50851PL Ed. 1
COMMISSIONING
WARNING: 230 Volts is present on the underside of the
printedcircuitassembly.
7. With the room empty, ensure that there are no spurious
movement signals liable to cause interference. Check this
with ventilation and other machinery running. Possible
interference sources are: fans turning, flapping notices,
flashingfluorescentlights,runningwateretc.
1. SetallmodeswitchestoON.
2. Adjustthe timer controls to zero (fully anticlockwise). Relay 1
willtimeoutin4seconds,Relay2in8(ifapplicable) enabling
theunittobe ‘walktested’.
3. Setbothrangecontrols fullyanticlockwise.
4. Leavetheareauntil thelightsgooff andthenre-enter.
6. Leavetheareaandwaitforthelights to turn off. Waitafurther
10 seconds then re-enter. Adjust the OFF range control
clockwise until the lights are switched on ONLY AS THE
AREAISENTERED.
5. AdjusttheONrangecontrolclockwisetoincreasesensitivity,
ensuring all areas are covered and that the lightsarekept on
with minimal movement.
*When set fully anticlockwise the OFF range is equal to
theONrange.
Swivel the detector head to give
best coverage - by experimenting with various orientations,
therangecontrolcan bekepttoa minimum setting.
CompleteCommissioning
8. SettheMODE switchtogivethedesired functions. (SeeModes
of Operationover.)
9. Set the OFF DELAY controls as required - each control has a
range of 0 to 16 minutes. A setting of around5 - 10 minutes is
usuallyappropriate.
Off Delay O/P1 relates to Relay 1 - Off Delay O/P2 relates to
Relay 2. Note that O/P2 commences to time out after O/P1 has
expired, therefore with O/P2 set to zero both circuits will time out
together.
10.Lockthedetectorheadinto positionbeforeleaving (seedetector
instructions).
Long Range Control Unit
Single Circuit
Dual Circuit
Installation &
Commissioning Instructions
At theend of theiruseful
life thepackaging and
product shouldbe
disposed ofvia a suitable
recycling centre.
Do notdispose of with
SENSORS
K4039
K4040
MK Electric
The Arnold Centre,Paycocke Road, Basildon,
Essex, SS14 3EA.UK
Tel: +44 (0)1268563720
Fax: +44 (0)1268563064
email: mktechnical@honeywell.com
Tel: +44 (0)1268563000
Fax: 012685 63404
Fax: +44 (0)1268563365 (International)
email: mkorderenquiries@honeywell.com
web site: www.mkelectric.co.uk
Novar ED&S Ltd (A HoneywellCompany),
Arlington Business Park,Bracknell, Berkshire, RG12 1EB
All marks in this documentidentified with a R or TM symbol
adjacent to the mark areTrade Marks of Novar ED&S Ltd.
Technical Help
Customer Service
______________________________________________________