MK SENTRY RCBO User Manual

SENTRY®RCBO
(Residual Current Operated Circuit Breaker with Integral Over-Current Protection)
Contents
Please leave this leaflet with the end user for future reference
52778PL Rev BB
2
ln this range of Single Module Width RCBO’s, each product provides dual protection; from Over-current via its MCB section, and from Earth Leaking Fault Current (Residual Current) via its RCD section.
These devices provide RCD protection in full compliance with the requirements of the Standard BS EN 6100 9-1. They also provide very effective RCD protection in the Supply Voltage Range of 110V to 253V a.c., meeting the requirements of the Standard for sensitivity and trip speed at
n
and 2n.
They meet the requirement of the current edition of the UK Wiring Regulations (BS 7671), as regards ability to trip with Earth Loop Impedance of up to 1667 Ω (for a 30mA RCD), by being able to operate with Earth Loop Impedance of up to 10,000 Ω.
A. INTRODUCTION
5
Mechanical
Terminal Capacity Line in - 25mm
2
Line and Neutral out - 25mm
2
Product Width 18mm Product Height above 76mm
Din Rail Product Length 118mm Suitable Mounting MK Sentry Consumer Unit
Enclosure (select from the MK range) Method of Mounting Top Hat Mounting (DIN)
in Enclosure Rail to EN 50022
Environmental
Ambient Temperature Range-5°C to +40°C Storage Temperature Range-30°C to +85°C Protection, Un-installed Device IP 20 Protection, Installed in the
Consumer Unit IP 40
C. PRODUCT SPECIFICATION (Cont.)
6
The products in this range comply with the requirements of the following standards:
BS EN 61009-1 BS IEC 61009-2-2 EN 61543 for EMC
D. STANDARDS COMPLIANCE
1. This product must be installed by a competent person (e.g. a qualified electrician) in accordance with these instructions and the appropriate clauses of the current edition of the IEE Wiring Regulations (BS7671) and Building Regulations.
2. The RCBO must be installed within a SENTRY
®
Consumer Unit
(select from the range of MK consumer units).
3. The RCBO should not be regarded as a substitute for basic safety precautions.
4. Test the RCBO quarterly, as detailed in the current edition of the IEE Wiring Regulations (BS 7671), by pressing the TEST BUTTON marked T, provided on the product (see label on the Consumer Unit).
E. SAFETY INSTRUCTIONS
7
Do not use the product if it fails to trip during this operation. Failure to trip indicates either no supply to the RCBO or a faulty device. Consult a qualified electrician or contact MK Technical Sales and Service Department.
Telephone: 01268 563720
(National)
+44 (0) 1268 563758 (I nternational)
5. Choose an RCBO from TABLE 1, with the correct ratings, for the circuit to be protected.
6. The RCBO’s in this range must not be used in ambient temperatures outside their specified range.
L IN
N
OUT
L
O
UT
I∆n 30mA
6000
3
230V
B32
7936s
ON
BS EN61009-1
Load
N
OUTLOUT
N
IN-Supply
(Blue)
FE
(White)
L IN-Supply
Blue Flying
Curled Neutral
Supply Lead
White or
Cream Flying Earth Supply Lead
Line Supply
E. SAFETY INSTRUCTIONS (Cont.)
8
1. The RCBO shall be installed at the source of the circuit in which the Earth Fault and Over-current protection is required.
2. The RCBO’s may be installed alongside other SENTRY
®
Modular Products, as part of a larger assembly.
3. The RCBO is a sensitive device designed for fixed installation in a clean and dry environment. The device must not be installed as part of a portable system which may be subject to mechanical shocks and vibration.
4. An adhesive label giving test instructions is provided with each RCBO. This label shall be placed in a prominent position close to the RCBO (preferably on the Consumer Unit Cover).
5. Upon completion of the installation, please leave this instruction leaflet in close proximity to the RCBO, for future reference.
F. INSTALLATION - GENERAL NOTES
4
Electrical
Number of Poles Single Pole with Solid
Neutral Rated Supply Voltage 230V a.c. +10%, -15% Supply Voltage Range 110 V to 253Va.c. Supply Frequency Range 45 to 66Hz Supply Voltage Range for 195V to 253V a.c.
Test Device Operation RCD Trip Current Rating 30 mA Operating Characteristics Type AC MCB Type B, C Rated Short Circuit 6 kA
Capacity Icn Neutral Connection Flying Lead Earth Connection Flying Lead
C. PRODUCT SPECIFICATION
3
The product range is given in Table 1 below.
All products in the range have an RCD trip current rating of 30mA.
Table 1
Type B RCBO Type C RCBO
List No. MCB Current List No. MCB Current
Rating A Rating A
07932s 6 08932s 6 07933s 10 08933s 10 07934s 16 08934s 16 07935s 20 08935s 20 07936s 32 08936s 32 07937s 40 08937s 40 07938s 45 08938s 45 07939s 50 08939s 50
B. PRODUCT RANGE
Figure 1
16
MK Electric Limited
The Arnold Ce ntre, Paycocke Road, Basildon, Essex SS14 3EA
Telephone: 012 68 563000 (National) Fax: 01268 563563 (UK Sales)
+44 (0) 1268 563360 (International) Email: mk.technical@honeywell.com Web site: www.mkelectric.co.uk
RCBO
tripped / off
NO
Can
RCBO be
switched on
again?
Switch off or disconnect all loads and/or appliances
protected by the RCBO. Inspect all items that were
connected to the RCBO circuit and do not
re-connect any items which show obvious signs of
being faulty (unusual visual signs or smell of
overheating or other faults).
Call a qualified Electrician to investigate further.
Y
ES
Can
R
CBO be
s
witched on
again?
C
heck RCBO
operation with
test button
Transient
Fault
If tripping
re-occurs seek
expert attention
Expert attention
is needed to correct fault
Check RCBO
is correctly
connected
Can
RCBO be
switched on
again?
Check RCBO
operation with
test button
Check RCBO
operation with
test button
Does RCBO
trip?
Fault rectified
by wiring
correction
Can
RCBO be
switched on
again?
Switch on or
reconnect loads
or appliances
one-by-one until RCBO
trips off
This load or appliance is faulty. Expert
attention is
needed to
correct fault
Disconnect the RCBO from the
circuit it is
protecting
(Load side only)
There is a
fault within the
load circuit.
Expert attention
needed to
correct fault
Switch off. Do not use. Contact MK
Technical Sales
Services
Switch off
RCBO. Do not use. Contact MK
Technical Sales
Services
YES NO
YES
YES
NO
NO
NO
YES
9
10
1. Choose and install a suitable enclosure from the Range of MK Sentry Consumer Units.
2. Mount the RCBO(s) on to the DIN rail in the enclosure with the L (Supply) terminal at the bottom (shown in Figure 1).
3. It is important that the RCBO is supplied via a Double Pole Isolator (Switch Disconnector).
4. Strip the Supply Neutral Cable and the Load Cables to expose 11mm of conductor.
5. Connect the Supply Line to the Line (Supply) Terminal at the bottom, using the busbar supplied with the Consumer Unit. Alternatively, a suitable cable can be used, which should be stripped to expose 12mm of conductor for connection.
6. Connect the Neutral (Blue) flying lead of the RCBO to the Supply Neutral Terminal Bar.
7. Connect the Earth (Cream) flying lead of the RCBO to the Supply Earth Terminal Bar.
8. Connect the Load, Line and Neutral connections to the outgoing terminals at the top of the RCBO, marked L (OUT) and N (OUT), respectively.
9. Connect the Load Earth conductor to the Earth Terminal Bar.
G. INSTALLATION
11
1. Insulation resistance tests NOTE: Disconnect the L Load, N Load and Earth before
conducting Insulation resistance testing to avoid damage to the RCBO unit.
2. After the installation is complete, turn on the supply to the RCBO and check that the supply voltage to the product is present at its L (Supply) and N (Supply) connection.
3. Switch on the RCBO by moving its switch dolly upwards to show ‘ON’ position. Press the Test Button on the device, the device should trip.
IMPORTANT: Upon completion, ensure that all terminal screws are tightened to the correct torque values (Load, Line and Neutral Terminal - 1.2 to 1.5 Nm, Supply Line Terminal - 2.0 to 2.5Nm).
10. Test the RCBO as detailed in Section H of this leaflet.
11. AFFIX LABEL SUPPLIED TO THE SENTRY®CONSUMER UNIT.
12. Leave this Instruction Leaflet with the end user for future use.
H. TESTING
12
4. Carry out the following tests using a calibrated RCD Tester.
Test Current Result
0.5IΔn RCBO must not trip
n RCBO must trip within 300 ms
2
n RCBO must trip within 200 ms
5
n RCBO must trip within 40 ms
If the device fails to trip as required in steps 3. and 4. above, do not use the product.
Failure to trip according to 3. and 4. above, after it is confirmed that the supply is present to the product, indicates to a faulty product. Consult a qualified electrician or contact, MK Electric Technical Sales and Service Department.
Telephone: 01268 563720 (National)
+44 (0) 1268 563758 (Inter national)
Maintenance
It is recommended that the RCBO is checked regularly, at least quarterly. Refer to Item 4 in Section E, Safety Instructions, of this leaflet.
14
If the black portion of the switch is in the ‘OFF’ position, this is an indication that a fault has caused the RCBO to trip.
Consult the Fault Identification Chart (Figure 2) to establish the cause.
Any repairs to appliances or alterations to the installation, to correct the fault, should be carried out by a competent person.
I. TRIPPING IN SERVICE
15
The Company undertakes to replace or repair, at its discretion, this product should it become defective within a period of 10 years after delivery, solely as a result of faulty materials and/or workmanship. Understandably, if the product has not been installed or maintained in accordance with the Company’s instructions, has not been used appropriately, or if any attempt has been made to rectify, dismantle or alter the product in any way, the guarantee will be invalidated.
This Guarantee states the Company’s entire liability. It does not extend to cover consequential loss or damage or installation costs arising from the defective product. This Guarantee does not restrict or infringe the normal statutory or other rights of the consumer.
MK Electric Limited wishes to make it clear that it will take all necessary legal action in any part of the world against any party found to be manufacturing, distributing, selling or otherwise dealing with any article which infringes the company’s design rights, copyrights or patents in its products, or any other rights of the company therein.
Design Right MK Electric Ltd.
J. GUARANTEE
Figure 2 F
ault Identification
Chart (Section I.)
Loading...