Mitsumi electronic PEAD-A24, PEAD-30, PEAD-42AA, PEAD-36 User Manual

Air-Conditioners
PEAD-A24,30,36,42AA
OPERATION MANUAL
For safe and correct use, please read this operation manual thoroughly before operating the air-conditioner unit.
MANUEL D’UTILISATION
Pour une utilisation correcte sans risques, veuillez lire le manuel d’utilisation en entier avant de vous servir du climatiseur.
FOR USER
POUR L’UTILISATEUR
English
Français
Contents
1. Safety Precautions ................................................................ 2
2. Parts Names .......................................................................... 2
3. Screen Configuration............................................................. 5
4. Setting the Day of the Week and Time .................................. 5
5. Operation............................................................................... 5
6. Timer ..................................................................................... 7
7. Other Functions ................................................................... 10
Note (Marking for WEEE)
This symbol mark is for EU countries only. This symbol mark is according to the directive 2002/96/EC Article 10 Information for users and Annex IV.
Your MITSUBISHI ELECTRIC product is designed and manufactured with high quality materials and components which can be recycled and reused. This symbol means that electrical and electronic equipment, at their end-of-life, should be disposed of separately from your house­hold waste. Please, dispose of this equipment at your local community waste collection/recycling centre. In the European Union there are separate collection systems for used electrical and electronic product. Please, help us to conserve the environment we live in!
1. Safety Precautions
s Before installing the unit, make sure you read all the “Safety
Precautions”.
s The “Safety Precautions” provide very important points regard-
ing safety. Make sure you follow them.
s Please report to or take consent by the supply authority be-
fore connection to the system.
8. Function Selection ............................................................... 11
9. Emergency Operation for Wireless Remote-controller (option)
.......................................................................................... 15
10. Care and Cleaning ............................................................ 15
11. Trouble Shooting................................................................ 16
12. Specifications .................................................................... 17
Symbols used in the text
Warning: Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution: Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates a part which must be grounded.
Warning:
• The unit must not be installed by the user. Ask the dealer or an authorized company to install the unit. If the unit is installed im­properly, water leakage, electric shock or fire may result.
• Do not stand on, or place any items on the unit.
• Do not splash water over the unit and do not touch the unit with wet hands. An electric shock may result.
• Do not spray combustible gas close to the unit. Fire may result.
• Do not place a gas heater or any other open-flame appliance where it will be exposed to the air discharged from the unit. Incomplete combustion may result.
• Do not remove the front panel or the fan guard from the outdoor unit when it is running.
Caution:
• Do not use any sharp object to push the buttons, as this may dam­age the remote controller.
•Never block or cover the indoor or outdoor unit’s intakes or outlets.
2. Parts Names
Indoor Unit
PEAD-A·AA
Fan steps 3 steps Vane – Louver – Filter Normal Filter cleaning indication
• When you notice exceptionally abnormal noise or vibration, stop operation, turn off the power switch, and contact your dealer.
• Never insert fingers, sticks etc. into the intakes or outlets.
• If you detect odd smells, stop using the unit, turn off the power switch and consult your dealer. Otherwise, a breakdown, electric shock or fire may result.
• This air conditioner is NOT intended for use by children or infirm persons without supervision.
•Young children must be supervised to ensure that they do not play with the air conditioner. If the refrigeration gas blows out or leaks, stop the operation of the
• air conditioner, thoroughly ventilate the room, and contact your dealer.
Disposing of the unit
When you need to dispose of the unit, consult your dealer.
PEAD-A·AA
Ceiling Concealed
2
2. Parts Names
Wired Remote-Controller
Display Section
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc. * Multilanguage display is sup-
ported.
“Centrally Controlled” indicator
Indicates that operation of the re­mote controller has been prohib­ited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time remaining.
TIME SUN MON TUE WED THU FRI SAT TIMER AFTER
ERROR CODE
˚F˚C
Hr AFTER
˚F˚C
ONLY1Hr.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to weak and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airflow di­rection also changes.
Room Temperature display
Shows the room temperature. The room temperature display range is 8–39°C. The display flashes if the temperature is less than 8 °C or 39 °C or more.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is station­ary.
(Power On indicator)
Indicates that the power is on.
ON OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
“Sensor” indication
Displayed when the remote controller sensor is used.
“Locked” indicator
Indicates that remote controller but­tons have been locked.
“Clean The Filter” indicator
Comes on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Operation Section
Set Temperature buttons
Down Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the door.
TEMP.
MENU
MONITOR/SET
BACK DAY
PAR-21MAA
CLOCK
ON/OFF
ON/OFF
FILTER
CHECK
OPERATION
Built-in temperature sensor
CLEAR
TEST
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
Operation button)
(
To preceding operation number.
Ventilation button (
Operation button)
To next operation number.
Note:
“PLEASE WAIT” message This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure.
“NOT AVAILABLE” message This message is displayed if a button is pressed to operate a function that the indoor unit does not have. If a single remote controller is used to simultaneously operate multiple indoor units that are different models, this message will not be displayed if any of the indoor units is equipped with the function.
3
2. Parts Names
Wireless Remote-Controller (option)
ON/OFF button
Pushing button starts operation. Pushing again stops operation.
TEST RUN
CHECK MODEL SELECT
SET TEMPERATURE button
SET TEMPERATURE button sets and any desired room tempera­ture.
FAN SPEED button
This button is used to set fan speed to low, medium or high.
MODE SELECT button
This button is used to change be­tween auto, cooling, heating and drying operation modes.
CHECK button
TEST RUN button
NOT AVAILABLE
ON/OFF
FAN
MODE
VANE
CHECK
LOUVER
TEST RUN
RESET
SET
TEMP
AUTO STOP
AUTO START
h
min
CLOCK
When using the wireless remote controller, point it towards the receiver on the indoor unit.
If the remote controller is operated within approximately two minutes after power is supplied
to the indoor unit, the indoor unit may beep twice as the unit is performing the initial auto­matic check.
The indoor unit beeps to confirm that the signal transmitted from the remote controller has been received. Signals can be received up to approximately 7 meters in a direct line from the indoor unit in an area 45° to the left and right of the unit. However, illumination such as fluorescent lights and strong light can affect the ability of the indoor unit to receive signals.
If the operation lamp near the receiver on the indoor unit is flashing, the unit needs to be inspected. Consult your dealer for service.
Handle the remote controller carefully! Do not drop the remote controller or subject it to strong shocks. In addition, do not get the remote controller wet or leave it in a location with high humidity.
To avoid misplacing the remote controller, install the holder included with the remote con­troller on a wall and be sure to always place the remote controller in the holder after use.
AUTO STOP/AUTO START button
Used for selecting timed starting or stopping.
VANE CONTROL button
Used to change the airflow direc­tion.
h button
Used for setting the current time.
min button
Used for setting the current time.
LOUVER button
Used for adjusting the airflow di­rection.
Battery installation/replacement
1. Remove the top cover, insert two AAA batter­ies, and then install the top cover.
1
2
3
Top cover
2. Press the Reset button.
Tw o AAA batteries Insert the negative (–)
end of each battery first. Install the batter­ies in the correct direc­tions (+, –)!
Press the Reset button with an object that has a narrow end.
4
3. Screen Configuration
Function Selection of remote controller
ADC
Standard Control Screens
OFF ON
BC
Timer Monitor Timer Setup
MON
TIMER
OFF
˚F˚F
WEEKLY
B
Set Day/Time
TIME SUN
˚F˚F
˚F
SUN MON TUE WED THU FRI SAT
WEEKLY
4. Setting the Day of the Week and Time
1
Day of the Week &
TIME SUN
˚F
˚F
2
TEMP.
MENU
BACK DAY
MONITOR/SET
PAR-21MAA
ON/OFF
CLOCK
OPERATION
ON/OFF
FILTER
CHECK
CLEAR
TEST
A
Note: The day and time will not appear if clock use has been disabled at Function Selection of remote controller.
Time display
9
4
<Screen Types>
For details on setting the language for the remote controller display, refer to section 8. Function Selection. The initial language setting is English.
Function Selection of remote controller: Set the functions and ranges available to the re­mote controller (timer functions, operating restric­tions, etc.)
Set Day/Time: Set the current day of the week or time.
Standard Control Screens:
View and set the air conditioning system’s oper­ating status
Timer Monitor: View the currently set timer (weekly timer, sim- ple timer, or Auto Off timer)
Timer Setup: Set the operation of any of the timers (weekly timer, simple timer, or Auto Off timer).
<How to change the screen> A :Hold down both the Mode button and the Timer On/Off button for 2
seconds.
B :Press the Timer Menu button. C :Press the Mode (Return) button. D :Press either of the Set Time buttons (
Day of the Week Setting
3
2
TIME SUN
or ).
4
Time Setting
1. Press the or Set Time button A to show display 2.
2. Press the Timer On/Off (Set Day) button 9 to set the day.
*Each press advances the day shown at 3 : Sun Mon ... Fri
Sat.
3. Press the appropriate Set Time button A as necessary to set the time.
*As you hold the button down, the time (at 4) will increment first in
minute intervals, then in ten-minute intervals, and then in one-hour in­tervals.
4. After making the appropriate settings at Steps 2 and 3, press the Filter
button 4 to lock in the values.
5. Operation
2
˚F
3
3
2
PAR-21MAA
5.1. Turning ON/OFF
<To Start Operation>
Press the ON/OFF button 1.
• The ON lamp 1 and the display area come on.
Note:
When the unit is restarted, initial settings are as follows.
Mode Temperature setting Fan speed
Airflow up/down
˚F
TEMP.
MENU
MONITOR/SET
CLOCK
ON/OFF
OPERATION
BACK DAY
7
Remote Controller settings Last operation mode Last set temperature Last set fan speed
COOL or DRY
Mode HEAT
FAN
ON/OFF
8
FILTER
CHECK
CLEAR
TEST
6
Horiz. outlet Last setting Horiz. outlet
6 4 5
8 7
1
1 5
2
6
1
2
ON/OFF
MODE
CHECK
LOUVER
TEST RUN
SET
(option)
AAA
FAN
VANE
RESET
AAA
TEMP
AUTO STOP
AUTO START
h
min
CLOCK
3 5
3
5
6
5
5. Operation
<To Stop Operation>
Press the ON/OFF button 1 again.
• The ON lamp 1 and the display area go dark.
Note: Even if you press the ON/OFF button immediately after shutting down the op­eration is progress, the air conditioner will not start for about three minutes. This is to prevent the internal components from being damaged.
5.2. Mode select
Press the operation mode ( ) button 2 and select the opera- tion mode 2.
s
Cooling mode
Drying mode
Fan mode
Heating mode
Automatic (cooling/heating) mode
Ventillation mode
Only indicated on the following condition
Wired remote controller used LOSSNAY connected
Information for multi system air conditioner (Outdoor unit: MXZ series)
ss
sMulti system air conditioner (Outdoor unit: MXZ series) can con-
ss
nect two or more indoor units with one outdoor unit. According to the capacity, two or more units can operate simultaneously.
• When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the other for heating, the opera­tion mode of the indoor unit that operates earlier is selected. The other indoor units that will start the operation later cannot operate, indicating an operation state in flashing. In this case, please set all the indoor units to the same operation mode.
• There might be a case that the indoor unit, which is operating in (AUTO) mode. Cannot change over to the operating mode (COOL HEAT) and becomes a state of standby.
• When indoor unit starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes (max. about 15 minutes) to blow out the warm air.
• In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
Because the room temperature is automatically adjusted in order to maintain a fixed effective temperature, cooling operation is performed a few degrees warmer and heating operation is performed a few degrees cooler than the set room temperature once the temperature is reached (automatic energy-saving operation).
5.3. Temperature setting
ss
sTo decrease the room temperature:
ss
Press
button 3 to set the desired temperature.
The selected temperature is displayed 3.
• Each time you press the button, the temperature value decreases by 2 °F [1 °C].
ss
sTo increase the room temperature:
ss
Press
button 3 to set the desired temperature.
The selected temperature is displayed 3.
• Each time you press the button, the temperature value decreases by 2 °F [1 °C].
•Available temperature ranges are as follows:
Cooling/Drying: 67 °F [19 °C] - 86 °F [30 °C] Heating: 63 °F [17 °C] - 83 °F [28 °C] Automatic: 67 °F [19 °C] - 83 °F [28 °C]
• The display flashes either 47 °F [8 °C] - 103 °F [39 °C] to inform you if the room temperature is lower or higher than the displayed temperature.
5.4. Fan speed setting
Press 5 button to select a desired fan speed.
• Each time you press the button, available options change with the
display 5 on the remote controller, as shown below.
Fan speed
3-stage
Low Medium High Auto
( )
Remote controller display
(
)
(
)
Automatic operation
According to a set temperature, cooling operation starts if the room tem­perature is too hot and heating operation starts if the room temperature is too cold.
During automatic operation, if the room temperature changes and re­mains 4 °F [2 °C] or more above the set temperature for 15 minutes, the air conditioner switches to cooling mode. If the room temperature re­mains 4 °F [2 °C] or more below the set temperature for 15 minutes, the air conditioner switches to heating mode.
Cooling mode
15 minutes (switches from cooling to heating)
15 minutes (switches from heating to cooling)
Set temperature +4 °F [2 °C]
Set temperature
Set temperature -4 °F [2 °C]
6
5. Operation
The display and the fan speed of the unit will differ in the following situa­tions:
• When STAND BY and DEFROST are displayed.
• Just after the heating mode (while waiting to change to another mode).
• When the temperature of the room is higher than the temperature set­ting of the unit operating in the heating mode.
• In the dry operation, the indoor fan automatically turns to low-speed operation. Switching of fan speed is impossible.
• When the temperature of the heat exchanger is low in the heating mode (e.g., immediately after heating operation starts).
Note:
In the following cases, the actual fan speed generated by the unit will differ from the speed shown the remote controller display.
1. While the display is showing “STAND BY” or “DEFROST”.
2. When the temperature of the heat exchanger is low in the heating mode.
(e.g. immediately after heating operation starts)
3. In HEAT mode, when room temperature is higher than the temperature
setting.
4. When the unit is in DRY mode.
6. Timer
6.1. For Wired Remote-controller
You can use Function Selection of remote controller to select which of three types of timer to use: 1 Weekly timer, 2 Simple timer, or 3 Auto Off timer.
6.1.1. Weekly Timer
The weekly timer can be used to set up to eight operations for each day of the week.
• Each operation may consist of any of the following: ON/OFF time
together with a temperature setting, or ON/OFF time only, or tempera­ture setting only.
• When the current time reaches a time set at this timer, the air
conditioner carries out the action set by the timer.
Time setting resolution for this timer is 1 minute.
Note: *1. Weekly Timer/Simple Timer/Auto Off Timer cannot be used at the same time. *2. The weekly timer will not operate when any of the following conditions is in
effect. The timer feature is off; the system is in an malfunction state; a test run is in progress; the remote controller is undergoing self-check or remote con­troller check; the user is in the process of setting a function; the user is in the process of setting the timer; the user is in the process of setting the current day of the week or time; the system is under central control. (Spe­cifically, the system will not carry out operations (unit on, unit off, or tem­perature setting) that are prohibited during these conditions.)
Operation No.
42 3
TEMP.
MENU
MONITOR/SET
BACK DAY
PAR-21MAA
2
CLOCK
A9 78
<How to Set the Weekly Timer>
1. Be sure that you are at a standard control screen, and that the weekly timer indicator 1 is shown in the display.
SUN
ON/OFF
Day Setting
ON
˚F
ON/OFF
OPERATION
WEEKLY
FILTER
CHECK
CLEAR
TEST
1
3 1 B
4
0
5.5. Ventillation
ss
sFor LOSSNAY combination
ss
5.5.1. For Wired Remote-controller
To run the ventilator together with the indoor unit:
Press the ON/OFF button 1.
• The Vent indication appears on the screen (at 8). The ventilator will now automatically operate whenever the indoor unit is running.
To run the ventilator independently:
Press the Mode button 2 until
cause the ventilator to start.
To change the ventilator force:
Press the Ventilation button 8 as necessary.
• Each press toggles the setting, as shown below.
Low High
5.5.2. For Wireless Remote-controller
The ventilator will automatically operate when the indoor unit turns on.
No indication on the wireless remote controller.
2. Press the Timer Menu button B, so that the Set-Up screen appears. (Note that each press of the button toggles the display between Set-Up and Monitor.)
3. Press the Timer On/Off (Set Day) button 9 to set the day. Each press advances the display at 3 to the next setting, in the following sequence: “Sun Mon Tues Wed Thurs Fri Sat” → “Sun” ... “Fri” → “Sat” → “Sun Mon Tues Wed Thurs Fri Sat”...
4. Press the appropriate operation number (1 to 8) 4. * Your inputs at Steps 3 and 4 will select one of the cells from the matrix
illustrated below. (The remote-controller display at left shows how the display would appear when setting Operation 1 for Sunday to the values indicated below.)
Setup Matrix
Op No.
No. 1
No. 2
No. 8
<Operation 1 settings for Sunday> Start the air conditioner at 8:30, with
the temperature set to 73 °F [23 °C].
Note: By setting the day to “Sun Mon Tues Wed Thurs Fri Sat”, you can set the same operation to be carried out at the same time every day. (Example: Operation 2 above, which is the same for all days of the week.)
<Setting the Weekly Timer>
Shows the time setting
5. Press the appropriate Set Time button A as necessary to set the de- sired time (at 5).
* As you hold the button down, the time first increments in minute inter-
vals, then in ten-minute intervals, and then in one-hour intervals.
6. Press the ON/OFF button 1 to select the desired operation (ON or OFF), at 6. * Each press changes the next setting, in the following sequence: No
display (no setting) “ON” “OFF”
or Operation button (7 or 8) as necessary to select the
Sunday Monday Saturday
• 8:30
• ON
• 73 °F [23 °C]
• 10:00
• OFF
• 10:00
• OFF
<Operation 2 settings for every day> Turn off the air conditioner at 10:00.
Shows the selected operation (ON or OFF)
6
5
SUN
˚F
* Does not appear if operation is not set.
ON
WEEKLY
appears on the display. This will
• 10:00
• OFF
• 10:00
• OFF
Shows the temperature setting
7
* Does not appear if temperature is not
set.
7
6. Timer
7. Press the appropriate Set Temperature button 3 to set the desired temperature (at 7).
* Each press changes the setting, in the following sequence: No
display (no setting) ⇔ 76 °F [24 °C] 78 °F [25 °C] ... 84 °F [29 °C] 86 °F [30 °C] 54 °F [12 °C] ... 73 °F [23 °C] No display. (Available range: The range for the setting is 54 °F [12 °C] to 86 °F [30 °C]. The actual range over which the temperature can be con­trolled, however, will vary according to the type of the connected unit.)
8. After making the appropriate settings at Steps 5, 6 and 7, press the Filter
button 4 to lock in the values. To clear the currently set values for the selected operation, press and quickly release the Check (Clear) button 0 once. * The displayed time setting will change to “—:—”, and the On/Off
and temperature settings will all disappear. (To clear all weekly timer settings at once, hold down the Check
(Clear) button 0 for two seconds or more. The display will begin flashing, indicating that all settings have been cleared.)
Note: Your new entries will be cancelled if you press the Mode (Return) button 2 before pressing the Filter
button 4.
If you have set two or more different operations for exactly the same time, only the operation with the highest Operation No. will be carried out.
9. Repeat Steps 3 to 8 as necessary to fill as many of the available cells as you wish.
10.Press the mode (Return) button 2 to return to the standard control screen and complete the setting procedure.
11.To activate the timer, press the Timer On/Off button 9, so that the “TIMER MODE OFF” indication disappears from the screen.
Be sure
that the “TIMER MODE OFF” indication is no longer displayed.
* If there are no timer settings, the “TIMER MODE OFF” indication
will flash on the screen.
<How to View the Weekly Timer Settings>
SUN
Timer Settings
9
˚F
ON OFF
WEEKLY
1
8
TIMER
1.
Be sure that the weekly timer indicator is visible on the screen (at 1).
2. Press the Timer Menu button B so that “TIMER MONITOR” is indi- cated on the screen (at 8).
3. Press the Timer On/Off (Set Day) button 9 as necessary to select the day you wish to view.
4. Press the
or Operation button (7 or 8) as necessary to change
the timer operation shown on the display (at 9). * Each press will advance to the next timer operation, in order of
time setting.
5. To close the monitor and return to the standard control screen, press the Mode (Return) button 2.
<To Turn Off the Weekly Timer>
Press the Timer On/Off button 9 so that “TIMER MODE OFF” appears at
0.
0
TIME SUN
˚F
˚F
WEEKLY
<To Turn On the Weekly Timer>
Press the Timer On/Off button 9 so that the “TIMER MODE OFF” indica- tion (at 0) goes dark.
TIME SUN
˚F
WEEKLY
0
˚F
6.1.2. Simple Timer
You can set the simple timer in any of three ways.
• Start time only: The air conditioner starts when the set time has elapsed.
• Stop time only: The air conditioner stops when the set time has elapsed.
• Start & stop times: The air conditioner starts and stops at the respective elapsed times.
The simple timer (start and stop) can be set only once within a 72-hour period. The time setting is made in hour increments.
Note: *1. Weekly Timer/Simple Timer/Auto Off Timer cannot be used at the same time. *2. The simple timer will not operate when any of the following conditions is in
effect. The timer is off; the system is in malfunction state; a test run is in progress; the remote controller is undergoing self-check or remote controller check; the user is in the process of selecting a function; the user is in the process of setting the timer; the system is under central control. (Under these con­ditions, On/Off operation is prohibited.)
ONHr
AFTER
SIMPLE
TEMP.
MENU
MONITOR/SET
BACK DAY
PAR-21MAA
ON/OFF
CLOCK
OPERATION
ON/OFF
FILTER
CHECK
CLEAR
TEST
2A9
<How to Set the Simple Timer>
Timer Setting
2
4
AFTER
ONHr
SIMPLE
Action (On or Off)
3
* “— —” is displayed if there is no
setting.
1
1. Be sure that you are at a standard control screen, and that the simple timer indicator is visible in the display (at 1). When something other than the Simple Timer is displayed, set it to SIMPLE TIMER using the function selection of remote controller (see
8.[4]–3 (3)) timer function setting.
2. Press the Timer Menu button B, so that the Set-Up screen appears. (Note that each press of the button toggles the display between Set-Up and Monitor.)
3. Press the ON/OFF button 1 to display the current ON or OFF simple timer setting. Press the button once to display the time remaining to ON, and then again to display the time remaining to OFF. (The ON/OFF indication appears at 3).
• “ON” timer:
The air conditioner will start operation when the specified number of hours has elapsed.
• “OFF” timer:
The air conditioner will stop operation when the specified number of hours has elapsed.
4. With “ON” or “OFF” showing at 3: Press the appropriate Set Time button A as necessary to set the hours to ON (if “ON” is displayed) or the hours to OFF (if “OFF” is displayed) at 4.
• Available Range: 1 to 72 hours
5. To set both the ON and OFF times, repeat Steps 3 and 4. * Note that ON and OFF times cannot be set to the same value.
6. To clear the current ON or OFF setting: Display the ON or OFF setting (see step 3) and then press the Check (Clear) button 0 so that the time setting clears to “—” at 4. (If you want to use only an ON setting or only an OFF setting, be sure that the setting you do not wish to use is shown as “—”.)
1
B 4
0
8
6. Timer
7. After completing steps 3 to 6 above, press the Filter button 4 to lock in the value.
Note: Your new settings will be cancelled if you press the Mode (Return) button 2 before pressing the Filter
button 4.
8. Press the Mode (Return) button 2 to return to the standard control screen.
9. Press the Timer On/Off button 9 to start the timer countdown. When the timer is running, the timer value is visible on the display. Be sure that the
timer value is visible and appropriate.
<Viewing the Current Simple Timer Settings>
Timer Setting
5
6
TIMER ON
OFFHrAFTER
SIMPLE
1
1. Be sure that the simple timer indicator is visible on the screen (at 1).
2. Press the Timer Menu button B, so that the “TIMER MONITOR” appears on the screen (at 5).
• If the ON or OFF simple timer is running, the current timer value will
appear at 6.
• If ON and OFF values have both been set, the two values appear
alternately.
3. Press the Mode (Return) button 2 to close the monitor display and return to the standard control screen.
<To Turn Off the Simple Timer...>
Press the Timer On/Off button 9 so that the timer setting no longer ap­pears on the screen (at 7).
7
Example 2:
Start the timer, with OFF time is sooner than ON time ON Setting: 5 hours OFF Setting: 2 hours
OFFHrAFTER
˚F
˚F
ONHr
AFTER
˚F
˚F
At Timer Start
Display shows the timer’s OFF setting (hours
SIMPLE
remaining to OFF).
At 2 hours after timer start
Display changes to show the timer’s ON setting
SIMPLE
(hours remaining to ON). The time displayed is ON setting (5 hours) – OFF setting (2 hours) = 3 hours.
At 5 hours after timer start
The air conditioner comes on, and will continue
SIMPLE
to run until someone turns it off.
6.1.3. Auto Off Timer
This timer begins countdown when the air conditioner starts, and shuts the air conditioner off when the set time has elapsed.
Available settings run from 30 minutes to 4 hours, in 30-minute intervals.
Note: *1. Weekly Timer/Simple Timer/Auto Off Timer cannot be used at the same time. *2. The Auto Off timer will not operate when any of the following conditions is
in effect. The timer is off; the system is in malfunction state; a test run is in progress; the remote controller is undergoing self-check or remote controller check; the user is in the process of selecting a function; the user is in the process of setting the timer; the system is under central control. (Under these con­ditions, On/Off operation is prohibited.)
˚F
˚F
SIMPLE
<To Turn On the Simple Timer...>
Press the Timer On/Off button 9 so that the timer setting becomes visible at 7.
˚F
7
ONHr
AFTER
˚F
SIMPLE
Examples
If ON and OFF times have both been set at the simple timer, operation and display are as indicated below.
Example 1:
Start the timer, with ON time set sooner than OFF time ON Setting: 3 hours OFF Setting: 7 hours
ONHr
AFTER
OFFHrAFTER
˚F
˚F
At Timer Start
SIMPLE
Display shows the timer’s ON setting (hours remaining to ON).
At 3 hours after timer start
Display changes to show the timer’s OFF set-
SIMPLE
ting (hours remaining to OFF). The time displayed is OFF setting (7 hours) – ON setting (3 hours) = 4 hours.
At 7 hours after timer start
The air conditioner goes off, and will remain off
SIMPLE
until someone restarts it.
AFTER OFF
OPERATION
AUTO OFF
ON/OFF
FILTER
CHECK
CLEAR
TEST
B 4
TEMP.
MENU
MONITOR/SET
BACK DAY
PAR-21MAA
ON/OFF
CLOCK
2A9
<How to Set the Auto Off Timer>
Timer Setting
2
3
AFTER OFF
AUTO OFF
1
1. Be sure that you are at a standard control screen, and that the Auto Off timer indicator is visible in the display (at 1). When something other than the Auto Off Timer is displayed, set it to AUTO OFF TIMER using the function selection of remote controller (see
8.[4]–3 (3)) timer function setting.
2. Hold down the Timer Menu button B for 3 seconds, so that the Set-Up screen appears. (Note that each press of the button toggles the display between Set-Up and Monitor.)
3. Press the appropriate Set Time button A as necessary to set the OFF time (at 3).
4. Press the Filter
Note: Your entry will be cancelled if you press the Mode (Return) button 2 before pressing the Filter
button 4 to lock in the setting.
button 4.
5. Press the Mode (Return) button 2 to complete the setting procedure and return to the standard control screen.
6. If the air conditioner is already running, the timer starts countdown immediately. Be sure to check that the timer setting appears cor-
rectly on the display.
9
6. Timer
<Checking the Current Auto Off Timer Setting>
Timer Setting
TIMER AFTER
5
OFF
AUTO OFF
1
4
1. Be sure that the “Auto Off” is visible on the screen (at 1).
2. Hold down the Timer Menu button B for 3 seconds, so that “TIMER MONITOR” is indicated on the screen (at 4).
• The timer remaining to shutdown appears at 5.
3. To close the monitor and return to the standard control screen, press the Mode (Return) button 2.
<To Turn Off the Auto Off Timer...>
Hold down the Timer On/Off button 9 for 3 seconds, so that “TIMER MODE OFF” appears (at 6) and the timer value (at 7) disappears.
7
6
˚F
Alternatively, turn off the air conditioner itself. The timer value (at 7) will disappear from the screen.
˚F
AUTO OFF
7
AUTO OFF
<To Turn On the Auto Off Timer...>
Hold down the Timer On/Off button 9 for 3 seconds. The “TIMER MODE OFF” indication disappears (at 6), and the timer setting comes on the display (at 7).
Alternatively, turn on the air conditioner. The timer value will appear at 7.
7
AFTER OFF
˚F
AUTO OFF
6
˚F
6.2. For wireless remote controller (option)
C
D
B
A
13
2
button.
SET
TEMP
FAN
VANE
LOUVER
CLOCK
RESET
AAA
AAA
AUTO STOP
AUTO START
h
min
ON/OFF
MODE
CHECK
TEST RUN
1) Set the current time
1 Press the CLOCK button using a thin stick and blink the time A. 2 Press the
h
min
and
button to set the current time.
3 Press the CLOCK button using a thin stick.
2) Set the time to start the unit as follows
1 Press the
AUTO START
button.
• Time can be set while the following symbol is blinking. On time: B START is blinking.
• The start times is displayed at A.
2 Use the 3 To cancel the ON timer, press the
3) Set the time to stop the unit as follows
1 Press the
h
and
AUTO STOP
min
buttons to set the desired time.
AUTO START
button.
button.
• Time can be set while the following symbol is blinking. Off time: C STOP is blinking.
• The stop times is displayed at D.
2 Use the 3 To cancel the OFF timer, press the
4) Changing the set times
Press the
AUTO START
min
h
and
buttons to set the desired time.
AUTO STOP
or
to cancel the timer and repeat from 2) or 3).
AUTO STOP
7. Other Functions
7.1. Locking the Remote Controller Buttons (Operation function limit controller)
If you wish, you can lock the remote controller buttons. You can use the
Function Selection of remote controller to select which type of lock to use. (For information about selecting the lock type, see section 8, item [4]–2 (1)). Specifically, you can use either of the following two lock types.
1Lock All Buttons:
Locks all of the buttons on the remote controller.
2Lock All Except ON/OFF:
Locks all buttons other than the ON/OFF button.
Note: The “Locked” indicator appears on the screen to indicate that buttons are cur­rently locked.
1
Lock Indicator
TIME SUN
FUNCTION
ON/OFF
˚F
OPERATION
ON/OFF
FILTER
CHECK
CLEAR
TEST
1
4
TEMP.
MENU
MONITOR/SET
BACK DAY
PAR-21MAA
˚F
CLOCK
<How to Lock the Buttons>
1. While holding down the Filter button 4, press and hold down the ON/OFF button 1 for 2 seconds. The “Locked” indication appears on the screen (at 1), indicating that the lock is now engaged. * If locking has been disabled in Function Selection of remote controller,
the screen will display the “Not Available” message when you press the buttons as described above.
˚F
˚F
1
FUNCTION
• If you press a locked button, the “Locked” indication (at 1) will blink on the display.
˚F
˚F
1
FUNCTION
<How to Unlock the Buttons>
1. While holding down the Filter button 4, press and hold down the ON/OFF button 1 for 2 seconds—so that the “Locked” indication disappears from the screen (at 1).
˚F
˚F
1
10
7. Other Functions
7.2. Error Codes indication
If you have entered contact number to be called in the event of a prob­lem, the screen displays this number. (You can set this up under Func­tion Selection of remote controller. For information, refer to section 8.)
ERROR CODE
˚F
˚F
When the Check button is pressed:
CALL:XXXX XXX:XXX
ON/OFF
ON/OFF
Error Code
ERROR CODE
If the ON lamp and error code are both flashing: This means that the air conditioner is out of order and operation has been stopped (and cannot resume). Take note of the indicated unit number and error code, then switch off the power to the air conditioner and call your dealer or servicer.
If only the error code is flashing (while the ON lamp remains lit): Opera-
ON/OFF
ON lamp (Flashing)
tion is continuing, but there may be a problem with the system. In this case, you should note down the error code and then call your dealer or servicer for advice. * If you have entered contact number to be called in the event of a
problem, push the Check button to display it on the screen. (You can set this up under Function Selection of remote controller. For infor-
Indoor Unit’s Refrigerant Address
Error Code
Alternating
Display
Indoor Unit No.
mation, refer to section 8.)
8. Function Selection
Function selection of remote controller
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed.
Item 1
1. Change Language (“CHANGE LANGUAGE”)
2. Function limit (“FUNCTION SELECTION”)
3. Mode selection (“MODE SELEC­TION”)
4. Display change (“DISP MODE SETTING”)
Item 2
Language setting to display
(1) Operation function limit setting (operation lock) (“LOCKING
FUNCTION”)
(2) Use of automatic mode setting (“SELECT AUTO MODE”)
(3) Temperature range limit setting (“LIMIT TEMP FUNCTION”)
(1) Remote controller main/sub setting (“CONTROLLER MAIN/
SUB”)
(2) Use of clock setting (“CLOCK”)
(3) Timer function setting (“WEEKLY TIMER”)
(4) Contact number setting for error situation (“CALL.”)
(1) Temperature display °C/°F setting (“TEMP MODE °C/°F”)
(2) Suction air temperature display setting (“ROOM TEMP DISP
SELECT”)
(3) Automatic cooling/heating display setting (“AUTO MODE
DISP C/H”)
Item 3 (Setting content)
• Display in multiple languages is possible
• Setting the range of operation limit (operation lock)
• Setting the use or non-use of “automatic” operation mode
• Setting the temperature adjustable range (maximum, minimum)
• Selecting main or sub remote controller * When two remote controllers are connected to one group, one controller
must be set to sub.
• Setting the use or non-use of clock function
• Setting the timer type
• Contact number display in case of error
• Setting the telephone number
• Setting the temperature unit (°F or °C) to display
• Setting the use or non-use of the display of indoor (suction) air tempera­ture
• Setting the use or non-use of the display of “Cooling” or “Heating” display during operation with automatic mode
11
Loading...
+ 25 hidden pages