Mitsumi electronic PKA-A12HA4, PKA-A18HA4 User Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS
SERVICE MANUAL
Indoor unit [Model names] [Service Ref.]
PKA-A12HA4
PKA-A18HA4
PKA-A12HA4 PKA-A18HA4
November 2010
No. OCH483
NOTE:
• This manual describes only service data of the indoor units.
• RoHS compliant products have <G> mark on the spec name plate.
INDOOR UNIT
TEMP.
WIRED REMOTE
CONTROLLER
ON/OFF
(Option)
COOL
DRY
AUTO
FAN
HEAT
IR WIRELESS REMOTE CONTROLLER (Option)
CONTENTS
1. REFERENCE MANUAL
2. SAFETY PRECAUTION
3. PART NAMES AND FUNCTIONS
4. SPECIFICATIONS
5. NOISE CRITERION CURVES
6. OUTLINES AND DIMENSIONS
7. WIRING DIAGRAM
8. REFRIGERANT SYSTEM DIAGRAM
9. TROUBLESHOOTING
10. SPECIAL FUNCTION
11. DISASSEMBLY PROCEDURE
............................................
.........................................10
.....................................
PARTS CATALOG (OCB483)
33223
...................................
...................................
...................
..........................
.......................
............
....................................
.......................
2
3 4
7
8 9
11 12 26 29
1
REFERENCE MANUAL
1-1. OUTDOOR UNIT SERVICE MANUAL
Service Ref. Service Manual No.
PUZ-A18/24/36NHA4 PUZ-A18/24/36NHA4-BS PUY-A12/18/24/36NHA4 PUY-A12/18/24/36NHA4-BS
Remote controller (Optional parts)
Radio frequency interface Wired remote controller IR wireless remote controller
RF thermostat
OCH481
OCB481
COOL
DRY
AUTO
FAN
HEAT
TEMP.
ON/OFF
2
2
SAFETY PRECAUTION
2-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply circuits must be disconnected.
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilising refrigerant R410A
Use new refrigerant pipes.
Make sure that the inside and outside of refrige­rant piping is clean and it has no contaminants such as sulfur, oxides, dirt, shaving particles, etc, which are hazards to refrigerant cycle. In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil etc.
Store the piping to be used indoors during installation, and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
The refrigerant oil applied to flare and flange connections must be ester oil, ether oil or alkylbenzene oil in a small amount.
If large amount of mineral oil enters, that can cause deterio­ration of refrigerant oil etc.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Tools for R410A Gauge manifold Charge hose
Gas leak detector
Torque wrench
Flare tool Size adjustment gauge Vacuum pump adaptor
Electronic refrigerant charging scale
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera­nt will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
3
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
Gauge manifold · Only for R410A
1
· Use the existing fitting
· Use high-tension side pressure of 5.3MPa·G or over.
Charge hose · Only for R410A
2
· Use pressure performance of 5.09MPa·G or over.
Electronic scale
3
Gas leak detector
4
Adaptor for reverse flow check
5
Refrigerant charge base
6
Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
7
Refrigerant recovery equipment
8
· Use the detector for R134a, R407C or R410A.
· Attach on vacuum pump.
· Cylinder with syphon
specifications
. (UNF1/2)
3
PART NAMES AND FUNCTIONS
Indoor unit
Filter
Louver
Air outlet
Air intake
Vane
4
Wired remote controller (Option)
Display Section
For purposes of this explanation, all parts of the display are shown. During actual operation, only the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc. *Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the remote controller has been prohib­ited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, the time to be switched off is shown.
TIME SUN MON TUE WED THU FRI SAT TIMER
AFTER
ERROR CODE
°F°C
Hr
AFTER
°F°C
ONLY1Hr.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
“One Hour Only” indicator
Displays if the airflow is set to low or downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off in 1 hour, when the airflow direction also changes.
Room Temperature display
Shows the room temperature. The room temperature display range is 46–102˚F. The display blinks if the temperature is less than 46˚F or 102˚F or more.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is not running.
(Power On indicator)
Indicates that the power is on.
ON
OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
“Sensor” indication
Displays when the remote controller sensor is used.
“Locked” indicator
Indicates that remote controller but­tons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Operation Section
Temperature setting buttons
Down
Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
TEMP.
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the cover
Note:
“PLEASE WAIT” message
This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recoveringfrom a power failure. “NOT AVAILABLE” message
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
BACK DAY
PAR-21MAA
MENU
MONITOR/SET
CLOCK
ON/OFF
OPERATION
ON/OFF
FILTER
CHECK
TEST
CLEAR
Built-in temperature sensor
If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as far as any of the indoor units is equipped with the function.
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button ( Operation button)
To return operation number
Ventilation button ( Operation button)
To go to next operation number
5
IR wireless remote controller (Option)
CHECK
TEST RUN
Indicate that the unit is being checked or test-run.
MODEL SELECT
Blinks when model is selected.
display
display
display
Lights up while the signal is transmitted to the indoor unit when the button is pressed.
Temperature setting display
Indicates the desired temperature setting which is set.
OPERATION MODE display
OPERATION MODE display Indicates which operation mode is in effect.
display
The vertical direction of airflow is indicated.
display
Displays selected fan speed.
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
FAN SPEED SELECT button
Changes the fan speed.
MODE SELECT button
Switches the operation mode between COOLING/DRY/FAN/HEATING and AUTO mode.
In case the outdoor unit is cooling only type, the heating and auto mode are not available.
COOL
DRY
AUTO
FAN
HEAT
RUN
MODEL SELECT
FAN
SWING
NOT AVAILABLE
TEST
CHECK
ON/OFF TEMP
FAN
MODE
CHECK
VAN E
LOUVER
TEST RUN
RESETSET CLOCK
°F °C
AMPMSTOP
AMPM
START
AUTO STOP
AUTO START
h
min
CLOCK display
Displays the current time.
TIMER display
Displays when in timer operation or when setting timer.
” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
button
Sets any desired room temperature.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch is set, the air conditioner will be
autom ati ca lly stopped at the preset time. AUTO START (ON timer): when this switch is set, the air conditioner will be automatically started at the preset time.
"h" and "min" buttons
Buttons used to set the “hour and minute” of
the current time and timer settings.
CHECK-TEST RUN button
Performs an inspection check or test operation. Do not use it for normal operation.
VANE CONTROL button
Changes the air flow direction.
LOUVER button
Changes left / right airflow direction.
(Not available for this model.)
CLOCK button
RESET button
SET button
6
4
SPECIFICATIONS
Service Ref.
Power supply(phase, cycle, voltage)
External finish Heat exchanger Fan Fan(drive) % No.
INDOOR UNIT
Operation control & Thermostat Noise level(Low-Middle-High) Field drain pipe O.D. Dimensions
Weight
Service Ref.
Power supply(phase, cycle, voltage)
External finish Heat exchanger Fan Fan(drive) % No.
INDOOR UNIT
Operation control & Thermostat Noise level(Low-Middle-High) Field drain pipe O.D. Dimensions
Weight
Max. Fuse Size Min.Circuit Ampacity
Fan motor output Fan motor
Airflow(Low-Middle-High)
External static pressure
Max. Fuse Size Min.Circuit Ampacity
Fan motor output Fan motor
Airflow(Low-Middle-High)
External static pressure
W
D H
W
D H
A A
kW
F.L.A
3
/min(CFM)
m
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
A
A
kW
F.L.A
*/min(CFM)
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
PKA-A12HA4
1 phase, 60Hz, 208/230V
15
1
White Munsell 1.0Y 9.2/0.2
Plate fin coil
Line flow fan (direct) % 1
0.030
0.33 Dry: 9-10.5-12 (320-370-425) Wet: 8-9.5-11 (290-335-380)
0(direct blow)
Remote controller & built-in
36-40-43
16(5/8)
898 (35-3/8)
249 (9-13/16)
295 (11-5/8)
13 (29)
PKA-A18HA4
1 phase, 60Hz, 208/230V
15
1
White Munsell 1.0Y 9.2/0.2
Plate fin coil
Line flow fan (direct) % 1
0.030
0.33
Dry: 9-10.5-12 (320-370-425)
Wet: 8-9.5-11 (290-335-380)
0(direct blow)
Remote controller & built-in
36-40-43
16(5/8)
898 (35-3/8)
249 (9-13/16)
295 (11-5/8)
13 (29)
7
5
NOISE CRITERION CURVES
PKA-A12HA4 PKA-A18HA4
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 μbar)
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
NOTCH
High
Low
BAND CENTER FREQUENCIES, Hz
SPL(dB)
43 36
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
UNIT
3.3ft
3.3ft
MICROPHONE
WALL
8
6
OUTLINES AND DIMENSIONS
PKA-A12HA4 PKA-A18HA4 Unit: inch (mm)
15-3/16(387)
7-3/4(197)
23-9/16(599)
7-1/2(192)
Top si de
Front side
Mount board
Right side
D
Sleeve (purchased locally)
:2-1/2~:3-1/8 (:65~:80)
Left side
Knock out hole for left piping
Through hole
:2-1/2~:3-1/8 (:65~:80)
Knock out hole for lower piping
77­Tapping screw hole
5/8(16)
1-1/16(28.5)
1-9/16(41)
3-1/16(78.5)
3-9/16(91)
4-1/16(103.5)
4-9/16(116)
6-1/2(166)
7(178.5)
8(203.5)
9-1/8(232.5) 9-15/16(253.5)
Wall hole for left rear piping
11-5/8(295)
5/16(8)
4-:5/16(:9) Bolt hole
:
3/16(:5.1)
0
2-1/8 (55)
C
17-5/8(449)
Vane(auto)
14-5/8(372.3)
14(356.3)
12-7/8(327.5)
11-7/16(291.5)
15-1/2(394)
Louver(manual)
10-3/8(265)
7-13/16(200)
8-13/16(225)
8-3/8(213)
9-5/16(238)
6-13/16(174)
10-15/16(278.3)
27-1/16(688)
35-3/8(898)
Front side(Grille open)
17-15/16(457)Gas pipe
21-3/16(539)Liquid pipe
24(610)Drain hose
Under side
24-1/16(612)
4-7/8(125)
2-3/4(70)
9/16(15)
0
Knock out hole for left rear piping 2-3/4×12-3/16(70×310)
Knock out hole for lower piping
2-1/4(58)
0
0
9/16(15)
2-3/4(70)
6-1/16(155)
6-5/8(169) 6-3/16(158)
7-3/16(184)
Operation lamp
Receiver
B
Center measurement hole :3/32(:2.5)
Mount board
5/32(3.8)
14-5/8(372.3)
14(356.3)
12-7/8(237.5)
11-7/16(291.5)
10-3/8(265)
9-5/16(238)
8-13/16(225)
7-13/16(200)
4-7/8(125)
Wall hole for
4-1/2(115)
5-1/2(140)
6-9/16(167)
7-9/16(193.5)
7-1/16(180.3)
11-1/16(281)
right rear piping
Knock out hole for right piping
Terminal block for indoor/outdoor connecting line
Terminal block for power supply (option)
Terminal block for MA-remote controller
Emergency operation switch (cooling/heating)
DEFROST/STAND BY lamp
Liquid pipe
Refrigerant Piping
Gas pipe
Drain hose
Indoor unit outline
13/16(21.8)
0 3/4(20)
1-1/4(32.7) 2-1/16(53.5) 2-9/16(66)
5(128.5) 6(153.5)
9-1/16(231.5)
10-3/4(273.2)
17-5/8(449)
:
6.35)
1/4F (
1/2F (:12.7)
:
5/8 (:16) O.D
A
3/16(5)9-13/16(249)
Knock out hole for piping
2-3/16(56)7/16(12.5)
A
1-11/16(43)
C
2-3/16(56)
1-3/4(46)
3/16(6)
1-11/16(43)
2-11/16(69)
2-3/16(56)
3/16(6)
1-3/4(46)
2-5/16(60)
1-11/16(43)
1-11/16(43)
D
2-5/16(59)
B
Required space(Indoor unit)
Min.1-31/32(50)
Min.1/4(7)
250mm,9-13/16inch or greater with
optional drain pump installation.
Min.8-5/8
(220)
(mm)
Air inlet
Air inlet
Air outlet
Min.5-7/8(150)
Min.1-31/32(50)
Min.9-13/16(250)
9
7
WIRING DIAGRAM
PKA-A12HA4 PKA-A18HA4
[LEGEND]
Symbol
I.B Indoor controller board
CN2L Connector (LOSSNAY) CN30 Connector (LLC) CN32 Connector ( Remote switch) CN41 Connector (HA terminal-A) CN51 Connector (Centrally control) CN90 Connector (Remote operation adapter) CN105 Connector (Radio frequency interface) CN152 Connector (Back-up heating) FUSE FUSE(T3.15AL250V) LED1 Power supply (I.B) LED2 Power supply (R.B) LED3 Transmission (Indoor-outdoor) SW1 Switch (Model selection) +See Table 1 SW2 SWE
RFI
Switch (Capacity code) +See Table 2 Connector (Emergency operation) Radio frequency interface for RF thermostat
Name
Symbol
Name M Vane motor MS Fan motor S.W
Switch board
SWE2 Emergency operation TB2 Terminal block (Indoor unit Power (option)) TB4 Terminal block (Indoor/outdoor connecting line) TB5 Terminal block (Remote controller transmission line) TH1 Room temp. Thermistor
(32°F/15ΚΩ, 77°F/5.4ΚΩ Detect)
TH2
Pipe temp. Thermistor/liquid
(32°F/15ΚΩ, 77°F/5.4ΚΩ Detect)
TH5
Cond./eva. temp. Thermistor
(32°F/15ΚΩ, 77°F/5.4ΚΩ Detect)
W.B Pcb for IR wireless remote controller
LED1 LED (Operation indication : Green) LED2 LED (Preparation for heating : Orange) REC1 Receiving unit
OPTION PART
R.B
Wired remote controller board Terminal block (Remote controller transmission line)
TB6
Refer to tables 1and 2
I.B
SWE
ON OFF
CN90 (WHT)
2
11 1 54
CN2L (RED)
CN152
CN151
(WHT)
11
M
CN20 (RED)
CN41
(WHT)
(WHT)
CN44
(WHT)
1414
TH1 TH2 TH5
LED1
LED3
LED2
11310
CN30 (BLK)
DB1
1139
CN32 (WHT)
CN51
(WHT)
CN4F
(WHT)
MS
3~
1
CNMF (WHT)
X1
CN105
(RED)
1525
5
RFI
6
FUSE
CNP(BLU)
CN3C (BLU)
LDSWE (A)
(BLU)
CNRU (WHT)
CN01 (BLK)
3 1
3
1
CN22 (BLU)
1 2
1 3
ORN
5
BLK
ORN BRN
S.W
2
LDSWE (B) SWE2
W.B
6
LD101 (B)
LED1
2
YLWYLW ORN
RU
REC1
LED2
TB4
S1 S2 S3
TB5
1 2
<+1>
<Table 1> SW1 (MODEL SELECTION)
SETTING
TO OUTDOOR UNIT
12345
<Table 2> SW2(CAPACITY CODE)
MODELS
PKA­A12HA4
PKA­A18HA4
The black square ( a switch position.
R.B
1
2
TB6
ON OFF
SETTING
12345
12345
)
indicates
ON OFF
ON OFF
Notes:
1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires. (specification of 230V), adopting superimposed system of power and signal.
+
1 : Use copper supply wires.
10
8
REFRIGERANT SYSTEM DIAGRAM
PKA-A12HA4 PKA-A18HA4
Heat exchanger
Strainer (#50)
Refrigerant GAS pipe connection (Flare)
Thermistor TH5 (Cond./ Eva.temperature)
Thermistor TH1 (Room temperature)
Thermistor TH2 Pipe temperature(Liquid)
Distributor with strainer (#50/#50)
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant LIQUID pipe connection (Flare)
Strainer (#50)
11