Air-Conditioners For Building Application
OUTDOOR UNIT
PUHY-P-TGMU-A
For use with R410A
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
MANUEL D’INSTALLATION
Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
GB
F
Page 2
5
AAFA
L
1
=
>
L
1
=
>
[Fig. 5.0.1]
(1)
(Unit : mm [in])
<A>
<A> : Top view
>
L
2
=
<B> : Side view
<C> : When there is little space up to an obstruction
>
L
=
A
A : Front
1
B : No restrictions on wall height (left and right)
C : Air outlet guide (Procured at the site)
(5)
>
250
*
E
D
=
[9-27/32]
D
AA
>
1
*
>
1000 [39-3/8]
=
E
L
=
(3)
(4)
>
=
>
=
300
[11-13/16]
B
45°
<A>
<A>
>
L
=
E
>
1000 [39-3/8]
=
E
A
D
D
1
D
>
1000 [39-3/8]
=
E
>
>
L
1
L
=
E
1
=
>
250 [9-27/32]**
=
>
250
=
[9-27/32]
>
900
=
AA
[35-7/16]
>
250
=
[9-27/32]
>
250
=
[9-27/32]
900
[35-7/16]
D
>
=
A
E
<B>(2)
>
1000
=
[39-3/8]
AAAAA
>
>
L1*
L
=
1
=
<C>
C
DD
<B>
>
L
2
<B>
=
h
H
H’
>
1000 [39-3/8]
=
>
L
1
=
>
L
2
=
A
>
A
L
1
=
6
[Fig. 6.0.1]
1 P72 ~ P144
<
8m
=
[26ft]
>
L
1
=
>
=
>
L
1
=
L
2
A
Hh
650 [25-19/32]
A
>
L
=
325 [2-13/16]
2
D : Must be open
h
H
E : Wall height (H)
F : No restrictions on wall height
(Unit : mm [in])
L1L2
450 [17-23/32]
100 [3-15/16]
(Unit : m [ft])
2 P168 ~ P234
<
40°
<
40°
=
<
8m
=
[26ft]
<
8m [26ft]
=
=
<
8m [26ft]
=
2
Page 3
7
[Fig. 7.1.1]
B
A : M10 anchor bolt procured at the site.
A
B : Corner is not seated.
8
[Fig. 8.2.1]
A
A
BCD
a
B
No.1
A(Unit : mm [in])
Å Outdoor model
P72
P96
P108
P126
P144
P168
P192
P204
P216
P234
*1 ø12.7 [1/2] for over 90m [295ft]
*2 ø12.7 [1/2] for over 40m [131ft]
<D> This figure shows the valve in the fully open state.
E
1
B
O
S
<A> [Ball valve (gas side/flanged type)]
EE
B
S
O
A
B
O
B
C
(Unit : mm [in])
<B> [Ball valve (liquid side)]
S
F
G
D
H
L
K
J
I
[Fig. 9.2.3]
[Fig. 9.3.1]
A
C
[Fig. 9.3.3]
A : Valve stem
B : Stopper pin
C : Packing (Accessory)
D : Connecting pipe (Accessory)
E : Open (Operate slowly)
F : Cap, copper packing
G : Service port
H : Flare nut
I : ø9.52 [3/8] (PUHY-P72 ~ P108)
ø12.7 [1/2] (PUHY-P126, PUHY-P144)
ø15.88 [5/8] (PUHY-P168 ~ P234)
J : ø22.2 [7/8] (PUHY-P96 ~ P108)
ø28.58 [1-1/8] (PUHY-P126 ~ P234)
K : Field piping
L : ø19.05 [3/4] (PUHY-P72)
9.3
[Fig. 9.3.2]
LO
B
A
HI
G
H
J
A : Nitrogen gas
B : To indoor unit
C : System analyzer
D : Lo knob
E : Hi knob
F : Ball valve
G : Liquid pipe
H : Gas pipe
I : Outdoor unit
J : Service port
F
B
B
C
LO
D
HI
E
I
D
EN
F
O
C
G
H
I
K
J
L
M
A : System analyzer
B : Lo knob
C : Hi knob
D : Ball valve
E : Liquid pipe
F : Gas pipe
G : Service port
H : Three-way joint
I : Valve
J : Valve
K : R410A cylinder
L : Scale
M : Vacuum pump
N : To indoor unit
O : Outdoor unit
A
B In case of the cylinder having no syphon pipe.
A : Syphon pipe
4
Page 5
9.4
C
A
B
D
E
[Fig. 9.4.1]
A : Steel wireB : Piping
C : Asphaltic oily mastic or asphalt
D : Heat insulation material A
E : Outer covering B
10
[Fig. 10.2.1]
[Fig. 10.3.1]
<A> Change the jumper connec-
tor from CN41 to CN40
<B> SW2-1:ON
10.2
L1 L2 L3M1M2 M1M2 S
TB1
TB3 TB7
ABC
10.3
OC
CN40
(51)
TB3
M1 M2
M1 M2 S
TB7
A : Power source
B : Transmission line
C : Ground screw
L1
ABC
M1 M2 S
M1 M2 S
IC
(04)
TB5
IC
(01)
TB5
M1 M2 S
IC
(05)
TB5
M1 M2 S
IC
(06)
TB5
[Fig. 9.4.2]
A
B
C
D
E
E
B
E
A
D
A : Liquid pipeB : Gas pipe
C : Electric wireD : Finishing tape
E : Insulator
[Fig. 9.4.3]
[Fig. 9.4.4]
<A> Inner wall (concealed)
A B
<B> Outer wall
D
C
A B
<C> Keep the jumper connector
on CN41
<B> SW2-1:ON
[Fig. 10.3.2]
<A> Change the jumper connec-
tor from CN41 to CN40
<B> SW2-1:ON
<C> Keep the jumper connector
on CN41
<B> SW2-1:ON
A : Group 1
B : Group 3
C : Group 5
D : Shielded wire
E : Sub remote
controller
( ) Address
r3
r1
D
L2
OC
CN40
(52)
TB3
M1 M2
M1 M2 S
TB7
System
L6
controller
M1M2S
OC
CN40
(51)
TB3
M1 M2
M1 M2 S
TB7
D
L2
OC
CN40
(52)
TB3
M1 M2
M1 M2 S
TB7
System
L6
controller
M1M2
S
ABAB AB
(101)
RC
L3
IC
M1 M2 S
(02)
TB5
TB5
M1 M2 S
L5
r4
AB
(103)
RC
L1
ABC
IC
(01)
TB5 TB15
M1 M2 12S
L3
IC
(02)
TB5
M1 M2 S
TB5
M1 M2 S
c1
c2
MA
TB5
TB15
M1 M2 S
12
r2
(105)
(155)
RC
RC
L4
IC
(03)
IC
(04)
L4
IC
(03)
TB15
12
AB
E
IC
(07)
TB5
M1 M2 S
IC
(05)
TB15
TB5
12
M1 M2 S
ABABAB
c2
MAMAMA
E
IC
(07)
TB15
TB5
12
M1 M2 S
c1
IC
(06)
c2
TB15
TB5
12
M1 M2 S
c1
c4
c3
<C> Outer wall (exposed)
E
I
<D> Floor (waterproofing)
B
D
F
G
B
<E> Roof pipe shaft
G
<F> Penetrating portion on fire
limit and boundary wall
I
J
D
B
H
F
A
1000
[39-3/8]
1000
[39-3/8]
(Unit : mm [in])
A : SleeveB : Heat insulating material
C : LaggingD : Caulking material
E : BandF : Waterproofing laye
G : Sleeve with edgeH : Lagging material
I : Mortar or other incombustible caulking
J : Incombustible heat insulation material
12. Information on rating plate ........................................................................ 15
• Have all electric work done by a licensed electrician according to “Electric Facility Engineering Standard” and “Interior Wire Regulations”and
the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is performed im-
properly, electric shock and fire may result.
• Securely install the outdoor unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly, dust or water may enter
the outdoor unit and fire or electric shock may result.
• When installing and moving the air conditioner to another site, do not
charge it with a refrigerant different from the refrigerant specified on the
unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrig-
erant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration from exceeding the safety limit if
the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to prevent the safety
limit from being exceeded. Should the refrigerant leak and cause the safety
limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or
an authorized technician.
- If the air conditioner is installed improperly, water leakage, electric shock, or
fire may result.
• After completing installation work, make sure that refrigerant gas is not
leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or
other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted
and operated forcibly, or par ts other than those specified by Mitsubishi Electric are used, fire or explosion may result.
• To dispose of this product, consult your dealer.
• The installer and system specialist shall secure safety against leakage
according to local regulation or standards.
- Following standards may be applicable if local regulation are not available.
• Pay special attention to the place of installation, such as a basement, etc.
where refrigeration gas can accumulate, since refrigeration is heavier
than the air.
• With Fresh air intake type, the installation site must be carefully chosen
because outdoor air can directly blow into the room when the thermostat
is turned off.
- Direct exposure to outdoor air may have harmful effects on people or food.
1.2. Precautions for devices that use R410A
refrigerant
Caution:
• Do not use existing refrigerant piping.
- The old refrigerant and refrigerator oil in the existing piping contains a large
amount of chlorine which may cause the refrigerator oil of the new unit to
deteriorate.
- R410A is a high-pressure refrigerant and can cause the existing piping to
burst.
• Use refrigerant piping made of phosphorus deoxidized copper and copper alloy seamless pipes and tubes. In addition, be sure that the inner
and outer surfaces of the pipes are clean and free of hazardous sulphur,
oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
- Contaminants on the inside of the refrigerant piping may cause the refriger-
ant residual oil to deteriorate.
6
Page 7
• Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing. (Store elbows and
other joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and
compressor trouble may result.
• Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator
oil to coat flares and flange connections.
- The refrigerator oil will degrade if it is mixed with a large amount of mineral
oil.
• Use liquid refrigerant to fill the system.
- If gas refrigerant is used to seal the system, the composition of the refriger-
ant in the cylinder will change and performance may drop.
• Do not use a refrigerant other than R410A.
- If another refrigerant (R22, etc.) is mixed with R410A, the chlorine in the
refrigerant may cause the refrigerator oil to deteriorate.
• Use a vacuum pump with a reverse flow check valve.
- The vacuum pump oil may flow back into the refrigerant cycle and cause the
refrigerator oil to deteriorate.
• Do not use the following tools that are used with conventional refrigerants.
(Gauge manifold, charge hose, gas leak detector, reverse flow check valve,
refrigerant charge base, refrigerant recovery equipment)
- If the conventional refrigerant and refrigerator oil are mixed in the R410A,
the refrigerant may deteriorated.
- If water is mixed in the R410A, the refrigerator oil may deteriorate.
- Since R410A does not contain any chlorine, gas leak detectors for conven-
tional refrigerants will not react to it.
• Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
• Be especially careful when managing the tools.
- If dust, dirt, or water gets into the refrigerant cycle, the refrigerant may dete-
riorate.
1.3. Before installation
Caution:
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
• Do not use the air conditioner where food, pets, plants, precision instruments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
• Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of
the air conditioner or damage its parts.
• When installing the unit in a hospital, communication station, or similar
place, provide sufficient protection against noise.
- Inverter equipment, private power generator, high-frequency medical equip-
ment, or radio communication equipment may cause the air conditioner to
operate erroneously, or fail to operate. On the other hand, the air conditioner
may affect such equipment by creating noise that disturbs medical treatment
or image broadcasting.
• Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged,
condensation may drip from the indoor unit. Perform collective drainage work
together with the outdoor unit, as required.
1.4. Before installation - electrical work
• Install the power cable so that tension is not applied to the cable.
- Tension may cause the cable to break and generate heat and cause a fire.
• Install a leak circuit breaker, as required.
- If a leak circuit breaker is not installed, electric shock may result.
• Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Use only a circuit breaker and fuse of the specified capacity.
- A fuse or circuit breaker of a larger capacity, a steel or copper wire may result
in a general unit failure or fire.
• Do not wash the air conditioner units.
- Washing them may cause an electric shock.
• Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall and cause personal injury
or property damage.
• Install the drain piping according to this Installation Manual to ensure
proper drainage. Wrap thermal insulation around the pipes to prevent
condensation.
- Improper drain piping may cause water leakage causing damage to furniture
and other possessions.
• Be very careful about transporting the product.
- One person should not carry the product as it weighs more than 20 kg [45LBS].
- Some products use PP bands for packaging. Do not use any PP bands as a
means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, support it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot
slip sideways.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children will not
play with them. If children play with a plastic bag which was not torn apart,
they face the risk of suffocation.
1.5. Before starting the test run
Caution:
• Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can
result in irreversible damage to internal parts. Keep the power switch turned
on during the operational season.
• Do not touch the switches with wet fingers.
- Touching a switch with wet fingers can cause electric shock.
• Do not touch the refrigerant pipes during and immediately after operation.
- During and immediately after operation, the refrigerant pipes may be hot or
cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may
suffer burns or frostbite if you touch the refrigerant pipes.
• Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not turn off the power immediately after stopping operation.
- Always wait at least five minutes before turning off the power. Otherwise,
water leakage and trouble may occur.
• Do not touch the surface of the compressor during servicing.
- If unit is connected to the supply and not running, crank case heater at com-
pressor base is operating.
GBDFEINLPGRRUTRCZSVSLHGPO
Caution:
• Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or
telephone ground lines. Improper grounding may result in electric shock.
2. About the product
• This unit uses R410A-type refrigerant
• Piping for systems using R410A may be different from that for systems using
conventional refrigerant because the design pressure in systems using R410A
is higher. Refer to Data Book for more information.
• Some of the tools and equipment used for installation with systems that use
other types of refrigerant cannot be used with the systems using R410A. Refer
to Data Book for more information.
• Do not use the existing piping, as it contains chlorine, which is found in conventional refrigerating machine oil and refrigerant. This chlorine will deteriorate
the refrigerant machine oil in the new equipment. The existing piping must not
be used as the design pressure in systems using R410A is higher than that in
the systems using other types of refrigerant and the existing pipes may burst.
7
Page 8
3. Specifications
Model
Noise level (50/60 Hz)
External static pressure
Indoor units
Operation
temperature
Model
Noise level (50/60 Hz)
External static pressure
– 5 °CDB ~ 43 °CDB [23 °FDB ~ 109 °FDB] (0 °CDB ~ 43 °CDB [32°FDB ~ 109 °FDB] with outdoor unit at lower position)
– 5 °CDB ~ 43 °CDB [23 °FDB ~ 109 °FDB] (0 °CDB ~ 43 °CDB [32°FDB ~ 109 °FDB] with outdoor unit at lower position)
2
Conduit mounting plate (ø46 [1-13/16])
6 Connecting pipe (Flare)
1 ~ 16
PUHY-P192
62 dB<A>
1 ~ 24
–
–
1 pc.
1 pc.
–
–
PUHY-P108
60 dB<A>
0 Pa
50 ~130 %
06 ~ 96
1 ~ 19
PUHY-P204
62 dB<A>
0 Pa
50 ~130 %
06 ~ 96
1 ~ 24
3
Conduit mounting plate (ø33 [1-5/16])
7 Connecting pipe (Flange)
1 pc.
1 pc.
–
–
1 pc.
1 pc.
PUHY-P126
61 dB<A>
1 ~ 20
PUHY-P216
62.5 dB<A>
1 ~ 32
PUHY-P144
61 dB<A>
1 ~ 22
PUHY-P234
63 dB<A>
1 ~ 32
(Unit : mm [in])
4
Conduit mounting plate (ø27 [1-3/32])
8 Packing (inside ø23 [29/32],
outsideø35 [1-13/32])
1 pc.
1 pc.
–
–
1 pc.
1 pc.
5. Space required around unit
[Fig. 5.0.1] (P.2)
<A> Top view<B> Side view
<C> When there is little space up to an obstruction
A FrontB No restrictions on wall height (left and right)
C Air outlet guide (Procured at the site) D Must be open
E Wall height (H)F No restrictions on wall height
(Unit : mm [in])
L1L2
450 [17-23/32] 100 [3-15/16]
(1) Basic space required
(2) When there is an obstruction above the unit
(3) When inlet air enters from right and left sides of unit
• Wall heights “H” of the front and the back sides shall be within total height of
unit.
• When wall height “H” exceeds total height of unit, add “h” dimension to L
2 of the Fig. 5.0.1.
L
“h” = wall height “H’” – total height of unit
1 and
(4) When unit is surrounded by walls
Note:
• Wall heights “H” of the front and the back sides shall be lower than either
the front or the back panel.
• If the panel height is exceeded, add the “h” dimension of the Fig. 5.0.1 to
1 and L2.
L
(Unit : mm [in])
L1L2
450 [17-23/32] 100 [3-15/16]
Example: When the “h” dimension is 100 mm [3-15/16in],
(5) Collective installation and continuous installation
• Space required for collective installation and continuous installation:
When installing several units, provide the space between each block considering passage for air and people.
• Open in two directions.
• In case of wall height “H” exceeds total height of unit, add “h” dimension (h =
wall height “H’” – total height of unit) to * marked dimension.
• If there is a wall at both the front and the rear of the unit, install up to four units
(Every three units in the case of P168 ~ P234.) consecutively in the side direction and provide a space of 1000 mm [39-3/8in] or more as inlet space/passage space for each four units (Every three units in the case of P168 ~ P234).
- Do not have only one person to carry product if it weighs more than 20 kg [46LBS].
- PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
- Do not touch heat exchanger fins with your bare hands. Otherwise you may cut your hands.
- Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
- When carrying outdoor unit, be sure to support it at four points. Carrying with 3-point support may make outdoor unit unstable, resulting in it falling.
8
Page 9
7. Installation of unit
7.1. Installation
[Fig. 7.1.1] (P.3)
A M10 anchor bolt procured at the site.B Corner is not seated.
• Fix unit tightly with bolts so that unit will not fall down due to earthquake or gust
of wind.
• Use concrete or angle bracket for foundation of unit.
• Vibration may be transmitted to the installation section and noise and vibration
may be generated from the floor and walls, depending on the installation conditions. Therefore, provide ample vibrationproofing (cushion pads, cushion
frame, etc.).
• Be sure that the corners are firmly seated. If the corners are not firmly seated,
the installation feet may be bent.
8. Refrigerant piping installation
Connecting the piping is a terminal-branch type in which refrigerant piping from
the outdoor unit is branched at the terminal and connected to each of the indoor
units.
The method of pipe connection is as follows: flare connection for the indoor units,
gas pipes for outdoor units, flare connection for P72 and brazed connection for P96 ~
P234; liquid pipes, flare connection. Note that the branched sections are brazed.
Warning:
Always use extreme care to prevent the refrigerant gas from leaking while
using fire or flame. If the refrigerant gas comes in to contact with a flame
from any source, such as a gas stove, it breaks down and generates a poisonous gas which can cause gas poisoning. Never weld in an unventilated
room. Always conduct an inspection for gas leakage after installation of the
refrigerant piping has been completed.
8.1. Caution
This unit uses refrigerant R410A. Follow the local regulations on materials and
pipe thickness when selecting pipes.
1 Use the following materials for refrigeration piping.
• Material: Use refrigerant piping made of phosphorus deoxidized copper.
In addition, be sure that the inner and outer surfaces of the pipes are clean
and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils,
moisture, or any other contaminant.
2 Commercially available piping often contains dust and other materials. Always
blow it clean with a dry inert gas.
3 Use care to prevent dust, water or other contaminants from entering the piping
during installation.
4 Reduce the number of bending portions as much as possible, and make bend-
ing radius as big as possible.
5 Always observe the restrictions on the refrigerant piping (such as rated length,
the difference between high/low pressures, and piping diameter). Failure to do
so can result in equipment failure or a decline in heating/cooling performance.
6 Either a lack or an excess of refrigerant causes the unit to make an emergency
stop. Charge the system with an appropriate amount of refrigerant. At such a
time, always properly charge the unit. When servicing, always check the notes
concerning pipe length and amount of additional refrigerant at both locations,
the refrigerant volume calculation table on the back of the service panel and
the additional refrigerant section on the labels for the combined number of
indoor units.
7 Use liquid refrigerant to fill the system.
8 Never use refrigerant to perform an air purge. Always evacuate using a vacuum
pump.
9 Always insulate the piping properly. Insufficient insulation will result in a de-
cline in heating/cooling performance, water drops from condensation and other
such problems.
0 When connecting the refrigerant piping, make sure the ball valve of the out-
door unit is completely closed (the factory setting) and do not operate it until
the refrigerant piping for the outdoor and indoor units has been connected, a
refrigerant leakage test has been performed and the evacuation process has
been completed.
A Residues in commercially available antioxidants may have adverse effects on
the equipment. Braze only with non-oxide brazing material. The use of other
brazing material may result in compressor damage.
(Refer to item 9.2. for detailed information on pipe connections and valve operations.)
B Never perform outdoor unit piping connection work when it is raining.
Warning:
• Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a personal
injury.
• Have installation work in order to protect against a strong wind and earthquake.
Any installation deficiency may cause unit to fall down, resulting in a
personal injury.
When building the foundation, give full attention to the floor strength, drain water
disposal <during operation, drain water flows out of the unit>, and piping and wiring routes.
Down piping and down wiring precautions
When down piping and down wiring are performed, be sure that foundation and
base work does not block the base through holes. When down piping is performed,
make the foundation at least 100 mm [3-15/16 in] high so that the piping can pass
under the bottom of the unit.
Warning
When installing and moving the unit, do not charge it with refrigerant other
than the refrigerant specified on the unit.
- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-
function and result in severe damage.
Caution:
• Use a vacuum pump with a reverse flow check valve.
- If the vacuum pump does not have a reverse flow check valve, the vacuum
pump oil may flow back into the refrigerant cycle and cause deterioration of
the refrigerator oil and other trouble.
• Do not use the tools shown below used with conventional refrigerant.
(Gauge manifold, charge hose, gas leak detector, check valve, refrigerant
charge base, vacuum gauge, refrigerant recovery equipment)
- Mixing of conventional refrigerant and refrigerator oil may cause the refrig-
erator oil to deteriorate.
- Mixing of water will cause the refrigerator oil to deteriorate.
- R410A refrigerant does not contain any chlorine. Therefore, gas leak detec-
tors for conventional refrigerants will not react to it.
• Manage the tools more carefully than normal.
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerator oil will dete-
riorate.
• Never use existing refrigerant piping.
- The large amount of chlorine in conventional refrigerant and refrigerator oil
in the existing piping will cause the new refrigerant to deteriorate.
• Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.
- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and
the compressor may fail.
• Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
• Do not use special detergents for washing piping.
8.2. Refrigerant piping system
Connection Example
[Fig. 8.2.1] [Fig. 8.2.2](P.3)
Å Outdoor modelı Liquid pipe
Ç Gas pipeÎ Total capacity of indoor units
‰ Model numberÏ Downstream unit model total
Ì Branch kit modelÓ The 1st branch of P168 ~ P234
¬ 4-Branching header (Downstream unit model total
Ô 8-Branching header (Downstream unit model total
10-Branching header (Downstream unit model total
A Outdoor unitB First branch
C Indoor unitD Cap
*1 ø12.7 [1/2] for over 90 m [295ft]
*2 ø12.7 [1/2] for over 40 m [131ft]
<
=
<
=
72)
144)
<
=
234)
GBDFEINLPGRRUTRCZSVSLHGPO
9
Page 10
9. Additional refrigerant charge
At the time of shipping, the outdoor unit is charged with the refrigerant. As this
charge does not include the amount needed for extended piping, additional charging for each refrigerant line will be required on site. In order that future servicing
may be properly provided, always keep a record of the size and length of each
refrigerant line and the amount of additional charge by writing it in the space provided on the outdoor unit.
9.1. Calculation of additional refrigerant
charge
• Calculate the amount of additional charge based on the length of the piping
extension and the size of the refrigerant line.
• Use the table to the below as a guide to calculating the amount of additional
charging and charge the system accordingly.
• If the calculation results in a fraction of less than 0.1 kg [4oz], round up to the
next 0.1 kg [4oz]. For example, if the result of the calculation was 11.38 kg
[402oz], round the result up to 11.4 kg [404oz].
<Additional Charge>
Additional
refrigerant charge
GBDFEINLPGRRUTRCZSVSLHGPO
(kg) [oz]
Liquid pipe size
Total length of
=++
ø19.05 [3/4]
(m) × 0.29 (kg/m)
(ft) × 3.1 (oz/ft)
Liquid pipe size
Total length of
+++ α
ø9.52 [3/8]
(m) × 0.06 (kg/m)
(ft) × 0.65 (oz/ft)
Liquid pipe size
Total length of
ø15.88 [5/8]
(m) × 0.2 (kg/m)
(ft) × 2.15 (oz/ft)
Liquid pipe size
Total length of
ø6.35 [1/4]
(m) × 0.024 (kg/m)
(ft) × 0.26 (oz/ft)
Liquid pipe size
Total length of
ø12.7 [1/2]
(m) × 0.12 (kg/m)
(ft) × 1.29 (oz/ft)
<Example>[Fig. 8.2.1] (P.3)
Indoor No.1: 48 A: ø12.7 [1/2] 40 m [131ft] a: ø9.52 [3/8] 10 m [32ft]
No.2: 36 B: ø9.52 [3/8] 10 m [32ft]b: ø9.52 [3/8]5 m [16ft]
No.3: 15 C:ø9.52 [3/8] 15 m [49ft] c: ø6.35 [1/4] 10 m [32ft]
No.4: 12 D:ø9.52 [3/8] 10 m [32ft] d: ø6.35 [1/4] 10 m [32ft]
No.5: 24e: ø9.52 [3/8] 10 m [32ft]
The total length of each liquid line is as follows:
ø12.7 [1/2]: A = 40 [131] = 40 m [131ft]
ø9.52 [3/8]: B + C + D + a + b + e
Models 61 to 1262.0 kg [71oz]
Models 127 to 1802.5 kg [89oz]
Models 181 to 2343.0 kg [106oz]
Models 235 to 2644.0 kg [142oz]
Models 265 to 3665.0 kg [177oz]
9.2. Precautions concerning piping connection and valve operation
• Conduct piping connection and valve operation accurately.
• The gas side connecting pipe is assembled in factory before shipment.
1 For brazing to the connecting pipe with flange, remove the connecting pipe
with flange from the ball valve, and braze it outside of the unit.
2 During the time when removing the connecting pipe with flange, remove
the seal attached on the rear side of this sheet and paste it onto the flange
surface of the ball valve to prevent the entry of dust into the valve.
3 The refrigerant circuit is closed with a round, close-packed packing upon
shipment to prevent gas leak between flanges. As no operation can be
done under this state, be sure to replace the packing with the hollow packing attached at the piping connection.
4 At the mounting of the hollow packing, wipe off dust attached on the flange
sheet surface and the packing. Coat refrigerating machine oil (Ester oil,
ether oil or alkylbenzene [small amount]) onto both surfaces of the packing.
[Fig. 9.2.1] (P.4)
A Close-packed packing
B Hollow packing
At the
conditions
below:
• After evacuation and refrigerant charge, ensure that the handle is fully open. If
operating with the valve closed, abnormal pressure will be imparted to the
high- or low-pressure side of the refrigerant circuit, giving damage to the compressor, four-way valve, etc.
• Determine the amount of additional refrigerant charge by using the formula,
and charge refrigerant additionally through the service port after completing
piping connection work.
• After completing work, tighten the service port and cap securely not to generate gas leak.
• Flare machining dimension for systems using R410A is larger than that for
systems using other types of refrigerant in order to increase the air tightness.
• Refer to the table on the below for flare machining dimensions, and follow the
regulations set forth by the local authorities. Seal off the opening of the pipe
with a closure material (not supplied) to keep small animals from entering the
pipe if that is a concern.
flare machining dimension (mm)
outer diameter
ø6.35
A
ø9.52
ø12.7
ø15.88
ø19.05
size in inches
1/4"
3/8"
1/2"
5/8"
3/4"
dimension A
R410A
9.1
13.2
16.6
19.7
24.0
flare nut size (mm)
dimension B
R410A
17.0
22.0
26.0
29.0
36.0
B
outer diameter
ø6.35
ø9.52
ø12.7
ø15.88
ø19.05
size in inches
1/4"
3/8"
1/2"
5/8"
3/4"
[Fig. 9.2.2] (P.4)
<A> [Ball valve (gas side/flanged type)]
<B> [Ball valve (liquid side)]
<C> [Ball valve (gas side/flared type)]
<D>This figure shows the valve in the fully open state.
A Valve stem
[Fully closed at the factory, when connecting the piping, when evacuating, and
when charging additional refrigerant. Open fully after the operations above are
completed.]
B Stopper pin [Prevents the valve stem from turning 90° or more.]
C Packing (Accessory)
[Use packing and securely install this pipe to the valve flange so that gas leakage
will not occur. (Tightening torque : 40 N·m [400 kg·cm]) Coat both surfaces of the
packing with refrigerating machine oil. (Ester oil, ether oil or alkylbenzene [small
amount])]
E Open (Operate slowly)
F Cap, copper packing
[Remove the cap and operate the valve stem. Always reinstall the cap after operation is completed. (Valve stem cap tightening torque: 23 ~ 27 N·m [230 ~
270 kg·cm])]
G Service port
[Use this port to evacuate the refrigerant piping and add an additional charge at
the site.
Open and close the port using a double-ended wrench.
Always reinstall the cap after operation is completed. (Service port cap tightening
torque: 12 ~ 15 N·m [120 ~ 150 kg·cm])]
H Flare nut
[Tightening torque: Refer to the chart on the next page.
Loosen and tighten this nut using a double-ended wrench.
Coat the flare contact surface with refrigerating machine oil (Ester oil, ether oil or
alkylbenzene [small amount])]
I ø9.52 [3/8] (PUHY-P72 ~ P108)
ø12.7 [1/2] (PUHY-P126, PUHY-P144)
ø15.88 [5/8] (PUHY-P168 ~ P234)
[With P96 and P108 types, when the piping length is long and the pipe size is
increased to ø12.7 [1/2], connect to a ø9.52 [3/8] pipe first and then connect to a
ø12.7 [1/2] pipe. (The maximum allowable length of the ø9.52 [3/8] pipe is 1 m
[39-3/8in].)]
J ø22.2 [7/8] (PUHY-P96 ~ P108)
ø28.58 [1-1/8] (PUHY-P126 ~ P234)
[With P96 and P108 types, when the piping length is long and the pipe size is
increased to ø12.7 [1/2], connect to a ø9.52 [3/8] pipe first and then connect to a
ø12.7 [1/2] pipe.(The maximum allowable length of the ø9.52 [3/8] pipe is 1 m
[39-3/8in].)]
K Field piping
[Braze to the connecting pipe. (When brazing, use unoxidized brazing.)]
Note:
If a torque wrench is not available, use the following method as a standard:
When you tighten the flare nut with a wrench, you will reach a point where
the tightening torque will abruptly increase. Turn the flare nut beyond this
point by the angle shown in the table above.
ø6.35 [1/4]14 to 18 / 140 to 180
ø9.52 [3/8]35 to 42 / 350 to 420
ø12.7 [1/2]50 to 57.5 / 500 to 575
ø15.88 [5/8]75 to 80 / 750 to 800
ø19.05 [3/4]100 to 140 / 1000 to 1400
Tightening angle (°)
30 to 60
ø19.05 [3/4]20 to 35
Caution:
• Always remove the connecting pipe from the ball valve and braze it outside the unit.
- Brazing the connecting pipe while it is installed will heat the ball valve and
cause trouble or gas leakage. The piping, etc. inside the unit may also be
burned.
• Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerating machine oil to coat flares and flange connections.
- The refrigerating machine oil will degrade if it is mixed with a large amount of
mineral oil.
• Keep the ball valve closed until refrigerant charging to the pipes to be
added on site has been completed. Opening the valve before charging
the refrigerant may result in unit damage.
• Do not use a leak detection additive.
9.3. Airtight test, evacuation, and refrigerant
charging
1 Airtight test
Perform with the ball valve of the outdoor unit closed, and pressurize the connection piping and the indoor unit from the service port provided on the ball
valve of the outdoor unit. (Always pressurize from both the high press pipe and
the low press pipe service ports.)
[Fig. 9.3.1] (P.4)
A Nitrogen gasB To indoor unitC System analyzer
D Lo knobE Hi knobF Ball valve
G Liquid pipeH Gas pipeI Outdoor unit
J Service port
Observe the following restrictions when conducting an air tightness test to prevent
negative effects on the refrigerating machine oil. Also, with nonazeotropic refrigerant (R410A), gas leakage causes the composition to change and affects performance. Therefore, perform the airtightness test cautiously.
GBDFEINLPGRRUTRCZSVSLHGPO
Airtight test procedure
1. Nitrogen gas pressurization
(1) After pressurizing to the design pressure (4.15 MPa [602psi]) using nitrogen gas, allow it to
stand for about one day. If the pressure does not drop, airtightness is good.
However, if the pressure drops, since the leaking point is unknown, the following bubble test
may also be performed.
(2) After the pressurization described above, spray the flare connection parts, brazed parts, flanges,
and other parts that may leak with a bubbling agent (Kyuboflex, etc.) and visually check for
bubbles.
(3) After the airtight test, wipe off the bubbling agent.
2. Pressurization using refrigerant gas and nitrogen gas
(1) Pressurizing to a gas pressure of approximately 0.2 MPa [29psi], pressurize to the design
pressure (4.15 MPa [602psi]) using nitrogen gas.
However, do not pressurize at one time. Stop during pressurization and check that the pressure does not drop.
(2) Check for gas leaks by checking the flare connection parts, brazed parts, flanges, and other
parts which may leak using an R410A compatible electric leak detector.
(3) This test may be used together the with bubble type gas leak test.
Caution:
Only use refrigerant R410A.
- The use of other refrigerant such as R22 or R407C, which contains chlorine, will
deteriorate the refrigerating machine oil or cause the compressor to malfunction.
2 Evacuation
Evacuate with the ball valve of the outdoor unit closed and evacuate both the
connection piping and the indoor unit from the service port provided on the ball
valve of the outdoor unit using a vacuum pump. (Always evacuate from the
service port of both liquid pipe and gas pipe.) After the vacuum reaches 650
Pa [abs] [0.0943 psi/5Torr], continue evacuation for at least one hour or more.
* Never perform air purging using refrigerant.
[Fig. 9.3.2] (P.4)
A System analyzerB Lo knobC Hi knob
D Ball valveE Liquid pipeF Gas pipe
G Service portH Three-way jointI Valve
J ValveK R410A cylinderL Scale
M Vacuum pumpN To indoor unitO Outdoor unit
Note:
• Always add an appropriate amount of refrigerant. Also always seal the
system with liquid refrigerant. Too much or too little refrigerant will cause
trouble.
• Use a gauge manifold, charging hose, and other parts for the refrigerant
indicated on the unit.
• Use a gravimeter. (One that can measure down to 0.1 kg [3oz].)
• Use a vacuum pump with a reverse flow check valve.
(Recommended vacuum gauge: ROBINAIR 14830A Thermistor Vacuum
Gauge)
Also use a vacuum gauge that reaches 65 Pa [abs] [0.00943 psi/0.5Torr]
or below after operating for five minutes.
3 Refrigerant Charging
9.4. Thermal insulation of refrigerant piping
Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas
pipe separately with enough thickness heat-resistant polyethylene, so that no gap
is observed in the joint between indoor unit and insulating material, and insulating
materials themselves. When insulation work is insufficient, there is a possibility of
condensation drip, etc. Pay special attention to insulation work to ceiling plenum.
Restriction
• If a flammable gas or air (oxygen) is used as the pressurization
gas, it may catch fire or explode.
• Do not use a refrigerant other than that indicated on the unit.
• Sealing with gas from a cylinder will cause the composition of
the refrigerant in the cylinder to change.
• Use a pressure gauge, charging hose, and other parts especially
for R410A.
• An electric leak detector for R22 cannot detect leaks of R410A.
• Do not use a haloid torch. (Leaks cannot be detected.)
Since the refrigerant used with the unit is nonazerotropic, it must be charged in
the liquid state. Consequently, when charging the unit with refrigerant from a
cylinder, if the cylinder does not have a syphon pipe, charge the liquid refrigerant by turning the cylinder upside-down as shown in Fig.9.3.3. If the cylinder
has a syphon pipe like that shown in the picture on the right, the liquid refrigerant can be charged with the cylinder standing upright. Therefore, give careful
attention to the cylinder specifications. If the unit should be charged with gas
refrigerant, replace all the refrigerant with new refrigerant. Do not use the refrigerant remaining in the cylinder.
[Fig. 9.3.3] (P.4)
A Syphon pipeB In case of the cylinder having no syphon pipe.
[Fig. 9.4.1] (P.5)
A Steel wireB Piping
C Asphaltic oily mastic or asphaltD Heat insulation material A
E Outer covering B
• When using polyethylene cover as covering material, asphalt roofing shall
not be required.
• No heat insulation must be provided for electric wires.
[Fig. 9.4.2] (P.5)
A Liquid pipeB Gas pipeC Electric wire
D Finishing tapeE Insulator
[Fig. 9.4.3] (P.5)
Penetrations
[Fig. 9.4.4] (P.5)
<A> Inner wall (concealed)<B> Outer wall
<C> Outer wall (exposed)<D> Floor (waterproofing)
<E> Roof pipe shaft
<F> Penetrating portion on fire limit and boundary wall
A SleeveB Heat insulating mater ial
C LaggingD Caulking material
E BandF Waterproofing laye
G Sleeve with edgeH Lagging material
I Mortar or other incombustible caulking
J Incombustible heat insulation material
GBDFEINLPGRRUTRCZSVSLHGPO
10. Wiring
When filling a gap with mortar, cover the penetration part with steel plate so that
the insulation material will not be caved in. For this part, use incombustible materials for both insulation and covering. (Vinyl covering should not be used.)
• Insulation materials for the pipes to be added on site must meet the following
specifications:
ø6.35 to 25.4 mm [1/4 to 1 in]
Thickness
Temperature Resistance
* Installation of pipes in a high-temperature high-humidity environment, such as
the top floor of a building, may require the use of insulation materials thicker
than the ones specified in the chart above.
* When certain specifications presented by the client must be met, ensure that
they also meet the specifications on the chart above.
10 mm min. [13/32 in min]
Pipe size
ø28.58 to 38.1 mm [1-1/8 to 1-1/2 in]
15 mm min. [19/32 in min]
100 °C min.
10.1. Caution
1 Follow ordinance of your governmental organization for technical standard re-
lated to electrical equipment, wiring regulations and guidance of each electric
power company.
2 Wiring for control (hereinafter referred to as transmission line) shall be (5 cm or
more [2in or more]) apart from power source wiring so that it is not influenced
by electric noise from power source wiring. (Do not insert transmission line
and power source wire in the same conduit.)
3 Be sure to provide designated grounding work to outdoor unit.
4 Give some allowance to wiring for electrical part box of indoor and outdoor
units, because the box is sometimes removed at the time of service work.
5 Never connect the main power source to terminal block of transmission line. If
connected, electrical parts will be burnt out.
6 Use 2-core shield cable for transmission line. If transmission lines of different
systems are wired with the same multiplecore cable, the resultant poor transmitting and receiving will cause erroneous operations.
7 Only the transmission line specified should be connected to the terminal block
for outdoor unit transmission.
(Transmission line to be connected with indoor unit : Terminal block TB3 for
transmission line, Other : Terminal block TB7 for centralized control)
Erroneous connection does not allow the system to operate.
8 In the case of connecting with an upper class controller or to conduct group
operation in different refrigerant systems, the control line for transmission is
required between the outdoor units.
Connect this control line between the terminal blocks for centralized control.
(2-wire line with no polarity)
When conducting group operation in different refrigerant systems without connecting to the upper class controller, replace the insertion of the short circuit
connector from CN41 of one outdoor unit to CN40.
9 Group is set by operating the remote controller.
10.2. Control box and connecting position of
wiring
1. Connect the indoor unit transmission line to transmission terminal block (TB3),
or connect the wiring between outdoor units or the wiring with the central control system to the central control terminal block (TB7).
When using shielded wiring, connect shield ground of the indoor unit transmission line to the ground screw (
tween outdoor units and the central control system transmission line to the
shield (S) terminal of the central control terminal block (TB7) shield (S) terminal. In addition, in the case of outdoor units whose power supply connector
CN41 has been replaced by CN40, the shield terminal (S) of terminal block
(TB7) of the central control system should also be connected to the ground
screw (
Fix the wiring securely in place with the cable strap at the bottom of the terminal block so that the external force if not applied to the terminal block. External
force applied to the terminal block may damage the block and short-circuit,
ground fault, or fire may result.
).
) and connect shield ground of the line be-
[Fig. 10.2.1](P.5)
A Power sourceB Transmission line
C Ground screw
2. Conduit mounting plates (ø27 mm [1-3/32 in], ø33 mm [1-5/16 in], ø46 mm [113/16 in], ø53 mm [2-3/32 in]) are being provided. Pass the power supply and
transmission wires through the appropriate knock-out holes, then remove the
knock-out piece from the bottom of the terminal box and connect the wires.
3. Fix power source wiring to terminal box by using buffer bushing for tensile
force (PG connection or the like).
4. Narrow the opening by using a conduit to keep small animals out.
10.3. Wiring transmission cables
1 Types of control cables
1. Wiring transmission cables
• Types of transmission cables: Shielding wire CVVS or CPEVS
• Cable diameter: More than 1.25 mm
• Maximum wiring length: Within 200 m [655ft]
• Maximum length of transmission lines for centralized control and indoor/outdoor transmission lines (Maximum length via indoor units): 500 m [1640ft] MAX
The maximum length of the wiring between power supply unit for transmission
lines (on the transmission lines for centralized control) and each outdoor unit
and system controller is 200 m [655ft].
2. Remote control cables
• M-NET Remote Controller
Kind of remote control cable
Cable diameter
Remarks
• MA Remote Controller
Kind of remote control cable
Cable diameter
Remarks
* Connected with simple remote controller.
2
[AWG16]
Sheathed 2-core cable (unshielded)
0.3 to 1.25 mm
(0.75 to 1.25 mm
When 10 m [32ft] is exceeded, use cable with
the same specifications as 1. Wiring transmission cables.
Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm
(0.75 to 1.25 mm
Within 200 m [656ft]
2
[AWG22 to 16]
2
[AWG18 to 16])*
2
[AWG22 to 16]
2
[AWG18 to 16])*
12
Page 13
2 Wiring examples
• Controller name, symbol and allowable number of controllers.
NameCodePossible unit connections
Outdoor unit
Indoor unit
Remote controller
Other
Variable capacity unit controller
Indoor unit controller
Remote controller (*1)
Transmission booster unit
OC
–
IC
1 to 32 units per 1 OC (*1)
RC
2 units maximum per group
RP
0 to 1 unit per 1 OC (*1)
*1 A transmission booster (RP) may be required depending on the number of connected indoor unit controllers.
Example of a group operation system with multiple outdoor units (Shielding wires and address setting are
necessary.)
<Examples of transmission cable wiring>
[Fig. 10.3.1] M-NET Remote Controller (P.5)
[Fig. 10.3.2] MA Remote Controller (P.5)
[Fig. 10.3.3] Transmission booster unit (P.5)
<A> Change the jumper connector from CN41 to CN40
<B> SW2-1:ON
<C> Keep the jumper connector on CN41
A Group 1B Group 3C Group 5D Shielded wireE Sub remote controller
( ) Address
<Wiring Method and Address Settings>
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the earth terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2 and
terminal S on the transmission cable block of the indoor unit (IC).
c. Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the
terminal block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC).
e. On one outdoor unit only, change the jumper connector on the control panel from CN41 to CN40.
f. Connect the terminal S on the terminal block for central control (TB7) for the outdoor unit (OC) for the unit into which the jumper connector was inserted into CN40 in Step
above to the ground terminal
g. Set the address setting switch as follows.
* To set the outdoor unit address to 100, the outdoor address setting switch must be set to 50.
UnitRangeSetting Method
IC (Main)01 to 50Use the most recent address within the same group of indoor units
IC (Sub)01 to 50
Outdoor Unit51 to 100Use the most recent address of all the indoor units plus 50
M-NET R/C (Main)101 to 150Set at an IC (Main) address within the same group plus 100
M-NET R/C (Sub)151 to 200Set at an IC (Main) address within the same group plus 150
MA R/C–Unnecessary address setting (Necessary main/sub setting)
h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.
in the electrical component box.
Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be
in sequence with the IC (Main)
GBDFEINLPGRRUTRCZSVSLHGPO
<Permissible Lengths>
1 M-NET Remote controller
• Max length via outdoor units: L
• Max transmission cable length: L
• Remote controller cable length: r
1+L2+L3+L4 and L1+L2+L3+L5 and L1+L2+L6
1 and L3+L4 and L3+L5 and L6 and L2+L6
1, r2, r3, r4
If the length exceeds 10 m [32ft], use a 1.25 mm
10 m [32ft] (0.3 to 1.25 mm2 [AWG22 to 16])
=
500 m [1640ft] (1.25 mm2 [AWG16] or more)
=
200 m [656ft] (1.25 mm2 [AWG16] or more)
=
2
[AWG16] shielded wire. The length of this section (L8) should be included in the
calculation of the maximum length and overall length.
2 MA Remote controller
• Max length via outdoor unit (M-NET cable): L1+L2+L3+L4 and L1+L2+L6= 500 m [1640ft] (1.25 mm2 [AWG16] or more)
• Max transmission cable length (M-NET cable): L
• Remote controller cable length: c
1+c2 and c1+c2+c3+c4
1 and L3+L4 and L6 and L2+L6
200 m [656ft] (0.3 to 1.25 mm2 [AWG22 to 16])
=
200 m [656ft] (1.25 mm2 [AWG16] or more)
=
3 Transmission booster
• Max transmission cable length (M-NET cable): 1 L
• Remote controller cable length: r
1, r2
=
If the length exceeds 10 m [32ft], use 1.25 mm
1+L2+L3+L5+L6
2 L
1+L2+L3+L5+L7
3 L
1+L2+L4
4 L
6+L5+L3+L4, L4+L3+L5+L7
10 m [32ft] (0.3 to 1.25 mm2 [AWG22 to 16])
200 m [656ft] (1.25 mm2 [AWG16])
=
200 m [656ft] (1.25 mm2 [AWG16])
=
200 m [656ft] (1.25 mm2 [AWG16])
=
200 m [656ft] (1.25 mm2 [AWG16])
=
2
[AWG16] shielded cable and calculate the length of that portion (L4 and L7) as within the
total extended length and the longest remote length.
10.4. Wiring of main power supply and equipment capacity
Schematic Drawing of Wiring (Example)
[Fig. 10.4.1] (P.5)
A Switch (Breakers for wiring and current leakage)B Breakers for current leakageC Outdoor unit
D Pull boxE Indoor unit
13
Page 14
Thickness of wire for main power supply, On/Off capacities
<Power soure : 208 V>
Minimum wire thickness (mm
P72
P96
P108
P126
Outdoor unit
Indoor unit
<Power soure : 230 V>
Outdoor unit
GBDFEINLPGRRUTRCZSVSLHGPO
Indoor unit
1. Use a separate power supply for the outdoor unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10 %.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example,
use wiring such as YZW.
6. A switch with at least 3 mm [1/8in] contact separation in each pole shall be provided by the Air conditioner installation.
P144
P168
P192
P204
P216
P234
P72
P96
P108
P126
P144
P168
P192
P204
P216
P234
Main cable
8.4/8
13.3/6
13.3/6
21.2/4
33.6/2
33.6/2
42.4/1
42.4/1
42.4/1
53.5/1/0
1.5
Minimum wire thickness (mm
Main cable
8.4/8
13.3/6
13.3/6
21.2/4
33.6/2
33.6/2
42.4/1
42.4/1
42.4/1
42.4/1
0.41/22
BranchCapacityFuse
–
–
–
–
–
–
–
–
–
–
1.5
BranchCapacityFuse
–
–
–
–
–
–
–
–
–
–
0.41/22
2
/AWG)
8.4/8
13.3/6
13.3/6
21.2/4
33.6/2
33.6/2
42.4/1
42.4/1
42.4/1
53.5/1/0
2
/AWG)
8.4/8
13.3/6
13.3/6
21.2/4
33.6/2
33.6/2
42.4/1
42.4/1
42.4/1
42.4/1
0.41/22
1.5
40
50
50
60
75
75
100
100
100
125
16
40
50
50
60
75
75
100
100
100
100
15
Switch (A)
Switch (A)
40
50
50
60
75
75
100
100
100
125
16
40
50
50
60
75
75
100
100
100
100
15
Breaker for
wiring (NFB)Ground
40
50
50
60
75
75
100
100
100
125
20
Breaker for
wiring (NFB)Ground
40
50
50
60
75
75
100
100
100
100
15
Breaker for current leakage
40 A 100 mA 0.1 sec. or less
50 A 100 mA 0.1 sec. or less
50 A 100 mA 0.1 sec. or less
60 A 100 mA 0.1 sec. or less
75 A 100 mA 0.1 sec. or less
75 A 100 mA 0.1 sec. or less
100 A 100 mA 0.1 sec. or less
100 A 100 mA 0.1 sec. or less
100 A 100 mA 0.1 sec. or less
125 A 100 mA 0.1 sec. or less
20 A 30 mA 0.1 sec. or less
Breaker for current leakage
40 A 100 mA 0.1 sec. or less
50 A 100 mA 0.1 sec. or less
50 A 100 mA 0.1 sec. or less
60 A 100 mA 0.1 sec. or less
75 A 100 mA 0.1 sec. or less
75 A 100 mA 0.1 sec. or less
100 A 100 mA 0.1 sec. or less
100 A 100 mA 0.1 sec. or less
100 A 100 mA 0.1 sec. or less
100 A 100 mA 0.1 sec. or less
20 A 30 mA 0.1 sec. or less
Warning:
• Be sure to use specified wires to connect so that no external force is imparted to terminal connections. If connections are not fixed firmly, it may cause
heating or fire.
• Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Caution:
• A breaker for current leakage must be attached to the power supply. If no earth leakage breaker is installed, it may cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction
of unit or fire.
11. Test run
11.1. The following phenomena do not represent trouble (emergency)
Phenomenon
Indoor unit does not the perform cooling (heating) operation.
The auto vane runs freely.
Fan setting changes during heating.
Fan stops during heating operation.
Fan does not stop while operation has been
stopped.
No setting of fan while start SW has been
turned on.
Outdoor unit does not operate by turning
switch on.
Indoor unit remote controller shows “HO” or
“PLEASE WAIT” indicator for about five minutes when turning ON universal power supply.
Drain pump does not stop while unit has been
stopped.
Drain pump continues to operate while unit
has been stopped.
Display of remote controller
“Cooling (heating)” flashes
Normal display
Normal display
Defrost display
No lighting
Heat ready
Normal display
“HO” or “PLEASE WAIT” flashes
Light out
When another indoor unit is performing the heating (cooling) operation, the cooling (heating) operation is not performed.
Because of the control operation of auto vane, it may change over to horizontal
blow automatically from the downward blow in cooling in case the downward
blow operation has been continued for 1 hour. At defrosting in heating, hot adjusting and thermostat OFF, it automatically changes over to horizontal blow.
Ultra-low speed operation is commenced at thermostat OFF.
Light air automatically changes over to set value by time or piping temperature at
thermostat ON.
The fan is to stop during defrosting.
Fan is to run for 1 minute after stopping to exhaust residual heat (only in heating).
Ultra low-speed operation for 5 minutes after SW ON or until piping temperature
becomes 35°C [95°F], low speed operation for 2 minutes thereafter, and then set
notch is commenced. (Hot adjust control)
When the outdoor unit is being cooled and the refrigerant is resting, warming up
operation is performed for at least 30 minutes to warm the compressor (only
P72).
During this time, only the fan operates.
System is being driven.
Operate remote controller again after “HO” or “PLEASE WAIT” disappear.
After a stop of cooling operation, unit continues to operate drain pump for three
minutes and then stops it.
Unit continues to operate drain pump if drainage is generated, even during a
stop.
Cause
14
Page 15
12. Information on rating plate
Refrigerant (R410A)kg
Model
Allowable pressure (Ps)
Net weightkg [LBS]
MANUFACTURER: MITSUBISHI ELECTRIC CORPORATION
AIR-CONDITIONING & REFRIGERATION SYSTEMS WORKS 5-66, TEBIRA, 6-CHOME, WAKAYAMA CITY, JAPAN
P72
7.0 [15 LBS 7oz]
222 [490]
9.5 [20 LBS 16oz]
P96
237 [524]
P108
9.5 [20 LBS 16oz]
237 [524]
13.0 [28 LBS 11oz]
279 [616]
P126
HP: 4.15 MPa [601psi], LP: 2.21 MPa [320psi]
P144
13.0 [28 LBS 11oz]
279 [616]
22.0 [48 LBS 9oz]
463 [1022]
P168
P192
22.0 [48 LBS 9oz]
463 [1022]
P204
22.0 [48 LBS 9oz]
463 [1022]
22.0 [48 LBS 9oz]
463 [1022]
P216
P234
22.0 [48 LBS 9oz]
463 [1022]
GBDFEINLPGRRUTRCZSVSLHGPO
15
Page 16
This product is designed and intended for use in the residential, commer-
cial and light-industrial environment.
WT04551X01
Please be sure to put the contact address/telephone number on
this manual before handing it to the customer.
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Printed in Japan
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.