Socket outlets, switches and other MK wiring accessories can be wall or bench mounted. Do not use a trailing lead for sockets and
connection units or mount any devices where they may be subject to excessive moisture or dampness.
Cable management
Socket outlets, switches and other MK wiring accessories can be mounted in a variety of MK trunking systems.
13A Socket Outlets
Standards and approvals
13A socket outlets comply with
BS 1363 Part 2:1995.
Replacement fuses to the 3 gang switchsocket
outlets (Logic Plus only) comply with
BS1362:1973.
TECHNICAL SPECIFICATION
ELECTRICAL
VOLTAGE RATING
250V a.c.
CURRENT RATING
13A
(3 Gang Switchsocket 13A total)
TERMINAL CAPACITY
Live, neutral & earth
3 x 2.5mm²
3 x 4mm²
2 x 6mm² (standard)
(Dual earth terminals on list Nos. K781, K2657,
K2737, K2746, K2757, all standard Edge and Aspect
sockets, K733, K2958, K2458, K2947, K2947D6,
K850, K2977, K2477, K3045, K3077, K2945,
K2945D6 and K5357)
PHYSICAL
AMBIENT OPERATING TEMPERATURE
–5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
Description
A range of socket outlets designed for ease of installation and having all the
advantageous design features of the MK range of wiring devices. The 2 gang
sockets with outboard rockers (available in Logic Plus and Albany Plus) are of
particular value for use by the inrm and partially sighted whilst the same feature in
Metalclad Plus is ideal for use with gloved hands.
Non-standard clean earth sockets are for use on installations where restricted
access is required and will only accept a 647WHI 13A non-standard plug with
T-shaped earth pin. The sockets have two independent earth terminals so that they
can also be used for ‘clean earth’ installations. The K2746CE and K2947CE also
have two independent earth terminals for ‘clean earth’ installations.
A variety of sockets (see Technical Specication) are tted with two earth terminals
on a common busbar to provide a double earth facility for use when installations
require a high integrity protective connection as specied within the latest edition of
BS7671 which should be referred to for guidance.
The products can be quickly installed as replacement for existing 13A sockets or in
a new installation.
Fuse carriers
(Logic Plus 3 gang switchsocket only)
The fuse carrier is opened by a fast-acting, screwdriver-operated, worm-drive screw
for ease of replacement.
WIRING DEVICES
For a full range of corresponding products,
see pages 32-188 in the product selector.
441
Wiring Devices Technical
WIRING DEVICES
13A Socket Outlets
Installation
1 gang switchsocket – view from rear
Top-facing, angled, backed-out terminals
make wiring easier and quicker.
FEATURES
l
Moulded ‘on’ indicator flash on plastic
switches will not rub off – totally safe
l
Matching Metal rocker Switches
(Edge™ and Aspect only)
l
Optional neon indicators in the switch
rockers with 175° visibility in the
horizontal and vertical planes
2 Gang Switchsocket Outlet with Integrated
Dual USB Charging Capability
Standards and approvals
Logic Plus™ 13A socket outlets and 2A USB
charging outlets comply with BS 5733 and
IEC 61558-2-16.
EMC Compatibility:
IEC 61000-6-1
IEC 61000-6-3
Products are CE marked and meet the
requirements of the Low Voltage, EMC, RoHS
and WEEE directives.
WIRING DEVICES
TECHNICAL SPECIFICATION
13A SOCKET OUTLETS
ELECTRICAL
VOLTAGE RATING
220-240V
CURRENT RATING
13A
Combined total 2A drawn from USB outlets
STANDBY POWER
150mW
TERMINAL CAPACITY
Live, neutral & earth
3 x 2.5mm
3 x 4mm
2 x 6mm2 (stranded)
PHYSICAL
AMBIENT OPERATING TEMPERATURE
–5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
2
2
Installation
Logic Plus™ socket outlets can be wall or bench
mounted.
Do not mount or use as a trailing socket or
where they may be subject to excessive
moisture or damp.
Description
A range of socket outlets designed for ease of installation and having all the
advantageous design features of the Logic Plus™ range. Dual USB charging outlets
offer end users easy access to power for charging a variety of devices such as
smart phones, tablets and cameras.
FEATURES
l
Moulded ‘on’ indicator flash on
switches will not rub off – totally safe
l
3 pin operated safety shutter on 13A
socket outlets
l
USB 2.0 and 3.0 compatible
l
Can charge a device at up to a full 2A
l
If only one device is connected to a
USB outlet the total output current of
2A is available from either outlet
l
If two devices are connected to USB
outlets the the total rated current of 2A
is divided between the two outlets
l
Differing manufacturers devices can
be charged simultaneously via the two
USB outlets
l
If the total charging current exceeds
the rated level of 2A then the device will
enter a current limiting safety mode
l
Electronically protected against an
overload or short circuit on either USB
outlet
l
USB outlets are designed to provide
optimum charging compatibility
across a wide range of devices
l
Printed terminal markings on grey rear
mouldings for clearer identification
l
Top access, angled terminals make
wiring easier and quicker
l
3mm minimum switch contact gap
l
Double pole switching
l
Additional electrical safety from
neutral ‘make first’, ‘break last’ feature
l
Switch contacts with silver contacts
on both surfaces for good continuity
l
Backed out and captive terminal
screws
l
Dual earthed
Dimensions (mm)
Cable management
Logic Plus™ socket outlets can be mounted in a
variety of MK trunking systems.
BOX TYPES WITHOUT PATRESS
GANGFLUSH
DEPTH 35MM DEPTH 40MM DEPTH 41MM
2 GANG
886 ZICK2172 WHI
SURFACE
INSULATED
SURFACE
METAL
K2212 ALM
K2214 ALM
146
40
86
28120.6
443
Wiring Devices Technical
– Aspect
WIRING DEVICES
2 Gang Switchsocket Outlet with Integrated
Dual USB Charging Capability
Standards and approvals
Aspect 13A socket outlets and 2A USB
charging outlets comply with BS 5733 and
IEC 61558-2-16.
EMC Compatibility:
IEC 61000-6-1
IEC 61000-6-3
Products are CE marked and meet the
requirements of the Low Voltage, EMC, RoHS
and WEEE directives.
mkelectric.co.uk
TECHNICAL SPECIFICATION
13A SOCKET OUTLETS
ELECTRICAL
VOLTAGE RATING
220-240V
CURRENT RATING
13A
Combined total 2A drawn from USB outlets
STANDBY POWER
150mW
TERMINAL CAPACITY
Live, neutral & earth
3 x 2.5mm
3 x 4mm
2 x 6mm2 (stranded)
PHYSICAL
AMBIENT OPERATING TEMPERATURE
–5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
2
2
Installation
Aspect socket outlets can be wall or bench
mounted.
Do not mount or use as a trailing socket or
where they may be subject to excessive
moisture or damp.
Description
A range of socket outlets designed for ease of installation and having all the
advantageous design features of the Aspect range. Dual USB charging outlets offer
end users easy access to power for charging a variety of devices such as smart
phones, tablets and cameras.
FEATURES
l
Slim screwless frontplate design
l
Matching metal rocker switches
l
3 pin operated safety shutter on 13A
socket outlets
l
USB 2.0 and 3.0 compatible
l
Can charge a device at up to a full 2A
l
If only one device is connected to a
USB outlet the total output current of
2A is available from either outlet
l
If two devices are connected to USB
outlets the the total rated current of 2A
is divided between the two outlets
l
Differing manufacturers devices can
be charged simultaneously via the two
USB outlets
l
If the total charging current exceeds
the rated level of 2A then the device will
enter a current limiting safety mode
l
Electronically protected against an
overload or short circuit on either USB
outlet
l
USB outlets are designed to provide
optimum charging compatibility
across a wide range of devices
l
Printed terminal markings on grey rear
mouldings for clearer identification
l
Top access, angled terminals make
wiring easier and quicker
l
3mm minimum switch contact gap
l
Double pole switching
l
Additional electrical safety from
neutral ‘make first’, ‘break last’ feature
l
Switch contacts with silver contacts
on both surfaces for good continuity
l
Backed out and captive terminal
screws
l
Dual earthed
Dimensions (mm)
444
Cable management
Aspect socket outlets can be mounted in
a variety of MK trunking systems.
BOX TYPES WITHOUT PATRESS
GANGFLUSH
2 GANG
DEPTH 47MM
878 ZIC
146.4
40
86.4
33
Technical Hotline
+44 (0)1268 563720
Wiring Devices Technical
2 Gang Switchsocket Outlet with Integrated
Dual USB Charging Capability
Standards and approvals
EdgeTM 13A socket outlets and 2A USB charging
outlets comply with BS 5733 and
IEC 61558-2-16.
EMC Compatibility:
IEC 61000-6-1
IEC 61000-6-3
Products are CE marked and meet the
requirements of the Low Voltage, EMC, RoHS
and WEEE directives.
WIRING DEVICES
– Edge™
TECHNICAL SPECIFICATION
13A SOCKET OUTLETS
ELECTRICAL
VOLTAGE RATING
220-240V
CURRENT RATING
13A
Combined total 2A drawn from USB outlets
STANDBY POWER
150mW
TERMINAL CAPACITY
Live, neutral & earth
3 x 2.5mm
3 x 4mm
2 x 6mm2 (stranded)
PHYSICAL
AMBIENT OPERATING TEMPERATURE
–5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
2
2
Installation
EdgeTM socket outlets can be wall or bench
mounted.
Do not mount or use as a trailing socket or
where they may be subject to excessive
moisture or damp.
Description
A range of socket outlets designed for ease of installation and having all the
advantageous design features of the EdgeTM range. Dual USB charging outlets offer
end users easy access to power for charging a variety of devices such as smart
phones, tablets and cameras.
FEATURES
l
l
Matching metal rocker switches
l
3 pin operated safety shutter on 13A
socket outlets
l
USB 2.0 and 3.0 compatible
l
Can charge a device at up to a full 2A
l
If only one device is connected to a
USB outlet the total output current of
2A is available from either outlet
l
If two devices are connected to USB
outlets the the total rated current of 2A
is divided between the two outlets
l
Differing manufacturers devices can
be charged simultaneously via the two
USB outlets
l
If the total charging current exceeds
the rated level of 2A then the device will
enter a current limiting safety mode
l
Electronically protected against an
overload or short circuit on either USB
outlet
USB Outlets are designed to provide
optimum charging compatibility
across a wide range of devices
l
Printed terminal markings on grey rear
mouldings for clearer identification
l
Top access, angled terminals make
wiring easier and quicker
l
3mm minimum switch contact gap
l
Double pole switching
l
Additional electrical safety from
neutral ‘make first’, ‘break last’ feature
l
Switch contacts with silver contacts
on both surfaces for good continuity
l
Backed out and captive terminal
screws
l
Dual earthed
Dimensions (mm)
Cable management
EdgeTM socket outlets can be mounted in
a variety of MK trunking systems.
BOX TYPES WITHOUT PATRESS
GANGFLUSH
2 GANG
DEPTH 47MM
878 ZIC
146
120.6
40
86
35.7
445
Wiring Devices Technical
– Albany Plus™
WIRING DEVICES
2 Gang Switchsocket Outlet with Integrated
Dual USB Charging Capability
Standards and approvals
Albany Plus™ 13A socket outlets and 2A USB
charging outlets comply with BS 5733 and
IEC 61558-2-16.
EMC Compatibility:
IEC 61000-6-1
IEC 61000-6-3
Products are CE marked and meet the
requirements of the Low Voltage, EMC, RoHS
and WEEE directives.
mkelectric.co.uk
TECHNICAL SPECIFICATION
13A SOCKET OUTLETS
ELECTRICAL
VOLTAGE RATING
220-240V
CURRENT RATING
13A
Combined total 2A drawn from USB outlets
STANDBY POWER
150mW
TERMINAL CAPACITY
Live, neutral & earth
3 x 2.5mm
3 x 4mm
2 x 6mm2 (stranded)
PHYSICAL
AMBIENT OPERATING TEMPERATURE
–5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
2
2
Installation
Albany Plus™ socket outlets can be wall or
bench mounted.
Do not mount or use as a trailing socket or
where they may be subject to excessive
moisture or damp.
Description
A range of socket outlets designed for ease of installation and having all the
advantageous design features of the Albany Plus™ range. Dual USB charging
outlets offer end users easy access to power for charging a variety of devices such
as smart phones, tablets and cameras.
FEATURES
l
Moulded ‘on’ indicator flash on
switches will not rub off – totally safe
l
3 pin operated safety shutter on 13A
socket outlets
l
USB 2.0 and 3.0 compatible
l
Can charge a device at up to a full 2A
l
If only one device is connected to a
USB outlet the total output current of
2A is available from either outlet
l
If two devices are connected to USB
outlets the the total rated current of 2A
is divided between the two outlets
l
Differing manufacturers devices can
be charged simultaneously via the two
USB outlets
l
If the total charging current exceeds
the rated level of 2A then the device will
enter a current limiting safety mode
l
Electronically protected against an
overload or short circuit on either USB
outlet
l
USB outlets are designed to provide
optimum charging compatibility
across a wide range of devices
l
Printed terminal markings on grey rear
mouldings for clearer identification
l
Top access, angled terminals make
wiring easier and quicker
l
3mm minimum switch contact gap
l
Double pole switching
l
Additional electrical safety from
neutral ‘make first’, ‘break last’ feature
l
Switch contacts with silver contacts
on both surfaces for good continuity
l
Backed out and captive terminal
screws
l
Dual earthed
Dimensions (mm)
446
Cable management
Albany Plus™ socket outlets can be mounted in
a variety of MK trunking systems.
BOX TYPES WITHOUT PATRESS
GANGFLUSH
DEPTH 35MM DEPTH 40MM DEPTH 41MM
2 GANG
886 ZICK2172 WHI
SURFACE
INSULATED
SURFACE
METAL
K2212ALM /
K2214ALM
146.1
40
85.8
27.7120.6
Technical Hotline
+44 (0)1268 563720
Wiring Devices Technical
– Metalclad Plus™
2 Gang Switchsocket Outlet with Integrated
Dual USB Charging Capability
Standards and approvals
Metalclad Plus™ 13A socket outlets and 2A USB
charging outlets comply with BS 5733 and
IEC 61558-2-16.
EMC Compatibility:
IEC 61000-6-1
IEC 61000-6-3
Products are CE marked and meet the
requirements of the Low Voltage, EMC, RoHS
and WEEE directives.
WIRING DEVICES
TECHNICAL SPECIFICATION
13A SOCKET OUTLETS
ELECTRICAL
VOLTAGE RATING
220-240V
CURRENT RATING
13A
Combined total 2A drawn from USB outlets
STANDBY POWER
150mW
TERMINAL CAPACITY
Live, neutral & earth
3 x 2.5mm
3 x 4mm
2 x 6mm2 (stranded)
PHYSICAL
AMBIENT OPERATING TEMPERATURE
–5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
2
2
Installation
Metalclad Plus™ socket outlets can be wall or
bench mounted.
Do not mount or use as a trailing socket or
where they may be subject to excessive
moisture or damp.
Description
A range of socket outlets designed for ease of installation and having all the
advantageous design features of the Metalclad Plus™ range. Dual USB charging
outlets offer end users easy access to power for charging a variety of devices such
as smart phones, tablets and cameras.
FEATURES
l
Moulded ‘on’ indicator flash on
switches will not rub off – totally safe
l
3 pin operated safety shutter on 13A
socket outlets
l
USB 2.0 and 3.0 compatible
l
Can charge a device at up to a full 2A
l
If only one device is connected to a
USB outlet the total output current of
2A is available from either outlet
l
If two devices are connected to USB
outlets the the total rated current of 2A
is divided between the two outlets
l
Differing manufacturers devices can
be charged simultaneously via the two
USB outlets
l
If the total charging current exceeds
the rated level of 2A then the device will
enter a current limiting safety mode
l
Electronically protected against an
overload or short circuit on either USB
outlet
l
USB outlets are designed to provide
optimum charging compatibility
across a wide range of devices
l
Printed terminal markings on grey rear
mouldings for clearer identification
l
Top access, angled terminals make
wiring easier and quicker
l
3mm minimum switch contact gap
l
Double pole switching
l
Additional electrical safety from
neutral ‘make first’, ‘break last’ feature
l
Switch contacts with silver contacts
on both surfaces for good continuity
l
Backed out and captive terminal
screws
l
Metallic powder paint finish is
corrosion and scratch resistant
l
Dual earthed
l
High impact resistance
Dimensions (mm)
Cable management
Metalclad Plus™ socket outlets can be mounted
in a variety of MK trunking systems.
BOX TYPES WITHOUT PATRESS
GANGFLUSHSURFACE
2 GANG
DEPTH
35MM
886 ZIC
DEPTH 38MM
K830 ALM (without knockouts)
K897 ALM and K897 WHI
(with 8 x 20mm knockouts)
146
85.8
40
27.7120.6
447
Wiring Devices Technical
T
T
test before use
press button - T
white
off
(tripped)
red
on
on
active control
device trips with
loss of mains
10mA tripping current
sentrysocket
rcd protected
WIRING DEVICES
Sentrysocket
Compliance with EC Directives,
Standards and approvals
All Sentrysockets comply with the following
EC Directives and are CE marked:
Low Voltage Directive
Electromagnetic Compatibility Directive
(89/336/EEC)
Sentrysocket RCD DP Single Sockets comply
with the requirements of the following standards:
BS7288:1990
BSEN50082-1:1998
Sentrysocket RCD SP Double Sockets
also comply with the requirements of
BSEN61543:1996.
mkelectric.co.uk
Description
Sentrysocket provides a high level of protection against electrocution and gives
further protection when used with appliances vulnerable to insulation damage,
particularly when they are in damp environments or outdoors. The Sentrysocket
units are not suitable for mounting in damp environments or outdoors.
Sentrysocket, incorporating an RCD, is part of a complete range of xed and
portable wiring devices and circuit protection devices suitable for use in domestic,
commercial and light industrial applications.
448
TECHNICAL SPECIFICATION
ELECTRICAL
RATED VOLTAGE
240V a.c.
CURRENT RATING
13A resistive
Rated tripping current 10mA/30mA
TERMINAL CAPACITY
2
for 1 gang
3 x 4mm
2
for 2 gang
2 x 4mm
PHYSICAL
AMBIENT OPERATING TEMPERATURE
–5°C to +40°C
IP RATING
IP2XD
IP66 (K56301/K56231/K56233)
MAX. INSTALLATION ALTITUDE
2000 metres
Sentrysockets are not suitable for connection across
two lines of a 127V line to Neutral Voltage System
Cable management
Logic Plus™, Albany Plus™ and Metalclad
Plus™ Sentrysockets can be mounted in a variety
of MK trunking systems.
Installation
Flush mounting steel wall box
It should be noted that some of the conduit
entries may be restricted, depending upon their
positions and the depth of box used.
Active control circuits
Incorporate a ‘Re-set’ mechanism and are mains failure sensitive, i.e. they will
function under all the normal conditions expected of an RCD, but will also trip in
the event of a power cut or a sudden, dramatic reduction in mains voltage. This
makes them ideal for use where it would be hazardous for equipment to suddenly
energise after return of mains power, such as use with rotating machinery and heat
developing apparatus.
Passive control circuits
Incorporate a ‘Stay-set’ mechanism and is mains failure proof, i.e. it will function
under all the normal conditions expected of an RCD and will not trip in the event
of a power cut. This makes it suitable for use with freezers or in inaccessible or
unmanned locations.
FEATURES
l
Suitable for most residential,
commercial and light industrial
applications
l
Active and passive control circuit
applications
l
Flexible and versatile in use
l
Single Sockets have double pole
switching, double sockets are single
pole switching
l
Masterseal Plus products are ideal
for use with equipment subject to wet
weather or high humidity
l
Part of a complete range of MK circuit
protection devices
l
They are a.c. and pulsating d.c.
sensitive for residual current
l
Double Socket products have an
enhanced RF Immunity performance
Sentrysockets products can be wall or bench mounted. Do not mount or use as a
trailing socket or where they maybe subject to excessive moisture or dampness.
Dimensions (mm)
Double socketSingle socket
146146
Flag below Reset (R) button.
Red : ON Black: OFF
sentrysocket
rcd protected
86
86
ALWAYS TEST BEFORE USE
Press Test (T) button, Red flag should
disappear. If it does not, do not use.
Press Reset (R) after testing.
T
R
120.6120.69
26.53.3
Technical Hotline
+44 (0)1268 563720
Sentrysocket
WIRING DEVICES
Wiring Devices Technical
Installation
Flush mounting steel wall box
It should be noted that some of the conduit entries may be restricted,
depending upon their positions and the depth of box used.
Socket Testing
Single Socket Testing
After installation, turn the mains electricity supply on.
To test that the Sentrysocket is functioning correctly:
1. Ensure that no appliance is connected to the Sentrysocket.
Switch Sentrysocket on: The switch should remain closed
and the red ag will appear in the window. If the switch fails to
remain closed, check that the Supply L and N connections are
not reversed or the Supply N connection is not open circuit. If
the Sentrysocket is correctly connected and still trips after being
switched on, the Sentrysocket is faulty and should not be used.
2. If the Sentrysocket stays on, press the test button: The
switch will open and the white ag will appear In the window.
If the Sentrysocket does not trip and there is mains voltage
present at the socket outlet, Sentrysocket is faulty and should
not be used.
3. Switch Sentrysocket on: Connect an RCD tester and ensure
that the Sentrysocket trips within the specied time:
≤ 200 ms AT RATED TRIP CURRENT
≤ 40 ms AT 5 x RATED TRIP CURRENT
If the Sentrysocket does not trip within the specied times then
the product is faulty and should not be used (If more than one
RCD is in series then there is no guarantee as to which device
will trip rst).
4. Reset all tripped RCD’s including the Sentrysocket.
5. Switch off the mains supply switch disconnector. On mains
failure, a Sentrysocket with Active Control Circuit will trip, whilst
a Sentrysocket with Passive Control Circuit will not trip. If the
Active Control device does not trip, it is faulty and should not
be used – see note below. If no faults have been found then
installation testing has been completed successfully.
Double Socket Testing
After installation, turn the mains electricity supply on.
To test that the Sentrysocket is functioning correctly follow the
steps 1 to 4 below:
1. Ensure that no appliance is connected to the Sentrysocket.
2. Reset – Press the button marked R (for Reset) – the contact
status indicator should show red, indicating that the socket
outlets are now live (if the switches are in the ON positions).
3. Test – Press the TEST button marked T (for Test), the product
should trip with the contact status indicator showing black. In
this state the socket outlets are disconnected from the supply.
4. Reset – Press the button marked R again, the contact status
indicator should show red.
5. Connect an RCD Tester to either socket outlet and ensure that
the Sentrysocket trips with the specied times below:
≤ 200 ms AT RATED TRIP CURRENT
≤ 40 ms AT 5 x RATED TRIP CURRENT
6. Reset the Sentrysocket as in step 2 above.
7. Switch off the Mains Supply Switch Disconnector.
8. A Sentrysocket with Active Control Circuit should trip while a
Sentrysocket with Passive Control Circuit should not trip.
If all the operations in steps 2 to 8 above give correct results, the
Sentrysocket RCD socket outlet is safe to use.
If the procedures in steps 2 to 8 above are not completed
correctly, do not use the Sentrysocket product and seek
professional advice or contact the MK Technical Sales and
Service department on +44 (0)1268 563720.
Note: If a fault is identied at any stage of installation testing procedure do
not use Sentrysocket, and contact your local electrician, or your local MK
stockist.
449
Wiring Devices Technical
WIRING DEVICES
Filtered Switchsocket Outlets (Logic Plus and Albany Plus)
Standards and approvals
Filtered socket outlets comply with
BS5733:2010.
TECHNICAL SPECIFICATION
ELECTRICAL
CURRENT RATING
13A maximum total for 2 sockets
VOLTAGE RATING
250V a.c.
EARTH LEAKAGE
0.5 mA
SUPPRESSION
150 kHz – 30 MHz (transients)
MAXIMUM ENERGY ABSORPTION
140 Joules L – N
140 Joules L – E
TERMINAL CAPACITY
2 x 6mm²
3 x 4mm²
3 x 2.5mm²
3 x 1.5mm²
PHYSICAL
AMBIENT OPERATING TEMPERATURE
-5°C to +40°C
THERMAL OVERLOAD
The K1826 and K2826 filter socket incorporates a
thermal overload device in the RFI filter section.
Overload current causes temperature rise, resulting in
automatic ‘trip out’. The overload device will re-set as
the temperature falls.
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
mkelectric.co.uk
Description
A range of sockets in the Logic Plus and Albany Plus styles, designed to combat
interference to or data losses on sensitive electrical products and systems due to
mains borne voltage spikes and RFI.
Such systems include:
l
Computer or microprocessor based equipment
l
Telecommunications systems
l
Electronic measurement equipment
l
Cash registers
l
Audio visual and hi- equipment
These products can be quickly installed as replacements for existing twin 13A
sockets or in a new installation.
Fitted with two earth terminals to provide a double earth facility for use when
installations require a high integrity protective connection as specied within the
latest edition of BS7671.
Filter cassettes
Filter cassettes are supplied with sockets and have an LED which shows green
under normal conditions but will turn red or extinguish when a replacement cassette
(K1800WHI) is required. An alarm will also beep at 5 second intervals to indicate
replacement necessity. It can be de-activated if required.
changes from green to red when
replacement required
l
Simple replacement of cassettes
l
10 year guarantee (except filter
cassette)
l
3mm minimum switch contact gap
l
Backed out and captive terminal
screws
Technical Hotline
Audible warningconnector
Audible warningconnector
Audible warning
+44 (0)1268 563720
Wiring Devices Technical
Filtered Switchsocket Outlets
WIRING DEVICES
Product features
Ensure that the connecting pins protruding from the bottom of
the replacement Filter Cassette are not damaged or bent before
installation. If in doubt, contact MK Technical Sales Service
Department on +44 (0)1268 563720.
The MK Filtered Switchsocket, in common with many other
lters uses Voltage Dependant Resistors for spike suppression
purposes. The performance of these devices will eventually
degrade with use to a level where they will no longer provide
adequate protection.
When this occurs the spike ler performance of the MK Filtered
Switchsocket outlet can be restored by replacing the lter cassette.
When the lter cassette needs replacing, the green indicator on
the Replacement Filer Cassette will glow red or go out, an audible
beep every ve seconds may also be heard.
Note: As with all lters, these Filter Sockets will reduce the magnitude
of RFI and spikes and consequently their ability to interfere with
connected equipment. They will not completely remove the
interference from the supply.
Filter indicator
Figure 1
Audible warning
connector
Replacement
filter cassette
Figure 2
4. Fit the new lter cassette by carefully sliding it into the aperture
and gently pushing it down while turning the screw clockwise
until the lter cassette is ush with the surface. Do not turn
the screw any further as this will cause distortion of the plastic
mouldings.
Product and packaging can safely be disposed of via standard
refuse facilities at the end of its useful life.
Figure 2a
Locking screw
Installation
Replaceable Spike Filter Cassette
Note: To ensure a safe installation;
l
this product should be installed by a competent person.
l
it is important that all connections are made as instructed.
1. The lter cassette can be removed and replaced without switching
off the mains or removing any plugs from the lter socket.
2. Remove the lter cassette by turning the jacking screw anti-
clockwise to partially eject it (see Figure 2), and then gently
pulling the cassette upwards, (see Figure 2a).
3. Only t the MK Replacement Filter Cassette (K1800WHI).
Unpack the new ler cassette and check that the pins along the
bottom edge are not bent or broken. If these pins are damaged,
do not t the replacement cassette. The audible sound indicating
that the lter cassette needs replacing, is optional. It may be
prevented by removing the small connector on the two end pins,
(see Figure 2b), before tting it into the socket.
Figure 2b
connector
451
Wiring Devices Technical
WIRING DEVICES
Round Pin Socket Outlets
Standards and approvals
Round pin socket outlets comply with
BS546:1950.
TECHNICAL SPECIFICATION
ELECTRICAL
VOLTAGE RATING
250V a.c.
TERMINAL CAPACITIES
2A sockets:
7 x 1mm²
4 x 1.5mm²
2 x 2.5mm²
1 x 4mm²
5A sockets:
3 x 2.5mm
2 x 4mm
2 x 6mm
15A sockets:
3 x 2.5mm²
3 x 4mm²
2 x 6mm² (stranded)
PHYSICAL
AMBIENT OPERATING TEMPERATURE
-5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
²
²
²
(stranded)
mkelectric.co.uk
Description
A range of round pin socket outlets designed for ease of installation and having all
the advantages and design features of the MK range of wiring devices.
These products can be quickly installed as replacements for existing socket outlets
or in new installations.
FEATURES
l
Top access terminals make wiring
easier and quicker
l
Integral ON indicator on plastic
switches will not rub off – totally safe
l
Switch contact gap, 3mm minimum
l
Double pole switching
l
Terminal screws backed out
l
Additional electrical safety from
neutral “make first”, “break last”
feature on switched sockets
l
Switch contacts with silver contact
points on both surfaces for good
continuity
l
5A and 15A sockets contain a 3 pin
operated safety shutter.
l
Printed terminal markings on grey rear
mouldings for clearer identification
452
Technical Hotline
+44 (0)1268 563720
Wiring Devices Technical
Non UK Socket Outlets
WIRING DEVICES
Standards and approvals
15A American sockets comply with
SASO2004:2003
16A 2P+E German sockets comply with
IEC60884-1:2006
TECHNICAL SPECIFICATION
ELECTRICAL
15A AMERICAN
VOLTAGE RATING
127V a.c.
CURRENT RATING
15A
TERMINAL CAPACITY
Live, neutral & earth
3 x 2.5mm²
2 x 4mm²
1 x 6mm² (stranded)
MAX. INSTALLATION ALTITUDE
2000 metres
16A 2P+E GERMAN SOCKET
VOLTAGE RATING
250V a.c.
CURRENT RATING
16A
TERMINAL CAPACITY
Live, neutral & earth
4 x 1.5mm²
2 x 2.5mm²
1 x 4mm²
PHYSICAL
AMBIENT OPERATING TEMPERATURE
-5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
15A AMERICAN (Logic Plus*)
BOX TYPES
GANGFLUSH
1 GANG861ZIC866ZICK2140WHI
2 GANG862ZIC886ZICK2142WHI
(FOR EXTRA WIRING SPACE)
FLUSH
SURFACE
16A 2P+E GERMAN (Logic Plus*)
BOX TYPES
GANGFLUSHSURFACE
1 GANG861ZICK2140WHI
2 GANG862ZICK2142WHI
Note: 16A 2P+E German Outlet: These products are NOT suitable for
25mm deep boxes.
*15A American Sockets and 16A 2P+E German Sockets are also
available in a modular format for MK decorative wiring device ranges.
453
L2L1N
L2L1N
N
Rear view of
Fan Isolator
Rear view of
Fan Isolator
Rear view of
Fan Isolator
Rear view of
Fan Isolator
L (switched)
N
L
Supply
L2L1N
L2L1N
N
L (unswitched)
To Fan Unit with Timer
(see Fan Unit Intructions)
L (switched)
N
L
Supply
L2L1N
L2L1N
N
L (unswitched)
To Fan Unit with Timer
(see Fan Unit Intructions)
L (switched)
N
L
Supply
L2L1N
L2L1N
N
To Fan Unit without Timer
(see Fan Unit Intructions)
To Fan Unit without Timer
(see Fan Unit Intructions)
L (switched)
N
L
Supply
Three pole switching for fan units incorporating timers
Two pole switching for fan units without timers
TOP
TOP
TOP
TOP
Wiring Devices Technical
WIRING DEVICES
Three Pole Fan Isolators
Standards and approvals
Comply with BSEN60669-2-4:2005
TECHNICAL SPECIFICATION
ELECTRICAL
VOLTAGE RATING
250V a.c.
CURRENT RATING
10A
RATED CONDITIONAL SHORT
CIRCUIT CURRENT (Inc)
3000A
TERMINAL CAPACITY
4 x 1mm²
4 x 1.5mm²
3 x 2.5mm²
2 x 4mm²
1 x 6mm²
CONTACT GAP
4mm switch contact gap
RECOMMENDED SCPD
GE Power Controls TIA32M40 32A IEC269-2-1 Fuse-link
PHYSICAL
AMBIENT OPERATING TEMPERATURE
-5°C to +40°C
IP RATING
IP4X
MAX. INSTALLATION ALTITUDE
2000 metres
Features
l
Switchlock list no. K4858 is available to allow
the isolator to be locked in the disconnected
position to facilitate fan maintenance
mkelectric.co.uk
Description
The MK Three Pole Fan Isolator provides a safe and simple method of isolating
mechanical fan units and is particularly useful in bathrooms, toilets, storerooms and
basements where there is little or no natural light.
For example, timer controlled fans are often linked into the lighting circuit for energy
saving and convenience. In such an installation there is often a need for the lighting
circuit to remain live to provide light whilst the fan unit is externally isolated so that
routine maintenance and repairs can be carried out in complete safety.
The fan isolator can be used as a double pole or triple pole isolator. In addition it
includes a clear on/off indicator and the frontplate features a fan isolator symbol for
easy circuit identication.
Wiring diagrams
454
Technical Hotline
+44 (0)1268 563720
Wiring Devices Technical
Shaver Socket Outlets
Standards and approvals
Shaver socket outlets comply with
BS4573:1970 and IEC60884-1:2006.
Plug pin apertures, and engagement face
dimensions comply with BS4573:1970.
TECHNICAL SPECIFICATION
ELECTRICAL
VOLTAGE RATING
200-250V a.c. Input
MAXIMUM LOAD
200 mA (internal thermister trip current)
TERMINAL CAPACITIES
Each terminal will accommodate
1 x 4mm², or 2 x 2.5mm², 3 x 1.5 solid conductors
PHYSICAL
AMBIENT OPERATING TEMPERATURE
-5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
WIRING DEVICES
– Logic Plus™
Description
Designed for ease of installation and having many of the advantageous features of
the Logic PlusTM range.
The shaver socket outlet accommodates the following plugs:
British 5mm dia pins on 16.6mm pitch (230V socket) to BS4573:1970.
European 4mm dia pins on 17 to 19mm pitch (230V socket) to IEC 83:1975
Standard C5.
Australian 6.5 x 1.6 at blades each set at 30° to the vertical on a nominal pitch of
13.7mm (230V socket).
AS C112:1964.
The fuse carrier is captive and opened by a fast acting, screwdriver operated worm
drive screw for ease of replacement.
FEATURES
l
Top access terminals make wiring
quicker and easier
l
Only one size of screwdriver required
for installation
l
Terminal screws supplied ‘backed out’
and held captive within the terminal
moulding
l
White printed terminal markings
on grey rear mouldings for clearer
identification
l
Front plate fixing screws retained on
rear case moulding
Installation
This shaver socket must not be used in bathrooms and washrooms. Non-isolated,
fused, shaver socket outlets must never be installed in any location subject to
splashes, condensation or damp conditions.
For installation in any other room where a wash basin or shower cubicle is installed
then refer to the current IET wiring regulations.
455
Wiring Devices Technical
WIRING DEVICES
Shaver/Toothbrush Supply Units
Standards and approvals
Shaver/Toothbrush supply units comply with
BS61558-2-5:1998
Accommodates plugs as follows:
l
British 5mm dia pins on 16.6mm pitch (230V
socket) to BS 4573:1970.
l
European 4mm dia pins on 17 to 19mm pitch
(230V socket) to BS EN 50075
l
Australian 6.5 x 1.6 at blades each set
at 30° to the vertical on a nominal pitch of
13.7mm (230V socket) AS/NZS 3112:2000
l
American 6.6 x 1.6 at horizontal blades
on 12.7mm pitch (115V socket) to UL498 /
NEMA WD6.
TECHNICAL SPECIFICATION
ELECTRICAL
VOLTAGE RATING
K701: 230V a.c. Input (will operate at 220-250V a.c.)
K706: 127V a.c. Input (will operate at 110-130V a.c.)
A range of 13A fused connection units and 20A DP switches designed for the
connection of refrigerators, water heaters, central heating boilers and other xed
appliances.
The ranges are designed for ease of instal la tion and have the advantageous design
features of the MK range of wiring devices.
Neon indicators
Products are available with Neon indicators included in the rockers of the switched
connection units. In the case of unswitched units, they are positioned centrally and
uppermost on the face plate. Neon indicators are integrally wired into the product
and do not require separate connection when installing. The design gives 175°
visibility in the horizon tal and vertical planes.
Fuse carriers
These are captive and are opened by a fast acting, screwdriver operated worm
drive for ease of replacement. A tamper-proof version is also available.
Fuse carriers can be locked open using a padlock, List No. K2000.
Flex outlets
Bottom outlet types are supplied with blanking plug allowing use where the bottom
outlet is not required.
The products are equipped with very strong, push-t nylon cord grips making
installation safe, quick and easy.
Flex outlet plate
An unfused ex outlet with cord grip and 3 pairs of terminals.
Installation
Wiring
Products must be installed in accordance with current IET Regulations.
WIRING DEVICES
Changing Fuses
1. Unscrew the fuse carrier screw to partially eject the carrier.
2. Carefully lever the carrier out further to remove the fuse.
Note: The carrier does not come fully out.
3. Always replace with a BS 1362 type fuse (as used in 13A plugs) of the correct
rating.
4. Consistent fuse blowing could mean a faulty appliance. If in doubt, consult a
qualied electrician.
5. Push carrier back until engaging with jacking screw. Screw the carrier down until
ush with surface of the plate. Do not over tighten the screw.
457
Wiring Devices Technical
WIRING DEVICES
13A Connection Units, 20A Switches and Flex Outlets
FEATURES
l
Optional indicators in the switch rockers with
175° visibility in the horizontal and vertical
planes
l
Worm-drive operated fuse carriers for
additional security (tamper-proof version
available)
l
Fuse carrier lockable in open position
l
All supply and load cables can be cut and
stripped to the same length
l
Integrally wired Neon indicators save
installation time
l
Push-fit cord grips, for safer, quicker
installation
l
Angled, top mounted terminal screws simplify
wiring
l
Moulded ‘on’ indicator flash on switches cannot
rub off – totally safe
l
Captive fuse carrier
l
Additional electrical safety from DP Switch,
neutral ‘make first’, ‘break last’ feature
l
Secure cable and flexible cord connection
l
All terminal and fixing screws operated by one-
size (4mm) screwdriver
l
Backed out and captive terminal screws
mkelectric.co.uk
Supply and load cable cords cut
and stripped to same length
Blanking plug for
bottom outlet
Bottom outlet and
cord grip
Note: These switches are not recommended for
switching large banks of PCs
Front outlet cord gripLockable fuse carrier
K1090WHI Flex Outlet
Supply and non exible load
cables
458
Technical Hotline
+44 (0)1268 563720
Wiring Devices Technical
20A Key Operated Fire Alarm Isolator Switch
TECHNICAL SPECIFICATION
ELECTRICAL
VOLTAGE RATING
250V a.c.
CURRENT RATING
20A
TERMINAL CAPACITIES
Live, Neutral & Earth
3 x 2.5mm²
3 x 4mm²
2 x 6mm²
PHYSICAL
AMBIENT OPERATING TEMPERATURE
–5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
Description
The isolators comply with BS 60669-2-4:2005
The Isolator is intended for use with building alarm systems that are required to
comply with BS 5839 Part 1.
FEATURES
l
The built in lock ensures power cannot
be provided without the key being
operated, making it safe to carry out
maintenance to fire alarms
l
Printed terminal markings on grey
rear of the switch moulding for clearer
identification
l
Double Pole switching
l
Only one size of screwdriver required
WIRING DEVICES
for installation
Note: The lock tted to these isolators is universal for all MK 20A Isolators in the range
i.e. a common key pro le.
However, the keys are different to those used on all other MK Key Operated Switched Products,
for added security.
459
Wiring Devices Technical
WIRING DEVICES
High Current Switches and Cooker Control Units
Standards and approvals
All DP switches in the range comply with
BSEN60669-1:1999.
All Cooker Control Units in the range comply
with BS4177:1992.
Cooker Connection Unit comply with
BSEN60670-22:2006
TECHNICAL SPECIFICATION
ELECTRICAL
VOLTAGE RATING
250V a.c.
CURRENT RATING
32A Switch
45A Cooker Control Unit
45A Cooker Connection Unit
50A Switch (Resistive Load)
SWITCH
3mm contact gap
Double pole operation –
except socket switch on Cooker Control Units
TERMINAL CAPACITY 50A SWITCHES
Cooker Control Units, and Cooker Connection Units:
4 x 4mm²
3 x 6mm²
1 x 10mm²
1 x 16mm²
TERMINAL CAPACITY, 32A SWITCH
3 x 2.5mm²
2 x 4mm²
1 x 6mm²
PHYSICAL
AMBIENT OPERATING TEMPERATURE
-5°C to +40°C
IP RATING
IP2XD
Cooker Control Units
IP4X
32A Switch, 50A Switch, Cooker Connection Unit
MAX. INSTALLATION ALTITUDE
2000 metres
mkelectric.co.uk
Description
A range of switches and cooker control units suitable for the switching of all
domestic, commercial and industrial appliances where higher current ratings are
required, i.e. cookers, heaters, units etc. Metal units are particularly suitable for
refurbishment projects.
FEATURES
l
Positive switch action
l
Positive double pole switching
l
Toggle action switches
Note: These switches are not recommended for
switching large banks of PCs
l
Metal front plates available
l
Replaceable neon indicators
l
Wide product choice
460
Technical Hotline
+44 (0)1268 563720
Plateswitches
Standards and approvals
All MK plateswitches comply with
BSEN60669-1:1999.
TECHNICAL SPECIFICATION
ELECTRICAL
VOLTAGE RATING
250V a.c.
CURRENT RATING
10A – no derating when used on fluorescent
or inductive loads
20A – no derating when used on fluorescent
or inductive loads
Push / Retractive switch types are not intended for
fluorescent loads.
TERMINAL CAPACITY
4 x 1mm²
4 x 1.5mm²
3 x 2.5mm²
2 x 4mm²
1 x 6mm²
CONTACT GAP
3mm switch contact gap
PHYSICAL
AMBIENT OPERATING TEMPERATURE
-5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
Operational testing (all plateswitches): tested to
100,000 operations for mechanical life tested to
40,000 operations at 10A rating tested to 10,000
operations at 20A rating.
Wiring Devices Technical
Description
MK plateswitches are designed to blend in with the decor, whilst complementing
a wide range of other MK wiring devices. They are designed for easy installation
in plasterdepth boxes and are suitable for controlling lighting circuits in domestic,
commercial and industrial applications.
Neon locator
A textured, polycarbonate moulding allowing the glow of the neon to be seen
at almost any angle. Designed to complement the Logic Plus 1, 2, or 3 gang
plateswitches.
It is easy to install in existing locations. For 3 gang applications using a 25mm deep
box simplies wiring.
FEATURES
l
Two way switches can be wired as one or two
way
l
Matching Grid switches available in 10 or
20A ratings
l
3mm switch contact gap
l
Positive switch action
l
Top access, backed out and captive terminal
screws
l
Neon locator available making switch easy to
find in darkened rooms (Logic Plus
TM
only)
WIRING DEVICES
461
N
L
1
Common
Lamp/s
N
L
1
Common
Lamp/s
N
L
Lamp/s
2
1
Common
1
2
Common
Two-way switches
Dotted lines show alternative switch positions
N
L
1
Common
Lamp/s
N
L
Lamp/s
2
1
Common
1
2
Common
Two-way switches
Dotted lines show alternative switch positions
N
L
2
1
Common
2
1
Common
Two-way switches
Dotted lines show alternative switch positions
Lamp/s
SW.L
N
L
1
Common
Lamp/s
N
L
Lamp/s
2
1
Common
1
2
Common
Two-way switches
Dotted lines show alternative switch positions
N
L
2
1
Common
2
1
Common
Two-way switches
Dotted lines show alternative switch positions
Lamp/s
SW.L
N
L
1
2
Common
2
1
Common
Two-wayswitch
Two-wayswitch
Dotted lines show alternative switch positions
Lamp/s
1
1
2
2
Intermediateswitch
Dotted lines show alternative switch positions
Wiring Devices Technical
WIRING DEVICES
Plateswitches
Wiring diagrams
One-way switching
L
N
Two-way switching – 2 wire control
mkelectric.co.uk
Common
1
Lamp/s
L
N
Two-way switching plus intermediate switching
– 2 wire control
L
N
Lamp/s
Two-way switching – 3 wire control
L
N
Lamp/s
Two-way switching plus intermediate switching
– 3 wire control
L
N
Lamp/s
Common
Two-way switches
1
2
Dotted lines show alternative switch positions
Common
Two-way
switch
2
1
Dotted lines show alternative switch positions
Common
Two-way switches
1
2
SW.L
Dotted lines show alternative switch positions
Common
Two-way
switch
1
2
SW.L
Common
2
1
Lamp/s
2
1
Intermediate
1
2
switch
Common
1
2
2
1
Intermediate
1
2
switch
Common
Two-way
switch
1
2
Common
Two-way
switch
1
2
462
N.B. Terminal positions may alter. The above diagrams are to
show wiring layout.
Technical Hotline
+44 (0)1268 563720
Wiring Devices Technical
Dimmer Switches
Standards and approvals
All CE marked Logic Plus™ dimmer switches
comply with the EC Low Voltage
They also comply with BS EN 60669-2-1 and
IEC 60669-2-1 (LED Intelligent Dimmer only)
*Non-UK dimmer switches see note below
TECHNICAL SPECIFICATION
ELECTRICAL
MAINS SUPPLY VOLTAGE
230V a.c. (Nominal)
220V a.c. (Nominal, Non-UK)
220V a.c. to 240V a.c. (For LED Intelligent Dimmer)
MAINS SUPPLY VOLTAGE RANGE
216V a.c. to 253V a.c.
200V a.c. to 250V a.c
198V a.c. to 264V a.c. (For LED Intelligent Dimmer)
MAINS SUPPLY FREQUENCY
50Hz ±3Hz
60Hz ±3Hz
TYPE OF LOADS
STANDARD DIMMERS
Fused GLS Tungsten Filament lamps only to
BSEN60064:1996 and BSEN60432-1:2000,
rated at 230/240V
INTELLIGENT DIMMERS AND
LED INTELLIGENT DIMMERS:
Fused GLS Tungsten Filament lamps to
BSEN60064:1996 and BSEN60432-1,2 rated at
230/240V. Dimmable wire wound or electronic Low
Voltage Transformers of good quality. Can also be
used with good quality mains voltage halogen lamps
incorporating GU10 bases. Please check with lamp
manufacturer to determine suitability.
Note: Transformer must be suitable for dimming
using phase delay (leading edge) and NOT only
phase cut (trailing edge) type of dimmers.
Warning: These dimmer switches are not suitable
for use with Fluorescent Lamps or Energy Saving
Lamps.
PHYSICAL
AMBIENT OPERATING TEMPERATURE
0°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
WIRING DEVICES
Description
MK dimmer switches can fall into one of four categories
1) Standard Dimmer Switches
2) Intelligent Dimmer Switches
3) Non-UK Dimmer Switches
4) LED Intelligent Dimmer Switches
Standard Dimmer Switches
Dimmer Switches belonging to this category employ simpler electronic circuitry and
the CE marked products make use of thermal switches to conform to the very stringent
requirements of the Standard BS EN 60669-2-1, for overload protection. They are only
suitable for use with normal tungsten lament lamps, conforming to BS EN 60064:1996
and BS EN 60432-1 Standards and do not have any added features, e.g. soft start,
ability to control dimmable transformers for low voltage, etc.
Standard Dimmer Switches are not suitable for use with transformers for Low Voltage
Lighting or Fluorescent Loads, including Energy Saving Lamps.
Intelligent and LED Intelligent Dimmer Switches
Dimmer Switches belonging to this category, employ the latest, state of the art,
micro-controller based electronic circuitry and use current sensing to compute the
load conditions. These products show progressive reaction to overload conditions,
depending on the extent of overload as shown in the table below. List numbers
belonging to this category are identied by the suffix letters LV, e.g. K1501WHILV.
All MK Intelligent Dimmer Switches employ one pole change over switches to
facilitate two way switching.
MK Intelligent and LED Intelligent Dimmer Switches are not suitable for use with
Fluorescent Loads, including Energy Saving Lamps.
*Non-UK Dimmer Switches
Dimmer switches belonging to this category only conform to the relevant parts of
BSEN66069-2-1. Loads suitable for use with standard dimmer switches above are
also suitable for use with this category of dimmer switch.
Only one Dimmer Switch can be used in a two-way switching circuit.
463
Push to
switch OFF
Push to
switch ON
Max
Push to
switch OFF
Wiring Devices Technical
WIRING DEVICES
Minimum Brightness Adjustment for LED Intelligent Dimmers
The light output of some LED lamps may appear to be too dim or invisible when the dimmer knob is at the minimum dim level. Follow the
steps below to adjust the minimum brightness level. This feature is primarily for adjusting the minimum brightness level of the LED lamp
although it can be used for other load types.
For a double gang dimmer, the light level of each gang has to be adjusted separately.
Step 1 – Access To Programming Mode
1. Push the dimmer knob so that it is in OFF state.
2. Set the dimmer knob to minimum level.
mkelectric.co.uk
Min
3. Turn on the dimmer and immediately rotate the knob 3 times in full rotary span within 5 seconds.
MaxMin
NOTE: Wait for 3 seconds, the lamp will then dim to minimun before automatically brightening to about 30% level. Turning/pushing the dimmer
knob before the end of automatic brightening will end access to programming mode
4. Dimmer enters programming mode.
Step 2 – Adjust Brightness Level and Exit Programming Mode
5. Rotate the dimmer knob anticlockwise to adjust the lamp to the desired brightness level.
NOTE: Some LED lamps may not work properly if the brightness level is set too low thus it is recommended to keep the brightness level of
the lamp at a visible level. The dimmer will exit programming mode automatically without saving the new setting if there is no dimmer knob
movement for 15 seconds. The dimmer will restore its factory default light level.
Turn anticlockwise to adjust
Min
6. Con rm the new setting and exit programming mode by turning OFF the dimmer.
7. The next time the dimmer is turned on the lamp will automatically brighten to the maximum level before dimming to the brightness
level corresponds to the knob level.
Technical Hotline
+44 (0)1268 563720
Wiring Devices Technical
Dimmer Switches
FEATURES
Intelligent and LED Intelligent Dimmer Switches
incorporate the following advancedfeatures
l
Suitable for dimming Low Voltage Halogen lamps via good quality,
fully dimmable electronic or wire-wound transformers. In addition,
LED Intelligent dimmer switches are suitable for dimmable LED bulbs
for incandescent replacement.
l
Can be used with good quality mains voltage halogen lamps
incorporating GU10 bases. Please check with lamp manufacturer to
determine suitability
l
Load current sensing:
These dimmers continuously monitor the load current to help protect
against overheating in wire wound transformers and to prevent
overloading of the dimmer for long term reliability
l
Soft Start, which gradually increases the light output from the load
over 1 to 3 seconds after switch on. The Soft Start feature is also
particularly beneficial when used to dim Mains Voltage Tungsten
Halogen lamps which inherently have a very high inrush current at
switch on
Standard Dimmer Switches
l
Suitable only for use with fused GLS Tungsten Filament lamps to
BSEN60064 and BSEN60432-1
l
One way dimmer switches incorporate manual soft start
l
Incorporate thermal switches for protection against overload
WIRING DEVICES
LOAD TYPES AND LOADINGS
DIMMER SERIESDIMMER SIZE
INTELLIGENT
DIMMER SWITCHES
STANDARD DIMMER
SWITCHES
LED INTELLIGENT
DIMMER SWITCHES
Do not connect more than the maximum number of transformers stated for each dimmer.
One-way switching
L
Supply 230V a.c. - 50Hz
N
(1GANG)
GLS AND MAINS
VOLTAGE HALOGEN
single dimmer 40-300W 40-240W/VA –4 –
double dimmer 2 x 40-300W 2 x 40-240W/VA –4 per dimmer –
single dimmer 60-500W 60-400W/VA –5 –
single dimmer 40-250W – –––
double dimmer2 x 40-250W––––
single dimmer 65-450W– –––
single dimmer 40-300W 40-240W/VA 4-70W 4 10
double dimmer 2 x 40-300W 2 x 40-240W/VA 2 x 4-70W 4 per dimmer 10 per dimmer
Do not unwind the twists in the wire pairs by more
than 13mm max.
Description
Suitable for use in all LJU6C and Euro frontplates, available in the Logic Plus range,
Cat 5e and Cat 6 modules suitable for use in structured cabling distribution systems.
Installation details and wiring diagram illustrations
TIA WIRING SCHEME COLOUR CODES
PIN NO.568A568B
1WHITE / greenWHITE / orange
2GREEN / whiteORANGE / white
3WHITE / orangeWHITE/ green
4BLUE / whiteBLUE / white
5WHITE / blueWHITE / blue
6ORANGE / whiteGREEN / white
7WHITE / brownWHITE / brown
8BROWN / whiteBROWN / white
Euro and LJU6C modules are to be wired as follows
7
1
8
2
3
456
RJ45 Cat.5e Euro K5845
2
468
1
3
6
RJ45 Cat.5e LJU6C K5745
8
2
4
5
2
1
6
3
RJ45 Cat.5e Euro - Angled K5844
RJ45 Cat.6 Euro - Angled K5746 - LJU6C
K5846 - Euro, K5864 - Euro Angled
8
2
7
1
6
1
7
4
5
4
3
5
RJ45 Cat.6 Screened
K5746S - LJU6C, K5846S - Euro
8
2
7
1
6
4
3
5
RJ45 Cat.5e Screened
K5845S - Euro
Technical Hotline
+44 (0)1268 563720
Wiring Devices Technical
Telephone, RJ11/12, BNC Data and Blank Modules
Standards and approvals
Telephone sockets K5820 and K5821 comply
with the following:
BS 6312: 2.2
Data sockets K5801, BS 5733: 2010
(where applicable).
IP2XD – K5820, K5821, K5801 and K5787.
IP4X – K180, K188, K186 and K170
MAX. INSTALLATION ALTITUDE
2000 metres
Description
A range of telephone, data and blank modules to t Euro and LJ6UC front plates.
BNC Euro modules with a 50Ohm crimp connector suitable for use with RG58,
URM43, URM76 and Beldon 9907 type co-axial cables are also available.
Installation (Telephone socket modules)
Product performance, systems compatibility
Master Sockets: For use as the rst socket outlet on a direct exchange. They
contain the required surge protector (for line protection against electrical surges)
and ringing capacitor.
Secondary Sockets: for use as extension sockets when connected on the same line
as a Master Socket.
‘F’ TYPE SATELLITE SOCKET (K3525), CABLE
SPECIFICATION
Co-axial cable: inner core diameter – 0.5-1.2mm
RJ11 (K4817), CABLE SPECIFICATION
Capable of taking 0.08 to 0.65mm² solid or stranded
cable
PHYSICAL
AMBIENT OPERATING TEMPERATURE
--5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
Description
A part of the very wide range of products to meet the latest technical requirements
and the standards applicable to modern technology in the installation of telephone
and television equipment. The master and secondary telephone sockets K422 and
K427 comply with relevant approvals for direct and indirect connections between a
termination point of a public telecommunications system and any piece of approved
telecommunications apparatus. For applications requiring twin or dual telephone
outlets, refer to the Modular Data section, pages 46-48.
Telephone and TV sockets t into plaster depth boxes (except for RJ11).
The F-type Satellite Socket may be used for connection of CATV, MATV and
satellite TV installations.
FEATURES
l
Single screw termination on TV outlets
l
Protected, fully enclosed PCBs
l
Meet all relevant BS requirements
l
Quick, simple and reliable terminal
connection
l
IDC connectors on telephone outlets
l
Part of a complete range of products
for telephone, television and data
processing requirements
l
Angled connector on TV outlets
l
Sockets fit in plaster depth boxes
(except K4817)
471
123456123456
First Socket Outlet
Master
Extension Outlet
Secondary
Wiring Devices Technical
WIRING DEVICES
Telephone, TV/FM and Satellite Socket Outlets
Installation (Telephone sockets)
Product performance, systems compatibility
Master Sockets: for use as the rst socket outlet
on a direct exchange or PABX line. They contain
surge protector (for line protection against
electrical surges) and ringing capacitor.
Secondary Sockets
For use as extension sockets when connected
on the same line as a Master Socket.
Installation tools required
MK IDC insertion tool List No. 400NAT (not
supplied with product).
mkelectric.co.uk
Wiring regulation restrictions
Domestic installations
Any number of MK sockets may be installed
thereafter, with a total REN (Ring Equivalent
Number) value of all telephone equipment
connected on a line not exceeding 4.
Telephone Wiring
Scheme
1 GREEN / white
2 BLUE / white
3 ORANGE / white
4 WHITE / orange
5 WHITE / blue
6 WHITE / green
Note: Main wire colour is shown in capitals
IDC
terminals
3
2
1
4
5
6
Cable Tie
fixing point
Cable tie
472
Technical Hotline
1
2
3
4
+44 (0)1268 563720
Wiring Devices Technical
Digital TV and Telephone Outlets
(Logic Plus and Modular Datacoms)
Installation (TV sockets)
Product performance, systems compatibility
Isolated Outlets are intended for use where
safety isolation (rated at 2000V ac) is required to
provide protection against faults occurring within
any mains powered product used on different
parts of the distribution system. They are not
suitable for use in systems where DC signals
are passed through the socket, (e.g. where
masthead/headend equipment is controlled by
receiver/decoder equipment).
Diplexer Outlets are used in distribution
systems where both TV and FM band signals
are combined on a single aerial downlead. The
ltering in the diplexer separates the appropriate
signals and feeds them through to the relevant
output connection port.
TV
VID
FM
TV DIST
3
4
DAB
1
WIRING DEVICES
TV
SAT 2
4
SAT 1
TV
TV
HI-FI
2
Cable Routing and Use of Cable Clamp
Sharp bends in the cable must be avoided
during installation. The single TV/FM socket is
tted with a cable clamp that can be xed on
either side of the termination position to facilitate
this.
When tightening the screening braid clamps
ensure that the cable is rmly gripped and that
the inner insulation is not squashed at beyond
a slight oval shape.
Safety Information
TV outlets or modules must not be installed
in the same enclosure as equipment rated in
excess of 50V, (e.g. mains rated 13A sockets or
switches).
TV
Method of installation of TV and FM aerial connection by using MK coaxial socket outlet and only one downlead.
Conventional distribution system for TV and FM signals using a single
aerial downlead.
The signals from the TV and FM aerials and the satellite dish are
combined together using two products. The rst combines the TV
and FM signals and the second adds the Sky signal to the TV/FM
signal and provides a DC control path to power the LNB unit on
the satellite dish. (These products are not supplied by MK).
The single aerial down lead feeds into the triplexer (black lines in
wiring diagram).
The separated satellite signal is then fed to the decoder. The
decoded satellite signal is then fed into the VCR along with the
TV signal from the Triplexer. The output signal from the VCR then
feeds into the TV and also back to the single outlet and onto the
distribution amplier (black lines in wiring diagram).
The single cable back-feed then feeds back to the input of a multi
way distribution amplier, (typically located in the loft or garage)
(red lines in wiring diagram).
Each individual output from the distribution amplier is then fed
to the individual rooms in the house to a standard TV (single
or diplexer) outlet to which the TV/VCR and/or Hi-Fi can be
connected (blue lines in wiring diagram).
4
VID
SKY/DIG
473
Wiring Devices Technical
WIRING DEVICES
Digital TV, Radio and Telephone Outlets
Standards and approvals
All Logic Plus TV Outlets comply with BS 5733
and BS EN 50083 where applicable.
Also IEC 169-2, BS EN 60169-24 and BS 6312
Part 2
Modular products are Euro compatible.
TECHNICAL SPECIFICATION
SINGLE OUTLETS
TV/FM IEC Male or Female DC-950MHz
SATF-Type DC-1.75GHz
DIPLEXER AND TRIPLEXER PRODUCTS
TV
Diplexer:
5-65MHz
470-862MHz
Triplexer:
5-65MHz
470-862MHz
FM
Diplexer: 87.5-108MHz
Triplexer: 87.5-108MHz
SAT
Diplexer: n/a
Triplexer: 950-2300MHz
TV/FM/DAB/SAT PRODUCTS FOR
DIGITAL RADIO
TV
Diplexer:
5-65MHz
470-862MHz
Triplexer:
5-65MHz
470-862MHz
FM/DAB
Diplexer: 87.5-230MHz
Triplexer: 87.5-230MHz
SAT OR SAT1
Diplexer: n/a
Triplexer: 950-2300MHz
SAT2
Diplexer: n/a
Triplexer: 5-2300MHz
mkelectric.co.uk
Description
There are two ranges of diplexer and triplexer products, an established range
suitable for VHF TV, and a range suitable for digital radio (DAB).
Diplexer modules are for connecting to a single co-axial aerial down lead carrying
combined TV and FM signals. The ltering in the diplexer splits out the appropriate
signal and feeds it to the relevant output connection.
A DC control path is provided in the TV signal path through the diplexer.
Triplexer modules are for connecting to a single co-axial aerial down lead carrying
combined TV, FM and SAT signals. The ltering in the triplexer splits out the
appropriate signal and feeds it to the relevant output connection.
A DC control path is provided in the SAT signal path through the triplexer.
The quad outlet contains a triplexer together with a separate satellite output, for use
with Sky+, or more complex installations.
Telephone secondary outlets are provided on some products for connection of
telephone or for interactive TV applications.
Screening braid to remain in
place over the inner insulation
6.5
TV Co-axial cable stripping details
Earth
terminal
Clamping
fixing screws
View with cable
clamp removed
Cable clamp
Co-axial
cable
123456123456
First Socket Outlet
Master
Extension Outlet
Secondary
+44 (0)1268 563720
Wiring Devices Technical
Digital TV/FM and Telephone Outlets
(Logic Plus and Modular Datacoms)
WIRING DEVICES
Installation
l
When installing the TV co-axial cable ensure
that all cable bends are smooth so that the
inner insulation is not crushed or squashed,
otherwise the TV signal quality may be
affected
l
Not suitable for loop-in loop-out installations
l
Use CT100 cable (or equivalent)
Earth terminal
Cable
clamping
plate
Foil EMC
screening
gasket
Clamping
plate fixing
Co-axial
cable
screws
Telephone Outlet Connection
Carefully strip 50mm of the telephone cable outer sheath to expose the inner
insulated conductors. Using the insertion tool supplied, (MK List no. 400NAT)
carefully push each lead into the appropriate IDC terminals according to the wiring
colour code stated in the telephone Wiring Scheme diagram.
Pins 1 and 6 are frequently unused, 4 wire cable may be used in these installations.
If an existing installation uses a different wiring colour code system, this should be
retained on any new or extended installation.
Additional secondary extension outlets should be wired in parallel with the existing
installation via the IDC terminals, (i.e. pin 1 to pin1, pin 2 to pin 2, etc).
In the event that the earth terminal is required to be used, the installer must ensure
that a suitable earth conductor is present to connect to the earth terminal. (In the
case of 2G products both TV modules should be earthed).
In the event that the earth terminal is required to be used, the installer must ensure
that a suitable earth conductor is present to connect to the earth terminal. (In the
case of 2G products both TV modules should be earthed).
Telephone Wiring
Scheme
1 GREEN / white
2 BLUE / white
3 ORANGE / white
4 WHITE / orange
5 WHITE / blue
6 WHITE / green
The 4-gang Combination Plate carries 2x 2-gang
13A DP switched sockets, plus a Quad TV, FM/
DAB, Satellite outlet, single TV (IEC Female)
and an additional Telephone socket.
Additionally, there is a 4-module Euro area
capable of accommodating any additional
telephone or media products from the Euro
modular range.
TECHNICAL SPECIFICATION
FRONTPLATE
The frontplate complies with the mechanical strength
requirements of BS 5733 2010.
SWITCHED SOCKET SPECIFICATION
Compliant to BS 1363 Part 2: 1995
ELECTRICAL
VOLTAGE RATING
250V a.c.
CURRENT RATING
13 Amp
TERMINAL CAPACITY
Live, Neutral & Earth
3 x 2.5mm²
3 x 4mm²
2 x 6mm² (standard)
PHYSICAL
AMBIENT OPERATING TEMPERATURE
-5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
Quad TV, FM/DAB, Satellite outlet
& additional TV Socket
As used on K3566 WHI
BT Telephone Socket
As used on K3566 WHI
4-module Euro Housing
This portion of the plate accepts up
to 4 x 50mm high by 25mm wide
Euro modules. (100mm x 50mm
aperture)
2 Gang Plate Description
The 2-gang Combination Plate carries a 2-gang
13A DP switched sockets and an additional
4-module Euro area capable of accommodating
any additional telephone or media products from
the Euro modular range.
TECHNICAL SPECIFICATION
FRONTPLATE
The frontplate complies with the mechanical strength
requirements of BS 5733 2010.
SWITCHED SOCKET SPECIFICATION
Compliant to BS 1363 Part 2: 1995
ELECTRICAL
VOLTAGE RATING
250V a.c.
CURRENT RATING
13 Amp
TERMINAL CAPACITY
Live, Neutral & Earth
3 x 2.5mm²
3 x 4mm²
2 x 6mm² (standard)
PHYSICAL
AMBIENT OPERATING TEMPERATURE
-5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
476
Note
l
Pre-configured back boxes available shall be used
with these plates. These are 853ZIC, which is
35mm deep, and for greater wiring space 854ZIC,
which is 47mm deep
l
These back boxes should always be used to ensure
alignment of the fixing screws is correct and proper
segmentation between mains and low voltage
products is maintained
l
Mains operated products and extra low voltage
modules must not be installed within the same
front plate aperture. Refers to BS 7671 IET Wiring
regulations for detail
l
When removing the fixing screws and front plate
from an installation to gain access to low voltage
modules, please be aware that there will also be
access to the mains supply
Note
l
Pre-configured back boxes available shall be used
with these plates. These are 853ZIC, which is
35mm deep, and for greater wiring space 854ZIC,
which is 47mm deep
l
These back boxes should always be used to ensure
alignment of the fixing screws is correct and proper
segmentation between mains and low voltage
products is maintained
l
Mains operated products and extra low voltage
modules must not be installed within the same
front plate aperture. Refers to BS 7671 IET Wiring
regulations for detail
l
When removing the fixing screws and front plate
from an installation to gain access to low voltage
modules, please be aware that there will also be
access to the mains supply
Technical Hotline
+44 (0)1268 563720
Wiring Devices Technical
Combination Plate
Standards and approvals
All Aspect 13A socket outlets comply with
BS 1363: Part 2:1995.
K24209 and K24210 comply with BS 5733:2010.
TECHNICAL SPECIFICATION
ELECTRICAL
VOLTAGE RATING
250V a.c.
CURRENT RATING
13A
TERMINAL CAPACITY
Live, neutral & earth
3 x 2.5mm²
3 x 4mm²
2 x 6mm² (stranded)
(Dual earth terminals)
PHYSICAL
AMBIENT OPERATING TEMPERATURE
–5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
MOUNTING BOXES
Combination Plate
List Number
K24206870ZIC
K24207870ZIC
K24208868ZIC
K24209858ZIC
K24210869ZIC
Bespoke requirements can be achieved through
the MK Design Service to deliver variation in
colours, materials, nishes and markings.
Euro apertures can also be converted to
grid-switch. For more information please visit
www.mkelectric.co.uk or call 01268 563720
47mm
Mounting Box
– Aspect
Description
A range of combination plates designed for ease of installation and having all the
advantageous design features of the Aspect range.
These combination socket outlets provide interior designers and installers with a
stylish and practical wiring device solution. The range also has larger euro module
frontplates to house eight and twelve single euro modules without the inclusion of
xed socket outlets. The K24209 combination socket outlet, for example allows for
the inclusion of up to eight single Euro modules, which could include datacoms,
telecoms, plus TV and Satellite modules.
Alternatively, Euro Power Modules i.e. German, French/Belgium and American
socket outlets may be used.
Note:
l
Pre-congured back boxes are designed for use with the combination plates.
These back boxes should always be used to ensure alignment of the xing
screws is correct and proper segregation between mains and extra low voltage
products is maintained
l
For Aspect products, back boxes must be installed 10mm sub ush to the wall
surface
l
Mains operated products and extra low voltage modules must not be installed
within the same frontplate aperture. Refer to BS 7671: 2008 for details
l
When removing the xing screws and frontplate from an installation to gain
access to low voltage modules, please be aware that there will also be access to
the mains supply
All pre-tted sockets come complete and are tted with two earth terminals on a
common busbar to provide a double earth facility for use when installations require
a high integrity protective connection as specied within BS 7671, IET Wiring
Regulations.
WIRING DEVICES
477
Wiring Devices Technical
– Aspect
WIRING DEVICES
Combination Plate
Features
l
Metal-capped rockers designed
to match the chosen front plate
nish
l
3 pin operated safety shutter
l
Printed terminal markings on
grey rear mouldings for clearer
identi cation
l
Top access, angled terminals
make wiring easier and quicker
l
3mm minimum switch contact gap
l
Double pole switching
l
Additional electrical safety from
neutral ‘make rst’, ‘break last’
feature
l
Switch contacts with silver
contacts on both surfaces for
good continuity
l
Dual earth terminals on pre- tted
sockets are for high integrity
earthing
l
Backed out and captive terminal
screws on pre- tted sockets
l
Pre-con gured backboxes to
ensure alignment of the xing
screws is correct and proper
segregation between circuits is
maintained to comply with
BS 7671 17th Edition wiring
regulations
mkelectric.co.uk
Installation
Aspect socket outlets can only be mounted on a wall. Do not mount or use as a
trailing socket or where they may be subject to excessive moisture or dampness.
Install corresponding back box 10mm sub ush to nished wall surface.
Aspect combination plates are supplied with clip on segregator.
Dimensions (mm)
K24206 and K24207
233.3
86
K24209K24210
146.4206.3
K24208
320.6
86
478
173.3
173.3
Technical Hotline
+44 (0)1268 563720
Wiring Devices Technical
Combination Plate
Standards and approvals
All Edge 13A socket outlets comply with
BS 1363: Part 2:1995.
K14209 and K14210 comply with BS 5733:2010.
TECHNICAL SPECIFICATION
ELECTRICAL
VOLTAGE RATING
250V a.c.
CURRENT RATING
13A
TERMINAL CAPACITY
Live, neutral & earth
3 x 2.5mm²
3 x 4mm²
2 x 6mm² (stranded)
(Dual earth terminals)
PHYSICAL
AMBIENT OPERATING TEMPERATURE
–5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
MOUNTING BOXES
Combination
Plate
List Number
K14200K14201K14202
K14205K14206K14207
K14100K14101K14102
K14216867ZIC
K14217867ZIC
K14208868ZIC
K14209858ZIC
K14210869ZIC
Bespoke requirements can be achieved through
the MK Design Service to deliver variation in
colours, materials, nishes and markings.
Euro apertures can also be converted to
grid-switch. For more information please visit
www.mkelectric.co.uk or call 01268 563720
35mm
Mounting Box
47mm
Mounting Box
– Edge™
Description
A range of combination plates designed for ease of installation and having all the
advantageous design features of the Edge range.
These combination socket outlets provide interior designers and installers with a
stylish and practical wiring device solution. The range also has larger euro module
frontplates to house eight and twelve single euro modules without the inclusion of
xed socket outlets. The K14100 combination socket outlet, for example allows for
the inclusion of up to eight single Euro modules, which could include datacoms,
telecoms, plus TV and Satellite modules.
Alternatively, Euro Power Modules i.e. German, French/Belgium and American
socket outlets may be used.
Note:
l
Pre-congured back boxes are designed for use with the combination plates.
These back boxes should always be used to ensure alignment of the xing
screws is correct and proper segregation between mains and extra low voltage
products is maintained
l
For Edge products, back boxes must be installed ush to the wall surface
l
Mains operated products and extra low voltage modules must not be installed
within the same frontplate aperture. Refer to BS 7671: 2008 for details
l
When removing the xing screws and frontplate from an installation to gain
access to low voltage modules, please be aware that there will also be access to
the mains supply
All pre-tted sockets come complete and are tted with two earth terminals on a
common busbar to provide a double earth facility for use when installations require
a high integrity protective connection as specied within BS 7671, IET Wiring
Regulations.
WIRING DEVICES
Combination plates allow the use of a variety of power and data modules making
them ideal for hotels.
479
Wiring Devices Technical
– Edge™
WIRING DEVICES
Combination Plate
Features
l
Metal-capped rockers designed
to match the chosen front plate
nish
l
3 pin operated safety shutter
l
Printed terminal markings on
grey rear mouldings for clearer
identi cation
l
Top access, angled terminals
make wiring easier and quicker
l
3mm minimum switch contact gap
l
Double pole switching
l
Additional electrical safety from
neutral ‘make rst’, ‘break last’
feature
l
Switch contacts with silver
contacts on both surfaces for
good continuity
l
Dual earth terminals on pre- tted
sockets are for high integrity
earthing
l
Backed out and captive terminal
screws on pre- tted sockets
l
Pre-con gured backboxes to
ensure alignment of the xing
screws is correct and proper
segregation between circuits is
maintained to comply with
BS 7671 17th Edition wiring
regulations
mkelectric.co.uk
Installation
Edge socket outlets can be mounted on either a wall or suitable bench mounted
trunking. Do not mount or use as a trailing socket or where they may be subject to
excessive moisture or dampness.
Dimensions (mm)
K14216 and K14217
233.3
86
K14209K14210
146.4206.3
173.3
K14200
173.3
442.8
86
K14100
293.6
173.3
480
K14208
320.6
K14205
407.9
86
86
Technical Hotline
+44 (0)1268 563720
Wiring Devices Technical
Key Operated Switchsocket Outlet
Standards and approvals
All Edge 13A socket outlets comply with
BS 1363: Part 2:1995.
TECHNICAL SPECIFICATION
ELECTRICAL
VOLTAGE RATING
250V a.c.
CURRENT RATING
13A
TERMINAL CAPACITY
Live, neutral & earth
3 x 2.5mm²
2 x 4mm²
1 x 6mm² (stranded)
(Dual earth terminals)
PHYSICAL
AMBIENT OPERATING TEMPERATURE
–5°C to +40°C
IP RATING
IP2XD
MAX. INSTALLATION ALTITUDE
2000 metres
Description
The Key Operated 13 amp socket is designed for ease of installation and has all
the design features of the Edge range. The built-in lock ensures that power cannot
be provided without key operation making it ideal for communal areas such as hotel
lobbies. The key can be removed from the lock in the on or off position leaving the
socket with or without power supply.
The product can be quickly installed as replacement for existing 2 gang 13 amp
sockets or in a new installation (assuming suitable 47mm deep mounting box is in
position).
Installation
Edge socket outlets can be wall or bench mounted. Do not mount or use as a
trailing socket or where they may be subject to excessive moisture or dampness.
WIRING DEVICES
– Edge™
Features
l
Built in lock ensures power
cannot be provided without key
operation
l
Printed terminal markings on
grey rear mouldings for clearer
identi cation
Note: The lock tted to each socket is universal. i.e. a common key pro le.
However, the keys are different to those used on MK Key Operated Fire Alarm Isolator
Switches, for added security.
l
Double pole switching
l
Only one size of screwdriver
required for installation
l
Dual earth terminals for high
integrity earthing
481
Wiring Devices Technical
– Edge™
WIRING DEVICES
EdgeTM Technical: General information
mkelectric.co.uk
Mounting Boxes
Due to the slimline design MK Edge accessories
require deeper back boxes than standard. They
are designed to t into folded metal boxes that
comply with BS 4662. To ensure products can
be correctly installed, the box must always be
installed ush or sub ush to the surface to a
maximum depth of 6mm.
The recommended depth of boxes for the
different types of wiring accessories are as
follows:
MOUNTING BOXES
ProductBox Depth
Socket Outlets35mm
Lockable Socket47mm
Lockable Switch47mm
German style 2 pole + E
Socket Outlet mounted in
Euro Frame
Connection Units47mm
Plateswitches35mm
Grid System Switches*35mm
Dimmer Switches35mm
Telephone, Television and
Data Outlets
47mm
35mm
Fixing Screws
The surface head of Edge xing screws is
treated and compliment the nish of the
frontplate. To prevent damage to the xing screw
extreme care is required. It is recommended that
a screwdriver with a maximum blade of 3.5mm
is used.
Cooker Control and 50A
Switches
Shaver Supply Units47mm
32A Triple Pole and Neutral
Switch
*Note: If Grid system accessories are to be tted and
the installation requires the attachment of conduit via
nuts inside the mounting box, then it is recommended
that a box depth of 47mm is used.
47mm
List no. 5268ALM
482
Figure 1a
Apply
in
di
Figure 1a
AdjustNorth/Southto align withplate aperture
Apply a forcein thisdirection
Force appliedtowards thewall
Figure 1b
Adjust
North/South
align
apertu
wall
AdjustNorth/Southto align withplate aperture
Force appliedtowards thewall
Apply aforce in thisdirection
Force appliedtowards thewall
support frame
AdjustNorth/Southto align withplate aperture
Force appliedtowards thewall
Apply aforce in thisdirection
Force appliedtowards thewall
Gently leveraway fromwall
Bladeto bebetweennotch inplate and ramp onsupport frame
AdjustNorth/Southto align withplate aperture
Force appliedtowards thewall
Apply aforce in thisdirection
Force appliedtowards thewall
Gently leveraway fromwall
Bladeto bebetweennotch inplate and ramp onsupport frame
Slidescrewdriverup to disengageother clip
Figure 4
AdjustNorth/Southto align withplate aperture
Force appliedtowards thewall
Apply aforce in thisdirection
Force appliedtowards thewall
Gently leveraway fromwall
Bladeto bebetweennotch inplate and ramp onsupport frame
Slidescrewdriverup to disengageother clip
Gently leveraway fromwall
Blade to bebetween notch inplate and ramp onsupport frame
Figure 4
Figure 5
Technical Hotline
+44 (0)1268 563720
Wiring Devices Technical
Aspect Installation
The MK ‘Aspect’ range of products consists of the main product
complete with its support frame and clipping medium, plus a
separate frontplate. The product is mounted to the wall, after
wiring, and the front plate clipped onto the frame.
1. The frontplate is supplied loose to aid installation.
2. Make sure not to crush or deform the spring steel clips situated
along one edge of the product support frame.
3. A gasket is also supplied with each product, which may prove
useful on uneven walls. See note 5 below.
4. Using the gasket with all switches and the German socket, will
ensure full compliance with the appropriate standards.
5. Both standards set out to guarantee full engagement of the
frontplate on uneven surfaces, even when there is a mismatch
of as much as 1mm between the distance the main body of the
product is from the wall and that of the front plate.
6. Where no gasket is used, if thick wallpapers are cut such that
they t around the support frame and therefore remain under
the edge of the frontplate, full plate engagement with the clips
may be restricted.
Note: When installing Aspect do not over tighten screws, so as to prevent
damage or distortion to the product or support frame.
Frontplate Removal
1. Turn off the power supply.
2. Carefully slide a screwdriver between the ramp on the main
body of the product and the notch in the lower right hand edge
of the plate.
3. On uneven walls, make sure the screwdriver does not go
between the spring steel ramp and the wall, or damage to the
wall and/or product could result.
4. Carefully slide the blade upwards and then gently lift the
handle away from the wall, which will lever the plate away from
the rst clip. See Fig.4.
5. With the rst clip released, support the plate with one hand and
continue to move the blade to the left under.
Data products in euromounting frames
Products operating at extra low voltage levels (<50v) must not
be mounted in the same Euro enclosures as equipment rated in
excess of 50v.
Cleaning Frontplates
In order to protect the quality surface nish of the front plate,
periodic cleaning should only consist of polishing with a dry lint
free soft cloth.
FIGURE 1A
a force
this
rection
FIGURE 1B
to
with plate
re
Frontplate Installation
FIGURE 2
Gently lever
away from
wall
FIGURE 3
FIGURE 4
Gently lever
away from
wall
FIGURE 5
WIRING DEVICES
– Aspect
Adjust
North/South
to align with
plate aperture
Force applied
towards the
wall
Apply a
force in this
direction
Force applied
towards the
Blade to be
between notch in
plate and ramp on
Slide screwdriver
up to disengage
other clip
Blade to be
between notch in
plate and ramp on
support frame
Slide screwdriver
to the left to
disengage other clip
For a full range of corresponding products,
see pages 98-128 in the product selector.
Frontplate Removal
483
Wiring Devices Technical
WIRING DEVICES
Decorative Technical: General information
Earthing: All Metal Frontplate Products
To comply with the latest edition of the BS7671 IET regulations: the metal front
plate must be earthed. All earth terminals provided must be connected to the
protective earth conductor.
Telephone Secondary and Data Sockets
To provide customers with a high level of exibility the voice and data decorative
wiring devices are available in modular formats.
For example to produce a Telephone Secondary Socket the following items are
required:
RANGEPRODUCTS REQUIRED
mkelectric.co.uk
Albany PlusK181K5821
AspectK24181K5821
EdgeK14181K5821
Or
RANGEPRODUCTS REQUIRED
Albany PlusK182K58212 x K186
AspectK24182K58212 x K186
EdgeK14182K58212 x K186
484