Mitsumi electronic R410A, PUY-A12, PEA-AAA, PCA-AKA, PKA-AHAL User Manual

...
Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS
March 2009
No. OCS14
TECHNICAL DATA BOOK
<Indoor unit> [Model names]
PLA-A·BA PKA-A·HA PKA-A·HAL PKA-A·KA PKA-A·KAL PCA-A·KA PEA-A·AA
PUZ-A18/24/30/36/42NHA3 PUZ-A18/24/30/36/42NHA3-BS PUY-A12/18/24/30/36/42NHA3 PUY-A12/18/24/30/36/42NHA3-BS
R410A
INVERTER
CONTENTS
1. REFERENCE SERVICE MANUAL
2. SPECIFICATIONS
3. OUTLINES AND DIMENSIONS
4. WIRING DIAGRAM
5. REFRIGERANT SYSTEM DIAGRAM
6. PERFORMANCE CURVES
7. CORRECTION FACTORS
8. AIR FLOW DATA
9. NOISE CRITERION CURVES
10. OPTIONAL PARTS
.......................................................................
................................................
...................................................................
......................................................
........................................................
......................................................................
..................................................
....................................................
.............................................
......................................
Back cover
2
3 10 21 30 33 35 36 45
Page 2
1
For information on service, please refer to the service manual as follows.
REFERENCE SERVICE MANUAL
1-1. INDOOR UNIT
Model name Service Ref.
PLA-A12/18/24/30/36/42BA PLA-A12/18/24/30/36/42BA1
PKA-A12/18HA PKA-A12/18HA PKA-A12/18HAL PKA-A12/18HAL
PKA-A24/30/36KA PKA-A24/30/36KA.TH PKA-A24/30/36KAL PKA-A24/30/36KAL.TH
PCA-A24/30/36/42KA PCA-A24/30/36/42KA
PEA-A12/18AA PEA-A12/18AA.TH
1-2. OUTDOOR UNIT
Model name Service Ref.
PUZ-A18/24/30/36/42NHA3 PUZ-A18/24/30/36/42NHA3-BS PUY-A12/18/24/30/36/42NHA3 PUY-A12/18/24/30/36/42NHA3-BS PUY-A12/18/24/30/36/42NHA3-BS
PUZ-A18/24/30/36/42NHA3 PUZ-A18/24/30/36/42NHA3-BS PUY-A12/18/24/30/36/42NHA3
Service Manual No.
OCH420 OCB420
OCH456
OCB456
OCH457
OCB457
OCH455 OCB455
HWE08070 BWE0811A
Service Manual No.
OCH458 OCB458
2
Page 3
2
SPECIFICATIONS
2-1. CEILING CASSETTE TYPE
Model name Indoor unit
Cooling
Heating
Heating at low ambient
Power supply
Voltage
Indoor unit
Remote Controller Outdoor unit
Refrigerant
Refrigerant pipe size
Refrigerant pipe length Height difference
Refrigerant Piping Connection Method
Outdoor unit
Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W EER Btu/h/W SEER Btu/h/W Moisture Removal Pints/h
*1 SHF
Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W COP W/W
*1
HSPF (/) Rated Capacity Btu/h Total Input W
*2 COP W/W
Phase, Cycle, Voltage Breaker size A Indoor - Outdoor S1-S2 Indoor - Outdoor S2-S3 Indoor - Remote Controller MCA A MOCP A Fan Motor F.L.A. Fan Motor Output W Air flow DRY (
Lo-M2-M1-Hi)WET Air flow DRY (
Lo-M2-M1-Hi)WET External pressure Pa Sound level dB(A (
Lo-M2-M1-Hi External finish (Panel Dimension W : mm [inch] Unit(Panel
Weight kg Unit(Panel Field drain pipe size O.D.
MCA A MOCP A Fan Motor F.L.A. Fan Motor Output W Compressor
Air flow CMM [CFM] Refrigerant Control Defrost Method Sound level at cooling dB(A Sound level at heating dB(A External finish Dimension
Weight Type Charge Oil Gas side O.D. Liquid side O.D.
Length
)
)
)
Btu/h/W
CMM CMM
)
D : mm [inch] H : mm [inch]
mm [inch]
R.L.A
L.R.A.
W : mm [inch]
D : mm [inch] H : mm [inch]
kg [lbs]
kg [lbs, oz]
L [oz] mm [inch] mm [inch]
CFM CFM
lbs
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Operating range
Indoor intake air temperature
Cooling
Heating
Maximum
Minimum
Maximum
Minimum
D.B. 35(95°F), W.B. 21.7(71°F) D.B. 19.4(67°F), W.B. 13.9(57°F) D.B. 26.7(80°F), W.B. 19.4(67°F) D.B. 21.1(70°F), W.B. 15.6(60°F)
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
PLA-A12BA PLA-A18BA PLA-A24BA PLA-A30BA PLA-A36BA PLA-A42BA
PUY-A12NHA3
PUY-A12NHA3-BS
12,000 18,000 24,000 30,000 35,000 42,000 12,000 18,000 24,000 30,000 35,000 42,000
6,000 8,000 12,000 12,000 12,000 18,000
1260 1940 2500 4100 4500 4600
9.59.39.67.37.89.1
13.5 14.2 13.6 13.6 14.2 14.4
1.7 3.0 5.1 7.2 8.1 10.9
0.84 0.81 0.76 0.73 0.74 0.71
------
------
------
------
------
------
------
------
------
11-12-13-15 12-14-16-18 14-16-18-21 20-23-26-30 22-25-28-31
10-11-12-14 11-13-15-17 13-15-17-20 19-22-25-29 21-24-27-30 390-420-460-530 420-490-570-640 490-570-640-740 710-810-920-1060 780-880-990-1090 350-390-420-490 390-460-530-600 460-530-600-710 670-770-880-1030 740-850-950-1060
)
27-28-29-31 28-29-31-32 28-30-32-34 32-34-37-40 34-36-39-41
15 20 30 40
) )
330+23 [13 + 7/8] 330+30 [13 + 1-3/16]
41 [90] 44 [97] 74 [163]
1.3 [2 lbs 14 oz] 1.7 [3 lbs 12 oz] 3.0 [6 lbs 10 oz]
0.65 (MEL56) [20] 0.87 (FV50S) [28]
Max. 30m [Max.100ft] Max. 50 [Max.165ft]
PUY-A18NHA3
PUY-A18NHA3-BS
15 25 30
258 (35) [ 10-3/16 (1-3/8) ] 298 (35) [ 11-3/4 (1-3/8) ]
22 (6) 23 (6) 25 (6)
49 (13) 51 (13) 55 (13)
13 18 25 26
0.35 0.75 0.4 + 0.4 40 75 86 + 86
SNB130FPBM1 TNB220FLHM ANV33FDPMT
34 [1,200] 55 [1,940]
800 [31-1/2] 950 [37-3/8]
600 [23-5/8] 943 [37-1/8] 1350 [53-1/8]
12.7 [1/2] 15.88 [5/8]
6.35 [1/4] 9.52 [3/8]
14 17.5 27.5
46 48 51
---
PUY-A24NHA3
PUY-A24NHA3-BS
1phase, 60Hz, 208/230V
12
0.51 1.00 50 120
White Munsell 6.4Y 8.9 / 0.4 840 (950) [ 33-1/16 (37-3/8) ] 840 (950) [ 33-1/16 (37-3/8) ]
12 20
Linear Expansion Valve
Ivory Munsell 3Y 7.8/1.1
Max. 30m [Max.100ft]
PUY-A30NHA3
PUY-A30NHA3-BS
AC 208 / 230V
DC24V DC12V
15
0
32 [ 1-1/4 ]
Attached in Grille
-
R410A
Not Supplied
Flared
PUY-A36NHA3
PUY-A36NHA3-BS
Outdoor intake air temperature
D.B. 46(115°F)
D.B. -18(0°F)*
D.B. 21.1(70°F), W.B. 15(59°F)
D.B. -11.1(12°F), W.B. -12.2(10°F)
PUY-A42NHA3
PUY-A42NHA3-BS
100 [3,530]
117 [258]
4.5 [10 lbs]
1.4 (FV50S) [45]
3
Page 4
Model name Indoor unit
Cooling
Heating
Heating at low ambient
Power supply
Voltage
Indoor unit
Remote Controller Outdoor unit
Refrigerant
Refrigerant pipe size Gas side O.D.
Refrigerant pipe length
Refrigerant Piping Connection Method
Outdoor unit
Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W EER Btu/h/W SEER Btu/h/W Moisture Removal Pints/h
*1 SHF
Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W COP W/W
*1
HSPF (/) Rated Capacity Btu/h Total Input W
*2 COP W/W
Phase, Cycle, Voltage Breaker size A Indoor - Outdoor S1-S2 Indoor - Outdoor S2-S3 Indoor - Remote Controller MCA A MOCP A Fan Motor F.L.A. Fan Motor Output W Air flow DRY CMM (
Lo-M2-M1-Hi)WET CMM Air flow DRY CFM (
Lo-M2-M1-Hi)WET CFM External pressure Pa Sound level dB(A (
Lo-M2-M1-Hi External finish (Panel Dimension W : mm [inch] Unit(Panel
Weight kg
Unit(Panel
Field drain pipe size O.D.
MCA A MOCP A Fan Motor F.L.A. Fan Motor Output W Compressor
Air flow CMM [CFM] Refrigerant Control Defrost Method Sound level at cooling Sound level at heating External finish Dimension
Weight Type Charge Oil
Liquid side O.D. Height difference Length
)
)
)
Btu/h/W
)
)
D : mm [inch] H : mm [inch]
lbs
mm [inch]
R.L.A
L.R.A.
)
dB(A
)
dB(A
W : mm [inch]
D : mm [inch] H : mm [inch]
kg [lbs]
kg [lbs, oz]
L [oz] mm [inch] mm [inch]
PLA-A18BA PLA-A24BA PLA-A30BA PLA-A36BA PLA-A42BA
PUZ-A18NHA3
PUZ-A18NHA3-BS
18,000 24,000 30,000 35,000 42,000 18,000 24,000 30,000 35,000 42,000
8,000 12,000 12,000 12,000 18,000
1940 2500 4100 4500 4600
9.3 9.6 7.3 7.8 9.1
14.2 13.6 13.6 14.2 14.4
3.0 5.1 7.2 8.1 10.9
0.81 0.76 0.73 0.74 0.71 20,000 28,000 34,000 38,000 48,000 19,000 26,000 32,000 37,000 45,000
8,000 12,000 12,000 12,000 18,000
1900 2570 3370 3300 4450
2.93 2.96 2.78 3.28 2.96
9.8 / 7.5 8.5 / 6.8 8.7 / 6.9 9.3 / 7.3 9.3 / 7.2 13,000 16,000 23,000 25,000 30,000
1590 2200 3050 3070 4300
2.40 2.14 2.20 2.37 2.05
15 25 30
420-490-570-640 490-570-640-740 710-810-920-1060 780-880-990-1090 390-460-530-600 460-530-600-710 670-770-880-1030 740-850-950-1060
22 (6) 23 (6) 25 (6)
49 (13) 51 (13) 55 (13)
13 18 25 26 15 30 40
0.35 0.75 0.4 + 0.4 40 75 86 + 86
SNB130FPBM1 TNB220FLHM ANV33FDPMT
34 [1,200] 55 [1,940] 100 [3,530]
46 48 51 47 50 55
800 [31-1/2] 950 [37-3/8]
330+23 [13 + 7/8] 330+30 [13 + 1-3/16]
600 [23-5/8] 943 [37-1/8] 1350 [53-1/8]
45 [99] 75 [165] 118 [260]
1.7 [3 lbs 12 oz] 3.0 [6 lbs 10 oz] 4.5 [10 lbs]
0.65 (MEL56) [20] 0.87 (FV50S) [28] 1.4 (FV50S) [45]
12.7 [1/2] 15.88 [5/8]
6.35 [1/4] 9.52 [3/8]
Max. 30m [Max.100ft]
PUZ-A24NHA3
PUZ-A24NHA3-BS
12
0.51 1.00 50 120
12-14-16-18 14-16-18-21 20-23-26-30 22-25-28-31 11-13-15-17 13-15-17-20 19-22-25-29 21-24-27-30
28-29-31-32 28-30-32-34 32-34-37-40 34-36-39-41
258 (35) [ 10-3/16 (1-3/8) ] 298 (35) [ 11-3/4 (1-3/8) ]
14 17.5 27.5
PUZ-A30NHA3
PUZ-A30NHA3-BS
1phase, 60Hz, 208/230V
AC 208 / 230V
DC24V DC12V
15
0
White Munsell 6.4Y 8.9 / 0.4
840 (950) [ 33-1/16 (37-3/8) ] 840 (950) [ 33-1/16 (37-3/8) ]
32 [ 1-1/4 ]
Attached in Grille
12 20
Linear Expansion Valve
Reverse Cycle
Ivory Munsell 3Y 7.8/1.1
R410A
Max. 30m [Max.100ft]
Max. 50 [Max.165ft]
Not Supplied
Flared
PUZ-A36NHA3
PUZ-A36NHA3-BS
PUZ-A42NHA3
PUZ-A42NHA3-BS
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Operating range
Cooling
Heating
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
Maximum
Minimum
Maximum
Minimum
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
Indoor intake air temperature
D.B. 35(95°F), W.B. 21.7(71°F) D.B. 19.4(67°F), W.B. 13.9(57°F) D.B. 26.7(80°F), W.B. 19.4(67°F) D.B. 21.1(70°F), W.B. 15.6(60°F)
Outdoor intake air temperature
D.B. 46(115°F)
D.B. -18(0°F)*
D.B. 21.1(70°F), W.B. 15(59°F)
D.B. -11.1(12°F), W.B. -12.2(10°F)
4
Page 5
2-2. WALL-MOUNTED TYPE
Indoor unit
Model name
Cooling Max. Capacity Btu/h 12,000 18,000 24,000 30,000 34,200
Heating Max. Capacity Btu/h
Heating Rated Capacity Btu/h at low ambient Total Input W
Power supply
Voltage
Indoor unit
Remote Controller Outdoor unit MCA A 13 18 25
Refrigerant Type R410A
Refrigerant pipe size Gas side O.D. mm [inch] 12.7 [1/2] 15.88 [5/8]
Refrigerant pipe length Height difference Max. 30m [Max. 100ft]
Refrigerant Piping Not Supplied Connection Method Flared
Outdoor unit
Rated Capacity Btu/h 12,000 18,000 24,000 30,000 34,200 Min. Capacity Btu/h 6,000 8,000 Total Input W EER Btu/h/W SEER Btu/h/W Moisture Removal Pints/h
*1 SHF
Rated Capacity Btu/h Min. Capacity Btu/h Total Input W COP W/W
*1 HSPF (/) Btu/h/W
*2 COP W/W
Phase, Cycle, Voltage 1phase , 60Hz , 208/230V Breaker size A 15 25 30 Indoor - Outdoor S1-S2 AC 208 / 230V Indoor - Outdoor S2-S3 DC24V Indoor - Remote Controller DC12V : Wired type MCA A 1 MOCP A 15 Fan Motor F.L.A. 0.33 0.36 0.57 Fan Motor Output W 30 56 Air flow DRY (Lo-Mid-Hi) WET CMM 8-9.5-11 16-18-20 18-21-23 Air flow DRY (Lo-Mid-Hi) WET CFM 290-335-380 570-635-700 635-730-830 External pressure Pa 0 Sound level (Lo-Mid-Hi) External finish (Panel) White Munsell 1.0Y 9.2/0.2 Dimension W : mm [inch] 898 [35-3/8] 1170 [46-1/16] Unit (Panel) D : mm [inch] 295 [11-5/8]249 [9-13/16]
Weight kg 13 21 Unit (Panel) lbs 29 46 Field drain pipe size I.D. mm [inch] 16 [5/8]
MOCP A152030 40 Fan Motor F.L.A. 0.35 0.75 Fan Motor Output W 40 75 Compressor SNB130FPBM1 TNB220FLHM
Air flow CMM [CFM] 34 [1,200] 55 [1,940] Refrigerant Control Linear Expansion Valve Defrost Method Sound level at cooling dB(A) 46 48 Sound level at heating dB(A) External finish Dimension
Weight kg [lbs]
Charge Oil L [oz]
Liquid side O.D. mm [inch] 6.35 [1/4] 9.52 [3/8]
Length Max. 30m [Max. 100ft] Max. 50m [Max. 165ft]
CMM 9-10.5-12 18-20-22 20-23-26
CFM 320-370-425 635-705-775 705-810-920
dB(A) 36-40-43 39-42-45 43-46-49
H : mm [inch]
R.L.A 12 L.R.A. 14 17.5
W : mm [inch]
D : mm [inch] H : mm [inch]
kg [lbs, oz]
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Operating range
Indoor intake air temperature
Cooling
Heating
Maximum
Minimum
Maximum
Minimum
D.B. 35(95°F), W.B. 21.7(71°F) D.B. 19.4(67°F), W.B. 13.9(57°F) D.B. 26.7(80°F), W.B. 19.4(67°F) D.B. 21.1(70°F), W.B. 15.6(60°F)
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
PKA-A12HA
PKA-A12HAL
PUY-A12NHA3
PUY-A12NHA3-BS
119 0
10.1
15.2
2.0
0.81
-----
-----
-----
-----
-----
-----
-----
-----
-----
800 [31-1/2] 950 [37-3/8]
330+23 [13 + 7/8] 330+30 [13 + 1-3/16]
600 [23-5/8] 943 [37-1/8]
41 [90] 44 [97] 74[163]
1.3 [2 lbs 14 oz] 1.7 [3 lbs 12 oz] 3.0 [6 lbs 10 oz]
0.65 (MEL56) [20] 0.87 (FV50S) [28]
PKA-A18HA
PKA-A18HAL
PUY-A18NHA3
PUY-A18NHA3-BS
2240
8.0
15.3
5.2
0.68
--
PKA-A24KA
PKA-A24KAL
PUY-A24NHA3
PUY-A24NHA3-BS
12,000
2270
10.6
17.0
5.0
0.77
Attached in Indoor Unit
-
Ivory Munsell 3Y 7.8/1.1
PKA-A30KA
PKA-A30KAL
PUY-A30NHA3
PUY-A30NHA3-BS
12,000
365 [14-3/8]295 [11-5/8]
4130
7.3
15.5
8.1
0.70
Outdoor intake air temperature
D.B. 46(115°F)
D.B. -18(0°F)*
D.B. 21.1(70°F), W.B. 15(59°F)
D.B. -11.1(12°F), W.B. -12.2(10°F)
PKA-A36KA
PKA-A36KAL
PUY-A36NHA3
PUY-A36NHA3-BS
12,000
5030
6.8
14.0
9.2
0.70
5
Page 6
Indoor unit
Model name
Cooling Max. Capacity Btu/h 18,000 24,000 30,000 34,200
Heating Max. Capacity Btu/h 20,000 28,000 34,000 38,000
Heating Rated Capacity Btu/h 13,000 at low ambient Total Input W
Power supply Phase, Cycle, Voltage 1phase , 60Hz , 208/230V
Voltage
Indoor unit MCA A
Remote Controller Attached in Indoor Unit Outdoor unit MCA A 13 18 25
Refrigerant Type
Refrigerant pipe size Gas side O.D.
Refrigerant pipe length Height difference
Refrigerant Piping Connection Method
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
Operating range
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Cooling
Heating
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
Outdoor unit
Rated Capacity Btu/h 18,000 24,000 30,000 34,200 Min. Capacity Btu/h 8,000 Total Input W EER Btu/h/W SEER Btu/h/W Moisture Removal Pints/h
*1 SHF
Rated Capacity Btu/h 19,000 26,000 32,000 37,000 Min. Capacity Btu/h 8,000 Total Input W COP W/W
*1 HSPF
(/)
*2 COP W/W
Breaker size A 15 25 30 Indoor - Outdoor S1-S2 Indoor - Outdoor S2-S3
Indoor - Remote Controller DC12V : Wired type
MOCP A Fan Motor F.L.A. Fan Motor Output W Air flow DRY (Lo-Mid-Hi) WET CMM Air flow DRY (Lo-Mid-Hi) WET CFM External pressure Pa Sound level (Lo-Mid-Hi) External finish (Panel) Dimension W : mm [inch] Unit (Panel) D : mm [inch]
Weight kg Unit (Panel) lbs Field drain pipe size I.D.
MOCP A 20 30 40 Fan Motor F.L.A. 0.35 0.75 Fan Motor Output W 40 75 Compressor SNB130FPBM1 TNB220FLHM
Air flow CMM [CFM] 34 [1,200] 55 [1,940] Refrigerant Control Linear Expansion Valve Defrost Method Reverse Cycle Sound level at cooling dB(A) 46 48 Sound level at heating dB(A) 47 50 External finish Ivory Munsell 3Y 7.8/1.1 Dimension
Weight kg [lbs]
Charge Oil
Liquid side O.D.
Length
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
Maximum
Minimum
Maximum
Minimum
Indoor intake air temperature
D.B. 35(95°F), W.B. 21.7(71°F) D.B. 19.4(67°F), W.B. 13.9(57°F) D.B. 26.7(80°F), W.B. 19.4(67°F) D.B. 21.1(70°F), W.B. 15.6(60°F)
Btu/h/W
CMM
CFM
dB(A)
H : mm [inch]
mm [inch]
R.L.A 12
L.R.A. 14 17.5
W : mm [inch]
D : mm [inch] H : mm [inch]
kg [lbs, oz]
L [oz] 0.65 (MEL56) [20] 0.87 (FV50S) [28] mm [inch] 12.7 [1/2] 15.88 [5/8] mm [inch] 6.35 [1/4] 9.52 [3/8]
PKA-A18HA
PKA-A18HAL
PUZ-A18NHA3
PUZ-A18NHA3-BS
2240
8.0
15.3
5.2
0.68
1970
2.83
9.5 / 7.6
1670
2.28
0.33 0.36 0.57 30 56
9-10.5-12 18-20-22 20-23-26
8-9.5-11 16-18-20 18-21-23 320-370-425 635-705-775 705-810-920 290-335-380 570-635-700
36-40-43 39-42-45 43-46-49
898 [35-3/8]
13 29
800 [31-1/2] 950 [37-3/8]
330+23 [13 + 7/8] 330+30 [13 + 1-3/16]
600 [23-5/8] 943 [37-1/8]
45 [99] 75 [165]
1.7 [3 lbs 12 oz] 3.0 [6 lbs 10 oz]
Max. 30m [Max. 100ft] Max. 50m [Max. 165ft]
PKA-A24KA
PKA-A24KAL
PUZ-A24NHA3
PUZ-A24NHA3-BS
12,000
2270
10.6
17.0
5.0
0.77
12,000
2330
3.27
10.8 / 8.6 18,000
2200
2.40
AC 208 / 230V
White Munsell 1.0Y 9.2/0.2
Max. 30m [Max. 100ft]
Not Supplied
Outdoor intake air temperature
D.B. 46(115°F)
D.B. 21.1(70°F), W.B. 15(59°F)
D.B. -11.1(12°F), W.B. -12.2(10°F)
D.B. -18(0°F)*
PKA-A30KA
PKA-A30KAL
PUZ-A30NHA3
PUZ-A30NHA3-BS
DC24V
1
15
0
1170 [46-1/16]
295 [11-5/8]249 [9-13/16] 365 [14-3/8]295 [11-5/8]
16 [5/8]
R410A
Flared
12,000
4130
7.3
15.5
8.1
0.70
12,000
3150
2.98
8.9 / 7.1 23,000 25,000
2850
2.37
21 46
PKA-A36KA
PKA-A36KAL
PUZ-A36NHA3
PUZ-A36NHA3-BS
635-730-830
12,000
5030
6.8
14.0
9.2
0.70
12,000
3610
3.00
9.3 / 7.5
3030
2.42
6
Page 7
2-3. CEILING-SUSPENDED TYPE
Model name Indoor unit
Cooling Max. Capacity Btu/h 24,000 30,000 35,000 42,000
Heating Max. Capacity Btu/h
Heating Rated Capacity Btu/h at low ambient Total Input W
Power supply Phase,Cycle,Voltage 1phase,60Hz,208/230V
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Indoor unit MCA A 1 2
Remote Controller Attached in Indoor Unit Outdoor unit MCA A 18 25 26
Refrigerant Type R410A
Refrigerant pipe size Gas side O.D. mm [inch] 15.88 [5/8]
Refrigerant pipe length Height difference Max. 30m [Max. 100ft]
Refrigerant Piping Not Supplied Connection Method Flared
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
Operating range
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Cooling
Heating
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
Maximum
Minimum
Maximum
Minimum
Outdoor unit
Rated Capacity Btu/h 24,000 30,000 35,000 42,000 Min. Capacity Btu/h 12,000 12,000 12,000 18,000 Total Input W 2340 3760 4630 4110 EER Btu/h/W 10.3 8.0 7.6 10.2 SEER Btu/h/W 16.8 14.5 14.4 15.8 Moisture Removal Pints/h 5.8 8.3 8.5 11.7
*1 SHF 0.73 0.69 0.73 0.69
Rated Capacity Btu/h Min. Capacity Btu/h Total Input W COP W/W
*1 HSPF (/) Btu/h/W
*2 COP W/W
Breaker size A 25 30
Indoor - Outdoor S2-S3 DC24V Indoor - Remote Controller DC12V
MOCP A 15 Fan Motor F.L.A. 0.54 0.97 Fan Motor Output W 95 160 Air flow DRY CMM 15-16-17-19 22-24-26-28 (
Lo-M2-M1-Hi)WET CMM 14-15-16-18 20-22-24-26 Air flow DRY CFM 530-565-600-670 775-850-920-990 (
Lo-M2-M1-Hi)WET CFM 495-530-565-635 705-775-850-920 External pressure Pa 0 Sound level dB(A (
Lo-M2-M1-Hi External finish (Panel Dimension W : mm [inch] 1600 [63]1280 [50-3/8] Unit(Panel
Weight kg 32 36 Unit(Panel Field drain pipe size O.D.
MOCP A 30 40 Fan Motor F.L.A. 0.75 0.4 + 0.4 Fan Motor Output W 75 86 + 86 Compressor TNB220FLHM ANV33FDPMT
Air flow CMM [CFM] 55 [1,940] 100 [3,530] Refrigerant Control Linear Expansion Valve Defrost Method Sound level at cooling Sound level at heating External finish Ivory Munsell 3Y 7.8/1.1 Dimension W : mm [inch] 950 [37-3/8]
Weight kg [lbs]
Charge 3.0 [6 lbs 10 oz] 4.5 [10 lbs] Oil L [oz] 0.87(FV50S)[28] 1.4(FV50S)[45]
Liquid side O.D. mm [inch] 9.52 [3/8]
Length Max. 50m [Max. 165ft]
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
)
)
)
)
Indoor intake air temperature
D.B. 35(95°F), W.B. 21.7(71°F) D.B. 19.4(67°F), W.B. 13.9(57°F) D.B. 26.7(80°F), W.B. 19.4(67°F) D.B. 21.1(70°F), W.B. 15.6(60°F)
)
D : mm [inch] 680 [26-3/4] H : mm [inch] 230 [9-1/16]
lbs 71 79
mm [inch] 26 [1-1/32]
R.L.A 12 20
L.R.A. 14 17.5 27.5
)
dB(A
)
dB(A
D : mm [inch] 330+30 [13 + 1-3/16] H : mm [inch] 943 [37-1/8] 1350 [53-1/8]
kg [lbs]
PCA-A24KA PCA-A30KA PCA-A36KA PCA-A42KA
PUY-A24NHA3
PUY-A24NHA3-BS
----
----
----
----
----
----
----
----
----
33-35-37-40
PUY-A30NHA3
PUY-A30NHA3-BS
16-17-18-20
15-16-17-19 565-600-635-705 530-565-600-670
35-37-39-41 37-39-41-43
White Munsell 6.4Y 8.9/0.4
48 51
--
74[163] 117 [258]
Outdoor intake air temperature
D.B. 46(115°F)
D.B. 21.1(70°F), W.B. 15(59°F)
D.B. -11.1(12°F), W.B. -12.2(10°F)
D.B. -18(0°F)*
PUY-A36NHA3
PUY-A36NHA3-BS
-
PUY-A42NHA3
PUY-A42NHA3-BS
23-25-27-29 21-23-25-27
810-885-955-1025
740-810-885-955
39-41-43-45
38 84
7
Page 8
Model name Indoor unit
Cooling
Heating
Heating at low ambient
Power supply
Voltage
Indoor unit
Remote Controller Outdoor unit
Refrigerant
Refrigerant pipe size
Refrigerant pipe length
Refrigerant Piping Connection Method
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
Operating range
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Cooling
Heating
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
Maximum Minimum Maximum Minimum
Outdoor unit
Max. Capacity Btu/h 24,000 30,000 35,000 42,000 Rated Capacity Btu/h 24,000 30,000 35,000 42,000 Min. Capacity Btu/h 12,000 12,000 12,000 18,000 Total Input W 2340 3760 4630 4110 EER Btu/h/W 10.3 8.0 7.6 10.2 SEER Btu/h/W 16.8 14.5 14.4 15.8 Moisture Removal Pints/h 5.8 8.3 8.5 11.7
*1 SHF 0.73 0.69 0.73 0.69
Max. Capacity Btu/h 28,000 34,000 38,000 48,000 Rated Capacity Btu/h 26,000 32,000 37,000 45,000 Min. Capacity Btu/h 12,000 12,000 12,000 18,000 Total Input W 2310 3210 3190 3830 COP W/W 3.30 2.92 3.40 3.44
*1 HSPF (/) Btu/h/W 10.9 / 8.9 9.2 / 7.1 10.2 / 8.1 10.2 / 8.3
Rated Capacity Btu/h 18,000 23,000 25,000 30,000 Total Input W 2220 2940 2800 3820
*2 COP W/W 2.38 2.29 2.62 2.30
Phase, Cycle, Voltage 1phase , 60Hz , 208/230V Breaker size A 25 30 Indoor - Outdoor S1-S2 AC 208 / 230V Indoor - Outdoor S2-S3 DC24V Indoor - Remote Controller DC12V MCA A MOCP A Fan Motor F.L.A. Fan Motor Output W Air flow DRY CMM
(Lo-M2-M1-Hi) WET CMM Air flow DRY CFM (Lo-M2-M1-Hi) WET CFM External pressure Pa Sound level dB(A) (Lo-M2-M1-Hi) External finish (Panel)
Dimension W : mm [inch] Unit (Panel) D : mm [inch]
Weight kg Unit (Panel) lbs Field drain pipe size O.D.
MCA A 18 25 26 MOCP A 30 40 Fan Motor F.L.A. 0.75 0.4 + 0.4 Fan Motor Output W 75 86 + 86 Compressor TNB220FLHM ANV33FDPMT
Air flow CMM [CFM] 55 [1,940] 100 [3,530] Refrigerant Control Linear Expansion Valve Defrost Method Reverse Cycle Sound level at cooling dB(A) 48 51 Sound level at heating dB(A) 50 55 External finish Ivory Munsell 3Y 7.8/1.1 Dimension W : mm [inch] 950 [37-3/8]
Weight kg [lbs] Type R410A Charge 3.0 [6 lbs 10 oz] 4.5 [10 lbs] Oil L [oz] 0.87 (FV50S) [28] 1.4 (FV50S) [45] Gas side O.D. mm [inch] 15.88 [5/8] Liquid side O.D. mm [inch] 9.52 [3/8] Height difference Max. 30m [Max. 100ft] Length Max. 50m [Max. 165ft]
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
Indoor intake air temperature
D.B. 35(95°F), W.B. 21.7(71°F) D.B. 19.4(67°F), W.B. 13.9(57°F) D.B. 26.7(80°F), W.B. 19.4(67°F) D.B. 21.1(70°F), W.B. 15.6(60°F)
H : mm [inch]
mm [inch] 26 [1-1/32]
R.L.A 12 20
L.R.A. 14 17.5 27.5
D : mm [inch] 330+30 [13 + 1-3/16] H : mm [inch] 943 [37-1/8] 1350 [53-1/8]
kg [lbs]
PCA-A24KA PCA-A30KA PCA-A36KA PCA-A42KA
PUZ-A24NHA3
PUZ-A24NHA3-BS
15-16-17-19 22-24-26-28
14-15-16-18 20-22-24-26 530-565-600-670 775-850-920-990 495-530-565-635 705-775-850-920
33-35-37-40
PUZ-A30NHA3
PUZ-A30NHA3-BS
12
0.54 0.97 95 160
16-17-18-20
15-16-17-19 565-600-635-705 530-565-600-670
35-37-39-41 37-39-41-43
White Munsell 6.4Y 8.9/0.4
680 [26-3/4]
32 36 71 79
75 [165] 118 [260]
Outdoor intake air temperature
D.B. 21.1(70°F), W.B. 15(59°F)
D.B. -11.1(12°F), W.B. -12.2(10°F)
230 [9-1/16]
Attached in Indoor Unit
Not Supplied
D.B. 46(115°F)
D.B. -18(0°F)*
PUZ-A36NHA3
PUZ-A36NHA3-BS
15
0
Flared
PUZ-A42NHA3
PUZ-A42NHA3-BS
810-885-955-1025
740-810-885-955
1600 [63]1280 [50-3/8]
23-25-27-29 21-23-25-27
39-41-43-45
38 84
8
Page 9
2-4. CEILING CONCEALED TYPE
Model name
Cooling
Heating
Heating at low ambient
Power supply
Voltage
Indoor unit
Remote Controller Outdoor unit
Refrigerant
Refrigerant pipe size
Refrigerant pipe length
Refrigerant Piping Connection Method
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) Outdoor : D.B. 35(95°F), W.B. 23.9(75°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F)
Operating range
Cooling
Heating
Maximum Minimum Maximum Minimum
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.)
indoor unit PEA-A12AA PEA-A18AA PEA-A18AA outdoor unit
Max. Capacity Btu/h 12,000 18,000 18,000 Rated Capacity Btu/h 12,000 18,000 18,000 Min. Capacity Btu/h 6,000 8,000 8,000 Total input W 1240 2150 2150 EER Btu/h 9.7 8.4 8.4 SEER Btu/h 13.8 14.3 14.3 Moisture Removal Pints/h 2.47 3.26 3.26
*1
SHF 0.77 0.80 0.80 Max. Capacity Btu/h - - 20,000 Rated Capacity Btu/h - - 19,000 Min. Capacity Btu/h - - 8,000 Total input W - - 1540 COP W/W - - 3.61 HSPF(IV/V) Btu/h/W - - 10.0 / 8.0
*1
Rated Capacity Btu/h - - 13,000 Total input W - - 1520 COP W/W - - 2.51
*2
Phase,Cycle,Voltage 1phase, 60Hz, 208/230V Breaker size A 15 indoor - outdoor S1-S2 AC208 / 230V indoor - outdoor S2-S3 DC24V indoor - Remote controller DC12V MCA A 1 2 MOCP A 15 15 Fan Motor F.L.A 0.57 0.74 Fan Motor Output W 96 Air fl ow DRY (Lo-Mid-Hi) WET Air fl ow DRY (Lo-Mid-Hi) WET External pressure in.WG [Pa] 0.02/0.06/0.14/0.20 [5/15/35/50] Sound level (Lo-Mid-Hi) External fi nish Galvanized Dimension Unit (Panel)
Weight kg 21 27 Unit lbs 48 60 Field Drain pipe seize O.D.
MCA A 13 MOCP A 15 20 Fan Motor F.L.A. 0.35 Fan Motor Output W 40 Compressor SNB130FPBM1
Air fl ow CMM[CFM] 34 [1,200] Refrigerant Control Linear Expansion Valve Defrost Method - - Reverse Cycle Sound level at cooling dB(A) 46 Sound level at heating dB(A) - - 47 External fi nish Ivory Munsell 3Y 7.8/1.1 Dimension
Weignt Type R410A Charge kg[lbs,oz] 1.3 [2lbs 14oz] 1.7 [3lbs 12oz] Oil L[oz] 0.65 (MEL 56) [20] Gas side O.D. mm[inch] 12.7 [1/2] Liquid side O.D. mm[inch] 6.35 [1/4] Height difference Max. 30m [Max.100ft] Length Max. 30m [Max.100ft]
CMM 7-9-11 12-15-18 CMM 6-8-10 11-14-17
CFM 247-317-388 423-529-635 CFM 222-285-349 381-476-572
dB(A)
W:mm[inch] 990[39] 1190[46-7/8] D:mm[inch] 700[27-9/16] 700[27-9/16] H:mm[inch] 200[7-7/8] 200[7-7/8]
mm[inch] 32 [1-9/32]
R.L.A. 12 L.R.A. 14
W:mm[inch] 800 [31-1/2] D:mm[inch] 330+23 [13+7/8] H:mm[inch] 600 [23-5/8]
kg[lbs]
PUY-A12NHA3 PUY-A18NHA3 PUZ-A18NHA3
PUY-A12NHA3-BS PUY-A18NHA3-BS PUZ-A18NHA3-BS
23-28-33 30-34-38
Attached in indoor Unit
41[90] 44[97] 45[99]
Not Supplied
Flared
(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F)
Indoor intake air temperature
D.B. 35(95°F), W.B. 21.7(71°F) D.B. 19.4(67°F), W.B. 13.9(57°F) D.B. 26.7(80°F), W.B. 19.4(67°F) D.B. 21.1(70°F), W.B. 15.6(60°F)
Outdoor intake air temperature
D.B. 46(115°F)
D.B. -18(0°F)*
D.B. 21.1(70°F), W.B. 15(59°F)
D.B. -11.1(12°F), W.B. -12.2(10°F)
9
Page 10
3
OUTLINES AND DIMENSIONS
INDOOR UNIT
Unit: inch (mm)
PLA-A12BA PLA-A18BA PLA-A24BA PLA-A30BA PLA-A36BA PLA-A42BA
25/32 to 1-25/32(20~45)
33-1/16(840)
Suspension bolt M10 or W3/8
+
Suspension bolt lower edge
Air intake grille
Fresh air intake hole
(160)
6-5/16
Branch duct hole
(90)
(150)
3-17/32
5-29/32
C
1
2
(170)
5-1/2
6-11/16
(140)
+
(500)
(950)
37-3/8
19-11/16
3-17/64
1-27/64
Ceiling
6-5/16
(160)
For MA-Remote controller terminal block
D
7-3/8
(187.5)
(60)
2-3/8
(50~70)
1-15/16~2-3/4
Air outlet hole
M
(83)
(36)
Corner pocket
Grille
Min.19-11/16(500)
Entire periphery
Ceiling hole
33-27/32 to 35-13/16(860~910)
31-7/8(810)
Suspension bolt pitch
Indoor unit/Outdoor unit connecting terminal block
For wiring replacement kit terminal block
33-1/16
(840)
23-1/2
37-3/8
(597)
(500)
(950)
14-27/3211-3/16
(377)
M
(284)
Air intake hole
19-11/16
Air outlet hole
Indoor unit
Min.94-1/2(2400) from floor
Floor
M
6-5/16
(160)
3-17/64
M
(83)
25/32 to 1-25/32(20~45)
(5/16)(5/16)
5
+35
-
(605 )
3/16
+1-3/8
-
(160)
(24)
Suspension bolt pitch
23-13/16
6-5/16
15/16
Drain pipe connected to VP-25
(156)
(105)
4-1/8
6-9/64
++
7-15/32
+
Ceiling
Grille
Drain hole Drain pump clean hole and Drain emergency drainage hole
Auto vane
(Air outlet)
(597)
23-1/2
Air intake hole
Vane motor
1-27/64
(36)
Models
PLA-A12BA PLA-A18BA
PLA-A24BA PLA-A30BA
PLA-A36BA PLA-A42BA
(7.5)
(620)
24-13/32
(7.5)
~45)
1-25/32
(20
25/32 to
(860~910)
Branch duct
Ceiling hole
33-27/32 to 35-13/1625/32
hole
Detail connecting of branch duct(Both aspects)
3-15/16
3-17/32
(90)
:
6-7/8
(
:
175)
Burring hole pitch
(100)
13-25/32
(350)
3-15/16
3-17/32
:
Cut out hole
(100)
(90)
Cut out hole
5-29/32
3-15/16
14-:1/8
Burring hole
(
:
150)
(100)
(
(130)
5-1/8
14-:2.8
(155)
6-3/32
Detail drawing of fresh air intake hole
to 1-25/32
(20~45)
Connected the attached flexible pipe or socket.
Keep 25/64(10)to 19/32(15) between unit ceiling and ceiling slab.
A
B
+
(190)
+5
0
0
+3/16
(35)
(17 )
1-3/8
11/ 16
In case of standard grille
Note1. As for drain pipe, please use VP-25(O.D.1-1/4(32mm) PVC TUBE). Drain pump is included. Max. lifting height is 70-7/18(850mm) from the ceiling.
2. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
3. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/power wires connection.
4. The height of the indoor unit can be adjusted with the grille attached.
5. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Add 5-5/16(135mm) to the dimensions + marked on the figure.
2) Optional high efficiency filter must be used jointly with optional multi-functional casement.
6. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/water dew.)
7. As for necessary installation/service space, please refer to the left figure.
1
Refrigerant pipe
····
:
6.35mm
Flared connection
····1/4
Refrigerant pipe
····
:
9.52mm
Flared connection
····3/8
Refrigerant pipe
:
12.7mm
···· Flared connection
····1/2
Refrigerant pipe
····
:
15.88mm
Flared connection
····5/8
)(
2
Burring hole
3-:1/8(3-:2.8)
6-7/32
+
( 158)
+
120°
Burring hole pitch
:
4-29/32(:125)
Cut out hole
120°
:
3-15/16(:100)
Ceiling
In case of wireless remote controller
Emergency operation switch<Cooling>
Emergency operation switch<Heating>
DEFROST/STAND BY lamp
Operation lamp
DCBA
2-29/32
(74)(80)(258)(241)
3-1/32
(77)
9-1/2
11-1/16
(281)
10-3/16
11-3/4 (298)
Receiver
3-5/32
3-11/32
(85)
++
)
(167)
6-9/16
10
Page 11
PKA-A12HA PKA-A12HAL PKA-A18HA PKA-A18HAL Unit: inch (mm)
15-3/16(387)
7-3/4(197)
23-9/16(599)
7-1/2(192)
Top side
Front side
Mount board
Right side
D
Sleeve (purchased locally)
:2-1/2~:3-1/8 (:65~:80)
Left side
Knockout hole for left piping
Through hole
:2-1/2~:3-1/8 (:65~:80)
Knock out hole for lower piping
77­Tapping screw hole
5/8(16)
1-1/16(28.5)
1-9/16(41)
3-1/16(78.5)
3-9/16(91)
4-1/16(103.5)
4-9/16(116)
6-1/2(166)
7(178.5)
8(203.5)
9-1/8(232.5) 9-15/16(253.5)
11-5/8(295)
5/16(8)
4-:5/16(:9) Bolt hole
:
3/16(:5.1)
0
Wall hole for left rear piping
2-1/8 (55)
Vane(auto)
C
14-5/8(372.3)
14(356.3)
15-1/2(394)
17-5/8(449)
Louver(manual)
12-7/8(327.5)
10-3/8(265)
11-7/16(291.5)
10-15/16(278.3)
24(610)Drain hose
24-1/16(612)
7-13/16(200)
8-13/16(225)
8-3/8(213)
9-5/16(238)
6-13/16(174)
27-1/16(688)
35-3/8(898)
Front side(Grille open)
17-15/16(457)Gas pipe
21-3/16(539)Liquid pipe
Under side
Knock out hole for lower piping
0
4-7/8(125)
2-3/4(70)
0
9/16(15)
9/16(15)
0
Knockout hole for rear piping 2-3/4×12-3/16(70×310)
Operation lamp
B
Center measurement hole :3/32(:2.5)
Mount board
2-1/4(58)
5/32(3.8)
10-3/8(265)
9-5/16(238)
8-13/16(225)
7-13/16(200)
2-3/4(70)
4-7/8(125)
4-1/2(115)
5-1/2(140)
6-9/16(167)
11-1/16(281)
7-9/16(193.5)
7-1/16(180.3)
6-1/16(155)
6-5/8(169) 6-3/16(158)
7-3/16(184)
14(356.3)
12-7/8(237.5)
11-7/16(291.5)
Wall hole for right rear piping
Terminal block for indoor/outdoor connecting line
Terminal block for power supply (option)
Terminal block for MA-remote controller (only PKA-A·HA models)
Emergency operation switch (cooling/heating)
DEFROST/STAND BY lamp
Refrigerant Piping
Drain hose
Receiver
Indoor unit outline
14-5/8(372.3)
13/16(21.8)
0 3/4(20)
1-1/4(32.7) 2-1/16(53.5) 2-9/16(66)
5(128.5) 6(153.5)
9-1/16(231.5)
10-3/4(273.2)
17-5/8(449)
9-13/16(249)
Knock out hole for right piping
Liquid pipe
Gas pipe
1/4F (:6.35)
1/2F (:12.7)
:
5/8 (:16) O.D
A
3/16(5)
Knockout hole for piping
A
1-11/16(43)
Required space(Indoor unit)
2-11/16(69)
1-11/16(43)
2-3/16(56)
3/16(6)
1-3/4(46)
2-5/16(60)
1-11/16(43)
1-11/16(43)
D
2-5/16(59)
B
Min.1-31/32(50)
Min.1/4(7)
250mm,9-13/16inch or greater with
optional drain pump installation.
2-3/16(56)7/16(12.5)
C
2-3/16(56)
1-3/4(46)
3/16(6)
Min.8-5/8
(220)
(mm)
Air inlet
Air inlet
Air outlet
Min.5-7/8(150)
Min.1-31/32(50)
Min.9-13/16(250)
11
Page 12
PKA-A24KA PKA-A24KAL PKA-A30KA PKA-A30KAL Unit: inch (mm) PKA-A36KA PKA-A36KAL
Top side
Front side
17(431.7)
Right side
Mount board
C
Knockout hole for left piping
Left side
2-9/16(65.2)
5-17/132(140.3)
7/16(11)
14-3/8(365)
16-11/16(423.7)
1-1/4(32)
2-3/32(53)
Min.9/32(7)
23/32(18)
2-29/32(74)
A
1-3/16(30)
1-3/8(35)
2-19/32(66)
Sleeve (purchased locally)
:2-15/16 (:75)
Required space(Indoor unit)
Min.2-27/32(72.4)
Vane(auto)
Through hole
:2-15/16~:3-5/32 (:75~:80)
Filter hook
Min.2(50.5)Min.8-21/32(220)
33-21/32(855)
Air inlet
Air outlet
46-1/16(1170)
Front side(Grille open)
17-15/32(444)Gas pipe
18-31/32(482)Liquid pipe
23-1/32(585)Drain hose
Under side
Louver(manual)
Knock out hole for lower piping
Min.9-27/32(250)
Center measurement hole :3/32(:2.5)
Min.1-7/8(48)
9-1/2(241)
 
C
Operation lamp
DEFROST/STAND BY lamp
Receiver
Terminal block for Outdoor unit
Terminal block for power supply (option)
Terminal block for MA-remote controller (only PKA-A·KA models)
Emergency operation switch (cooling/heating)
4-27/32(123)
6-1/16(154)
5-9/32(134)
Piping connection department
Liquid pipe
BB
Gas pipe
Drain hose
Knockout hole for piping
2-5/8(67)
3-1/32(77)
2-9/16(65)
5/16(7.8)
B
2-9/16(65)
13/32(10.7)
11-5/8(295)
3/16(5)
Knock out hole for right piping
Refrigerant pipe: 3/8 O.D(:9.52)
Flared connection: 3/8F
Refrigerant pipe: 5/8 O.D(:15.88)
Flared connection: 5/8F
5/8(:16) O.D
A
3-1/32(77)
2-5/8(67)
5/16(7.8)
3-1/32(77) 3-7/16(87)
2-9/16(65)
75-:3/16(:5.1) Tapping screw hole
5/8(15.5)
31/32(25)
1-31/32(50)
2-15/16(75) 3-15/16(100) 4-19/32(117)
4-29/32(125) 5-19/32(142)
7-9/16(192) 9-17/32(242)
11(279.5)
11-1/2(292)
0
4-:11/3 2(:9) Bolt hole
20-3/8(517.4)
17-7/8(454)
23-1/32(585)
20-7/8(530.5)
17-9/32(439)
16-3/32(408.5)
15-1/8(384)
15-1/8(384)
16-15/16(430.5)
Wall hole for left rear piping
14-11/32(364)
12-3/8(314)
13-11/32(339)
2-1/8(54)
0
1/8(3)
0
4-11/32(110)
2-3/8(60)
13/32(10)
0
7-7/16(189)
Knockout hole for rear piping 2-15/16×18-29/32(75×480)
13/32(10)
2-3/8(60)
4-11/32(110)
Mount board
8-17/32(216.5)
Wall hole for right rear piping
12-3/8(314)
R1-15/32(R37.5)
12
15-1/8(384.5)
14-11/32(364)
16-3/32(408.5)
15-1/8(384)
13-11/32(339)
13-3/4(349.2)
18-5/16(465.5)
17-7/8(454)
17-9/32(439)
17-11/16(449.2)
Indoor unit outline
2-1/8(54) 1-1/4(32) 31/32(25) 1/2(12.5) 0 1/2(12.5) 1-15/32(37.5) 2-15/32(62.5) 3-7/16(87.5) 4-1/8(104.5)
5-3/32(129.5)
6-9/16(167) 8-17/32(217) 9-1/32(229.5) 10-13/32(264) 11-1/2(292)
12-5/32(308.5) 12-1/4(311)
23-1/32(585)
Page 13
PCA-A24KA PCA-A30KA Unit: inch (mm)
Drainage
liquid Φ3/8(Φ9.52)
gas Φ5/8(Φ15.88)
When drain socket
is installed
9-5/16(236)
7-7/8(200)
9-3/16(233)
9-11/16(246)
7-1/16(180)
Emergency operation
switch <Heating>
DEFROST/STAND BY lamp
Operation lamp
Receiver
In case of wireless remote controller
and i-see sensor(Optional Parts)
Emergency operation
switch <Cooling>
2-1/4(57)
i-see sensor
NOTES.
26-3/4(680)
18-3/4(476)
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the drain lift up
mechanism(option parts),refrigerant pipe will be only upward.
10(254)
6
2-7/16(62)
3-1/8(80)
12-5/8(320)
26-3/4(680)
2(51)
3/8(10)
3/16(5)
14
9/16
In case of wireless
remote controller
and i-see sensor
9-1/16(230)
7-11/16(195)
3-7/16(88)
3-5/16(84)
(Optional Parts)
3-3/8(85)
5-1/2(140)
11/16(18)
5-7/8(150)
48-11/16(1237) (Suspension bolt pitch)
46-3/16(1173)
7-3/16(182)
47-3/16(1198)
Air outlet
4-15/16(126)
1/16(1)
7-1/12(190)
1-7/16(37)
1/16(2) 1/16(2)50-3/8(1280)
Air intake
4
3-3/8(85)
10-1/4(260)
1/16(2)
3-3/8(86)
120°
Ceiling
3(76)
5-7/16(138)
11/16(18)
Φ125)
1-1/2(38)
Φ4-15/16(
4-3/4(121)
4-7/8(124)
15-1/4(387)
7
7
8
8
18-1/8(461)
In case of the rear pipe arrangement, make sure to
remove the shaded portions from the independent piece.
Then put the independent piece back in initial
1-7/8(48)5/16(8)
position.(The heat exchanger might be clogged because of dust)
When drain socket
Drainage
is installed
9-11/16(246)
9-3/16(233)
2
1
5
[FRONT VIEW]
Electrical box
3
7-1/2(190)
2-15/16(75)
2
When electrical box
is pulled down
1-13/16(46)
13
Electrical box
Drainage pipe connection(1(26mm)I.D.)
Drainage pipe connection(for the left arrangement)
Knockout hole for left drain-piping arrangement
Refrigerant-pipe connection(gas pipe side/flared connection)
Refrigerant-pipe connection(liquid pipe side/flared connection)
Knockout hole for upper drain pipe arrangement
Knockout hole for fresh air intake Φ3-15/16(Φ100)
Knockout hole for wiring arrangement Φ7/8(Φ22)
3
214
5
6
Accessory...Drain socket (1(26mm) I.D.)
8
7
Page 14
PCA-A36KA PCA-A42KA Unit: inch (mm)
Drainage
When drain socket
is installed
gas Φ5/8(Φ15.88)
liquid Φ3/8(Φ9.52)
9-5/16(236)
9-3/16(233)
7-7/8(200)
7-1/16(180)
2(51)
3/8(10)
80
3-1/8
62
2-7/165-1/2
6
26-3/4(680)
12-5/8(320)
3/16(5)
1/16(2)
9-1/16(230)
9-11/16(246)
14
9/16
In case of wireless
remote controller
and i-see sensor
(Optional Parts)
7-11/16(195)
3-7/16(88)
3-5/16(84)
85
Emergency operation
switch <Heating>
DEFROST/STAND BY lamp
Operation lamp
Receiver
In case of wireless remote controller
and i-see sensor(Optional Parts)
Emergency operation
switch <Cooling>
57
2-1/4
26-3/4(680)
18-3/4(476)
10(254)
Air intake
140
11/16(18)
5-7/8(150)
61-5/16(1557) (Suspension bolt pitch)
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the drain lift up
mechanism (option parts),refrigerant pipe will be only upward.
4-15/16(126)
1/16(1)
4
3-3/8(85)
10-1/4(260)
1/16(2)
3-3/8(86)
1
1
5
120°
7-1/2(190)
5-7/16(138)
11/16(18)
1-7/16(37)
1-1/2(38)
15/16(Φ125)
Φ4-
4-3/4(121)
15-1/4(387)
7
8
18-1/8(461)
Ceiling
3(76)
[FRONT VIEW]
4-7/8(124)
In case of the rear pipe arrangement, make sure to
remove the shaded portions from the independent piece.
Then put the independent piece back in initial
position.(The heat exchanger might be clogged because of dust)
58-3/4(1493)
1/16(2) 63(1600)
Electrical box
1-7/8(48)5/16(8)
7-3/16 3-3/8
Air outlet
Drainage
When drain socket
is installed
9-11/16(246)
9-3/16(233)
2
182
59-3/4(1518)
Knockout hole for upper drain pipe arrangement
Knockout hole for fresh air intake Φ3-15/16(Φ100)
Knockout hole for wiring arrangement Φ7/8(Φ22)
Drainage pipe connection(1(26mm)I.D.)
Drainage pipe connection(for the left arrangement)
Knockout hole for left drain-piping arrangement
Refrigerant-pipe connection
(gas pipe side/flared connection)
Refrigerant-pipe connection
(liquid pipe side/flared connection)
5
4
3
2
11
Accessory...Drain socket (1(26mm)I.D.)
8
7
6
Electrical box
3
7-1/2(190)
When electrical box
2-15/16(75)
2-15/16(75)
2
1-13/16(46)
is pulled down
14
Page 15
PEA-A12AA PEA-A18AA Unit: mm (inch)
345(13-19/32)
15(19/32)
D (Duct)
25(1)
57(2-1/4)
20(13/16)
23(29/32)
(5-29/32)
150(Duct)
2X2-ø2.9(1/8)
Refrigerant piping
flare connection (gas)
159(6-9/32)
2XE-ø2.9(1/8)
Air outlet
100(3-15/16)X(E-1)=F
100(3-15/16)
10 (13/32)
49
30(1-3/16)
57(2-1/4)
(1-15/16) (24-5/8)
Drain pipe(O.D.ø32(1-1/4))
23 (29/32) 10 (13/32)
25(1)
116
100
(3-15/16)
(2-25/32)(4-19/32)
270(10-21/32)
Refrigerant piping
flare connection (liquid)
625 (Suspension bolt pitch)
700(27-9/16)
677(26-21/32)
70
Drain pipe(O.D.ø32(1-1/4)) (Emergency draining)
Suspension bolt hole 4-14X30(9/16X1-3/16) Slot
L-ø2.9(1/8)
A
C
Air inlet
90
(3-9/16)
M
N
B (Suspension bolt pitch)
23(29/32)
Knockout hole (Indoor/outdoor connecting line)
Control box
170(6-23/32)
102(4-1/32)
200(7-7/8)
Terminal block (Indoor/outdoor connecting line)
Terminal block (Remote controller transmission line)
Drain pipe(O.D.ø32(1-1/4)) (Spontaneous draining)
37(1-15/32)
100 (3-15/16)
20 (13/16)
12(1/2)
88(3-15/32)
H
100(3-15/16)XJ=K
88(3-15/32)
100(3-15/16)
157.5 (6-7/32) 37(1-15/32)
Air filter
12(1/2)
20(13/16)
ø
27(1-3/32)
Knockout hole ø27(1-3/32) (Remote controller transmission line)
450
777
(30-19/32)
450
-23/32)
(17
More than 300
(11-13/16)
50
Note2
(1-31/32)
50(1-31/32)
G
(1-3
1/32
50 ~ 150
~ 5-29/32)
(17-23/32)
Required space for service and maintenance
D
(37-1/2)
(45-3/8)
C
(39-5/16)
1198
(47-3/16)
(33-7/8)
1060
(41-3/4)
Model A
PEA-A12AA
PEA-A18AA
Note1.Use M10 screw for the suspension bolt (field supply).
2.Keep the service space for the maintenance at the bottom.
3.This chart indicates for PEA-A12AA model,which has 2 fans. PEA-A18AA models have 4 fans.
4.In case an inlet duct is used,remove the air filter(supply with
the unit), then install the filter(field supply) at suction side. * PEA-A12AA Gas pipe: Connect the joint :12.7, 1/2” (supply with the unit).
900 952 998 860
(35-7/16)
1100B1152
(43-5/16)
Access door
F
E
800 1000 860
9
(31-1/2)
1000
11
(39-3/8)
175p5(6-29/32p7/32)
(Actual length)
J
HG
7
(33-7/8)
(39-3/8)
1060
1200
(47-1/4)
(41-3/4)
9
Less than 300
K
700
(27-9/16)
900
(35-7/16)
(11-13/16)
Drain hose (I.D.ø32(1-1/4)) <accessory>
1
N
M
L
20
24
1039
(40-29/32)
1239
(48-25/32)
Gas pipe Liquid pipe
990
ø9.52(3/8) *
(39)
1190
ø12.7(1/2)
(46-7/8)
(21-21/32)
Less than 550
(13/32)
More than 10
Ceiling surface
(13/16)
Make the access door at the appointed position
More than 20
properly for service maintenance.
Access door
mm(in.)
2
ø6.35(1/4)
15
Page 16
OUTDOOR UNIT Unit: mm (inch) PUY-A12NHA3(-BS) PUY-A18NHA3(-BS) PUZ-A18NHA3(-BS)
400<15-25/32>
347.5<13-11/16>
Air intake
43.6<1-23/32>
152<6>
Air intake
45.4<1-25/32>
Air discharge
4-oval hole
18<23/32>
Handle
600<23-5/8>
W33<1-5/16> drain hole
155
40<1-9/16>
330<13>
300<11-13/16>
32.5<1-9/32>
22<7/8>
2-W22.2<7/8> 1/2 conduit hole
38<1-1/2>241<9-1/2>
365<14-3/8>
23<29/32>
155<6-3/32>
90<3-17/32>
Service panel
Service panel for charge plug
Connection for liquid pipe
FLARE W6.35<1/4>
10<3/8>
300<11-13/16>
150<5-29/32>
287.5<11-11/32>
Installation bolt pitch
500<19-11/16>
800<31-1/2>
Free space around the outdoor unit (basic example)
Min.100mm<3-15/16>
*1 *2
Min.500mm<19-11/16>
2 sides should be open in the right, left and rear side.
Min.100mm<3-15/16> as long as no obstacle is placed on the rear and light-and-left sides
open
of the unit
Basically
Min.350mm<13-25/32>
*1
Min.100mm<3-15/16>
69<2-23/32>
Connection for gas pipe
Service port
144<5-21/32>
183<7-7/32>
FOUNDATION BOLTS
Please secure the unit firmly with 4 foundation M10<W3/8> bolts. (Bolts, washers and nut must be purchased locally.)
<Foundation bolt height>
FOUNDATION
18mm<23/32>
Max.
PIPING-WIRING DIRECTION
Piping and wiring connection can
be made from the rear direction only.
FLARE W12.7<1/2>
Minimum installation space for outdoor unit
*1 In the place where short cycle tends to occur, cooling and heating capacity and power consumption might get lowered 10%. Air outlet guide (optional PAC-SG58SG-E) will help them improve. *2 If air discharges to the wall, the surface might get stained.
16
Page 17
PUZ-A24NHA3(-BS) PUY-A24NHA3(-BS) Unit: mm (inch)
Min. 10mm
<3/8>
Min. 10mm
<3/8>
Min. 100mm
<3-15/16>
Min. 500mm
<19-11/16>
Min.
100mm
<3-15/16>
Min.
500mm
<191/16>
Max.
300mm<1-3/16>
Min.
10mm
<3/8>
Min.
500mm
<19-11/16>
Service space
FOUNDATION
<Foundation bolt height>
FREE
When installing the conduit,
Set the attachment to the
inner side of each panel.
1/2 Conduit attachment
2-:22.2<7/8>
40<1-9/16>
31<1-7/32>
74<2-19/32>
330 <13>
175 <6-7/8>
600 <23-5/8>
175 <6-7/8>
53 <2-3/32>
28 <1-3/32>
370 <14-9/16>
19 <3/4>
56 <2-7/32>
45 <1-25/32>
42 <1-21/32>
66 <2-5/8>
417 <16-13/32>
2-U Shaped notched hole
(Foundfation Bolt M10<W3/8>)
Side Air Intake
Rear Air Intake
Air Discharge
2-12%36 Oval hole
(Foundation Bolt M10<W3/8>)
30 <1-3/16>
Side Air Intake
Handle
Rear piping cover
Front piping cover
81<3-3/16>
219 <8-5/8>
30 <1-3/16>
71 <2-13/16>
71 <2-13/16>
Bottom piping hole
(Knockout)
Drain hole
(5-:33<1-5/16>)
Handle
Handle
Rear Air Intake
Air Intake
670 <26-3/8>
*1 443<17-7/16>
*1 447<17-19/32>
322 <12-11/16>
950 <37-13/32>
473 <18-5/8>
943 <37-1/8>
23<29/32>
2
1
Handle
Handle
Service panel
Earth terminal
Left···Power supply wiring
Reight···Indoor/Outdoor wiring
Terminal Block
Conduit hole
(2-
:
27<1-1/16>Knockout)
Right trunking hole
(Knockout)
Right piping hole
(Knockout)
65<2-9/16>
92<3-5/8>
40 <1-9/16> 45 <1-25/32>
19<3/4>
27<1-1/16>
23<29/32>
23<29/32>
73<2-7/8>
Conduit hole
(2-:27<1-1/16>Knockout)
Front trunking hole
(Knockout)
Front piping hole
(Knockout)
:
92
<3-5/8>
Conduit hole
(2-
:
27<1-1/16>Knockout)
Rear trunking hole
(Knockout)
Rear piping hole
(Knockout)
220
<8-21/32>
145
<5-23/32>
145
<5-23/32>
145
<5-23/32>
55<2-3/16>
63<2-1/2>
63<2-1/2>
75
<2-31/32>
40<1-9/16>
45<1-25/32>
40<1-9/16>
23<29/32>
73<2-7/8>
63<2-1/2>
55<2-3/16>
27<1-1/16>
:92<3-5/8>
:
92<3-5/8>
73<2-7/8>
27<1-1/16>
92<3-5/8>
92<3-5/8>
65<2-9/16>
95<3-5/8>
55<2-3/16>
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
Dimensions of space needed
for service access are
shown in the below diagram.
Please secure the unit firmly
with 4 foundation (M10<W3/8>)
bolts. (Bolts and washers must
be purchased locally.)
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
····Refrigerant GAS pipe connction (FLARE):15.88<5/8>
····Refrigerant LIQUID pipe connection (FLARE): 9.52<3/8>
*1 ····Indication of STOP VALVE connection location.
Example of Notes
Piping Knockout Hole Details
1 FREE SPACE (Around the unit)
2 SERVICE SPACE
3 FOUNDATION BOLTS
4 PIPING-WIRING DIRECTIONS
PUZ-A30NHA3(-BS) PUY-A30NHA3(-BS) PUZ-A36NHA3(-BS) PUY-A36NHA3(-BS)
17
Page 18
PUZ-A42NHA3(-BS) Unit: mm (inch) PUY-A42NHA3(-BS)
417<16-13/32>
19<3/4>
2-U Shaped notched hole
(Foundation Bolt M10<W3/8>)
175<6-7/8>
600<23-5/8>
Rear Air Intake
175<6-7/8>
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
<Foundation bolt height>
Please secure the unit firmly
with 4 foundation (M10<W3/8>)
bolts. (Bolts and washers must
3 FOUNDATION BOLTS
be purchased locally.)
<5-29/32> 150mm Min.
Dimensions of space needed
for service access are
shown in the below diagram.
370<14-9/16>
56<2-7/32>
45<1-25/32>
330<13>30<1-3/16>
Side Air Intake
FOUNDATION
<19-11/16> 500mm Min.
2 SERVICE SPACE
Min.
10mm<3/8>
42<1-21/32>
66<2-5/8>
Air Discharge
<1-3/16> 30mm Min.
Min.
500mm
<19-11/16>
Service space
28<1-3/32>
53<2-3/32>
2-12%36 Oval hole
(Foundation Bolt M10<W3/8>)
Left···Power supply wiring
Terminal Block
950<37-13/32>
Earth terminal
322<12-11/16>
Handle
Side Air Intake
Rear Air Intake
Handle
Right····Indoor/Outdoor wiring
Service panel
Handle
Handle
Handle
1076<42-3/8>
635<25>
1350<53-5/32>
1
2
Air intake
* 1 447<17-19/32>
Front piping cover
* 1 443<17-7/16>
23<29/32>
371<14-19/32>
When installing the conduit.
Rear piping cover
Set the attachment to the
inner side of each panel.
Conduit hole
(2-:27<1-1/16>Knockout)
Bottom piping hole
71<2-13/16>
71<2-13/16>
1/2 Conduit attachment
2-:22.2<7/8>
Conduit hole
(2-:27<1-1/16>Knockout)
40<1-9/16>
45<1-25/32>
Right trunking hole
(Knockout)
40<1-9/16>
75
<2-31/32>
Right piping hole
(Knockout)
45<1-25/32>
(Knockout)
219<8-5/8>
Rear trunking hole
(Knockout)
55<2-3/16>
63<2-1/2>
73<2-7/8>
63<2-1/2>
92<3-5/8>
73<2-7/8>
<2-1/2>
63
55<2-3/16>
31<1-7/32>
40<1-9/16>
74<2-19/32>
/8>
:92
<3-5
/8>
:92
<3-5
55<2-3/16>
27<1-1/16>
Drain hole
5-:33<1-5/16>
145
<5-23/32>
145
<5-23/32>
145
<5-23/32>
220
<8-21/32>
81<3-3/16>
30<1-3/16>
Rear piping hole
(Knockout)
92<3-5/8>
65<2-9/16>
27<1-1/16>
23<29/32>
92<3-5/8>
19<3/4>
73<2-7/8>
23<29/32>
23<29/32>
27<1-1/16>
Min. 10mm
<3/8>
FREE
The diagram below shows a
basic example.
Explantion of particular details are
1 FREE SPACE (Around the unit)
given in the installation manuals etc.
<3/8>
Min. 10mm
Min. 150mm
<5-29/32>
<39-3/8>
Min. 1000mm
····Refrigerant GAS pipe connction (FLARE):15.88<5/8>
····Refrigerant LIQUID pipe connection (FLARE): 9.52<3/8>
Example of Notes
*1 ····Indication of STOP VALVE connection location.
18
/8>
92
:
(Knockout)
<3-5
65<2-9/16>
92<3-5/8>
Front piping hole
(Knockout)
40<1-9/16>
Conduit hole
(2-:27<1-1/16>Knockout)
Piping Knockout Hole Details
Front trunking hole
Page 19
WIRED REMOTE CONTROLLER
48.5<1-15/16>
130<5-1/8>
120<4-3/4>
19
<3/4>
Unit: mm (inch)
19
Page 20
WIRELESS REMOTE CONTROLLER
58<2-9/32>
COOL
DRY
AUTO
FAN
HEAT
TEST
CHECK
RUN
MODEL
SELECT
FAN
SWING
NOT AVAILABLE
START
°F °C
AMPMSTOP
AMPM
Unit: mm (inch)
159.3<6-3/8>
19<3/4>
55<2-5/32>
20
Page 21
4
WIRING DIAGRAM
PLA-A12BA PLA-A18BA PLA-A24BA PLA-A30BA PLA-A36BA PLA-A42BA
[LEGEND]
SYMBOL SYMBOLNAME NAME
I.B INDOOR CONTROLLER BOARD
CN2L CN24 CONNECTOR<BACK-UP HEATING> CN30 CONNECTOR<LLC> CN32 CN41 CN51 DSA FUSE LED1 LED2 LED3 SW1 SW2 SWE X1
ZNR01,02 DP FS
I.B
13
CN3G (BLK)
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) SURGE ABSORBER FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) +See table 1. SWITCH (CAPACITY CODE) +See table 2. CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN PUMP) VAR IST OR
DRAIN-UP MACHINE DRAIN FLOAT SWITCH
Refer to tables 1 and 2.
VAN E
CNV
(WHT)
1011121314151617181920
123456789
LED3 LED2 LED1
I-SEE
SENSOR
CN4Y (WHT)
4
I-SEE
BZ
SENSOR
LED2
I-SEE SENSOR CORNER PANEL
LED1
RU
(OPTIONAL PART)
W.B
MVMVMVMV
GRILLE
5555
MMMM
WIRELESS
CN90
(WHT)
9
CNB
SW1
SW2
SENSOR MOTOR
5
M
MT
SW2SW1
I-SEE
CN6Y (RED)
21 TB6
R.B
J42J41
Pair No.
CN2L
21
CNAC (WHT)
36141911
MF MV TB4 TB5,TB6
TH1
TH2
TH5
OPTION PART
W.B
TB5
TRANSMISSION WIRES DC12V
CN32
(WHT)
1
CN51
(WHT)
CN24
51
CN41
(WHT)
41
SWE
ON OFF
FLOAT SW
LIQUID/PIPE
CN4F
(WHT)
FAN MOTOR VANE MOTOR TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP. THERMISTOR (32˚F/ 15kΩ, 77˚F / 5.4kΩ DETECT) PIPE TEMP. THERMISTOR/LIQUID (32˚F/ 15kΩ, 77˚F/ 5.4kΩ DETECT) COND. / EVA. TEMP. THERMISTOR (32˚F/ 15kΩ, 77˚F/ 5.4kΩ DETECT)
PCB FOR WIRELESS REMOTE CONTROLLER
BZ
BUZZER
LED1
LED (OPERATION INDICATION : GREEN)
LED2
LED (PREPARATION FOR HEATING : ORANGE) RECEIVING UNIT
RU SW1
EMERGENCY OPERATION (HEAT / DOWN)
SW2
EMERGENCY OPERATION (COOL / UP)
2 1
135
OUTDOOR
3
2
CN44
(WHT)
(YLW)
REMOCON
t˚t˚
TH5TH2FSTH1
INDOOR/OUTDOOR
COMMUNICATION
112
CN22
(BLU)
INTAKE
CN20
(RED)
t˚
13
CN3C
(BLU)
CN30
(GRN)
13
RECTIFICATION
CN01
(BLK)
DSA
U
ZNR02
DC280V
FAN CNMF (WHT
)
71121414 4 31
MS
3~
MF
DP
U
ZNR01
X1
D.U.M
CNP
(BLU)
M 1~
FUSE
+Be sure to turn off the power source and then disconnect fan motor connector. (Failure to do so will cause trouble in fan motor.)
YLW
ORN
ORN BRN
YLW ORN
TB4
+1
S1 S2 S3
TO OUTDOOR UNIT
<Table 1>SW1(MODEL SELECTION)
SW1
Service
12345
ON OFF
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal block.
<Table 2>SW2(CAPACITY CODE)
MODELS
PLA-A12BA
PLA-A18BA
PLA-A24BA
Service
12345
12345
12345
ON OFF
ON OFF
ON OFF
SW2
MODELS
PLA-A30BA
PLA-A36BA
PLA-A42BA
Service
12345
12345
12345
ON OFF
ON OFF
ON OFF
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wiring.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing.
+1.Use copper supply wires.
[Self-diagnosis]
1.For details on how to operate self-diagnosis with the wireless remote control, refer to the technical manuals etc.
2.For the wired remote control:When you quickly press twice the CHECK switch on the remote control, the unit begins self-diagnosis, and Check Codes generated in the past appear on the display.
21
Page 22
PKA-A12HA PKA-A18HA PKA-A12HAL PKA-A18HAL
[Explanation of symbols]
Symbol
I.B Indoor controller board
CN2L Connector (LOSSNAY) CN30 Connector (LLC) CN32 Connector ( Remote switch) CN41 Connector (HA terminal-A) CN51 Connector (Centrally control) CN90 Connector (Remote operation adapter) CN152 Connector (Back-up heating) DSA Surge absorber FUSE FUSE(T3.15AL250V) LED1 Power supply (I.B) LED2 Power supply (R.B) LED3 Transmission (Indoor-outdoor) SW1 Switch (Model selection) +See table 1 SW2
Switch (Capacity code) +See table 2 Connector (Emergency operation)
SWE ZNR01,02
Varistor
R.B
Wired remote controller
TB6
Terminal block (Remote controller transmission line)
Name
I.B
T11 DB1
SWE
ON OFF
Refer to tables 1and 2
CN151 (WHT)
11
M
2
11 1 54
CN2L
(RED)
CN152
(WHT)
CN20
(RED)
○t○t○
t
TH1 TH2 TH5
CN90
(WHT)
141425
CN41
(WHT)
CN44
(WHT)
LED1
LED3
LED2
11310
CN30 (BLK)
Notes:
1.SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3)for correct wirings.
3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system for power and signal.
+
1: If indoor and outdoor units have separate power supplies, refer to Fig 1.
+
2: For power supply system of this unit, refer to the caution label located near this diagram.
+
3: Use copper supply wires.
Symbol M Vane motor MS Fan motor
Switch board
S.W
SWE2 Emergency operation TB2 Terminal block(Indoor unit Power (option)) TB4 Terminal block (Indoor/outdoor connecting line) TB5 Terminal block (Remote controller transmission line) TH1 Room temp. Thermistor
(32°F/15ΚΩ, 77°F/5.4ΚΩ Detect)
TH2
Pipe temp. Thermistor/liquid
(32°F/15ΚΩ, 77°F/5.4ΚΩ Detect)
TH5
Cond./eva. temp. Thermistor
(32°F/15ΚΩ, 77°F/5.4ΚΩ Detect)
W.B Pcb for wireless remote controller
LED1 LED (Operation indication: Green)
LED2 LED (Preparation for heating: Orange)
REC1 Receiving unit
MS
3~
CNMF (WHT)
U
U
X1
CNP(BLU)
6
FUSE
CN01 (BLK)
DSA
3 1
3
CN3C (BLU)
1
LDSWE(A
(BLU)
CNRU (WHT)
1
CN22 (BLU)
2
)
1139
CN32
(WHT)
CN51
(WHT)
CN4F
(WHT)
1
ZNR01
ZNR02
Name
1 3
ORN
5
BLK
ORN
BRN
W.B
6
LD101(B)
LED1
YLWYLW ORN
2
RU
REC1
LED2
TB4 S1 S2 S3
S.W
LDSWE(B) SWE2
<+3>
TO OUTDOOR UNIT
+1(Fig. 1)
CN01 (BLK)
1 3 5
I.B
<Table 1> SW1 (MODEL SELECTION)
SETTING
12345
<Table 2> SW2(CAPACITY CODE)
MODELS
A12
12345
R.B
1 2
TB6
TB2
RED
L1
BLU
L2
/
YLW
GR
TB4
YLW
S1
ORN ORN
S2
BRN
S3
COMMUNICATION
BLU
BLU
TB5
For PKA-A.HA
I.B
YLW ORN
3
1
CN3C(BLU)
A18
1 2
GRN
INDOOR/OUTDOOR
ON OFF
SETTING
12345
POWER SUPPLY 208/230V 60Hz
TO OUTDOOR UNIT
ON OFF
ON OFF
22
Page 23
PKA-A24KA PKA-A24KAL PKA-A30KA PKA-A30KAL PKA-A36KA PKA-A36KAL
Notes:
1.SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3)for correct wirings.
3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system for power and signal.
+
1: If indoor and outdoor units have separate power supplies, refer to Fig 1.
+
2: For power supply system of this unit, refer to the caution label located near this diagram.
+
3: Use copper supply wires.
23
Page 24
PCA-A24KA PCA-A30KA PCA-A36KA PCA-A42KA
[LEGEND]
SYMBOL SYMBOLNAME NAME
I.B
CN2L CN24 CN30 CN32 CN41 CN51 DSA FUSE LED1 LED2 LED3 SW1 SW2 SWE X1
ZNR01,02 R.B MF MV
INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR (BACK-UP HEATING) CONNECTOR (LLC) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) SURGE ABSORBER FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) +See table 1 SWITCH (CAPACITY CODE) +See table 2 CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN LIFT UP MECHANISM) VAR IST OR WIRED REMOTE CONTROLLER BOARD
FAN MOTOR
VANE MOTOR
TB4 TB5,TB6
TH1
TH2
TH5
OPTIONAL PARTS
W.B
BZ LED1 LED2 RU SW1 SW2
DP
FS
TERMINAL BLOCK (
INDOOR/OUTDOOR CONNECTING LINE TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE)
ROOM TEMP. THERMISTOR (32ºF / 15kΩ, 77ºF/ 5. 4kΩ DETECT) PIPE TEMP. THERMISTOR/LIQUID (32ºF / 15kΩ, 77ºF/ 5. 4kΩ DETECT) COND. / EVA. TEMP. THERMISTOR (32ºF / 15kΩ, 77ºF/ 5. 4kΩ DETECT)
PCB FOR WIRELESS REMOTE CONTROLLER BUZZER LED (OPERATION INDICATION : GREEN) LED (PREPARATION FOR HEATING : ORANGE) RECEIVING UNIT EMERGENCY OPERATION (HEAT / DOWN) EMERGENCY OPERATION (COOL / UP) DRAIN LIFT UP MECHANISM DRAIN FLOAT SWITCH
)
I.B
VAN E
CNV
20
(WHT)
12345678910111213141516171819
I-SEE
WIRELESS
CN90
(WHT)
19
9
CNB
5
M
MV
W.B
(OPTIONAL PARTS)
<Table 2>SW2(CAPACITY CODE)
MODELS
PCA-A24KA
PCA-A30KA
BZ
SW1
LED2
SW2
LED1
RU
Service Service
12345
12345
SENSOR
CN4Y
(WHT)
141 6
4
I-SEE
SENSOR
I-SEE SENSOR
(OPTIONAL PARTS)
SW2
MODELS
PCA-A36KA
ON OFF
PCA-A42KA
ON OFF
LED3 LED2 LED1
I-SEE
SENSOR MOTOR
CN6Y
(RED)
5
When attaching
M
drain lift up
MT
mechanism (optional parts), remove the jumper connector CN4F and fit the drain float switch (FS).
12345
ON OFF
12345
ON OFF
Refer to tables 1 and 2
2
1
TB6
R.B
SW2SW1
J42J41
Pair No.
CN51(WHT)
51
CN2L
21
(RED)
FLOAT SW
CN4F
(WHT)
ON OFF
4
When attaching drain lift up mechanism (optional parts)
FLOAT SW
CN4F
(WHT)
TB5
2
TRANSMISSION WIRES DC12V
CN32
(WHT)
CN41(WHT)
41
SWE
1
113
CN24
(YLW)
14
FS
INDOOR/OUTDOOR
COMMUNICATION
12
21
REMOCON
CN22
(BLU)
INTAKE
LIQUID/PIPE
CN44
(WHT)
14
t° t°
TH2 TH5 TH1
<Table 1>SW1(MODEL SELECTION)
SW1
Service
12345
ON OFF
OUTDOOR
135
CN01
3
1
CN3C
(BLU)
DC294~325V
RECTIFICATION
CN30
CN20
(GRN)
(RED)
1
21
+
Be sure to turn off the source power
(BLK)
DSA
U
ZNR02
FAN CNMF (WHT
)
741
331
MS
3~
MF
(OPTIONAL PARTS)
M
1~
DP
U
ZNR01
X1
D.U.M
CNP
(BLU)
FUSE
YLW
ORN
ORN BRN
YLW
ORN
TB4
S2 S3
+
1
S1
and then disconnect fan motor connector. (Failure to do so will cause trouble in Fan motor)
TO OUTDOOR UNIT
1.SymboIs used in wiring diagram above are, : Connector,
Notes:
: Terminal block.
2.
Indoor and outdoor connecting wires have poIarities, make sure
to match terminal numbers (S1, S2, S3) for correct wirings.
3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing.
+
1: Use copper supply wire.
[Self-diagnosis]
1.For details on how to operate self-diagnosis with the wireless remote control,refer to the technical manuals etc.
2.For the wired remote control:When you quickly press twice the CHECK switch on the remote control, the unit begins self­ diagnosis, and Check Codes generated in the past appear on the display. For Check Codes and Symptoms refer to the table below.
24
Page 25
PEA-A12AA PEA-A18AA
TB15
TO MA REMOTE CONTROLLER
SYMBOL EXPLANATION
I. B.
FUSE FUSE AC250V 6.3A
ZNR01,02 VARISTOR
DSA
CN2L
CN32
CN41
CN51
CN90 CONNECTOR (WIRELESS)
LED1 POWER SUPPLY(I.B.)
Note1.Since the outdoor side electric wiring may change be sure
to check the outdoor unit electric wiring for servicing.
Indoor and outdoor connecting wires have poIarities, make sure to match terminal
2.
numbers (S1, S2, S3)for correct wirings.
3.Symbols used in wiring diagram above are, :Connector, :Terminal.
4.Use copper supply wire.
1 2
SW2SW1
CN2L
LED3
CN90
NAME
INDOOR CONTROLLER BOARD
ARRESTER
AUX. RELAYX1
CONNECTOR (LOSSNAY)
CONNECTOR (BACK-UP HEATING)CN24
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
CN24
CN32
(Yellow)
CN41
CN51
ON
OFF
SWE
LED2
21
tot
FS TH2 TH5 TH1
LED2
LED3
SW1
SW2
SWE
TH1 INTAKE AIR TEMP. THERMISTOR
TH2 PIPE TEMP. THERMISTOR/LIQUID
TH5 COND./EVA. TEMP. THERMISTOR
FS FLOAT SWITCH
TB4
TB15
I. B.
3
1
CN3C
12
CN22
(Blue)
DC310~340V Rectify circuit
LED1
LED1
CN20CN44CN4F
4231
o
(Red)
12
o
t
(Blue)
CNMF
M
ZNR01
1456734
U
CN01
(Black)
ZNR02
Fan motor
EMANLOBMYSLOBMYS
POWER SUPPLY(I.B.)
TRANSMISSION(INDOOR-OUTDOOR)
SWITCH (FOR MODE SELECTION)
SWITCH (FOR CAPACITY CODE)
CONNECTOR (EMERGENCY OPERATION)
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE)
INSIDE SECTION OF CONTROL BOX
135
DSA
U
FUSE
X1
CNP
31
M
1~
Drainpump
(Blue)
CONTROL BOX
PARTS LOCATION
TB4
S1 S2
S3
I
. B.
TO OUTDOOR UNIT
4BT51BT
25
Page 26
PUZ-A18NHA3 PUZ-A18NHA3-BS PUY-A12/18NHA3 PUY-A12/18NHA3-BS
[LEGEND]
SYMBOL TB1 MC MF1 21S4 63H TH3 TH6 TH7 TH8 TH32 LEV-A ACL CY1,CY2 P. B .
TABR/S TABU/V/W
MF1
MS
3~
Terminal Block<Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch
Thermistor<Outdoor Pipe>
Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Thermistor<Heatsink> Thermistor<Shell> Electronic Expansion Valve
Reactor Capacitor Power Circuit Board Connection Terminal<L1/L2-Phase> Connection Terminal<U/V/W-Phase>
C. B.
1
3
1
CNDC
(PNK)
CNS
(WHT)
31
NAME SYMBOL NAME SYMBOL NAME
PFC IPM CB1~CB3
N.F.
LI/LO NI/NO EI,E2,E3 52C
C.B.
SW1
SW4 SW5 SW6 SW7 SW8
63H
412112
TH3
(WHT)
31
63H
(YLW)
CN2
(WHT)
71
5
F3
F4
7
CNF1
(WHT)
F2
F1
TH32
(BLK)
TRANS
CNAC (WHT)
TH7 TH6 TH3TH32
21
43
t° t° t°
TH7/6 (RED)
Converter Power Module Main Smoothing Capacitor
Noise Filter Circuit Board Connection Terminal<L1-Phase> Connection Terminal<L2-Phase> Connection Terminal<Ground>
52C Relay
Controller Circuit Board Switch<
Forced Defrost, Defect History
Record Reset, Refrigerant Address> Switch<Test Operation> Switch<Function Switch> Switch<Model Select> Switch<Function Setup> Switch<Function Setup>
LEV-A
LED2
M
LEV-A (WHT)
LED1
21S4
(GRN)
61
1
CN4
(WHT)
12
2
21S4
3
31
CNVMNT
(WHT)
CNM
(WHT)
X55
X52
13
1313
SV2
(BLU)
PUZ only
CNMNT
(WHT)
CN52C
(RED)
SW9 LED1,LED2 F1~F4 SWP CN31 SS CNM
CNMNT
CNVMNT
CNDM CN51 X51, X52, X55
When M-NET adapter is connected
5
ABS
CN5
1
LED2
LED3
LED4
M-NET ADAPTER
2 1
CN2M
LED5
TB7
M-NET
SW7
SW9
3
1
(WHT)
5
(WHT)
1
5
5
+1+1
51
SW5SW8SW4 SWP
SW6SW1
14
CN31
221
X51
SS
(WHT)
CNDM
CN51
Switch LED<Operation Inspection Indicators> Fuse<T6.3AL250V> Switch<Pump Down> Connector<Emergency Operation> Connector<Connection for Option> Connector<A-Control Service Inspection Kit> Connector <Connected to Optional M-NET Adapter Board> Connector <Connected to Optional M-NET Adapter Board>
Connector <Connected for Option (Contact Input)> Connector <Connected for Option (Signal output)>
Relay
SW11
SW1
(WHT)
SW12
CND
(WHT)
(WHT)
31
LED1
3
P. B .
PFC
TABR
RED
WHT
TABS
CB1 CB2 CB3
+1 MODEL SELECT
MODEL SW6
ON
PUZ-A18N
OFF
PUY-A12N
PUY-A18N
123456
ON
OFF
123456
ON
OFF
123456
78
78
78
+2. SW5-1 to 4 : Function switch
MC
MS
3~
UVW
BLK
WHT
RED
TABU
TABV
TABW
SW5-5.6
ON
OFF
123456
ON
OFF
123456
ON
OFF
123456
RED
WHT
RED
WHT
ACL
1
CN5
2
(RED)
IPM
1
CN4
2
(WHT)
1
CN3
(WHT)
2
1
CN2
(WHT)
7
+2
RED
L1 L2 GR S1 S2 S3
BLU
2
2
TH8
GRN
RED
WHT
N. F.
LO NO
52C
1
3
5
YLW
ORN
BRN
CY1 CY2
(RED)
CNAC2
1
3
(WHT)
CNAC1
U
LI EI NI
1
2
(BLK)
CN52C
E3
CN5
(RED)
1
2
E2
U
M-NET ADAPTER
SYMBOL
TB7
2
CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5
2
Terminal Block<M-net connection> Connector<Transmission> Connector<Power Supply> Connector<M-NET communication> Switch<Status of communication> Switch<Address setting : 1s digit> Switch<Address setting : 10s digit> LED<Power Supply : DC5V> LED<Connection to Outdoor Unit> LED<Transmission : Sending> LED<Transmission : Recelving> LED<Power Supply : DC12V>
NAME
TB1
POWER SUPPLY 208 / 230V 60Hz
INDOOR UNIT
+Use copper supply wires.
26
Page 27
PUZ-A24NHA3 PUZ-A24NHA3-BS PUY-A24NHA3 PUY-A24NHA3-BS
[LEGEND]
SYMBOL TB1 MC MF1 21S4 63H SV Solenoid Valve (Bypass Valve) TH3 TH6 TH7 TH8 TH32 LEV-A ACL
CY1,CY2
P.B.
Terminal Block<Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch
Thermistor<Outdoor Pipe>
Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Thermistor<Heatsink> Thermistor<Shell> Electronic Expansion Valve
Reactor Capacitor Power Circuit Board
TABR/S
Connection Terminal<L1/L2-Phase>
TABU/V/W
Connection Terminal<U/V/W-Phase>
NAME SYMBOL NAME SYMBOL NAME
N.F.
C.B.
C. B.
CNF1
1
MF1 MS
3~
CNS
(WHT)
3
1
CNDC (PNK)
31
7
(WHT)
F2
F1
TH32 (BLK)
TRANS
CNAC (WHT)
Converter
PFC
Power Module
IPM
Main Smoothing Capacitor
CB1~CB3
LI/LO NI/NO EI,E2,E3 52C
SW1
SW4 SW5 SW6 SW7 SW8 SW9
Noise Filter Circuit Board Connection Terminal<L1-Phase> Connection Terminal<L2-Phase> Connection Terminal<Ground>
52C Relay
Controller Circuit Board Switch<Forced Defrost, Defect History Record Reset, Refrigerant Address> Switch<Test Operation> Switch<Function Switch> Switch<Model Select> Switch<Function Setup> Switch<Function Setup> Switch
TH7 TH6 TH3TH32
21
43
t° t° t°
TH7/6 (RED)
63H
412121
TH3
(WHT)
LED2
31
63H
(YLW)
CN2
(WHT)
71
5
F3
F4
(GRN)
PUZ only
21S4
LEV-A
LEV-A (WHT)
21S4
M
LED1
61
CNVMNT
1
CN4
(WHT)
12
2
X52
13
SV
3
31
(WHT)
CNM
(WHT)
X55
13 13
SV2
(BLU)
CNMNT
(WHT)
CN52C
(RED)
5
51
14
221
LED1,LED2
LED<Operation Inspection Indicators>
F1~F4
Fuse<T6.3AL250V>
SWP
Switch<Pump Down>
CN31
Connector<Emergency Operation>
SS
CNM CNMNT
CNVMNT
CNDM CN51 X51,X52,X55
Connector<Connection for Option>
Connector<A-Control Service Inspection Kit> Connector
<Connected to Optional M-NET Adapter Board> Connector
<Connected to Optional M-NET Adapter Board> Connector <Connected for Option (Contact Input)> Connector <Connected for Option (Signal output)> Relay
When M-NET adapter is connected
5
1
+
+1
SW7
SW5SW8SW4 SWP
SW6SW1
SW9
CN31
3
ABS
1
(WHT)
CNDM
5
CN51
(WHT)
1
X51
SS
(WHT)
5
SW1
CN5
(WHT)
1
LED2
LED3
LED4
M-NET ADAPTER
2 1
CN2M
(WHT)
LED1
LED5
3
TB7
M-NET
SW11
SW12
CND
(WHT)
31
P. B.
PFC
+1 MODEL SELECT
MODEL SW6
ON
PUZ-A24N
OFF
123456
ON
PUY-A24N
OFF
123456
+2. SW5-1 to 4 : Function switch
M-NET ADAPTER
SYMBOL
Terminal Block<M-net connection>
TB7
Connector<Transmission>
CN5
Connector<Power Supply>
CND
Connector<M-NET communication>
CN2M
Switch<Status of communication>
SW1
Switch<Address setting : 1s digit>
SW11
Switch<Address setting : 10s digit>
SW12
LED<Power Supply : DC5V>
LED1
LED<Connection to Outdoor Unit>
LED2
LED<Transmission : Sending>
LED3
LED<Transmission : Recelving>
LED4
LED<Power Supply : DC12V>
LED5
BLK
TABR
RED
WHT
TABS
CB1 CB2 CB3
ON
OFF
7878123456
ON
OFF
123456
NAME
MC
MS
3~
UVW
WHT
RED
TABU
TABV
TABW
SW5-5.6
RED
WHT
RED
WHT
ACL
1
CN5
2
(RED)
IPM
1
CN4
2
(WHT)
1
CN3
(WHT)
2
1
CN2
(WHT)
7
+2
RED
BLU
L1 L2 GR
POWER SUPPLY 208 / 230V 60Hz
+Use copper supply wires.
2
2
TH8
5
GRN
S1 S2 S3
YLW
INDOOR UNIT
ORN
BRN
CY1 CY2
TB1
1
3
(RED)
CNAC2
1
3
(WHT)
CNAC1
RED
LO NO
52C
U
LI
WHT
N. F.
2
1
2
(BLK)
CN52C
E3
CN5
(RED)
1
2
2
E2
U
EI
NI
27
Page 28
PUZ-A30/36NHA3 PUZ-A30/36NHA3-BS PUY-A30/36NHA3 PUY-A30/36NHA3-BS
[LEGEND]
SYMBOL TB1 MC MF1 21S4 SV Solenoid Valve (Bypass Valve) 63H TH3 TH6 TH7 TH8 TH32 LEV-A DCL CY1, CY2 ACTM
Terminal Block<Power Supply, Indoor/Outdoor > Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve)
High Pressure Switch
Thermistor<Outdoor Pipe>
Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Thermistor<Heatsink> Thermistor<Shell> Electronic Expansion Valve
Reactor
Capacitor
Active Filter Module
NAME SYMBOL NAME SYMBOL NAME
C. B.
1
MF1
MS 3~
2
CNS
(WHT)
31
4
7
TH8
2
2
3
1
7
CNDC
(PNK)
CNF1
(WHT)
F2
F1
1
CNAF
(WHT)
6 1
(WHT)
7 1 2 1 2 1 2
TABN
TABP
P. B .
CN2
CN3
(WHT)
CN5
(RED)
CN4
(WHT)
P.B.
TABU/V/W TABS/T TABP1/P2 TABN1/N2 DS2, DS3 IPM
N.F.
LI/LO NI/NO EI, E2 52C
C.B.
F1~F4 SW1
TH32 (BLK)
TRANS
CNAC (WHT)
IPM
RED
TABP 2
Power Circuit Board Connection Terminal<U/V/W-Phase> Connection Terminal<L1/L2-Phase> Connection Terminal<DC Voltage> Connection Terminal<DC Voltage> Diode Bridge Power Module Noise Filter Circuit Board Connection Lead<L1-Phase> Connection Lead<L2-Phase> Connection Terminal<Ground> 52C Relay Controller Circuit Board Fuse<T6.3AL250V> Switch<
Forced Defrost, Defect History Record
Reset, Refrigerant Address>
TH7TH6 TH3TH32
t° t° t°
TH7/6 (RED)
21
43
TABV
TABU
RED
WHT
UVW
MS
3~
63H
412121
TH3
(WHT)
31
63H
(YLW)
CN2
(WHT)
71
7
F3
F4
21S4
PUZ only
CNDC
(PNK)
2
1
3
TABN 1
U
BLK
TABW
BLK
MC
LED2
DS3
DS2
2
13
(GRN)
LEV-A
(WHT)
X52
21S4
TABP 1
M
LEV-A (WHT)
CN4
12
TABT
TABS
TABN2
WHT
LED1
SW4
Switch<Test Operation>
SW5
Switch<Function Switch>
SW6
Switch<Model Select>
SW7
Switch<Function Setup>
SW8
Switch<Function Setup>
SW9
Switch
SWP
Switch<Pump Down>
CN31
Connector<Emergency Operation>
LED1,LED2
LED<Operation Inspection Indicators>
SS
Connector<Connection for Option>
CNM
Connector<A-Control Service Inspection Kit> Connector<Connected to Optional M-NET Adapter Board>
CNMNT CNVMNT
Connector<Connected to Optional M-NET Adapter Board>
CNDM
Connector< Connected for Option (Contact Input)> Connector< Connected for Option (Signal output)>
CN51
Relay
X51,X52,X55
3
5
61
31
51
CNVMNT
CNMNT
SW5SW8SW4SWP
X51
SS
(WHT)
SW6SW1
14
CN31
SV
BLU
WHT
RED
(WHT)
(WHT)
1
CNM
(WHT)
CN52C
(RED)
221
X55
13
13
SV2
(BLU)
+1+1
(WHT)
CNDM
CN51
(WHT)
CNAC2
3
1
CNAC1
SW7
SW9
3
1
3151
LO
(RED)
(WHT)
LI NI
When M-NET adapter is connected
5
ABS
BLU
WHT
NO
52C
U
U
5
CN5
(WHT)
1
LED2 LED3 LED4
M-NET ADAPTER
2
1
CN2M
(WHT)
LED5
TB7
M-NET
N. F.
1
2
(BLK)
CN52C
E2
1
2
CN5
(RED)
EI
SW1
LED1
CND
(WHT)
31
3
2
SW11
SW12
2
+
1 MODEL SELECT
MODEL SW6
ON
PUZ-A30N
OFF
123456
ON
PUZ-A36N
OFF
123456
ON
PUY-A30N
OFF
123456
ON
PUY-A36N
OFF
+
2. SW5-1 to 4 : Function switch
M-NET ADAPTER
123456
SYMBOL
Terminal Block<M-net connection>
TB7
Connector<Transmission>
CN5
Connector<Power Supply>
CND
Connector<M-NET communication>
CN2M
Switch<Status of communication>
SW1
Switch<Address setting : 1s digit>
SW11
Switch<Address setting : 10s digit>
SW12
LED<Power Supply : DC5V>
LED1
LED<Connection to Outdoor Unit>
LED2
LED<Transmission : Sending>
LED3
LED<Transmission : Recelving>
LED4
LED<Power Supply : DC12V>
LED5
78
78
78
78
NAME
OFF
OFF
OFF
OFF
ON
ON
ON
ON
SW5-5.6
123456
123456
123456
123456
+
DCL
2
BLK
ACTM
4
BLK
WHT
L1
L2
16
REDRED
P
N1 N2
WHT
Io
BLU
RED
L1 L2 GR
POWER SUPPLY 208 / 230V 60Hz
+
Use copper supply wires.
YLW
GRN
S1 S2 S3
ORN
INDOOR UNIT
BRN
TB1
CY1 CY2
28
Page 29
PUZ-A42NHA3 PUZ-A42NHA3-BS PUY-A42NHA3 PUY-A42NHA3-BS
[LEGEND]
SYMBOL TB1 MC MF1,MF2 21S4 63H 63L TH3 TH4 TH6 TH7 TH8 LEV-A DCL CY1, CY2 Capacitor ACTM CB
Terminal Block<Power Supply, Indoor/Outdoor > Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch Low Pressure Switch
Thermistor<Outdoor Pipe>
Thermistor<Discharge> Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Thermistor<Heatsink> Electronic Expansion Valve
Reactor
Active Filter Module Main Smoothing Capacitor
NAME SYMBOL NAME SYMBOL NAME
C. B.
1
MF1
MS
3~
1
MF2
MS
3~
2
CNS
(WHT)
31
3
1
CNDC (PNK)
7
7
CNF1
(WHT)
CNF2
(WHT)
F2
F1
P.B.
TABU/V/W TABS/T TABP1/P2/P TABN1/N2/N DS2, DS3 IPM
N.F.
LI/LO NI/NO EI, E2 52C
C.B.
F1~F4 SW1
TRANS
CNAC
(WHT)
Power Circuit Board Connection Terminal<U/V/W-Phase> Connection Terminal<L1/L2-Phase> Connection Terminal<DC Voltage> Connection Terminal<DC Voltage> Diode Bridge Power Module Noise Filter Circuit Board Connection Lead<L1-Phase> Connection Lead<L2-Phase> Connection Terminal<Ground> 52C Relay Controller Circuit Board Fuse<
T6.3AL250V>
Switch<
Forced Defrost, Defect History Record
Reset, Refrigerant Address>
63L
TH4
(WHT)
CN2
(WHT)
F3
F4
63L
(RED)
7
63H
31
63H
(YLW)
71
TH7TH6 TH3 TH4
t° t° t° t°
412121
TH3
TH7/6
(WHT)
(RED)
21
43
31
2
21S4
+2 PUZ only
LED2
LEV-A
LEV-A (WHT)
CN4
(WHT)
12
M
X52
13 13
21S4
(GRN)
61
LED1
3
CNVMNT
(WHT)
1
CNM
(WHT)
SW4 SW5 SW6 SW7 SW8 SW9 SWP CN31 LED1,LED2 SS CNM CNMNT CNVMNT CNDM CN51 X51,X52
31
CNMNT (WHT)
CN52C
(RED)
Switch<Test Operation> Switch<Function Switch> Switch<Model Select> Switch<Function Setup> Switch<Function Setup> Switch Switch<Pump Down> Connector<Emergency Operation> LED<Operation Inspection Indicators> Connector<Connection for Option> Connector<A-Control Service Inspection Kit> Connector<Connected to Optional M-NET Adapter Board> Connector<Connected to Optional M-NET Adapter Board> Connector< Connected for Option (Contact Input)>
Connector< Connected for Option (Signal output)>
5
14
221
51
(WHT)
Relay
+1+1
SW5SW8SW4SWP
SW6SW1
CN31
X51
SS
(WHT)
CNDM
CN51
SW7
SW9
3151
(WHT)
When M-NET adapter is connected
5
ABS
5
1
2 1
TB7
M-NET
SW1
CN5
(WHT)
LED2 LED3 LED4
M-NET ADAPTER
CND
CN2M
(WHT)
(WHT)
31
LED1
LED5
3
SW11
SW12
+1 MODEL SELECT
MODEL SW6
ON
PUZ-A42N
OFF
123456
ON
PUY-A42N
OFF
+2. SW5-1 to 4 : Function switch
M-NET ADAPTER
123456
SYMBOL
Terminal Block<M-net connection>
TB7
Connector<Transmission>
CN5
Connector<Power Supply>
CND
Connector<M-NET communication>
CN2M
Switch<Status of communication>
SW1
Switch<Address setting : 1s digit>
SW11
Switch<Address setting : 10s digit>
SW12
LED<Power Supply : DC5V>
LED1
LED<Connection to Outdoor Unit>
LED2
LED<Transmission : Sending>
LED3
LED<Transmission : Recelving>
LED4
LED<Power Supply : DC12V>
LED5
P. B .
4
1
CNAF (WHT)
6
7
1
CN2
(WHT)
7
TH8
1
CN3
2
(WHT)
2
1
CN5
2
(RED)
2
1
CN4
2
(WHT)
WHT
TABN
CB
TABP
RED
SW5-5.6
ON
OFF
7878123456
ON
OFF
123456
NAME
N. F.
BLU
WHT
LO
NO
1
2
CN52C
E2
1
2
CN5
EI
2
(BLK)
2
(RED)
52C
TABT
BLU
2
TABN1
L2
DS3
DS2
U
BLK
4
WHT
16
N1 N2
YLW
GRN
S1 S2 S3
INDOOR UNIT
3
1
CNAC2
3
1
CNAC1
ORN
(RED)
(WHT)
LI NI
BRN
TB1
CY1 CY2
U
U
TABS
WHT
TABP1
RED
TABN2
WHT
BLU
RED
REDRED
P
WHT
Io
L1 L2 GR
POWER SUPPLY 208 / 230V 60Hz
+Use copper supply wires.
CNDC
(PNK)
1
IPM
RED
TABP2
TABU
RED
UVW
+2
3
TABV
TABW
WHT
BLK
M
3~
MC
DCL
BLK
L1
BLK
ACTM
29
Page 30
5
REFRIGERANT SYSTEM DIAGRAM
5-1. INDOOR UNIT PLA-A·BA PCA-A·KA PEA-A·AA
Strainer(#50)
Heat exchanger
Refrigerant GAS pipe connection (Flare)
Thermistor TH5 (Cond./Eva. temperature)
Refrigerant LIQUID pipe connection
Distributor with strainer(#50)
Thermistor TH1 (Room temperature)
Thermistor TH2 Pipe temperature (Liquid)
(Flare)
Strainer(#50)
PKA-A·HA PKA-A·HAL PKA-A·KA PKA-A·KAL
Refrigerant flow in cooling
Refrigerant flow in heating
Thermistor TH5 (Cond./ Eva.temperature)
Heat exchanger
Thermistor TH1 (Room temperature)
Thermistor TH2 Pipe temperature(Liquid)
Distributor with strainer (#50/#50 : HA(L)) (#50/#100 : KA(L))
Strainer (#50)
Refrigerant GAS pipe connection (Flare)
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant LIQUID pipe connection (Flare)
Strainer (#50)
30
Page 31
5-2. OUTDOOR UNIT Unit: mm (inch) PUZ-A18NHA3(-BS)
Stop valve (with service port)
Refrigerant GAS pipe
12.7 (W1/2)
Refrigerant LIQUID pipe
6.35 (W1/4)
(#50)
Strainer
Accumulator
Stop valve
4-way valve
High pressure protect switch
Compressor
Service port(check)
Outdoor heat exchanger
Muffler
Thermistor (TH32)
(#100)
Strainer
(#100)
Strainer
Linear expansion valve
Thermistor (TH6)
Thermistor (TH3)
Distributor
PUZ-A24NHA3(-BS) PUZ-A30NHA3(-BS) PUZ-A36NHA3(-BS)
Refrigerant GAS pipe
15.88 (W5/8)
Refrigerant LIQUID pipe
9.52 (W3/8)
Ball valve
(#50)
Strainer
Service port (check)
Accumulator
Stop valve (with service port)
Bypass valve
4-way valve
Muffler
Service port (check)
Compressor
High pressure protect switch
Outdoor heat exchanger
Thermistor (TH32)
(#100)
Strainer
Linear expansion valve
(#100)
Strainer
Thermistor (TH6)
Thermistor (TH3)
Distributor
<4-way valve solenoid coil> Heating : ON Cooling : OFF
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant flow in cooling Refrigerant flow in heating
PUZ-A42NHA3(-BS)
Refrigerant GAS pipe
15.88 (W5/8)
Strainer
Refrigerant LIQUID pipe
9.52 (W3/8)
(with service port)
Ball valve
Strainer
(#100)
Stop valve
Low pressure protect switch
4-way valve
(#50)
Service port (check)
Accumulator
Service port (check)
High pressure protect switch
Muffler
Thermistor (TH4)
Compressor
Strainer
(#100)
Linear expansion valve
Strainer
(#100)
31
Outdoor heat exchanger
Thermistor (TH6)
Thermistor (TH3)
Distributor
Refrigerant flow in cooling Refrigerant flow in heating
Page 32
PUY-A12NHA3(-BS) PUY-A18NHA3(-BS)
Unit: mm (inch)
Stop valve (with service port)
Refrigerant GAS pipe
12.7 (W1/2)
Refrigerant LIQUID pipe
6.35 (W1/4)
(#50)
Strainer
Accumulator
Stop valve
High pressure protect switch
Compressor
Service port (Check)
Outdoor heat exchanger
Thermistor (TH32)
(#100)
Strainer
(#100)
Strainer
Linear expansion valve
Thermistor (TH6)
Thermistor (TH3)
Distributor
PUY-A24NHA3(-BS) PUY-A30NHA3(-BS) PUY-A36NHA3(-BS)
Service port (check)
High pressure protect switch
Thermistor (TH32)
(#100)
Strainer
Linear expansion valve
Outdoor heat exchanger
(#100)
Strainer
Thermistor (TH6)
Thermistor (TH3)
Distributor
Refrigerant GAS pipe
15.88 (W5/8)
Refrigerant LIQUID pipe
9.52 (W3/8)
Ball valve
(#50)
Strainer
Service port (check)
Accumulator
Stop valve (with service port)
Bypass valve
Compressor
Refrigerant flow in cooling
Refrigerant flow in cooling
PUY-A42NHA3(-BS)
Ball valve
Refrigerant GAS pipe
15.88 (W5/8)
Accumulator
Refrigerant LIQUID pipe
9.52 (W3/8)
Low pressure protect switch
(#50)
Strainer
Strainer
Service port (check)
Stop valve (with service port)
(#100)
Service port (check)
High pressure protect switch
Thermistor (TH4)
Compressor
Strainer
(#100)
Linear expansion valve
Strainer
(#100)
Outdoor heat exchanger
Thermistor (TH6)
Thermistor (TH3)
32
Distributor
Refrigerant flow in cooling
Page 33
6
PERFORMANCE CURVES
FOR THE COMBINATION OF OUTDOOR UNIT PUZ-A·NHA3(-BS), PUY-A·NHA3(-BS)
Cooling performance curve
1.4
1.2 INDOOR W.B.(˚C)
CAPACITY (RATIO)TOTAL INPUT (RATIO)
1.0
0.8
1.2
1.0
22 (72˚F)
20 (68˚F) 18 (64˚F)
16 (61˚F)
INDOOR
W.B.(˚C)
22
(72˚F)
20
(68˚F)
18
(64˚F)
16
(61˚F)
0.8
0.6
0.4
(23˚F) (32˚F) (50˚F) (68˚F) (86˚F) (104˚F) (115˚F)
10
OUTDOOR D.B.(˚C)
Note : This diagram shows the case where the operation frequency of a compressor is fixed.
20 30 46400-5
33
Page 34
1.4
Heating performance curve
Correcting the capacity line influenced by frosting Not correcting the capacity line influenced by frosting
INDOOR
D.B.(˚C)
CAPACITY (RATIO)TOTAL INPUT (RATIO)
1.2
1.0
0.8
0.6
0.4
1.4
1.2
In some cases, heating operation cannot be conducted with the maximum frequency in the area below the slanting line.
In some cases, heating operation cannot be conducted with the maximum frequency in the area above the slanting line.
15 (59˚F)
˚
F)
20 (68
˚
F)
25 (77
INDOOR
D.B.(˚C)
25 (77
˚
F)
20 (68
˚
F)
1.0
0.8
0.6
0.4
-12 -10 -5 0 5 10 15
(10˚F) (14˚F) (23˚F) (32˚F) (41˚F) (50˚F) (59˚F)
OUTDOOR W.B.(˚C)
Note : This diagram shows the case where the operation frequency of a compressor is fixed.
34
15 (59
˚
F)
Page 35
7
CORRECTION FACTORS
7-1. COOLING CAPACITY CORRECTION FACTORS
Outdoor unit
PUY-A12/18 PUZ-A18 PUY-A24/30/36 PUZ-A24/30/36 PUY-A42 PUZ-A42
1.00
1.00
1.00
0.985
0.988
0.985
Refrigerant piping length (one way)
20m (70ft)10m (33ft)5m (16ft)
0.957
0.966
0.957
7-2. HEATING CAPACITY CORRECTION FACTORS
Outdoor unit
PUZ-A18
1.00
0.997
Refrigerant piping length (one way)
20m (70ft)10m (33ft)5m (16ft)
0.991
30m (100ft) 40m (130ft) 50m (165ft)
0.931
0.946
0.931
30m (100ft) 40m (130ft) 50m (165ft)
0.985
0.929
0.908
0.913
0.886
PUZ-A
PUZ-A
24/30/36
42
1.00
1.00
0.997
0.997
0.991
0.991
0.985
0.985
0.979
0.979
7-3. CAPACITY CORRECTION
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity curves below. Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m) Corrected pipe length (ft) = actual pipe length (ft) + number of bends x 1 (ft)
100
95
90
85
Cooling
Heating
Heating A18,24,30,36,42 models (Up to 30m(100ft) for A18 model)
Cooling A24,30,36 model
Cooling A12,18,42 models
(Up to 30m (100ft) for A12/18 models)
0.973
0.973
Capacity ratio [%]
80
75
70
5 101520253035404550
<16> <33> <50> <70> <80> <100> <115> <130> <150> <165>mft
Corrected pipe length
35
Page 36
7-4. ADDITION OF REFRIGERANT
• Additional charging is not necessary if the pipe length does not exceed 20 m(70 ft) for A12-A36 or 30 m(100 ft) for A42.
• If the pipe length exceeds the specified length above, charge the unit with additional R410A refrigerant according to the permitted pipe lengths in the chart below.
* When the unit is stopped, charge the unit with the additional refrigerant through the liquid stop valve after the pipe
extensions and indoor unit have been vacuumized.
* When the unit is operating, add refrigerant to the gas check valve using a safety charger. Do not add liquid refrigerant
directly to the check valve.
* After charging the unit with refrigerant, note the added refrigerant amount on the service label (attached to the unit).
• Be careful when installing multiple units. Connecting to an incorrect indoor unit can lead to abnormally high pressure and have
a serious effect on operation performance.
Model
A12, A18 30 m, 100 ft 30 m, 100 ft 0
A24, A30, A36 50 m, 165 ft 30 m, 100 ft 0
A42 50 m, 16 5 ft 30 m, 100 ft 0 0 0 0
Max. pipe
length
Max. height
difference
20 m 25 m 27 m 30 m 33.5 m 36.6 m 40 m 43 m 45.5 m 48.8 m 50 m
70 ft 80 ft 90 ft 100 ft 110 ft 120 ft 130 ft 140 ft 150 ft 160 ft 165 ft
0.06 kg 0.11 kg 0.17 kg 2 oz 4 oz 6 oz
0.17 kg 0.34 kg 0.51 kg 0.68 kg 0.85 kg 1.02 kg 1.19 kg 1.36 kg 1.53 kg 1.70 kg 6 oz 12 oz 18 oz 24 oz 30 oz 36 oz 42 oz 48 oz 54 oz 60 oz
Additional refrigerant charging amount (kg/oz)
0.17 kg 0.34 kg 0.51 kg 0.68 kg 0.85 kg 1.02 kg 1.19 kg 6 oz 12 oz 18 oz 24 oz 30 oz 36 oz 42 oz
8
AIR FLOW DATA
8-1. OUTLET AIR SPEED AND COVERAGE RANGE
PLA-A30BA PLA-A36BA PLA-A42BA
740
12.1(3.7) 18(5.6)
1060
17.4(5.3) 26(8.0)
1090
17.7(5.4) 26(8.2)
PKA-A36KA
PKA-A36KAL
920
22.3(6.8) 53(16.1)
PCA-A36KA
990
11.8(3.6)
41(12.5)
PCA-A42KA
1025
12.1(3.7) 42(12.9)
Air flow Air speed Coverage range
Air flow Air speed Coverage range
Air flow Air speed Coverage range
Air flow Air speed Coverage range
CFM
ft/sec.(m/sec.)
ft(m)
CFM
ft/sec.(m/sec.)
ft(m)
CFM
ft/sec.(m/sec.)
ft(m)
CFM
ft/sec.(m/sec.)
ft(m)
PLA-A12BA PLA-A18BA
530
8.5(2.6) 13(4.1)
640
10.5(3.2) 15(4.8)
PKA-A12HA
PKA-A12HAL
425
20.0(6.1) 35(10.8)
PKA-A24KA
PKA-A24KAL
775
19.7(6.0) 47(14.3)
PCA-A24KA
670
10.2(3.1) 32(9.6)
PLA-A24BA
640
10.5(3.2) 15(4.8)
PKA-A18HA
PKA-A18HAL
425
20.0(6.1) 35(10.8)
PKA-A30KA
PKA-A30KAL
775
19.7(6.0) 47(14.3)
PCA-A30KA
705
10.5(3.2)
33(10.1)
The air coverage range is the distance to which the 0.8 ft/sec. air can reach, when air is blown out horizontally from the unit at the High notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furni­ture inside the room.
36
Page 37
8-2. PLA-A·BA
8-2-1 FRESH AIR INTAKE AND BRANCH DUCT
1. Branch duct hole and fresh air intake hole (Fig. 1)
At the time of installation, use the duct holes (cut out) located at the positions shown in Fig.1, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note: The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 5-5/16 to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur.
Unit : inch(mm)
[Fig. 1]
Fresh air intake hole
Refrigerant pipe
Indoor unit
Branch duct hole
Drain pipe
:6-7/8(:175) burring hole pitch
Branch duct hole diagram (view from either side)
Fresh air intake hole diagram
3-:1/8(:2.8) burring hole
120
(*158)
6-7/32
3-17/32
3-15/16
3-15/16
(90)
3-17/32
(90)
70
(90)
(100)
13-25/32(350)
:4-29/32(:125) burring hole pitch
120
3-:15/16(:100) cut out hole
Ceiling
3-15/16(100)
5-1/8(130)
*6-3/32(155)
*6-9/16(167)
14-:1/8(:2.8) burring hole
:5-29/32(:150) cut out hole
2. Fresh air intake (Installation at site)
By mounting the optional multi-function casement to the indoor unit main body, and mounting the duct flange (option) onto it further, fresh exterior air intake can be accomplished. (The mounting of the multi-function casement increases the height of the ceiling plenum by 5-5/16(135mm).)
37
Page 38
3. Fresh air intake amount & static pressure characteristics
1 PLA-A12 · A18 · A24 · A30BA
Multifunction casement + High efficiency filter Multifunction casement + Standard filter
50(20)
)]
-2
0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 012
50 100 150 200
Taking air into the unit
50(20)
)]
-2
0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 012
50 100 150 200
2 PLA-A36 · A42BA
2 - inlet
1 - inlet
345
Air flow rate
3456
Air flow rate
[CMM]
6
[CFM]
[CMM]
[CFM]
50(20)
)]
-2
0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 012
How to read curves
Curve in the
1
graphs
0
Q
2
Q
3
Q
Qa
2 - inlet
1 - inlet
50 100 150 200
Duct characteristics at site
A
C
B
345
Q…Designed amount of fresh air intake A…Static pressure loss of fresh air
intake duct system with air flow amount Q
B…Forced static pressure at air condi-
tioner inlet with air flow amount Q
A
EC
C…Static pressure of booster fan with
air flow amount Q
D…Static pressure loss increase amount
of fresh air intake dust system for air flow amount Q
E…Static pressure of indoor unit with air
flow amount Q
AD
Qa…Estimated amount of fresh air
intake without D
<Pa(in.W.G.o10-2)>
<Pa(in.W.G.o10-2)>
<Pa(in.W.G.o10-2)>
<Pa(in.W.G.o10-2)> <Pa(in.W.G.o10-2)>
<CMM(CFM)>
Multifunction casement + Standard filter Multifunction casement + High efficiency filter
6
[CMM]
[CFM]
<CMM(CFM)>
50(20)
)]
-2
0 0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 02
50 100 150 200 250
Taking air into the unit
50(20)
)]
-2
0
-50(-20)
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80) 02
50 100 150 200 250
50(20)
)]
-2
-50(-20)
2 - inlet
1 - inlet
48
Air flow rate
48
Air flow rate
6
6
[CMM]
[CFM]
[CMM]
[CFM]
-100(-40)
-150(-60)
Static pressure [Pa(in.W.G.%10
-200(-80)
1 - inlet
02
50 100 150 200 250
48
Air flow rate
2 - inlet
6
[CMM]
[CFM]
38
Page 39
4. Change of outlet numbers
The optional air outlet is necessary. To change the air outlet number to 3-, or 2-way outlet, the outlet number should be closed with the operational air outlet shutter.
When the air outlets are closed, close the vane by removing the vane connector.
Indoor unit
Button
Vane motor
Up/down vanes
Connector
Vane motor
Connector
Button
5. Branch duct and change of outlet numbers
<4- way air flow and branch duct>
Branch duct
Air intake
+ Branch duct should be connected to one of the branch duct holes on the main unit.
Air outlet
Outlet concave portion
Air outlet shutter plate (Option)
<3- way air flow and branch duct>
Branch duct
Air outlet closed position
<2- way air flow and branch duct>
Branch duct
Air
Air
outlet
outlet
closed
closed
position
position
Air intake
Air intake
+ Close the outlet on the side of branch duct and air flows in 3 directions.
Air outlet
+ The outlet on the side of branch duct and one of the other outlets are closed. Air flows in 2 directions.
Air outlet closed position
39
Page 40
PLA-A30BA
30(12)
)]Static pressure [Pa(in.W.G%10
-2
20(8)
4-way air flow (horizontal vane) Round duct 4-way air flow (horizontal vane) Rectangular duct
30(12)
)]Static pressure [Pa(in.W.G%10
-2
Duct Duct
20(8)
Static pressure [Pa(in.W.G%10
10(4)
High
Low
0
0
0 50 100 150 200 250 [CFM]
2
4 6 8[CMM]
10(4)
Low
High
Static pressure [Pa(in.W.G%10
0
0
0 50 100 150 200 250 [CFM]
2 4 6 8[CMM]
Air flow rate Air flow rate
3-way air flow (horizontal vane) Round duct 3-way air flow (horizontal vane) Rectangular duct
80(32)
70(28)
)]Static pressure [Pa(in.W.G%10
-2
60(24)
50(20)
40(16)
30(12)
Duct
Close
80(32)
70(28)
)]
-2
60(24)
50(20)
40(16)
30(12)
Duct
Close
High
20(8)
Low
10(4)
0
0246810[CMM]
0 50 100 150 200 250 300 [CFM]
High
Air flow rate Air flow rate
2-way air flow (horizontal vane) Round duct
80(32)
70(28)
)]
-2
60(24)
50(20)
40(16)
30(12)
20(8)
Low
10(4)
0
0 2 4 6 8 10 12[CMM]
0 50 100 150 200 250 300 [CFM]
• Use 1 of the 2 duct holes on the indoor unit.
• Air flow rate of PLA-A12~24BA can be calculated from the air flow rate based on the characteristic of the duct for PLA-A30BA.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way air flow.
Duct
Close
High
Air flow rate
Close
350 400
20(8)
Low
10(4)
0
0246810[CMM]
0 50 100 150 200 250 300 [CFM]
2-way air flow (horizontal vane) Rectangular duct
80(32)
70(28)
)]
-2
60(24)
50(20)
40(16)
30(12)
20(8)
Static pressure [Pa(in.W.G%10
10(4)
0
0 2 4 6 8 10 12[CMM]
0 50 100 150 200 250 300 [CFM]
Low
Duct
Close
High
350 400
Air flow rate
Close
40
Page 41
PLA-A42BA
4-way air flow (horizontal vane) Round duct
30(12)
)]Static pressure [Pa(in.W.G%10
-2
Duct
20(8)
10(4)
Static pressure [Pa(in.W.G%10
Low
0
0
0 50 100 150
2 4 6 8[CMM]
High
Air flow rate
200
250 [CFM]
)]
-2
Static pressure [Pa(in.W.G%10
4-way air flow (horizontal vane) Rectangular duct
30(12)
Duct
20(8)
10(4)
200
High
250 [CFM]
Low
0
0
0 50 100 150
2 4 6 8[CMM]
Air flow rate
3-way air flow (horizontal vane) Round duct 3-way air flow (horizontal vane) Rectangular duct
80(32)
70(28)
)]Static pressure [Pa(in.W.G%10
-2
60(24)
50(20)
40(16)
30(12)
Duct
Close
High
80(32)
70(28)
)]
-2
60(24)
50(20)
40(16)
30(12)
Duct
Close
High
20(8)
10(4)
0
0 2 4 6 8 10[CMM]
0 50 100 150 200 250 300 [CFM]
2-way air flow (horizontal vane) Round duct
100(40)
90(36)
80(32)
70(28)
)]
-2
60(24)
50(20)
40(16)
30(12)
20(8)
10(4)
0
0 2 4 6 8 10 12[CMM]
0 50 100 150 200 250 300 [CFM]
Low
Low
Air flow rate Air flow rate
Duct
Close
Close
High
350 400
20(8)
Static pressure [Pa(in.W.G%10
10(4)
0
0246810[CMM]
0 50 100 150 200 250 300 [CFM]
2-way air flow (horizontal vane) Rectangular duct
100(40)
90(36)
80(32)
70(28)
)]
-2
60(24)
50(20)
40(16)
Low
Duct
Close
Low
30(12)
20(8)
Static pressure [Pa(in.W.G%10
10(4)
0
0 2 4 6 8 10 12[CMM]
0 50 100 150 200 250 300 [CFM]
Air flow rate Air flow rate
• Use 1 of the 2 duct holes on the indoor unit.
• Air flow rate of PLA-A36BA can be calculated from the air flow rate based on the characteristic of the duct for PLA-A42BA.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way air flow.
Close
High
350 400
41
Page 42
8-3. PCA-A·KA FRESH AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS
PCA-A24, 30KA
50(20)
0
-50(-20)
-100(-40)
-150(-60)
-200(-80)
-250(-100)
-300(-120)
Static pressure[Pa(in.W.G.×10ˉ²]
0 1 2 3 4
50 100
Airflow rate
Fresh air intake hole
At the time of installation, use the duct holes (knock out)
A
B
C
located at the positions shown in the left diagram, as and when required.
A
Indoor unit
B
Fresh air intake hole (knock out hole)
C
Filter
in. (mm)
ABC
10-3/16
(259.5)
ø 3-15/16
(ø 100)
4-5/16
(109)
How to read curves
[CMM] [CFM]
Curve in the
1
graphs
0
2
3
Duct characteristics at site
A
C
Q
Q
B
A
EC
Q…Designed amount of fresh air intake A…Static pressure loss of fresh air
intake duct system with airflow amount Q <Pa(in.W.G.x10-2)>
B…Forced static pressure at air con-
ditioner inlet with airflow amount Q
C…Static pressure of booster fan with
airflow amount Q <Pa(in.W.G.x10
D…Static pressure loss increase amount
of fresh air intake duct system for airflow amount Q <Pa(in.W.G.x10
E…Static pressure of indoor unit with
airflow amount Q <Pa(in.W.G.x10
Qa…Estimated amount of fresh air
intake without D <CMM(CFM)>
<CMM(CFM)>
<Pa(in.W.G.x10-2)>
-2
-2
-2
)>
)> )>
PCA-A36, 42KA
50(20)
0
-50(-20)
-100(-40)
-150(-60)
-200(-80)
-250(-100)
-300(-120)
Static pressure[Pa(in.W.G.×10ˉ²]
0 1 2 3 4
50 100
Airflow rate
Q
AD
Qa
[CMM] [CFM]
42
Page 43
8-4. PEA-A·AA
INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
PEA-A12AA
(External static pressure 0.020[in.WG](5Pa) 208/230V 60Hz
40
[0.16]
30
[0.12]
20
[0.08]
High
External static pressure [in.WG](Pa)
10
[0.04]
Low
0
6 7 8 9 10 11 12
[212] [247] [282] [318] [353] [388] [424]
Middle
Airflow rate(m
3
/min)[CFM]
Rated point
PEA-A12AA
(External static pressure 0.140[in.WG](35Pa) 208/230V 60Hz
80
[0.32]
70
[0.28]
60
[0.24]
50
[0.20]
40
[0.16]
Middle
3
/min)[CFM]
Rated point
30
[0.12]
20
External static pressure [in.WG](Pa)
[0.08]
10
[0.04]
0
6 7 8 9 10 11 12
[212] [247] [282] [318] [353] [388] [424]
Low
Airflow rate(m
Limit
Limit
High
PEA-A12AA
(External static pressure 0.060[in.WG](15Pa) 208/230V 60Hz
50
[0.20]
40
[0.16]
30
[0.12]
20
[0.08]
External static pressure [in.WG](Pa)
10
[0.04]
0
6789101112
[212] [247] [282] [318] [353] [388] [424]
Low
Middle
Airflow rate(m
3
/min)[CFM]
High
Rated point
PEA-A12AA
(External static pressure 0.200[in.WG](50Pa) 208/230V 60Hz
80
[0.32]
70
[0.28]
60
[0.24]
50
[0.20]
40
[0.16]
30
[0.12]
20
External static pressure [in.WG](Pa)
[0.08]
10
[0.04]
0
6789101112
[212] [247] [282] [318] [353] [388] [424]
Low
Airflow rate(m
Middle
3
/min)[CFM]
Limit
Rated point
Limit
High
43
Page 44
PEA-A18AA
]
(External static pressure 0.020[in.WG](5Pa) 208/230V 60Hz
40
[0.16]
Limit
30
[0.12]
20
[0.08]
10
External static pressure [in.WG](Pa)
[0.04]
Low
0
9 10111213141516171819
[318] [353] [388] [424] [494][459] [530] [565] [600] [671][636]
Middle
Airflow rate(m
High
3
/min)[CFM]
Rated point
PEA-A18AA
(External static pressure 0.060[in.WG](15Pa) 208/230V 60Hz
50
[0.20]
Limit
40
[0.16]
High
30
[0.12]
Middle
20
[0.08]
External static pressure [in.WG](Pa)
10
[0.04]
0
9 10111213141516171819
[318] [353] [388] [424] [494][459] [530] [565] [600] [671][636]
Low
Airflow rate(m
3
/min)[CFM]
Rated point
PEA-A18AA
(External static pressure 0.140[in.WG](35Pa) 208/230V 60Hz
80
[0.32]
70
[0.28]
60
[0.24]
50
[0.20]
40
[0.16]
30
[0.12]
External static pressure [in.WG](Pa)
20
[0.08]
10
[0.04]
0
9 10111213141516171819
[318] [353] [388] [424] [494][459] [530] [565] [600] [671][636]
Low
Middle
3
Limit
High
Rated point
PEA-A18AA
(External static pressure 0.200[in.WG](50Pa) 208/230V 60Hz
80
[0.32]
70
[0.28]
60
[0.24]
50
[0.20]
40
[0.16]
30
[0.12]
20
External static pressure [in.WG](Pa)
[0.08]
10
[0.04]
0
9 10111213141516171819
[318] [353] [388] [424] [494][459] [530] [565] [600] [671][636]
Low
Airflow rate(m
Limit
Middle
3
/min)[CFM
High
Rated point
44
Page 45
9
NOISE CRITERION CURVES
PLA-A12BA PLA-A18BA
NOTCH SPL(dB) LINE
High 31 Medium1 29 Medium2 28
Low 27
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH SPL(dB) LINE
High 32 Medium1 31 Medium2 29
Low 28
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
PLA-A24BA PLA-A30BA
NOTCH SPL(dB) LINE
High 32 Medium1 31 Medium2 29
Low 28
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH SPL(dB) LINE
High 34 Medium1 32 Medium2 30
Low 28
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
45
Page 46
PLA-A36BA PLA-A42BA
NOTCH SPL(dB) LINE
High 40 Medium1 37 Medium2 34
Low 32
NOTCH SPL(dB) LINE
High 41 Medium1 39 Medium2 36
Low 34
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
CEILING
UNIT
5ft
MICROPHONE
46
Page 47
PKA-A12HA PKA-A18HA PKA-A12HAL PKA-A18HAL
NOTCH
High
Low
SPL(dB)
43 36
LINE
PKA-A24KA PKA-A30KA PKA-A24KAL PKA-A30KAL
NOTCH
High
Low
SPL(dB)39LINE
45
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 bar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 bar)
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
UNIT
3.3ft
3.3ft
MICROPHONE
WALL
PKA-A36KA PKA-A36KAL
90
)
80
bar
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB= 0.0002
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH
High
Low
SPL(dB)43LINE
49
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
47
Page 48
PCA-A24KA PCA-A30KA
NOTCH
Medium1 Medium2
90
High
Low
SPL(dB)
40 37 35 33
LINE
90
NOTCH
High Medium1 Medium2
Low
SPL(dB)
41 39 37 35
LINE
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
PCA-A36KA
90
BAND CENTER FREQUENCIES, Hz
NOTCH
High Medium1 Medium2
Low
SPL(dB)
43 41 39 37
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
PCA-A42KA
90
BAND CENTER FREQUENCIES, Hz
NOTCH
High Medium1 Medium2
Low
SPL(dB)
45 43 41 39
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
3.3ft
3.3ft about 4.62ft
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
ceiling
unit
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
MICROPHONE
48
Page 49
PEA-A12AA
External static pressure :
0.020[in.WG](5Pa)
90
NOTCH
High
Middle
Low
SPL(dB)
33 28 23
<60Hz>
LINE
PEA-A12AA
External static pressure :
0.060[in.WG](15Pa)
90
NOTCH
High
Middle
Low
SPL(dB)
33 28 23
<60Hz>
LINE
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
PEA-A12AA
External static pressure :
0.140[in.WG](35Pa)
90
80
NOTCH
High
Middle
Low
SPL(dB)
34 29 24
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
<60Hz>
LINE
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
PEA-A12AA
External static pressure :
0.200[in.WG](50Pa)
90
80
NOTCH
High
Middle
Low
SPL(dB)
35 31 25
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
<60Hz>
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation.
Aux. duct
test unit
6.6ft
3.3ft
Measurement location
49
5ft
Page 50
PEA-A18AA
External static pressure :
0.020[in.WG](5Pa)
90
NOTCH
High
Middle
Low
SPL(dB)
37 33 29
<60Hz>
LINE
PEA-A18AA
External static pressure :
0.060[in.WG](15Pa)
90
NOTCH
High
Middle
Low
SPL(dB)
38 34 30
<60Hz>
LINE
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
PEA-A18AA
External static pressure :
0.140[in.WG](35Pa)
90
NOTCH
High
Middle
Low
SPL(dB)
39 35 31
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
<60Hz>
LINE
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
PEA-A18AA
External static pressure :
0.200[in.WG](50Pa)
90
NOTCH
High
Middle
Low
SPL(dB)
39 36 32
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
<60Hz>
LINE
bar)
80
μ
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
bar)
80
μ
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation.
50
Page 51
PUY-A12NHA3 (-BS) PUY-A18NHA3 (-BS) PUZ-A18NHA3 (-BS)
90
MICROPHONE
MODE
COOLING
HEATING
5ft
SPL(dB)
46 47
LINE
3.3ft UNIT
GROUND
PUY-A24/30/36NHA3(-BS) PUZ-A24/30/36NHA3(-BS)
90
MODE
COOLING
HEATING
SPL(dB)
48 50
LINE
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
PUY-A42NHA3(-BS) PUZ-A42NHA3(-BS)
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
MODE
COOLING
HEATING
90
80
SPL(dB)
80
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE 51 55
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
51
Page 52
10
OPTIONAL PARTS
10-1. INDOOR UNIT
Part Name Model Name Applicable model Remote sensor (extensible) PAC-SE41TS-E
Connector for CN51 (output for remote display + pulse12V input)
Connector for CN32 (remote ON/OFF) PAC-SE55RA-E Connector for CN30 (LLC) PAC-SE57RA-E PLA-A·BA, PKA-A·HA(L)/KA(L), PCA-A·KA Connector for CN24 (Back up heating) PAC-SE56RA-E PLA-A·BA, PCA-A·KA, PEA-A·AA Connector for CN152 (Back up heating) PAC-SE59RA-E PKA-A·HA(L)/KA(L)
Power supply terminal kit
Decoration panel with wired remote controller PLP-42BAMD Decoration panel PLP-40BAU Multi-function casement PAC-SH53TM-E Flange for fresh air intake PAC-SH65OF-E High-effi ciency fi lter element
(PAC-SH53TM-E is needed.) i-see sensor corner panel PAC-SA1ME-E Wireless signal receiver PAR-SA9FA-E Wireless remote controller kit PAR-SW96U-E Space panel PAC-SH48AS-E Air outlet shutter plate PAC-SH51SP-E
High effi ciency fi lter Drain lift up mechanism PAC-SH84DM-E
i-see Sensor PAC-SH91MK-E Wireless remote controller kit
with i-see Sensor Wireless remote controller kit PAR-SL93B-E Wireless remote controller PAR-FL32MA-E PEA-A·AA
PAC-88HA-E (1pc.) PAC-725AD (10pcs.)
PAC-SH55HR-E PLA-A·BA PAC-SG95HR-E PKA-A·HA(L)/KA(L) PAC-SH98HR-E PCA-A·KA
PAC-SH59KF-E
PAC-SH89KF-E PCA-A24/30KA PAC-SH90KF-E PCA-A36/42KA
PAR-SA92MW-E
All models
PLA-A·BA
PCA-A·KA
10-2. OUTDOOR UNIT
Part Name Model Name Applicable model M-NET adapter PAC-SF80MA-E
All modelsA-control service tool PAC-SK52ST Drain socket PAC-SG61DS-E Air outlet guide
(A42 needs 2 pieces.) Air protect guide
(A42 needs 2 pieces.) Drain pan Distribution pipe for twin use MSDD-50SR-E A24,36
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2009 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Mar. 2009 No.OCS14 PDF6 Made in Japan
PAC-SG58SG-E A12,18 PAC-SG59SG-E A24-42 PAC-SG56AG-E A12,18 PAC-SH63AG-E A24-42 PAC-SG63DP-E A12,18 PAC-SG64DP-E A24-42
New publication, effective Mar. 2009 Specifications subject to change without notice
Loading...