35mm* Knockouts Knockouts 1 Gang 861 866 K899 ALM K829 ALM 2 Gang 862 886 K897 ALM K830 ALM
* Boxes providing extra wiring space
Surface metal boxes are suitable for mounting Albany Plus (MCO finish), or as spares for Metalclad Plus.
B. RECOMMENDED MK BOX LN’s Cont
1. To prevent the risk of electrocution it is essential to turn off the mains electricity supply before commencing work.
2. Do not work on this product live.
3. To ensure a safe installation;
- this product should be installed by a
competent person (e.g. a qualified electrician) in accordance with these instructions and the appropriate clauses of the current edition of the IEE Wiring Regulations (BS 7671).
- it is essential that all connections are made as
instructed, that cables are not stressed and that terminal screws are fully tightened.
- all sockets must be earthed and the earth
leads adequately sleeved.
C. SAFETY INSTRUCTIONS
LN
Fig.1: Rear View of a 2 Gang 13A Inboard Switchsocket Showing Typical Wiring Connections
Black Green/yellow
To Mounting Box Earth Terminal if appropriate
Red
C. SAFETY INSTRUCTIONS (Cont.)
4. Ensure that all electrical connections are correct and fully secured and that the product is screwed securely to its mounting box before turning the mains electricity supply on.
5. To prevent fire hazard do not exceed the
maximum rated current of the socket.
IMPORTANT: Refer to safety instructions before starting work (Section C).
1. Remove frontplate fixing screws from their location on the back of the product.
2. Ensure the mounting box is firmly secured to the wall. Flush mounted boxes should be installed flush or sub-flush to the surface.
3. Strip back outer cable sheath and trim wires to the appropriate length to allow cable ends to reach terminals.
4. Carefully strip red and black insulation by 13mm (
1
2
inch).
5. Slide a length of green/yellow insulating sleeve on to bare earth wire.
6. You must connect the correct wire to the correct terminal (refer to fig.1).
Note: Terminal screws are positioned ready for installation and should not be unscrewed further.
The red wire must be connected to the terminal marked L.
The black wire must be connected to the terminal marked N.
The bare wire (green/yellow sleeved) must be connected to the terminal marked .
If product has TWO earth terminals - either or both can be used for normal installations.
If you are connecting non standard socket outlets refer to Section D1.
If you are connecting socket outlets using the double earth facility, refer to Section D2.
Where a mounting box earth terminal is provided, connect a length of green/yellow sleeved wire between the terminal and the earth terminal on the socket. Tighten all terminal screws securely, ensuring all conductors are clamped.
7. Carefully push wired unit back into the mounting box, ensuring cables are not trapped or pinched.
8. Locate and tighten frontplate fixing screws. Do not overtighten screws, to do so may damage frontplate or box threads.
The completed installation should be tested in accordance with the current IEE Wiring Regulations by a qualified electrician.
If in any doubt, contact MK Technical Sales Service Department. Telephone 01268 563720.
D. INSTALLATION
D. INSTALLATION (Cont.)
D1. INSTALLATION OF NON STANDARD AND CLEAN EARTH 13 AMP SOCKETS
These switchsockets are for use on installations where restricted access or a clean earth is required. Non standard sockets will only accept MK LN 647 13A Non-Standard Plug, with ‘T’ shaped earth pin.
1. For use as a ‘Restricted-use’ socket (refer to fig. 2), leave the earth wire-link in position
and wire as instructed in Section D. Either or both terminals can be used for the circuit protective conductor and the mounting box bonding earth.
2. For use on a ‘Clean Earth’ installation (refer to fig. 3 overleaf).
- Remove earth wire link.
-
Connect socket as instructed in Section D except: connect the functional clean earth supply
conductor to the terminal
marked , connect the circuit protective conductor (CPC) and any mounting box earth to the terminal marked .
Restricted Use Installation
Fig. 2: Rear view of a 2 gang non standard
13A switch-
socket showing terminal markings and earth wire link.
LN
Black
Green/
yellow
Red
Circuit Protective Conductor (CPC)
To Mounting Box Earth Terminal
Fig.1a: Rear View of 2A Socket showing Typical Wiring Connections
N
N
MADE IN
UK
2A 250V
L
BS546
Green/yellow
Red
Black
LN
Base and Terminal Layout of the
5 and 15 Amp Sockets
Earth Wire Link
1.5mm Metal Frontplate Product Ranges:
Flush Metal Boxes: 35mm 47mm* 1 Gang 866 877 2 Gang 886 878
* Boxes providing extra wiring space
B. RECOMMENDED MK BOX LN’s
14 15 16
17 18 19
13
20
21 22 23 24
One gang switchsockets, two gang outboard switchsockets, two gang unswitched sockets and three gang switchsockets are fitted with two earth terminals, (identified ), on a common
busbar to provide a double earth facililty for use when installations require additional earthing capacity and are to comply with Regulation 607 of BS 7671 IEE Wiring Regulations. These should be referred to for specialist installation guidelines.
For normal installations either or both earth terminals may be used. See figure 4 for typical terminal layout.
D2. INSTALLATION OF 13A SOCKETS WITH DOUBLE EARTH FACILITY
Fig. 4: Rear views of 1 & 2 gang 13A switchsockets with double earth facility, showing positions of earth terminals
In order to protect the quality surface of the front plate periodic cleaning should only consist of polishing with a dry lint free soft cloth. On no account should abrasive or domestic cleaners be used.
F. CLEANING
3 GANG SOCKETS ONLY
1. Remove all plugs from socket outlet.
2. Unscrew fuse carrier fixing screw to partially eject fuse carrier (see Fig. 5a).
Pull carrier out releasing fuse (see Fig. 5b). Note: fuse carrier cannot be fully removed from the product.
Fit new fuse, push fuse carrier in and tighten screw until carrier is fully home ie. flush with socket surface. Do not overtighten.
3. Always fit a BS 1362 type 13A fuse (as used in 13A plugs).
4. Plug in appliances one by one and check operation.
If new fuse blows again, the last appliance connected may be faulty or you have exceeded the maximum total load of 13 Amp (3250 watts).
If in doubt consult a qualified electrician.
E. CHANGING THE FUSE
Fig. 5bFig. 5a
The Company undertakes to replace or repair, at its discretion, this product should it become defective within a period of 20 years after delivery, solely as a result of faulty materials and/or workmanship. Understandably, if the product has not been installed or maintained in accordance with the Company’s instructions, has not been used appropriately, or if any attempt has been made to rectify, dismantle or alter the product in any way, the guarantee will be invalidated.
This Guarantee states the Company’s entire liability. It does not extend to cover consequential loss or damage or installation costs arising from the defective product. This Guarantee does not restrict or infringe the normal statutory or other rights of the consumer.
H. GUARANTEE
MK Electric Limited wishes to make it clear that it owns all the original designs of the products which it manufactures (whether or not listed in this leaflet) and that it will take all necessary legal action in any part of the world against any party found to be manufacturing, distributing, selling or otherwise dealing with any article which infringes the company’s intellectual property in its own products, or any other right of the company therein.
Intellectual Property Application
Patent EP 00539093 Patent 2261120 Patent 2266814 Registered Design 2025114 Registered Design 2025115 Registered Design 2025116 Registered Design 2031394 Registered Design 2031395 Registered Design 2031396
Compliance with E.U. Directives
Non-Standard socket outlets comply with the requirements of the Low Voltage Directive (72/23/EEC).
Note: Standard sockets (BS 1363 and BS 546) do
not fall within the scope of this Directive.
COMPLIANCE WITH E.U. DIRECTIVES
D1. (continued)
NL
Clean Earth Installation
Fig. 3: Rear view of a 1 gang non standard
13A switchsocket showing terminal markings and earth wire link removed.
(Black)
CPC and to Mounting
Box Earth Terminal
(Green/yellow)
(Red)
Functional Clean earth (Green/yellow)
®
It’s simply safer to say MK
MK Electric Limited
The Arnold Centre, Paycocke Road, Basildon,
Essex SS14 3EA
Telephone 01268 563000 (National)
Telephone +44 (0) 1268 563000 (International)
Facsimile 01268 563563 (UK Sales)
Facsimile +44 (0) 1268 563360 (International)
email: more@mkelectric.co.uk
web site: www.mkelectric.co.uk