COMMISSIONING WARNING: 230 Volts is present on the underside of the
printedcircuitassembly.
7. With the room empty, ensure that there are no spurious movement signals liable to cause interference. Check this with ventilation and other machinery running. Possible interference sources are: fans turning, flapping notices, flashingfluorescentlights,runningwateretc.
1. SetallmodeswitchestoON.
2. Adjustthe timer controls to zero (fully anticlockwise). Relay 1 willtimeoutin4seconds,Relay2in8(ifapplicable) enabling theunittobe ‘walktested’.
3. Setbothrangecontrols fullyanticlockwise.
4. Leavetheareauntil thelightsgooff andthenre-enter.
6. Leavetheareaandwaitforthelights to turn off. Waitafurther 10 seconds then re-enter. Adjust the OFF range control clockwise until the lights are switched on ONLY AS THE AREAISENTERED.
5. AdjusttheONrangecontrolclockwisetoincreasesensitivity, ensuring all areas are covered and that the lightsarekept on with minimal movement.
*When set fully anticlockwise the OFF range is equal to theONrange.
Swivel the detector head to give best coverage - by experimenting with various orientations, therangecontrolcan bekepttoa minimum setting.
CompleteCommissioning
8. SettheMODE switchtogivethedesired functions. (SeeModes of Operationover.)
9. Set the OFF DELAY controls as required - each control has a range of 0 to 16 minutes. A setting of around5 - 10 minutes is usuallyappropriate.
Off Delay O/P1 relates to Relay 1 - Off Delay O/P2 relates to Relay 2. Note that O/P2 commences to time out after O/P1 has expired, therefore with O/P2 set to zero both circuits will time out together.
10.Lockthedetectorheadinto positionbeforeleaving (seedetector instructions).
Long Range Control Unit
Single Circuit
Dual Circuit
Installation & Commissioning Instructions
At theend of theiruseful life thepackaging and product shouldbe disposed ofvia a suitable recycling centre. Do notdispose of with
SENSORS
K4039 K4040
MK Electric
The Arnold Centre,Paycocke Road, Basildon,
Essex, SS14 3EA.UK
Tel: +44 (0)1268563720 Fax: +44 (0)1268563064
email: mktechnical@honeywell.com
Tel: +44 (0)1268563000
Fax: 012685 63404
Fax: +44 (0)1268563365 (International)
email: mkorderenquiries@honeywell.com
web site: www.mkelectric.co.uk
Novar ED&S Ltd (A HoneywellCompany),
Arlington Business Park,Bracknell, Berkshire, RG12 1EB
All marks in this documentidentified with a R or TM symbol
adjacent to the mark areTrade Marks of Novar ED&S Ltd.
Technical Help
Customer Service
______________________________________________________
WHERETOFIT
A corner position often takes maximum advantage of the detection pattern. Reflections from walls and ceilings will increase performance further and extend coverage into non­line-of-sight areas. The detector responds to movement through glass therefore point away from thin partitions and windowswhichviewonto activity.
Itisgenerallyadvisabletoseparatethedetectorand controlunit forconvenience of wiringandcommissioning. Do not fit in roof spaceor otherinaccessiblelocations.
LongRangeControl Unit - K4039 / K4040
For usewith 30mand 60m Range Detectors. 230V 50/60Hz 10 Watt. Switch capacity: 10 amp 230V ac. Incandescent lamps:1500W max (at 230V) K4039 output: 1 x single pole volt-free. K4040 output: 2 x single pole volt-free. Each Control Unit will support up to two detectors.
SEEOVERLEAF FOR
COMMISSIONING
INSTRUCTIONS
MODESOF OPERATION
Whenmovement is detectedthelights switchon,whenthearea is vacatedlightsswitchoff.
Relay 1 can be set to semi-automatic by setting the first of the 4-pole switches to off. In these circumstances, a push-button is requiredto activaterelay1. Relay2willalwaysbefullyautomatic.
The MODE of operation is selected by a 4-pole switchinside the enclosure.
ELECTRICAL CONNECTIONS
Cable access can be made at the side or end of the control unit adjacent to the terminal blocks. Select entry points with care and keep all cables away from the underside of the printedcircuit board (PCB).
SwitchforSemi-AutomaticOperation (PB1 or PB2)
Theswitchisconnectedacrosslow-voltageterminalsDandE. Itcanonlyswitchthe loadONand cannotswitchOFFinstandardcontrollers. Accidentalactionwhentheroom isinuse does notmatter. Thecontrolunitrespondstoachange ofstateandnotanONor an OFFstatethereforeanyconvenienttypeof switchmaybeused.If several
switchesare required,theymust bemomentaryactiontypes(egpush-buttons). Floorpads maybeused forprecisethresholdor zonecontrol.
1 2 3 4 5 6 7
L N E
Relay R1
Relay R2
230V
Connections
230V
AC
Supply
Volt free
N/O Contact
Volt free
N/O Contact
(K4040 Control
Unit only)
12V
Connections
A B C D E F G
A B C
Screened lead. See Detector Installation Instructions.
Push button connection for manual on / auto off applications (optional)
Photocell connection or link
CONTROL
UNIT
DETECTOR(S)
If no photocell isfitted, set switches 2 and 4 to ON and link connections FandG on theControlUnit.
Relay 1 = auto on / auto off.
Relay 1 = manual on / auto off.
Photocell is inactive on circuit 1 - active on
circuit 2.
Photocell is active on both circuits.
Power up condition = load ON.
Power up condition = load OFF.
Photocell operates in passive mode.
Photocell operates in active mode.
Lights come on immediately presence is detected.
The user must press a push button to switch on the lights but they will go off automatically when the room is vacated.
All movement signals are ignored for 15 seconds after power is applied.
See photocell instructions.
See photocell instructions.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
SWITCH POLE OPERATIONMODE
1
2
3
4
1 2 3 4